To remove the side panels loosen the screws B and C
3
(Fig. 2.3), bring the base of the panels away from the
boiler and lift them, freeing them from the top hooks.
4
Fig. 2.1
1Right side panel
2Front panel
3Control panel lid
4Control panel cover
5Service panel
6Left side panel
2.2Body panels
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
For the most part of the check and maintenance operations it is necessary to remove one or more panels of
the case.
The side panels can be removed only after the removal
of the front panel.
To remove the front panel remove screws A (Fig. 2.2),
lift the panel and remove it.
B
C
Fig. 2.3 --- bottom view of the boiler
D
B
2.3Control panel
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
To gain access to the parts located inside the control
panel proceed as follows:
1Remove the front panel of the case.
2Loosen the screws B and C (Fig. 2.3).
3RemovethescrewsD.
4Move the lower part of the side panels as indi-
cated in Fig. 2.4 and pull the control panel.
When completely pulled out, the panel can rotate
45˚ downwards to facilitate the service operations on the internal parts.
2
Page 5
Fig. 2.4
5RemovethescrewsE and remove the service
panel (Fig. 2.5).
F
F
E
General access and emptying hydraulic circuits
To gain access to the parts contained in the sealed
chamber it is necessary to remove the lid of the s ealed
chamber.
For this purpose, remove the front and side panels of
the case, remove the screws G as indicated in Fig. 2.6
and remove the lid.
2.5Emptying the primary circuit
1Close the c.h. circuit flow and return cocks H.
(Fig. 2.7).
Fig. 2.5
6RemovethescrewsF andremovethecontrol
panel lid (Fig. 2.5).
2.4Access to the sealed chamber
G
H
K
Fig. 2.7 --- bottom view of the boiler
2Remove the front and right panels of the boiler.
3Open the drain tap I (Fig. 2.9 combi or Fig. 2.10
only c.h.) until the boiler is completely emptied.
4To help t he draining of the primary circuit loose
the condensing heat exchanger air purger valve
J (Fig. 2.8).
J
Fig. 2.6
G
Fig. 2.8
Attention: some water could remain in the condensing heat exchanger.
5Close drain tap once the emptying has been
completed.
3
Page 6
General access and emptying hydraulic circuits
I
Fig. 2.9
I
Fig. 2.10
2.6Emptying the d.h.w. circuit
6Close the d.c.w. inlet cock K (Fig. 2.7).
7Open one or more hot water taps until the boiler
has been completely emptied.
4
Page 7
3Diagrams
3.1Wiring diagram
M110B.24SM/... M110B.32SM/...
Electric supply
terminal block
LN
External controls
terminal block
bn
gnye
bu
bkbu
Three way
diverter valve
1
M
3
2
Gas valve
1
4
bu
bn
bu
gnye
5
gnye
123
bn
Pump
gnye bu
bn
~
rdbkwh
D.h.w. temperature
probe NTC
C.h. temperature
bu
bk
t
rd
probe NTC
t
bu
D.h.w. flow
switch
bu
wh
bn bu
bnbk bu
F1F2
X16
bn
whwh
F3
bu bn
LD1LD2LD3
Transfor mer
230V~ / 24V~
bn = brown
bu = blue
bk = black
wh = white
rd = r ed
gy = grey
gn = green
ye = yellow
vt = violet
og = orange
gnye = green/yellow
rdwh = red/white
Safety
wh
bu
X10X11
X13
X2
rd
bk
wh
gn
Time switch
rd wh bk
bnbu
X12
bububnbn
gnye
gnye
X3
T3
bu
bn
P6
Generator
Ignition
electrodes
gnye
K3
gnye
gy
X15
X6
bu bn
X24
bn bu
Spark
X7
X5
bu bn
X14
X17
K1
wh
whog
K2
K4
X22
rd
bk
bu
gy
wh
P3
bk
wh
Flame detection
electrode
X23
Fan
X1
LD4
Primary circuit
t
Flue
rd
rd
rd
flow switch
bkwh
SB1
rd
gybuwh
M
~
bk
gy
temperature
probe NTC
wh
bk
rd
NO
gy
wh
Safety
thermal fuse
bk rd
bu bu
gy
gy
X9
COM
gy
gy
thermostat
t
5
Page 8
Diagrams
3.2Wiring diagram
M110B.24SR/...
Electric supply
terminal block
LN
External controls
terminal block
bn
gnye
bu
bn bu
bnbk bu
123
bkbu
bn
Pump
gnye bu
bn
bnbu
bu bn
Gas valve
1
4
bu
bn
bu
gnye
5
gnye
C.h. temperature
probe NTC
bu
t
bu
X7
F1F2
X16
bn
whwh
F3
X5
bu bn
LD1LD2LD3
Transfor mer
230V~ / 24V~
bn = brown
bu = blue
bk = black
wh = white
rd = r ed
gy = grey
gn = green
ye = yellow
vt = violet
og = orange
gnye = green/yellow
rdwh = red/white
This reading is a reference value for the gas valve setting.
installation manual for proper values.
circuit and the intervention of the safety thermostat.
5A j a m m e d b y --- p a s s c o u l d c a u s e t h e o v e r --- h e a t i n g o f t h e m a i n
6Using the flue analyzer, check the CO
stop valves.
the flue terminal is correctly installed (see clearances) and en-
2Verify the soundness of the gas supply pipe, the position of
3C heck for soundness and absence of obstructions. Verify that
sert a flow rate limiter (14.6).
7Check the pressurization of the expansion vessel. Refer to the
8d.h.w. pressure too high or flow rate too high. If necessary in-
9The boiler doesn’t reach the nominal heat input.
sure that exhaust gas is not sucked back by the boiler.
(see also installation manual).
4C heck for soundness of the circuit and verify its correct filling
Defect
#
Section of the manual !
(note ref. in brackets)
The boiler does not supply d.h.w.
(cold water from the tap).
Regular operation in c/h mode even
during a drawing off d.h.w.
On c/h mode the temperature of the
main circuit reaches 90qCandthec/h
L o c k --- o u t s i g n a l l a m p r e d
system does not heat.
Incorrect modulationJJJJ
Noisy bolierJJJJJJ
Poor c.h. / d.h.w. temperature (9)JJJJJFPoor d.h.w. temperature. Regular
operationinc/hmode.
Low d.h.w. flow rateJJJ
Water leaks from the safety valve dur-
ing operation on c/h
Water leaks from the safety valve
The boiler operates correctly on
d.h.w. mode.
OF
when the boiler is off.
---
---
Note
Useful information can be obtained also from the
optical indication given by the appliance oper-
Verify the integrity of supply cable, plug and external fuses.
Check the polarity of line and neutral connection
ation l ights (see section 9.4).
1Check for 230V~ between line (L) and neutral (N)
9
Page 12
5Condensing heat exchanger
5.1Function
The Condensing heat exchanger A in Fig. 5.1 has the
function of transferring heat produced from combustion of the gas and from the flue exhausted gas to the
water circulating in it.
A
C
B
Fig. 5.1
By reducing the combustion products temperature, the
latent heat of the vapour is transferred to the water circuit, allowing an extra gain of useful heat.
The condensed vapour is then drained through the
condensate trap B and the draining pipe C.
H
J
IFEI
D
KLMN
G
5.2Removal
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
1D isconnect the flue system from the boiler.
2Remove the fan group (rubber pipe, gas pipe) fol-
lowing the instructions from 1 to 6 in section 17.2.
3D isconnect the detection electrode connector D,
the ignition electrodes connector E and the earth
wire F.
4D isconnect the fan connector G by pressing the
plastic hook placed on the side of the connector
(Fig. 5.2).
5Unscrew the nuts H (Fig. 5.2).
6Remove the fan---burner group I.
7Empty the primary circuit of the boiler.
8RemovetheclipsJ (Fig. 5.2).
9Loosen the connection K and slightly move the
pipe L upwards, turn it towards left (Fig. 5.2) and
then move the pipe downwards freeing it from the
Condensing heat exchanger.
Fig. 5.2
10Loosen the connection M and slightly move the
pipe N upwards, turn it towards left (Fig. 5.2) and
then move the pipe downwards freeing it from the
Condensing heat exchanger.
R
Q
P
O
10
Fig. 5.3
Page 13
Condensing heat exchanger
11Using pliers, remove the spring O moving it
downwards and disconnect the rubber pipe P
(Fig. 5.3).
12Unscrew the screws Q and remove the clamps
(Fig. 5.3).
13Disconnect the two connectors R by pressing the
plastic hook placed on the side of the connector
(Fig. 5.3).
14Remove the Condensing heat exchanger by
levering it and sliding it forwards.
15Reassemble the Condensing heat exchanger
carrying out the removal operations in reverse
order.
Ensure to tight the nuts H --- Fig. 5.2 firmly
5.3Cleaning
If there are deposits of dirt on the coil of the Condensing
heat exchanger, clean with a bristle paintbrush and re-
move the dust with a hoover.
Warning: After cleaning or replacement as
detailed above, if it deemed necessary to
undertake a combustion analysis, refer to
the appropriate chapter Maintenance of the
installation instructions manual.
S
Fig. 5.4
The siliconic gasket S Fig. 5.4 m ust be replaced
every 2 years.
11
Page 14
6D.h.w. heat exchanger
6.1Function
The d.h.w heat exchanger A in Fig. 6.1 and Fig. 6.3 allows the instantaneous transfer of heat from the primary
hydraulic circuit to the water destined for d. h.w use.
A
A
Fig. 6.1
The schematic structure is shown in Fig. 6.2.
B
Fig. 6.3
5Remove the pump following the instructions in
section 7.3.
A
C
Fig. 6.4
6Completely unscrew the Allen key screws C
(Fig. 6.4) w hich hold the exchanger to the plastic
groups.
7Move the exchanger towards the rear of the boiler
and extract it.
Reassemble the d.h.w.heat exchanger carrying out the
removal operations in the reverse order.
Primary hydraulic circuit
Domestic hot water circuit
Fig. 6.2
6.2Removal
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
1Remove the front and right hand side panels of
the case.
2Empty the primary circuit and the d.h.w circuit of
the boiler.
3Completely unscrew the A llen key screws B
(Fig. 6.3) which hold the exchanger to the brass
group.
4Remove the electric actuator following the in-
structions in section 8.3.
12
Warning: to lubricate the O-- ring gaskets
exclusively use a silicone base grease
compatible to be in contact with foods and
approved by the local water Authorities.
Attention. When reassembling the exchanger be
sure to put the off centre location/securing pin indicated in Fig. 6.5 towards the left side of the boiler.
Fig. 6.5
Page 15
7Pump
7.1Function
The pump A in Fig. 7.1 and Fig. 7.2 has the function of
making the water in the main circuit circulate through
the main condensing heat exchanger and therefore
through the c.h. system (during the c.h. function) or
through the secondary heat exchanger (during the
d.h.w. function).
A
nCheck that the impeller is integral with the rotor.
With the boiler off remove the front and right hand side
case panels, lower the control panel and empty the pri mary circuit.
Remove the pump head by undoing the screws which
hold it to the pump body and check that the impeller is
firmly joined to the rotor.
7.3Removal
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
1Remove the front and right hand side case pan-
els.
2Empty the primary circuit of the boiler.
3Extract and lower the control panel.
4Disconnect the connector B (Fig. 7.2)(Fig. 7.3).
5Loosen the connection C,and pull up and turn to
the left the pipe D.
6C.h. only model remove the fork E and remove
pressure gauge connection F (Fig. 7.3)
7C.h. only model remove the fork G, loosen the
connection H and remove the pipe I (Fig. 7.3)
Fig. 7.1
7.2Checks
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
nCheck that the pump is not seized and that the
movement of the rotor is not subject to mechanical impediments.
With the boiler off, remove the front panel. Remove the
air release plug of the pump and turn the rotor with a
screwdriver.
nCheck the electrical continuity.
With the boiler off, remove the front panel and disconnect the connector B (Fig. 7.2).
Measure the electrical resistance between the pump
supply connections.
D
C
B
A
Fig. 7.2
D
C
E
J
K
H
I
F
G
Electrical resistance of the windings (at ambient temperature) must be about 230 8.
nCheck the absence of starting defects.
With the boiler off remove the front case panel.
Remove the air release plug from the pump. Start the
boiler and with a screwdriver, turn the rotor in the direction of the arrow. If there is a defect in starting, the rotor
will begin to turn normally only starting it manually.
B
A
Fig. 7.3 c.h. only model
8Remove the locking plate J.
J
K
13
Page 16
Pump
9Unscrew the two screws K that hold the pump on
theframeandremovethepump.
Reassemble the pump carrying out the removal operations in the reverse order. When reassembling the
pump, check the correct location of the O---ring gasket
in the inlet port of the pump that seals the connection
between the pump and the plastic group.
14
Page 17
8Three way diverter valve
8.1Function
The diverter valve A (Fig. 8.1) has the function of modifying the hydraulic circuit of the boiler by means of an
electric command given by the electronic control p.c.b.
in order to send the water that exits the primary heat exchanger towards the c. h. system or towards the d.h.w.
heat exchanger.
A
B
3
2
rd = r ed
bk = black
wh = white
F i g . 8 . 2 --- D . h . w . m o d e
B
bk
wh
230 V
3
2
Spindle B
not visible
1
9,4 Kohm
Open circuit
rd
0V
Spindle B
visible
1
Open circuit
Fig. 8.1
8.2Checks
nCheck the electrical continuity
Fig. 8.2 indicates the relationship between the electric
command coming from the electronic control p.c.b.
and the positionof the actuator B (brass spindle) when
the boiler operates in d.h.w. mode.
Fig. 8.3 indicates the relationship between the electric
command coming from the electronic control p.c.b.
and the position of the actuator B (brass spindle) when
the boiler operates in c.h. mode.
In both figures the relationship between the position of
the actuator and the resistance of the motor windings
(the motor must be disconnected from the wiring) is
also given.
rd = r ed
bk = black
wh = white
F i g . 8 . 3 --- C . h . m o d e
wh
bk
0V
rd
230 V
9,4 Kohm
8.3Removal of the electric actuator
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
1Remove the front case panel.
2D isconnect the connectors C (Fig. 8.4).
3Remove the fixing spring D and remove the
actuator E.
Reassemble the actuator carrying out the re -
moval operations in the reverse order.
When reassembling the actuator, refer to Fig. 8.2
--- Fig. 8.3 or to the wiring diagram in section 8.2
for the correct wiring connection.
15
Page 18
Three way diverter valve
E
C
D
Fig. 8.4
8.4Removal of the diverter group and its
internal parts
1Removethefrontandbothsidecasepanels.
2Empty the primary circuit and the d.h.w. circuit of
the boiler.
3Remove the electric actuator (see section 8.3).
4Remove the fixing spring F (Fig. 8.5) and remove
the primary circuit flow switch G.
5D isconnect both c.h. and d.h.w. temperature
probe, respectively H and I .
6Unscrew the connector J, the c.h. flow connector
and the d.h.w. outlet connector.
L
L
M
Fig. 8.6 Rear view of the boiler
10Refer to the exploded view in Fig. 8.7 to remove
the internal parts of the three way diverter valve.
J
H
Fig. 8.5
F
G
I
7Remove the d.h.w. heat exchanger (see section
6.2).
8RemovetheforkK andmoveawaythepipeL
(Fig. 8.6).
9Unscrew the screw M andremovethediverter
group.
Fig. 8.7
11Reassemble the diverter group carrying out the
removal operations in the reverse order.
Warning: to lubricate the O-- ring gaskets
exclusively use a silicone base grease
compatible to be in contact with foods and
approved by the local water Authorities.
16
Page 19
9Electronic control/ignition p.c.b.
9.1Function
Inlet Information
OntheElectroniccontrol/ignition
p.c.b.......
Function control
C.h. temperature adjustment
D.h.w. temperature adjustment
Boiler reset button
(control panel fascia)
From other boiler devices....
C.h. temperature probe NTC
D.h.w. temperature probe NTC
D.h.w. flow switch
Primary circuit flow switch
Flue temperature probe NTC
Safety thermal fuse
Safety thermostat
Flame detection electrode
Room thermostat (if fitted)
Time switch
Outlet command
Pump
Three way diverter valve
Gas valve
Fan
Ignition electrodes
Appliance operation lights*
L o c k --- o u t s i g n a l l a m p *
*control panel fascia
Fig. 9.1
The fundamental function of the Electronic control/ignition p.c.b. is that of controlling the boiler in relation t o
the external needs (i.e. heating the dwelling or heating
the water for d. h.w. use) and operating in order to keep
the temperature of the hydraulic circuits constant.
This is obviously possible within the useful power and
maximum working temperature limits foreseen.
Generally, the Electronic control/ignition p.c.b. receives
inlet information coming from the boiler (the sensors)
or from the outside (knobs, room thermostat, etc.), processes it and consequently acts with outlet commands
on other components of the boiler (Fig. 9.1).
The Electronic control/ignition p.c.b. is also a full sequence ignition device and does a sequence of operations (ignition cycle) which lead to the ignition of the
gas at the burner
It checks the presence of the flame during the entire
period in which it is activated and supplies the fan regulating its speed.
The Electronic control/ignition p.c.b. has a safety func-tion and any incorrect interventions or tampering can
result in conditions of dangerous functioning of the
boiler.
The Electronic control/ignition p.c.b. can lock the functioning of the boiler (lock state) and stop its functioning
up to the resetting intervention. The lock is signalled by
the lighting of the lock--- out signal lamp and the device
can be reset only by using the boiler reset button
placed on the control panel fascia.
Some components which are connected to the device
can activate the lock state. The causes of a lock state
could be:
fThe intervention of the safety thermostat (over-
heat of the primary circuit).
fThe intervention of the flue temperature probe
(overheat of the combustion products).
fA fault on gas supply.
fFaulty ignition (faulty ignition electrodes, their wir-
fFaulty gas valve (faulty on ---off operators or not
electrically supplied).
fFaulty Electronic control/ignition p.c.b..
Other components like the primary circuit flow switch
can temporarily stop the ignition of the burner but allow
its ignition when the cause of the intervention has
stopped.
Fig. 9. 20 and Fig. 9.21 show the sequence of the operations that are carried out at the start of every ignition
cycle and during normal functioning.
9.2Selection and adjustment devices
On the Electronic control/ignition p.c.b. several selection, adjustment and protection devices are located.
(Fig. 9.2).
Some of these devices are directly accessible by the
user (function control, temperature adjustment poten-
17
Page 20
Electronic control/ignition p.c.b.
tiometers etc.) others, like the fuses, are accessible by
removing the service panel.
32610
131112141719151618
Fig. 9.2
917845
1x7 connector --- electric supply terminal block and
external controls terminal block.
2Fuse F1, F2 3,15 A F
3Fuse F3, 400 mA T
4x12 connector --- pump and 3way diverter valve
5x17 connector --- gas valve
6x14 connector --- external temperature probe
(optional)
7x9 connector --- safety thermostat, flue t empera-
ture probe NTC, c.h. temperature probe NTC
8x11 connector --- d.h.w. temperature probe
9x10 connector --- d.h.w. flow switch
10x13 connector --- remote control (optional)
11x2 connector --- timer
12Lock --- out signal lamp
13Boiler reset button
14Function control / C.h. temperature adjustment
15x22 connector --- fan
16x24 connector --- transformer
17D.h.w. temperature adjustment
18x5 connector --- transformer
19Appliance operation lights
9.3Checking the temperature
The Electronic control/ignition p.c.b. makes it possible
to separately adjust the c. h. water flow temperature and
d.h.w. outlet temperature.
The temperature of the water is converted into an elec tric signal by means of temperature probes.
The user, setting the desired temperature with the control panel knobs operates the variable elements (14 and
17 in Fig. 9.2) of the electronic control p.c.b.
If the power requested is lower than 40% of the maximum power output then control is achieved by switching ON the burner at minimum power, then switching
OFF (ON/OFF function). If the power requested is
higher, then the burner is switched ON at maximum
power and will control by modulating to 40% of the
maximum power output.
During the c.h. operation (Fig. 9.3), the signal coming
from the c.h. temperature probe is compared to the signal given by the control panel through the adjustment
made by the user (knob
). The result of such a com-
parison operates the fan speed thus regulating the gas
flow rate and consequently changing the useful output
of the boiler.
Fig. 9.3
When the boiler functions in d.h.w. (Fig. 9.4), the signal
coming from the d.h.w. temperature probe is compared
with the signal given by the control panel through the
adjustment made by the user (knob
).
18
Page 21
Electronic control/ignition p.c.b.
With the boiler switched ON (or)allthelamps
(19 in Fig. 9.2) are activated.
The following table gives the relationship between each
of the possible lamp combinations and their meaning.
Normally operating boiler
(see the p revious table for details)
C.h. operation
D.h.w. operation
Frost protect operation
D.h.w. operation
Excessive temperature on primary circuit
Faulty c.h. temperature probe NTC
90 ˚C
Fig. 9.4
Normally, the result of the comparison between these
two signals directly operates the fan speed adjusting
the useful output generated in order to stabilize the
temperature of the exiting water.
If during the d.h.w. mode operation, the temperature of
the primary circuit goes over 90qC, the useful output is
automatically reduced so that the primary circuit can-
not reach excessive temperatures.
The control sequences in
function and infunc-
tion are illustrated in detail in sections 9.11 and 9.12.
9.4Operation lights
The Electronic control/ignition p.c.b. is provided with
three lamps (L.E.D. indicators) 19 in Fig. 9.2 that give
optical information during the operation of the boiler.
The green lamp on the left gives information whether
the boiler is in stand ---by mode or during the normal
operation of the boiler.
The following table gives the relationship betw een the
lamps indication and their meaning.
Faulty d.h.w temperature probe NTC
Faulty primary circuit
(no water or absence of flow)
Lack of burner ignition
Safety thermostat lock out
Faulty fan control system
Flue temperature probe NTC lock out
Open flue temperature probe NTC
Faulty external temperature probe NTC
Flame detection error
Lack of power supply or faulty electronic
control p.c.b.
Faulty Electronic control/ignition p.c.b.. *
Lamp
OFF
* These conditions are normal only for a short time when the
power supply is applied to the boiler.
If permanent they indicate a faulty p.c.b.
Lamp
ON
Flashing lamp, alone
or simultaneously
with an other lamp.
Flashing lamp,
alternate with
another lamp.
A short pulse every 4 seconds
1secondON1secondOFF
Boiler in stand --- by condition.
(function control in
position).
Anti--- freeze system active.
Boiler ON condition
(function control inor
position)
9.5Setting the boiler control function modes
It is possible to select the various boiler control function
modes by using the function selector knob A and the
D.h.w. temperature control knob B (Fig. 9.5).
On model M110B.24SR/... the knob B is used just for
boiler setting and doesn’t affect the boiler functions
during the normal operation.
During the function modes setting, the boiler does not
operate.
19
Page 22
Electronic control/ignition p.c.b.
A
B
Fig. 9.5
CED
9.6Adjustment of maximum useful output in
c.h. mode
The following procedure allows the output of the boiler
for c.h. to be limited to meet the system requirement.
Adjusting the maximum useful output in c.h. mode
does not prevent the boiler firing at maximum rate for
d.h.w. production.
1Turn the boiler ON positioning the function selec-
tor knob A as indicated in Fig. 9.6.
Knob positionMaximum useful output in c.h. mode
15,8 (19 789)8,2 (27 977)
29,0 (30 707)12,4 (42 307)
312,2 (41 625)16,5 (56 296)
415,5 (52 884)20,7 (70 626)
518,7 (63 802)24,8 (84 614)
621,9 (74 720)29,0 (98 944)
725,1 (85 638)33,1 (112 933)
Tab . 9 . 1
non condensing
kW (BTU/h)
M110B.24SM/...
M110B.24SR/...
4
3
2
1
M110B.32SM/...
5
6
7
B
Fig. 9.8
5To memorize the setting keep pressed the reset
button C for about 5 seconds until the lights E
briefly blinks simultaneously.
6To reset the boiler to the normal operation turn it
OFF and ON by the function selector knob A. In
any case, the boiler automatically resets to its normal operation after 10 minutes.
E
Fig. 9.6
AB
C
D
2Keep pressed the reset button C for about 10 sec-
onds until the lock--- out signal lamp D blinks.
3The lamps E should give the indication as in
Fig. 9. 7 (maximum c.h. useful output adjust-
ment). If not, press the reset button repeatedly to
obtain it.
Where:
Fig. 9.7
Lamp OFF
Lamp ON
At this step it is possible to visualize the current setting
by keeping the reset button C pressed for more than 5
seconds. The lamps will flash a number of times corresponding to the setting (Tab. 9.1 and Fig. 9.8).
4To change the setting turn the knob B on a posi-
tion corresponding to the desired maximum use-
ful output (Tab. 9.1 and Fig. 9.8).
By turning the knob B, the lock ---out signal lamp
D blinks quickly (2 per seconds) indicating that
the setting has changed and must be memo-
rised.
20
9.7Reignition frequency setting
It is possible to select the minimum time that must pass
between two ignitions of the burner in c.h. function
mode.
1Turn the boiler ON positioning the function selec-
tor knob A as indicated in Fig. 9.9.
E
Fig. 9.9
2Keep pressed the reset button C for about 10 sec-
onds until the lock--- out signal lamp D blinks.
3The lamps E should give the indication as in
Fig. 9. 10 (reignition frequency). If not, press the
reset button repeatedly to obtain it.
Where:
Fig. 9.10
At this step it is possible to visualize the current setting
by keeping the reset button C pressed for more than 5
AB
C
Lamp OFF
Lamp ON
D
Page 23
Electronic control/ignition p.c.b.
seconds. The lamps will flash a number of times corre-
sponding to the setting (Fig. 9.11).
4To change the setting turn the knob B on a posi-
tion corresponding to the desired delay.
By turning the knob B, the lock ---out signal lamp
D blinks quickly (2 per seconds) indicating that
the setting has changed and must be memorised.
4
51/2
4
5
7
6
7
81/2
B
Delay (minutes)
Setting No.
Fig. 9.11
11/2
0
3
3
2
1
5To memorize the setting keep pressed the reset
button C for about 5 seconds until the lights E
briefly blinks simultaneously.
6To reset the boiler to the normal operation turn it
OFF and ON by the function selector knob A. In
any case, the boiler automatically resets to its normal operation after 10 minutes.
Factory setting = 3 minutes
9.8Combi / C.H. only mode setting
Two different options are available on the Electronic
control/ignition p.c.b. and proper setting must be done
after a replacement of the p.c.b.
1Remove the front panel of the case.
2Turn ON the power supply. Lamps E give the in-
dication as in Fig. 9.12.
6Press the reset button C repeatedly (2 times) until
the lamps E give the indication as in Fig. 9.14
(boiler mode).
Where:
Fig. 9.14
Lamp OFF
Lamp ON
At this step it is possible to visualize the current setting
by keeping the reset button C pressed for more than 5
seconds. The lamps E will flash a number of times
corresponding to the setting (Fig. 9.15).
M110B.24SR/...
4flashes
M110B.24SM/...
M110B.32SM/...
1flash
B
Fig. 9.15
7To change the setting turn the knob B on a posi-
tioncorrespondingtotheboilermodels
(Fig. 9.15). By turning the knob B, the lock--- out
signal lamp D blinks quickly (2 per seconds) indicating that the setting has changed and must be
memorised.
8To memorize the setting keep pressed the reset
button C for about 5 seconds until the lights E
briefly blinks simultaneously.
9Press the reset button C once until the lamps E
give the indication as in Fig. 9.16 (boiler mode).
Where:
Fig. 9.12
Lamp OFF
Lamp Flashing
3Position the function selector A as in NO TAG and
disconnect the C.h. temperature probe.
4Keep pressed the reset button C for about 10 sec-
onds (Fig. 9.13) until the lock--- out signal lamp D
blinks.
5Connect the c.h.temperature probe.
E
Fig. 9.13
AB
C
D
Where:
Fig. 9.16
Lamp OFF
Lamp ON
It’s now possible to check the current setting by pressing reset button C for more than 5 seconds. The three
lamps E will flash a number of times corresponding to
the setting as in Fig. 9.17 (once for the combination and
four times for system boilers). At this point only the right
green light flashes.
M110B.24SR/...
4flashes
M110B.24SM/...
M110B.32SM/...
1flash
B
Fig. 9.17
21
Page 24
Electronic control/ignition p.c.b.
10Turn the water control to minimum. Lock--- out
lamp blinks (2 per second) indicating the setting
has changed
11To change the setting turn the k nob B on a posi-
tioncorrespondingtotheboilermodel
(Fig. 9.17).
12To memorize the setting keep pressed the reset
button C for about 5 seconds until the lights E
briefly blinks simultaneously. At this point only the
right green light flashes.
13To reset the boiler to the normal operation turn it
OFF and ON by the function selector knob A.
9.9Checks
nCheck that the fuses are complete
If the Electronic control/ignition p.c.b. does not supply
any device (pump, fan, etc.) check that the fuses 2 and
3(Fig. 9.2) are complete.
If a fuse has blown replace it with one that has the same
characteristics after having identified the reason for failure.
nLock sequence
Start the boiler until the burner is ignited.
With the burner firing, interrupt the gas supply. The
Electronic control/ignition p.c.b. must carry out four
complete ignition cycles and then, after about 4 minutes, goes to lock --- out state.
By turning the boiler on and off by means of the function
switch the device must not unlock and the burner must
not turn on.
9.10Removal of the electronic control p.c.b
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
When replacing the Electronic control/ignition
p.c.b. it is advisable to go throughthe setting modes
of the boiler here described in sections 9.5 to 9.7.
The spare electronic control/ignition p.c.b. is set for
natural gas.
If the boiler is fed with different gas type, go through
the Gas conversion operations described in the In-
stallation manual.
If an external temperature probe (optional) is fitted,
the coefficient K has also to be set as described in
the Commissioning chapter of the installation manual.
1Gain access to the parts located inside the con-
trol panel as explained in the section 2.3 of this
manual.
2Remove all the wiring connected to the Electronic
control/ignition p.c.b.
.
To disconnect the connectors delicately flex t he
hook present on one side of each socket.
3Remove the spindles of the c.h. and d.h.w. tem -
perature adjustment knobs by delicately pulling
them with pliers in the direction shown by the
arrow in Fig. 9.18
Fig. 9.18
.
4Unscrew the four screw s that hold the Electronic
control/ignition p.c.b. on to the control panel.
5Remove it by lifting its rear edge and freeing it
from any of the wiring.
6Re---assemble the Electronic control/ignition
p.c.b. following the removal procedures in the reverse order.
Important
When re ---assembling the Electronic control/ignition
p.c.b.:
7It is not necessary to utilise static protections but
it is advisable to ensure that the pcb is handled
with care and h eld at the edges and with clean dry
hands.
8Fit the p.c.b. into the control panel by first insert-
ing the front lower edge under the control knob
shafts. Lower the rear edge and ensure that no
wiring is trapped beneath.
9Insert the spindles in the control panel knobs until
the notch A (Fig. 9.19) reaches the potentiometer
edge. It is not necessary to force them in the
knob.
10While tightening the screws that fix the Electronic
control/ignition p.c.b. on the control panel, keep
the p.c.b. towards the control panel fascia mak-
22
Page 25
Electronic control/ignition p.c.b.
ing sure of the contact between the boiler reset
button B and the tab C (Fig. 9.19).
A
Fig. 9.19
A
B
C
Attention
After installing the Electronic control/ignition p.c.b. :
11Make sure the c.h. (
) and d.h.w. ()tem-
perature adjustment knobs can move freely for
the complete range.
If not, remove the spindle again as described at
step 3, turn the knob half a turn and re --- insert the
spindle.
12Make sure that the settings comply with the in-
dications given in section 9.5.
13Operate the boiler and close the gas inlet cock so
that the boiler goes into the safety lock ---out state.
Verify the correct operation of the boiler reset button by pressing and releasing it.
Warning: After cleaning or replacement as
detailed above, if it deemed necessary to
undertake a combustion analysis, refer to
the appropriate chapter Maintenance of the
installation instructions manual.
23
Page 26
Electronic control/ignition p.c.b.
9.11Thermal control in the ””mode
Switch in thefunction mode
YES
Operation lights
temperature higher than that
circulator on
Is primary circuit
selected?
NO
NO
YES
YES
checks fan rpm
water from the domestic hot
starts fan
Is fan rpm
exact?
Tak i n g
water circuit?
YES
lock memorised?
Main circuit pressure
YES
NO
switch consense?
NO
temperature higher than 110˚C?
circulator off
fan still
YES
NO
Is flue
stop circulator (3min)
Operation lights
cancels lock
NO
starts ignition discharges
Opens gas valve
beginning of ignition period
NO
NO
Is fan rpm
exact?
turns on lock --- out light
Opeartion lights
flame presence?
YESNO
End of ignition
period?
YES
End of wait
period?
YES
flame presence?
NO
closes gas valve
interrupts ignition discharges
memorizes lock
turns on lock --- out light
NO
r e s e t p u s h --- b u t t o n
stops fan
pressed?
YES
beginning of wait period
YES
YES
interrupts ignition discharges
YES
gas valve open
fan runs
Fig. 9.20
24
safety thermostat or flue
temperature probe lock out?
YES
YESNO
flame presence?
NO
Page 27
9.12Thermal control in the ””mode
Switch in thefunction mode
Electronic control/ignition p.c.b.
See functioning with the function
control in themode
(sec. 9.11)
YES
Opeartion lights
Is primary circuit
temperature higher than that
selected?
NO
NO
YES
YES
checks fan rpm
water from the domestic hot
starts fan
Is fan rpm
exact?
Tak i n g
water circuit?
YES
lock memorised?
Main circuit pressure
YES
NO
circulator on
switch consense?
NO
temperature higher than 110˚C?
Request for heat from
room thermostat?
YES
NO
Is flue
NO
circulator off
fan still
stop circulator (3min)
Operation lights
cancels lock
NO
starts ignition discharges
Opens gas valve
beginning of ignition period
NO
NO
Is fan rpm
exact?
turns on lock --- out light
Opeartion lights
flame presence?
YESNO
End of ignition
period?
YES
End of wait
period?
YES
flame presence?
NO
closes gas valve
interrupts ignition discharges
memorizes lock
turns on lock --- out light
NO
r e s e t p u s h --- b u t t o n
stops fan
pressed?
YES
beginning of wait period
YES
YES
interrupts ignition discharges
YES
gas valve open
fan runs
Fig. 9.21
safety thermostat or flue
temperature probe lock out?
YES
YESNO
flame presence?
NO
25
Page 28
10Transformer
10.1Removal
2D isconnect the four connectors A.
3Unscrewthe screws B andremovethe
Transformer C by sliding it forward.
4Reassemble the Transformer carrying out the re-
moval operations in the reverse order.
After reassembling ensure the wires are correctly
connected (see Fig. 10.2)
C
B
A
Fig. 10.1
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
1Removeallthecasepanelsandthesealed
chamber lid (see section 2).
smaller
connector
smaller
connector
Fig. 10.2
larger
connector
clamp for fitting
the transformer
larger
connector
10.2Check the transformer
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
1Remove the Transformer (see section 10.1)
2Measure the electrical resistance of the primary
and secondary windings.
The primary should have a resistance approx. 35
ohm and the secondary approx. 1,4 ohm.
26
Page 29
11Gas valve
11.3Adjustment
11.1Function
The Gas valve A in Fig. 11.1 controls the gas inflow to
the boiler burner.
A
Fig. 11.1
By means of an electric command given to the on ---off
operators the passage of the gas through the Gas valve
can be opened or closed.
Warning: isolate the boiler from the mains
electricitysupplybeforeremovingany
covering or component.
Check the supply pressure before making any adjustment to the gas valve.
1Close the gas inlet valve.
2Remove the front panel of the case and lower the
control panel (see sections 2.2 and 2.3).
3Loosen the internal screw on the Inlet Pressure
Test Point 5 (Fig. 11.2) of the Gas valve and connect a pressure gauge using a suitable hose.
4Open the gas inlet valve.
5Turn on the electricity supply to the boiler, switch-
ing on the fused spur isolation switch.
The appliance operation light on the left will flash
every 4 seconds.
6Set the function knobs as illustrated in Fig. 11.4.
7Open at least one hot water tap fully.
8Read the inlet pressure value and ensure that it is
within the limits given in the table Gas supplypressures, of the user/installation manual
If it does not comply with the required pressure
check the gas supply line and governor for faults
and/or correct adjustment.
9Switch off the boilerclose the gas inlet valve and
close the water tap.
10Disconnect the pressure gauge and close the
Inlet Pressure Test Point 5 (Fig. 11.2).
11.2Description of the parts (Fig. 11.2)
1Maximum gas pressure adjustment
2Minimum gas pressure adjustment
3On---off operators
4On --- off operators electric connector
5Gas valve inlet pressure test point
1
2
5
4
Fig. 11.2
Gas valve adjustment
11Fit the probe of the flue analyser in the flue ex-
haust sampling point located on the exhaust
pipes of the boiler (Fig. 11.3).
air--- flue exhaust
sampling points
3
Fig. 11.3
12Turn on the boiler, switching on the fused spur
isolation switch.
13Open the gas inlet valve.
14Set the function knob B as indicated in Fig. 11.4.
The appliance operation light on the left will flash
every 4 seconds.
27
Page 30
Gas valve
E
Fig. 11.4
BF
C
D
15Keep pressed the reset button C for about 10
seconds (Fig. 11.4) until the lock--- out signal
lamp D blinks.
16The lamps E should give the indication as in
Fig. 11.5.
Where:
Fig. 11.5
Lamp OFF
Lamp ON
17Release and keep the reset button C pressed for
more than 5 seconds until the lock --- out signal
lamp D is switched off.
The boiler will now go through an ignition sequence and the burner w ill light.
18Open at least one hot water tap fully.
Adjusting minimum gas valve setting
19Set the knob F to the minimum position as illus-
trated in Fig. 11.6.
E
Fig. 11.7
BF
C
D
23Allow the analyser to give a stable reading.
24Read the CO
%value.
2
It should be between 9,0 and 9,8 % (natural gas
G20) or between 10,0 and 11,0 % (LPG G31).
To ad j u s t t h e CO
Fig. 11.2) (by rotating it clockwise the CO
% value rotate screw (1 ---
2
2
%de-
creases).
25Switch off the boiler and turn off the hot wat er
tap(s).
26Close the air---flue sampling points.
27After adjustment fit the protective brass plug (2,
Fig. 11.2).
Important: after the gas pressure checks and any
adjustment operations, all of the test points must be
sealed.
11.4Checks
Warning: isolate the boiler from the mains
electricitysupplybeforeremovingany
covering or component.
nCheck the on--- off operators coils
1Remove the front panel of the case.
2Disconnect the electrical connector 4 (Fig. 11.2).
3Measure the electrical resistance between the
connector pins of the on--- off operators as illustrated in Fig. 11.8.
E
Fig. 11.6
BF
C
D
20Allow the analyser to give a stable reading.
21Read the CO
%value.
2
It should be between 9,0 and 9,8 % (natural gas
G20) or between 10,0 and 11,0 % (LPG G31).
To a d j u st t h e C O
% value remove the brass plug
2
by unscrewing it and rotate the Allen key screw ø
4 mm (2 --- Fig. 11.2) (by rotating it clockwise the
%increases).
CO
2
Checking the maximum gas valve setting
22Set the knob F to the maximum position as illus-
trated in Fig. 11.7.
28
ON---OFF Operator
approx. 6 400 8*
ON---OFF Operator
approx. 920 8*
* at ambient temperature.
Fig. 11.8
11.5Removal of the gas valve
Warning: isolate the boiler from the mains
electricitysupplybeforeremovingany
covering or component.
1Remove the front panel of the case as explained
in the section 2.3 of this manual and the sealed
chamber lid.
2RemovethescrewG and disconnect the con-
nector H (Fig. 11.9).
Page 31
Gas valve
5Unscrew the connector K (Fig. 11.9), remove the
fixing fork L and remove the pipe M (Fig. 11.10).
K
J
I
HG
Fig. 11.9
3Turn off the gas supply and disconnect the gas
isolation cock connector from the inlet port of the
gas valve.
4Using pliers, remove the spring I and the rubber
pipe J (Fig. 11.9).
L
M
Fig. 11.10
N
Fig. 11.11
6Unscrew the s crews N and remove the valve
(Fig. 11.11).
7Reassemble the valve carrying out the removal
operations in reverse order.
Before to fit a new valve it is advisable to pre -- set it
as hereafter explained.
8Remove the brass plug and turn the plastic screw
inside it fully clockwise until it stops. Do not overtight.
9Turn it counter---clockwise 2 and 3/4 turns.
10Adjustthegasvalveusingtheflueanalyserasde-
scribed in section 11.3.
After any service operation on the components of
the gas circuit check all the connections for gas
leaks.
Warning: After cleaning or replacement as
detailed above, it is deemed necessary to
undertake a combustion analysis as detailed
in chapter 11.3 section 11.
29
Page 32
12Primary circuit flow switch
12.1Function
The Primary circuit flow switch (A in Fig. 12.1) function
is to detect water flow rate through the primary hydraulic circuit of the boiler.
A
I
Boiler OFFB oiler ON
Fig. 12.2
B
nElectrical check
It is possible to verify the general operation of the switch
by measuring the electric resistance between the contacts C. and N.O. of the switch.
1Remove the switch as explained in section
NO TAG.
2Measure the electrical resistance between the
tabs marked C. and N.O. (Fig. 12.3).
The contact must be normally open.
3Operate the switch by hand and verify that the
contact is now closed.
C
N.O.
do not use
Fig. 12.3
12.3Removal
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
Fig. 12.1
This hydraulic/membrane operated electrical micro--switch device will control the functioning of the ignition
control circuit, providing there is an adequate quantity
and flow of water in the primary circuit. Any failure of the
pump or obstructions in the primary circuit, whilst in
either c.h. or d.h.w. modes, will not allow the device to
operate.
This device is connected to the electronic control p.c.b.
and if, after the pump operates, it does not activate within 20 seconds the control board w ill indicate that a fault
condition (see section 9.4 of this manual) has occurred.
12.2Checks
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
nMechanical function
1Remove the front panel of the case.
2Start and stop the boiler either in d.h.w. or c.h.
mode.
3Looking through the switch box verify the position
of the lever B referring to Fig. 12.2.
30
nRemoval of the switch
1Remove the front panel of the case.
2RemovetheforkC (Fig. 12.4).
3Open the box and disconnect the switch.
4Re --- assemble the parts in reverse order of re-
moval. Refer to Fig. 12.3 for the correct wiring
connectors on the switch
Removal of the membrane
n
1Remove the front and right hand side panels of
the case, turn off the flow and return isolation
valves and empty the primary circuit.
2RemovetheforkC that holds the micro---switch
housing D (Fig. 12.4).
C
D
Fig. 12.4
Page 33
Primary circuit flow switch
3Unscrew the four screws E (see Fig. 12.5) open
the hydraulic operator and remove the membrane F.
F
G
E
H
Fig. 12.5
4Reassemble the parts in reverse order of removal.
When assembling the membrane, ensure that its
concaveside faces towards the actuator plate G and
the reference indicated aligns with the seat H (see
Fig. 12.5).
13Expansion vessel and
temperature---pressure gauge
13.1Function
sion vessel can be changed without removing the
boiler.
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
1Remove the front and left hand side panels of the
case, turn off the flow and return isolation valves
and empty the primary circuit.
2Completely unscrew the connection K,thelock-
nut L (Fig. 13.2) and remove the expansion
vessel from the top of the boiler.
L
K
The Expansion vessel (I in Fig. 12.1) function is to allow
for the volume expansion of the c.h. circuit water due
to the temperature rise.
13.2Checks
1Turn off the flow and return isolation valves and
empty the primary circuit of the boiler.
2Remove the protective cap J (Fig. 13.1) from the
valve on the top of t he expansion vessel and connect a suitable air pressure gauge.
I
Fig. 13.1
3Check the pre--- load pressure and refer to the
section Expansion vessel in the User manual andinstallation instructions for the correct value.
Fig. 13.2
3Re --- assemble the parts in reverse order of re-
moval.
13.4Removal of the temperature---pressure
gauge
1Remove the front and right hand side panels of
the case, turn off the flow and return isolation
valves and empty the primary circuit.
2RemovetheforkM and the probe holder spring
N (Fig. 13.3).
3Squeeze the tabs O to release the temperature ---
pressure gauge P and remove it.
4Re --- assemble the parts in reverse order of re-
moval.
M
N
O
P
13.3Removal of the expansion vessel
If there is at least 400 mm clearance above the boiler
and the rear exit flue can be easily removed, the expan-
Fig. 13.3
31
Page 34
14D.h.w. flow switch, filter and flow
limiter
14.1Function
The d.h.w. flow switch A in Fig. 14.1 is a device that
generates an electrical signal when hot water is drawn.
2
1
3
4
A
Fig. 14.1
Whentheflowratethroughthed.h.w.circuitreaches
about 2,5 litres/min’, the float 5 (Fig. 14.3) is dragged
upwards and the magnetic in it, getting closer to the
sensor 8 closes the electric contact.
D
C
8
Fig. 14.3
5
6
7
14.3Checks
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
nSensor operation
1Remove the front panel of the case.
2Measure the electrical resistance at the leads of
the sensor. Without water being drawn, the contact must be open. By opening a hot water tap the
contact must be close (electrical resistance zero
8).
14.4Removal of the sensor
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
1Remove the front panel of the case.
2D isconnect the connectors B and remove the
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
1Remove the front panel of the case and empty the
d.h.w. circuit.
2Remove the sensor (see section 14.4).
3RemovetheforkD andpulluptheflowswitch
plug 1 with the help of a screwdriver.
4To remove the filter from the flow switch group
separate the filter 6 from the body 4 (Fig. 14.3) by
levering it.
5Reassemble the parts following the removing se-
quence in reverse order.
14.6Flow limiter
The M110B.24SM/... model is factory fitted with a 10
litre/min. flow limiter.
Page 35
D.h.w. flow switch, filter and flow limiter
If on the M110B.32SM/... model the flow rate of the
d.h.w. circuit is too high, it is possible to limit it by installing a flow limiter. The following sizes are available:
Nominal flow rate (litres/min)
Colour
10Blue
12Red
14Pink
To in st a ll t h e f l o w l i m it e r:
1Remove the flow switch group as explained in the
section 14.5.
2Separate the flow switch plug 1 from the body 4
levering with a screwdriver one of the two hooks.
1
4
Fig. 14.4
3Insert the flow limiter 3 as shown in Fig. 14.3
4Reassemble the group following the above se-
quence in reverse order.
33
Page 36
15Te m p e r a t u r e pr o b e
15.1Function
The Temperature probe has the function of converting
the temperature of the water in the hydraulic circuit
where it is installed into an electrical signal (resistance).
The relation between temperature and electrical resistance is stated in Fig. 15.1.
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
Disconnect the cable from the Temperature probe.
Measure the temperature of the pipe near the Temperature probe and check the electrical resistance according to the graph in Fig. 15.1.
15.3Removal of the c.h.Temperature probe
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
1Removeallthecasepanelsandthesealed
chamber lid.
2Empty the primary circuit of the boiler.
3Remove the electric connector C and unscrew
the c.h. Temperature probe A --- F i g . 1 5 . 3 o r
Fig. 15.4
4Reassemble the c.h.Temperature probe carrying
out the removal operations in reverse order.
On the boiler there are two Temperature probes. One
on the output of the primary condensing heat exchanger (c. h. Temperature probe) A in Fig. 15.2 and
Fig. 15.3; one on the output of the d.h.w. heat exchanger (d.h.w. Temperature probe) B in Fig. 15.2 and
Fig. 15.3.
A
B
A
B
C
D
Fig. 15.3
A
C
Fig. 15.2
34
c.h.
return
c.h.
flow
d.h.w.
inlet
d.h.w.
outlet
Fig. 15.4
Page 37
Temp e rat ure pro b e
15.4Removal of the d.h.w.Temperature probe
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
1Remove the front panel of the case.
2Empty the d.h.w circuit of the boiler.
3Remove the electric connector D and unscrew
the d.h.w. Temperature probe B --- F i g . 1 5 . 3
4Reassemble the d.h.w. Temperature probe carry-
ing out the removal operations in reverse order.
Warning: to lubricate the O-- ring gaskets
exclusively use a silicone base grease
compatible to be in contact with foods and
approved by the local water Authorities.
35
Page 38
16B y --- pa s s v a l v e
16.1Function
The By---pass valve A in Fig. 16. 1 is located between
the c.h. water flow and return and its function is that of
guaranteeing a minimum flow across the primary heat
exchanger if the circulation across the c.h. system is
completely closed.
The By ---pass valve is fitted on the rear side of the diverter group.
2Empty the primary circuit of the boiler.
3Remove the diverter group as described in the
section 8.4 of this manual.
4Unscrew the connector B and remove the by ---
pass valve C (Fig. 16.2) (Fig. 16.3).
B
C
Fig. 16.2
A
Fig. 16.1
16.2Removal
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
1Removeallthecasepanels.
CB
Fig. 16.3
5Reassemble the by --- pass valve as illustrated in
Fig. 16.2 --- Fig. 16.3 reversing the order of removal.
36
Page 39
17Fan and Air box
17.1Function
The function of the Fan A (Fig. 17.1) is to force the mixture of air and gas into the burner.
The function of the Air box B is to mix the gas and the
air in the right proportion.
The flow rate of the air--- gas mixture and consequently
the input power of the boiler is proportionalto the speed
of the fan that is controlled by the electronic control
p.c.b.
3Disconnect the air manifold C (Fig. 17.2) by pul-
ling it.
I
D
F
H
A
B
Fig. 17.1
17.2Removal of the Air box and the Fan
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
1Turn off the gas supply.
2Removeallthecasepanelsandthesealed
chamber lid (see section 2).
K
J
Fan g asket
Fig. 17.3
G
4D isconnect the rubber pipe D (Fig. 17.3).
E
Fig. 17.4
5Unscrew the gas connector E (Fig. 17.4)
6Remove the fixing fork F andremovethegaspipe
G (Fig. 17.3).
7Loosen without removing the screw H.
8RemovethescrewsI and the air box J.Leavethe
air box with the air manifold clamped to the water
pipe.
9D isconnect the fan connector K by pressing the
plastic hook placed on the side of the connector
(Fig. 17.2).
10Unscrew the screws L (Fig. 17.2).
11Remove the fan M.
12Assemble the Fan and the Air box carrying out
the removal operations in reverse sequence.
Fig. 17.2
Before reassemblingensure the fan gasket
L
M
(Fig. 17.3) is correctly mounted.
Warning: After cleaning or replacement as
detailed above, if it deemed necessary to
C
undertake a combustion analysis, refer to
the appropriate chapter Maintenance of the
installation instructions manual.
37
Page 40
18Ignition and detection electrodes,
burner and spark generator
18.1Function
Three electrodes are fitted on the fan --- burner group.
Two of them, fitted on the right side of the fan--- burner
group A, are the ignition electrodes B and are connected to the spark generator C.
On the left side is the detection electrode D and it detects the presence of the flame.
J
K
B
I
D
I
K
A
I
J
E
Fig. 18.2
18.2Removal of the Ignition and detection
electrodes
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
1Removeallthecasepanelsandthesealed
chamber lid (see section 2) .
2D isconnect the ignition electrodes connector F
and the earth wire G from the spark generator C
(Fig. 18. 1) and disconnect the detection electrode connector H.
3Unscrew the screws I andremovetheignition
electrodes B and the detection electrode D
(Fig. 18.1).
4Assemble the Ignition and detection electrodes
carrying out the removal operation in reverse order.
C
H
Fig. 18.1
GF
The burner E is fitted on the rear of the fan ---burner
group A.
38
When reassembling the ignition electrodes be sure
to connect correctly the wires to the spark generator (see Fig. 18.3)
earth wire
ignition electrodes
wire
C
Fig. 18.3
18.3Removal of the burner
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
1Remove the air box and the fan (see section 17.2)
2Remove the Ignition and detection electrodes
(see section 18.2).
Page 41
Ignition and detection electrodes
t
3Unscrew the screws J (Fig. 18.1 )and remove the
cover of the combustion chamber.
4Unscrew the screws K (Fig. 18.1 ) and remove the
A i r --- g a s d u c t li d .
5Remove the burner by sliding it forward.
burner gaske
Before reassembling ensure the burner gasket is
correctly located.
Warning: After cleaning or replacement as
detailed above, if it deemed necessary to
undertake a combustion analysis, refer to
the appropriate chapter Maintenance of the
installation instructions manual.
18.4Removal of the front insulation panel
See warning note at the end of this chapter before
toremovethispart.
1Remove the Ignition and detection electrodes
(see section 18.2).
2Remove the burner (see section 18.3).
3Removethe
4Assemble the new front insulation carrying out
the removal operation in reverse order.
When fitting the new panel ensure that the electrodes holes coincide with the holes of the combustion chamber.
front insulation panel (Fig. 18.6).
locating tab
Fig. 18.4
6Assemble the burner carrying out the removal
operation in reverse order. Ensure the burner is
correctly located by lining up the locating tab
(Fig. 18.4).
burner gasket
A i r --- g a s d u c t g a s k e t
Fig. 18.5
front insulation
Siliconic gasket
Fig. 18.6
The siliconic gasket (Fig. 18.6) must be replaced if
damaged or anyway every 2 years.
The front insulation (Fig. 18.6) must be replaced if
damaged or wet
18.5Removal of the rear insulation
See warning note at the end of this chapter before
toremovethispart.
Attention: Cover the inner of the condensing heat
exchanger to avoid that dirt and debris fall in the
coil.
1Do the operations of section 18.3 from step 1 to
step 3.
2Unscrew the screw L, remove the washer M and
the rear insulation N (Fig. 18.7).
39
Page 42
Ignition and detection electrodes
N
L
M
Fig. 18.7
The rear insulation (Fig. 18.7) must be replaced if
damaged or wet
There is not a significant way to verify the integrity of the
spark generator.
When the fan turns but the burner does not light a possible cause is a faulty spark generator and it is advisable
to replace it to locate the fault.
nCheck the position of the electrode edges
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
1Remove the ignition electrodes (see section 18.2)
2Check for the correct distance between the me-
tallic edges of the ignition electrode (see Fig. 18.9
--- Fig. 18.10).
3,5 mm
earth electrode
18.6Removal of the spark generator
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
1Removeallthecasepanelsandthesealed
chamber lid.
2D isconnect the spark generator connector
coming from the control p.c.b, the electrodes wire
and the earth wire coming from the ignition electrodes (Fig. 18.8).
ignition electrodes
wire
O
earth wire
O
C
spark generator
connector
Fig. 18.8
3Unscrew the screws O and remove the spark
generator
.
4Assemble the spark generator carrying out the re-
moval operation in reverse order.
When reassembling the spark generator be sure to
connect correctly the wires.
18.7Checks
nCheck of the spark generator
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
40
Ignition electrode
Fig. 18.9
nCheck the connection wires.
7mm
Ignition electrode
Fig. 18.10
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
1Removeallthecasepanelsandthesealed
chamber lid.
Page 43
Ignition and detection electrodes
2Check for the integrity of the insulation of wires
which connect the electrodes to the spark generator and to the control/ignition p.c.b.
Warning -- Insulation panels material handling care
Mineral fibres are used in this appliance for the insulation panels of the combustion chamber
Excessive exposure to these materials may cause temporary irritation to eyes, skin and respiratory tract.
Known hazards --- Some people can suffer reddening
and itching of the skin. Fibre entry into the eye will
cause foreign body irritation, which can cause severe
irritation to people wearing contact lenses. Irritation to
respiratory tract.
Precautions --- Dust goggles w ill protect eyes. People
with a history of skin complaints may be particularly
susceptible to irritation. High dust levels are only likely
to arise following harsh abrasion. In general, normal
handling and use will not present high risk, follow good
hygiene practices, wash hands before, touching eyes,
consuming food, drinking or using the toilet.
Firstaid---Medicalattentionmustbesoughtfollowing
eye contact or prolonged reddening of the skin.
41
Page 44
19Safety thermostat
19.1Function
The safety thermostat A in Fig. 19.1 is a device that
senses the temperature of the primary circuit water
which flows in the outlet pipe of t he condensing heat exchanger.
If the temperature control system of the boiler fails and
the temperature of the primary circuit reaches a dangerous temperature, the safety thermostat opens the
electric circuit that supplies the on--- off operators of the
gas valve.
Consequently, the full sequence ignition device attempts to light the burner and, at the end, locks the
boiler and lights the lock--- out signal lamp.
A
nElectrical function
1Removeallthecasepanelsandthelidofthe
sealed chamber.
2D isconnect the safety thermostat and check its
electrical function. Normally (no intervention) the
contact must be closed (electrical resistance zero
8).
19.3Removal
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
1Removeallthecasepanelsandthelidofthe
sealed chamber.
2Disconnect the wiring B (detail in Fig. 19.2).
3Unscrew the screws C which hold the overheat
thermostat on the pipe of the condensing heat exchanger and remove it.
C
Fig. 19.1
19.2Checks
nOverheat temperature value
1Set the temperature control knobs to their max.
position and run the boiler in d.h.w. and c.h.
2Allow the boiler to reach its maximum operating
temperature (monitor the temperature gauge on
the instrument panel). The boiler should maintain
a temperature below that of the safety thermostat
and no overheat intervention should occur.
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
B
Fig. 19.2
4Reassemble the overheat thermostat carrying out
the operations in reverse order.
5Apply an adequate quantity of heat conducting
compound between the pipe and the thermostat.
Warning: After cleaning or replacement as
detailed above, if it deemed necessary to
undertake a combustion analysis, refer to
the appropriate chapter Maintenance of the
installation instructions manual.
42
Page 45
20Flue temperature probe NTC and
Safety thermal fuse
20.1Function
The Flue t emperature probe NTC A in Fig. 20.1 and
Fig. 20.2 senses the temperature of the combustion
products that flow through the condensing heat exchanger.
B
A
NTC and acts as a safety device in extreme case of incorrect operation of the Flue temperature control system.
Reaching the breakdown temperature it opens the circuit and locks out the boiler.
In case of intervention of this safety device the heat ex changer (part shown in Fig. 20.3) may be damaged
and must be replaced.
Fig. 20.1
If the temperature of the combustion products circuit
reaches the limit temperature, the Flue temperature
probe NTC reduces the gas flow rate to the burner. The
temperature of the combustion products should decrease to a safe value temperature.
In the case that the temperature of the combustion
products reaches a potentially dangerous value, it
stops the boiler operation (lock--- out).
This allows the use of plastic materials for the flue outlet
pipes and bends.
The use of kits different from the original isn’t however
allowed, since the flue pipes are integral parts of the
boiler.
A
C
Fig. 20.2
B
ASafetythermalfuse B in Fig. 20.1 --- Fig. 20.2 is also
connected in series with the Flue temperature probe
Fig. 20.3
20.2Removal
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
1Removeallthecasepanelsandthesealed
chamber lid.
2D isconnect the connector C from the Flue tem-
perature probe NTC by pressing the plastic hook
placed on the side of the connector.
3Unscrew and remove the flue temperature probe
A (Fig. 20.2) from the condensing heat exchanger.
4Assemble the Flue temperature probe NTC carry-
ing out the removal operations in reverse sequence.
20.3Checks
nOverheat temperature value
1Set the temperature control knobs to their max.
position and run the boiler in d.h.w. and c.h.
2Allow the boiler to reach its maximum operating
temperature (monitor the temperature gauge on
the instrument panel). The boiler should maintain
a temperature below that of the Flue temperature
probe NTC and no overheat intervention should
occur.
nTemperature --- resistance relationship
1Remove the Flue temperature probe NTC (see
section 20.2).
2Measure the Flue temperature probe NTC electri-
cal resistance at the ambient temperature and
check it according to the graph in Fig. 20.4
Unscrew the plug on the bottom of the trap and remove
dirt eventually deposit.
The condensate trap A in Fig. 21.1 and Fig. 21.2 allows
the discharge of the condensate via the condensate
drain pipe avoiding in the mean time the escape of
combustion products.
A plastic ball closes the trap outlet in case that the trap
is empty.
21.3Removal
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
1Remove the front and left case panels.
2D isconnect the trap from the draining pipe.
3Using pliers, remove the spring B moving it up-
wards and remove the flexible pipe C.
4Unscrew the screw D and remove the trap.
5Unscrew the lock ---nut E and separate the trap
from its bracket.
6Reassemble carrying out the removal operations
in reverse order.
D
C
B
E
A
Fig. 21.1
If the drain pipe is plugged or in any case in which the
condensate isn’t correctly evacuated, the condensate
level in the trap rises till it reaches the detection electrode in the combustion chamber thus causing the
boiler lock---out.
Biasi UK Ltd
Newman Park, Western Way
Wednesbury, WS10 7BJ
Sales Tel No: 0121 506 1340
Sales Fax No: 0121 506 1360
Service Tel No: 0121 506 1350
Service Fax No: 0121 506 1370
www.biasi.co.uk
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.