Biddle CA2 User Manual

Manual
Comfort Air Curtain
Model CA
2
a
Version of manual: 6.1
Original manual
COMFORT AIR CURTAIN
2
. . . Table of contents
1 Introduction 4
1.1 About this manual 4
1.2 About the automatic CHIPS control 4
1.3 How to use this manual 4
1.4 About the unit 6
1.5 Safety instructions 11
2 Installation 13
2.1 Safety instructions 13
2.2 Delivery check 13
2.3 General working method 13
2.4 Fixing the unit 14
2.5 Connect the unit to the central heating installation (CA2 W) 18
2.6 Connect the unit to a Daikin system (CA2 V and CA2 Q) 20
2.7 Connecting the unit to the power supply 22
2.8 Installing control panel and external controls 25
2.9 Finishing the unit 29
2.10 Switching on and checking function 34
3 Operation 36
3.1 Introduction 36
3.2 Switching ON and OFF 36
3.3 The Home screen 37
3.4 CHIPS control 37
3.5 Faults 39
3.6 Main menu 39
3.7 Preferences 41
3.8 Settings 41
3.9 Configuration 42
3.10 Maintenance 45
3.11 USB 46
4 Maintenance 48
4.1 Replacing or cleaning the filter 48
4.2 Cleaning the unit 50
4.3 Scheduled maintenance 51
5 Faults 52
5.1 Safety instructions 52
5.2 Resolving simple problems 52
5.3 Fault messages in control panel 53
5.4 Remedying faults with error message 54
5.5 Remedying faults without message 58
MANUAL
Version: 6.1 (05-12-2011) 3
6Service 60
6.1 Safety instructions 60
6.2 Access to the interior of the unit 60
6.3 Electronics module 61
6.4 Daikin electronics (CA2 V and CA2 Q) 62
6.5 Fuses 63
6.6 Removing the discharge section 63
6.7 Venting the heat exchanger 64
6.8 Bleeding the heat exchanger 64
6.9 Entering the unit code 65
6.10 Resetting the PIN code 66
6.11 Configuration of the Biddle control cable 66
7 Dismantling 67
INTRODUCTION COMFORT AIR CURTAIN
4
1. . Introduction
1.1 About this manual
1.1.1 General
This manual describes the installation, operation and maintenance of the comf
ort air curtain model CA
2
with CHIPS control. The manual also provides instructions and information on service operations.
1.2 About the automatic CHIPS control
The CHIPS control matches the strength and heat of the air curtain to changing weather conditions. This reduces energy consumption and improves comfort through selection of the optimum setting under all circumstances. CHIPS stands for “Corrective Heat and Impulse Prediction System”.
The operation of the air curtain is based on the outside tem
perature and the room temperature near the air curtain.
1.3 How to use this manual
If you are unfamiliar with the comfort air curtain, read this manual section by section.
If you are familiar with the device, you may use this manual as a r
eference. Refer to the table of contents for looking up
information.
For CA
2
V and CA2 Q only:
This manual makes cross-reference to the manuals of the Daikin components (outdoor unit, indoor un
it, control panel,
etc.).
MANUAL INTRODUCTION
Version: 6.1 (05-12-2011) 5
1.3.1 Symbols used in the manual
The following symbols are used in this manual:
Note:
n Draws your attention to an important part of the text.
Read this part of the text thoroughly.
Caution:
c If you do not perform this procedure or action correctly,
you may damage the device. Follow the instructions strictly.
Warning:
w If you do not perform this procedure or action
correctly, you may cause damage and/or bodily
injury.
Follow the instructions strictly.
Danger:
d This indicates actions which are not permitted.
Ignoring this warning may lead to serious damage
or accidents which may involve bodily injury.
The action may be carried out only by qualified
staff perf
orming maintenance or repair works.
1.3.2 Pictograms on the unit and in the manual
The pictograms in Table 1-1 warn of potential risks and/or dangers. The pictograms can be found opposite the text discus
sing risk-entailing operations. The same pictograms will
also be found on the unit.
Table 1-1 Picto
grams
P
ICTOGRAM DESCRIPTION
ê
Warning: You are entering an area of the unit containing ‘live’ components. Accessible to qualified maintenance staff only. Exercise caution.
ç
Warning: This surface or part can be hot. There is a risk of burns on contact.
INTRODUCTION COMFORT AIR CURTAIN
6
1.3.3 Related documentation
In addition to this manual, the following document has been sup
plied with the unit:
Wiring diagram for installation and service
1.4 About the unit
1.4.1 Applications
The comfort air curtain is inten
ded for the separation of climates between two rooms, and for the heating and filtering (filter class EN779-G2) of air. The unit is installed above the doorway, across its full width.
The free-hanging model is designed for free, visible installation above the door.
The recessed model is designed for integration into a false ceiling or into a cove, with the inlet opening possibly at some distance from the unit.
The cassette model is designed for installation above a false ceiling, with the inlet opening close to the unit and with easy access to the unit.
CA2 V and CA2 Q
The CA
2
V/CA2 Q air curtain is connected to a Daikin direct expansion system. The air blown through the unit is heated by the cooling medium. The air curtain is controlled and operated partly by the Daikin system and partly by the Biddle system.
MANUAL INTRODUCTION
Version: 6.1 (05-12-2011) 7
The system has a number of limitations:
The unit is only suitable for use in Daikin direct expansion systems.
The unit is not suitable for cooling.
The temperature control is less accurate than with water or electric heating.
The Daikin system has to be active at all times.
Other versions and intended use.
On request, versions can be supplied for other applications.
Warning:
w Applications other than those described above are
not considered to be an intended use. Biddle
assumes no responsibility for damage or injury
resulting from applications other than the intended
use. The intended use also implies observance of
and compliance with the instructions in this
manual.
1.4.2 Function
The air curtain blows out a stream of heated air straight down, thus achieving the following:
The exchange of air between two rooms due to temperature differences (convection) is stopped.
The cold air entering across the floor due to draught is heated.
Depending on the air curtains setting, the unit can also blow unheated air.
1.4.3 Models and type designations
Ta b l e 1-2 provides an overview of available models of the comfort air curtain and the corresponding type designations. Combined, the type designations constitute the type code, for instance: CA2
S-100-W-F. Not every combination is available.
If some part of the manual applies to certain models only, these will be indicated using the corresponding type designation, for example:
-CA2 S, M: Models with capacity S or M;
-CA2 100: Models with discharge width 100;
INTRODUCTION COMFORT AIR CURTAIN
8
-CA2 W: Water-heated models;
-CA
2
E: Electrically-heated models;
-CA
2
F: Free-hanging models.
Note:
n In the illustrations in this manual, the following unit type is
used as a general example: CA2 M-150-W-F. The a
ppearance of your unit may be different but its function is
the same, unless stated otherwise.
Table 1-2 Ex
planation of the type code
P
ART TYPE CODE DESIGNATION MEANING
Product series CA
2
General reference for the series
Daikin system V For connection to Daikin VRV system (‘mu
lti’)
Q For connection to Daikin ERQ system (‘pai
r’)
Capacity S, M, L or XL Small, medium, large or extra large range
Discharge width 100, 150, 200 or 250 Discharge width in cm
Heating W Water heating
E Electric heating
A Without heating
DK Heating with Daikin direct expansion system
Mounting method F Free-hanging model
R Recessed model
C Cassette model
Valve (only CA
2
W) 2-way Two-way valve installed instead of a three-way valve.
Colour (only CA
2
V
and CA
2
Q)
B white
S aluminium
X non-standard colour
Control panel (only CA
2
V and CA2 Q)
C B-touch control panel included
N Not included (if several units are connected in one
instal
lation)
1
MANUAL INTRODUCTION
Version: 6.1 (05-12-2011) 9
Type CA M-150-W-F
Code 1213 U 230 V 1N~ 50 Hz
Biddle bv Markowei 4 NL-9288 HA Kootstertille
Nº 5426/1-1 00-01 I
max
L1 2.4 A
I
max
L2 -
M 60 kg I
max
L3 -
Medium LPHW P
motor
0.56 kW
p
max
1400 kPa P
heating
-
Example of a type plate
1.4.4 Type plate
The type plate 1 is located on the left at the front of the unit.
This manual refers to the following data on the type plate:
Ty
pe: Complete type code of the unit;
Code: Unit co
de of the Biddle electronics;
M: W
eight of the unit;
Medium: Heati
ng medium
Capacity index:
Daikin capacity index
P
max
: Maximum permissible working pressure in the hot
water circuit (at 110 ºC);
U, I
max
, P
motor
and P
heating
: Maximum load on the electrical
system by the unit.
1.4.5 Field of application
The Comfort Air Curtain is predominantl
y used in commercial premises at an ambient temperature of max. 40°C. The following limits must thereby be observed:
Table 1-3 Appl
ication limits
Ambient temperature 5°C to 40°C
System voltage see type plate
Power see type plate
Maximum discharge temperature 50°C
Heating medium CA W water with max. 20% glycol
Maximum working pressure and temperature 6 bar at 110°C
Maximum valve pressure difference:
- CA S/M
- CA L/XL
0.5 bar
1.0 bar
Warning:
w The air curtain must not be employed in potentially
explosive atmospheres, wet environments,
outdoors or in very dusty or aggressive air. Biddle
assumes no responsibility for damage or injury
resulting from use in these situations.
1.4.6 CE standard
Q
The air curtain satisfies the applicable CE standards. The complete CE declaration can be found at the Biddle website.
INTRODUCTION COMFORT AIR CURTAIN
10
1.4.7 Modifications and changes
No changes or modifications may be made to the unit which could influence its safety without the approval of Biddle. Changes or modifications will void the CE declaration.
1.4.8 Components and accessories
Note:
n The type code of components and accessories must
correspond to that of the unit with which they will be employed.
Components
The following components are delivered separately but always required:
b-touch control panel (able to control a maximum of 10 units);
Outdoor sensor;
Biddle control cable, available in various lengths;
only with free-hanging models: set of end caps.
Accessories
The following accessories are available as options:
Door contact switch;
Wall bracket set, ‘Standard’ or ‘Design’;
Threaded rod lining;
Long-life filter (instead of the standard inlet grates and/or grilles);
BMS interface module (instead of control panel);
Air flow sensor (to detect whether the fans are running).
For CA2 V and CA2 Q only: Daikin components
The following Daikin components are required for an installation:
Outdoor unit
Optional: One or more indoor units
Daikin control panel
Connections materials, such as cooling lines, wiring, etc.: See the Installation manual for the outdoor unit
MANUAL INTRODUCTION
Version: 6.1 (05-12-2011) 11
Caution:
c The control system and capacity index of the Daikin
outdoor unit must correspond to those of the Biddle air curtain.
1.5 Safety instructions
1.5.1 Operation
Warning:
w Do not put any objects in the inlets and outlets.
Warning:
w Do not block the inlets and outlets.
ç
Warning:
w The upper surface of the unit becomes hot during
operation.
Caution:
c In exceptional situations, water may run out of the unit.
Therefore do not place anything under the unit that could be damaged as a result.
1.5.2 Installation, maintenance and service
Danger:
d The unit may be opened by qualified technical staff
only.
Warning:
w Perform the following actions before opening the
unit:
ê
1. Switch the unit OFF using the control panel.
2. Wait until the fans have stopped.
3.
ç
Allow the unit to cool down.
The heat exchanger and/or the heating elements can get v
ery hot. Moreover, the fans may continue to rotate for a
while.
INTRODUCTION COMFORT AIR CURTAIN
12
4. For CA2 V and CA2 Q: Switch off the Daikin system and disconnect the power supply from the Daikin outdoor unit.
5. Disconnect the power supply (remove plug from socket or move isolation switch to OFF).
6. For water-heated models: Close the central heating supply (if possible).
Caution:
c For CA
2
V and CA2 Q: If the system operates in defrost mode or has been in operation recently, there may be water in the inspection panel.
Warning:
w The fins of the heat exchanger are sharp.
MANUAL INSTALLATION
Version: 6.1 (05-12-2011) 13
2 . . Installation
2.1 Safety instructions
Danger:
d Installation work on the unit may be performed by
qualified technical staff only.
Warning:
w Before opening the unit: Observe the safety
instructions in section
1.5.
2.2 Delivery check
1. Check the unit and its packaging for correct delivery. Immediately report to the supplier any damage caused in transit.
2. Make sure that all components and accompanying parts have been supplied.
2.3 General working method
Working method
Biddle recommends the following working method for installing the comfort air curtain:
1. Mount the unit (section 2.4).
2. For water-heated models:CA2 W:
Connect the unit to the central heating system (section
2.5).
For models for connection to a Daikin direct expansion system
CA
2
V and CA2 Q:
Install the Daikin components as described in the respective installation manuals:
- Outdoor unit;
- If installed in your system: Indoor unit(s);
- Control panel.
INSTALLATION COMFORT AIR CURTAIN
14
3. Connect the unit to the power supply (section 2.7).
4. Install the control panel, the outdoor sensor and (any optional) connections to external controls (section
2.8).
5. Finish the unit (section 2.9).
6. For models for connection to a Daikin direct expansion system
CA
2
V and CA2 Q:
Connect the air curtain unit to the Daikin system (section
2.6).
7. Switch on the power supply.
8. During the first start, the installation guide is started. Follow this through to carry out the most frequently needed settings.
If the installation guide is not displayed, it can be started with
Menu>Maintenance>Installation.
9. Check the function of the unit (section 2.10).
General instructions
Some parts of this section are applicable only to certain models. Where this is the case, it will be indicated. If no specific model is referred to, the description applies to all models.
Note:
n Make sure you perform all installation operations that are
required for your unit.
Check the type plate. Refer to section 1.4.3 if you are not sure about the model or type of your unit.
Note:
n Protect the unit from damage and ingress of dust, cement,
etc. throughout the installation. You can, for instance, use the packaging for protection.
2.4 Fixing the unit
2.4.1 Determining the location of the unit
Danger:
d Do not install the unit in a vertical position.
x
h
b
MANUAL INSTALLATION
Version: 6.1 (05-12-2011) 15
Make sure that the structure from which the unit is about to be suspended can bear the weight of the unit. The weight is specified on the type plate (see section 1.4.4).
Note the following dimensions:
- The unit must be at least as wide as the doorway
(dimension b).
- Position the unit as near to the doorway as possible.
- The maximum mounting height of the unit (dimension
h,
measured from the floor to the discharge grille) depends on the unit type and circumstances. If in doubt, ask Biddle for advice on the correct height.
Warning:
w The minimum mounting height (dimension h) is
1.8 m.
ç
Warning:
w The top of the unit may get hot. Mount the unit
with a minimum clearance of 25 mm from the
ceilin
g (dimension x).
2.4.2 Fix the suspension brackets
1
2
3
1. Fix four threaded rods M8 according to the dimensions in Table 2-1. Make sure the threaded rods are perpendicular.
Note:
n Units of type CA
2
250 have three suspension brackets. Fix
six threaded rods for that type.
2. Apply a lock nut 1 to each threaded rod.
3. Apply the suspension brackets 2 onto the threaded rods, and a
pply the nuts 3.
4. Make sure the suspension brackets are suspended horizontall
y and flush.
5. Secure each suspension bracket by tightening the lock nuts
1.
Table 2-1 Dimensions for suspending unit
R
EFERENCE TYPE DIMENSIONS
a
b
c
d
a all models as needed
b CA
2
S 119 mm
CA
2
M 119 mm
CA
2
L 200 mm
CA
2
XL 200 mm
c all models 197 mm
d CA
2
100 500 mm
CA
2
150 1000 mm
CA
2
200 1500 mm
CA
2
250 (six
threaded rods)
2 x 1,000 mm
2
2
1
1
INSTALLATION COMFORT AIR CURTAIN
16
2.4.3 Suspending and securing the unit
1. Remove the components and packaging from the pallet with the unit on
it. Leave the unit on the pallet.
2. The unit is fixed to the pallet with two transportation bra
ckets 1. Remove the screws 2. Do not remove the
bra
ckets from the unit.
3. Tilt the unit across the pallet and lay it down as shown opposite.
4. Lift the pallet, with the unit on it, and hook the unit into the suspensio
n brackets.
1
MANUAL INSTALLATION
Version: 6.1 (05-12-2011) 17
Caution:
c Depending on the weight (specified on the type plate, see
section 1.4.4), either use a lifting device or lift the unit with at least 2 persons.
Note:
n Always use the pallet when lifting the unit to prevent any
damage. This helps to avoid damage.
5. The unit now suspends from the suspension brackets: Take th
e pallet away.
6. Remove the transportation brackets 1 from the unit.
2 3
INSTALLATION COMFORT AIR CURTAIN
18
7. Fit a lock plate 3 to each suspension bracket.
Warning:
w The unit may fall down if you do not secure the
suspension.
8. Check whether the unit is suspended firmly:
- Try to push the unit from its suspension.
- Shake the unit for a few seconds.
Warning:
w Ensure you do not run any risk, should the unit
drop down.
2.5 Connect the unit to the central heating installation (CA2 W)
2
1
2.5.1 Particulars
Caution:
c The supply and return pipes of the central heating system
must be connected to the correct corresponding connections 1. The directions are indicated on the unit us
ing arrows.
The maximum permissible operating pressure of the hot wate
r circuit is specified on the type plate (see section 1.4.4). It is based on a water temperature of 110 ºC.
Caution:
c The unit has an integrated water control. The central
heating connection must not be fitted with a control valve.
The water-side control valve is automaticall
y closed as standard if the air curtain and/or the heating is switched off. This can be altered at the control panel via
Menu>configuration>77. Valve open.
Caution:
c Biddle recommends the inclusion of a valve in each pipe.
The bleed valve 2 of the heat exchanger is located at the
l
eft in the top of the unit.
CA S/M CA L/XL
A
B
AB
A
B
AB
MANUAL INSTALLATION
Version: 6.1 (05-12-2011) 19
Units with side connection
On request, units with electrical 12 and water-side 3 con
nections on the side can be supplied. The water-side control is then not built-in, but has to be connected outside the unit during installation.
1. Connect the valve to the connections 3 as shown in the
diag
ram opposite.
2. Connect the valve drive to terminal 2.
2.5.2 Frost protection
The electronic control features integrated fr
ost protection. It
works in two stages:
1. If the discharge air temperature falls to below 5 ºC:
- the control panel will temporarily display fault message E6
(see section 5.3);
- the valve of the integral water control will open fully;
- the output on the unit giv
es a signal for the central
heating installation (if function
61a/b. Function of output
1/2
on the operating panel is set to Frost protection).
2. If the discharge air temperature falls to below 2 ºC:
- fault message E6 will become final;
- the fans will be switched off, but the valve of the water contr
ol will stay open.
The frost protection is automaticall
y lifted when the incoming
or outgoing air temperature rises to above 8 ºC.
Caution:
c The frost protection reduces the risk of freezing but does
not warrant 100% protection.
Take the following precautions if you install the unit in a r
oom where frost may occur:
- Provide for constant circulation of the water at the rig
ht temperature;
- Add up to 20% glycol to the water when the unit is not in operati
on during the wintertime;
- Or drain the system and the unit (see section 6.8).
2.5.3 Connect the unit
1. Connect the unit to the central heating
system.
INSTALLATION COMFORT AIR CURTAIN
20
2. Vent the heat exchanger.
3. Check the connections for leaks.
2.6 Connect the unit to a Daikin system (CA2 V and CA2 Q)
2.6.1 Preconditions for connection to a Daikin system
The Daikin system must always be active when the Biddle air cur
tain is active.
A control system must be connected to the Daikin system. This can
also be a Daikin control panel that is connected
to the Biddle air curtain.
Warning:
w Units of type CA
2
V may only be connected to a
Daikin VRV system.Units of type CA
2
Q may only
be connected to a Daikin ERQ system.These units
are not interchangeable.
2.6.2 Connection of the control system
All models
Caution:
c Use cable with a cross-section of min. 0.75 mm².
X84
Models with discharge width 150, 200 or 250
1. Connect the control system of the Daikin system to term
inal X84 on the upper side of the air curtain:
- Connect the control cable of the outdoor unit to
F1/
F2.
- If ins
talled on your unit: Connect the Daikin control
panel to P1/P2.
2. Install the cable sheath (su
pplied) on the terminal.
1
2
Models with discharge width 100
1. Remove the cover 1 of the box on the side of the unit.
2. Optiona
l: Remove the box from the unit:
MANUAL INSTALLATION
Version: 6.1 (05-12-2011) 21
- Remove the bracket 2 from the unit and the box.
- Install the box on the wall at an appropriate point.
Caution:
c Do not disconnect the wiring between the box and the
unit.
3
4
3. Lay the control cable(s) into the box, through the free
cable gland(s) 3.
4. Connect the controller of the system to the terminal block
4:
- Connect the control cable of the outdoor unit to F1/ F2.
- If installed on y
our unit: Connect the Daikin control
panel to P1/P2.
5. Tighten the cable gland(s).
6. Install cover 1 on the box again.
2.6.3 Connection of cooling medium
Install the lines according to the installation manual of the Daikin outdoor unit.
Solder the lines to the pipes protruding out of the upper side of the u
nit.
2.6.4 Settings on the Daikin control panel
You can make local settings on the Daikin control panel as described in the cor
responding installation manual.
The units described in this manual have a few additional setting possibilities:.
M
ODE
NUMBER
FIRST
CODE NUMBER
DESCRIPTION
OF THE SETTING
SECOND CODE NUMBER
01 02 03 04
(22) 3 Function of air
cu
rtain when
not heating
(23) 8 Function of air
cu
rtain in
defrost mode
(standard settin
g)
unheated (standar
d
setting)
unheated at
standstill (if 23-8 is set to 01)
--
at standstill
un
heated unheated --
INSTALLATION COMFORT AIR CURTAIN
22
2.7 Connecting the unit to the power supply
2.7.1 All models
Warning:
w Do not turn on the unit from the power supply. Use
the control panel.
Warning:
w Every unit must be separately fused in accordance
with table 2-2.
Table 2-2 Fus
e values
Note:
n Multiple units may only be served by a common fuse if
their total current consumption is less than 10A.
2.7.2 Models with water heating (CA
2
W) and models
for connection to a Daikin system (CA
2
V and
CA
2
Q)
1. Ensure that an (earthed) power point is available at a m
aximum of 1.5 m from the left side of the unit.
Warning:
w The unit must be grounded.
M
AXIMUM AMPERAGE ON
TYPE PLATE
L1, L2 OR L3
M
AXIMUM FUSE VALUE
A
<= 10A 16A
<= 15A 20A
<= 20A 25A
<= 25A 35A
<= 35A 50A
<= 50A 63A
<= 65A 80A
<= 80A 100A
<= 102A 125A
MANUAL INSTALLATION
Version: 6.1 (05-12-2011) 23
Warning:
w The wall socket must remain accessible after the
installation of the unit to be able to disconnect the
unit from the mains when maintenance work is to
be performed.
2.7.3 Connection of models with electric heating
(CA E)
Danger:
d Do not perform the connection work unless you
are qualified to work with three-phase current.
Particulars
Connect the unit to the power su
pply with a 5-core cable (not supplied). The maximum load data are specified on the type plate (see section 1.4.4).
123N
Contact clearance
RS TN
An isolation switch (not supplied) must be fitted between the unit and the power supply. This switch must:
-be all-pole;
- have a minimum contact clearance of 3 mm;
- be positioned at a
maximum of 4 m from the left side
of the unit.
Warning:
w The unit must not be switchable using the power
supply cable: use the control panel for that.
Warning:
w The unit must be grounded.
Warning:
w Connect the unit in accordance with the applicable
local requirements.
INSTALLATION COMFORT AIR CURTAIN
24
Connect the unit
Warning:
w Make sure that the power supply you are working
on is switched off.
1
1
1
1
1. Fit the isolation switch and connect it to the power supply.
2. Remove the inspection panel:
- Remove the screws 1.
- Pull the panel a little forward and take it away.
Caution:
c The whole panel will come loose when you pull it forward:
Take care it does not fall down.
2
3. Fix the cable gland 2 to the unit.
4. Lead the power supply cable through the cable swivel.
5. Connect the cable to the terminal 3 in the unit according
to th
e wiring diagram.
3
Note:
n The design in your unit may differ from the illustration.
MANUAL INSTALLATION
Version: 6.1 (05-12-2011) 25
6. Put back and screw down the inspection panel.
Warning:
w Always attach the inspection panel using flanged
bolts with milled edges: these are needed for the
earth connection.
7. Connect the power supply cable to the isolation switch.
Caution:
c Do not yet switch the power supply on.
2.8 Installing control panel and external controls
2.8.1 Control panel details
Posi tioning
You may fix the control panel either to the wall or to a sta
ndard socket.
Cabling
Note:
n Take the following into account, otherwise faults may
occur:
- The control cable between the control panel and the
(f
irst) connected unit must not be more than 50 m
long.
- Keep control cables away from electromagnetic fields
and interf
erence sources such as high-voltage cables
and fluorescent-light starters.
- Stretch control cables out or roll them up neatly.
- Do not remove the dummy plug, unless otherwise
stated.
Note:
n Use only control cables from Biddle. Standard modular
telephone cable is not suitable.
Multiple units operated from one control panel
Type CA M-150-W-F
Code 1213 U 230 V 1N~ 50 Hz
Biddle bv Markowei 4 NL-9288 HA Kootstertille
Nº 5426/1-1 00-01 I
max
L1 2.4 A
I
max
L2 -
M 60 kg I
max
L3 -
Medium LPHW P
motor
0.56 kW
p
max
1400 kPa P
heating
-
code
Up to 10 units can be connected to one single control panel. To do so, the units must be interlinked.
INSTALLATION COMFORT AIR CURTAIN
26
The total length of the control cables is not to exceed 100 m.
Only units that have the same second digit in the unit code (see “code” on the type plate, section
1.4.4) can be
controlled in combination with the same control panel.
2.8.2 External control details
Input on the control panel (X426)
The control panel has one input signal interface. This can be used for an external ON/OFF signal or for an additional temperature sensor.
Input on the unit I1-I1
The unit has one input signal interface. A timer, a door switch, a room thermostat or a BMS (building management system) signal may be connected to this.
Caution:
c Both inputs are designed for controls with potential-free
contacts, and are not to be loaded.
Caution:
c The inputs of multiple units must not be connected to each
other.
Warning:
w With units connected to a Daikin system (CA
2
V
and CA
2
Q), the units must not be frequently
switched ON and OFF via the inputs. This can
cause damage to the unit or to the Daikin system.
With function
60. Function of input, the settings Unit
on/off locally, Switch all units on/off are therefore not
permitted. With the setting
Quick speed up, function
54. Strength with door closed must not be set to zero.
Note:
n With the setting All units OFF and with the NC (normally
closed) settings of function
61a/b. Function of output 1/2, a
jumper must be laid to the input for all the other connected units.
MANUAL INSTALLATION
Version: 6.1 (05-12-2011) 27
Outputs on the unit O1-O1 and O2-O2
The unit has an interface for two output signals: These can be used, f
or instance, for controlling the central heating or cooling system or for status messages to a building management system.
Caution:
c The outputs are potential-free contacts (relays). Their
maximum load is 24 V / 1 A.
Options and operation
Options and operation depend on the inputs or output as well as
on the control panel settings. These are further described
in section Operation.
2.8.3 Mounting and connecting control panel
1. Lay the control cable.
2. If t
he external-control input in the control panel is used: lay the necessary cabling. The cable core diameter is not to exceed 0.75 mm.
3. Push the operating panel out of the wall holder.
4. Connect the control cable to
terminal X397 and (if installed) the cable for the external control to terminal X426 of the wall holder.
5. Screw the wall holder onto the plug socket or the wall.
6. Place the control panel back in the wall holder.
7. Optional: Lock the control panel with the screw on the underside
.
2.8.4 Connecting control panel to unit
The control panel connections G and D are located on the connector plate on the upper side of the unit. The two sockets are identical. One of the two sockets has a dummy plug.
1. Connect the control cable to the free terminal
G or D.
INSTALLATION COMFORT AIR CURTAIN
28
Note:
n Do not remove the dummy plug from the other socket, as
this may lead to faults.
Note:
n Leave about 30 cm excess cable length: it will be needed to
take the electronics out when servicing the unit.
Multiple units operated from one control panel
1. For each unit to be linked, remove the dummy plug from sock
et
G or D.
2. Interlink the units: Connect the control cables to
G and D.
Note:
n Do not remove the dummy plug from the last unit, as this
may lead to faults.
2.8.5 Installing the outdoor sensor
Caution:
c The automatic control is less efficient without an outdoor
sensor.
1. Install the outdoor sensor on the wall:
- At least 1 metre to the side of the door opening or at
least
2 metres above the door opening
- out of the sun and protected against rain.
2. Connect a cable (not supplied) between outdoor sensor 1 an
d unit.
3. Connect the sensor to terminal X82 on the upper side of the air cur
tain.
4. Install the cable sheath (su
pplied) on the terminal.
MANUAL INSTALLATION
Version: 6.1 (05-12-2011) 29
Note:
n Leave about 30 cm excess cable length: it will be needed to
take the electronics out when servicing the unit.
2.8.6 Connecting external controls to the unit
(optional)
The terminals are located in the connector plate on the top of the unit. The corresponding connectors are located in the terminals.
Connect the cable for the output signals to terminal O1­O1 o
r O2-O2.
Connect the cable for the input signal to terminal I1-I1.
Note:
n Leave about 30 cm excess cable length: it will be needed to
take the electronics out when servicing the unit.
2.9 Finishing the unit
2.9.1 Finishing free-hanging models
1
2
Position the side caps
1. Fit the end caps to either side of the unit:
- Hook the end caps 1 into the slots in side 2.
- Push the caps down until you hear a click.
If linking two or more units to each other, fit the end caps to
the outer ends.
3
Position the inlet grilles
2. Fit the inlet grilles to the unit:
- Hook the grilles onto the upper side of the unit.
- The back of each grille has a projection. Fit the grille
w
ith the projection into the rectangular hole 3.
INSTALLATION COMFORT AIR CURTAIN
30
2.9.2 Finishing recessed models
General
Note:
n Ensure that the unit remains accessible for maintenance
and repair through, for instance, an inspection hatch.
1
Adjusting the discharge duct
If linking two or more units to each other
, you must adjust the discharge duct so that the finishing edges will not be in each other’s way.
1. Remove the end piece with finishing edge 1.
2
2. Mount the end piece without finishing edge 2.
3
4
Installing the discharge duct
3. Make a hole in the ceiling for the discharge (for
dimensions, see T
able 2-3).
4. Fix the two angle sections3 with sheet metal screws to
the unit, along
the edges of the discharge opening.
5. Slide the discharge duct 4 into the discharge opening until
the desir
ed height is reached.
MANUAL INSTALLATION
Version: 6.1 (05-12-2011) 31
6. Using sheet metal screws, fix the discharge duct to the
angle sections 3.
Installing the grille plenum of the inlet section
7. Make a hole in the false ceiling for the inlet section (see T
able 2-4).
8. Take the inlet grille out of its frame:
- Push the two pins 1 in the grille towards one another
and ti
lt the grille outward.
- Push the two pins at 2 towards one another and take
t
he grille out.
Table 2-3 Dis
charge section hole dimensions
R
EFEREN
CE
TYPE DIMENSIONS
b
a
a CA2 S-R 102 mm
CA
2
M-R 102 mm
CA
2
L-R 133,5 mm
CA
2
XL-R 133,5 mm
b CA
2
100-R 1008 mm
CA
2
150-R 1508 mm
CA
2
200-R 2008 mm
CA
2
250-R 2508 mm
Table 2-4 Inlet section hole dimensions
R
EFEREN
CE
TYPE DIMENSIONS
b
a
a CA2 S-R 268 mm
CA
2
M-R 268 mm
CA
2
L-R 368 mm
CA
2
XL-R 368 mm
b CA
2
100-R 1008 mm
CA
2
150-R 1508 mm
CA
2
200-R 2008 mm
CA
2
250-R 2508 mm
1
1
2
2
INSTALLATION COMFORT AIR CURTAIN
32
9. Mount the grille plenum to the inlet grille frame.
10. Put the grille back into its frame.
11. Fix the edge finishing strips to the frame.
12. Suspend the inlet section. To do so
, use the supplied screw
eyes or four threaded rods, M6.
Connect the unit plenum and grille plenum
13. Connect the unit plenum to the grille plenum using flexible ducts.
Use hose clips to fix the ducts.
2.9.3 Finishing cassette models
Note:
n With the unit types CA
2
200 and CA2 250, the components of the inlet section are supplied in two sections.
1
2
2
Installing the inlet case
1. Mount the inlet case on the unit:
- Hook the inlet case onto the
upper side of the unit.
- Screw flange 1 of the inlet case to the unit.
2. Fix the angle points 2 of the inlet case to the ceiling. To
d
o so, use the supplied screw eyes or two threaded rods,
M6.
Table 2-5 Plenum duct diameter
TYPE DUCT DIAMETER
CA2 S-R 160 mm
CA
2
M-R 160 mm
CA
2
L-R 250 mm
CA
2
XL-R 250 mm
MANUAL INSTALLATION
Version: 6.1 (05-12-2011) 33
Warning:
w If you do not fix the inlet case to the ceiling, the
unit may tip over and fall out of the suspension
brackets.
1
1
2
2
Installing the inlet plenum
3. Take the inlet grille out of its frame:
- Push the two pins 1 in the grille towards one another
and ti
lt the grille outward.
- Push the two pins at 2 towards one another and take
t
he grille out.
4. Screw the frame onto the inlet case.
5. Put the grille back into its frame.
Finishing
6. Fix the edge finishing strips around the unit.
INSTALLATION COMFORT AIR CURTAIN
34
7. Make a hole in the false ceiling with the dimensions stated in Table 2-6.
2.10 Switching on and checking function
For models connected to a Daikin system CA2 V and
CA
2
Q:
Switch on the Daikin indoor units and outdoor unit.
For all models
1. Check the following connections:
-Power supply;
- Control cables between control panel and unit (or
un
its);
-For CA
2
V and CA2 Q: Control cables between unit(s)
and Daikin components.
- External control components (if used).
2. Switch the power supply on and/or plug in all connected un
its.
When you switch on the power supply for the first time, the contr
ol panel searches for connected units and then
immediately displays the number of connected units.
3. During the first start, the installation guide is started. F
ollow this through to carry out the most frequently
needed settings.
If the installation guide is not displayed, it can be started wi
th
Menu>Maintenance>Installation.
Table 2-6 Un
it hole dimensions
R
EFEREN
CE
TYPE DIMENSIONS
b
a
a CA2 S-C 829 mm
CA
2
M-C 829 mm
CA
2
L-C 1113 mm
CA
2
XL-C 1113 mm
b CA
2
100-C 1008 mm
CA
2
150-C 1508 mm
CA
2
200-C 2008 mm
CA
2
250-C 2508 mm
MANUAL INSTALLATION
Version: 6.1 (05-12-2011) 35
If the control unit does not function, or if the display shows an error messages, consult section
Faults.
For models with water heating or connected to a
Daikin system
4. Check that the heat exchanger is connected correctly.
5. Make sure the central heating system or the Daikin system is turned on.
6. Make sure heating is enabled in the control panel.
7. Feel if the discharged air stream gets warm. This may take some time.
8. Vent the heat exchanger, if necessary.
For models with electric heating
9. Make sure heating is enabled in the control panel.
10. Feel if the discharged air stream gets warm.
For models without heating
11. Feel if the unit discharges air.
OPERATION COMFORT AIR CURTAIN
36
3. . Operation
3.1 Introduction
This section describes the functions of the b-touch control panel required for the use of the comfort air curtain.
The b-touch control panel has a touchscreen with which all th
e functions can be controlled:
Switch the air curtain ON and OFF;
Set the strength of the air curtain;
Switch the heating ON and OFF;
Carry out settings to adapt the function of the air curtain to y
our situation.
Multiple units operated from one control panel
If multiple units are connected to the b-touch con
trol panel,
the settings are the same for all units.
Settings
Select to save the settings and return to the previous screen.
Select to return to the previous screen without saving the changes.
Help function
?
You can call up additional information on your momentary point of operation at any time by touching
Help.
3.2 Switching ON and OFF
3.2.1 Switching the air curtain ON and OFF
You can switch the air curtain ON and OFF manually. Independentl
y of this, the unit can be controlled by external
MANUAL OPERATION
Version: 6.1 (05-12-2011) 37
controls (see function 53. Control panel input and 60.
Function of input).
•Touch
ON/OFF to switch the air curtain ON or OFF.
When the unit is switched on, the scr
een will go dark after a short time to save energy. When the screen is touched, it lights up again. This function cannot be deactivated.
When the unit is switched off, the scr
een will go black after a short time. Touch the screen to activate it again.
3.3 The Home screen
The settings of the air curtain and the room temperature can be adjusted in the Home screen.
Touch the parts of the air curtain icon to select manual or autom
atic and to adjust the strength of the air curtain or the
room temperature.
Touch the air flow icon to obtain brief information on the operation of the un
it.
To u c h
Menu to call up the main menu.
3.4 CHIPS control
The air curtain operates as standard with fully automatic control. Depending on the selected settings, the air curtain can also be controlled manually.
In automatic mode, the unit operates under CHIPS control. This con
trol matches the strength and heat of the air curtain to changing weather conditions. This reduces energy consumption and improves comfort through selection of the optimum setting under all circumstances. CHIPS stands for “Corrective Heat and Impulse Prediction System”.
The operation of the air curtain is based on the outside temp
erature and the room temperature near the air curtain.
OPERATION COMFORT AIR CURTAIN
38
3.4.1 Automatic or manual control
The air curtain has an automatic an
d a manual mode. These can be selected by touching the uppermost part of the air curtain icon.
When the unit is switched on, it is always in automatic mode. I
f you wish to operate the unit only in manual mode, switch off
the automatic mode via
Menu>Settings>1. Select modes.
3.4.2 Adjust the strength of the air curtain
Adjust the automatic strength control
In automatic mode, the strength and temperature of the air stream are controlled automatically. Due to weather conditions, you might want to adjust the automatic setting. If you feel a cold draught along the floor, you can increase the automatic strength.
Note:
n The adjustment of the automatic strength is not always
directly translated into a different fan speed.
Manual setting of the strength
With the manual setting, you have 6 strengths to chose from. To achieve maximum climate separation with minimum energy consumption, Biddle recommends to select the lowest strength at which no draught occurs. This setting may need to be changed during the day.
3.4.3 Recommended setting of the air curtain
To obtain the maximum separation effect and the greatest comf
ort possible with the least possible energy consumption,
Biddle recommends use of the fully automatic CHIPS control.
3.4.4 Controlling the temperature
You can set the temperature to a comfortable level. This is the temperature at the air curtain.
With units connected to a Daikin system (CA
2
V and CA2 Q), the temperature control is less accurate than with water or electric heating.
MANUAL OPERATION
Version: 6.1 (05-12-2011) 39
3.5 Faults
ä
The symbol ä indicates that there is a fault. The fault message is displayed alongside.
Touch this message for further inf
ormation on the fault and
for instructions as to how to react.
Warning:
w Some faults may cause damage or danger for
persons if they are disregarded. If ä is displayed,
f
ollow the instructions as to how to react shown on
the operating panel.
Note:
n The symbol ä and the fault message remain displayed as
long as the fault has not been remedied.
If a fault has remedied itself, a corresponding message will be displa
yed. Touch this message to display the
Error history and
to read out the last five faults and the times of their occu
rrence. This list can also be read out by touching
Menu>Maintenance>Error history.
3.6 Main menu
To u c h Menu to call up the main menu. Here you can set up a number of frequently occurring functions and make settings in sub-menus to adapt the function of the air curtain to your specific situation.
To u c h
Home to return to the Home screen again.
v and x allow you to scroll through the list.
If the control panel is not operated for some time, it returns autom
atically to the Home screen without saving the changes.
Lock the screen Select
Lock screen to prevent unauthorised access. The # icon
appears on the screen
Unlocking
Touch the screen for 5 seconds to unlock.
OPERATION COMFORT AIR CURTAIN
40
Switching the heating ON and OFF
The heating of the air curtain can be switched ON and OFF manually. This can be useful in summertime when no heating is necessary.
Switching the heating OFF disables
the room temperature
control.
This function can be deactivated via setting 89
in the
configuration menu.
•Select
Heating to switch the heating ON and OFF. When
the heating is switched off, the air stream is displayed in blue.
The heating can also be switched off b
y an external signal at
the input of the unit, see
menu>Configuration>60. Function of
input
, setting Heating OFF.
Filter Dirty filters reduce the effectiveness of the air curtain. It is
ther
efore necessary to clean or replace the filters at regular intervals. The service life of the filter is calculated in relation to the use of the air curtain. You can adjust this by setting the maximum service life of the filter.
When the maximum service life is reached, a message appears on the
Home screen.
You may clean the filter with, for instance
, a vacuum cleaner,
see section
Maintenance. After some cleanings, however, the
filter must be replaced. New filters are available from Biddle.
When using long-life filters:
The service life of the filter m
ust be set to the maximum
value.
Cleaning the screen The use of the touchscreen can lea
ve marks or fingerprints on
the screen. The screen can be cleaned using a damp, soft cloth.
Timer The b-touch control panel has a week timer. You can set two
star
t and stop times for every day of the week. The unit is on between the start time and the stop time. The second start and stop times are optional.
When the button
ON/OFF is displayed on the screen, the unit
can also be switched ON or OFF manually. From the next switching moment the unit then follows the timer again.
MANUAL OPERATION
Version: 6.1 (05-12-2011) 41
When the timer is switched on, the @ icon is displayed in the blue bar of the Home screen.
3.7 Preferences
The menu Preferences allows you to make settings for the use of the control panel.
Set language You can select a language for the control panel. Select the
desired language from the list.
Set date and time The date and time are necessary for the timer function and in
order to track usage statistics of the unit.
The automatic summer time function switches the clock to summer or winter time according to the applicable European rules. If you do not use this function, you can switch to summer time manually. The clock is then set one hour forward.
Display brightness Set the brightness of the display according to your personal
preference or according to the circumstances.
3.8 Settings
The menu Settings allows you to make setting which influence the day-to-day use of the unit.
1. Select modes The operating panel offers various operating modes. The function Select modes allows you to choose which of these modes can be selected on the HOME screen.
5. Room temperature The default room temperature is the temperature setting at every start-up of the unit.
This can be overruled manually.
6. Minimum air temperature Set the minimum difference between the room temperature and the discharge temperature.
This difference can be increased for more comfort. A small difference saves energy.
OPERATION COMFORT AIR CURTAIN
42
9. Calibration An unfavourable position of the operating panel or using the
temperature sensor in the air curtain can be the reason why the temperature displayed differs from the real temperature.
Use this function to adjust the temperature reading.
11. Standard settings Restores the standard factory settings. The settings made in the
Configuration menu are retained.
3.9 Configuration
The Configuration menu allows you to make settings to adjust the operation of the unit to the room and the system. Usually, this level is used only for installation, maintenance and service purposes.
50. Access protection Access to the whole operating panel or only to the menu can be protected with a four-digit PIN code.
The default PIN code is 0000.
51. Indoor sensor Both the unit and the operating panel have a sensor which measures the indoor temperature. Choose one that the system is to use:
Select the sensor on the unit for automatic control. This is
the standard setting.
Select the sensor on the control panel if you also wish to
use the air curtain for heating the room. In this case comfort may be reduced by draughts along the floor.
52. Function of ON/OFF button The unit can be switched ON and OFF manually. It can also be switched ON and OFF via the internal timer or via an external release signal at the input of the operating panel or of the unit. In this case you can disable the manual switching ON and OFF. The
ON/OFF button is then not displayed on the Home screen.
53. Control panel input The control panel has one input signal interface. This can be used for an external ON/OFF signal or for an additional temperature sensor.
When the timer is in use, the ON/OFF function of the input of the control panel is deactivated, irrespective of this setting.
If an additional temperature sensor is connected, this takes over the function of the sensor in the control panel.
MANUAL OPERATION
Version: 6.1 (05-12-2011) 43
See also section 2.8.
54. Strength with door closed Set the minimum fan speed when contact is made with the input. Use a door switch here to reduce the fan speed when the door is closed.
This has an effect only when function 60. Function of input is set to Quick speed up or Slow speed up.
55. Winter setting door If the difference between the desired and the actual room temperature is larger than this value, contact is made. An automatic sliding door can then be set to half open.
This has an effect only when function 61a/b. Function of output
1/2 is set to Winter setting door.
58. Maximum strength The maximum fan speed can be limited in order to limit the noise level. This function has an effect only in Automatic mode.
Use of this function can reduce the comfort.
60. Function of input The unit has one input which can be used to have a function controlled by an external accessory such as a door switch, thermostat or a signal from a building management system (BMS).
If several units are connected to one control panel, only one input can be used. The effect of this input is then the same for all the units.
The function Unit OFF locally has an effect only on the units whose inputs are in use.
When the timer is in use, the function All units ON/OFF of the input on the unit is deactivated, irrespective of this setting.
With the setting All units OFF and with the NC (normally closed) settings, a jumper must be laid to the input for all the other connected units.
See also section 2.8.
61a/b. Function of output 1/2 The unit has an interface for two output signals: These can be
used, for example, for controlling the central heating or cooling system, or for transmitting status reports to a BMS.
The outputs function independently of one another.
OPERATION COMFORT AIR CURTAIN
44
Multiple units operated from one control panel
The outputs always have a global effect: The signals are always the same in all units connected to the control panel.
See also section 2.8.
69. Temperature display The room temperature is displayed as default. With this function you can select another temperature to display or switch off the temperature display.
72. Error output Some fault messages may be caused by external factors such as the central heating system and do not necessarily have an influence on the function of the air curtain.
Use this function to suppress these messages. Messages concerning safety are always displayed.
76. Release delay When you are using an input, you can allow the effect of an incoming signal to continue for some time after the signal has passed (releasedelay').'
This setting can be used, for example, in combination with a door switch to allow the unit to continue to run for a short time after the door has been closed.
77. Valve open When the unit is switched off, the valve in the unit is closed by default.
Select Valve open and set the opening percentage of the valve to always keep a flow over the heat exchanger into the unit.
80. Fan OFF temperature When there is only a small difference in temperature between outdoors and indoors, there is less need for a climate separation. In order to save energy, the fans can be switched off when there is only a small difference in temperature.
Set this value to zero to allow the fans to run at all times.
x
h
b
MANUAL OPERATION
Version: 6.1 (05-12-2011) 45
82. Installation height
In order to use the automatic control as efficiently as possible and with minimum energy consumption it is necessary to set the installation height of the air curtain correctly.
If there is a continuously large draught through the door, this value can be
increased in order to adapt the strength of the air
curtain.
The installation height is the distance
h between the floor and
the underside of the discharge grille.
84. Heating off temperature If the outdoor temperature rises ab
ove this setting, the
heating of the air curtain is switched off.
A higher value offers greater comfort, a lower value saves en
ergy.
88. Outdoor temperature The default outdoor temperature is used if
an outdoor sensor
is not connected to a unit or has not been recognised.
Caution:
c The automatic control is less efficient without an outdoor
sensor.
89. Heating off option Use this function to switch on or off the possibility for the user to
switch the heating ON or OFF manually.
3.10 Maintenance
The Maintenance menu contains information on the use of the unit and offers a number of functions which are necessary for remedying faults.
Status Provides information on the operation of the unit.
Current error messages Gives an overview of current errors. The error messages can
also be
deleted here.
Error history Gives an overview of the last five errors which have occurred.
OPERATION COMFORT AIR CURTAIN
46
Installation guide This guides you through the most frequently required settings.
Unit code For the input of the unit code after replacement of a printed
cir
cuit board in a unit.
Standard settings Restores the standard factory settings. The settings made in
th
e Configuration menu are retained.
Factory configuration Restores the standard factory configuration. All settings are
th
en lost.
Reset control panel The control panel searches for connection to the connected
units
again.
Use this function when remedying faults and during connection
or disconnection of units.
3.11 USB
The control panel has a USB port to which only a USB flash drive can be connected. This is used for
Updating the software
Importing and exporting settings
Exporting of operating data
This menu is automatically activated when a USB flash drive is connected. Th
e menu is closed again when the USB flash drive
is disconnected.
Caution:
c Do not remove the USB flash drive during updates or
during the import or export of data.
Warning:
w Connection of other electronic devices to the USB
port can cause serious damage to the control panel
or to other electronic components.
Software update Biddle is working continuously on improving its products and
r
ecommends that you update the software of the control panel when updates become available. Consult the Biddle website for availability.
MANUAL OPERATION
Version: 6.1 (05-12-2011) 47
The installed version of the software can be read out with
Maintenance>Status.
Download the latest version of the software via the Biddle website.
Export/import settings For copying settings between control panels.
Export log ......... The Export log functions write data on the operation of the
air curtain to the USB flash drive. These data can then be analysed on a computer.
MAINTENANCE COMFORT AIR CURTAIN
48
4. . Maintenance
4.1 Replacing or cleaning the filter
4.1.1 Introduction
Dirty filters reduce the effectiveness of the air curtain. It is ther
efore necessary to clean or replace the filters at regular intervals. The service life of the filter is calculated in relation to the use of the air curtain. You can alter this by setting the maximum service life of the filter.
You may clean the filter with, for instance
, a vacuum cleaner. After a few cleanings, however, the filter must be replaced. New filters are available from Biddle.
4.1.2 Cleaning the filter
1. Select
Menu>Filter>Clean filter on the control panel.
2. Wait until the fans have stopped and the heat exchanger
has cooled do
wn.
3. Clean or replace the filters
4. Select OK on the control panel when you have finished
cle
aning or replacing the filters.
The service life of the filters is then reset to zero.
4.1.3 Removing the filter
Free-hanging models
1. Remove the inlet grille from the unit:
- Lift the grille at the bottom and unhook it.
MANUAL MAINTENANCE
Version: 6.1 (05-12-2011) 49
2. Remove the aluminum grille from the inlet grille:
- Slide the grille upward.
- Tilt the grille a little up.
- Remove the aluminum grille from the grille.
3. Clean or replace the filter.
correct
wrong
Note:
n When putting the grille back:
Ensure you put it back correctly into the inlet grille.
1
1
Recessed and cassette models
1. Open the inlet grille:
- Push the two pins 1 in the grille towards one
another
: The grille will tilt down.
2. Slide the filter out of the grille.
3. Clean or replace the filter.
1
1
Long-life filter in free-hanging models
1. Remove the inlet grate from the unit:
- Lift the grate at the bottom and unhook it.
2. Loosen the screws 1.
2
3
3
3
4
5
MAINTENANCE COMFORT AIR CURTAIN
50
3. Remove the filter module 2 from the inlet grate.
4. Remove the filter from the filter module:
- Loosen the screws 3.
- Remove the strip4.
- Do the same on the other side of the module.
- Take out the filter material 5.
5. Clean or replace the filter.
6. Mount all components in reverse order to the dismantling.
1
1
2
2
Long-life filter in recessed and cassette models
1. Take the inlet grille out of its frame:
- Push the two pins 1 in the grille towards one
an
other:
The grille will tilt down.
- Push the two pins (at 2) towards one another and take
the gril
le out.
3
4
4
3
3
4
3
2. Loosen the screws 3 and remove the strips 4.
3. Slide the filter out of the grille.
4. Clean or replace the filter.
5. Mount all components in reverse order to the dismantling.
4.2 Cleaning the unit
You may clean the exterior of the unit with a damp cloth and a domestic cleansing agent. Do not use any solvents.
Caution:
c Make sure no water runs into the unit.
MANUAL MAINTENANCE
Version: 6.1 (05-12-2011) 51
4.3 Scheduled maintenance
Biddle recommends that the following inspection and maintenance work is performed by an installer or other technical expert every year.
Check if the filter is clean enough and undamaged. Replace the filter if necessary (see section
4.1).
Check that the heat exchanger or the electric heating elements are clean. Settled dust may cause unpleasant smells.
Gently remove dust with a vacuum cleaner.
Caution:
c The fins of the heat exchanger are delicate parts.
Warning:
w The fins of the heat exchanger are sharp.
Check the operation of the fans.
Check if the control panel has stored any error messages (see section
5.3).
FAULTS COMFORT AIR CURTAIN
52
5. . Faults
5.1 Safety instructions
Danger:
d Work on the unit’s interior shall be performed by
qualified technical staff only.
Warning:
w Before opening the unit: Observe the safety
instructions in section
1.5.
5.2 Resolving simple problems
If you suspect a fault, first try to resolve the problem using the below table. You need not be an expert for this.
PROBLEM LIKELY CAUSE WHAT TO DO
The unit does not work, and the control panel display is blank.
The unit is switched off. Activate the display by touching.
No power supply to the control panel.
Check the power supply:
• plug in power point;
• isolation switch;
•unit live.
The display is on, but does not react to touch.
If the # symbol is shown on the display: The display is locked.
Touch the screen for 5 seconds to unlock.
The air curtain is switched Off but is still working.
Only electrically-heated models: unit is cooling down automatically.
This is not a fault. Normally, the unit will automatically shut down within 10 minutes.
The unit blows out cold air (without fault message).
If the air current on the display is blue: Heating is switched off.
Switch the heating on via
Menu>Heating
The discharge temperature is dependent on the indoor and outdoor temperature
This is not a fault. If this is considered a problem, the value of function
84. Heating off
temperature
can be increased.
The unit is on but the fans are not running.
The fans may be switched off if there is only a small difference in temperature between indoors and outdoors.
This is not a fault. If this is considered a problem, the value of function
80. Fan off
temperature
can be set to zero.
MANUAL FAULTS
Version: 6.1 (05-12-2011) 53
5.3 Fault messages in control panel
5.3.1 Reading out faults
Current faults
ä
Current faults are displayed on the Home screen. If a fault has remedied itself, a corresponding message will be displayed.
When the error message is touch
ed, an explanation of the actions to be taken appears on the screen. The message disappears from the Home screen only when the fault has been remedied.
There may be more than one fault at the same time. You can r
ead out a list of current error codes via
Menu>Maintenance>Current faults.
No-longer-current faults
If a fault has remedied itself, a corresponding message will be di
splayed. Touch this message to display the
Fault history and to
read out the last five faults and the times of their occurrence.
The display flickers The power supply is too low or
not cons
tant
Reduce the brightness of the display to a level at which flickering no longer occurs
The length of the control cable betw
een control panel and the
first unit is too long
Remove unnecessary cable length
For units connected to a Daikin system CA
2
V and CA2 Q:
The buttons
and on the Daikin control panel do not fu
nction.
These buttons have no function. The air curtain is operated with
the Bid
dle b-touch control panel.
The air curtain discharged unheated air
.
A fault has occurred in the Daikin system
Check the settings on the Daikin control panel.
The Daikin system has au
tomatically switched the
heating off.
Check the settings on the Daikin contr
ol panel.
The air curtain discharges unheated or cold
air, or does not function, and the Daikin control panel shows
.
The Daikin system is operating in defr
ost mode. This takes 5 to 10
minutes.
Wait until defrosting has been completed.
P
ROBLE M LIKELY CAUSE WHAT TO DO
FAULTS COMFORT AIR CURTAIN
54
This list can also be read out via Menu>Maintenance>Fault
history
.
This message disappears when touched or when the unit is switched on again.
5.3.2 Deleting faults
Most fault messages will disappear automatically when the problem is resolved. Certain faults have to be remedied, however, by deleting the error message via
Menu>Maintenance>Current faults.
5.3.3 Reconfiguring the control panel
Some faults can be remedied by reconfiguring the control panel via
Menu>Maintenance>Reconfigure: The panel then
searches for connected units again.
All settings are retained.
5.4 Remedying faults with error message
Try to remedy faults that come with an fault message using the below table. No technical expertise is needed for this.
CODE LIKELY CAUSE WHAT TO DO
E1 The control panel does not
communicate with one or more connected units.
This fault may occur:
• when a connected unit is removed or replaced;
• due to a short failure in the power supply to a connected unit;
• due to incorrect cabling;
• due to a defect.
1. Reset the control panel (see section 5.3.3).
2. Check if power is supplied to all connected units.
3. Check if the dummy plug is present in the connector
plate of the last connected unit.
4. Check the control cables:
- are they connected and free from breaks?
- are they stretched out or rolled up neatly?
- are they shielded from magnetic fields?
5. Check printed circuit board fuse F2 in all connected units.
6. Check wiring between connector plate and connectors X380 and X390 on the printed circuit board.
MANUAL FAULTS
Version: 6.1 (05-12-2011) 55
E2 Units that have a not allowed or
unknown unit code, or a not allowed combination of unit codes, are connected.
1. Check and compare the unit codes on the type plate (see sections
1.4.4 and 2.8.1).
The control panel software is outdated.
1. Check the version number of the software (
Menu>Maintenance>Status).
The control panel is live but does not communicate with any unit.
1. Reset the control panel (see section 5.3.3).
2. Check the control cables:
- are they connected correctly and free from breaks?
- are they stretched out or rolled up neatly?
- are they shielded from magnetic fields?
3. Check wiring between connector plate and connectors X380 and X390 on the printed circuit board.
E3 Electrically-heated models:
The control in the unit detected a too high temperature, and switched the heating off, or the temperature sensor (PTC) does not work.
If you disregard this fault,
damage to the unit may occur.
1. Delete the fault message (see section 5.3.2).
2. Check the fans. If one or more fans do not work,
check:
- the fan wiring;
- the connections on the printed circuit board (connectors X130, X120 and X110);
- the transformer fuse;
- the transformer itself.
If these are OK: Replace the fan.
3. Check the PTC wiring and connection. If these are OK: Replace the PTC.
E4 Electrically-heated models:
The high-limit thermostat switched the unit Off: this is to protect against overheating.
This fault may occur:
• if the unit has been temporarily dead, e.g., due to a power failure;
• if the filter is dirty and lets insufficient air through.
In other cases, there may be a
serious defect that may pose a
risk to persons.
1. Delete the fault message (see section 5.3.2).
2. Check the fans. If one or more fans do not work,
check:
- the fan wiring;
- the connections on the printed circuit board (connectors X130, X120 and X110);
- the transformer fuse;
- the transformer itself.
If these are OK: Replace the fan.
3. Check the filter for contamination. Clean or replace it if necessary.
Contact Biddle if this fault occurs more often.
CODE LIKELY CAUSE WHAT TO DO
FAULTS COMFORT AIR CURTAIN
56
E5 Electrically-heated models:
Heating does not stop because of a faulty relay.
This may be a serious defect
that may pose a risk to persons.
1. Delete the fault message (see section 5.3.2).
2. Switch the power supply to the unit Off and On.
3. Let the air curtain work for some time with the
heating disabled (see section
3.6) and check if the
discharged air stays cold.
A dangerous defect is concerned if:
- heating yet continues;
- this fault message returns within 30 minutes;
- this fault occurs frequently.
In any such case, act as follows:
- disconnect the unit from the power supply immediately.
-contact Biddle.
E6 For water-heated models:
Risk of freezing because discharge air temperature is too low. Frost protection has been activated (see section
2.5.2).
Freezing may cause damage to
the heat exchanger.
1. Ensure that the temperature in the room gets higher
than 8
ºC.
2. Follow the instructions for fault code F3.
You can avoid this fault by having the central heating system switched on by the unit in the event of a frost risk (Set function
61a/b. Function of output to Frost protection).
E7 No air flow.
The unitselectricheatingwillbeswitchedof f.'
1. Delete the fault message (see section 5.3.2).
2. Check the fans. If one or more fans do not work,
check:
- the fan wiring;
- the connections on the printed circuit board (connectors X130, X120 and X110);
- the transformer fuse;
- the transformer itself.
If these are OK: Replace the fan.
F1 Fault in air valve. 1. Delete the fault message (see section 5.3.2).
2. Change the heating strength using the control panel, and check if the air valve can move.
3. Remove any obstacles from the air valve’s range.
4. Check that the unit is not switched on at the power
supply source (if the unit is switched on at the power supply source, this can damage the valve drive)
5. Check wiring and connectors X140 and X210.
6. Replace the valve drive.
CODE LIKELY CAUSE WHAT TO DO
MANUAL FAULTS
Version: 6.1 (05-12-2011) 57
F2 For water-heated models:
Overheating.
This fault may occur if the control valve does not work correctly.
1. Switch the air curtain Off using the control panel, wait for one minute, and switch it On again.
2. Check that the connections of the supply and return pipes have not been interchanged.
3. CA S/M: Check the LED on the valve drive: it should come on when the unit is switched Off and On using the control panel.
4. Check the wiring and connectors of the valve drive (X230) and the discharge air temperature sensor (X350).
5. Take the drive from the valve, and check the interior for mechanical operation and defects.
F3 For water-heated models:
The central heating system switches on later than the unit.
Yo u m a y :
• switch on the central heating system earlier;
• have the central heating system switched on by the unit (Function
61a/b Function of output to Heating ON);
• switch off this error message at installer level (Function
72. Set error display to disable).
For water-heated models:
Underheating.
This fault may occur:
• if not enough hot water is supplied;
• if the control valve does not work correctly.
1. Check the central heating system:
-is it turned on?
- is it able to supply enough hot water?
2. Check if the entire heat exchange element gets hot: if not, vent it.
3. CA S/M: Check the LED on the valve drive: it must come on when a higher or lower heating strength is being set.
4. Check the wiring and connectors of the valve drive (X230) and the inlet air temperature sensor (X360).
5. Take the drive from the valve, and check the interior for mechanical operation and defects.
Electrically-heated models:
There is too little heating because one or more heating elements do not work.
1. Check the mains fuses.
2. Check the wiring and connections of the heating
elements, using the wiring diagram as a reference.
If they are OK, a relay is defective: contact Biddle.
F3 For all models:
If the fans do not revolve:
1. Delete the fault message (see section 5.3.2).
2. Check the fans. If one or more fans do not work,
check:
- the fan wiring;
- the connections on the printed circuit board (connectors X130, X120 and X110);
- the transformer fuse;
- the transformer itself.
CODE LIKELY CAUSE WHAT TO DO
FAULTS COMFORT AIR CURTAIN
58
5.5 Remedying faults without message
If you suspect a fault but no fault message is displayed:
1. Using section 5.2, check if you can easily resolve the problem.
2. Try to resolve the problem using the below table. Technical expertise is required for this.
F4 The temperature sensor in the
control panel is defective.
The room temperature control is now based only on the sensor at the unit’s air inlet.
Replace the control panel if you wish to have the room temperature controlled with the sensor in the control panel (if function
51. Indoor sensor is set to Control panel).
F5 The temperature sensor in the
discharge section does not work.
1. Check the sensor’s wiring and connection (connector X350).
2. Replace the sensor.
F6 The temperature sensor in the inlet
section does not work.
1. Check the sensor’s wiring and connection (connector X360).
2. Replace the sensor.
F8 Air flow sensor is defective. 1. Delete the fault message (see section 5.3.2).
2. Check the wiring of the air flow sensor and the connection of the sensor (connector X370).
3. Replace the sensor.
CODE LIKELY CAUSE WHAT TO DO
PROBLEM LIKELY CAUSE WHAT TO DO
The control panel works normally but the unit does not respond.
The unit is controlled by a signal from an external control.
1. Check the functions 60. Function of input and 76.
Release delay
in the menu Configuration.
The fans may be switched off if there is only a small difference in temperature between indoors and outdoors.
This is not a fault. If this is considered a problem, the value of function
80. Fan off temperature can be
set to zero.
The fans are dead. 1. Check the transformer fuse.
2. Check the wiring between the transformer and the fans (connectors X120 and X130).
3. Replace the transformer.
MANUAL FAULTS
Version: 6.1 (05-12-2011) 59
The unit is not functioning, the display is black and does not react to touch.
The unit is dead. 1. Check the power connections and wiring.
The connection between the control panel and the printed circuit board is not correct.
1. Check the control cable.
2. Check wiring between connector plate and
printed circuit board (connectors X380 and X390).
The printed circuit board does not work: the LEDs on the printed circuit board are not lit.
1. Check fuse F2.
2. Check the power supply cable (connector
X110).
3. Replace the printed circuit board.
The control panel is defective.
1. Check the control panel by connecting it to another unit with another cable. Replace the control panel if it does not work.
One fan does not work.
The fan is dead or defective. 1. Check the wiring of the fan.
2. Check the transformer fuse.
3. Replace the fan.
The fans do not operate at a certain strength.
The connection to the relevant tap is not correct.
1. Check the transformer connections.
2. Check connector X130.
For units connected to a Daikin system CA2 V and CA2 Q:
The display of the Daikin control panel is blank.
No power supply to the connected unit.
1. Check the power supply.
2. Consult the installation manual of the control
panel.
3. Contact the supplier.
Poor connection to the control panel.
The Daikin electronics in the air curtain are defective.
The Daikin control panel signals a fault (flashing LED and/or error code).
Daikin electronics in the unit or outdoor unit detects a fault.
1. Consult the service manual of the outdoor unit.
2. Contact the supplier.
The unit constantly discharges cool air and/or condensation drips from the unit.
There is a fault in the air curtain.
Warning: This situation
can result in danger and/
or damage.
1. Switch off the whole system immediately.
2. Contact the supplier.
PROBLE M LIKELY CAUSE WHAT TO DO
SERVICE COMFORT AIR CURTAIN
60
6. . Service
6.1 Safety instructions
Danger:
d Service on the unit may be performed by qualified
technical staff only.
Warning:
w Before opening the unit: Observe the safety
instructions in section 1.5.
6.2 Access to the interior of the unit
For all models
1. Switch the unit OFF using the control panel.
Warning:
w Disconnect the power supply (remove plug from
power point or move isolation switch to OFF).
For free-hanging models
2. Remove the inlet grilles from the unit:
- Lift the grille at the bottom and unhook it.
1
1
2
2
For cassette models
1. Take the inlet grille out of its frame:
- Push the two pins 1 in the grille towards one
an
other:
The grille will tilt down.
- Push the two pins at 2 towards one another and take
the gril
le out.
3
3
MANUAL SERVICE
Version: 6.1 (05-12-2011) 61
2. Loosen screws 3 and remove the frame.
1
1
1
1
For all models
3. Remove the inspection panel:
- Remove the screws 1.
- Pull the panel a little forward and take it away.
Caution:
c The whole panel will come loose when you pull it forward:
Take care it does not fall down.
Warning:
w When replacing the inspection panel, always attach
it using flanged bolts with milled edges: These are
needed for the earth connection.
6.3 Electronics module
6.3.1 Introduction
The unit contains one electronics module. It includes:
-the transformer;
- the printed circuit board;
- the connector plate;
- the fuses.
SERVICE COMFORT AIR CURTAIN
62
6.3.2 Removing the electronics module out
1. Switch the unit OFF using the control panel.
Warning:
w Disconnect the power supply (remove plug from
power point or move isolation switch to OFF).
1
2. Remove the inspection panel (see section 6.2).
3. Disconnect all unit-connected connectors and grounded conne
ctions from the printed circuit board.
4. Remove the screws 1.
5. Remove the electronics module.
6. Disconnect the connectors from the connector plate.
Note:
n The electronics module in your unit may look different
from the module illustrated opposite.
6.4 Daikin electronics (CA2 V and CA2 Q)
6.4.1 Introduction
In addition to the Biddle electron
ics, the unit also contains a
Daikin electronics module.
6.4.2 Access to the electronics in the unit
Warning:
w Before opening the unit:
Observe the safety instructions in section1.4.
1
3
2
All models
1. Remove the inspection panel 1 of the unit (see manual of the Air Cur
tain Model CA).
2. The Biddle electronics is located at 2.
3
2
MANUAL SERVICE
Version: 6.1 (05-12-2011) 63
Models with discharge width 150, 200 or 250
3. Remove cover 3. The Daikin electronics are located
behind this
cover.
4
Models with discharge width 100
4. Remove cover 4 on the side of the unit. The Daikin
electr
onics are located behind this cover.
6.5 Fuses
The unit has two fuses:
- Transformer fuse 1.
-Fuse 2 (F2) of the printed circuit board;
The values are indicated for the fuses.
For CA
2
V and CA2 Q only:
The Daikin electronics module has one extra fuse on the printed circuit board, indicated with F1U.
6.6 Removing the discharge section
The discharge section houses the air valve mechanism and drive.
For recessed models
1. Remove the discharge duct from the unit (see section 2.9.2).
SERVICE COMFORT AIR CURTAIN
64
For all models
1
2
2
1. Remove the inspection panel (see section 6.2).
2. The discharge section has the f
ollowing connections to the
electronics module (at 1):
- The valve drive connections on the printed circuit boa
rd (connectors X140 and X210);
- The earth connection.
Disconnect these connections.
3. Between the fins of the discharge grille
, there are 4 screws
(at 2): Loosen these.
Caution:
c Support the discharge section while loosening the screws.
4. The discharge section is now detached: Remove it carefully.
6.7 Venting the heat exchanger
1
For water-heated models only
The air relief valve 1 is located in the upper left of the unit.
6.8 Bleeding the heat exchanger
1
For water-heated models only
The drain plug 1 is located on the left of the unit.
MANUAL SERVICE
Version: 6.1 (05-12-2011) 65
6.9 Entering the unit code
6.9.1 Introduction
The unit code must be entered after replacing the printed ci
rcuit board in the unit. The unit code depends on the unit
type and is indicated on the type plate (see section 1.4.4.)
There are two methods for entering the unit code:
Directly via the control panel i
f one unit is connected;
Via the printed circuit board and the control panel if more th
an one unit is connected.
Warning:
w The input of an incorrect code will result in a poor
performance of the unit.
6.9.2 Entering the unit code via the control panel
Caution:
c Entering the unit code using this method functions only if
one unit is connected to the control panel. If necessary, connect the control panel separately to the unit in question.
1. Select
Menu>Maintenance>Unit code.
2. Enter the unit code via the control panel and press
OK.
The operating panel now searches for the unit again.
6.9.3 Entering the unit code via the printed circuit
board and the control panel
ê
1. Connect the power supply (insert plug into power point or move isolation switch to On).
Warning:
w Do NOT touch any live parts.
2. Press down the microswitch on the printed circuit board (at 3).
The LED next to the microswitch will start flashing.
The control panel displays four numbers: These represent th
e unit code.
3. Enter the unit code via the control panel and press
OK.
SERVICE COMFORT AIR CURTAIN
66
ê
4. Press down microswitch 1.
The LED next to the microswitch no longer flashes.
The unit code is now set.
5. Reset the control panel (see section 5.3.3).
6.10 Resetting the PIN code
The PIN code of the control panel can be reset using a USB flash drive:
1. Connect a USB flash drive to the control panel. The USB menu is activated
2. Press x for 10 seconds. The PIN code is reset and a new PIN code has to be ente
red.
3. Quit the USB menu by removing the USB flash drive.
6.11 Configuration of the Biddle control cable
The control cable for Biddle units is different from standard modular telephone cables.
The connectors are Type RJ-11, but the connections are s
traight. The core is connected to the same pin at both ends
of the cable.
Table 6-1 Colour codes of Bid
dle cables
P
IN COLOUR
165432
1 (not used)
2 black
3 red
4 green
5 yellow
6 (not used)
MANUAL DISMANTLING
Version: 6.1 (05-12-2011) 67
7 . . Dismantling
Dismantling the system, handling coolant, oil and other com­ponents should be performed by a
qualified engineer in com-
pliance with relevant local and national regulations.
Any used electrical/electronic devices must be handed in for pr
ocessing in compliance with EU regulations. By ensuring that this product is disposed of in the correct manner, you prevent any damage to human health and/or the environment. For more information about this subject, please contact your sup­plier or local government agency.
68
Copyright and trademarks
All the information and drawings in this manual are the property of Biddle and may not be used (other than for the actual operation of the device), photocopied, duplicated, translated and/or be brought to the attention of third parties without Biddle’s prior written permission.
The name Biddle is a registered trademark.
Warranty and Liability
Please refer to Biddle’s Terms of Sales and Delivery for warranty and liability conditions.
Biddle excludes liability for consequential loss at all times and under all circumstances.
Liability for the contents of this manual
However much care might have been taken in ensuring the correctness and, where necessary, completeness of the description of the relevant parts, Biddle disclaims all liability for damage resulting from any inaccuracies and/or deficiencies in this manual.
Should you detect any errors or ambiguities in this manual then
we would be pleased to hear from you: it helps us
to improve our documentation even further.
Biddle retains the right to change the speci
fications stated in this manual.
For more information
If you have any comments or questions about specific topics relating to this product, please do not hesitate to contact Biddle.
Address for the UK:
Bid
dle Air Systems Ltd.
St. Mary’s Road Nuneaton Warwickshire CV11 5AU United Kingdom
tel: 024 7638 4233 fax: 024 7637 3621
e-mail: sales@biddle-air.co.uk internet: www.biddle-air.com
Address for other countries:
Biddle bv
P. O . B o x 1 5 NL-9288 ZG Kootstertille The Netherlands
tel: +31 512 33 55 24 fax: +31 512 33 55 54
e-mail: export@biddle.nl internet: www.biddle.info
Loading...