Bettis QC40 ASi Module Installation Guide

Installation guide
DOC.IG.QC40.1 Rev. 3
FieldQ Control Module
QC40 AS-Interface
FieldQ
May 2018
FieldQ
FieldQ
May 2018
Installation guide
DOC.IG.QC40.1 Rev. 3
QC40 - AS-Interface Weather proof IP66/ NEMA4X
QC40 - AS-Interface Non-Incendive or Non Sparking
Note:
These variations can be equipped with one or two pilot valves:
* One pilot valve is default and suitable for normal
operation of double acting or spring return actuators.
* Two pilot valves are required for Fail in Last
Position function on double acting actuators. The enclosures have a IP66 or NEMA 4X, ingress protected rating.
2 Before starting
* Actuator must be isolated both pneumatically and electrically before any (dis)assembly
is begun. * Hazards related to the control of external processes under measurement, are beyond the scope of of the content described in
this document. * Installation, adjustment, putting into service, use, assembly, disassembly and maintenance of the control module must be done by
qualified personnel. * Do not install, operate, or maintain a Q series control module without being fully trained and qualified in valve, actuator, and accessory installation, operation, and maintenance. * To avoid personal injury or property damage, it is important to carefully read, understand, and follow all of the contents of this manual, including all safety cautions and warnings. * Be sure that the actuator is correctly mounted before connecting air supply and electrical wiring (see Installation & Operation Manual FieldQ Valve Actuator, DOC.IOM.Q.E) * Check the module label for the right execution (see figure 2.2) * Check the type of actuator: single or double acting (see figure 2.2). * For mechanical installation of the module see installation instruction leaflet DOC.QC4.MTI.1, as shipped with the module. * If you have any questions regarding these instructions, contact your Emerson sales office before proceeding as shipped with the module.
1
2
Fig. 2.1 Check proper mounting before connecting air
supply and electrical wiring.
2
Control Module Label =
QC40..WP.. = ASI
OK
QC40..x4.. = ASI Non Incendive /
Non Sparking
OK
Actuator Label =
QS xxxx = Single acting (Spring Return)
QD xxxx = Double acting
Note: x is variable based on the certification type.
Fig. 2.2 Identification
Installation guide
DOC.IG.QC40.1 Rev. 3
FieldQ
May 2018
2.1 Mechanical alignment and mounting of the control module
The control module is equipped with an alignment­edge on top of the module. This allows easy alignment and mounting of the control module on to the actuator housing.
Procedure: (see figure 2.3)
1. First take care that both mating faces from the
actuator and control module are clean and free of dirt.
2. Check if the module has the required function
3. Remove the transparent film from the
control module.
4. Ensure seals are placed correctly.
5. Level the screws with the surface.
6. Place the alignment-edge (1) of the control
module at the top of the pneumatic interface.
7. Flip the module down taking care that the IPT
Probe (2) on the actuator fits in the mating hole on the control module and loosely place the screws.
8. Tighten screws according force in sequence.
Tightening moments
The Control Module should be fastened by using an Allen key and applying the following tightening moments:
- Allen Key: No 5
- Torque: 6.1 to 6.6 Nm (54 - 58.4 In.lbs)
Alignment-edge
(1)
Alignment-edge
IPT probe
(2)
Fig. 2.3 Alignment and mounting of control
module to actuator
Terminal compartment with:
- AS-I cartridge and
- switch cartridge
Lockable
Module cover
Fig 2.4 Control module overview
Control Module
Type Label
Pneumatic connections
Option: Local Manual Control
Option: Additional Local Manual Control
for “Fail in Last Position”
Option: 1 or 2 speed control throttles
3
FieldQ
May 2018
3 Pneumatic connections
Installation guide
DOC.IG.QC40.1 Rev. 3
IMPORTANT
1 The actuator/valve combination can move
after connecting the air supply.
2 Ensure that the QC40 control modules are
mounted properly to the actuator to achieve good functioning and the required ingress protection, before connecting the air supply.
3 Check that the maximum supply pressure
P
= 8bar/116Psi
max
4 Be sure that the minimum required supply
pressure for the application is available at the actuator.
5 Take appropriate measures to prevent
condensation or moisture to entering the actuator or the control module. Condensation or moisture can damage these components and can result in failures.
6 The exhaust ports Ra and Rb on the module
(see figure 3.1) are shipped from the factory with transport protection.
* If ingress protection IP66 or NEMA 4X is
required, appropriate connections must be used in exhaust ports Ra & Rb.
3.1 Operating media :
* Air or inert gasses. * Air filtered at 50μm. * Dew point 10 K below operating temperature. * For subzero applications take
appropriate measures.
3.2 Single acting (spring return) or Double acting actuator :
1 Remove the transport sticker from the
air supply (Ps).
2 Connect air supply to port (Ps).
Single acting
Control
Module cover
Double acting
Fig. 3.1 Pneumatic connections
OK
Fig 3.2 Install drip loops
Ra
Ps
1/4” BSP or 1/4” NPT
Ra
Rb
Ps
1/4” BSP or 1/4” NPT
50µm
4
Installation guide
DOC.IG.QC40.1 Rev. 3
4 Electric Connections
FieldQ
May 2018
Table 4.1 Electrical data QC40 - ASI
Protocol AS-Interface Spec3.0 Maximum Voltage 31.6V
Minimum Current (pilot valves off)
Nominal Current (one pilot valve activated)
Maximum Current Consumption (one pilot valve application)
Maximum Current Consumption (two pilot valves application)
Protection Short circuit detection
Note: The current consumption of feedback switches is included. Check the product data sheet for one or two pilot valves application.
Environmental conditions :
Temperature *
Humidity
Altitude
Use In- and outdoor.
34mA at 26.5V
85mA at 26.5V
125mA at 26.5V
140mA at 26.5V
Ambient: -25°C to +60°C (-4°F to +140°F) Maximum Surface: 80°C (176°F)
0 to 85% at 25°C(+77°F) derate to 50% above 40°C (104°F) (non-condensing).
Operating full power available up to 2000 meter (6000 feet).
Table 4.2 Wiring dimensions
Wire type: Dimensions:
Cable range 0.33 - 2.5mm2 or 22 - 12AWG
Please check www.as-interface.net for various application guides like installation and wiring guidelines.
Table 4.3 Tools
Screw: Tool:
Terminals Screw driver: 0.6 x 3.5
Earth screws
Screw driver for cross slotted Phillips screws nr. 2.
WARNING:
* If the Control Module is used in a manner not
specified by the manufacturer, the protection provided by the equipment may be impaired.
* If required, mount earth wire (1) between top
(2) and bottom (3) ring of earth wire connection (see figure 4.1).
4.1 Electrical data for hazardous area executions
Please check chapter 10 for electrical data and instructions in case an “Non Incendive/Non Sparking” Control Module is used in hazardous locations (Zone 2 or Class I Div.2).
* In case the Control module is used in Hazardous
locations, check the Control Drawings as per chapter 10 for the applicable temperature range.
* The current restricted power supply meets NEC
Class 2, as described by the National Electrical Code® (ANSI/NFPA 70 (NEC®))
Fig. 4.1 Earth wire connections
5
FieldQ
May 2018
Installation guide
DOC.IG.QC40.1 Rev. 3
4.2 Procedure
1 Remove Control Module cover (see figure 4.2). 2 Guide the cable(s) through the electrical
entry(ies).
- Use and mount cable glands as required by national or local legislation.
- When IP66/NEMA4X ingress protection is required, the electrical entries must be fitted with glands rated IP66/NEMA4X or higher.
3 Make the electrical connections as shown in
figure 4.3.
- For hazardous area connections, see the instructions in chapter 10
- Quick connectors, as shown below, are allowed to be used only for non-explosion safety product application
4 Mount the function module cover to the housing
(see figure 4.2) or continue with chapter 5. Take care that the cover seal is in place to comply to dust and water tightness according to IP66 / NEMA4X.
Terminal compartment
Lockable Module cover
Electrical entries:
3/4”NPT
or M20
1/2”NPT
or M20
Control Module
Type Label
LED’s for Fault, Power, Open and Close position
FAULT
POWER
Wiring Terminals
Fig. 4.2 Terminal connections behind cover.
AS-I terminal wiring connections:
QC40 AS-I control module
Field wiring Actuator wiring
AS-I
Power
supply
Note: Terminal 2 can be used for shield.
+
1
2
-
3
Quick connector pinouts:
(male chassis part)
Brown
1
3
4
3
2
1
4
2
M127/8" UNC
1
3
Blue
Quick connector option
Connect only the brown and blue wires. Where applicable, cut away unused wires.
Fig. 4.3 Terminal connections and quick
connector pinouts
1 2
3
Terminals
6
Installation guide
DOC.IG.QC40.1 Rev. 3
5 Commissioning
FieldQ
May 2018
In order to commission the QC40 ASI Control Module, the following actions must be considered or done:
1 Re-adjustment of the limit switch points if the
factory setting do not meet the application requirements
2 Addressing of the QC40 ASI Control Module
5.1 Re-adjustment of the limit switch points
5.1.1 Factory switch point settings
Mechanical stroke: 90°±0.5° (Actuator setting)
Switch points: ± 15° before each end of
Adjustable range: -20° to +3° at each end.
Switch points
stroke (open and closed position, see fig 5.1).
20°
Closed
90°
20°
Open
Fig. 5.1 Adjustable range
If required the mechanical stroke and the limit switch setting can be re-adjusted.
- For mechanical stroke adjustment of the actuator, please see document DOC.IOM.Q.E, available from www.emerson.com/fieldq.
- For re-adjusting the limit switches, see procedure below.
5.1.2 Before re-adjusting the limit switch points
IMPORTANT
* Before mounting the actuator on the valve, be
sure that both the actuator and the valve have the same “open” or “closed” position.
* Set the Mechanical stroke before setting the
limit switches.
5.1.3 Pneumatic and electrical connections
Make pneumatic and electrical connections before adjusting the limit switch setting. See chapter 3 and 4.
5.1.4 Switch point setting and valve rotation direction.
The QC40 ASI Control Module is equipped with non-intrusive switch point adjustment. The adjustment screws are accessible behind a shield in the front of the module (see fig 5.2).
This means that the switch point adjustment can be done without opening the module.
Normally valves are “Closed” after a clock wise rotation.
- In this case the top adjustment screw (see
fig. 5.2), sets the switch point of the “Closed” position and bottom adjustment screw sets the switch point of the “Open” position.
- For a valve that is “Open” after a clock wise
rotation, the position feedback will be reversed.
The table below indicates which re-adjustment screw is related to the “Open” or “Closed” switch point setting.
Table 5.1 Re-adjustment screws
Re-adjustment screw :
Bottom Open position Close position Top Close position Open position
Valve movement
“Close” after
a clock wise
rotation
“Open” af ter
a clock wise
rotation
7
FieldQ
May 2018
Installation guide
DOC.IG.QC40.1 Rev. 3
5.1.5 Working principles Switch Operating Mechanism (see fig 5.2)
The Switch Operating Mechanism is intend to operate the position feedback switches and allows adjustment of the switch points in the open and closed end positions. Factory setting is that the switches are activated 15° before the end of the open and closed stroke.
Switch Operation
The rotation of the actuators pinion operates the IPT device (1) which results in a linear movement. The linear movement of the IPT device operates lever (3). The lever amplifies the linear movement of the IPT device and operates the switch operating rod (5). Dowel pin (6) in the rod operated the levers of the open and closed switch elements (8 & 9).
8
6
7
5
The lever is of the “floating” type. When the IPT device operates the lever, it moves completely upwards until it meets the upper pivot block (4). At this point the lever will tip over and pull down the switch operating rod (5) and operates the bottom switch (7). When the IPT device moves back the springs cause the lever to move completely downwards until it meets the lower pivot block (2). At this point the lever will tip over and push up the switch operating rod (5) and operates the top switch (8).
Switch point adjustment
The position of the lower pivot block (2) can be changed by adjustment screw (10) and the position of the upper pivot block (4) can be changed by adjustment screw (9).
By adjusting the position of these pivot blocks the switch points will be changed.
The adjustment screws (9 & 10) can be found behind the shield (12) in front of the module. To access the adjustment screws loosen the screw (11) and rotate the shield (12) as shown.
H
E
W
N
N
E
E
N
N
I
P
N
R
G
A
E
O
!
W
R
-
-
T
G
O
I
10
9
15
N
O
D
Z
E
D
4
3
10
9
2
1
11
12
Fig. 5.2 Working principles Switch Operating Mechanism
8
Installation guide
DOC.IG.QC40.1 Rev. 3
FieldQ
May 2018
5.1.6 Re-adjustment of switch points
IMPORTANT
The procedure below assumes:
- That the actuator and control modules are
according the factory settings.
- If th e switch setting is somehow lost or forgotten,
then consult paragraph 6.3 to set the switch point setting back to factory setting.
- That the actuator / valve assembly is closed
after a clock wise rotation (see chapter 5.1.4).
Below procedure assures that the position feedback complies more accurately with the valve position and will set the switch point at approximately 4° before the end of the stroke.
To set and detect the Open or Closed switch points, the QC40 AS-I module has two LED’s that light up if the Open or Closed position limit switch is activated.
Procedure (see fig 5.3):
1. Loosen the screw (1) of the shield (2) and turn
the shield down.
Closed Position:
2. Send an “Close” command to the ASI module,
wait and make sure the valve has moved to closed position.
3. Turn top screw (3) counter clock wise (do not
force the adjustment screw) until the switch trips and the corresponding LED (5) goes out.
4. Turn top screw (3) clock wise (do not force the
adjustment screw) until the switch trips and the corresponding LED (5) goes on. This position represents the actual, mechanical “closed” position of the valve.
5. Turn the screw minimal a 1/2 turn clock wise.
The “closed” position switch point is now set.
Open Position:
5. Send an “Open” command to the ASI module,
wait and make sure the valve has moved to open position.
6. Turn bottom screw (4) clock wise (do not force
the adjustment screw) until the switch trips and the corresponding LED (6) goes out.
7. Turn bottom screw (4) counter clock wise
(do not force the adjustment screw) until the switch trips and the corresponding LED (6) goes on. This position represents the actual “open” position of the valve.
8. Turn the screw minimal a 1/2 turn counter clock wise. The “open” position switch point is now set.
9. Turn the shield (2) back over the adjustment screws and fasten it with the screw (1).
Important:
During switch point adjustment, do not force the adjustment screws when you feel an obstruction. Forcing the adjustment screws can damage the cross head of the adjustment screw.
Table 5.2 Tool table
Shield screw Cross slotted Phillips nr. PH2
Adjustment screws
5
6
0.6 x 3.5 or
Cross slotted Phillips nr. PH2
FAULT
POWER
3
4
1
2
“Closed”
Switch point adjustment
FAULT
POWER
6
Note:
360° rotation of adjustment screw is ±8° adjustment of switch point.
“Open”
Switch point adjustment
FAULT
POWER
5
Fig. 5.3 Re-adjustment screws for “Open” and
“Closed” position feedback
9
FieldQ
May 2018
Installation guide
DOC.IG.QC40.1 Rev. 3
5.2 Addressing
The QC40 ASI module supports the ASI-3 profile. When a module ships from the factory, it has the slave address “0”.
The slave address can be changed using a master device. Please check the applicable sections of the documentation supplied with these devices.
Table 5.2.1 Programming notes:
Factory address 00 EID1 7
IO-Code 6 EID2 E ID-Code A Parameter 00
Q-Series data bits Functions Typ e DI’s DO’s
D0 Bi-directional
D1 Bi-directional
Feedback “Closed” Feedback “Open”
Solenoid 2 Control Solenoid 1 Control
D2 Bi-directional Not used D3 Bi-directional Not used
5.2.2 Diagnostics
- The ASI communications watchdog is activated.
- The control electronics in the module are monitored for short circuit.
- Diagnostics information is communicated via ASI slave status LEDs and Master (see table 3)
Red
Green
FAULT
POWER
FAULT
POWER
Fig. 5.4 ASI slave status LEDs
Table 5.2.2 ASI slave status LEDs (see figure 5.4)
Flags in the master Possible reason Suggested action
Config. Error
Periphery Fault
Symptom
Normal operation
Indication at the slave LEDs
Green Red
On Off reset reset Everything OK -/-
On On set reset Master in STOP Mode
No data exchanges
“Slave not in LPS Slave with wrong IO/ID Reset at Slave active
Slave address = 0” Serious peripheral error with reset
On Blinking set undefined
Short circuit or line
break
10
Check master
configuration
Check slave
configuration
Contact Emerson
Actuation Technologies
Installation guide
DOC.IG.QC40.1 Rev. 3
FieldQ
May 2018
5.3 Check operation
5.3.1 Default (single) pilot valve operation
1. For function test, the unit must be connected to an ASI master device or an ASI gateway.
2. Connect pressure according chapter 3 and the ASI bus signal according chapter 4.
3. For sending the “Open” or “Closed” command, check the applicable sections of the documentation supplied with the ASI master device or the ASI gateway.
4. Send an “Open” command to the Solenoid 1 DO (Data bit D1) of the ASI module.
5. Actuator moves to “Open” position.
6. Send an “Close” command to the Solenoid 1 DO (Data bit D1) of the ASI module.
7. Actuator moves to “Closed” position.
8. Mount the Control Module cover to the housing (see figure 3.1).
5.3.2 Dual pilot valve (Fail in Last Position) operatation
Important:
The QC40 ASI Control module with Dual Pilot valves has only the Fail-in-Last-Position function when the module is mouted to a double acting actuator.
1. For function test, the unit must be connected to
an ASI master device or an ASI gateway.
2. Connect pressure according chapter 3 and the
ASI bus signal according chapter 4.
3. For sending the “Open” or “Closed” command,
check the applicable sections of the documentation supplied with the ASI master device or the ASI gateway.
4. Send an “Open” command to the Solenoid 1
DO (Data bit D1) of the ASI module while “Close” command to Solenoid 2 DO (Data bit D0).
5. Actuator moves to “Open” position.
6. Remove the ASI wiring from the module
terminals.
7. The double acting actuator should not rotate.
8. Re-connect the ASI bus signal according
chapter 4.
9. Send an “Open” command to the Solenoid 2
DO (Data bit D0) of the ASI module while “Close” command to Solenoid 1DO (Data bit D1).
10. Actuator moves to “Closed” position.
11. Remove the ASI wiring from the
module terminals.
12. The double acting actuator should not rotate.
13. Mount the Control Module cover to the housing
(see figure 3.1).
11
FieldQ
May 2018
6 Trouble shooting
Installation guide
DOC.IG.QC40.1 Rev. 3
6.1 The “Open” and “Closed” position feedback signals are reversed from the actual valve positions.
1 Check if the actuator is correctly mounted to
the valve. Before mounting the actuator on the valve, the actuator and the valve should have the same “open” or ‘closed” position (see Installation &
Operation Manual FieldQ Valve Actuator DOC.IOM.Q.E).
2 Some valves may be operated in such a way that
they are:
- “Open” after a clock wise rotation and
- “Closed” after a clock wise rotation.
3 Please see § 5.1 for setting the “Open” and
“Closed” position feedback signals
6.2 The actuator does not give (good) position feedback signals.
1 Check if the actuator is correctly mounted to
the valve.
2 Re-adjust the limit switch setting as per
chapter § 5.1
6.3 Factory setting of the switch points.
IMPORTANT
The procedure below assumes:
- That the actuator / valve assembly is closed
after a clock wise rotation (see also § 5.1).
- The control module is pneumatically and
electrically connected according chapter 3 and 4.
This procedure sets the switch point settings of the switches, back to the factory settings (±15° before each end of stroke), assuming a mechanical stroke of 90°±0.5° of the actuator.
To set and detect the Open or Closed switch points, the QC40 AS-I module has two LED’s that light up if the Open or Closed position limit switch is activated.
Procedure (see fig 5.3):
1. Loosen the screw (1) of the shield (2) and turn the shield down.
Closed Position:
2. Send an “Close” command to the ASI module.
3. Turn top screw (3) counter clock wise maximum 20 turns, (do not force the adjustment screw) until the switch trips and the corresponding LED (5) goes out.
4. Turn top screw (3) clock wise 1 3/4 turn (do not force the adjustment screw). The “closed” position switch point is now set to factory setting.
Open Position:
5. Send an “Open” command to the ASI module.
6. Turn bottom screw (4) clock wise maximum 20 turns, (do not force the adjustment screw) until the switch trips and the corresponding LED (6) goes out.
7. Turn bottom screw (4) counter clock wise 1 3/4 turn (do not force the adjustment screw) The “open” position switch point is now set to factory setting.
8. Turn the shield (2) back over the adjustment screws and fasten it with the screw (1).
Important: Do not force the adjustment screws
During switch point adjustment, do not force the adjustment screws when you feel an obstruction. Forcing the adjustment screws can damage the cross head of the adjustment screw.
12
Installation guide
DOC.IG.QC40.1 Rev. 3
7 Maintenance 8 Optional Controls
FieldQ
May 2018
The FieldQ control modules are designed to operate without maintenance. For any further maintenance to the actuator see Installation & Operation Manual FieldQ Valve Actuator, DOC.IOM.Q.E or contact your local FieldQ representative.
Installation, adjustment, putting into service, use, assembly, disassembly, maintenance and repair of the control module must be done by qualified personnel.
For any further maintenance to the control module see Maintenance Manual, DOC.MM.QC40.E or contact your local FieldQ representative.
Installation, adjustment, putting into service, use, assembly, disassembly, maintenance and repair of the control module must be done by the qualified personnel.
WARNING
!
• Substitutionofcomponentsmayimpair suitability of the equipment
Location for 2nd Manual Control
Lock
45°
Unlock
On
Off
Default location of Manual Control
8.1 Manual Control options
(see figure 8.1)
For commissioning, emergency or maintenance purposes, the FieldQ can be supplied with one or two Manual Control options. These can operate the spool valve(s) inside the module and as such operate the actuator, when there is air pressure available, but no control signal or power supply.
8.1.1 Mounting Manual Control
1 To add a Manual Control, remove the plug(s) in
front of the module and turn in the Manual Control.
- For normal operation the module should be fitted with one Manual Control.
- For Double Acting with a Fail-in-Last-Position function, two Manual Control can be fitted.
8.1.2 Manual Control operation
1 The Manual Control has a
“Push & Lock” function:
- To operate the Manual Control, use a screw driver, push to activate and release to de-activate the pilot valves.
- If required turn it 45°, to lock it in position and keep the actuator in its operated state.
2 In case of a Fail in Last Position configuration
with two manual controls:
- The manual control on the right side (default location) will pressurize the central air chamber and cause the actuator to rotate counter clock wise. For reverse acting FieldQ actuators (Assembly code CC) the actuator will rotate clock wise.
- The manual control on the left side (Location for 2nd Manual Control) will pressurize the end cap air chambers and cause the actuator to rotate clock wise. For reverse acting FieldQ actuators (Assembly code CC) the actuator will rotate counter clock wise.
- In order to operate one of the manual control, be sure the opposite manual control is de-activated and unlocked.
Fig. 8.1 Local Manual Control options
13
FieldQ
May 2018
Installation guide
DOC.IG.QC40.1 Rev. 3
9 Related Information
8.2 Speed control option
(see figure 8.2)
The FieldQ can be supplied with a Speed Control option. One throttle is required for Spring Return actuators and up to two for Double Acting actuators.
The speed control throttle controls the air flow in and out of an air chamber and as such limits the speed of the “Opening” and “Closing” stroke simultaneously.
8.2.1 Mounting Speed Control throttle(s):
1 Remove the plug(s) at the side of the module
and turn in the throttle (1). 2 Spring Return actuators: Use the top entry only. 3 Double acting actuators: Use both bottom and
top entries.
- For standard actuators, the top entry will throttle the closing stroke.
- For standard actuators, the bottom entry will throttle the opening stroke.
- For reverse acting actuators, the opposite strokes will be throttled.
8.2.2 Adjusting Speed Control throttle(s):
1 Remove the nut cap (2). 2 Clockwise rotation of the adjustment screw
reduces the speed.
3 Counter clockwise rotation of the adjustment
screw increases the speed.
4 Replace the nut cap.
Other documents containing information related to the FieldQ Module include:
- 1.604.13: QC40 AS-I Control Module data sheets
- DOC.IOM.Q.E: Installation Operation & Maintenance Manual.
These documents are available, in multiple languages, for download go to www.emerson.com/fieldq
9.1 Applied IECEx standards
The following standards are applied:
- For FieldQ Control Module QC40...P4... ,
IEC 60079-0 Ed. 6.0 : 2011 IEC 60079-15 Ed. 4.0 : 2010 IEC 60079-31 Ed. 2.0 : 2013
9.2 RoHS Directive
This product is only intended for use in large scale fixed installation excluded from the scope of Directive 2011/65/EU on the restriction of the use of certain hazardous substances in electrical and electronic equipment (RoHS 2).
2
Fig. 8.2 Speed control operation
14
Spring Return:
Top entry only.
Double Acting: Bottom and/or top entries.
1
Installation guide
DOC.IG.QC40.1 Rev. 3
10 EU Declaration of Conformity
FieldQ
May 2018
Legal representative entity for the
European Union:
Emerson Process Management, Valve Automation
Asveldweg 11, 7556 BR Hengelo Netherlands
ROC nr 8460 Rev. 0
FieldQ
EU DECLARATION OF CONFORMITY
Issued in accordance with the
EMC Directive 2014/30/EU, Appendix 1
ATEX Directive 2014/34/EU
We hereby declare, that the products specied below meet the basic health and safety requirements of the
above mentioned European Directives.
Product description: QC40 AS-I Control module
Serial number: Each Control module has an identiable serial number Year of Construction: Each Control module has an identiable Year of Construction Manufacturer: Emerson Machinery Equipment (Shenzhen) Co. Ltd.
Bao Heng Technology Industry Park Phase 2, North Hong Lang 2nd Road District 68, Bao’an District,
518101 Shenzhen, China
EMC Directive 2014/30/EU
Typ es: QC40...
Applicable standards: IEC61326-1 : 2012 NAMUR Recommendations : NE21: 2004
ATEX DIRECTIVE
Typ es: QC40...P4...
ATEX Certicate No.: DEKRA 16ATEX0098 X
Marking:
Ta = -25°C ... +60°C
Applicable standards: EN 60079-0 : 2012 + A11:2013 EN 60079-15:2010 EN 60079-31:2014 Notied body: DEKRA Certication B.V., Notied body no : 0344
Meander 1051, 6825 MJ Arnhem, The Netherlands
II 3 G Ex nA IIC T4 Gc II 2 D Ex tb IIIC T80°C Db
Signed:
____________________________
Name:
S. Ooi
Position:
Vice President, Global Marketing & Pneumatic/Hydraulic SBU Emerson, Actuation Technologies
Date:
2016-11-25
Place:EN
Houston TX, U.S.A.
15
FieldQ
May 2018
Installation guide
DOC.IG.QC40.1 Rev. 3
11 QC40 ASI Smart Modules Non Incendive / Non sparking
11.1 Product marking
IECEx Hazardous or Classified Location
Certificate No.: DEK 16.0061 X Non-Sparking Ex nA IIC T4 Gc Ex tb IIIC T80°C Db
ATEX Hazardous or Classified Location
Certificate No.: DEKRA 16ATEX0100 X Non-Sparking
II 3 G Ex nA IIC T4 Gc II 2 D Ex tb IIIC T80°C Db
FM Hazardous or Classified Location
Non Incendive
- Class I, II, III, Division 2, Groups ABCDEFG, T4
- Class 1, Zone 2, Group IIC T4
CSA Hazardous or Classified Location
Certificate No.: CSA 17CA70125362X Class I, Division 2, Groups A, B, C and D, T4; Class II, Division 1, Group E, F and G, T80°C; Class III, Division 1, T80°C Ex nA nC IIC T4 Gc Ex tb IIIC T80°C Db
Ambient temperature:
T4 @ Ta = -25°C...+60°C IP66/Nema 4X
Terminals
Lockable cover
Do not open when energized
Fig 11.1 Product marking
Type plate
11.2 ATEX / IECEx Intended use
• TheControlModuleQC40..P4..ofthe FieldQ pneumatic actuator is a Group II category 3G (ATEX) equipment with protection level Gc (IECEx).
• TheFieldQpneumaticactuatorsisaGroupII
category 2 equipment.
• Bothareintendedforuseinareasinwhich
explosive atmospheres caused by mixtures of air and gases, vapors, mists or by air/dusts are likely to occur.
• Thereforetheassemblymaybeusedin hazardous area classified Zones 2 (Gasses) and/or 21, 22 (Dust).
11.3 Safety instructions
WARNING
!
• Personalinjuryorpropertydamagecaused
by fire or explosion may occur if the module is opened in any area which contains a potentially explosive atmosphere or has been classified as hazardous.
• Donotopenwhenmoduleisenergized.
• Preventanykindignitionduringinstallation,
adjustment, putting into service and use.
• Assembly,disassemblyandmaintenance
must be done in safe area’s without a potential explosion hazard.
• Installation,adjustment,puttingintoservice,
use, assembly, disassembly and maintenance or repair, shall be carried out in accordance with the applicable code of practice by suitably-trained personnel.
• Provisionsmustbemadetopreventthe
rated supply voltage being exceeded by more than 40%.
• Potentialelectrostaticcharginghazard,clean
only with a damp cloth - danger of propagating discharge.
• Theapparatusshallbeinstalledinsuchaway
that the risk from electrostatic discharges and propagating brush discharges caused by rapid flow of dust is avoided.
• Precautionshallbetakentoavoiddangerof
ignition due to electrostatic charges on the marking plate of the enclosure.
16
Installation guide
DOC.IG.QC40.1 Rev. 3
FieldQ
May 2018
• Substitutionofelectronicscartridge,switch
cartridge, pilot valve cartridge, pneumatic cartridge, enclosure and seals must be with parts from Emerson else the suitability for Division 2 will be impaired.
11.4 CSA safety instructions
• The equipment may be used in zones 2 with
ammable gases and vapours with apparatus groups IIA, IIB & IIC and with temperature classes T1, T2, T3, T4.
• The equipment may be used in zones 21 &
22 with ammable dusts, bres and yings in groups IIIA, IIB and IIC, with a layer auto­ignition temperature of not less than 75 K above the maximum surface temperature marked in the dust coding.
• There are no special checking or maintenance
conditions other than a periodic check.
• With regard to explosion safety, it is not
necessary to check for correct operation.
• If the equipment is likely to come into contact
with aggressive substances, e.g. acidic liquids or gases that may attack metals or solvents that may affect polymeric materials, then it is the responsibility of the user to take suitable precautions that prevent it from being adversely affected thus ensuring that the type of protection is not compromised.
11.5 Wiring instructions QC40 -
Non Incendive / Non Sparking
Protocol AS-Interface Spec3.0 Maximum Voltage 31.6V
Minimum Current (pilot valves off)
Nominal Current (one pilot valve activated)
Maximum Current Consumption (one pilot valve application)
Maximum Current Consumption (two pilot valves application)
Protection Short circuit detection
* The current restricted power supply meets NEC
Class 2, as described by the National Electrical Code® (ANSI/NFPA 70 (NEC®))
Terminal connections
Unclassified or Non Hazardous Location
34mA at 26.5V
85mA at 26.5V
125mA at 26.5V
140mA at 26.5V
Hazardous or Classified Location
AS-I power supply
+
-
Warning
* Explosion hazard. Do not disconnect
equipment when a flammable or combustible atmosphere is present.
* Use installation wiring connections
with admitted maximum operating temperature of at least 20 ºC (68°F) higher than maximum ambient.
1 2 3
17
FieldQ
May 2018
Installation guide
DOC.IG.QC40.1 Rev. 3
18
Installation guide
DOC.IG.QC40.1 Rev. 3
FieldQ
May 2018
19
World Area Configuration Centers (WACC) offer sales support, service, inventory and commissioning to our global customers. Choose the WACC or sales office nearest you:
NORTH & SOUTH AMERICA
19200 Northwest Freeway Houston TX 77065 USA T +1 281 477 4100
Av. Hollingsworth 325 Iporanga Sorocaba SP 18087-105 Brazil T +55 15 3413 8888
ASIA PACIFIC
No. 9 Gul Road #01-02 Singapore 629361 T +65 6777 8211
No. 1 Lai Yuan Road Wuqing Development Area Tianjin 301700 P. R. China T +86 22 8212 3300
For complete list of sales and manufacturing sites, please visit www.emerson.com/actuationtechnologieslocations or contact us at info.actuationtechnologies@emerson.com
MIDDLE EAST & AFRICA
P. O. Box 17033 Jebel Ali Free Zone Dubai T +971 4 811 8100
P. O. Box 10305 Jubail 31961 Saudi Arabia T +966 3 340 8650
24 Angus Crescent Longmeadow Business Estate East P.O. Box 6908 Greenstone 1616 Modderfontein Extension 5 South Africa T +27 11 451 3700
EUROPE
Holland Fasor 6 Székesfehérvár 8000 Hungary T +36 22 53 09 50
Strada Biffi 165 29017 Fiorenzuola d’Arda (PC) Italy T +39 0523 944 411
www.emerson.com/fi eldq
©2018 Emerson. All rights reserved.
The Emerson logo is a trademark and service mark of Emerson Electric Co. FieldQ companies. All other marks are property of their respective owners.
The contents of this publication are presented for information purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available on request. We reserve the right to modify or improve the designs or specifications of our products at any time without notice.
TM
is a mark of one of the Emerson family of
FieldQ
Loading...