biasi M96.24SM/C, M96.28SM/C, M96.28SR/C User guide

Page 1
Wall hung, fan flue, room sealed, high efficiency gas boiler
User manual and Installation instructions
RIVA COMPACT HE
Models
M96.24SM/C M96.28SM/C M96.28SR/C
This product has an energy rating B on a scale of A to G For more information see www.boilers.org.uk This is a certification mark
Page 2
Congratulations on your choice.
RIVA COMPACT HE
They are fully electronically controlled and have electronic ignition. The materialsthey are made of and the control systems they areequippedwithgive you safety,
a high level of comfort and energy savings to allow you to get the greatest benefit out of independent heating.
RIVA COMPACT HE
the water vapour formed during the combustion is condensed out. This allows a gain of useful heat that otherwise would be lost.
Remember that...
n The manual
must be read thoroughly, so that you will
---
be able to use the boiler in a safe and sen­sible way;
must be carefully kept. It may be necess-
---
ary for reference in the future.
n First lighting up
competent and responsible engineer.
n The manufacturer
disclaim all liability for any translations of
---
the present manual from which incorrect in­terpretation may occur
cannot be held responsible for non---ob-
---
servance of instructions contained in this manual or for the consequences of any pro­cedure not specifically described.
are condensing high efficiency sealed chamber fan flue gas boilers.
allow a higher efficiency by reducing the flue gas temperature such that
valve and consequent escape of water, if not connected correctly to the drain.
the installer has connected the conden-
---
sate outlet to a suitable drain pipe.
n On detecting the smell of gas
don’t operate any electrical switches, the
---
telephone or any device that may produce sparks;
open the windows and doors at once to
must be carried out by
---
create a draught of air which will purge the area;
shut off the gas cocks;
---
get the assistance of a qualified person.
---
n Do not touch the appliance
the body that are wet or damp and/or bare feet.
n Do not block or modify
outlet and pipework
with parts of
the condensate
Using the boiler...
n Before lighting the boiler
vised to have a professionally qualified per­son check that the installation of the gas supply
is gas--- tight;
---
is of the correct gauge for the flow to the
---
boiler;
is fitted with all the safety and control de-
---
vices required by the current Regulations.
n Ensure that
the installer has connected the pressure
---
relief valve outlet to a drain pipe. The manu­facturers are not responsible for damage caused by opening of the pressure relief
you are ad-
n In case of structural work
ance near the exhaust duct and/or fume ex­haust devices or their attachments, turn off the appliance. On completion of the work, have a professionally qualified person check their efficiency.
n Repairs
ried out only by an approved engineer, using genuine spare parts. Thus do no more than switching off the boiler yourself (see the in­structions).
n Your boiler
a temperature less than boiling point;
--- must be connected to a central heating system and/or a hot water supply system, compatible with its performance and output;
(under guarantee) must be car-
allows heating up of water to
or mainten-
Page 3
--- can be used only for those purposes for
which it has been specially designed;
--- must not be touched by children or by
those unfamiliar with its operation;
--- must not be exposed to weather condi-
tions.
n During the operation
it is quite normal
that the boiler produces a white plume of condensation vapour from the flue terminal. This is due to the high efficiency of the ap­pliance and may be particularly evident with low outdoor temperatures.
Safe handling of
substances
Biasi products are manufactured in accordance with ISO 9000 and do not, and willnot, contain any hazardous materials or substances such as as­bestos, mercury or C.F.C.’s. The appliance packaging does not contain any substances, which maybe considered a hazard to health.
Combustion chamber panels
Material: mineral fibers
Known hazards --- Some people can suffer red­dening and itching of the skin. Fibre entry into the eye will cause foreign body irritation, which can cause severe irritation to people wearing contact lenses. Irritation to respiratory tract.
Precautions --- Dust goggles will protect eyes. People with a history of skin complaints may be particularly susceptible to irritation. High dust le­vels are only likely to arise following harsh ab­rasion. In general, normal handling and use will not present high risk, follow good hygiene prac­tices,wash hands before, touching eyes,consum­ing food, drinking or using the toilet.
First aid --- Medical attention must be sought fol­lowing eye contact or prolonged reddening of the skin.
Thermostat / Temperature gauge
Description --- Sealed phial and capillary contain­ing liquid.
Known hazards --- irritating to skin, eyes and throat. Vapour is harmful. Inflammable --- do not extinguish with water.
Precautions --- Do not incinerate. Avoid contact with broken/leaking phials. Do not purposely puncture.
First aid medical attention must be sought follow­ing eyes/skin contact, wash with clean water.
Appliance category II Country of destination: United Kingdom
This appliance conforms with the EEC directive 90/396 and, consequently, it hasthe rightto make use of the brand name
Moreover, the appliance conforms with the EEC directive 87/308relative to the prevention and elimina­tion of radio disturbances.
The appliance is built to comply with the regulation now in force regarding gas appliance’s safety and the European regulation now in force relative to safety of household and similar electricalappliances.
The manufacturer, in the continuous pocess to improve his products, reserves the right to modify the data expressed in the present documentation at any time and without prior notice.
The present documentation is an informative support and it cannot be considered as a contract to­wards third parties.
Gas G20 20 mbar, G30 29 mbar, G31 37 mbar
2H3+
Page 4
Boiler installation and commissioning tips
n The installation
a qualified person who will be responsible for observing the current Regulations.
must be carried out by
Installing the boiler...
Do not forget to remove the transit caps
n
and plugs from the boiler connections these are fitted to every boiler.
Keep the boiler clear of dust during in-
n
stallation and in particular do not allow any dust or debris to enter the top of the boiler where the flue connection is made. It is rec­ommended that you put a dust sheet over the top of the boiler until you are ready to make the flue connection.
Because every boiler is fired and tested
n
live at the factory, a small amount of water re­mains within the boiler. It is possible for this water to initially cause the pump to seize. It is therefore recommended that the pump rotor be manually turned to free its rotation before turning the boiler on.
Remember to release the auto air purge
n
before filling the boiler. See the instructionsto identify the location of this device.
Do not remove the cap of the pressure
n
test points of the air switch (top left side of the boiler).
You are strongly advised to flush out the
n
system both cold and hot in order to remove system and installation debris.
It is also sensible to initially fire and com-
n
mission the boiler before connecting any ex­ternal controlssuch as aroom thermostat. By this method if you have a subsequent prob­lem following the addition of an external con­trol you can eliminate the boiler from your fault analysis.
Do not forget to range rate the boiler to
n
suit the system requirements. This pro­cedure is covered in the commissioning sec­tion of the installation manual.
If the boiler is fitted with a digital pro-
n
grammer, when setting the times for auto­matic operation, remember that for every “ON” time there must be an “OFF” time to fol­low and that on every occasion you enter a time you must also indicate which days that you want the boiler to follow the timed set­tings.
Some products incorporate an anti cycl-
n
ing time delay. It is normal when first switch­ing the boiler on for the boiler to operate on heating for a few seconds then switch off. After 3---4 minutes has elapsed the boiler will then re ignite and operate perfectly normally. The ignition delay cycle does not prevent normal operation of the boiler to provide d.h.w.
If you are in any doubts as to the installa-
n
tion or operation of the boiler please read the instruction manuals thoroughly and then if necessary contact Biasi UK for advice and assistance.
Please remember that if you are in any doubt about the installation of this product you can contact our Technical Helpline on tel. 01902 304400
Page 5
TABLE OF CONTENTS
1 Appliance description 2. . . . . . . . . .
1.1 Overview 2. . . . . . . . . . . . . . . . . . . . . .
1.2 Control panel 2. . . . . . . . . . . . . . . . . .
1.3 Isolation valves 2. . . . . . . . . . . . . . . . .
1.4 Technical data 2. . . . . . . . . . . . . . . . .
1.5 Operation lights 3. . . . . . . . . . . . . . . .
2 Instructions for use 4. . . . . . . . . . . .
2.1 Warnings 4. . . . . . . . . . . . . . . . . . . . . .
2.2 Refilling procedure 4. . . . . . . . . . . . . .
2.3 Ignition 5. . . . . . . . . . . . . . . . . . . . . . . .
4 Technical information 12. . . . . . . . . .
4.1 Overview 12. . . . . . . . . . . . . . . . . . . . . .
4.2 Main diagram (combi) 13. . . . . . . . . . .
4.3 Main diagram (c.h. only) 14. . . . . . . . .
4.4 Hydraulic specifications 15. . . . . . . . .
4.5 Expansion vessel 15. . . . . . . . . . . . . . .
4.6 Technical data M96.24SM/... 16. . . . . .
4.7 Technical data
M96.28SM/... M96.28SR/... 18. . . . . . .
5 General requirements 20. . . . . . . . . .
5.1 Related documents 20. . . . . . . . . . . . .
5.2 Location of appliance 20. . . . . . . . . . .
5.3 Flue system 20. . . . . . . . . . . . . . . . . . . .
5.4 Gas supply 21. . . . . . . . . . . . . . . . . . . .
5.5 Air supply 21. . . . . . . . . . . . . . . . . . . . .
5.6 Ventilation 21. . . . . . . . . . . . . . . . . . . . .
5.7 Condensate drain 21. . . . . . . . . . . . . .
5.8 Water circulation (c.h.) 21. . . . . . . . . . .
5.9 Domestic water 22. . . . . . . . . . . . . . . . .
5.10 Water treatment 22. . . . . . . . . . . . . . . .
5.11 Electrical supply 23. . . . . . . . . . . . . . . .
6 Installation 24. . . . . . . . . . . . . . . . . . . .
6.1 Warnings 24. . . . . . . . . . . . . . . . . . . . . .
6.2 Precautions for installation 24. . . . . . .
2.4 C.h. circuit temperature 5. . . . . . . . . .
2.5 D.h.w. temperature (combi) 6. . . . . .
2.6 Extinguishing 6. . . . . . . . . . . . . . . . . .
2.7 Built in time switch 7. . . . . . . . . . . . . .
3 Useful advice 10. . . . . . . . . . . . . . . . .
3.1 Central heating 10. . . . . . . . . . . . . . . . .
3.2 Frost protection 10. . . . . . . . . . . . . . . .
3.3 Periodic maintenance 10. . . . . . . . . . .
3.4 External cleaning 10. . . . . . . . . . . . . . .
3.5 Operational faults 10. . . . . . . . . . . . . . .
6.3 Installing the bracket 24. . . . . . . . . . . .
6.4 Overall dimensions 25. . . . . . . . . . . . .
6.5 Joints 25. . . . . . . . . . . . . . . . . . . . . . . . .
6.6 Mounting the boiler 25. . . . . . . . . . . . .
6.7 Fitting the flue system 26. . . . . . . . . . .
6.8 Choice of flue 26. . . . . . . . . . . . . . . . . .
6.9 Electrical connections 27. . . . . . . . . . .
6.10 External frost protection 29. . . . . . . . .
6.11 Connecting a M96.28SR/...
system boiler to a cylinder 29. . . . . . .
7 Commissioning 31. . . . . . . . . . . . . . .
7.1 Electrical installation 31. . . . . . . . . . . .
7.2 Gas supply installation 31. . . . . . . . . .
7.3 Filling the d.h.w. system 31. . . . . . . . .
7.4 Initial filling of the system 31. . . . . . . .
7.5 Condensate pipe and traps 32. . . . . .
7.6 Lighting the boiler 32. . . . . . . . . . . . . .
7.7 Checking the gas pressure
at the burner 32. . . . . . . . . . . . . . . . . . .
7.8 Adjusting the burner ignition 33. . . . .
7.9 Adjustment of useful c.h. output 34. .
7.10 Checking the ignition device 35. . . . .
7.11 Checking the flue system 35. . . . . . . .
7.12 Checking the condensate drain pipe 35
7.13 Instructing the user 35. . . . . . . . . . . . .
USE
INSTALLATIONMAINTENANCE
8 Gas conversion 36. . . . . . . . . . . . . . .
8.1 Warnings 36. . . . . . . . . . . . . . . . . . . . . .
8.2 Procedures 36. . . . . . . . . . . . . . . . . . . .
9 Maintenance 37. . . . . . . . . . . . . . . . . .
9.1 Warnings 37. . . . . . . . . . . . . . . . . . . . . .
9.2 Dismantling the external panels 37. . .
9.3 Emptying the d.h.w. system (combi) 37
9.4 Emptying the c.h. system 37. . . . . . . .
Abbreviations used in the manual C.h. = Central heating D.h.w. = Domestic hot water D.c.w. = Domestic cold water
9.5 Combustion analysis check 38. . . . . .
9.6 Cleaning the primary heat exchanger 38
9.7 Checking the pressurisation
in the expansion vessel 38. . . . . . . . . .
9.8 Cleaning the burner 38. . . . . . . . . . . . .
9.9 Checking the flue 38. . . . . . . . . . . . . . .
9.10 Drain pipe inspection 38. . . . . . . . . . . .
9.11 Visual inspection of appliance 38. . . .
9.12 Gas pressures and soundness 38. . .
1
Page 6
1 APPLIANCE DESCRIPTION
*notonM96.28SR/...boile
r
1.1 Overview
USE
Fig. 1.1
1 Case front panel
2 Control panel
3 Control panel cover
1.2 Control panel
4 C.h. circuit temperature and pressure gauge
5 Time switch (c.h. control) *
6 Lock---out signal lamp
7 Lockout reset button
8 Function selector and c.h. temp. control knob
9 D.h.w. temperature control knob *
10 Appliance operation lights
1.3 Isolation valves
1
16
15
14
13
2
3
Fig. 1.2 (bottom view of the boiler)
11 Condensate drain pipe
12 C.h. return valve
13 D.c.w. inlet valve *
14 Gas inlet valve
15 D.h.w. outlet pipe *
16 C.h. flow valve
12
11
1.4 Technical data
For detailed technical data see section 4.6 or 4.7 of this manual.
M96.24SM/... M96.28SM/...
89 7 6 4510
M96.28SR/...
Fig. 1.3
2
Page 7
Appliance description
LampOFFLampONFlashinglamp,aloneorsimultaneously
Flashinglamp,alternatewithanother
*notonM96.28SR/...boile
r
1.5 Operation lights
Three lights (10 in Fig. 1.3) give detailed indication regarding the operation of the boiler.
The following table gives the relationship between each of the possible light combinations and their meaning.
USE
with an other lamp.
A short pulse every 4 seconds: stand--- by condition Function selector in position. Anti---freeze system active
1 second pulse every 2 seconds: normally operating boiler. Function selector in or position
C.h. operation
D.h.w. operation *
Frost protect operation
D.h.w. operation Excessive temperature on primary circuit *
Faulty c.h. temperature probe NTC
lamp.
Faulty d.h.w temperature probe NTC *
Faulty primary circuit (no water or absence of flow)
Lack of burner ignition (no ignition signal from the full seqence ignition device)
Ignition gas pressure adjustment
Minimum gas pressure adjustment
3
Page 8
2 INSTRUCTIONS FOR USE
2.1 Warnings
Biasi UK Ltd support the Benchmark initiat­ive. The Benchmark Log Book is located at the back of this manual and should be com­pleted by the Installing/Commisssioning Engineer and handed over to the User for
USE
future reference by other visiting En­gineers. Also included is the Service Inter­val Record card that should be completed by the Service Engineer following the an­nual service maintenance of the boiler and system.
All CORGI Registered Installers carry a CORGI ID card, and have a registration number. Both should be recorded in your Benchmark Log Book. You can check your installer is registered by calling CORGI di­rect on 01256 372300.
In order to guarantee safety and correct oper­ation, it is essential that all the tests are carried out by a competent and responsible service engineer before lighting up the boiler.
The tests are described in the installation in- structions in section 7 commissioning.
Ensure that the c.h. circuit is regularly filled with water (even if the boiler is only used for d.h.w. supply) checking thatthe pressure indi­cated on the temperature and pressure gauge 4 is not lower than that shown in Fig. 2.2.
If the pressure reading on the pressure gauge is belowthat shown in Fig. 2.2, then the system willrequire topping up. A filling loop is normally provided by the installer for this purpose.
If you are in any doubt regarding this pro­cedure you are advised to contact your In­staller or an Approved Engineer.
This appliance is provided with a built in anti--­freeze system that operates the boiler when the temperature is below 4 ° C Therefore, when the boiler is not lit or used in cold weather, with consequent risk of freezing
do not switch off the boiler at the fused spur isolation switch or close the gas inlet cock
When you do not expect to use the boiler for a long period and the boiler is not to be used for frost protection then follow the instructions given in section 2.6 on page 6.
2.2 Refilling procedure
1 Isolate the boiler from the electrical supply at
the fused spur. Reconnect the filling loop as demonstrated in Fig. 2.1.
Control valve
Double check valve
Temporary connection
Supply pipe
(cold water inlet)
C.h. return pipe
Fig. 2.1
2 Open the valves of the filling loop and watch
the gauge until it reaches normal filling pres­sure as shown in Fig. 2.2.
Fig. 2.2
3 Close the valves and remove the filling loop.
If you experience any difficulty with the oper­ation of the boiler, switch off the boiler immedi­ately at the fused spur isolation switch and contact your Installer or an approved Service Engineer
Air introduced into the boiler during this filling pro­cess will vent through the automatic air purger fitted to the boiler. You may also find it necessary to vent air from your radiator circuit using your radiator key, however be aware that excessive venting will cause the pressure in the system to drop.
Always ensure thatthe pressure gauge isset at the
.
required pressure.
Control valve
4
Normal filling pressure
4
Page 9
Instructions for use
2.3 Ignition
1 Check that the valves located in the lower part
of the boiler are open (Fig. 2.3).
Open position
Fig. 2.3
2 Turn on the electricity supply to the boiler,
switching on the fused spur isolation switch. The appliance operation light 10 (Fig. 2.4) will flash every 4 seconds (stand---by condition).
3 If the boileris to be used for c.h. and d.h.w posi-
tion the function selector 8 as in Fig. 2.4 (combi) or in Fig. 2.5 (c.h. only). The appliance operation light 10 will flash every 2 seconds (operating boiler).
810
USE
810
Fig. 2.6
2.4 C.h. circuit temperature
The output temperature of c.h. water is adjustable from a minimum of about 38°C to a maximum of about 85°C (Fig. 2.7), by turning the function se­lector (8).
Adjustment of c.h. output on the boiler is auto­matic. The greatest output pre --- set in the factory can, however, be reduced in level according to actual system requirements; this does not affect the maximum output in d.h.w. operation.
Such adjustments must be carried out by a quali­fied person; therefore we advise you to contact your installer or Service Agent.
Adjustment of the boiler temperature alters the gas flow at the burner according to the thermal de­mand in the system. So it is usual to see the burner lit at the minimum level for more or less long periods.
Fig. 2.4
810
Fig. 2.5
4 If d.h.w. supply only is required (combi), posi-
tion the function selector 8 as in Fig. 2.6. The appliance operation light 10 will flash every 2 seconds (operating boiler).
Minimum
Maximum
Fig. 2.7
5
Page 10
Instructions for use
Adjustment
In order to achieve optimal settings for economy and comfort, we recommend adjusting the oper­ating temperature of the c.h. water according to the outside temperature, positioning the knob as follows:
USE
From 5 to 15 ° C
Between
---5 and +5 ° C
Lower than
---5 ° C
Fig. 2.8
Your qualified installer will be able to recommend the most suitable adjustment for your system.
The temperature and pressure gauge (4, Fig. 1.3 on page 2) will allow you to check that the settem­perature is obtained.
The adjustment system integrated within the boiler automatically controls the flow of gas to the burner in order to keep the temperature of d.h.w. delivered constant, between the limits of maxi­mum and minimum output.
Where the demand is at a low level or with the tem­perature set to the minimum, it is normal to see a cycle of lighting and extinguishing of the burner when running.
Adjustment
It is advisable to adjust the d.h.w. temperature to a level commensurate with the demand, minimis­ing the need to mix with cold water. In this way, the automatic control facilities will be fully exploited.
Moreover, where the amount of limescale present in the water may be particularly great, not exceed­ing the position in ture control knob 9 corresponding to about 50°C (Fig. 2.10), minimises annoying incidences of scale deposits and clogging.
Fig. 2.10
of the d.h.w. tempera-
2.5 D.h.w. temperature (combi)
The temperature of the d.h.w. leaving the boiler can be varied from a minimum of about 35°C to a maximum of about 55°C (Fig. 2.9), by turning the temperature control knob 9.
Minimum
Maximum
Fig. 2.9
Adjustment of the d.h.w. temperature is complete­ly separate from that of the c.h. circuit.
9
9
Fig. 2.10
In these cases, however, it is advisable to install a small water treatment device or softener. With such a device you should avoid periodic descal­ing.
Consequently,the d.h.w.heat exchanger will keep its performance consistent for a longer period of time with resulting gas savings.
If the demand for d.h.w. is so great as to prevent reaching a high enough temperature, have the ap­propriate output limiting valve installed by your in­staller or an Authorised Service Engineer.
2.6 Extinguishing
To turn the boiler off set the function selector 8 to the position shown in Fig. 2.11 (combi) or Fig. 2.12 (c.h. only).
6
Page 11
Instructions for use
The appliance operation light 10 will flash every 4 seconds.
810
Fig. 2.11
810
2.7 Built in time switch (combi)
The combi boilersare equipped with a built in elec­tronic time switch (5, Fig. 1.3 on page 2) which controls the c.h. operation.
G
BCDEF
Fig. 2.14
H
A
USE
Fig. 2.12
When you do not expect to use the boiler for a long period:
1 Switch off the electricity supply to the boiler, by
means of the fused spur isolation switch;
2 Shut off the gas supply cock 14 and the valves
for the water circuits fitted under the boiler (Fig. 2.13).
3 Empty the water circuits, if necessary, as
shown in the installation instructions in the sec­tion maintenance.
14
Fig. 2.13
Closed position
Display and control panel
A Mode selector switch
B Reset button
C Enter button
D Increase “+” setting button
E Decrease “--- ” setting button
F On--- off button
G Time display
H ON--- OFF display
Setting the current time
Note: with a new unit or when the reset button B has been pressed and the selector switch A is to
the position, the time display G is flashing.
Set the mode selector switch A to the position and press the buttons D or E until the current time appears in the display G.
The clock starts by moving the switch A to the AUTO position.
Setting example shown in Fig. 2.15: Current time 16.30.
7
Page 12
Instructions for use
A
A
USE
Fig. 2.15
Setting the switching time
20 memorylocations are available, corresponding to 10 on---off sequences.
Set the mode selector switch A to theC1position. The symbols shown in Fig. 2.16 appears in the display.
Fig. 2.16
Press the buttons D or E to set the desired ON time.
Press the “enter” button C to confirm the setting and to continue programming the OFF time.
Set the OFF time as explained above for the ON setting and confirm by pressing the “enter” button C. Proceed in the same way for other settings.
Setting example shown in Fig. 2.17: A --- ON time 7.45. B --- OFF time 10.30.
Fig. 2.18
Note: when the mode selector switch A is in the
AUTO
fused spur isolationswitch, the display H indicates only the OFF state. The other indications are blanked.
Reading the timed settings
Set the mode selector switch A to theC1position. The symbols shown in Fig. 2.16 appears in the
A
display.
Press the “enter” button C. Each time the button is pressed the display showsthe details of the next setting.
Changing or deleting the timed settings
Set the mode selector switch A to theC1position. The symbols shown in Fig. 2.16 appears in the display.
Press the “enter” button C until the display shows the setting to be modified or deleted.
The time setting can be modified now by pressing button D or E and the operation can be switched on or off by pressing the button F.
To delete a time set press the button D or E until the symbols shown in Fig. 2.16 appears in the time display G.
The new settings are memorized by moving the switch A to a different position.
position and the boiler is switched off at the
A B
Fig. 2.17
Activating the timed settings
Set the mode selector switch A to the tion shown in Fig. 2.18.
The current time appears in the display. The ON --­OFF display H indicates the current state of oper­ation (according to the settings).
8
AUTO
posi-
Manual operation
The operation of the time switch can be forced on or off constantly or for a timed period.
To force set the mode selector switch A to the tion. The symbols shown in Fig. 2.19 appears on the display.
constantly
on or off the timer operation
TIMER
posi-
Page 13
Instructions for use
Fig. 2.19
The operation can be switched permanently on or off by pressing the button F and leaving the switch A in the
To force mode selector switch A in the
Set the time delay by pressing the button D or E and the operation can be forced on or off by pres­sing the button F.
The time delay can be set within the following ranges:
1 to 23 hours with steps of 1 hour 1 to 27 days with steps of 1 day
The time delay setting is activated by moving the switch A to the The ON --- OFF display H flashesindicating that the current state of operation has been forced.
TIMER
a timed delay
position.
AUTO
on or off operation, set the
TIMER
position.
position.
To delete the timed delay setting, setthe mode se­lector switch A in the button D or E until the symbols shown in Fig. 2.19 appears in the display and then set the mode se­lector switch A to the
Setting example shown in Fig. 2.20: forced ON state for 4 hours.
Fig. 2.20
Resetting
To completely reset the timer, press the reset but­ton with a pointed object (pencil).
CAUTION: pushing the reset button will complete­ly erase the settings as well as all the data, includ­ing the current time.
TIMER
AUTO
position, press the
position
USE
9
Page 14
3 USEFUL ADVICE
3.1 Central heating
---
general check of the appliance’s operation.
For reasonably economical service install a room thermostat.
Never shut off the radiator in the area where the room thermostat is installed.
USE
If a radiator (or a convector) does not heat up, check that no air is present in it and that its valve is open.
If the ambient temperature is too high, do not alter the radiator valves. Reduce the central heating temperature instead by means of the room ther­mostat and the function selector (8 in Fig. 3.1).
8
Fig. 3.1
3.4 External cleaning
Before carrying out any cleaning, disconnect the appliance from the electrical mains, using the fused spur isolation switch fitted adjacent to the appliance.
To clean the external panels, use a cloth soaked in soapy water. Do not use solvents, abrasive powd­ers or sponges.
Do not carry out cleaning of the appliance and/or its parts with readily flammable substances (for example petrol, alcohols, naphtha, etc.).
3.5 Operational faults
If the lock--- out signal lamp comes on
this indicates that the safety lock--- out 6 (Fig. 3.2) has stopped the boiler
To re --- start the boiler, it is necessary to press the boiler reset button 7 (Fig. 3.2).
3.2 Frost protection
This appliance is provided with a built in anti--­freeze system that operates the boiler when the temperature is below 4 ° C Therefore, when the boiler is not lit and used in cold weather, with consequent risk of freezing
not switch off the boiler at the fused spur isola­tion switch or close the gas inlet cock
.
do
3.3 Periodic maintenance
For efficient and continuous operation of the boiler, it is advisable to arrange maintenance and cleaning by an Authorised Service Centre En­gineer, at least once a year.
During the service, the most important compo­nents of the boiler will be inspected and cleaned. This service can be part of a maintenance con­tract.
In particular, you are advised to have the following checks carried out:
---
primary heat exchanger;
---
domestic hot water heat exchanger;
---
burner;
---
exhaust fume duct and flue;
---
pressurisation of the expansion tank;
---
filling up of the central heating circuit;
---
bleeding of air from the central heatingsystem;
6
7
Fig. 3.2
For the first lighting up and following maintenance procedures for the gas supply, it may be necess­ary to repeat the resetting operation several times so as to remove the air present in the pipework.
Safety lock--- out may occour even in case of an blockage of the condensate drainage (e.g. plugged drain pipe).
It is advisable to check the condensate drainage pipe and traps for cleaness.
In case of persistent lock--- out call a competent and responsible service engineer.
If noises due to air bubbles are heard during operation...
you should check that the pressure on the tem­perature and pressure gauge (Fig. 2.2 on page 4) is not below the correct setting. If required, top up the system correctly, as de­scribed in the section 2.2 of this manual. Bleed any air present in the radiators, if necessary.
10
Page 15
Useful advice
If the pressure on the temperature and pres­sure gauge (4 on page 2) has gone down...
it is necessary to top up the appliance with water again, so as to raise the pressure to an adequate levelas described in the section 2.2 of this manual.
If topping up with water has to be done very fre­quently, have the system checked for leaks.
If water comes out of the pressure relief valve
Check on the temperature and pressure gauge (4 on page 2) that the pressure in the central heating circuit is not close to 3 bars. In this case, tempera­ture rise in the circuit can cause the pressure relief valve to open.
So that this does not happen and to decrease the pressure to a normal value, it is advisable to vent some of the water in the appliance through the bleed valves present in the radiators.
If in time, a reduction in domestic hot water supply is observed...
The likely causes may be impurities caught in the domestic hot water flow switch filter or limescale deposited in the domestic hot water heat ex­changer. It is advisable to have the appliance cleaned out by an Authorised Service Centre En­gineer.
If water should occasionally leak from the boiler...
shut off the valves positioned under the boiler (Fig. 2.13 on page 7) and call an Authorised Ser­vice Centre Engineer.
If the left appliance operation light 10 (Fig. 3.3) flashes very quickly the boiler is detecting a fault.
10
Fig. 3.3
In this case or in case of problems other than those mentioned here, switch off the boiler, as described in section 2.6 on page 6 and call a competent and responsible service engineer.
USE
11
Page 16
4 TECHNICAL INFORMATION
4.1 Overview
32
31
30
INSTALLATION
29
28
27
26 25
24
23
Fig. 4.1
11 Condensate drain pipe 12 C.h. return valve 13 Domestic cold water inlet valve 14 Gas inlet valve
33
34 37
35
20
2122
19
36
17
18
15 D.h.w. outlet pipe 16 C.h. flow valve 17 Condensate trap
18 Main circuit drain valve
19 Automatic air purger valve
20 Pump
21 Pump vent plug
22 Modulation gas valve
23 D.h.w. temperature probe NTC
24 Primary circuit flow switch
25 C.h. temperature probe NTC
26 Three---way diverter valve
27 Flame--- detecting electrode
28 Ignition electrodes
29 Burner
30 Combustion chamber
31 Primary heat exchanger
32 Fan
33 Air switch pressure test points
34 Flue thermostat
35 Air pressure switch
36 Co ndensing heat exchanger
37 Safety thermostat
38 D.h.w. flow switch
39 C.h. pressure relief valve
40 Modulation operator
41 Gas valve outlet pressure test point
42 Gas valve inlet pressure test point
43 D.h.w. heat exchanger
44 C.h. expansion tank
45 By --- pass valve
46 Venturi device
47 Domestic water circuit filter
48 D.h.w. flow limiter
49 Flue outlet pipe
50 Air intake pipe
12
Page 17
Technical information
4.2 Main diagram (combi)
50
34
36
49
46
27
28
17
40
11
31
29
32
41
42
22
44
35
18
39
19
24
37
20
45
25
26
48
47
38
43
INSTALLATION
23
Fig. 4.2
12 131614
15
13
Page 18
Technical information
4.3 Main diagram (c.h. only)
34
36
50
49
INSTALLATION
46
27
28
17
40
11
31
29
32
41
42
22
35
37
19
20
44
25
24
39
45
18
Fig. 4.3
14
12 1614
Page 19
Technical information
4.4 Hydraulic specifications
kPa bar
0.6
60
50
0.5
40
0.4
0.3
30
20
0.2
0.1
10
0
0.0
0 200 400 600 800 1000 1200 1400
l/h
Fig. 4.4
The hydraulic specifications in Fig. 4.4 represent the pressure (available head for the central heat­ing system) as a function of the flow rate.
The load loss due to the boiler has already been subtracted.
tem component cocks, the by--- pass valve ensur­es a minimum flow of water through the primary heat exchanger.
4.5 Expansion vessel
Note: this boiler is designed for operation only in a sealed central heating system
The height difference between the pressure relief valve and the highest point in the system may be 7m at most.
For greater differences, increase the pre --- load pressure in the expansion vessel (44 on page 12) and the system, when cold, by 0.1 bar for each additional 1m.
Capacity l 6,0
Pre--- load pressure kPa
bar
Maximum volume of water
l 132
in the system *
Tab. 4.1
100
1,0
INSTALLATION
Output with thermostat cocks shut off
The boiler is fitted with an automatic by --- pass valve (45 on page 12), which protects the primary heat exchanger.
In case of excessive reduction or total blockage of water circulation in the central heating system owing to closure of the thermostatic valves or sys-
* Where conditions are:
---
Average maximum temperature of the system is 80°C
---
Initial temperature when filling up the system is 10°C
For systems with volumes greater than 132 l, an additional expansion vessel must be provided.
15
Page 20
Technical information
4.6 Technical data
mod. M96.24SM/...
Heat input
Nominal kW
Minimum kW
Useful output G20
Maximum kW
Minimum kW
Maximum condensing kW
(A)
INSTALLATION
Minimum condensing kW
Useful output G30 G31
Maximum kW
Minimum kW
Maximum condensing kW
Minimum condensing kW
BTU/h
BTU/h
BTU/h
BTU/h
BTU/h
BTU/h
BTU/h
BTU/h
BTU/h
BTU/h
25,0
85 295
11,0
37 530
24,6
83 973
10,2
34 936
26,6
90 754
11,1
37 871
23,7
80 894
10,2
34 936
26,6
90 754
10,8
36 997
Central heating
Maximum flow temp. ° C 85
Minimum flow temp. ° C 38
Minimum return temp. ° C 30
Maximum pressure kPa
bar
Minimum pressure kPa
bar
Available head (in 1000 l/h)
Seasonal efficiency
(B)
G20
Seasonal efficiency G30 G31
(B)
kPa
bar
band %
band %
300
30
0,3
25
0,25
87,7
86,9
Domestic hot water
Maximum temperature ° C 55
Minimum temperature ° C 35
Maximum pressure kPa
bar
Minimum pressure kPa
bar
1 000
10
30
0,3
Flow rate
minimum l/min 2,5
30° rise
35° rise
40° rise
(C)
(C)
(C)
l/min 12,1
l/min 10,1
l/min 8,7
3
B
B
Gas supply pressures
Gas Natural
G20
Norm. Pa
mbar
Max Pa
mbar
Min. Pa
mbar
2 000
2 500
1 700
20
25
17
Butane
G30
2 900
29
3 500
35
2 000
20
Propane
G31
3 700
4 500
2 500
1 mbar approximately equals 10 mm H2O
(A)
referred to the net calorific value at 15 ° C and 1013,25 mbar
G 20 = 34,02 MJ/m3,G 30 = 45,6 MJ/kg, G 31 = 46,4 MJ/kg
(B)
The value is used in the UK Government’s Standard Assessment Procedure (SAP) for energy rating
of dwellings. The test data from which it has been calculated have been certified by a notified body.
(C)
Values subject to tolerance
16
37
45
25
Page 21
Technical information
Gas pressures at the burner
Gas Natural
G20
Max. Pa
mbar
Min. Pa
mbar
Ignition Pa
mbar
1080
10,8
150
1,5
600
6,0
Butane
G30
2800
28,0
550
5,5
1200
12,0
Propane
G31
3550
35,5
770
7,7
1300
13,0
1 mbar approximately equals 10 mm H2O
Gas rate
Gas Natural
G20
m3/h
Butane
G30
kg/h
Propane
G31
kg/h
Max. 2,65 1,97 1,94
Min. 1,16 0,87 0,85
Flue design
Flue pipe diameter
Coaxial mm 60/100
Twin split pipes mm 80
Roof mm 80/125
Nominal heat flow rate
(A)(D)
Exhaust temperature
Smoke production
(D)
(D)
kW 25,0
° C 90
kg/h 68
Flue gas figures
Nominal heat input
(A)(D)
kW 25,0
CO2content % 6,4
O2content % 11,1
CO content ppm 50
Exhaust temperature
(D)
° C 90
INSTALLATION
Injectors
Natural G20 130
Butane G30 75
Propane G31 75
Electrical Data
Voltage V~ 230
Frequency Hz 50
Power consumption W 140
Protection degree IPX4D
External fuse rating A 3
Internal fuse rating A 1,6 T
Other specifications
Height mm 803
Width mm 400
Depth mm 350
Weight (dry) kg 42,5
Water volume in the boiler
l (kg) 2,1
(up to 1 bar)
(D)
Values refer to tests with a 1 m chimney working at the nominal heat input
17
Page 22
Technical information
4.7 Technical data mod.
M96.28SM/... M96.28SR/...
Heat input
Nominal kW
Minimum kW
Useful output G20
Maximum kW
Minimum kW
Maximum condensing kW
(A)
INSTALLATION
Minimum condensing kW
Useful output G30 G31
Maximum kW
Minimum kW
Maximum condensing kW
Minimum condensing kW
BTU/h
BTU/h
BTU/h
BTU/h
BTU/h
BTU/h
BTU/h
BTU/h
BTU/h
BTU/h
29,0
98 942
13,0
44 353
28,3
96 488
12,1
41 284
30,7
104 602
13,2
44 965
27,4
93 599
12,1
41 284
30,7
104 602
12,9
44 016
Central heating
Maximum flow temp. ° C 85
Minimum flow temp. ° C 38
Minimum return temp. ° C 30
Maximum pressure kPa
bar
Minimum pressure kPa
bar
Available head (in 1000 l/h)
Seasonal efficiency
(B)
G20
Seasonal efficiency G30 G31
(B)
kPa
bar
band %
band %
300
30
0,3
25
0,25
87,5
87,0
Domestic hot water (M96.28SM/... only)
Maximum temperature ° C 55
Minimum temperature ° C 35
Maximum pressure kPa
bar
Minimum pressure kPa
bar
1 000
10
30
0,3
Flow rate
minimum l/min 2,5
30° rise
35° rise
40° rise
(C)
(C)
(C)
l/min 14,0
l/min 11,7
l/min 10,1
3
B
B
Gas supply pressures
Gas Natural
G20
Norm. Pa
mbar
Max Pa
mbar
Min. Pa
mbar
2 000
2 500
1 700
20
25
17
Butane
G30
2 900
29
3 500
35
2 000
20
Propane
G31
3 700
4 500
2 500
1 mbar approximately equals 10 mm H2O
(A)
referred to the net calorific value at 15 ° C and 1013,25 mbar
G 20 = 34,02 MJ/m3,G 30 = 45,6 MJ/kg, G 31 = 46,4 MJ/kg
(B)
The value is used in the UK Government’s Standard Assessment Procedure (SAP) for energy rating
of dwellings. The test data from which it has been calculated have been certified by a notified body.
(C)
Values subject to tolerance
18
37
45
25
Page 23
Technical information
Gas pressures at the burner
Gas Natural
G20
Max. Pa
mbar
Min. Pa
mbar
Ignition Pa
mbar
1000
10,0
160
1,6
600
6,0
Butane
G30
2800
28,0
590
5,9
1200
12,0
Propane
G31
3600
36,0
770
7,7
1300
13,0
1 mbar approximately equals 10 mm H2O
Gas rate
Gas Natural
G20
m3/h
Butane
G30
kg/h
Propane
G31
kg/h
Max. 3,07 2,29 2,25
Min. 1,28 1,03 1,01
Flue design
Flue pipe diameter
Coaxial mm 60/100
Twin split pipes mm 80
Roof mm 80/125
Nominal heat flow rate
(A)(D)
Exhaust temperature
Smoke production
(D)
(D)
kW 29,0
° C 90
kg/h 76
Flue gas figures
Nominal heat input
(A)(D)
kW 29,0
CO2content % 6,8
O2content % 10,7
CO content ppm 75
Exhaust temperature
(D)
° C 90
INSTALLATION
Injectors
Natural G20 130
Butane G30 75
Propane G31 75
Electrical Data
Voltage V~ 230
Frequency Hz 50
Power consumption W 160
Protection degree IPX4D
External fuse rating A 3
Internal fuse rating A 1,6 T
Other specifications
Height mm 803
Width mm 400
Depth mm 350
Weight (dry) kg 44,5
Water volume in the boiler
l (kg) 2,2
(up to 1 bar)
(D)
Values refer to tests with a 1 m chimney working at the nominal heat input
19
Page 24
5 GENERAL REQUIREMENTS
Biasi UK Ltd support the Benchmark initiative. The Benchmark Log Bookis located at the back of this manual and should be completed by the Installing/Commisssioning Engineer and handed over to the User for future reference by other visiting Engineers. Also included is the Service Interval Record card that should be completed by the Service Engineer following the annual service maintenance of the boiler and system.
This appliance must be installed by a compet­ent person in accordance with the Gas Safety (installation & Use) Regulations.
5.1 Related documents
The installation of this appliance must be in ac­cordance with the relevant requirements of the
INSTALLATION
current Gas Safety (Installation & Use) Regula­tions, the Local Building Regulations, the current I.E.E. Wiring Regulations, the Regulations and by--- laws of the local water undertaking, and in Scotland, in accordance with the Building Stan­dards (Scotland) Regulation. Health and safety document n° 635 ”Electricity at work regs.”.
It should also be in accordance with the British Standard Codes of Practice:
5.3 Flue system
The provision forsatisfactory flue terminationmust be made as described in BS 5440 part 1.
The appliance mustbe installed so that the flue ter­minal is exposed to external air.
It must not be installed so that the terminal dis­charges into an other room or space as an out­house or lean---to. It is important that the position of the terminal allows a free passage of air across at all times.
The terminalshould belocated with due regard for the damage or discoloration that might occur to building products in the vicinity.
In cold and/or humid weather water vapour may condense on leaving the flue terminal; the effect of such ”steaming” must be considered.
Pluming may easily occur at the terminal. Where possible, terminal position which could cause a nuisance should be avoided.
The minimum acceptable spacing from the ter­minal to obstructions and ventilation openings are specified in Fig. 5.1.
5.2 Location of appliance
The appliance may be installed in any room or in­ternal space, although particular attention is drawn to the requirementsof the current I.E.E. Wir­ing Regulations, and in Scotland, the electrical provisions of the Building Regulations applicable in Scotland, with respect to the installation of the combined appliance in a room containing a bath or shower.
Where a room--- sealed appliance is installed in a room containing a bath or shower, any electri­cal switch or appliance control, utilising mains electricity should be so situated that it cannot be touched by a person using the bath or shower.
The location must permit the provision of an ad­equate flue and termination.
For unusual locations special procedures may be necessary and BS 6798 gives detailed guidance on this aspect.
A compartment used to enclose the appliance must be designed specifically for this purpose.
This appliance is not suitable for external installa­tion.
M
HI
BC
F
D
J
A
O
N
E
F
G
KL
G
Fig. 5.1
Terminal position mm
A Directly below a window or other opening 300. . . .
B Below gutters, soil pipes or drain pipes 75. . . . . .
C Below eaves 200. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D Below balconies or car port roof 650. . . . . . . . . . . .
E From vertical drain pipes and soil pipes 75. . . . . .
F From internal or external corners 300. . . . . . . . . . . .
G Above ground or balcony level 300. . . . . . . . . . . . .
H From a surface facing a terminal 600. . . . . . . . . . . .
I From a terminal facing a terminal 1 200. . . . . . . . . . .
J From an opening in the car port.
(e.g. door, window) into dwelling 1 200. . . . . . . . .
K Vertically from a terminal in the same wall 1 500. . L Horizontally from a terminal in the same wall 300. .
Table follows in next page
M Above the roof pitch with roof slope less
20
rev. 17.09.93
Page 25
General requirements
than or equal to 30° 600. . . . . . . . . . . . . . . . . . . . . .
Above the roof pitch with roof slope
more than 30° 1 000. . . . . . . . . . . . . . . . . . . . . . . . .
N From wall face 600. . . . . . . . . . . . . . . . . . . . . . . . . . .
O From an opening 300. . . . . . . . . . . . . . . . . . . . . . . . .
* specific manufacturer requirements
5.4 Gas supply
The Gas meter is connected to the service pipe by the local gas region or a local gas region contrac­tor.
If the gas supply for the boiler serves other appliances ensure that an adequate supply is available both to the boiler and the other appliance when they are in use at the same time.
Pipework must be of adequate size. Pipes of a smallersize than the boiler inlet connection should not be used.
Installation pipes should be fitted in accordance with BS 6891 and the complete installation should be tested for soundness.
The length of the condensate pipe should be kept at minimum.
To avoid condensate being trapped:
---
the drainpipe should be run with a fallof atleast
2.5° (45 mm/m) away from the boiler;
---
the number of bends and joints should be kept at minimum;
---
the drainpipe should be adequately fixed to pevent pipe sagging.
If a part of the drainpipe runs externally this part should pe kept as short aspossible and protected to reduce the risk of freezing.
Condensate drain
INSTALLATION
5.5 Air supply
The room in which the boiler is installed does not require a purpose provided air vent.
5.6 Ventilation
If installed in a cupboard or compartment, it is not necessary to provide additional ventilation for cooling for this particular product. However con­sideration must be given to clearance require­ments for maintenance (see section 6.2) and under no circumstances must storedarticles be al­lowed to come into contact with the boiler or flue pipe.
5.7 Condensate drain
Ensure that the condensate discharge complies with the national or local regulations in force.
The condensate pipe must be fitted in accordance with Building Regulations.
Drainpipe material should be resistant to acid as the condensate is slightly acid with a pH less than
6.5.
The boiler includes a trap (17 on page 12) that pre­vents the combustion products entering the drain, however an additional trap with a sealof at least 75 mm and an air break between thetraps is required (Fig. 5.2).
Fig. 5.2
5.8 Water circulation (c.h.)
Detailed recommendations are given in BS 6798 and BS 5449; the following notes are given for general guidance.
Pipework
The return temperature must not be lower of 30 ° C.
Copper tubing to BSEN 1057is recommended for water pipes. Jointing should be either with capil­lary soldered or with compression fittings.
Where possible pipes should have a gradient to ensure air is carried naturally to air release points and water flows naturally to drain taps.
The appliance has a built--- in automatic air release valve, it should be ensured as far as possible that the appliance heat exchanger is not a natural col­lecting point for air.
Except where providing useful heat, pipes should be insulated to prevent heat loss and to avoid freezing.
Particular attention should be paid to pipes pas­sing through ventilated spaces in roofs and under floors.
By--- pass
rev. 17.09.93
21
Page 26
General requirements
The appliance includes an automatic by--- pass valve which protects the main heat exchanger in case of reduced or interrupted water circulation through the heating system due to the closing of thermostatic valvesor cock--- type valves within the system.
The by--- pass is calibrated to assure a minimum flow of 500--- 600 lts/hr through the main heat ex­changer.
If you are installing a system that includes thermo­static radiator valves (TRV) and/or small bore (8--- 10 mm) it may be necessary to fit an external by--- pass to facilitate correct operation of the boiler.
Air release points
These must be fitted atall high pointswhere air will natural collect and must be sited to facilitate com­plete filling of the system.
INSTALLATION
Expansion vessel
The appliance has an integral sealed expansion vessel to accommodate the increase of water vol­ume when the system is heated.
Refer to Tab. 4.1 on page 15 for its technical data. If the heating circuit has an unusually high water
content, calculate the total expansion and add an additional sealed expansion vessel with adequate capacity.
Mains water feed: central heating
There must be no direct connection to the mains water supply even through a non return valve, without the approval of the Local Water Authority.
Mains water feed: hot water supply
The domestic section of the boiler is designed to withstand an internal domestic water pressure of 10 bar. Where it is likely that the mains domestic water pressure may exceed 5 bar, it is possible due to internal “water hammer” effects that the pressure within the domestic system can increase to a level in excess of the 10 bar limit.
In these circumstances it is therefore recom­mended that a 3 bar pressure reducing valve be fitted to the incoming mains water supply and a mini expansion vessel installed on the domestic circuit.
These devices will protect the boiler and the do­mestic system from damage due to excessive do­mestic water pressure.
Filling
A method for initially filling the system and replac­ing water lost during servicing must be provided and it must comply with local water authority regu­lations.
The correct method is shown in Fig. 5.3.
The temporary connection must be removed immediately after filling.
Control valve
Double check valve
Temporary connection
Supply pipe
(cold water inlet)
C.h. return pipe
Control valve
Fig. 5.3
The installer should ensure that no leaks exist either inside the boiler or on the system as fre­quent filling of the system could cause premature scaling of the heat exchanger.
5.9 Domestic water
The domestic water installation must be in accord­ance with the relevant recommendations of BS
5546. Copper tubing to BS EN 1057 is recom­mended for water carrying pipework and must be use for pipework carrying potable water.
5.10 Water treatment
Central heating circuit
Where a new boiler is fitted to a new system with either plastic or copper pipes, it is important the system is fully flushed, on completion, to ensure flux residues, swarfs, oils and other installation de­bris is removed.
Where a new boiler is fitted to an existing system, it is important the debris from the existing system is fully removed in order to ensure the efficiency of the new appliance is maintained.
Detailson flushing procedure are given in the sec­tion 7.4 of this manual.
Domestic hot water circuit (scale protection)
In areas where the water is ’hard’ (i.e. more than 200 ppm total hardness as defined by BS 7593:
22
rev. 17.09.93
Page 27
General requirements
1993 Table 2) it is recommended that a proprietary scale--- reducing device is fitted into the boiler cold supply, within the requirements of the local water company.
5.11 Electrical supply
Warning, this appliance must be earthed.
External wiring to the appliance must be carried out by a competent person and be in accordance with the current I.E.E. Regulations and any local regulations which apply.
The boiler is supplied for connection to a 230 V~ 50 Hz supply. The supply must be fused at 3A.
The method of connection to the electricity supply must facilitate complete electrical isolation of the appliance by the use of a fused double pole isola­tor having a contact separation of at least 3 mm between poles or alternatively, by the use of a 3A fused three pin plug and unswitched shuttered socket outlet both complying with BS 1363.
The point of connection to the electricity supply must be readily accessible and adjacent to the appliance except were the appliance is installed in a bathroom this must then be sited outside the bathroom.
INSTALLATION
rev. 17.09.93
23
Page 28
6 INSTALLATION
6.1 Warnings
The use of gas appliances is subject to statutory control; it is essential to observe the current regulations and laws in force (see also chapter 5).
The appliance must discharge combustion products directly outside or into a suitable ex­haust duct designed for this purpose.
Combustion products must be discharged using original flue kits only, since they are inte­gral parts of the boiler.
For LPG, the appliance must also conform with the requirements of the distributors and com­ply with current Regulations and laws in force.
The safety relief valve and the condensate drain must be connected to a suitable drain, or discharge in a safe manner.
INSTALLATION
The electrical wiring must conform with current Regulations, in particular:
---
the boiler rect bonding clamp.
---
a fused spur isolation switch, with a gap of at least3 mm between the contacts mustbe installed near to the boiler. Refer to section
6.9 in this chapter for the electrical connec­tions.
In no circumstances will the manufacturer be held responsible if the warnings and in­structions contained in this manual have not been complied with.
must
be earthed using the cor-
6.2 Precautions for installation
For the installation proceed as follows:
---
The boiler must be fixed to a strong wall.
---
The dimensions for the exhaust fume duct de­tailed in section6.7 and the correctprocedures for installing the duct, depicted in the instruc­tion leaflet included with the flue kit, must be complied with during installation.
---
To allow maintenance procedures it is necess­ary to leave the minimum gaps indicated in Fig. 6.1.
200
25 50
200
Fig. 6.1 (all dimensions in mm)
---
When installing the boiler in a cupboard, cover or alcove allow at least50mm permanent clear­ance from the front face of the boiler. Also en­sure sufficient clearance to allow free access for servicing and the lowering of the front con­trol panel.
---
If the boiler is installed outside, cover the ap­pliance to protect it against the elements and add some special anti--- freeze (neutralised) to the c.h. system.
---
Before installing the boiler on an existing c.h. system, flush it out thoroughly before fitting the boiler, so as to remove muddy deposits.
---
It is advisable to equip the system with a sedi­ment filter, oruse a water--- treatment product in the circulating water. The latter option in particular, not only cleans out the system, but also has an anti---corrosive effect by promoting formation of a protective skin on metal surfaces and neutralising gases present in the water. We recommend the use of a suitable universal inhibitory to protect the c.h. system from cor­rosion.
6.3 Installing the bracket
Precautions
Before mounting the bracket, check that the di­mensions for fitting the exhaust fume duct are complied with (refer to the leaflet included with the flue kit, packed separately).
24
Page 29
Installation
Utilise the paper template supplied with the boiler to determine the fixing position for the bracket and boiler. Securely mount the bracket to the wall using appropriate fixings suitable for the type of wall construction and capable of supporting the total (wet) load. Refer to the weight given in the technical data tables specific for each model.
6.4 Overall dimensions
200
65645265 200
B
ø100
31
16
C.h.
return
Condensate drain
A
A, B and C
190
Boiler front
350
connection
area
C
ø80 ø80
803
245
196
50
35
700
60 60
C.h. flow
47
115 142
Electric
connection
area
100
D.h.w.
outlet
*
400
Gas
73
257
Cold
water
inlet
**
A --- air intake/flue outlet pipe (co---axial) B --- flue outlet pipe ø 80 mm (twin kit) C --- air intake pipe ø 80 mm (twin kit) * not present on c.h. only boilers
Fig. 6.2 (all dimensions in mm)
6.5 Joints
Functions Pipe sizes (o.d)
Gas, c.h. return, c.h. flow ø 22
D.c.w. inlet * ø 15
D.h.w. outlet * ø 15
Pressure relief valve ø 15
Condensate drain ø 25 (plastic)
* not present on c.h. only boilers
Tab. 6.1 (sizes in mm o.d.)
6.6 Mounting the boiler
1 Take the protective caps off the boiler pipe-
work.
2 Thoroughly clean the connections.
3 Mount the boiler on its bracket.
4 Fix the c.h. valves A and gas cock B (¾”) to the
boiler using the ¾” gaskets (Fig. 6.3)
5 Fix the ø 22 mmpipes C (c.h. circuit) to the c.h.
valves A and the ø 22 mm pipe D (gas) to the cock B using the ¾” gaskets.
6 Repeat the above procedure for the d.c.w. inlet
utilising the ½” cold water inlet valve E, the ø 15 mm copper tail F with its connection nut and two ½” gaskets.
7 Fix the ø 15 mm copper tail G with the ½” con-
nection nut and a ½” gasket.
C
D
G
F
C
A
B
E
A
Fig. 6.3
INSTALLATION
25
Page 30
Installation
8 Connect the pipe H (Fig. 6.4) from the pres-
sure relief valve to the safety discharge pipe­work.
9 Fit the condensate drain 11 (Fig. 6.4) in the air
brake connected to the drainage pipework. See also section 5.7 in this manual.
INSTALLATION
11H
Fig. 6.4
6.7 Fitting the flue system
Refer to the assembly instructions contained with­in the chosen flue kit packaging for the correct as­sembly and installation.
In general, it has to be taken in consideration that the horizontal sections of the flue pipe must have an horizontal sloping not less than 1.5 deg. (25 mm per metre) towards the boiler.
In the standard horizontal flue kit (Fig. 6.5A) the flue pipe is angled within the air duct therefore the air duct must be horizontally installed.
If one or more extensions have to be used they must be adequately supported so that there is no sag in the flue pipe and a minimum fall of 1,5 deg. (25 mm per metre) over the whole length towards the boiler is ensured.
6.8 Choice of flue
The following flue kits are available for connecting to the boiler:
Standard horizontal flue kit (Fig. 6.5A)
Co--- axial 60/100mm --- nominal length 1m
This kitis normally supplied with the boiler and can be fitted to allow discharge to the rear or either side of the boiler via the flanged boiler adapter elbow. Minimum length required is 0.3 m. Maxi­mum equivalent length of 2,7 metres can be achieved utilisingextensions. This flue system can only be used to discharge horizontally, it is not de­signed to enable termination in the vertical plane.
Vertical kit with 90° elbow (Fig. 6.5B)
Co--- axial 60/100 mm
Supplied with a straight flanged adapter a co --­axial elbow and a co---axial pipe with terminal, this kit allows for a vertical rise of 0,5 m from the boiler. In all circumstances the flue terminal must dis­charge horizontally and the equivalent flue length must not exceed 2,7 metres.
Elbows 45° & 90° (Fig. 6.5C)
Co--- axial 60/100mm.
Elbow kits enable the standard flue kits to be offset to overcome obstructions or ensure the correct clearances for the flue terminal. Each elbow used in addition to the standard flanged elbow reduces the overall acceptable length of the flue system as follows:
45° reduce length by 0.5 m. 90° reduce length by 1 m.
B
ø 60/100
Min = 0,3 m
Max = 2,7 m
A
ø 60/100
90° =--- 1m
45° =--- 0,5m
C
Fig. 6.5
Twin pipe kits ø 80 mm (Fig. 6.6)
Various twin (split) pipes kits and optional acces­sories (elbows) are available to assist in the ter­mination of the flue where the boiler is installed in a location remote to an outside wall.
These kits allow for separation of the air supply pipe from the pipe that discharges the exhaust
26
Page 31
Installation
gasses. Consequently it is possible to extend the flue system to a greater distance than that pro­vided by the standard horizontal co--- axial flue.
If either an additional 45° or 90° accessory elbow is used then the maximum permissible length of either pipe must be reduced by 0.90 m or 1,65 m respectively.
90° =--- 1,65 m
45° =--- 0,90 m
Fig. 6.6
Two restrictors with different size are supplied with the twin pipe kit and have to be installed between the boiler and the air intake adapter (Fig. 6.7).
Air intake adapter
This kit allows vertical termination of the flue pipe through the roof. The kit is 1.2 m in length. Exten­sion pieces (Co--- axial) are also available which al­lows the flue system to be extended to a total overall maximum permissible length. Optional 45° and 90° elbows can be used to offset the flue route.
Each additional elbow reduces the overall accept­able length of the flue system as follows:
45° reduce length by 0.5 m. 90° reduce length by 1 m.
90° =--- 1m
INSTALLATION
max = 8.5 m
45° =--- 0,5m
Fig. 6.8
Restrictor
Gasket
Fig. 6.7
For the correct use of the restrictors
pipes
refer to Tab. 6.2.
Equivalent length
with twin
Restrictor
(air duct + flue duct)
Between 1 and 15 m ø 50 mm
More than 15 m up to 30 m ø 55 mm
6.9 Electrical connections
Connection to the electricity supply
1 Remove the front panel of the case (see the
section 9.2 in this manual).
2 Remove the screws I and J (Fig. 6.9).
3 Loosen the screws K.
Tab. 6.2
Vertical--- roof kit (Fig. 6.8)
27
Page 32
Installation
I
J
K
J
INSTALLATION
Fig. 6.9
4 Remove the side panels or move the lower part
of the side panels as indicated in Fig. 6.10 and pull the control panel. When completely pulled out, the panel can ro­tate 45° downwards to facilitate the operations on the internal parts.
L
Fig. 6.11
For the electrical connection to the boiler use elec­tricwires which conform to the current regulations, with flexible cord, each core having a cross sec­tion area
6 Connect the electrical supply flexible cord
coming from the fused spur isolation switch to the power supply terminal block of the boiler (Fig. 6.12) keeping the same connections for the live (brown wire) and the neutral (blue wire). External 3 A fuse or fused plug with same current rating is recommended.
Do not connect live wires to terminals to which the room thermostat must be con­nected.
Connect the earth wire (yellow/green).
7
not less than 0,75 mm
2
.
Fig. 6.10
5 Loosen the screws L and remove the service
panel (Fig. 6.11).
Connection of a room thermostat
The room thermostat must be connected to the terminal block situated next to the control panel.
When connecting any type of external control, the link M in Fig. 6.12 must be removed.
28
Page 33
Installation
L N
Power supply terminal block
12
External controls terminal block
M
To fused spur isolation switch
3
Fig. 6.12
8 Connect the room thermostat between ter-
minals 1 and 3 as shown in Fig. 6.13.
Do not connect live wires to terminals to which the room thermostat must be con­nected.
Room thermostat
Power supply terminal block
L N
T
To the external control device
To the fused spur isolation switch
Fig. 6.14
6.10 External frost protection
10 Connect the frost thermostat between ter-
minals 1 and 2 as shown in Fig. 6.15.
Do not connect live wires to terminals to which the room thermostat must be con­nected.
Frost thermostat
Room thermostat
INSTALLATION
External controls terminal block
3
12
Fig. 6.13
9 Route the electrical supply flexible cord and
the external control flexible cord as illustrated in Fig. 6.14. Lock the flexible cords in place with the flexible cord clamps
L N
T
3
Fig. 6.15
T
Power supply terminal block
12
External controls terminal block
6.11 Connecting a M96.28SR/...
system boiler to a cylinder
Two schematic wiring diagrams are given in this section showing two possible ways to connect an external programmer to a mid --- position diverter valve to provide independent timed and thermo­static control of heating and hot water.
In both diagrams the earth wires are not shown for clarity. Earth wiring
must
be fitted as necessary.
29
Page 34
Installation
L
N
MAINS 230V a.c. Switched 3 Amp fused, spur
Valve colour key BR --- Brown
BL --- Blue GR --- Grey
INSTALLATION
OR --- Orange
Fig. 6.16 --- relay controlled boiler
Programmer
Room thermostat
Cylinder thermostat
BL
GRBROR
Mid--- position diverter valve
Relay
Remove room thermostat link
L N
Power supply terminal block
321
M96.28SR/...
External control
terminal block
L
N
MAINS 230V a.c. Switched 3 Amp fused, spur
Valve colour key BR --- Brown
BL --- Blue GR --- Grey OR --- Orange
Programmer
Fig. 6.17 --- directly controlled boiler
Room thermostat
Cylinder thermostat
BL
GRBROR
Mid--- position diverter valve
L N
Power supply terminal block
Do not
remove room thermostat link
321
M96.28SR/...
External control
terminal block
30
Page 35
7 COMMISSIONING
Ensure that the Benchmark Log Book is satis­factorily commpleted during the commssion­ing process. The Log Book is locatedat the end of this manual. This manual should be handed to the User following completion of the installa­tion and commissioning process. Failure to comply with these requirments may invalidate the manufacturers guarantee.
7.1 Electrical installation
Preliminary electrical system checks to ensure electrical safety shall be carried out by a compet­ent person. i.e. polarity, earth continuity, resis­tance to earth and short circuit.
If a fault has occurred on the appliance the fault find­ing procedure should be followed as specified in the service manual.
7.2 Gas supply installation
1 Inspect the entire installation including the gas
meter, test for soundness and purge, all as de­scribed in BS 6891;
2 Open the gas cock 14 (Fig. 7.1) on the
appliance and check the gas connector on the appliance for leaks.
14 13
Fig. 7.1
Open position
7.3 Filling the d.h.w. system
1 Close all hot water draw--- off taps.
2 Open the cold water inlet valve 13 (Fig. 7.1).
3 Slowly open each draw --- off tap and close it
only when clear water, free of bubbles, flows out.
7.4 Initial filling of the system
1 Open the c.h. flow and return valves.
2 Remove the front panel of the case (see the
section 9.2 in this manual.
3 Unscrew the cap on the automatic air purger-
valve 19 (Fig. 7.2) one full turn and leave open permanently.
4 Gradually open stopcock at the filling point
connection to the c.h. system until water is heard to flow; do not open fully.
19 21
Fig. 7.2
5 Open each radiator air vent starting at the
lowest point of the system and close it only when clear water, free of bubbles, flows out.
6 Purge the air from the pump by unscrewing the
pump plug 21 (Fig. 7.2); release the pump shaft by turning in the direction indicated by the arrow on the information plate.
7 Replace the pump plug.
8 Continue filling the system. The actual reading
should ideally be 1,3 bar and not less than 0,3 bar.
9 Close all air release valves on the c.h. system.
10 Inspect the boiler and the system for water
soundness and remedy any leaks discovered.
11 Cold flush the system to remove any loose par-
ticlesand any system debris before starting the boiler for the first time
The flushing procedure must be in line with BS7593
tems.
Treatment of Water in d.h.w. c.h. Sys-
INSTALLATION
31
Page 36
Commissioning
When the installation and second filling are completed turn on the c.h. system and run it until the temperature has reached the boiler operating temperature. The system must then be immediately flushed through.
This procedure must be repeated twice more.
During this operation we highly recommend the use of a c.h. flushing detergent in the quan­tities as specified by the appropriate manufac­turer, whose function it is to dissolve any foreign matter which may be in the system.
The above operation could save the invalida­tion of your boilers guarantee and will also pre­vent problems which you may experience in the future if an inhibitory is not used.
INSTALLATION
7.5 Condensate pipe and traps
The full length of the condensate pipe should be check for leaks.
The boiler has a built--- in condensate trap pro­vided with a ball valve that prevents the escape of combustion products when the trap is empty.
It is however recommended that any other trap in the drain system is correctly filled with water before to run the boiler.
810 7 6
Fig. 7.3
810 7 6
Fig. 7.4
The boiler will now go through an ignition se­quence and the burner will light.
If during the ignition attempt period the boiler fails to light, the full sequence control p.c.b. will go to lockout and the lock--- out signal lamp 6 will ap­pear.
To reset the boiler press and release the boiler re­set button 7 (Fig. 7.3).
7.6 Lighting the boiler
Some products incorporate an anti cycling time delay. It isnormal when first switching the boiler on for the boiler to operate on heating for a few sec­onds then switch off. After 3 --- 4 minutes has elapsed the boiler will then re ignite and operate perfectly normally. The ignition delay cycle does not prevent normal operation of the boiler to pro­vide d.h.w..
If external controls are fitted (e. g. Timeclock, room thermostat) ensure they ”call for heat”.
1 Turn on the electricity supply to the boiler,
switching on the fused spur isolation switch. The appliance operation light 10 will flash every 4 seconds.
2 Turn the function selector 8 as in Fig. 7.3
(combi) or Fig. 7.4 (c.h. only). The appliance operation light 10 will flash every 2 seconds.
7.7 Checking the gas pressure at
the burner
This boiler has been tested to the highest qual­ity control standards.
The maximum and minimum gas pressures are already set during this quality control process however the checking procedure must be fol­lowed to ensure maximum operating efficiency from the boiler.
1 Remove the front panel of the case (see sec-
tion 9.2 in this manual).
2 Loosen the internal screw 41 (Fig. 7.5) on the
Outlet Pressure Test Point of the Gas Valve and connect a pressure gauge using a suitable hose.
32
Page 37
Commissioning
3 Set the d.h.w. and c.h. temperature control
knobs to their maximum position.
4 Switch on the boiler and open at least one hot
water tap fully.
5 Check the maximum gas pressure and com-
pare the value on the gauge with the value indi­cated in the sections 4.6 or 4.7 (gas pressures at the burner), accordingly with the model of boiler installed.
6 Check the maximum gas flow at the gas meter
and compare the value indicated in the sec­tions 4.6 or 4.7 (gas rate), accordingly with the model of boiler installed.
7 Switch off the boiler.
8 Disconnect the gas modulator coil by remov-
ing the electrical connector A (Fig. 7.5).
41
A
indicated in the sections 4.6 or 4.7 (gas pres­sures at the burner), accordingly with the model of boiler installed. If the ignition gas pressure is not set correctly see section 7.8 in this manual for the adjust­ment procedure. If ignition gas pressure is cor­rect switch dip--- switch ”3” to the ON position.
15 Switch off the boiler, turn off the hot water tap(s)
and disconnect the pressure gauge.
If the maximum and minimum gas pressures measured above are not in accordance with the technical data (sections 4.6 or 4.7) then adjust­ment willbe necessary. A full explanation of the gas pressure adjustment procedure is given in the Gas Valve section of the service manual. If maximum and/or minimum gas pressures are adjusted then the ignition gas pressure must be checked and adjusted if necessary.
Important: after the gas pressure checks and any adjustment operations, all of the testpoints and adjustment devices must be sealed.
INSTALLATION
Fig. 7.5
9 Switch on the boiler.
10 Check the minimum gas pressure and com-
pare the value on the gauge with the value indi­cated in the sections 4.6 or 4.7 (gas pressures at the burner), accordingly with the model of boiler installed.
11 Switch off the boiler and re---connect the elec-
trical connector A to the modulator coil.
12 Access the main control panel (see section 6.9,
follow steps 2 --- 5)
13 Switch on the boiler.
14 Check the ignition gas pressure by setting
dip--- switch ”3” (Fig. 7.8) to the OFF position. Compare the value on the gauge with the value
7.8 Adjusting the burner ignition
1 Turn off the boiler by means of the fused spur
isolation switch provided adjacent to the ap­pliance.
2 Make sure that the function selector 8 is set to
the position in Fig. 7.6 and that the timer selec­tor switch and room thermostat, if fitted, is set to “demand heat”.
Fig. 7.6
3 Unscrew the gas valve’s outlet pressure test
point 41 (Fig. 7.5) and connect a pressure gauge.
33
Page 38
Commissioning
4 Loosen the screws B and remove the service
panel (Fig. 7.7).
B
Fig. 7.7
5 Turn on the boiler.
INSTALLATION
6 Check that the boiler lights up uniformly and
adjust the ignition gas pressure, if necessary.
To adjust the ignition gas pressure, set dip--- switch ”3” (Fig. 7.8) to the OFF positionand adjust poten­tiometer marked “ACC” with a screwdriver until correct ignition gas pressure is obtained.
+
RISC
+
ACC
ON
2 3
1
4
is set to the ’OFF’ position there will be approxi­mately 30 seconds re--- ignition delay period.
Whilst checking or adjusting the c.h. output, and fault finding on the boiler it may be necessary to switch the re--- ignition delay mechanism (dips­witch 4) to the ’OFF’ position.
Refer to the diagrams shown in Fig. 7.9, Fig. 7.10 or Fig. 7.11 and select the correct central heating output gas pressure to meet with the central heat­ing system requirements.
With the boiler operating in c.h. mode, use a suit­able screwdriver to turn the adjustment potentio­meter marked “RISC” (Fig. 7.8). Rotating the potentiometer anti --- clockwise re­duces the maximum supply current to the gas modulator device, and thus reduces the gas pres­sure to the burner.
kW
Natural (G20) 29 27 25 23 21 19 17 15 13 11
9
1 2 3 4 5 6 7 8 9 10 11
M96.24SM/... M96.28SM/... M96.28SR/...
mbar
Fig. 7.9
OFF
Fig. 7.8
Refer to the table gas pressures at the burner in the sections 4.6 or 4.7 for appropriate value.
7 Having finished this procedure, reset dip---
switch ”3” to the ON position.
7.9 Adjustment of useful c.h.
output
If the burner function selector (dipswitch number 4 on the main P.C.B.) is set to the ’ON’ position it will activate the re --- ignition delay period of ap­proximately 4 minutes. When dipswitch number 4
34
Page 39
Commissioning
kW
28 26 24 22 20 18 16 14 12 10
5 7 9 11 13 15 17 19 21 23 25 27 29
M96.24SM/... M96.28SM/... M96.28SR/...
Fig. 7.10
kW
29 27 25 23 21 19 17 15 13 11
9
7 10 13 16 19 22 25 28 31 34 37
M96.24SM/... M96.28SM/... M96.28SR/...
Fig. 7.11
Butane (G30)
mbar
Propane (G31)
mbar
7.10 Checking the ignition device
With the burner on high flame close the gas cock. About 10 seconds after, the lock--- out signal lamp
6 (Fig. 1.3 on page 2) must appear. To reset the boiler press and release the boiler
reset button 7 (Fig. 1.3 on page 2).
7.11 Checking the flue system
The flue system should be visually checked for soundness. Check all clamps, gaskets and fixings are secure and tight.
Ensure that the flue terminal is sitedcorrectly in ac­cordance with the flue fitting instructions and Fig. 5.1 on page 20 of this manual.
To carry out a combustion check refer to the in­structions given in the section 9.5 of this manual.
Reference figures are given in the sections 4.6 or
4.7 of this manual (Flue gas figures).
7.12 Checking the condensate
drain pipe
Check the soundness and integrity of the conden­sate drain pipe.
Verify the cleaness and correct filling of the con­densate traps.
7.13 Instructing the user
Hand over this combined User & Installation man­ual and the Service manual to the end user and ex­plain how to use the unit in both c.h. and d.h.w. modes.
Take the User step by step through the lighting in­structions.
Show the User how to switch off the appliance quickly and indicate the position of the electric supply isolator.
Explain the proper use and adjustment of all sys­tem controls; this will ensure the greatest possible fuel economy.
Explain the function and use of the function selec­tor.
Explain and demonstrate the function of time and temperature controls (if fitted).
Explain how to turn off the appliance for both short and long periods and advise on the precautions necessary to prevent damage should the appliance be inoperative when freezing condi­tions may occur.
Fill in the details required on the Boiler Guarantee Certificate and hand to the User advising them to return the correct section for boiler Guarantee reg­istration.
Finally, advise the User that, for continued safe and efficient operation, the appliance must be ser­viced by a competent person at least once a year.
INSTALLATION
35
Page 40
8 GAS CONVERSION
NaturalgasL.P.G
.
8.1 Warnings
Procedures to adapt the boiler to the type of gas available
must be carried out
by a com-
petent and responsible person.
Components used to adapt it to the type of gas available must be genuine parts only.
8.2 Procedures
1 Check that the gas cock (14 in Fig. 9.3) fitted
under the boiler is turned off and the appliance is is switched off at the mains isolating spur.
2 Remove the front and side panels of the case
(see the section General access and emptying hydraulic circuits in the service manual).
3 Take off the lid of the sealed chamber.
4 Take the front panel of the combustion
chamber off and remove the burner (29 on page 12). See section Ignition and detection electrodesin theservice manual for detailed in­structions.
5 Carry out the conversion for the type of gas, re-
placing the burner injectors correctly.
6 Re--- assemble the burner, the front panel of the
combustion chamber and the lid of the sealed chamber.
7 Extract the control panel as explained in the
section 6.9 of this manual.
MAINTENANCE
8 Loosen the screws C and remove the service
panel (Fig. 8.1).
C
9 set correctly the dip--- switch ”2” to the correct
position (Fig. 8.2) in accordance with the follo­wing table.
Gas supply Position of dip---switch 2
Natural gas On
L.P.G. Off
ON
1 2 3
OFF
4
ON
2
OFF
4
3
1
Fig. 8.2
10 Calibrate the gas valve according to the in-
structions given in the service manual, section Modulating gas valve --- Adjustment.
11 Set the correct gas pressure for central heating
output required, see section 7.9 in this manual.
12 Stick on the inside of the left hand side panel
adjacent to the data badge the self--- adhesive label (included with the conversion kit) indicat­ing the type of gas, and the gas pressures to which the appliance has been set.
13 Replace the service panel, the front and side
panels of the case.
Fig. 8.1
36
Page 41
9 MAINTENANCE
9.1 Warnings
The procedures detailed in this chapter
be carried out only by a professionally qualified person.
contact an Authorised Service Agent.
For efficient and continuous operation of the boiler you are advised to have, at least once a year, maintenance and cleaning done by an Approved Service engineer.
Isolate the appliance from the electricity supply
switch adjacent to the appliance and
the gas
cedures, whatsoever, for cleaning, mainten­ance, opening or dismantling boiler panels.
by turning off the fused spur isolation
cock, before carrying out any pro-
Thus you are advised to
must
turn off
9.2 Dismantling the external
panels
Front panel
1 Loosen the three screws A (Fig. 9.1).
2 Lift and remove the panel.
Side panels
3 Loosen the screws B. Bring the bottom of the
panels away from the boiler and lift them, free­ing them from the top hooks (Fig. 9.2).
B
Fig. 9.2
Air--- Flue exhaust Sampling points
9.3 Emptying the d.h.w. system
(combi)
1 Turn off the d.c.w. inlet isolating valve (13 in
Fig. 9.3) and turn on the hot water taps and any drain cocks.
Closed position
A
12
141316
Fig. 9.3
MAINTENANCE
9.4 Emptying the c.h. system
Fig. 9.1
1 Close the c.h. isolating valves (12 and 16 in
Fig. 9.3).
2 Open the central heating drain cock (18 in
Fig. 9.4).
37
Page 42
Maintenance
3 A small quantity of water will remain in the
d.h.w. heat exchanger after draining. If the boiler is being drained to prevent freezing, the d.h.w. heat exchanger must be removed and inverted to drain fully or an antifreeze solution added.
18
Fig. 9.4
9.5 Combustion analysis check
If it is necessary to carry out a combustionanalysis remove the plugs indicated in Fig. 9.1.
Reference figures are given in the sections 4.6 or
4.7 of this manual (Flue gas figures).
9.6 Cleaning the primary heat
MAINTENANCE
1 Take off the front of the case.
2 Take off the removable front of the air--- tight
If you notice dirt on the fins of the primary heat ex­changer (31 on page 12):
3 cover the sloping surfaces of the burner (29 on
4 Brush out the primary heat exchanger (31 on
NOTE --- When removing the airtight chamber cover it is not necessary to remove the screws lo­cated at the top edge on either side.
exchanger
chamber and the front panel of the combustion chamber.
page 12) entirely in a protective layer (sheetsof newspaper or similar).
page 12) with a bristle paintbrush.
sure in the expansion vessel is not less than 1 bar. See also section 4.5 page 15 of this manual.
If the pressure is lower, take steps to correct the pressure level.
9.8 Cleaning the burner
The sloping and multi---gas type burner (29 on page 12) does not need special maintenance, but it is sufficient to dust it with a bristle paintbrush.
To reach the burner:
1 Take off the front of the case.
2 Take off the removable front of the air--- tight
chamber and the front panel of the combustion chamber.
3 Brush out the burner with a bristle paintbrush.
NOTE --- When removing the airtight chamber cover it is not necessary to remove the screws lo­cated at the top edge on either side.
9.9 Checking the flue
Have the integrity of the flue outlet pipe (49 on page 13) air intake pipe (50 on page 13), checked periodically, the venturi device* (46 on page 13) cleaned and the efficiency of the flue safety circuit checked at least once a year.
* For details see the section Fan, venturi device and air pressure switch in the service manual.
For all the above maintenance operations it is ad­visable to call an approved Service Engineer.
9.10 Drain pipe inspection
Check the soundness and integrity of the conden­sate drain pipe.
Verify the cleaness and correct filling of the con­densate traps.
9.11 Visual inspection of
appliance
Visually inspect all water joints, seals and connec­tions for any evidence of leakage and retighten, grease or replace them as necessary.
9.7 Checking the pressurisation
in the expansion vessel
Empty the central heating system as described in section 9.4 of this chapter and checkthat thepres-
38
9.12 Gas pressures and soundness
Check appliance for gas soundness. Recheck op­erational pressures and adjust as necessary as described in section 7.7 page 32 of this manual.
Page 43
Maintenance
MAINTENANCE
39
Page 44
Page 45
Page 46
Page 47
Page 48
*1796211132*
17962.1113.2 0605 48A5 UK
Biasi U.K. Ltd Unit 31/33, Planetary Road Industrial Estate, Neachells Lane Willenhall, Wolverhampton WV 13 3XB Technical helpline: 01902 304 400 Web site: www.biasi.co.uk
Loading...