Bettis Programming: TEC2 Configuration file convert from TEC2000 using DCMlink Manuals & Guides

Configuration Instructions
ACT-MAN-01-04-EN Rev. A
September 2018
TEC2 Configuration file convert from TEC2000 (Model 500 Discontinued)
Using DCMlink
TM
ACT-MAN-01-04-EN Rev. B
Table of Contents
Section 1: Document Purpose
1.1 Export TEC2000 conguration (Method: TEClink) .......................................... 1
1.2 Export TEC2000 conguration (Method: DCMlinkTM) ..................................... 3
1.3 Import conguration to TEC2 unit (Method: DCMlinkTM) ............................... 8
Table of Contents
September 2018
Table of Contents
3
Section 1: Document Purpose
September 2018
ACT-MAN-01-04-EN Rev. B
Section 1: Document Purpose
This document is to show TEC user (1) how to export the conguration le from TEC2000 before perform the “TEC2 covert” which is changing electronics device inside TEC2000 unit into TEC2 electronics. (2) how to import TEC2000 conguration les into TEC2 electronics. There are two tools can be used to export the conguration from TEC2000 electronics actuator. First one is TEClink and second one is DCMlinkTM. Since TEClink is no longer support TEC2, DCMlinkTM becomes only available tools to access network to the conguration for conguration import process.Export TEC2000 conguration (Method: TEClink)
1.1 Export TEC2000 configuration (Method: TEClink)
1. Connect unit with RS485 Modbus on STC21/STC23 (RDM) or STC39 to STC44 with Modbus network.
2. TEClink export conguration from unit. (Using TEClink to export conguration le)
a) Set the comport and speed correct till the “Green” communication light
shows at the button status bar which means the communication between TEClink and Unit has built up successfully.
3. Click Recv and wait 10 second till the button color comes back.
1
Document Purpose
ACT-MAN-01-04-EN Rev. B
4. Click Save conguration le (.TEC) le at desire location
5. Save TEC2000 conguration le as unit serial number. (as example is 135614B01.
6. To make sure the TEC conguration export correctly, click “User” to read the
7. Open the TEC conguration le from the location you saved.
Section 1: Document Purpose
September 2018
(Not avaliable-it’s reading in process) (avaliable-it’s nish reading process)
TEC)
current parameter from the unit.
8. If user does not see any column is blue after open the le, the conguration is export correctly.
Document Purpose
2
Section 1: Document Purpose
September 2018
1.2 Export TEC2000 configuration (Method: DCMlinkTM)
1. Using DCMlinkTM to perform the conguration export, it requires the DCMlinkTM
rev is greater than 1.2 and licensed. To perform export / import process,
DCMlinkTM application requires to grand Emerson license.
(Please consult Emerson Sales Team for more information).
ACT-MAN-01-04-EN Rev. B
2. Build up communication channel.
a) Click tool bar “DCMlinkTM Setup”
b) Click “Preference”
3
Document Purpose
ACT-MAN-01-04-EN Rev. B
Section 1: Document Purpose
September 2018
c) High light the Modbus option and click “Add” button.
d) In the Pop-up screen, Choose RDM Slave for TEC2000 and Choose COM
port same as RS485 converter. The Baud Rate/ Parity/Stop Bits will be default as below number. Then Click the same button.
COM2
Document Purpose
4
Section 1: Document Purpose
September 2018
e) User should see the communication channel has built(RDM Slave) from
3. Scan unit under communication channel
a) Right click on Comport and choose “Scan for New Device”
ACT-MAN-01-04-EN Rev. B
DCMlinkTM as below. *note: Only TEC2000 in DCMlinkTM will be required
to use Slave mode to communicate unit.
b) Enter the unit choose to 0 and click start to scan network.
The red color of 0 which means the unit is not available at the network.
The blue color of 0 which means the unit is available at the network.
5
Document Purpose
ACT-MAN-01-04-EN Rev. B
Section 1: Document Purpose
September 2018
c) Once unit found in the network and close the pop-up screen of MODBUS,
user should see the unit serial number shows under the “COMPORT (RDM Slave)”
Document Purpose
4. Enter unit setup menu to export the conguration le.
a) Right click on the unit S/N and choose the “Detailed Setup”
6
Section 1: Document Purpose
September 2018
b) Processing of communication to TEC2000 unit will show below prompt
c) Location the “Export conguration” and click to save the conguration
ACT-MAN-01-04-EN Rev. B
d) Save le with unit serial number.
NOTE:
During the export process, the format of conguration le generate from TEClink is *.TEC and the format of conguration le generate from DCMlinkTM is *.cfg. the contents of conguration le are same either it’s generated from TEClink or
DCMlinkTM.
7
Document Purpose
ACT-MAN-01-04-EN Rev. B
Section 1: Document Purpose
1.3 Import configuration to TEC2 unit (Method: DCMlinkTM)
1. Set the comport with baud rate 115200 (Modbus Master)-if go through STC36 / STC38.
Set the comport with baud rate 9600 (Modbus-bus/Modbus repeater)-if go through STC 39 to STC44, Modbus Network channel A and B.
September 2018
2. Scan the unit through comport with unit address 1.
a) The dark green color as below is recongized as TEC2 unit.
b) The Pink color as below is recongized as MODEL500 unit. (Default)
(Model 500 Discontinued)
Document Purpose
8
Section 1: Document Purpose
September 2018
3. Click stop and Close after the unit is able to identied by DCMlinkTM and at the
protocol area, the unit tag will appear under comport.
4. Right click on the unit with “Detail Setup” and nd the “Load conguration”
button.
ACT-MAN-01-04-EN Rev. B
5. Load the conguration le from TEC2000 conguration le (*.TEC or *CFG)
6. After loading the conguration le, user will see the color changes through the
load process.
9
Document Purpose
ACT-MAN-01-04-EN Rev. B
7. After all the changes made, exit out from the Setup.
Section 1: Document Purpose
September 2018
a) Yellow Tag (the parameter needs to change after upload conguration
le)
b) Blue arrow
1) (Left arrow means write into conguration le, Right arrow means read from unit to overwrite the upload conguration.)
2) In order to upload all of the parameter into actuator, user needs to click all “LEFT ARROW” at each lines and tags.
3) After all “LEFT ARROW” has been click, the tag color will change from “Yellow” to “Gray” which means the conguration has changed but hasn’t save yet.
Document Purpose
8. After all “Detial Setup” has been made, user needs change the “Factory Setting”. It’s at Tools/Factory/Factory Settings. **note: if DCMlinkTM has no Emerson licensed, the factory setting will be disable till grant the licensed.
a) Click the button “Load conguration”
10
Section 1: Document Purpose
September 2018
b) Click all blue “LEFT ARROW” to make the changes.
ACT-MAN-01-04-EN Rev. B
c) Verify the critical parameter befor exit from factory setup.
1) Actuator Model (default is Model500, and needs change to TEC2)
2) Drive Sleeve (Close CW/Close CCW)
3) Worm Gear(Right hand/Left Hand)
4) Starter Type(Solid State/Electrical Mech)
5) Phase(Single Phase/Three phase)
6) Reverse Rotation(Yes/No)
7) Firmware CCM/LDM/RDM
A) CCM: 1.0.4.
B) LDM: 1.0.4.
8) Auxiliary Control Module
11
Document Purpose
ACT-MAN-01-04-EN Rev. B
9. Completed conguration le migration from TEC2000 electronics to TEC2
10. Export the nal change of conguration le from TEC2 and send the copy of le
11. Commisson the unit.
9) Network Adapter
d) Exit out the Setup to save the changes.
electronics.
back to Emerson as archive for future reference.
Section 1: Document Purpose
September 2018
NOTE:
if user has difculty to hav original TEC le, please consult Emerson team for sup­porting conguration le.
Document Purpose
12
World Area Confi guration Centers (WACC) offer sales support, service, inventory and commissioning to our global customers. Choose the WACC or sales offi ce nearest you:
NORTH & SOUTH AMERICA
19200 Northwest Freeway Houston TX 77065
USA T +1 281 477 4100
Av. Hollingsworth 325 Iporanga Sorocaba SP 18087-105 Brazil
MIDDLE EAST & AFRICA
P. O. Box 17033 Jebel Ali Free Zone Dubai T +971 4 811 8100
P. O. Box 10305 Jubail 31961 Saudi Arabia T +966 3 340 8650
T +55 15 3413 8888
24 Angus Crescent
ASIA PACIFIC
Longmeadow Business Estate East
P.O. Box 6908 Greenstone No. 9 Gul Road #01-02 Singapore 629361 T +65 6777 8211
No. 1 Lai Yuan Road
1616 Modderfontein Extension 5
South Africa
T +27 11 451 3700
EUROPE
Wuqing Development Area
Tianjin 301700
P. R. China T +86 22 8212 3300
Holland Fasor 6
Székesfehérvár 8000
Hungary
T +36 22 53 09 50
Strada Biffi 165
29017 Fiorenzuola d’Arda (PC)
Italy
T +39 0523 944 411
For complete list of sales and manufacturing sites, please visit
www.emerson.com/actuationtechnologieslocations or contact us at info.actuationtechnologies@emerson.com
www.emerson.com/bettis
©2018 Emerson. All rights reserved.
The Emerson logo is a trademark and service mark of Emerson Electric Co.
TM
is a mark of one of the Emerson family of companies.
Bettis All other marks are property of their respective owners.
The contents of this publication are presented for information purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available on request. We reserve the right to modify or improve the designs or specifications of our products at any time without notice.
Loading...