Biddle IndAC User Manual

Page 1
Q
Manual
Industrial Air Curtain
Model IndAC
Version 2.1
27-10-2008
English
Page 2
B
Copyright
All the information and drawings in this man­ual are the property of Biddle and may not be used (other than for the actual operation of the device), photocopied, duplicated, trans­lated and/or be brought to the attention of third parties without Biddle’s prior written permission.
The name Biddle is a registered trademark.
Trademarks
The name Biddle is a registered trademark of Biddle bv.
Warranty (guarantee) and liability
Please refer to Biddle's Terms of Sales and Delivery for warranty (guarantee) and liability conditions.
Biddle excludes liability for consequential loss at all times and under all circumstances.
For more information
If you have any comments or questions about specific topics relating to this product, please do not hesitate to contact Biddle.
Addresses
United Kingdom
Biddle Air Systems Ltd.
St. Mary’s Road Nuneaton Warwickshire CV11 5AU United Kingdom
Telephone: 024 7638 4233 Fax: 024 7637 3621
E-mail: [email protected] Internet: www.biddle-air.com
Canada
Biddle Air Systems Ltd.
11 King St. Unit # 3 Barrie, ON L4N 6B5
Liability for the contents of this manual
However much care might have been taken in ensuring the correctness and, where nec­essary, completeness of the description of the relevant parts, Biddle disclaims all liability for damage resulting from any inaccuracies and/or deficiencies in this manual.
Should you detect any errors or ambiguities in this manual then we would be pleased to hear from you: it helps us to improve our documentation even further.
Biddle retains the right to change the specifi­cations stated in this manual.
telephone: 705 797 0007 fax: 705 797 0013
toll free: 866 693 4333
e-mail: [email protected] internet: www.biddle.ca
Other countries
Biddle Export
PO Box 15 NL-9288 ZG Kootstertille The Netherlands
Telephone: +31 512 335555 Fax: +31 512 335554
E-mail: [email protected] Internet: www.biddle.info
2
Manual model IndAC
Page 3
Industrial Air Curtain Contents
2.5 Installing units vertically .................. 10
Contents
1 Introduction ........................4
1.1 About this manual ............................. 4
1.2 How to use this manual .................... 4
1.2.1 Marginal symbols in the manual ......... 4
1.2.2 Pictograms used on the unit and in
the manual................................................... 4
1.2.3 Related documentation....................... 4
1.3 About the unit.................................... 5
1.3.1 Applications ........................................ 5
1.3.2 Principle of operation.......................... 5
1.3.3 Type designation, unit......................... 5
1.3.4 Installation positions ........................... 6
1.3.5 Type plate ........................................... 6
1.4 Required parts .................................. 6
1.4.1 Supplied parts..................................... 6
1.4.2 Accessories ........................................ 7
1.4.3 Parts not supplied............................... 7
1.5 Safety instructions ............................ 7
1.5.1 Operation............................................ 7
1.5.2 Installation, maintenance and
service ......................................................... 7
2 Installation..........................8
2.5.1 Method of installation........................ 10
2.5.2 Positioning ........................................ 10
2.5.3 Installing the units..............................11
2.5.4 Securing ........................................... 12
2.6 Connecting units to the CH system 12
2.6.1 General............................................. 12
2.6.2 Connecting water pipes .................... 13
2.7 Connecting the fans........................ 13
2.7.1 General............................................. 13
2.7.2 Making connections within the units . 13
2.8 Connecting the electric heating ...... 14
2.8.1 General............................................. 14
2.8.2 Opening the heating section............. 15
2.8.3 Connecting the feeder cable............. 15
2.8.4 Connecting the control cable within
the units ..................................................... 15
2.9 Finishing ......................................... 16
2.10 Switching on and checking
operation............................................... 16
3 Maintenance ....................18
3.1 Safety instructions .......................... 18
3.2 Access ............................................ 18
3.2.1 Fans.................................................. 18
3.2.2 Heating element ............................... 19
3.3 Cleaning.......................................... 19
3.4 Scheduled maintenance ................. 19
2.1 Safety instructions ............................ 8
2.2 Delivery check .................................. 8
3.4.1 Monthly maintenance ....................... 19
3.4.2 Annual maintenance ......................... 20
2.3 General instructions.......................... 8
2.3.1 Order of working ................................. 8
2.3.2 Miscellaneous..................................... 8
2.4 Suspending units horizontally........... 8
2.4.1 Method of suspension......................... 8
2.4.2 Positioning .......................................... 9
2.4.3 Mounting the units .............................. 9
2.4.4 Adjusting and securing ..................... 10
4 Solving problems .............21
4.1.1 General............................................. 21
4.1.2 Unit does not discharge any air ........ 21
4.1.3 Unit discharges little air..................... 21
4.1.4 Unit does not heat, or too little.......... 21
Version 2.1, English (27-10-2008) 3
Page 4
B
d
1 Introduction
1.1 About this manual
This manual describes the installation and maintenance of the Industrial Air Curtain, model IndAC.
Danger:
This indicates actions which are not per­mitted. Ignoring this warning may lead to serious damage or accidents that may involve physical injury.
Only for …
For units with …:
The description applies only to models that have the feature referred to.
If no specific model is referred to, the de­scription applies to all models.
1.2.2 Pictograms used on the unit and in the manual
The below pictograms refer to possible risks or dangers. These pictograms can also be found on the unit.
1.2 How to use this manual
1.2.1 Marginal symbols in the manual
n
Note:
Draws your attention to an important part of the text.
c
Caution:
If you do not carry out this procedure or action correctly, you may damage the unit.
So, follow the instructions carefully.
w
Warning:
If you do not carry out this procedure or action correctly, you may cause material damage and/or physical injury.
So, follow the instructions carefully.
ê
ç
1.2.3 Related documentation
In addition to this manual, the following docu­ment is supplied with the unit:
- wiring diagram for installation and ser­vice purposes.
w
Warning:
You are entering an area which contains live components.
Accessible to qualified mainte­nance staff only. Caution is urged.
w
Warning:
This surface or part can be hot. There is a risk of burns on con­tact.
4
Manual model IndAC
Page 5
Industrial Air Curtain 1 Introduction
1.3 About the unit
1.3.1 Applications
The air curtain model IndAC is designed to separate the indoor and outdoor climates or the climates in two rooms. It is installed above or next to the door, across the full width or length of the doorway. The IndAC model is particularly suitable for larger doors in industrial buildings.
Depending on the type, the air curtain is either hung horizontally above the doorway or installed vertically next to the doorway (to the left or right or on both sides).
1.3.2 Principle of operation
The air curtain draws air from the room and blows it, either heated or not, as a directional air stream across the doorway.
The air curtain reduces the undesired effects of an open door by either reducing the ex­change of air between two rooms or heating the entering air, or by combining these two features.
1.3.3 Type designation, unit
The type designations, when combined, constitute the type code for the relevant unit, for instance:
IndAC S-150-W1-0 IndAC M-200-E-1L IndAC L-225-A-2R
Example of a horizontal installation
Various combinations can be made.
Explanation of type code of unit
Series
Range
Unit Size
Heating
Installation Position
IndAC
S, M, L, XL
150, 200, 225
W1, W2, W3
E
A
0 1L, 1R 2L, 2R
Industrial Air Curtain
air discharge length (in cm)
hot water
electric
without heat­ing (Ambient)
See section
1.3.4.
Example of a vertical installation
Version 2.1, English (27-10-2008) 5
Page 6
B
1.3.5 Type plate
1.3.4 Installation positions
c
Caution:
The unit has been specifically designed for the installation position indicated in the type code. The unit cannot be used in a different position.
horizontal,
0
above door
vertical, left of
1L
door, square to wall
You will find the type plate on the heating section of the unit.
Type IndAC M-200-W2
Biddle bv Markowei 4 NL-9288 HA Kootstertille
Example of a type plate
References on the type plate
Type
M
P
max
U
I
max
Code U 400 V 3N~ 50 Hz
Nº 123456/1-1 06-36 I
M 133 kg I
Medium LPHW P
p
800 kPa P
max
max
I
max
max
heating
L1 2,1 A
L2 2,1 A
L3 2,1 A
motor
1,08 kW
-
full type code of unit
weight of unit
maximum permissible operating pressure (for units with water heat­ing)
supply voltage
maximum current strength
vertical, right of
1R
door, square to wall
vertical, left of
2L
door, parallel to wall
vertical, right of
2R
door, parallel to wall
P
motor
P
heating
maximum input power for fans
maximum input power for heating (with electrically heated units)
1.4 Required parts
1.4.1 Supplied parts
With each installation:
- cable to connect units to each other
With horizontal installation:
- suspension rails (2 per unit, also used for
fixing the unit to the pallet)
With vertical installation:
intake and discharge direction (not to be
blocked)
inspection side (to be accessible)
fan terminal box
6
- coupling plates (2 per unit)
- securing bracket
Manual model IndAC
Page 7
Industrial Air Curtain 1 Introduction
1.5.2 Installation, maintenance and
n
Note :
On delivery, some parts may have been packaged within the unit (behind the inspec­tion panel).
1.4.2 Accessories
service
w
Warning:
The unit may be opened by qualified technical staff only.
With each installation:
- control unit (always required)
With vertical installation:
- base plate (recommended)
1.4.3 Parts not supplied
The following parts required for installation should be purchased from other suppliers:
- threaded rods (metric M12)
- cable to connect unit and control unit
- isolating switch
ê ç
Before opening the unit:
- Switch the unit off with the control unit.
- Wait until the fans have stopped.
- Allow the unit to cool down as the heat
exchanger can be very hot.
- Switch the unit off at the mains.
- Close CH supply (if possible).
w
The fins of the heat exchanger are sharp.
Warning:
- fuse for control unit
- door contact switch (optional)
- room thermostat (optional)
1.5 Safety instructions
1.5.1 Operation
w
Warning:
Do not insert any objects into the intake and discharge openings.
Never block the intake and discharge openings.
ç
For units with heating: the intake side can be hot.
Version 2.1, English (27-10-2008) 7
Page 8
B
2.3.2 Miscellaneous
2 Installation
c
Caution:
The infiltration of coarse dust, cement, etc.
2.1 Safety instructions
may damage the unit. So long as such con­taminants are in the room,
w
Warning:
Installation works may be performed by qualified technical staff only.
Do not perform any connection work unless you are qualified to work with 400V three-phase current.
Before opening the unit, follow the safety instructions in section 1.5.
2.2 Delivery check
- On delivery, check the unit and its pack-
aging. Report any transit damage imme­diately to the driver and supplier.
- Make sure that all parts have been sup­plied (see section 1.4). Report any de­fects to the supplier immediately.
- do not put the unit into operation;
- cover the intake and discharge openings.
The packaging, for example, can be used for this.
2.4 Suspending units horizontally
Only with installation position type 0
2.3 General instructions
2.3.1 Order of working
Biddle recommends following the order of working described in this section for perform­ing the installation works.
n
Note:
Make sure you perform all operations that are required for the installation of your unit. Check the type plate and refer to section
1.3.5 if you are not sure about the model or
type of your unit.
Example of a horizontal installation
2.4.1 Method of suspension
This manual assumes suspension from an auxiliary structure, consisting of two horizon­tal beams positioned above the door.
8
Manual model IndAC
Page 9
Industrial Air Curtain 2 Installation
Example of an auxiliary structure
You may also fix the units directly to the ceiling, or to another horizontal structure, using the screw holes in the upper side of the unit.
Make sure that the structure from which the unit is to be suspended can hold the weight of the unit.
2.4.2 Positioning
- Position the bottom face of the unit at the
same height as the doorway.
- Position the discharge side of the unit as closely as possible to the doorway to en­sure optimum operation.
- Center the row of units in relation to the doorway.
- Units of different widths can be posi­tioned in random order.
2 Insert threaded rods 1 (M12) into the
four screw holes in the upper side of the unit.
3 Provide all threaded rods with locknuts
2, and tighten these.
w
Warning:
The threaded rods must be secured, oth­erwise the unit may come down.
- Make sure that the inspection and intake
sides of the units remain accessible for maintenance.
w
Warning:
Ensure that all units can freely take in and blow out air across the entire width.
2.4.3 Mounting the units
Perform the following for each unit:
1 Lay the unit down in horizontal position.
Version 2.1, English (27-10-2008) 9
4 Provide all threaded rods with lock-
nuts 3.
5 Bring the unit into position using lifting
equipment.
6 Put the suspension rails 4 upon the
auxiliary structure, and fasten them with nuts 5 to the threaded rods of the unit.
7 Allow the unit to hang freely.
Page 10
B
2.4.4 Adjusting and securing
1 Position the units against one another, in
one line, by placing the suspension rails 6 against one another. You may want to fix the suspension rails to one another.
c
Caution:
Allow the units to hang independently from each other. Do not fix them directly to one another.
2.5 Installing units vertically
Only with installation position types 1 and 2
Example of a vertical installation
2 Fasten the suspension rails to the auxil-
iary structure.
w
Warning:
Make sure that the suspension rails can never come loose from the auxiliary structure.
3 Adjust the units to the same height, and
level them by tightening the nuts 5.
c
Caution:
Ensure that the units are level in both direc­tions; otherwise the fans may run out of true.
4 Secure the suspension to the threaded
rods by tightening the locknuts 3.
w
Warning:
The threaded rods must be secured, oth­erwise the unit may come down.
2.5.1 Method of installation
This manual assumes that the unit will be placed on a base plate (accessory). The units are stacked on one another.
c
Caution:
If no base plate is used, provide for a hori­zontal and completely even surface, other­wise the fans may run out of true.
Whilst the units could be standing freely, it is always necessary to secure them to the wall.
2.5.2 Positioning
- Depending on the type, position the units
to the left or right side of the door. Refer to section 1.3.4.
c
Caution:
Do not install the unit in any position other than that for which it is designed.
10
- Position the discharge side of the unit at the same width as the doorway.
- Position the discharge side of the unit as closely as possible to the doorway to en­sure optimum operation.
Manual model IndAC
Page 11
Industrial Air Curtain 2 Installation
- Units of different dimensions can be stacked in random order.
- Make sure that the intake and inspection sides of the units remain accessible for maintenance purposes.
w
Warning:
Ensure that all units can freely take in and blow out air across the entire height.
2.5.3 Installing the units
1 Position and fix the base plate 1 to the
floor.
c
Caution:
Ensure that the base plate is level.
2 Position the first unit on the base plate.
3 Fasten the unit to the base plate using
coupling plates 2.
c
Caution:
Screw the coupling plates to both sides of the unit.
4 Position the second unit on top of the
first one, and fasten them to one another using coupling plates 3.
Version 2.1, English (27-10-2008) 11
Page 12
B
c
Caution:
Screw the coupling plates to both sides of the unit.
5 Position the third unit, if any, in the same
way.
2.5.4 Securing
2.6 Connecting units to the
CH system
Only for units with water heating (type W)
2.6.1 General
The connections for the supply and return pipes are indicated on the units using arrows.
Valves for venting 1 and draining 2 the heat exchanger are located on the air intake side.
1 Fasten a securing bracket 4 to the top-
most unit using one of the screw holes in the unit.
2 Fasten the securing bracket to a wall or
other permanent structure.
c
Caution:
If you place more than 3 units on top of each other: apply a securing bracket to each
2nd or 3rd unit.
c
Caution:
Biddle recommends the inclusion of a valve in each pipe.
c
Caution:
The fans are not resistant to high tempera­tures. Where necessary, take measures to limit the discharge air temperature.
12
Manual model IndAC
Page 13
Industrial Air Curtain 2 Installation
Critical discharge air temperatures and water temperature ranges (with 400V/50Hz only)
unit type maximum
allowed dis­charge air temperature
S-W1 M-W1
S-W2 M-W2
S-W3 M-W3
L-W1 XL-W1
L-W3 XL-W3
65 °C above
65 °C above
65 °C above
65 °C above
65 °C above
water tem­perature ranges where exceedance may occur
120/100 °C
90/70 °C or 82/71 °C
80/60 °C
130/110 °C
90/70 °C
- The mains power supply to the control unit must be separately fused.
- In emergency and maintenance situa­tions, it must be possible to switch off the entire installation using an isolating switch.
- All connections must be made according to the applicable local laws, regulations and standards.
w
Warning:
The units and must be earthed (grounded).
2.7.2 Making connections within the
units
2.6.2 Connecting water pipes
1 Lay and connect the water pipes to the
units.
2 Fill the CH system.
3 Vent the heat exchangers.
4 Check the connections for leaks.
2.7 Connecting the fans
2.7.1 General
The fans in the units are powered centrally and controlled from the control unit. The control unit is connected to the mains power supply.
c
Caution:
- The power supply to the fans may be
wired through between 3 units at most (with type XL: 2 units at most).
Cabling with horizontal installation position type 0 (equal to vertical installation position type 1)
Consult Biddle if you are going to con­nect more than 3 units (XL: 2 units) to one control unit.
Version 2.1, English (27-10-2008) 13
Page 14
B
- Apply a cable gland in the feed-
through 5 for pull relief purposes.
4 Connect the feeder cable to the terminal
blocks in the terminal boxes 2 according to the wiring diagram.
c
Caution:
Do not yet switch the mains supply on.
2.8 Connecting the electric
heating
Only for units with electric heating (type E)
Cabling with vertical installation position type 2
1 Remove the inspection panel 1 from the
free side of the unit.
2 Remove the cover from terminal box 2.
3 Lay the feeder cable between the control
unit and the terminal box in one unit of your choice as well as between the ter­minal boxes in the units.
- Lead the cable through the walls of
the units, via the holes 3 and 5. You may lead the cable inward through either end of the row of units.
- Fasten the cable to the edge 4 in-
side the unit using the cable clips.
w
Warning:
Do not allow the cable to lie or hang loosely.
- Make the grommets in the terminal
boxes to measure.
2.8.1 General
The electric heating of each unit is separately connected to the mains power supply. The heating is controlled using the control unit.
c
Caution:
- In emergency and maintenance situa-
tions, it must be possible to switch off the entire installation using an isolating switch.
- All connections must be made according to the applicable local laws, regulations and standards.
n
Note :
Each unit has an isolating switch to facilitate maintenance. This switch switches off only the electric heating of the relevant unit and does not affect the fans or the other units.
w
Warning:
The units must be earthed (grounded).
14
c
Caution:
Ensure the grommets have such tight fit around the cable that they remain watertight.
Manual model IndAC
Page 15
Industrial Air Curtain 2 Installation
2.8.2 Opening the heating section
Perform the following for each unit:
1 Set the isolating switch 1 on the unit to
the zero position.
2 Remove the cover 2.
3 Remove the inlet grille 3.
4 Remove the cover from the cable com-
partment 4.
- Lay the cable in the cable compart-
ment 4.
w
Warning:
Do not allow the cable to lie or hang loosely.
- Apply a cable gland in the feed-
through for pull relief purposes.
2 Connect the feeder cable to the isolating
switch 5 (blue) according to the wiring diagram. Connect the earth cable to the terminal block 6 (green and yellow).
2.8.4 Connecting the control cable
within the units
2.8.3 Connecting the feeder cable
w
Warning:
Make sure that the mains power supply is switched off.
Perform the following for each unit:
1 Lay the control cable between the control
unit and one unit of your choice as well as between the different units.
- Lead the cable either through hole 2
or 3. You may lead the cable inward through either end of the row of units.
- Lay the cable in the cable compart-
ment 4.
1 Lay the feeder cable to the unit:
- Lead the cable through either hole 1
or 2 or 3. You may lead the cable through an adjacent unit.
- Where necessary, interchange the
cable entry plate at hole 2 or 3.
Version 2.1, English (27-10-2008) 15
w
Warning:
Do not allow the cable to lie or hang loosely.
- Apply a cable gland in the feed-
through for pull relief purposes.
Page 16
B
2 In each unit, connect the control cable to
the terminal block 7 according to the wiring diagram.
2.9 Finishing
For units with electric heating:
1 Place cover 4 back on the cable com-
partment.
2 Place the inlet grilles 3 back.
3 Place the cover 2 back.
2.10 Switching on and
checking operation
For all units:
1 Check the following connections:
- power supply;
- cabling between control unit and
units, and between the different units;
- external control components (if any).
2 Switch the mains supply on.
3 Switch the air curtain on using the control
unit, and check if the air curtain blows out air.
c
Caution:
If the fans run out of true, the unit may not be standing or hanging completely level. Correct this where necessary.
For all units:
4 Place the covers back on the terminal
boxes 2 in order to protect the connec­tions from dirt and cleaning.
5 Place the inspection panels 1 back.
4 Check the direction of rotation of the
fans.
wrong: the blades go forward
If necessary, correct the direction of rota­tion by interchanging the connections of two phases from the mains supply.
c
Caution:
The fans are not resistant to prolonged rotation in the wrong direction.
For water-heated units:
correct: the blades go backward
16
5 Check if the heat exchanger is con-
nected correctly.
6 Make sure the CH system is turned on.
7 Feel whether the discharged air gets
warm.
Manual model IndAC
Page 17
Industrial Air Curtain 2 Installation
8 Vent the heat exchanger, if necessary.
For units with electric heating:
9 Set the isolating switches on all units to
position 1.
10 Switch the air curtain on using the control
unit.
11 Feel if the discharged air gets warm.
Version 2.1, English (27-10-2008) 17
Page 18
B
3 Maintenance
3.1 Safety instructions
w
Warning:
Maintenance works may be performed by qualified technical staff only.
Before opening the unit, follow the safety instructions in section 1.5.
1 Remove the discharge section 1: loosen
3.2 Access
bolts 2 and unhook the discharge sec­tion.
3.2.1 Fans
With horizontal installation position type 0, and vertical installation position type 1:
2 To access the terminal box of the fans:
remove inspection panel 3.
3 To take out the fans: loosen bolts 4 and
take out the fan along with bracket 5.
With vertical installation position type 2:
18
1 Remove inspection panel 3.
2 To take out the fans: loosen bolts 4 and
take out the fan along with bracket 5.
Manual model IndAC
Page 19
Industrial Air Curtain 3 Maintenance
3.2.2 Heating element
For water-heated units:
3 Remove the inlet grille 3.
4 Remove the cover from the cable com-
partment 4.
3.3 Cleaning
You can clean the unit's interior and exterior with water and a domestic cleaning agent. Do not use any solvents.
The fans can be cleaned with water as well. The unit has holes for the discharge of water.
w
Warning:
Do not spray water on the fans and termi­nal boxes.
Carefully remove dust from the heating ele­ment with a vacuum cleaner.
1 Remove inlet grille 1.
For units with electric heating:
d
Danger:
Do not clean electrically-heated units with water.
3.4 Scheduled maintenance
3.4.1 Monthly maintenance
- Check the heating elements and the fans
for dust and other contaminants. Clean if necessary.
- Check if all fans are working.
- Check if the air curtain is working at all
control unit settings.
- Check the discharge section for con­taminations and/or blockages; clean if necessary.
For units with water heating:
- Check for water leaks. If there is a leak,
disconnect the unit from the mains, and
1 Set the isolating switch 1 on the unit to
the zero position.
2 Remove the cover 2.
Version 2.1, English (27-10-2008) 19
repair the leak.
- Check if the water circuit contains any entrapped air. Bleed if necessary.
Page 20
B
3.4.2 Annual maintenance
- Perform all monthly checks.
- Check the cabling between the terminal
boxes in the units and the control unit.
- Check the casing, the hanging or fixing construction, and the securing of each unit.
- Check if the fans are mounted correctly and are not running out of true. If neces­sary, fasten them again.
For units with electric heating:
- Check the wiring between the control unit
and the heating section.
- Check the feeder cables and the connec­tions in the heating section.
- Check the relays in the heating section.
20
Manual model IndAC
Page 21
Industrial Air Curtain 4 Solving problems
For electrically heated units:
4 Solving
problems
4.1.1 General
If the air curtain does not work, or not prop­erly, perform the checks mentioned below.
If that does not help, there may be a defect. In that case, alert the installer.
4.1.2 Unit does not discharge any air
1 Check whether the air curtain has been
switched on by the control unit: see the control unit documentation.
2 Check if the unit is not disabled by an
external control component (door switch or room thermostat).
3 Check if mains power is supplied.
4 Check whether the isolating switch on all
units is set to position 1.
5 Check if mains power is supplied to each
unit.
6 Reset the high-limit thermostat: see the
control unit documentation
7 Check the control knob 1 in the unit: it
must always be set to 60° C.
4 Reset the thermal protector of the fans
to: see the control unit documentation.
4.1.3 Unit discharges little air
1 Remove obstacles in front of intake and
discharge openings.
2 Check the heat exchanger for contami-
nation. Clean it if necessary.
3 Check the direction of rotation of the
fans: see section 2.10.
4.1.4 Unit does not heat, or too little
1 When facing draught: select a higher fan
speed using the operation switch.
2 Does the unit blow out enough air? If not,
perform the checks in sections 4.1.2 and
4.1.3.
For water-heated units:
3 Check the operation of the CH system.
Version 2.1, English (27-10-2008) 21
Page 22
B Blank
22
Manual model IndAC
Page 23
Industrial Air Curtain Blank
Version 2.1, English (27-10-2008) 23
Page 24
Declaration of Conformity
Manufacturer: Biddle BV
Address: Markowei 4 9288 HA Kootstertille THE NETHERLANDS
We declare that the following product.
Product description: Industrial air curtain
Brand: Biddle
Model: IndAC
Type: IndAC S-150-W, S-200-W, M-150-W, M-200-W
IndAC L-150-W, L-225-W, XL-150-W, XL-225-W IndAC S-150-E, S-200-E, M-150-E, M-200-E IndAC S-150-A, S-200-A, M-150-A, M-200-A IndAC L-150-A, L-225-A, XL-150-A, XL-225-A
In accordance with the following Directives:
73/23/EEC the Low Voltage Directive
89/336/EEC the Electromagnetic Compatibility Directive
Has been designed and manufactured to the following specifications:
EN 50081-2:1993 EMC – Generic emission standard
part 2. Industrial environments.
EN 50082-2:1994 EMC – Generic immunity standard
part 2. Industrial environments.
I hereby declare that the equipment named above has been designed to comply with the relevant sections of the above referenced specifications. The unit complies with all essentials requirements of the directives.
Signed by : P. Stoelwinder, Managing Director, 2007
CE declaration IndAC standard.doc