Section 1: Preface
March 2020
Section 1: Preface
The VSM02 module is a precision timer that uses microprocessor technology to control
the speed of valve travel in selected applications. As such, it provides the ability to
control valve speed while opening and closing or selectively in only one direction.
Valve operation can be setup to start at one speed and change to a slower speed as
required. External equipment operation can be interlocked with the VSM02 so that valve
operation is based on specic process conditions.
VSM02 mounts with 2 slotted screws in the ISM location or on the back of an ISM module
with hex standoffs. The module switches a SSR (solid state relay) selectively to apply power
to the actuator motor. This extends the life of the electro-mechanical reversing contactor.
It also prevents valve plugging during instant direction reversal of the actuator.
The VSM02 has 6 timers, allowing selection of 3 different motor speeds during valve
operation. Motor speed can be congured to vary two times in one direction.
The module can only be used to slow down the speed of the actuator. Settings on the
module pulses the SSR with an ON or OFF duty cycle according to adjustments.
Adjustments include BCD dial type switches and a x10 multiplier (DIP switch setting) for
setting each timer function.
Quick Start Guide
QSG-02-04-55-0016-EN Rev. 0
The OPEN control determines the speed of the opening valve stroke. This is disabled by
setting OPEN “ON” dial to zero.
The CLOSE control determines the speed of the closing valve stroke. This is disabled by
setting CLOSE “ON” dial to zero.
Water hammer is normally used with the intermediate limit switch LSA to change speeds.
When the contacts are closed by valve travel, the timer is activated.
It overrides all other speed controls while activated.
1
Preface
Page 5
Quick Start Guide
QSG-02-04-55-0016-EN Rev. 0
Section 2: Timer Settings
Each dial sets timer in one second increments from 0 to 9. Setting the x10 DIP switch
associated with each timer will multiply the time by 10. Thus, when the DIP switch of a
timer is ON, the time is set in increments of 10 seconds for each graduation the dial from
0 to 90 seconds, i.e. 10, 20, 30, 40, etc.
Section 2: Timer Settings
March 2020
Timer Settings
2
Page 6
Section 3: Components
March 2020
Section 3: Components
Figure 1 Typical Board
BCD Dial Switch
Quick Start Guide
QSG-02-04-55-0016-EN Rev. 0
LED
x10 DIP Switch
Figure 2 Wiring Diagram
Stop
WATER
HAMMER
VSM-02
Close
CLOSE OPEN
Open
Water Hammer
Intermediate
Contacts
Selector
3
Components
Page 7
Quick Start Guide
QSG-02-04-55-0016-EN Rev. 0
Section 4: Operating Modes and Jumpers
March 2020
Section 4: Operating Modes and Jumpers
4.1 Features
• Open Speed Control
• Close Speed Control
• Water Hammer Control
• Run LED displays S/W version number and then ashes 0.5 second ON and
0.5 second OFF for visual indication of time in seconds
Table 1.
Adjustment Rangex10 DIP Switch
0 - 9 secondsOFF
0 - 90 secondsON
NOTE:
Minimum ON or OFF time is 1 second setting. Timers always start with a 1 second OFF time
to prevent valve plugging on instant reversal. Zero ON time setting disables the timer.
4.2 Water Hammer
Set LSA to start timer position or use external switch.
OPERATING MODE ADD JUMPER BETWEEN TBM TERMINALS
Close direction only 41 and 9
Open direction only 41 and 10
Both close and open 41 and S
External control only 42 and external switched 115 V AC
LSA and external control 42 and external switched 115 V AC to 41
Disabled Disconnect all jumpers from terminals 41 and 42
4.3Open Timer
Set LSA or LSB to start or disable water hammer timer position
If water hammer is not used in the closing direction, either LSA or LSB may be used to
change opening speed by enabling or disabling water hammer. Connect jumper wire
between 10 and the selected LSA or LSB switch terminal. When the switch activating
water hammer is closed, the water hammer timer will override opening timer. If water
hammer timer “off time” is set to zero, then the actuator will travel at full speed when the
switch is closed.
Operating Modes and Jumpers
4
Page 8
Section 5: Software Version Number Display
March 2020
QSG-02-04-55-0016-EN Rev. 0
Quick Start Guide
Section 5: Software Version Number Display
Each time the module is powered on by OPEN or CLOSE command, the run LED displays
software version number rst and then ashes 0.5 second ON and 0.5 second OFF for visual
indication of time in seconds. Version number is displayed by 0.7 second ashes in the
following sequence.
At power up the LED is ON for 4 seconds and ashes the number of times equal to the rst
(most signicant) digit. After which it is ON for 2 seconds and then ashes the number of
times equal to the second (least signicant) digit.
Example: version 1.1 will be ON for 4 seconds, ash one time and then ON for 2 seconds
and then ash one time. After a short off time delay the normal 0.5 second ON and
0.5 second OFF sequence will begin.
5
Software Version Number Display
Page 9
Page 10
World Area Conguration Centers (WACC) offer sales support, ser vice,
inventory and commissioning to our global customers.
Choose the WACC or sales ofce nearest you:
NORTH & SOUTH AMERICA
19200 Northwest Freeway
Houston TX 77065
USA
T +1 281 477 4100
Av. Hollingsworth
325 Iporanga Sorocaba
SP 18087-105
Brazil
MIDDLE EAST & AFRICA
P. O. Box 17033
Jebel Ali Free Zone
Dubai
T +971 4 811 8100
P. O. Box 10305
Jubail 31961
Saudi Arabia
T +966 3 340 8650
T +55 15 3413 8888
24 Angus Crescent
ASIA PACIFIC
Longmeadow Business Estate East
P.O. Box 6908 Greenstone
No. 9 Gul Road
#01-02 Singapore 629361
T +65 6777 8211
No. 1 Lai Yuan Road
1616 Modderfontein Extension 5
South Africa
T +27 11 451 3700
EUROPE
Wuqing Development Area
Tianjin 301700
P. R. China
T +86 22 8212 3300
Holland Fasor 6
Székesfehérvár 8000
Hungary
T +36 22 53 09 50
Strada Biffi 165
29017 Fiorenzuola d’Arda (PC)
Italy
T +39 0523 944 411
For complete list of sales and manufacturing sites, please visit
www.emerson.com/actuationtechnologieslocationsor contact us at
info.actuationtechnologies@emerson.com
The Emerson logo is a trademark and service mark of Emerson Electric Co.
TM
is a mark of one of the Emerson family of companies.
Bettis
All other marks are property of their respective owners.
The contents of this publication are presented for information purposes
only, and while every effort has been made to ensure their accuracy, they
are not to be construed as warranties or guarantees, express or implied,
regarding the products or services described herein or their use or
applicability. All sales are governed by our terms and conditions, which are
available on request. We reserve the right to modify or improve the designs
or specifications of our products at any time without notice.