Bettis VSM02 Quick Start Guide

Page 1
Quick Start Guide
QSG-02-04-55-0016-EN Rev. 0
March 2020
Bettis M2CP Variable Speed Module (VSM02)
Page 2
Page 3
Quick Start Guide
QSG-02-04-55-0016-EN Rev. 0
Section 1: Preface
Section 2: Timer Settings
Section 3: Components
Section 4: Operating Modes and Jumpers
4.1 Features ........................................................................................................ 4
4.2 Water Hammer ............................................................................................. 4
4.3 Open Timer ................................................................................................... 4
Section 5: Software Version Number Display
Table of Contents
March 2020
ITable of Contents
Page 4
Section 1: Preface
March 2020
Section 1: Preface
The VSM02 module is a precision timer that uses microprocessor technology to control the speed of valve travel in selected applications. As such, it provides the ability to control valve speed while opening and closing or selectively in only one direction. Valve operation can be setup to start at one speed and change to a slower speed as required. External equipment operation can be interlocked with the VSM02 so that valve
operation is based on specic process conditions.
VSM02 mounts with 2 slotted screws in the ISM location or on the back of an ISM module with hex standoffs. The module switches a SSR (solid state relay) selectively to apply power to the actuator motor. This extends the life of the electro-mechanical reversing contactor. It also prevents valve plugging during instant direction reversal of the actuator.
The VSM02 has 6 timers, allowing selection of 3 different motor speeds during valve operation. Motor speed can be congured to vary two times in one direction. The module can only be used to slow down the speed of the actuator. Settings on the module pulses the SSR with an ON or OFF duty cycle according to adjustments. Adjustments include BCD dial type switches and a x10 multiplier (DIP switch setting) for setting each timer function.
Quick Start Guide
QSG-02-04-55-0016-EN Rev. 0
The OPEN control determines the speed of the opening valve stroke. This is disabled by setting OPEN “ON” dial to zero.
The CLOSE control determines the speed of the closing valve stroke. This is disabled by setting CLOSE “ON” dial to zero.
Water hammer is normally used with the intermediate limit switch LSA to change speeds. When the contacts are closed by valve travel, the timer is activated. It overrides all other speed controls while activated.
1
Preface
Page 5
Quick Start Guide
QSG-02-04-55-0016-EN Rev. 0
Section 2: Timer Settings
Each dial sets timer in one second increments from 0 to 9. Setting the x10 DIP switch associated with each timer will multiply the time by 10. Thus, when the DIP switch of a timer is ON, the time is set in increments of 10 seconds for each graduation the dial from 0 to 90 seconds, i.e. 10, 20, 30, 40, etc.
Section 2: Timer Settings
March 2020
Timer Settings
2
Page 6
Section 3: Components
March 2020
Section 3: Components
Figure 1 Typical Board
BCD Dial Switch
Quick Start Guide
QSG-02-04-55-0016-EN Rev. 0
LED
x10 DIP Switch
Figure 2 Wiring Diagram
Stop
WATER
HAMMER
VSM-02
Close
CLOSE OPEN
Open
Water Hammer
Intermediate
Contacts
Selector
3
Components
Page 7
Quick Start Guide
QSG-02-04-55-0016-EN Rev. 0
Section 4: Operating Modes and Jumpers
March 2020
Section 4: Operating Modes and Jumpers
4.1 Features
Open Speed Control
Close Speed Control
Water Hammer Control
Run LED displays S/W version number and then ashes 0.5 second ON and
0.5 second OFF for visual indication of time in seconds
Table 1.
Adjustment Range x10 DIP Switch
0 - 9 seconds OFF 0 - 90 seconds ON
NOTE:
Minimum ON or OFF time is 1 second setting. Timers always start with a 1 second OFF time to prevent valve plugging on instant reversal. Zero ON time setting disables the timer.
4.2 Water Hammer
Set LSA to start timer position or use external switch.
OPERATING MODE ADD JUMPER BETWEEN TBM TERMINALS
Close direction only 41 and 9
Open direction only 41 and 10
Both close and open 41 and S
External control only 42 and external switched 115 V AC
LSA and external control 42 and external switched 115 V AC to 41
Disabled Disconnect all jumpers from terminals 41 and 42
4.3 Open Timer
Set LSA or LSB to start or disable water hammer timer position
If water hammer is not used in the closing direction, either LSA or LSB may be used to change opening speed by enabling or disabling water hammer. Connect jumper wire between 10 and the selected LSA or LSB switch terminal. When the switch activating water hammer is closed, the water hammer timer will override opening timer. If water hammer timer “off time” is set to zero, then the actuator will travel at full speed when the switch is closed.
Operating Modes and Jumpers
4
Page 8
Section 5: Software Version Number Display
March 2020
QSG-02-04-55-0016-EN Rev. 0
Quick Start Guide
Section 5: Software Version Number Display
Each time the module is powered on by OPEN or CLOSE command, the run LED displays
software version number rst and then ashes 0.5 second ON and 0.5 second OFF for visual indication of time in seconds. Version number is displayed by 0.7 second ashes in the
following sequence.
At power up the LED is ON for 4 seconds and ashes the number of times equal to the rst (most signicant) digit. After which it is ON for 2 seconds and then ashes the number of times equal to the second (least signicant) digit.
Example: version 1.1 will be ON for 4 seconds, ash one time and then ON for 2 seconds and then ash one time. After a short off time delay the normal 0.5 second ON and
0.5 second OFF sequence will begin.
5
Software Version Number Display
Page 9
Page 10
World Area Conguration Centers (WACC) offer sales support, ser vice, inventory and commissioning to our global customers. Choose the WACC or sales ofce nearest you:
NORTH & SOUTH AMERICA
19200 Northwest Freeway Houston TX 77065 USA T +1 281 477 4100
Av. Hollingsworth 325 Iporanga Sorocaba SP 18087-105 Brazil
MIDDLE EAST & AFRICA
P. O. Box 17033 Jebel Ali Free Zone Dubai T +971 4 811 8100
P. O. Box 10305 Jubail 31961 Saudi Arabia T +966 3 340 8650
T +55 15 3413 8888
24 Angus Crescent
ASIA PACIFIC
Longmeadow Business Estate East
P.O. Box 6908 Greenstone No. 9 Gul Road #01-02 Singapore 629361 T +65 6777 8211
No. 1 Lai Yuan Road
1616 Modderfontein Extension 5
South Africa
T +27 11 451 3700
EUROPE
Wuqing Development Area Tianjin 301700 P. R. China T +86 22 8212 3300
Holland Fasor 6
Székesfehérvár 8000
Hungary
T +36 22 53 09 50
Strada Biffi 165
29017 Fiorenzuola d’Arda (PC)
Italy
T +39 0523 944 411
For complete list of sales and manufacturing sites, please visit
www.emerson.com/actuationtechnologieslocations or contact us at info.actuationtechnologies@emerson.com
www.emerson.com/bettis
VCIOM-15074-EN ©2020 Emerson. All rights reserved.
The Emerson logo is a trademark and service mark of Emerson Electric Co.
TM
is a mark of one of the Emerson family of companies.
Bettis All other marks are property of their respective owners.
The contents of this publication are presented for information purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available on request. We reserve the right to modify or improve the designs or specifications of our products at any time without notice.
Loading...