biasi M90E.24S, M90E.28S, M90E.32S User guide

Page 1
User manual and Installation instructions
RIVA COMPACT
Models:
M90E.24S M90E.28S M90E.32S
Page 2
Page 3
Congratulations on your choice. Your boiler is electronically controll e d and has electronic ignition. The materials it is made of and the control systems it is equipped with give you safety, a high
Remember that...
n The manual must be read thoroughly, so
that you will be able to use the boiler in a safe and sensible way; must be carefully kept. It may be necessary for reference in the future.
n First lighting up must be carried out by
competent and responsible engineer.
n The manufacturer disclaim all liability for
any translations of the present manual from which incorrect interpretation may occur; cannot be held responsible for non---observ­ance of instructions contained in this manual or for the consequences of any procedure not specifically described.
Using the boiler...
n Before lighting the boiler,youaread-
vised to have a professionally qualified per­son check that the installation of the gas supply:
--- i s g a s --- t i g ht ;
---isofthecorrectgaugefortheflowtothe
boiler;
---is fitted with all the safety and control de-
vices required by the current Regulations;
Ensure that the installer has connected the pressure relief valve outlet to a drain pipe. The manufacturers are not responsible for damage caused by opening of the pressure relief valve and consequent escape of water, if not connected correctly to the drain.
n On detecting the smell of gas
--- don’t operate any electrical switches, the telephone or any device that may produce sparks;
--- open the windows and doors at once to create a draught of air which will purge the area;
--- shut off the gas cocks;
--- get the assistance of a qualified person.
n Do not touch the appliance with parts of
thebodythatarewetordampand/orbare feet.
n In case of structural work or mainten-
ance near the exhaust duct and/or fume ex­haust devices or their attachments, turn off the appliance. On completion of the work, have a professionally qualified person check their efficiency.
n Repairs (under guarantee) must be car-
ried out only by an approved engineer, using genuine spare parts. Thus do no more than switching off the boiler yourself (see the in­structions).
n Your boiler allows heating up of water to
a temperature less than boiling point;
--- must be connected to a central heating system and/or a hot water supply system, compatible with its performance and output;
--- can be used only for those purposes for which it has been specially designed;
--- must not be touched by children or by those unfamiliar with its operation;
--- must not be exposed to weather condi­tions.
Page 4
Safe handling of
substances
Biasi products are manufactured in accordance with ISO 9000 and do not, and will not, contain any hazardous materials or substances such as as­bestos, mercury or C.F.C.’s. The appliance packaging does not contain any substances, which maybe considered a hazard to health.
Combustion chamber panels
Material: mineral fibers
Known hazards --- Some p eople can suffer red­dening and itching of the skin. Fibre entry into the eye will cause foreign body irritation, which can cause severe irritation to people wearing contact lenses. Irritation to respiratory tract.
Precautions --- Dust goggles will protect eyes. People with a history of skin complaints may be particularly susceptible to irritation. High dust le-
vels are only likely to arise following harsh ab­rasion. In general, normal handling and use will not p resent high risk, follow good hygiene prac­tices,wash handsbefore, touching eyes,consum­ing food, drinking or using the toilet.
Firstaid ---Medicalattentionmustbesoughtfol­lowing eye contact or prolonged reddening of the skin.
Thermostat / Temperature gauge
Description --- Sealed phial and capillary contain­ing liquid.
Known hazards --- irritating to skin, eyes and throat. Vapour is harmful. Inflammable --- do not extinguish with water.
Precautions --- Do not incinerate. Avoid contact with broken/leaking phials. Do not purposely puncture.
Firstaidmedicalattentionmustbesoughtfollow­ing eyes/skin contact, wash with clean water.
Appliance category II Country of destination: United Kingdom (GB) Irealnd (IE)
This appliance conforms with the EEC directive90/396 and, consequently, it hasthe rightto makeuse of the brand name
Moreover,the appliance conforms with the EEC directive 87/308 relative to the prevention and elimina­tion of radio disturbances.
The appliance is built to complywith the regulationnow in force regarding gas appliance’s safety and the European regulation now in force relative to safety of household and similar electrical appliances.
The manufacturer, in the continuous pocess to improve his products, reserves the right to modify the data expressed in the present documentation at any time and without prior notice.
The present documentation is an informative support and it cannot b e considered as a contract to­wards third parties.
Gas G20 20 mbar, G30 29 mbar, G31 37 mbar
2H3+
Page 5
Boiler installation and commissioning tips
n The installation must be carried out by
a qualified person who will be responsible for observing the current Regulations.
Installing the boiler...
n Donotforgettoremovethetransitcaps
and plugs from the boiler connections these are fitted to every boiler.
n Keep the boiler clear of dust during in-
stallation and in particular do not allow any dust or debris to enter the top of the boiler where the flue connection is made. It is rec­ommended that you put a dust sheet over the top of the boiler until you are ready to make the flue connection.
n Because every boiler is fired and tested
live at the factory, a small amount of water re­mains within the boiler. It is possible for this water to initially cause the pump to seize. It is therefore recommended that the pump rotor be manually turned to free its rotation before turning the boiler on.
n Remember to release the auto air purge
before fillingthe boiler. See the instructions to identify the location of this device.
n Do not remove the cap of the pressure
test points of the air switch (top left side of the boiler).
n You are strongly advised to flush out the
system both cold and hot in order to remove system and installation debris.
n It is also sensible to initially fire and com-
mission the boiler before connecting any ex­ternal controls such as a room thermostat.By this method if you have a subsequent prob­lem following the addition of an external con­trol you can eliminate the boiler from your fault analysis.
n Donotforgettorangeratetheboilerto
suit the system requirements. This pro­cedure is covered in the commissioning sec­tion of the installation manual.
n If the boiler is fitted with a digital pro-
grammer, when setting the times for auto­matic operation, remember that for every “ON” time there must be an “OFF” time to fol­low and that on every occasion you enter a time you must also indicate which days that you want the boiler to follow the timed set­tings.
n Some products incorporate an anti cycl-
ing time delay. It is normal when first switch­ing the boiler on for the boiler to operate on heating for a few seconds then switch off. After 3 --- 4 minutes has elapsed the boiler will then re ignite and operate perfectly normally. The ignition delay cycle does not prevent normal operation of the boiler to provide d.h.w.
n If you are in any doubts as to the installa-
tion or operation of the boiler please read the instruction manuals thoroughly and then if necessary contact Biasi UK for advice and assistance.
Please remember that if you are in any doubt about the installation of this product you can contact our Technical Helpline on tel. 0121 506 1350
Page 6
TABLE OF CONTENTS
1 Appliance description 1..........
1.1 Overview 1......................
1.2 Control panel 1..................
1.3 Isolation valves 1.................
USE
1.4 Technical data 1.................
2 Instructions for use 2............
2.1 Warnings 2......................
2.2 Refilling procedure 2..............
2.3 Ignition 3........................
2.4 C.h. circuit temperature 3..........
4 Technical information 11..........
4.1 Overview 11......................
4.2 Main diagram 12..................
4.3 Hydraulic specifications 13.........
4.4 Expansion vessel 13...............
4.5 Technical data M90E.24S 14........
4.6 Technical data M90E.28S 16........
4.7 Technical data M90E.32S 18........
INSTALLATIONMAINTENANCE
5 General requirements 20..........
5.1 Related documents 20.............
5.2 Location of appliance 20...........
5.3 Flue system 20....................
5.4 Gas supply 21....................
5.5 Air supply 21.....................
5.6 Ventilation 21.....................
5.7 Water circulation (c.h.) 21...........
5.8 Domestic water 22.................
5.9 Water treatment 22................
5.10 Electrical supply 22................
6 Installation 24....................
6.1 Warnings 24......................
6.2 Precautions for installation 24.......
2.5 D.h.w. temperature 4..............
2.6 Extinguishing 4..................
2.7 Built in time switch A 5............
2.8 Built in time switch B 7............
3Usefuladvice 9.................
3.1 Central heating 9.................
3.2 Frost protection 9................
3.3 Periodic maintenance 9...........
3.4 External cleaning 9...............
3.5 Operational faults 9...............
6.3 Installing the bracket 24............
6.4 O verall dimensions 25.............
6.5 Joints 25.........................
6.6 Mounting the boiler 25.............
6.7 Fitting the flue system 26...........
6.8 Flue restrictors 26.................
6.9 Choice of flue 26..................
6.10 Electrical connections 28...........
6.11 External frost protection 30.........
7 Commissioning 31...............
7.1 Electrical installation 31............
7.2 Gas supply installation 31..........
7.3 Filling the d.h.w. system 31.........
7.4 Initial filling of the system 31........
7.5 Lighting the boiler 32..............
7.6 C hecking the gas pressure
at the burner 32...................
7.7 Adjusting the burner ignition 33.....
7.8 Adjustment of useful c.h. output 34..
7.9 C hecking the ignition device 36.....
7.10 Checking the flue system 36........
7.11 Instructing the user 36.............
8 Gas conversion 37...............
8.1 Warnings 37......................
8.2 Procedures 37....................
9 Maintenance 39..................
9.1 Warnings 39......................
9.2 Dismantling the external panels 39...
9.3 Emptying the d.h.w. system 39......
9.4 Emptying the c.h. system 39........
Abbreviations used in the manual C.h. = Central heating D.h.w. = Domestic hot water D.c.w . = Domestic cold water
9.5 Combustion analysis check 40......
9.6 Cleaning the primary
heat exchanger 40................
9.7 Checking the pressurisation
in the expansion vessel 41..........
9.8 Cleaning the burner 41.............
9.9 C hecking the flue 41...............
9.10 Visual inspection of appliance 41....
9.11 Gas pressures and soundness 41...
Page 7
1 APPLIANCE DESCRIPTION
1.1 Overview
1
2
3
Fig. 1.1
1 Case front panel
2 Control panel
3 Control panel cover
1.2 Control panel
4 C.h. circuit temperature and pressure gauge
5 Time switch (c.h. control)
6 Lock---out signal lamp
7 Lockout reset button
8 Function selector and c.h. temperature control
knob
9 D.h.w. temperature control knob
10 Appliance operation light
1.3 Isolation valves
13 1115 1214
Fig. 1.2 (bottom view of the boiler)
11 C.h. return valve
12 D.c.w. inlet valve
13 Gas inlet valve
14 D.h.w. outlet pipe
15 C.h. flow valve
1.4 Technical data
For detailed technical data see section 4.5 or 4.6 of this manual.
USE
10 89 7 6 45
Fig. 1.3
1
Page 8
2 INSTRUCTIONS FOR USE
2.1 Warnings
Biasi UK Ltd support the Benchmark initiat­ive. T he Benchmark Log Book is located at the back of this manual and should be com­pleted by the Installing/Commisssioning Engineer and handed over to the User for
USE
future reference by other visiting En­gineers. Also included is the Service Inter­valRecordcardthatshouldbecompleted by the Service Engineer following the an­nual service maintenance of the boiler and system.
All CORGI Registered Installers carry a CORGI ID card, and have a registration number. Both should be recorded in your Benchmark Log Book. You can check your installer is registered by calling CORGI di­rect on 01256 372300.
In order to guarantee safety and correct oper­ation, it is essential that all the tests are carried out by a competent and responsible service engineer before lighting up the boiler.
The tests are described in the installation in- structions in section 7 commissioning.
Ensure that the c.h. circuit is regularly filled with water (even if the boiler is only used for d.h.w. supply)checking that the pressure indi­cated on the temperature and pressure gauge 4 is not lower than that shown in Fig. 2.2.
If the pressure reading on the pressure gauge is below that shown in Fig. 2.2, then the system will require topping up. A filling loop is normally provided by the installer for this purpose.
If you are in any doubt regarding this pro­cedure you are advised to contact your In ­staller or an Approved Engineer.
This appliance is provided with a built in anti--­freeze system that operates the boiler when the temperature is below 4 ˚C Therefore, when the boiler is not lit or used in cold weather, with consequent risk of freezing
do not switch off the boiler at the fused spur isolation switch or close the gas inlet cock.
When you do not expect to use the boiler for a long period and the boiler is not to be used for frost protection then follow the instructions giveninsection2.6onpage4.
2.2 Refilling procedure
1 Isolate the boiler from the electrical supply at
the fused spur. Reconnect the filling loop as demonstrated in Fig. 2.1.
Control valve
Double check valve
Te m p o r a ry connection
Supply pipe
(cold wa ter inl et)
C.h. return pipe
Fig. 2.1
2 Open the valves of the filling loop and watch
the gauge until it reaches normal filling pres­sure as shown in Fig. 2.2.
Fig. 2.2
3 Close the valves and remove the filling loop.
If you experience any difficulty with the oper­ation of the boiler, switch off the boiler immedi­ately at the fused spur isolation switch and contactyourInstalleroranapprovedService Engineer
Air introduced into the boiler during this fillingpro­cess will vent through the automatic air purger fitted to the boiler. You may also find it necessary to vent air from your radiator circuit using your radiator key, however be aware that excessive venting will cause the pressure in the system to drop.
Always ensure that the pressuregauge is set at the required pressure.
Control valve
4
Normal filling pressure
2
Page 9
Instructions for use
2.3 Ignition
1 C heck that the valves located in the lower part
of the boiler are open (Fig. 2.3).
Open position
Fig. 2.3
2 Turn on the electricity supply to the boiler,
switching on the fused spur isolation switch. The appliance operation light 10 (Fig. 2.4) will flash every 4 seconds (stand---by condition).
3 If theboiler is to be used for c.h. and d.h.wposi-
tion the function selector 8 as in Fig. 2.4. The appliance operation light 10 will flash every 2 seconds (operating boiler).
810
2.4 C.h. circuit temperature
The output temperature of c.h. water is adjustable from a minimum of about 38°C to a maximum of about 85°C (Fig. 2.6), by turning the function se­lector (8).
Adjustment of c.h. output on the boiler is auto­matic. The greatest output pre --- set in the factory can, however, be reduced in level according to actual system requirements; this does not affect the maximum output in d.h.w. operation.
Such adjustments must be carried out by a quali­fied person; therefore we advise you to contact yourinstallerorServiceAgent.
Adjustment of the boiler temperature alters the gas flow at the burner according to the thermal de­mand in the system. Soit isusual tosee the burner lit at the minimum level for more or less long periods.
Minimum
Maximum
USE
Fig. 2.4
4 If d.h.w. supply only is required, position the
function selector 8 as in Fig. 2.5. The appliance operation light 10 will flash every 2 seconds (operating boiler).
810
Fig. 2.5
Fig. 2.6
Adjustment
In order to achieve optimal settings for economy and comfort, we recommend adjusting the oper­ating temperature of the c.h. water according to the outside temperature, positioning the knob as follows:
From 5 to 15 ˚C
Fig. 2.7
Between
--- 5 a n d + 5 ˚C
Lower than
--- 5 ˚C
3
Page 10
Instructions for use
Your qualified installer will be able to recommend the most suitable adjustment for your system.
The temperature and pressure gauge (4, Fig. 1.3 on page 1) will allow you to check that the set tem­perature is obtained.
USE
2.5 D.h.w. temperature
The temperature of the d.h.w. leaving the boiler can be varied from a minimum of about 35°Ctoa maximum of about 55°C (Fig. 2.8), by turning the temperature control knob 9.
Minimum
Maximum
Fig. 2.8
Adjustment of the d.h.w. temperature is complete­ly separate from that of the c.h. circuit.
The adjustment system integrated within the boiler automatically controls the flow of gas to the burner in order to keep the temperature of d.h.w. delivered constant, between the limits of maxi­mum and minimum output.
Where the demand isat a low levelor withthe tem­perature set to the minimum, it is normal to see a cycle of lighting and extinguishing of the burner when running.
Adjustment
It is advisable to adjust the d.h.w. temperature to a level commensurate with the demand, minimis­ing the need to mix with cold water. In this way, the automatic control facilities will be fully exploited.
Moreover, where the amount of limescale present in the water may be particularly great, not exceed­ing the position in Fig. 2.9 of the d.h.w. tempera­ture control knob 9 corresponding to about 50°C
(Fig. 2.9), minimisesannoying incidences of scale deposits and clogging.
Fig. 2.9
In these cases, however, it is advisable to install a small water treatment device or softener. With such a device you should avoid periodic descal­ing.
Consequently, the d.h.w.heat exchanger willkeep its performance consistent for a longer period of time with resulting gas savings.
9
If the demand for d.h.w. is so great as to prevent reachinga high enough temperature, have the ap­propriate output limiting valve installed by your in­staller or an Authorised Service Engineer.
2.6 Extinguishing
To turn the boiler off set the function selector 8 to the position shown in Fig. 2.10. The appliance operation light 10 will flash every 4 seconds.
Fig. 2.10
When you do not expectto use the boiler for a long period:
1 Switch off the electricity supply to the boiler, by
means of the fused spur isolation switch;
2 Shut off the gas supply cock 13 and the valves
for the water circuits fitted under the boiler (Fig. 2.11).
9
810
4
Page 11
Instructions for use
3 Empty the water circuits, if necessary, as
shownintheinstallation instructions in the sec- tion maintenance.
13
Fig. 2.11
Closed position
2.7 Built in time switch A
The combi boilers are equipped with a built inelec­tronic time switch (5, Fig. 1.3 on page 1) which controls the c.h. operation.
G
H
A
Setting the current time
Note: with a new unit or when the reset button B has been pressed and the selector switch A is to
the
position, the time display G is flashing.
Set the mode selector switch A to the and press the buttons D or E until the current time appears in the display G.
The clock starts by moving the switch A to the AUTO position.
Setting example shown in Fig. 2.13: Current time 16.30.
Fig. 2.13
Setting the switching time
20 memory locationsare available, corresponding to 10 on--- off sequences.
Set the mode selector switch A to the C1 position. The symbols shown in Fig. 2.14 appears in the display.
position
A
A
USE
Fig. 2.12
Display and control panel
A Mode selector switch
B Reset button
C Enter button
D Increase “+” setting button
E Decrease “ --- ” setting button
F O n --- o f f b u t t o n
G Time display
H O N --- O F F d i s p la y
Fig. 2.14
Press the buttons D or E to set the desired O N
BCDEF
time.
Press the “enter” button C to confirm the setting and to continue programming the OFF time.
SettheOFFtimeasexplainedabovefortheON setting and confirm by pressing the “enter” button C. Proceed in the same way for other settings.
Setting example shown in Fig. 2.15: A --- ON time 7.45. B --- OFF time 10.30.
5
Page 12
Instructions for use
AB
Fig. 2.15
USE
Activating the timed settings
Set the mode selector switch A to the AUTO posi­tion shown in Fig. 2.16.
The current time appears in the display. The ON--­OFF display H indicates the current state of oper­ation (according to the settings).
Fig. 2.16
Note: when the mode selector switch A is in the AUTO position and the boiler is switched off at the fused spur isolation switch, the display H indicates only the OFF state. The other indications are blanked.
Reading the timed settings
Set the mode selector switch A to the C1 position. The symbols shown in Fig. 2.14 appears in the display.
Press the “enter” button C. Each time the button is pressed the display shows the details of the next setting.
Changing or deleting the timed settings
Set the mode selector switch A to the C1 position. The symbols shown in Fig. 2.14 appears in the display.
Press the “enter” button C until the d isplay shows the setting to be modified or deleted.
Thetimesettingcanbemodifiednowbypressing button D or E and the operation can be switched on or off by pressing the button F.
To delete a time set press the button D or E until the symbols shown in Fig. 2.14 appears in the time display G.
The new settigs are memorized by moving the switch A to a different position.
Manual operation
The operation of the time switch can be forced on or off constantly or for a timed period.
6
To f or ce constantly on or off the timer operation set the mode selector switch A to the TIMER posi- tion. The symbols shown in Fig. 2.17 appears on the display.
Fig. 2.17
The operation can be switched permanently on or off by pressing the button F and leaving the switch
A
AintheTIMER position.
To for c e atimeddelayon or off operation, set the mode selector switch A in the TIMER position.
Set the time delay by pressing the button D or E and the operation can be forced on or off by pres­sing the button F.
Thetimedelaycanbesetwithinthefollowing ranges:
1to23hourswithstepsof1hour 1to27dayswithstepsof1day
The time delay setting is activated by moving the switch A to the AUTO position. The ON --- OFF display H flashes indicating that the current state of operation has been forced.
To delete the timed delay setting, set the mode se­lector switch A in the TIMER position, press the button D or E until the symbols shown in Fig. 2.17 appears in the display and then set the mode se­lector switch A to the AUTO position
Setting example shown in Fig. 2.18: forced ON state for 4 hours.
Fig. 2.18
Resetting
To completely reset the timer, press the reset but­ton with a pointed object (pencil).
CAUTION: pushing the reset button will complete­ly erase the settings as well as all the data, includ­ing the current time.
Page 13
Instructions for use
2.8 Built in time switch B
The combi boilers are equipped with a built inelec­tronic time switch which controls the c.h. oper­ation.
H
Fig. 2.19
Display and control panel
A Mode selector switch
B Reset button
C OK button
D Increase “+” setting button
E Decrease “ --- ” setting button
F O n --- o f f b u t t o n
G Time display
H O N --- O F F d i s p la y
Setting the current time
Press repeatedly the button A until the display shows the symbol
Press the buttons D or E until the current time ap­pears in the display G.
The clock starts by pressing the button A to show the symbol AUTO.
Setting example shown in Fig. 2.20: Current time 16.30, day Thursday.
G
A
BCD EF
Setting the switching time
28 memory locationsare available, corresponding to 14 on--- off sequences.
Press repeatedly the button A until the display shows the symbol C1 (Fig. 2.21)
The symbols shown in Fig. 2.21 appears in the display.
A
Fig. 2.21
Press the buttons D or E to set the desired O N time.
Press the “OK” button C to confirm the setting and to continue programming the OFF time.
SettheOFFtimeasexplainedabovefortheON setting and confirm by pressing the “enter” button C. Proceed in the same way for other settings.
Setting example shown in Fig. 2.22: A --- ON time 7.45. B --- OFF time 10.30.
AB
Fig. 2.22
Activating the timed settings
The current time appears in the display. The ON --­OFF display H indicates the current state of oper­ation (according to the settings).
A
USE
Fig. 2.20
Fig. 2.23
Note: when the display shows the symbol AUTO
A
and the boiler is switched off at the fused spur isolation switch, the display H indicates only the OFF state. The other indications are blanked.
Reading the timed settings
7
Page 14
Instructions for use
Press repeatedly the button A until the display shows the symbol C1 (Fig. 2.21)
The symbols shown in Fig. 2.21 appears in the display.
Press the “OK” button C. Each time the button is pressed the display shows the details of the next
USE
setting.
Changing or deleting the timed settings
Press repeatedly the button A until the display shows the symbol C1 (Fig. 2.21)
The symbols shown in Fig. 2.21 appears in the display.
Press the “OK” button C until the display shows the setting to be modified or deleted.
Thetimesettingcanbemodifiednowbypressing button D or E and the operation can be switched on or off by pressing the button F.
To delete a time set press the button D or E until the symbols shown in Fig. 2.21 appears in the time display G.
The new settings are memorised by pressing the button A.
Manual operation
The operation of the time switch can be forced on or off constantly or for a timed period.
To f or ce constantly on or off the timer operation press repeatedly the button A until the display shows the symbol TIMER. The symbols shown in Fig. 2.24 appears on the display.
To f o rc e atimeddelayon or off operation, press repeatedly the button A until the display shows the symbol TIMER.
Set the time delay by pressing the button D or E and the operation can be forced on or off by pres­sing the button F.
Thetimedelaycanbesetwithinthefollowing ranges:
1to23hourswithstepsof1hour 1to27dayswithstepsof1day
Pressthe button A until the display shows thesym­bol AUTO. The ON --- OFF display H flashes indicating that the current state of operation has been forced.
To delete the timed delay setting, press repeatedly the button A until the display shows the symbol TIMER, press the button D or E until the symbols showninFig.2.25appearsinthedisplayandthen pressthe button A until the displayshows thesym­bol AUTO.
Setting example shown in Fig. 2.25: forced ON state for 4 hours.
A
Fig. 2.25
A
Fig. 2.24
The operation can be switched permanently on or off by pressing the button F and leaving the dis­play shows the symbol TIMER.
8
Note:If during manual operation, power supply turns off, timer must be set again following previ­ous steps
Resetting
To completely reset the timer, press the reset but­ton with a pointed object (pencil). CAUTION: pushing the reset button will complete­ly erase the settings as well as all the data, includ­ing the current time.
Page 15
3 USEFUL ADVICE
3.1 Central heating
For reasonably economical service install a room thermostat.
Never shut off the radiator in the area where the room thermostat is installed.
If a radiator (or a convector) does not heat up, check that no air is present in it and that its valve is open.
If the ambient temperature is too high, do not alter the radiator valves. Reduce the central heating temperature instead by means of the room ther­mostat and the function selector (8 in Fig. 3.1).
8
Fig. 3.1
3.2 Frost protection
This appliance is provided with a built in anti --­freeze system that operates the boiler when the temperature is below 4 ˚C Therefore, when the boiler is not lit and used in cold weather, with consequent risk of freezing do
not switch off the boiler at the fused spur isola­tion switch or close the gas inlet cock.
3.3 Periodic maintenance
For efficient and continuous operation of the boiler, it is advisable to arrange maintenance and cleaning by an Authorised Service Centre En­gineer, at least once a year.
During the service, the most important compo­nents of the boiler will be inspected and cleaned. This service can be part of a maintenance con­tract.
In particular,you are advised to have the following checks carried out:
--- primary heat exchanger;
--- d omestic hot water heat exchanger;
--- burner;
--- exhaust fume duct and flue;
--- pressurisation of the expansion tank;
--- filling up of the central heating circuit;
--- bleeding of air from the central heating system;
--- general check of the appliance’s operation.
3.4 External cleaning
Before carrying out any cleaning, disconnect the appliance from the electrical mains, using the fused spur isolation switch fitted adjacent to the appliance.
To clean the external panels, use a cloth soaked in soapy water. Do n ot use solvents, abrasive powd­ers or sponges.
Do not carry out cleaning of the appliance and/or its parts with readily flammable substances (for example petrol, alcohols, naphtha, etc.).
3.5 Operational faults
If the lock---out signal lamp comes on
this indicates that the safety lock --- out 6 (Fig. 3.2) has stopped the boiler
To re --- start the boiler, it is necessary to press the boiler reset button 7 (Fig. 3.2).
6
7
Fig. 3.2
Forthe firstlighting up and following maintenance procedures for the gas supply, it may be necess­ary to repeat the resetting operation several times so as to remove the air present in the pipework.
If noises due to air bubbles are heard during operation...
you should check that the p ressure on the tem­perature and pressure gauge (Fig. 2.2 on page 2) is not below the correct setting. If required, top up the system correctly, as de­scribed in the section 2.2 of this manual. Bleed any air present in theradiators, ifnecessary.
If the pressure on the temperature and pres­suregauge(4onpage1)hasgonedown...
it is necessary to top up the appliance with water again, so as to raise the pressure to an adequate level as described in the section 2.2 of thismanual.
If topping up with water has to be done very fre­quently, have the system checked for leaks.
USE
9
Page 16
Useful advice
If water comes out of the pressure relief valve
Check on the temperature and pressure gauge (4 on page 1) that the pressure in the central heating circuit is not close to 3 bars. In this case, tempera­ture rise in the circuit can cause the pressure relief valve to open.
USE
So that this does not happen and to decrease the pressure to a normal value, it is advisable to vent some of the water in the appliance through the bleed valves present in the radiators.
If in time, a reduction in domestic hot water supply is observed...
The likely causes may be impurities caught in the domestic hot water flow switch filter or limescale deposited in the domestic hot water heat ex­changer. It is advisable to have the app liance cleaned out by an Authorised Service Centre En­gineer.
If water should occasionally leak from the boiler...
shut off the valves positioned under the boiler (Fig. 2.11 on page 5) and call an Authorised Ser­vice Centre Engineer.
If the appliance operation light 10 (Fig. 3.3) flashes very quickly the boiler is faulty.
10
Fig. 3.3
In this case or in case of problems other than those mentioned here, switch off the boiler, as describedinsection2.6onpage4andcalla competent and responsible service engineer.
10
Page 17
4 TECHNICAL INFORMATION
4.1 Overview
32
31
30
29
28
27
26
Fig. 4.1
11 C.h. return valve 12 Domestic cold water inlet valve
33
25 1822
24
21
34
2023
35
19 16
17
13 Gas inlet valve 14 D.h.w. outlet pipe 15 C.h. flow valve 16 D.h.w. temperature probe NTC
17 Main circuit drain valve
18 C.h. pressure relief valve
19 Pump
20 Pump vent plug
21 Automatic air purger valve
22 D.h.w. flow switch
23 Modulation gas valve
24 Primary circuit flow switch
25 C.h. temperature probe NTC
2 6 T h r e e --- w a y d i v e r t e r v a l v e
27 Flame --- detecting electrode
28 Ignition electrodes
29 Burner
30 Combustion chamber
31 Primary heat exchanger
32 Air pressure switch
33 Air switch pressure test points
34 Fan
35 Safety thermostat
36 Modulation operator
37 Gas valve outlet pressure test point
38 Gas valve inlet pressure test point
39 D.h.w. heat exchanger
40 C.h. expansion tank
4 1 B y --- p a s s v a l v e
42 Venturi device
43 Domestic water circuit filter
44 D.h.w. flow limiter
45 Flue outlet pipe
46 Air intake pipe
INSTALLATION
11
Page 18
Technical information
4.2 Main diagram
21
46
16
24
35
19
45
26
39
25
44 43
22
42
32
31
INSTALLATION
28
27
37
36
23
38
34
29
40
Fig. 4.2
12
13
18
11
41
15
17
12
14
Page 19
Technical information
4.3 Hydraulic specifications
kPa bar
0.6
60
50
0.5
40
0.4
0.3
30
20
0.2
0.1
10
0
0.0
0 200 400 600 800 1000 1200 1400
l/h
Fig. 4.3
The hydraulic specifications in Fig. 4.3 represent the pressure (available head for the central heat­ing system) as a function of the flow rate.
The load loss due to the boiler has already been subtracted.
Output with thermostat cocks shut off
The boiler is fitted with an automatic by --- pass valve (41 on page 11), which protects the primary heat exchanger.
In case of excessive reduction or total blockage of water circulation in the central heating system owing to closure of the thermostatic valves or sys-
tem component cocks, the by--- pass valve ensur­es a minimum flow of water through the primary heat exchanger.
4.4 Expansion vessel
Note:thisboilerisdesignedforoperationonly in a sealed central heating system
The height difference between the pressure relief valve and the highest point in the system may be 7m at most.
For greater differences, increase the pre--- load pressure in the expansion vessel (40 on page 11) and the system, when cold, by 0.1 bar for each additional 1m.
Capacity
P r e --- lo a d p r e s s u r e kPa
Maximum volume of water in the system *
Tab . 4. 1
* Where conditions are:
--- Averag e maximum temperature of the system
is 80°C
--- Initial temperature when filling up the system is
10°C
For systems with volumes greater than 104l, an additional expansion vessel must be provided.
l 6,0
100
bar
1,0
l 104
INSTALLATION
13
Page 20
Technical information
4.5 Technical data M90E.24S
Nominal heat input kW
Minimum heat input kW
Maximum useful output kW
Minimum useful output kW
Central heating
Maximum temperature ˚C 85 Minimum temperature ˚C 38
Maximum pressure kPa
INSTALLATION
Minimum pressure kPa
Available head (in 1000 l/h)
Domestic hot water
Maximum temperature ˚C 55
Minimum temperature ˚C 35
Maximum pressure kPa
Minimum pressure kPa
Flow rate
minimum l/min 2,5 30˚ rise l/min 11,6*
35˚ rise l/min 10,0* 40˚ rise l/min 8,7*
BTU/h
BTU/h
BTU/h
BTU/h
bar
bar
kPa
bar
bar
bar
26,6
90 754
11,0
37 530
24,3
82 906
9,1
31 047
250
2,5
30
0,3
27
0,27
1 000
30
0,3
Injectors
Natural G20 130
Butane G30 77
Propane G31 77
Gas supply pressures
Gas norm. min max
Natural G20
Butane G30
Propane G31
Pa
mbar
Pa
mbar
Pa
mbar
2 000201 700172 500
25
2 900292 000203 500
35
3 700372 500254 500
45
Gaspressuresattheburner
Gas min max Ignition
Natural G20
Butane G30
Propane G31
10
Gas rate
Gas min max
Natural
Pa
mbar
Pa
mbar
Pa
mbar
180
1,8
500
5,0
610
6,1
1 170
11,7
2 760
27,6
3 570
35,7
600
6,0
1 200
1 300
m3/h 1,16 2,82
12
13
G20
Butane
kg/h 0,87 2,09
G30
Propane
kg/h 0,85 2,06
G31
* calculated values subject to tolerance Net calorific value at 15 ˚C and 1013,25 mbar
G 20 34,02 MJ/m
3
G 30 45,6 MJ/kg G 31 46,4 MJ/kg 1 mbar approximately equals 10 mm H
O
2
14
Page 21
Technical information
Electrical Data
Voltage V~ 230
Frequency Hz 50
Power consumption W 150
Protection degree IPX4D
External fuse rating A 3
Internal fuse rating A 1,6 T
Flue design
Flue pipe diameter
Coaxial mm 60/100
Twin split pipes mm 80
Roof mm 80/125
Nominal heat flow rate** kW 26,6 Exhaust temperature** ˚C 145
Smoke production** kg/h 55,1
Flue gas figures
Nominal heat input** kW 26.6
CO2content % 7,0
O2content % 8,4
CO content ppm 150
Exhaust temperature** ˚C 145
INSTALLATION
Other specifications
Height mm 703
Width mm 400
Depth mm 325
Weight (dry) kg 37
Water volume in the boler (up to 1 bar)
** Values refer to tests with a 1 m chimney working at the nominal heat input
l(kg) 1,0
15
Page 22
Technical information
4.6 Technical data M90E.28S
Nominal heat input kW
Minimum heat input kW
Maximum useful output kW
Minimum useful output kW
Central heating
Maximum temperature ˚C 85 Minimum temperature ˚C 38
Maximum pressure kPa
INSTALLATION
Minimum pressure kPa
Available head (in 1000 l/h)
Domestic hot water
Maximum temperature ˚C 55
Minimum temperature ˚C 35
Maximum pressure kPa
Minimum pressure kPa
Flow rate
minimum l/min 2,5 30˚ rise l/min 13,6* 35˚ rise l/min 11,6*
40˚ rise l/min 10,2*
BTU/h
BTU/h
BTU/h
BTU/h
bar
bar
kPa
bar
bar
bar
31,1
106 107
13,0
44 353
28,4
96 895
10,8
36 847
250
2,5
30
0,3
27
0,27
1 000
30
0,3
Injectors
Natural G20 130
Butane G30 77
Propane G31 77
Gas supply pressures
Gas norm. min max
Natural G20
Butane G30
Propane G31
Pa
mbar
Pa
mbar
Pa
mbar
2 000201 700172 500
25
2 900292 000203 500
35
3 700372 500254 500
45
Gaspressuresattheburner
Gas min max Ignition
Natural G20
Butane G30
Propane G31
10
Gas rate
Pa
mbar
Pa
mbar
Pa
mbar
180
1,8
450
4,5
570
5,7
1 170
11,7
2 760
27,6
3 570
35,7
600
6,0
1 200
12
1 300
13
Gas min max
Natural
m3/h 1,37 3,29
G20
Butane
kg/h 1,02 2,45
G30
Propane
kg/h 1,00 2,41
G31
* calculated values subject to tolerance
For the net calorific values of G20, G30, G31 see the technical data at page 14
1 mbar approximately equals 10 mm H
O
2
16
Page 23
Technical information
Electrical Data
Voltage V~ 230
Frequency Hz 50
Power consumption W 170
Protection degree IPX4D
External fuse rating A 3
Internal fuse rating A 1,6 T
Flue design
Flue pipe diameter
Coaxial mm 60/100
Twin split pipes mm 80
Roof mm 80/125
Nominal heat flow rate** kW 31,1
Exhaust temperature** ˚C 165
Smoke production** kg/h 70,6
Flue gas figures
Nominal heat input** kW 31,1
CO2content % 6,3
O2content % 9,7
CO content ppm <100 Exhaust temperature** ˚C 165
INSTALLATION
Other specifications
Height mm 703
Width mm 400
Depth mm 325
Weight (dry) kg 39
Water volume in the boler (up to 1 bar)
** Values refer to tests with a 1 m chimney working at the nominal heat input
l(kg) 1,1
17
Page 24
Technical information
4.7 Technical data M90E.32S
Nominal heat input kW
Minimum heat input kW
Maximum useful output kW
Minimum useful output kW
Central heating
Maximum temperature ˚C 85 Minimum temperature ˚C 38
Maximum pressure kPa
INSTALLATION
Minimum pressure kPa
Available head (in 1000 l/h)
Domestic hot water
Maximum temperature ˚C 55
Minimum temperature ˚C 35
Maximum pressure kPa
Minimum pressure kPa
Flow rate
minimum l/min 2,5 30˚ rise l/min 15,3* 35˚ rise l/min 13,1*
40˚ rise l/min 11,5*
Injectors
Natural G20 130
Butane G30 77
Propane G31 77
BTU/h
BTU/h
BTU/h
BTU/h
bar
bar
kPa
bar
bar
bar
35,2
120 102
15,5
52 886
32,0
109 184
12,7
43 435
250
2,5
30
0,3
27
0,27
1 000
30
0,3
Gas supply pressures
Gas norm. min max
Natural G20
Butane G30
Propane G31
Pa
mbar
Pa
mbar
Pa
mbar
2 000201 700172 500
25
2 900292 000203 500
35
3 700372 500254 500
45
Gaspressuresattheburner
Gas min max Ignition
Natural G20
Butane G30
Propane G31
Pa
mbar
Pa
mbar
Pa
mbar
180
1,8
500
5,0
670
6,7
1 170
11,7
2 760
27,6
3 570
35,7
600
6,0
1 200
12
1 300
13
Gas rate
Gas min max
Natural
m3/h 1,64 3,73
G20
10
Butane G30
Propane
kg/h 1,22 2,78
kg/h 1,20 2,73
G31
Electrical Data
Voltage V~ 230
Frequency Hz 50
Power consumption W 180
Protection degree IPX4D
External fuse rating A 3
Internal fuse rating A 1,6 T
* calculated values subject to tolerance
For the net calorific values of G20, G30, G31 see the technical data at page 14
1 mbar approximately equals 10 mm H
O
2
18
Page 25
Technical information
Flue design
Flue pipe diameter
Coaxial mm 60/100
Twin split pipes mm 80
Roof mm 80/125
Nominal heat flow rate** kW 35,2
Exhaust temperature** ˚C 155
Smoke production** kg/h 90
Flue gas figures
Nominal heat input** kW 35,2
CO2content % 6,5
O2content % 9,3
CO content ppm 200
Exhaust temperature** ˚C 155
Other specifications
Height mm 703
Width mm 400
Depth mm 325
Weight (dry) kg 39
Water volume in the boler (up to 1 bar)
l(kg) 1,1
INSTALLATION
** Values refer to tests with a 1 m chimney working at the nominal heat input
19
Page 26
5 GENERAL REQUIREMENTS
Biasi UK Ltd support the Benchmark initiative. The BenchmarkLog Book is located at theback of this manual and should be completed by the Installing/Commisssioning Engineer and handed over to the User for future reference by other visiting Engineers. Also included is the Service Interval R ecord card that should be completed by the Service Engineer following the annual service maintenance of the boiler and system.
For Ireland (IE), it is necessary to complete a “Declaration of Conformity” to indicate com­pliance to I.S.813.2002.
This appliance must be installed by a compet­ent person in accordance with the Gas Safety (installation & U se) Regulations.
INSTALLATION
5.1 Related documents
The installation of this appliance must be in ac­cordance with the relevant requirements of the current Gas Safety (Installation & Use) Regula­tions, the Local Building Regulations, the current I.E.E. Wiring Regulations, the Regulations and by --- laws of the local water undertaking, and in Scotland, in accordance with the Building Stan­dards (Scotland) Regulation. Health and safety document n˚ 635 ”Electricity at work regs.”.
It should also be in accordance with the British Standard Codes of Practice:
In Ireland (IE). The installation must be carried out by a Competent Person and installed in accord­ance with the current edition of I.S.813.2002 “Do­mestic Gas Installations” the current Building Regulationsand reference should be made to the current ETCI rules for electrical installations.
cal switch or appliance control, utilising mains electricity should be so situated that it cannot be touched by a person using the bath or shower.
The location must permit the provision of an ad­equate flue and termination.
For unusual locations special procedures may be necessary and BS 6798 gives detailed guidance on this aspect.
A compartment used to enclose the appliance must be designed specifically for this purpose.
This appliance is not suitable for external installa­tion.
5.3 Flue system
The provision for satisfactory flue termination must be made as described in BS 5440 part 1.
For Ireland (IE), refer to I.S.813.2002. The appliance must be installed so thatthe flue ter-
minal is exposed to external air.
It must not be installed so that the terminal dis­charges into an other room or space as an out­house or lean --- to. It is important that the position of the terminal allows a free passage of air across at all times.
The terminal should be located with due regard for the damage or discoloration that might occur to building products in the vicinity.
In cold and/or humid weather water vapour may condenseon leaving the flue terminal;the effectof such ”steaming” must be considered.
The minimum acceptable spacing from the ter­minal to obstructions and ventilation openings are specified in Fig. 5.1.
5.2 Location of appliance
The appliance may be installed in any room or in­ternal space, although particular attention is drawn tothe requirements of the current I.E.E. Wir­ing Regulations, and in Scotland, the electrical provisions of the Building Regulations applicable in Scotland, with respect to the installation of the combined appliance in a room containing a bath or shower.
For Ireland (IE), reference should be made to the current edition of I.S.813.2002 and the current ETCI rules for electrical installations.
Where a room--- sealed appliance is installed in a room containing a bath or shower, any electri-
20
Fig. 5.1
BC
F
D
IJ
K
rev . 17.09.93
N
A
E
G
H
O
LM
G
Page 27
General requirements
Ter minal po s i tio n mm
A Directly below a window or other opening 300. ...
B Below gutters, soil pipes or drain pipes 75. .....
C Below eaves 200. ............................
D Below balconies or car port roof 200*. ..........
E From vertical drain pipes and soil pipes 75. .....
F From internal corners 150*. ...................
G From external corners 75*. ....................
H Above ground or balcony level 300. ............
I From a surface facing a terminal 600.. ...........
J From a terminal facing a terminal 1 200. .........
K From an opening in the car port.
(e.g.door,window)intodwelling 1200.........
L Vertically from a terminal in the same wall 1 500.. M Horizontally from a terminal in the same wall 300. N Above the roof pitch with roof slope less.
than or equal to 30˚ 350......................
Above the roof pitch with roof slope
more than 30˚ 600...........................
O From wall face 600. ..........................
* specific manufacturer requirements
5.4 Gas supply
The Gas meter is connected to the service pipe by the local gas region or a local gas region contrac­tor.
If the gas supply for the boiler serves other appliances ensure that an adequate supply is available both to the boiler and the other appliance when they are in use at the same time.
Pipework must be of adequate size. Pipes of a smaller size than the boiler inlet connection should not be used.
Installation pipes should be fitted in accordance with BS 6891 and the complete installation should be tested for soundness.
For Ireland (IE), refer to I.S.813.2002.
5.7 Water circulation (c.h.)
Detailed recommendations are given in BS 6798 and BS 5449; the following notes are given for general guidance.
For Ireland (IE), refer to I.S.813.2002.
Pipework
Copper tubing to BS EN 1057 is recommended for water pipes. Jointing should be either with capil­lary soldered or with compression fittings.
Where possible pipes should have a gradient to ensure air is carried naturally to air release points and water flows naturally to drain taps.
The appliance has a built --- in automatic air release valve, it should be ensured as far as possible that the appliance heat exchanger is not a natural col­lecting point for air.
Except where providing useful heat, pipes should be insulated to prevent heat loss and to avoid freezing.
Particular attention should be paid to pipes pas­sing through ventilated spaces in roofsand under floors.
B y --- p a s s
The appliance includes an automatic by --- pass valve which protects the main heat exchanger in case of reduced or interrupted water circulation through the heating system due to the closing of thermostatic valves or cock---type valves within the system.
The by - -- pass is calibrated to assure a minimum flow of 500--- 600 lts/hr through the main heat ex­changer.
If you are installing a system that includesthermo­static radiator valves (TRV) and/or small bore
5.5 Air supply
The room in which the boiler is installed does not require a purpose provided air vent.
(8---10 mm) it may be necessary to fit an external by --- pass to facilitate correct operation of the boiler.
Air release points
5.6 Ventilation
If installed in a cupboard or compartment, it is not necessary to provide additional ventilation for cooling for this particular product. However con­sideration must be given to clearance require­ments for maintenance (see section 6.2) and under no circumstancesmust storedarticles be al­lowed to come into contact with the boiler or flue pipe.
Thesemustbefittedatallhighpointswhereairwill natural collect and must be sited to facilitate com­pletefillingofthesystem.
Expansion vessel
The appliance has an integral sealed expansion vessel to accommodate the increase of water vol­ume when the system is heated.
Refer to Tab. 4.1 on page 13 for its technical data.
INSTALLATION
rev . 17.09.93
21
Page 28
General requirements
If the heating circuit has an unusually high water content, calculate the total expansion and add an additional sealed expansion vessel with adequate capacity.
Mains water feed: central heating
There must be no direct connection to the mains water supply even through a non return valve, without the approval of the Local Water Authority.
Mains water feed: hot water supply
The domestic section of the boiler is designed to withstand an internal domestic water pressure of 10 bar. Where it is likely that the mains domestic water pressure may exceed 5 bar, it is possible due to internal “water hammer” effects that the pressure within the domestic system can increase to a level in excess of the 10 bar limit.
In these circumstances it is therefore recom-
INSTALLATION
mended that a 3 bar pressure reducing valve be fitted to the incoming mains water supply and a mini expansion vessel installed on the domestic circuit.
These devices will protect the boiler and the do­mestic system from damage due to excessive do­mestic water pressure.
Filling
A method for initially filling the system and replac­ing water lost during servicing must be provided and itmust comply withlocal water authority regu­lations.
The correct method is shown in Fig. 5.2.
The temporary connection must be removed immediately after filling.
Control valve
Double check valve
Te m p o r a ry connection
Supply pipe
(cold wa ter inl et)
C.h. return pipe
Control valve
Fig. 5.2
The installer should ensure that no leaks exist either inside the boiler or on the system as fre­quent filling of the system could cause premature scaling of the heat exchanger.
5.8 Domestic water
The domestic water installation must be in accord­ance with the relevant recommendations of BS
5546. Copper tubing to BS EN 1057 is recom­mended for water carrying pipework and must be use for pipework carrying potable water.
For Ireland (IE), refer to I.S.813.2002.
5.9 Water treatment
Central heating circuit
Where a new boiler is fitted to a new system with either plastic or copper pipes, it is important the system is fully flushed, on completion, to ensure flux residues, swarfs, oils and other installation de­bris is removed.
Where a new boiler is fitted to an existing system, it is important the debris from the existing system is fully removed in order to ensure the efficiency of the new appliance is maintained.
Details on flushing procedure are given in the sec­tion 7.4 of this manual.
Domestichotwatercircuit(scaleprotection)
In areas where the water is ’hard’ (i.e. more than 200 ppm total hardness as defined by BS 7593: 1993 Table 2) it is recommended that a proprietary scale---reducing device is fitted into the boiler cold supply, within the requirements of the local water company.
5.10 Electrical supply
Warning, this appliance must be earthed.
External wiring to the appliance must be carried out by a competent person and be in accordance with the current I.E.E. Regulations and any local regulations which apply.
Reference should be made tu the current ETCI rules for electrical installations.
For Ireland (IE), refer to I.S.813.2002. The boiler is supplied for connection to a 230 V~
50 Hz supply. The supply must be fused at 3A. The method of connection to the electricity supply
must facilitate complete electrical isolation of the appliancebytheuseofafuseddoublepoleisola­tor having a contact separation of at least 3 mm between poles or alternatively, by the use of a 3A
22
rev . 17.09.93
Page 29
General requirements
fused three pin plug and unswitched shuttered socket outlet both complying with BS 1363.
The point of connection to the electricity supply must be readily accessible and adjacent to the applianceexcept were the appliance isinstalled in
a bathroom this must then be sited outside the bathroom.
INSTALLATION
rev . 17.09.93
23
Page 30
6 INSTALLATION
6.1 Warnings
The use of gas appliances is subject to statutory control; it is essential to observe the current regulations and laws in force (see also chapter 5).
The appliance must discharge combustion products directly outside or into a suitable ex­haust duct designed for this purpose.
Combustion products must be discharged using original flue kits only, sincethey are inte­gral parts of the boiler.
ForLPG, the appliance must also conform with the requirements of the distributors and com­ply with current Regulations and laws in force.
The safety relief valve must be connected to a suitable drain, or discharge in a safe manner.
The electrical wiring must conformwith current
INSTALLATION
Regulations, in particular:
--- the boiler must be earthed using the cor­rect bonding clamp.
--- Adjacent to the boiler a fused spur isolation switch must be installed which permits a complete switching off in the conditions of the overvoltage category III. Refer to sec­tion 6.10 in this chapter for the electrical connections.
In no circumstances will the manufacturer be held responsible if the warnings and in­structions contained in this manual have not been complied with.
6.2 Precautions for installation
For the installation proceed as follows:
--- The boiler must be fixed to a strong wall.
--- The dimensions for the exhaust fume duct de-
tailed in section 6.7 and the correct procedures for installing the duct, depicted in the instruc­tion leaflet included with the flue kit, must be complied with during installation.
--- To allow maintenance procedures it is necess­ary to leave the minimum gaps indicated in Fig. 6.1.
250
25 50
200
Fig. 6.1 (all dimensions in mm)
--- When installing the boiler in a cupboard, cover or alcove allow at least 50mm permanent clear­ance from the front face of the boiler. Also en­sure sufficient clearance to allow free access for servicing and the lowering of the front con­trol panel.
--- If the boiler is installed outside, cover the ap­pliance to protect it against the elements and add some special anti --- f reeze (neutralised) to the c.h. system.
--- Before installing the boiler on an existing c.h. system,flush it out thoroughly beforefitting the boiler, so as to remove muddy deposits.
--- It is advisable to equip the system with a sedi­ment filter, or use a water--- treatment product in the circulating water. The latter option in particular, not only cleans out the system, but also has an anti --- corrosive effect by promoting formation of a protective skin on metal surfaces and neutralising gases present in the water. We recommend the use of a suitable universal inhibitory to protect the c.h. system from cor­rosion.
6.3 Installing the bracket
Precautions
Before mounting the bracket, check that the di­mensions for fitting the exhaust fume duct are complied with (refer to the leafletincluded with the flue kit, packed separately).
24
Page 31
Installation
Utilise the paper template supplied with the boiler to determine the fixing position for the bracket and boiler. Securely mount the bracket to the wall using appropriate fixings suitable for the type of wall construction and capable of supporting the total (wet) load. Refer to the weight given in the technical data tables specific for each model.
6.4 Overall dimensions
C
95
35 165
193
20
101
85 255
20
561
D.h.w.
outlet*
C.h.
flow
83
* not present on c.h. only boilers
A --- a i r i n ta k e / f l ue o u t l e t p i p e ø 1 0 0 (c o --- a x i a l ) B --- flue outlet pipe ø 80 (twin kit) C --- air intake pipe ø 80 mm (twin kit)
Gas
inlet *
400
250
mounting
bracket
Cold
water
65645265
Wall
return
B
A
703
C.h.
Fig. 6.2 (all dimensions in mm)
147
237
AandB
325
C
6.6 Mounting the boiler
1 Take the protective caps off the boiler pipe-
work.
2 Thoroughly clean the connections.
3 Mount the boiler on its bracket.
4 Fix the c.h. valves A and gas cock B (¾”) to the
boiler using the ¾” gaskets (Fig. 6.3)
5 Fix the ø 22 mm pipes C (c.h. circuit) to the c.h.
valves A and the ø 22 mm pipe D (gas) to the cock B using the ¾” gaskets.
6 Repeat the above procedure for the d.c.w. inlet
utilising the ½” cold water inletvalve E,the ø 15 mm copper tail F with its connection nut and two ½” gaskets.
7 Fix the ø 15 mm copper tail G with the ½” con-
nection nut and a ½” gasket.
8 Connect the pipe H (Fig. 6.4) from the pres-
sure relief valve to the safety discharge pipe­work.
C
G
A
B
E
A
Fig. 6.3
D
F
C
INSTALLATION
6.5 Joints
Functions Pipe sizes
Gas, c.h. return, c.h. flow ø22
D.c.w. inlet ø15
D.h.w. outlet ø15
Pressure relief valve ø15
Tab. 6.1 (sizes in mm o.d.)
H
Fig. 6.4
25
Page 32
Installation
6.7 Fitting the flue system
Refer to the assembly instructions contained with­in the chosen flue kit packaging for the correct as­sembly and installation.
6.8 Flue restrictors
Two restrictors with different size are supplied with the boilers M90E.24S and M90E.28S. A 44 mm size is fitted to the boiler and a 47 mm size is supplied in a separate bag.
Two restrictors with different size are supplied with the boiler M90E.32S. A 47 mm size is fitted to the boiler and a 50 mm size is supplied in a separate bag.
Thesizeismarkedontherestrictorbody.
INSTALLATION
For the correct use of the restrictors w i t h c o --- a x i a l pipes ø 60/100 mm refer to:
Tab. 6.2 for models M90E.24S and M90E.28S Tab. 6.3 for model M90E.32S
For the correct use of the restrictors with vertical roof kit ø 80/125 mm refer to: Tab. 6.4 for models M90E.24S, M90E.28S Tab. 6.5 for the model M90E.32S
For the correct use of the restrictors with twin pipes refer to Fig. 6.8 for the models M90E.24S; and M90E.28S, refer to Fig. 6.9 for the model M90E.32S.
Models M90E.24S, M90E.28S
Equivalent length (ø 80/125) Restrictor
Between 0,5 and 1,5 m ø44mm
More than 1,5 m up to 6,5 m ø47mm
More than 6,5 m up to 8,5 m no restrictor
Tab . 6. 4 FOR VERTICAL ROOF KIT
Model M90E.32S
Equivalent length (ø 80/125) Restrictor
Between0,5and4m ø47mm
More than 4 m up to 6 m no restrictor
Tab . 6. 5 FOR VERTICAL ROOF KIT
Theappropriaterestrictor,whennecessary,must be fitted in the flue outlet elbow as indicated in Fig. 6.5.
Model M90E.24S, M90E.28S
Equivalent length (ø 60/100) Restrictor
Between0,3and1m ø44mm
More than 1 m up to 2 m ø47mm
More than 2 m up to 3 m no restrictor
Tab . 6. 2 FOR CO--- AXIAL STANDARD FLUE
Model M90E.32S
Equivalent length (ø 60/100) Restrictor
Between0,3and1m ø47mm
More than 1 m up to 2,7 m no restrictor
Tab . 6. 3 FOR CO--- AXIAL STANDARD FLUE
26
Fig. 6.5
6.9 Choice of flue
The following flue kits are available for connecting to the boiler:
Standard horizontal flue kit (Fig. 6.6A)
Co--- axial 60/100mm --- nominal length 1m
This kit is normally supplied with the boiler and can be fitted to allow discharge to the rear or either side of the boiler via the flanged boiler adapter elbow. Minimum length required is 0.3 m. Maxi­mum equivalent length of 3 metres for models M90E.24S, M90E.28S and 2,7 metres for the model M90E.32S can be achieved utilising exten­sions. This flue system can only be used to dis-
Page 33
Installation
charge horizontally, it is not designed to enable termination in the vertical plane.
Vertical kit with 90˚ elbow (Fig. 6.6B)
Co-- -axial 60/100 mm
Supplied with a straight flanged adapter a co--­axial elbow and a co--- axial pipe with terminal, this kit allows for a vertical rise of 0,3 m from the boiler. In all circumstances the flue terminal must dis­charge horizontally and the equivalent flue length must not exceed 3 metres for models M90E.24S, M90E.28S and 2,7 metres for the model M90E.32S.
Elbows 45˚ &90˚ (Fig. 6.6C)
Co-- -axial 60/100mm.
Elbow kits enable the standardflue kits to be offset to overcome obstructions or ensure the correct clearancesfor the flue terminal. Each elbow used in addition to the standard flanged elbow reduces the overall acceptable length of the flue system as follows:
45˚ reduce length by 0,5 m. 90˚ reduce length by 1 m.
B
ø 60/100
See section 6.9
A
ø 60/100
90˚= --- 1 m
45˚= --- 0 , 5 m
C
Fig. 6.6
Twin pipe kits ø 80 mm (Fig. 6.7)
Various twin (split) pipes kits and optional acces­sories (elbows) are available to assist in the ter­mination of the flue where the boiler is installed in
a location remote to an outside wall. These kits allow for separation of the air supply pipe from the pipe that discharges the exhaust gases. Conse­quently it is possible to extend the flue system to a greater distance than that provided by the stan­dard horizontal co --- axial flue.
If either an additional 45˚ or 90˚ accessory elbow is used then the maximum permissible length of either pipe must be reduced by 0.90 m or 2,75 m respectively.
90˚=--- 2,75 m
45˚=--- 0,90 m
Fig. 6.7
The graph in Fig. 6.8 demonstrates the allowable equivalent lengths for the air supply and flue ex­haust pipes of models M90E.24S and M90E.28S.
Flue exhaust ”a” 32 30 28 26 24 22 20 18 16 14 12 10
Restrictor
8
47 mm
6 4 2 0
02468101214161820222426283032
Allowed values
Restrictor
M90E.24S M90E.28S
No
Air intake ”b”
Fig. 6.8 (all dimensions in metres)
INSTALLATION
27
Page 34
Installation
The graph in Fig. 6.9 demonstrates the allowable equivalent lengths for the air supply and flue ex­haust pipes of model M90E.32S
Flue exhaust ”a”
16 15 14 13 12 11 10
9 8 7 6 5 4 3 2 1 0
012345678910111213141516
INSTALLATION
Restrictor
50 mm
Allowed values
No
Restrictor
Fig. 6.9
Vertical--- roof kit (Fig. 6.10)
This kit allows vertical termination of the flue pipe through the roof. The kit is 1.2 m in length. Exten­sion pieces (Co --- axial) are also available which al­lows the flue system to be extended to a total overall maximum permissible length. Optional45˚ and 90˚ elbows can be used to offset theflueroute.
M90E.32S
Air intake ”b”
Vertical flue kit --- condensation
When fitting the 80/125 l flue kits where the equiv­alent fluelength exceeds 3 m a condensate collec­tor and syphon are required.
If the appliance normally operates at minimum output power at very low temperatures (e.g. 40 ˚C return / 60 ˚C flow), the above equivalent length should be reduced to 1 m.
The syphon must also be connected to a suitable drain.
Please, see the boiler accessory leaflet available from your Supplier for details or contact Biasi UK Technical Helpline.
6.10 Electrical connections
Connection to the electricity supply
1 Remove the front panel of the case (see the
section 9.2 in this manual).
2 Remove the screws I and J (Fig. 6.11).
3 Loosen the screws K.
I
Fig. 6.10
28
See Tab. 6.4 for 24 and 28 kW models)
Max length
See Tab. 6.5 for 32 kW model
J
I
KJ
K
Fig. 6.11
4 Remove the side panels or move the lower part
of the side panels as indicated in Fig. 6.12 and pull the control panel. When completely pulled out, the panel can ro­tate 45˚ downwards to facilitate the operations on the internal p arts.
Page 35
Installation
which the room thermostat must be con­nected.
7 Connect the earth wire (yellow/green).
Connection of a room thermostat
The room thermostat must be connected to the terminal block situated next to the control panel.
When connecting any type of external control, the link M in Fig. 6.14 must be removed.
To fu se d s p u r isolation switch
LN
Power supply terminal block
Fig. 6.12
5 Loosen the screws L and remove the service
panel (Fig. 6.13).
L
Fig. 6.13
Forthe electrical connection to the boiler use elec­tricwireswhich conform to the current regulations, with flexible cord, each core having a cross sec­tion area notlessthan0,75mm
2
.
6 Connect the electrical supply flexible cord
coming from the fused spur isolation switch to the power supply terminal block of the boiler (Fig. 6.14) keeping the same connections for the live (brown wire) and the neutral (blue wire). External3 A fuse or fused plug with same current rating is recommended.
Do not connect live wires to terminals to
M
3
12
External co ntrols terminal block
Fig. 6.14
8 Connect the room thermostat between ter-
minals 1 and 3 as shown in Fig. 6.15.
Do not connect live wires to terminals to which the room thermostat must be con­nected.
Room thermostat
Power supply terminal block
LN
T
External co ntrols terminal block
3
Fig. 6.15
9 Route the electrical supply flexible cord and
the external control flexible cord as illustrated in Fig. 6.16.
12
INSTALLATION
29
Page 36
Installation
Lock the flexible cords in place with the flexible cord clamps
To th e e x t er n a l control device
To th e f u s e d s p u r isolation switch
Fig. 6.16
INSTALLATION
6.11 External frost protection
10 Connect the frost thermostat between ter-
minals 1 and 2 as shown in Fig. 6.17.
Do not connect live wires to terminals to which the room thermostat must be con­nected.
Frost thermostat
Room thermostat
LN
T
Fig. 6.17
T
Power supply terminal block
12
External co ntrols
3
terminal block
30
Page 37
7 COMMISSIONING
Ensure that the Benchmark Log Book is satis­factorily commpleted during the commssion­ing process. The Log Book is located at theend of this manual. This manual should be handed to the User following completion of the installa­tion and commissioning process. Failure to comply with these requirments may invalidate the manufacturers guarantee.
For Ireland (IE), it is necessary to complete a “Declaration of Conformity” to indicate com­pliance to I.S.813.2002.
7.1 Electrical installation
Preliminary electrical system checks to ensure electrical safety shall be carried out by a compet­ent person. i.e. polarity, earth continuity, resis­tance to earth and short circuit.
If a fault has occurred on the appliance the fault find­ing procedure should be follo we d as specified in the service manual.
7.2 Gas supply installation
1 Inspect the entire installation including the gas
meter, test for soundness and purge, all as de­scribed in BS 6891.
For Ireland (IE), refer to I.S.813.2002.
2 Open the gas cock 13 (Fig. 7.1) on the
appliance and check the gasconnector on the appliance for leaks.
13 12
Fig. 7.1
Open position
7.3 Filling the d.h.w. system
1 Close all hot water draw---off taps.
2 Open the cold water inlet valve 12 (Fig. 7.1).
3 Slowly open each draw--- off tap and close it
only when clear water, free of bubbles, flows out.
7.4 Initial filling of the system
1 Open the c.h. flow and return valves.
2 Remove the front panel of the case (see the
section 9.2 in this manual.
3 Unscrew the cap on the automatic air purger-
valve 21 (Fig. 7.2) one full turn and leave open permanently.
4 Gradually open stopcock at the filling point
connection to the c.h. system until water is heard to flow; do not open fully.
21
20
Fig. 7.2
5 Open each radiator air vent starting at the
lowest point of the system and close it only when clear water, free of bubbles, flows out.
6 Purge the air fromthe pump b y unscrewingthe
pump plug 20 (Fig. 7.2); release the pump shaft by turning in the direction indicated by the arrow on the information plate.
7 Replace the pump plug.
8 Continue filling the system. The actualreading
should ideally be 1,3 bar and not less than 0,3 bar.
9 Close all air release valves on the c.h. system.
10 Inspect the boiler and the system for water
soundness and remedy any leaks discovered.
11 Cold flush the system to remove any loose par-
ticles and any system debris before starting the boiler for the first time
INSTALLATION
31
Page 38
Commissioning
The flushing procedure must be in line with BS7593 Treatment of Water in d.h.w. c.h. Sys -
tems.
When the installation and second filling are completed turn on the c.h. system and run it until the temperature has reached the boiler operating temperature. The system must then be immediately flushed through.
This procedure must be repeated twice more.
During this operation we highly recommend the use of a c.h. flushing detergent in the quan­titiesas specified by the appropriate manufac­turer, whose function it is to dissolve any foreignmatterwhichmaybeinthesystem.
The above operation could save the invalida-
INSTALLATION
tion of your boilers guaranteeand willalso pre­vent problems which you may experience in the future if an inhibitory is not used.
7.5 Lighting the boiler
Some products incorporate an anti cycling time delay. Itis normal whenfirst switchingthe boiler on for the boiler to operate on heating for a few sec­onds then switch off. After 3--- 4 minutes has elapsed the boiler will then re ignite and operate perfectly normally. The ignition delay cycle does not prevent normal operation of the boiler to pro­vide d.h.w..
If external controls are fitted (e. g. Timeclock, room thermostat) ensure they ”call for heat”.
1 Turn on the electricity supply to the boiler,
switching on the fused spur isolation switch. The appliance operation light 10 will flash every 4 seconds.
2 Turn the function selector 8 as in Fig. 7.3. The
appliance operation light 10 will flash every 2 seconds.
810
Fig. 7.3
The boiler will now go through an ignition se­quence and the burner will light.
If during the ignition attempt period the boiler fails to light, the full sequence control p.c.b. will go to lockout and the lock --- out signal lamp 6 will ap­pear.
To reset the boiler press and release the boiler re­set button 7 (Fig. 7.3).
7.6 Checking the gas pressure at
the burner
This boiler has been tested to the highest qual ­ity control standards.
The maximum and minimum gas pressures are already set during this quality control process however the checking procedure must be fol­lowedto ensure maximum operating efficiency from the boiler.
1 Remove the front panel of the case (see sec-
tion 9.2 in this manual).
2 Loosen the internal screw 37 (Fig. 7.4) on the
Outlet Pressure Test Point of the Gas Valve and connect a pressure gauge using a suitable hose.
3 Set the d.h.w. and c.h. temperature control
knobs to their maximum position.
32
Page 39
Commissioning
4 Switchontheboilerandopenatleastonehot
water tap fully.
5 Check the maximum gas pressure and com-
pare the value on the gauge with the value indi­cated in the sections 4.5, 4.6 or 4.7 (gas pressures at the burner), accordingly with the model of boiler installed.
6 Check the maximum gas flow at the gas meter
and compare the value indicated in the sec­tions 4.5, 4.6 or 4.7 (gas rate), accordingly with the model of boiler installed.
7 Switch off the boiler.
8 Disconnect the gas modulator coil by remov-
ing the electrical connector A (Fig. 7.4).
37
Fig. 7.4
9 Switchontheboiler.
10 Check the minimum gas pressure and com-
pare the value on the gauge with the value indi­cated in the sections 4.5, 4.6 or 4.7 (gas pressures at the burner), accordingly with the model of boiler installed.
11 Switch off the boiler and re ---connect the elec-
trical connector A to the modulator coil.
12 Access the main control panel (see section
6.10, follow steps 2 --- 5)
13 Switch on the boiler.
14 Check the ignition gas pressure by setting
dip --- switch ”3” (NO TAG) to the OFF position. Compare the value on the gauge with the value indicated in the sections 4.5, 4.6 or 4.7 (gas pressures at the burner), accordingly with the model of boiler installed. If the ignition gas pressure is not set correctly see section 7.7 in this manual for the adjust­ment procedure. If ignition gas pressure iscor­rect switch dip - -- switch ”3” to the ON position.
A
15 Switch off the boiler, turn off the hot water tap(s)
and disconnect the pressure gauge.
If the maximum and minimum gas pressures measuredaboveare notin accordance with the technicaldata (sections 4.5, 4.6 or 4.7 ) then ad­justment will be necessary. A full explanation of the gas pressure adjustment procedure is givenintheGasValvesectionoftheservice manual.If maximumand/orminimum gas pres­sures are adjusted then the ignition gas pres­sure must be checked and adjusted if necessary.
Important: after the gas pressure checks and any adjustment operations, all of the test points and adjustment devices must be sealed.
7.7 Adjusting the burner ignition
1 Turn off the boiler by means of the fused spur
isolation switch provided adjacent to the ap­pliance.
2 Open the gas valve outlet pressure test point
37 (Fig. 7.4) and connect the gauge.
3 Turn the boiler O N positioning the control se-
lectors 8 in the positions as shown in as in Fig. 7.5 and ensure that the timer selector switch and room thermostat, if fitted, are set to “heat demand”.
8
Fig. 7.5
4 Watch the gauge and check to see if the igni-
tion pressure registered corresponds to the va­lues as given in the Technical Data. Turn off the boiler and reignite it by turning the functionse­lector 8 to the OFF position and then back to that indicated in Fig. 7.5
5 Repeat this process two to three times leaving
30 second intervals between each ignition. Check the ignition pressures and visually
INSTALLATION
33
Page 40
Commissioning
check that the burner lights uniformly and in a controlled manner.
6 If the burner ignition is not uniformly controlled
then checks should be made to:
--- the flue installation and termination.
--- that the burner and injectors are clean.
--- that the boiler is set for the correct gas used
(see Section Gas Conversion of this manual)
7 If the ignition pressure recorded is not as indi-
cated in the TechnicalData thenrefer to section “Ignition gas pressure adjustment” of the Ser­vice Manual for the necessary adjustment pro­cedures.
Important: after the gas pressure checks and any adjustment operations, all of the test points must be sealed and replace the adjustment protection cap.
INSTALLATION
7.8 Adjustment of useful c.h.
output
The following procedure allows the output of the boiler for central heating to be adjusted to meet the system requirement. Adjusting the useful cen­tral output does not prevent the b oiler firing at maximum rate for domestic hot water production.
Refer to Fig. 7.13, Fig. 7.14 and Fig. 7.15 (de­pending on the gas used) and determine the cor­rect burner pressure appertaining to the output required f or the central heating requirement.
1 Remove the front panel of the case.
2 Loosen the screws B and remove the service
panel (Fig. 7.6).
B
4 Rotate the knob 9 as in Fig. 7.7
5 Turn the boiler ON positioning the function se-
lector 8 as indicated in Fig. 7.7 and ensure that the timer selector switch and room thermostat, if fitted, are set to “heat demand”. Run the boiler in c.h. mode (do not open any d.h.w. tap).
810
Fig. 7.7
6 Keep pressed the reset button 7 for about 10
secondsuntil thelock--- out signallamp 6 blinks (Fig. 7.7).
ON
LD1 LD2 LD3
Fig. 7.8
7 The lamps 10 should give the indication as in
Fig. 7.8 - -- Fig. 7.9. If not, press the reset button 7 (Fig. 7.7) repeat­edly to obtain it.
7 69
10
Fig. 7.6
3 Open the gas valve outlet pressure test point
37 (Fig. 7.4) and connect the gauge.
34
Where: Lamp OFF
Lamp ON
Fig. 7.9
8 Keep pressed the reset button 7 (Fig. 7.7) for
about 5 seconds. TheboilerrunsinC.hmodeandthelamp6 (Fig. 7.7) is switched OFF.
Page 41
Commissioning
The lamps 10 give the indication as in Fig. 7.8
--- Fig. 7.10
Where: Lamp OFF
Flashing lamp, alone or simulta­neously with an other lamp
Fig. 7.10
9 Rotate the knob 9 in Fig. 7.7 to obtain the pres-
sure to the burner to meet with the central heat­ing system requirements. Refer to the diagrams shown in Fig. 7.13, Fig. 7.14 or Fig. 7.15 By rotating clockwise the pressure increases.
10 Make a note of the position of the knob 9 and
recorded this in Fig. 7.11 below with an *.
810
Fig. 7.11
11 Keep pressed the reset button 7 for about 10
seconds until the lock--- out signal lamp 6 blinks.
Note: during the adjustment theboiler doesn’t op­erate.
12 Press the reset button 7 repeatedly (2 times)
until the lamps 10 give the indication as in Fig. 7.8 --- Fig. 7.12 (useful c.h. output adjust­ment mode).
Where: Lamp OFF
Fig. 7.12
13 Set the knob 9 on the position corresponding
to the position obtained on step 9.
7 69
Lamp ON
By turning the knob 9, the lock --- out signal lamp 6 blinks quickly (2 per second) indicating that the setting has changed and must b e me­morised by keeping pressed the reset button 7 for about 5 seconds until the lamps 10 all briefly simultaneously blink.
14 To reset the boiler to the normal operation turn
it OFF and ON by the function selector 8. Inany case, the boiler automatically resets to its nor­mal operation after 10 minutes.
kW
32 30 28 26 24 22 20 18 16 14 12 10
23456789101112
M90E.24S M90E.28S
M90E.32S
Fig. 7.13
kW
32 30 28 26 24 22 20 18 16 14 12 10
6 9 12 15 18 21 24 27
M90E.24S M90E.28S
M90E.32S
Fig. 7.14
Natural (G20)
mbar
Butane (G30)
mbar
INSTALLATION
35
Page 42
Commissioning
kW
32 30 28 26 24 22 20 18 16 14 12 10
8 111417202326293235
M90E.24S M90E.28S
M90E.32S
INSTALLATION
Fig. 7.15
Propane (G31)
mbar
7.9 Checking the ignition device
With the burner on high flame close the gas cock. About 10 seconds after, the lock --- out signal lamp
6(Fig.1.3onpage1)mustappear. To reset the boiler press and release the boiler
reset button 7 (Fig. 1.3 on page 1).
7.10 Checkingthefluesystem
Thefluesystemshouldbevisuallycheckedfor soundness. Check all clamps, gaskets and fixings aresecureandtight.
Ensure that the flue terminal is sited correctly in ac­cordance with the flue fitting instructions and Fig. 5.1 on page 20 of this manual.
To carry out a combustion check refer to the in­structions given in the section 9.5 of this manual.
Reference figures are given in the sections 4.5, 4.6 or 4.7 of this manual (Flue gas figures).
7.11 Instructing the user
Hand over this combined User & Installation man­ual and the Service manual tothe end user and ex­plain how to use the unit in both c.h. and d.h.w. modes.
Take the User step by step through the lighting in­structions.
Show the User how to switch off the appliance quickly and indicate the position of the electric supply isolator.
Explain the proper use and adjustment of all sys­tem controls; this will ensure the greatest possible fuel economy.
Explain the function and use of the function selec­tor.
Explain and demonstrate the function of time and temperature controls (if fitted).
Explain how to turn off the appliance for both short and long periods and advise on the precautions necessary to prevent damage should the appliance be inoperative when freezing condi­tions may occur.
Fill in the details required on the Boiler Guarantee Certificate and hand to the User advising them to return the correct section for boiler Guarantee reg­istration.
Finally, advise the User that, for continued safe and efficient operation, theappliance must beser­viced by a competent person at least once a year.
36
Page 43
8 GAS CONVERSION
8.1 Warnings
The commissioning of this boiler and sys­tem must only be undertaken by a pro­fessionally qualified person in accordance with the requirements of the Gas Safety In­stallation and Use Regulations and be ap­proved by C.O.R.G.I.
Components used to adapt it to the type of gas available must be genuine parts only.
8.2 Procedures
1 Check that the gas cock (13 in Fig. 8.1) fitted
under the boiler is turned off and the appliance is is switched off at the mains isolating spur .
13
Fig. 8.1
2 Remove the front and side panels of the case
(see the section General access and emptying hydraulic circuits in the service manual).
3 Takeoffthelidofthesealedchamber.
4 Take the front panel of the combustion
chamber off and remove the burner (29 on page 11). See section Ignition and detection electrodes in the service manual for detailed in­structions.
5 Carry out theconversion for the type of gas, re-
placing the burner injectors correctly.
6 Re --- assemble the burner, the front panel of the
combustion chamber and the lid of the sealed chamber.
7 Extract the control panel as explained in the
section 6.10 of this manual.
Closed position
8 Loosen the screws C and remove the service
panel (Fig. 8.2).
C
Fig. 8.2
9 Switch on the appliance at the mains isolating
spur.
10 Turn the boiler OFF positioning the function se-
lector 8 as indicated in Fig. 8.3
810
Fig. 8.3
11 Disconnect the C.h. temperature probe NTC
25 in Fig. 8.4
25
Fig. 8.4
12 Keep pressed the reset button 7 for about 10
seconds until the lock--- out signal lamp 6 blinks.
13 Connect the C.h. temperature probe NTC 25 in
Fig. 8.4
7 69
MAINTENANCE
37
Page 44
Gas conversion
ON
LD1 LD2 LD3
10
Fig. 8.5
14 Press the reset button 7(Fig. 8.3) repeatedly (4
times) until the lamps 10 give the indication as in Fig. 8.5 --- Fig. 8.6 (gas type mode).
Where: Lamp OFF
Lamp ON
Fig. 8.6
At this step it is possible to visualize the current set­ting by keeping the reset button 7 pressed for more than 5 seconds. The lamps 10 will flash a number of times corresponding to the setting of the knob 9 in Fig. 8.7.
Gas type
MAINTENANCE
NATURAL
Fig. 8.7
Gas supply
Natural gas
L.P.G. 4 165 mA
Setting No.
GAS
1
Position of knob 9
1 125 mA
Approx. Max current through the modulator device
L.P.G.
4
15 To change the setting turn the knob 9 on a posi-
tion corresponding to the gas used as shown in Fig. 8.7. By turning the knob 9, the lock --- out signal lamp 6 blinks quickly (2 per seconds) indicat­ing that the setting has changed and must be memorised.
16 To memorize the setting keep pressed the
reset button 7 for about 5 seconds until the lamps 10 briefly blinks simultaneously.
17 Open the gas cock (13 in Fig. 8.9)
13
Fig. 8.9
18 To reset the boiler to the normal operation turn
it ON by the function selector 8 on the desired operation and checking the ignition pressure and that the burner lights up uniformly. In any case, the boiler automatically resets to its nor­mal operation after 10 minutes.
Factory setting = Natural gas (as illustrated)
19 Calibrate the gas valve according to the in-
structions given in the service manual, section Modulating gas valve --- Adjustment.
20 Set the correct gas pressure for centralh eating
output required, see section 7.8 in this manual.
21 Stick on the inside of the left hand side panel
9
adjacent to the data badge the self--- adhesive label (included with the conversion kit) indicat­ing the type of gas, and the gas pressures to which the appliance has been set.
22 Replace the service panel, the front and side
panels of the case.
Open position
Fig. 8.8
38
Page 45
9 MAINTENANCE
9.1 Warnings
The procedures detailed in this chapter must be carried out only by a professionally qualified person. Thus you are advised to
contact an Authorised Service Agent.
For Ireland (IE), the servicing work must be carried out by a competent Person
For efficient and continuous operation of the boiler you are advised to have, at least once a year, maintenance and cleaning done by an Approved Service engineer.
Isolate the appliance from the electricity supply by turning off the fused spur isolation switch adjacent to the appliance and turn off the gas cock, before carrying out any pro-
cedures, whatsoever, for cleaning, mainten­ance, opening or dismantling boiler panels.
9.2 Dismantling the external
panels
Front panel
1 Loosen the two screws A (Fig. 9.1).
2Liftandremovethepanel.
Side panels
3 Loosen the screws B. Bring the bottom of the
panels away from the boiler and lift them, free­ingthemfromthetophooks(Fig.9.2).
Fig. 9.2
9.3 Emptying the d.h.w. system
1 Turn off the d.c.w. inlet isolating valve (12 in
Fig. 9.3) and turnon thehot watertaps and any drain cocks.
A
B
MAINTENANCE
11
Fig. 9.1
131215
Fig. 9.3
Closed position
9.4 Emptying the c.h. system
1 Close the c.h. isolating valves (11 and 15 in
Fig. 9.3).
2 Open the central heating drain cock (17 in
Fig. 9.4).
39
Page 46
Maintenance
17
Fig. 9.4
3 A small quantity of water will remain in the
d.h.w. heat exchanger after draining. If the boiler is being drained to prevent freezing, the d.h.w. heat exchanger must be removed and inverted to d rain fully or an antifreeze solution added.
Air--- Flue exhaust Sampling points
9.5 Combustion analysis check
To carry out a combustion analysis:
1 remove the front panel of the case (see the sec-
tion 9.2 in this manual).
MAINTENANCE
2 Remove the plugs indicated in Fig. 9.5.
40
Fig. 9.5
Reference figures are given in the sections 4.5 or
4.6 of this manual (Flue gas figures).
9.6 Cleaning the primary heat
exchanger
1 Takeoffthefrontofthecase.
2 Take off the removable front of the air---tight
chamberand thefront panelof the combustion chamber.
If you notice dirt on the fins of the primary heat ex­changer (31 on page 11):
3 cover the sloping surfacesof the burner (29 on
page 11) entirely in a protective layer (sheets of newspaper or similar).
4 Brush out the primary heat exchanger (31 on
page 11) with a bristle paintbrush.
NOTE --- When removing the airtight chamber cover it is not necessary to remove the screws lo­cated at the top edge on either side.
Page 47
Maintenance
9.7 Checking the pressurisation
in the expansion vessel
Empty the central heating system as described in section 9.4 of this chapter and check that the pres­sure in the expansion vessel is not less than 1 bar. See also section 4.4 page 13 of this manual.
If the pressure is lower, take steps to correct the pressure level.
9.8 Cleaning the burner
The sloping and multi--- gas type burner (29 on page 11) does not need special maintenance, but it is sufficient to dust it with a bristle paintbrush.
To reach the burner:
1 Takeoffthefrontofthecase.
2 Take off the removable front of the air---tight
chamberand thefront panelof the combustion chamber.
3 Bru sh out the burner with a bristle paintbrush.
NOTE --- When removing the airtight chamber cover it is not necessary to remove the screws lo­cated at the top edge on either side.
9.9 Checking the flue
Have the integrity of the flue outlet pipe (45 on page 12) air intake pipe (46 on page 12), checked periodically, the venturi device* (42 on page 12) cleaned and the efficiency of the flue safety circuit checked at least once a year.
* For details see the section Fan, venturi device and air pressure switch in the service manual.
For all the above maintenance operations it is ad­visable to call an approved Service Engineer.
9.10 Visual inspection of
appliance
Visually inspect all water joints, seals and connec­tions for any evidence of leakage and retighten, grease or replace them as necessary.
9.11 Gas pressures and
soundness
Check appliance for gas soundness. Recheck op­erational pressures and adjust as necessary as described in section 7.6 page 32 of this manual.
MAINTENANCE
41
Page 48
Page 49
Page 50
Page 51
Page 52
*1796209158*
07/05
2008
N
17962.0915.8 1908 52A5 UK
Biasi UK Ltd Newman Park, Western Way Wednesbury, WS10 7BJ Sales Tel No: 0121 506 1340 Sales Fax No: 0121 506 1360 Service Tel No: 0121 506 1350 Service Fax No: 0121 506 1370 www.biasi.co.uk
Loading...