Bettis Integrated Control modules QC41, QC42, QC43 Installation Guide

Page 1
Installation Guide Bettis Q-Series
APPROVED
DOC.IG.BQC44.1 Rev. 1 February 2017
Installation Guide Integrated Control Modules
QC44 Intrinsically Safe
Page 2
Bettis Q-Series Installation Guide
February 2017 DOC.IG.BQC44.1 Rev. 1
1 Applicable Control modules:
QC44 - I.S. - Intrinsically Safe
Note:
This QC44 control module can be equipped with one or two pilot valves: * One pilot valve is default and suitable for normal
operation of double acting or spring return actuators.
* Two pilot valves are required for Fail in Last
Position function on double acting actuators.
The enclosures of both Weather Proof and Explosion Proof / Flame proof modules, have a IP66 or NEMA 4X, ingress protected rating.
2 Before starting
* Actuator must be isolated both pneumatically
and electrically before any (dis)assembly is begun.
* Installation, adjustment, putting into service,
use, assembly, disassembly and maintenance of the control module must be done by qualified personnel.
* Be sure that the actuator is correctly mounted
before connecting air supply and electrical wiring (see Installation & Operation Manual Bettis Q-Series Valve Actuator, DOC .IOM.Q.E)
* Check the module label for the right execution
(see figure 2.2)
* Check the type of actuator: single or double
acting (see figure 2.2).
* For mechanical installation of the module see
installation instruction leaflet DOC.BQC4.MTI.1, as shipped with the module.
2.1 Intended use
The Bettis Q-Series actuator is an integrated concept for the automation of quarter turn valves, dampers or other quarter turn applications. It consists of two basic parts (see figure 2.1):
1. Pneumatic actuator
2. Control Module The control module allows operation of the actuator and supplies position feedback signals.
Fig. 2.1 Check proper mounting before connecting air
supply and electrical wiring.
2
Control Module Type Label =
QC44..P1.. = Intrinsically Safe
Actuator Type Label = QS xxxx = Single acting (Spring Return) QD xxxx = Double acting
Fig. 2.2 Identification
Page 3
Installation Guide Bettis Q-Series
DOC.IG.BQC44.1 Rev. 1 February 2017
2.2 Mechanical alignment and mounting of the control module
The control module is equipped with an alignment­edge on top of the module. This allows easy alignment and mounting of the control module on to the actuator housing.
Procedure: (see gure 2.3)
1. First take care that both mating faces from the
actuator and control module are clean and free of dirt.
2. Check if the module has the required function
3. Remove the transparent film from the control
module.
4. Ensure seals are placed correctly.
5. Level the screws with the surface.
6. Place the alignment-edge (1) of the control
module at the top of the pneumatic interface.
7. Flip the module down taking care that the IPT
Probe (see fig 5; nr.2) on the actuator fits in the mating hole on the control module and loosely place the screws.
8. Tighten screws according force in sequence.
Tightening moments
The Control Module should be fastened by using an Allen key and applying the following tightening moments:
- Allen Key No 5: 6.1 to 6.6 Nm
(54 - 58.4 In.lbs)
Alignment-edge
Alignment-edge
IPT probe
Fig. 2.3 Alignment and mounting of control
module to actuator
3
Page 4
Bettis Q-Series Installation Guide
February 2017 DOC.IG.BQC44.1 Rev. 1
3 Pneumatic connections
IMPORTANT
Single acting
1 The actuator/valve combination can move
after connecting the air supply.
2 Ensure that the QC4x control modules are
mounted properly to the actuator to achieve good functioning and the required ingress protection, before connecting the air supply.
3 Check that the maximum supply pressure
P
= 8bar/116Psi
max
4 Be sure that the minimum required supply
pressure for the application is available at the actuator.
5 Take appropriate measures to prevent
condensation or moisture to entering the actuator or the control module. Condensation or moisture can damage these components and can result in failures.
6 The exhaust ports Ra and Rb on the module
(see gure 3.1) are shipped from the factory
with transport protection.
* If ingress protection IP66 or NEMA 4X is
required, appropriate connections must be used in exhaust ports Ra & Rb.
3.1 Operating media :
* Air or inert gasses. * Air filtered at 50 micron without condensate. * Dew point at -20˚C. * For subzero applications take appropriate
measures.
3.2 Single acting (spring return) or Double
acting actuator :
1 Remove the transport sticker from the air supply
(Ps).
2 Connect air supply to port (Ps).
Control Module cover
Double acting
Fig. 3.1 Pneumatic connections
Ra
Ps 1/4” BSP or 1/4” NPT
Ra
Rb
Ps 1/4” BSP or 1/4” NPT
4
Page 5
Installation Guide Bettis Q-Series
DOC.IG.BQC44.1 Rev. 1 February 2017
4 Electric Connections
The QC44 Intrinsically Safe Control Module contains a pilot valve for controlling the actuator and switches for position feedback.
WARNING:
* If the Control Module is used in a manner not
specied by the manufacturer, the protection
provided by the equipment may be impaired.
* If required, mount earth wire (1) between top
(2) and stainless steel washer (3) of earth wire connection (see gure 4.2).
* Use and mount cable glands as required by
national or local legislation.
* If IP66 or NEMA 4X ingress protection is
required, then the electrical entries must be
tted with devices rated IP66 or NEMA 4X.
Electrical safety requirements:
Use In- and outdoor.
Altitude
Maximum rela­tive humidity
Mains supply fluctuation Over voltage category
Pollution degree
Temperature see table 4.1
Operating full power available up to 2000 meter (6000 feet). 80% for temperatures up to 31°C (87.8°F) decreasing linearly to 50% relative humidity at 40°C (104°F).
up to ±10% of nominal voltage
II
2 (3 when the cover remains closed)
Caution! :
Risk of electric shock
* Installation, adjustment, putting into service,
use, assembly, disassembly and maintenance of the control module is strictly reserved to
qualied personnel.
* Do not attempt to install or repair any electric
device without shutting off incoming power.
Terminals
Lockable Module cover
Electrical entries:
3/4”NPT or M20
1/2”NPT or M20
Switch terminals
Control Module Type Label
Pilot valve terminals
Option: Manual
control Option: Additional manual control for “Fail in Last Position”
Fig. 4.1 Terminal connections behind cover.
Fig. 4.2 Earth wire connection
5
Page 6
Bettis Q-Series Installation Guide
February 2017 DOC.IG.BQC44.1 Rev. 1
4.1 Connecting Pilot valve(s)
The Control Module can be equipped with one or two pilot valves: * One pilot valve is default and suitable for normal
operation of double acting or spring return actuators
* Two pilot valves are required for Fail in Last
Position for double acting actuators.
IMPORTANT
For hazardous area installations see instructions in Chapter 11.
1. Before connecting the pilot valve, check the voltage on the control module label.
2 Remove control module cover (see figure 4.1). 3 Guide the cable(s) through the electrical
entry(ies).
- Use and mount cable glands as required by
national or local legislation.
4 For normal operation, make the electrical
connections as shown in figure 4.3.
For double acting actuators with Fail in
Last Position function, make the electrical connections as shown in figure 4.4
5 Mount the control module cover to the housing
(see figure 4.1) or continue with chapter 5. Take care that the cover seal is in place to comply to dust and water tightness according to IP66 or NEMA4X.
6 Lock the cover in position by turning the lock
screw in, until it blocks.
4.1.1 Tools
Table 4.1 Tool table
For terminals Screw driver 0.6 x 3.5 Cover lock screw Allen key nr 2
4.1.2 Typical functional ratings Pilot Valve
The pilot valve inside the Control Module sends the actuator to its open or closed position.
IMPORTANT
The below mentioned typical functional ratings are applicable for non-hazardous areas.
Table 4.2 Typical functional ratings Pilot Valve
Voltage Turn on V 16.4 ... 28
Turn off V 5.7
Current Turn on mA 25mA±10%
Turn off mA 7
Coil Resistance = 563 (Ta + 234 + 10)
254
0.5W
Cable range:
0.2 - 2.5mm2 or 30-12AWG
Fig. 4.3 Default Pilot valve wiring connections
0.5W
Cable range:
0.2 - 2.5mm2 or 30-12AWG
Fig. 4.4 Pilot valve wiring connections for
Fail in Last Position
6
Page 7
Installation Guide Bettis Q-Series
-3° 15° 75° 93° 0° 90°
DOC.IG.BQC44.1 Rev. 1 February 2017
4.2 Connecting Mechanical Feedback switches
IMPORTANT
The below mentioned typical switch specifications are applicable for non-hazardous areas.
1. Before connecting the switches, check the model code on the Control Module label.
QCXX.xxxMxx = Mechanical switches QCXX.xxxGxx = Mechanical switches
(gold plated)
2 Guide the cable(s) through the electrical
entry(ies).
- Use and mount cable glands as required by
national or local legislation.
3. Make connections as shown in figure 4.6 and table 4.3/4.4
4. Mount the Control Module cover. Take care that the cover seal is in place to comply to dust and water tightness according to IP66 or NEMA4X.
IMPORTANT
For hazardous area installations see instructions in Chapter 11.
Table 4.3 Mechanical switches
Option code M Option code G (gold contacts) Typ e Mechanical Voltage M: 277 VAC or 250VDC (maximum)
G: 125 VAC or 30VDC (maximum) Contacts NO and NC Temperature See table 4.1
Notes:
1. The mechanical (M-type) switches are rated for 3 A with inductive load.
2 The mechanical (G-type) switches have gold
contacts. For applications where the benefits of gold contacts are required, the maximum current is 0.1 A.
Table 4. 4 Maximum currents mechanical switches
Switch voltage M type switch G type switch
125 VAC 10 A (3 A1) 0.1 A
2
250 VAC 10 A (3 A1) ­30 VDC 0.5 A 0.1 A
2
125 VDC 0.5 A ­250 VDC 0.25 A -
Contact Switch signal and adjustable
Normally
Open
Contacts
Switch
operation
Switched
Unswitched
Signal
switch range
Close
switch
Rotation
Open
Switch
Fig 4.5 Adjustable switch range and factory settings
Wiring diagram:
- M = Mechanical
- G = Mechanical, gold contacts
Open Close
Cable range : 0.2 - 2.5mm2 or 30-12AWG
1 Wiring diagram shown, is applicable for actuators with
assembly code “CW”. For actuators with assembly code “CC” (reverse acting) the “Open” and “Closed” switch connections are also reversed.
2 Wiring diagram is shown in the actuators mid-stroke position.
Fig 4.6 Wiring diagram mechanical switches
7
Page 8
Bettis Q-Series Installation Guide
-3° 15° 75° 93°
90°
3mA
1mA
-3° 15° 75° 93°
90°
3mA
1mA
3mA
1 mA
3mA
1 mA
-3° 15° 75° 93° 0° 90°
February 2017 DOC.IG.BQC44.1 Rev. 1
4.3 Connecting 2-Wire proximity switches
IMPORTANT
The below mentioned typical switch specifications are applicable for non-hazardous areas.
1. Before connecting the switches, check the model code on the Control Module label.
QCXX.xxxNxx = 2-Wire NAMUR proximity 2 Guide the cable(s) through the electrical
entry(ies).
- Use and mount cable glands as required by
national or local legislation.
3. Make connections as shown in figure 4.9 and table 4.5.
4. Mount the Control Module cover. Take care that the cover seal is in place to comply to dust and water tightness according to IP66 or NEMA4X.
IMPORTANT
For hazardous area installations see instructions in paragraph Chapter 11.
Table 4.5 2-Wire NAMUR proximity switches
Option code N Typ e 2-wire inductive, normally closed Voltage 8 VDC nominal Output Unswitched: > 3mA
Switched: < 1mA Temperature See table 4.1 Compliant to DIN EN 60947-5-6 (NAMUR)
Switch
2-Wire 115V
proximity
switch
Switch
operation
Switched
Unswitched
Switch signal and adjustable
switch range
Close
switch
Signal
Rotation
Fig 4.7 Switch characteristics 2-wire 230VAC
proximity switch
Switch
operation
Open Switch
Unswitched
Switched
Close Switch
Unswitched
Switched
Switch signal and adjustable switch range
2-wire NAMUR proximity switch
Rotation
3mA
3mA
1mA
1 mA
Open
Switch
8
-3° 15° 75° 93°
90°
Rotation
Fig 4.8 Switch characteristics 2-wire NAMUR
proximity switch
Page 9
Installation Guide Bettis Q-Series
DOC.IG.BQC44.1 Rev. 1 February 2017
Wiring diagram:
- 2-Wire NAMUR proximity switches
L-
2
1
2
1
Open
Cable range : 0.2 - 2.5mm2 or 30-12AWG
1 Wiring diagram shown, is applicable for actuators with assembly
code “CW”. For actuators with assembly code “CC” (reverse acting) the “Open” and “Closed” switch connections are also reversed.
3
L+
5
L-
4
2
1
Close
6
L+
Fig 4.9 Wiring diagram 2-Wire proximity switches.
9
Page 10
Bettis Q-Series Installation Guide
15°
max
15°
max
February 2017 DOC.IG.BQC44.1 Rev. 1
5 Limit switch setting
5.1 Factory settings
Mechanical stroke : 90°±0.5° (Actuator setting) Switch points : ± 15° before each end of
stroke (open and closed position, see fig 5.1).
Adjustable range : See chapter 4.2 for the
applicable switch type.
Closed
Switch points
Open
Factory settings
Fig. 5.1 Adjustable range and factory settings
If required the mechanical stroke and the limit switch setting can be re-adjusted.
- For mechanical stroke adjustment please see document DOC.IOM.Q.E, available from www.emersonprocess.com/bettis
- For re-adjusting the limit switches, see procedure below.
5.2 Before re-adjusting the limit switches.
IMPORTANT
* Before mounting the actuator on the valve, be
sure that both the actuator and the valve have the same “open” or “closed” position.
* Set the Mechanical stroke before setting the
limit switches.
5.2.1 Pneumatic and electrical connections
Make pneumatic and electrical connections before adjusting the limit switch setting. See chapter 3 and 4.
5.2.2 Switch point setting and valve rotation direction.
The QC44 is equipped with non-intrusive switch adjustment. The adjustment screws are accessible behind a small shield in the front of the module (see fig 5.3). This means that the switch adjustment can be done without opening the module.
Normally valves are “Closed” after a clock wise rotation.
- In this case the top adjustment screw (see
fig. 5.3), sets the switch point of the “Closed” position and bottom adjustment screw sets the switch point of the “Open” position.
- When you have a valve that is “Open” after a
clock wise rotation, the position feedback will be reversed.
The table below indicates which re-adjustment screw and terminals are related to the “Open” or “Closed” switch point setting (see fig 16).
Table 5.1 Re-adjustment screws
Re-
adjust-
ment
screw :
Terminals
Valve movement
“Close” after
a clock wise
rotation
“Open” af ter
a clock wise
rotation
Bottom 1, 2, & 3 Open position Close position
Top 4, 5, & 6 Close position Open position
10
Page 11
Installation Guide Bettis Q-Series
DOC.IG.BQC44.1 Rev. 1 February 2017
5.2.3 Working principles Switch Operating Mechanism (see g 5.2)
The Switch Operating Mechanism is intend to operate the position feedback switches and allows adjustment of the switch points in the open and closed end positions. Factory setting is that the switches are activated 15° before the end of the open and closed stroke.
Switch Operation
The rotation of the actuators pinion operates the IPT device (1) which results in a linear movement. The linear movement of the IPT device operates lever (3). The lever amplifies the linear movement of the IPT device and operates the switch operating rod (5). Dowel pin (6) in the rod operated the levers of the open and closed switch elements (8 & 9).
The lever is of the “floating” type. When the IPT device operates the lever, it moves completely upwards until it meets the upper pivot block (4). At this point the lever will tip over and pull down the switch operating rod (5) and operates the bottom switch (7). When the IPT device moves back the springs cause the lever to move completely downwards until it meets the lower pivot block (2). At this point the lever will tip over and push up the switch operating rod (5) and operates the top switch (8).
Switch point adjustment
The position of the lower pivot block (2) can be changed by adjustment screw (10) and the position of the upper pivot block (4) can be changed by adjustment screw (9).
By adjusting the position of these pivot blocks the switch points will be changed.
The adjustment screws (9 & 10) can be found behind the shield (12) in front of the module. To access the adjustment screws loosen the screw (11) and rotate the shield (12) as shown.
Caution: Do not force the
adjustment screws when resistance is felt.
During adjustment there are three situations that can damage the adjustment screw head and internal mechanisms when forcing the adjustment screws.
1. Pivot block (2) will be blocked at bottom if screw (10) is rotated too much counter clock wise.
2. Pivot block (3) will be blocked at top if screw (9) is rotated too much clock wise.
3. Pivot blocks (2&3) will interfere with each other, if the adjustment screws (9&10) are rotated too much in the direction according to their related arrows.
Situation 1 and 2 may happen in combination with situation 3.
8
6
7
5
Fig. 5.2 Working principles Switch Operating Mechanism
10
9
4
3
2
1
15
10
12
H
E
W
N
N
E
E
N
N
I
P
N
R
G
A
E
O
!
W
R
-
-
T
G
O
I
N
O
D
Z
E
D
9
11
11
Page 12
Bettis Q-Series Installation Guide
February 2017 DOC.IG.BQC44.1 Rev. 1
5.3 Re-adjustment of switch points
IMPORTANT
The procedure below assumes:
- That the actuator and control modules are according the factory settings.
If the switch setting is somehow lost or
forgotten, then consult paragraph 6.3 to set the switch point setting back to factory
setting.
- That the actuator / valve assembly is closed
after a clock wise rotation (see chapter 5.2).
Below procedure assures that the position feedback complies more accurately with the valve position and will set the switch point at approximately 4° before the end of the stroke.
To set and detect the switch point, use a multi meter, connected to the switch terminals, to measure a resistance change as applicable per switch type (see applicable wiring diagram in chapter 4.2). For the proximity switches, you can use a proximity switch tester.
Procedure (see g 5.3):
1. Remove cover (15) and loosen the screw (11) of the shield (12) and turn the shield down.
Closed Position:
2. Move the actuator/valve assembly to the closed position by removing the control signal from pilot valve terminal 8 and 9 (see § 4.1).
3. Turn top screw (10) counter clock wise (do not force the adjustment screw) until the switch trips to the “off state” (no signal).
4. Turn top screw (10) clock wise (do not force the adjustment screw) until the switch trips to the “on state”. This position represents the actual, mechanical “closed” position of the valve.
5. Turn the screw minimal a 1/2 turn clock wise. The “closed” position switch point is now set.
Open Position:
6. Move the actuator to the open position by applying the applicable voltage to pilot valve terminal 8 and 9 (see § 4.1).
7. Turn bottom screw (9) clock wise (do not force the adjustment screw) until the switch trips to the “off state” (no signal).
8. Turn bottom screw (9) counter clock wise (do not force the adjustment screw) until the switch trips to the “on state”. This position rep­resents the actual “open” position of the valve.
9. Turn the screw minimal a 1/2 turn counter clock wise. The “open” position switch point is now
set.
10. Turn the shield (12) back over the adjustment screws and fasten it with the screw (11) and mount the main round cover back in place.
Table 5.2 Tool table
Shield screw Cross slotted Phillips nr. PH2
Adjustment screws
15
0.6 x 3.5 or
Cross slotted Phillips nr. PH2
H
E
W
N
N
E
E
N
N
I
P
N
R
G
A
E
O
!
W
R
-
-
T
G
O
I
Z
N
E
O
D
D
10
9
11
12
“Closed”
Switch point adjustment
“Open”
Switch point adjustment
Note:
360° rotation of adjustment screw is ±8° adjustment of switch point.
Fig. 5.3 Re-adjustment screws for “Open” and
“Closed” position feedback
12
Page 13
Installation Guide Bettis Q-Series
DOC.IG.BQC44.1 Rev. 1 February 2017
6 Trouble shooting
5.4 Check operation
5.4.1 Default (single) pilot valve
1 Connect pressure according chapter 3 and a
control signal to terminals (7) 8 and 9 according
§ 4.1 figure 4.3.
2 Actuator moves to “Open” position. “Open”
limit switch is activated and “Close” limit switch
is deactivated. 3 Remove voltage from terminals 9 and 8. 4 Actuator moves to “Close” position. “Close”
limit switch is activated and “Open” limit switch
is deactivated. 6 Mount the cover to the Control Module
(see fig. 4.1).
5.4.2 Dual pilot valve (Fail in Last Position)
operation
1. Connect pressure according chapter 3 and a
control signal to terminals (7) 8 and 9 according
§ 4.1 figure 4.4.
2. Actuator moves to “Open” position. “Open”
limit switch is activated and “Close” limit switch
is deactivated.
3. Remove voltage from terminals 9 and 8.
4. Actuator Stays in the “Open” position.
5. Connect pressure according chapter 3 and
a control signal to terminals (10) 11 and 12
according § 4.1 figure 4.4.
6. Actuator moves to “Closed” position. “Close”
limit switch is activated and “Open” limit switch
is deactivated.
7. Remove voltage from terminals 9 and 8.
8. Actuator Stays in the “Closed” position.
9. Mount the cover to the Control Module
(see fig. 4.1).
6.1 The “Open” and “Closed” position
feedback signals are reversed from the
actual valve positions.
1 Check if the actuator is correctly mounted to the
valve. Before mounting the actuator on the valve, the actuator and the valve should have the same “open” or ‘closed” position (see Installation
& Operation Manual Bettis Q-Series Valve
Actuator DOC.IOM.Q.E).
2 Some valves may be operated in such a way that
they are:
- “Open” after a clock wise rotation and
- “Closed” after a clock wise rotation.
3 Please see § 5.2 for setting the “Open” and
“Closed” position feedback signals
6.2 The actuator does not give (good) position feedback signals.
1 Check if the actuator is correctly mounted to the
valve.
2 Re-adjust the limit switch setting as per chapter
5.3
6.3 Factory setting of the switch points.
IMPORTANT
The procedure below assumes:
- That the actuator / valve assembly is closed
after a clock wise rotation (see also § 5.1).
- The control module is pneumatically and
electrically connected according chapter 3 and 4.
This procedure sets the switch point settings of the switches, back to the factory settings (±15° before each end of stroke), assuming a mechanical stroke of 90°±0.5° of the actuator.
To set and detect the switch point, use a multi me­ter, connected to the switch terminals, to measure a resistance change as applicable per switch type (see applicable wiring diagram in chapter 4.2). For the proximity switches, you can use a proximity switch tester.
13
Page 14
Bettis Q-Series Installation Guide
February 2017 DOC.IG.BQC44.1 Rev. 1
7 Maintenance
The Bettis Q-Series Control Modules are designed
Procedure (see g 5.3):
1. Remove cover (15) and loosen the screw (11) of the shield (12) and turn the shield down.
Closed Position:
2. Move the actuator/valve assembly to the closed position by removing the control signal from terminal 8 and 9 (see § 4.1).
3. Turn top screw (10) counter clock wise maximum 20 turns, (do not force the adjustment screw) until the switch trips to the “off state” (no signal).
4. Turn top screw (10) clock wise 1 3/4 turn
(do not force the adjustment screw).
The “closed” position switch point is now set to factory setting.
Open Position:
5. Move the actuator to the open position by ap­plying the applicable voltage to terminal 8 and 9 (see § 4.1).
6. Turn bottom screw (9) clock wise maximum 20 turns, (do not force the adjustment screw) until the switch trips to the “on state” (no signal).
7. Turn bottom screw (9) counter clock wise 1 3/4 turn (do not force the adjustment screw) The “open” position switch point is now set to factory setting.
8. Turn the shield (12) back over the adjustment screws and fasten it with the screw (11) and mount cover (15) back in place.
Important: Do not force the adjustment screws
During switch point adjustment, do not force the adjustment screws when you feel an obstruction. Forcing the adjustment screws can damage the cross head of the adjustment screw.
to operate without maintenance. For any further maintenance to the actuator see Installation & Operation Manual Bettis Q-Series Valve Actuator, DOC.IOM.Q.E or contact your local Bettis Q-Series representative. Installation, adjustment, putting into service, use, assembly, disassembly, maintenance and repair of the Control Module must be done by qualified personnel.
Note:
This product is only intended for use in large-scale fixed installations excluded from the scope of Directive 2011/65/EU on the restriction of the use of certain hazardous substances in electrical and electronic equipment (RoHS 2).
8 Optional Controls
8.1 Manual Control options
(see figure 8.1)
Location for 2nd Manual Control
Lock
45°
Unlock
Fig. 8.1 Local Manual Control options
For commissioning, emergency or maintenance purposes, the Bettis Q-Series can be supplied with one or two Manual Control options. These can operate the pilot valve(s) inside the module and as such operate the actuator, when there is air pressure available, but no control signal or power supply.
8.1.1 Mounting Manual Control
1 To add a Manual Control, remove the plug(s)
in front of the module and turn in the Manual Control.
- For normal operation the module should be fitted with one Manual Control.
- For Double Acting with a Fail-in-Last-Position function, two Manual Control can be fitted.
On
Off
Default location of Manual Control
14
Page 15
Installation Guide Bettis Q-Series
DOC.IG.BQC44.1 Rev. 1 February 2017
8.1.2 Manual Control operation
1 The Manual Control has a “Push & Lock”
function:
- To operate the Manual Control, use a screw driver, push to activate and release to de­activate the pilot valves.
- If required turn it 45°, to lock it in position and keep the actuator in its operated state.
2 In case of a Fail in Last Position configuration
with two manual controls:
- The manual control on the right side (default location) will pressurize the central air chamber and cause the actuator to rotate counter clock wise. For reverse acting Bettis Q-Series actuators (Assembly code CC) the actuator will rotate clock wise.
- The manual control on the left side (Location for 2nd Manual Control) will pressurize the end cap air chambers and cause the actuator to rotate clock wise. For reverse acting Bettis Q-Series actuators (Assembly code CC) the actuator will rotate counter clock wise.
- In order to operate one of the manual control, be sure the opposite manual control is de-activated and unlocked.
3 It is possible to rotate the screw multiple cycles.
The unit will than toggle every 90° between “locked” (1) and “unlocked” (0).
8.2 Speed control option
(see figure 8.2). The Bettis Q-Series can be supplied with a Speed Control option. One throttle is required for Spring Return actuators and up to two for Double Acting actuators. The speed control throttle controls the air flow in and out of an air chamber and as such limits
Spring Return: Top entry only.
Double Acting: Bottom and/or top entries.
1
2
Fig. 8.2 Speed control operation
the speed of the “Opening” and “Closing” stroke simultaneously.
8.2.1 Mounting Speed Control throttle(s):
1 Remove the plug(s) at the side of the module
and turn in the throttle (1). 2 Spring Return actuators: Use the top entry only. 3 Double acting actuators: Use both bottom and
top entries.
- For standard actuators, the top entry will throttle the closing stroke.
- For standard actuators, the bottom entry will throttle the opening stroke.
- For reverse acting actuators, the opposite strokes will be throttled.
8.2.2 Adjusting Speed Control throttle(s):
1 Remove the nut cap (2). 2 Clockwise rotation of the adjustment screw
reduces the speed.
3 Counter clockwise rotation of the adjustment
screw increases the speed.
4 Replace the nut cap.
9 Related Information
Other documents containing information related to the Bettis Q-Series Module include:
- Q1.604.10 Bettis Q-Series Control Module
- DOC.IOM.Q.E Installation Operation &
These documents are available, in multiple languages, for download from
www.emerson.com/bettis
data sheets
Maintenance Manual.
15
Page 16
Bettis Q-Series Installation Guide
February 2017 DOC.IG.BQC44.1 Rev. 1
11 Intrinsically Safe Electrical connections
11.1 Product QC44.xP1Nxx1
This section is about intrinsically safe connections for the QC44 control module with the N-type switches.
Terminals
Control Module Cover
Type Label
Fig 11.1 Product marking
ATEX Hazardous or Classied Location
0344 Certificate: Pending
II 1 G Ex iaT* II 1 G Ex tD A20 T80°C IP65
Hazardous or Classied Location
Intrinsically safe, Class I, II, III, Division 1,
Groups ABCDEFG T*, Type 4X
Ex ia IIC, T*, IP65
DIP A20 TA 80°C
Certificate: Pending
Temperature range T*:
Table 11.1 Temperature class
Connection
Type 1 40 60 60 Type 2 33 53 60 Type 3 12 32 49
Note:
The Connection Type refers to the entity parameters of the IS barriers used for connection of the switches, See Table 11.2. For double-acting Fail in Last Position, Only T4 to T1 are applicable with Maximum Ambient Temperature = 50˚C.
T ambient at T class:
T6 (°C) T5 (°C) T4 – T1 (°C)
11.1.1 ATEX Intended use
The Control Module QC44.xP1Nxx1 of the Bettis Q-Series pneumatic actuator is Group II category 1 equipment and intended for use in areas in which explosive atmospheres caused by mixtures of air and gases, vapours, mists or by air/dusts are likely to occur.
The pneumatic actuator part, together with the pneumatic Module part of the Bettis Q-Series pneu­matic actuators is a Group II category 2 equipment and intended for use in areas in which explosive atmospheres caused by mixtures of air and gases, vapours, mists or by air/dusts are likely to occur. Therefore it may be used in (ATEX) classified Zones 1, 2 (Gasses) and/or 21, 22 (Dust).
11.1.2 Special conditions for safe use
• The material for the Control Module housing is an aluminum alloy. When the unit is used in a potentionally explosive atmosphere, requiring ATEX equipment category 1 G, the unit must be installed in such a way, that even in the event of rare incidents, an ignition source due to impact or friction between the enclosure and iron/steel is prevented.
• Only non-combustible fluids may be used in the pneumatic circuit.
Note: the surface temperature of the module has
been determined without a dust layer.
• Potential electrostatic charging hazard, clean only with a damp cloth - danger of propagating discharge.
• The apparatus shall be installed in such a way that the risk from electrostatic discharges and propagating brush discharges caused by rapid flow of dust is avoided.
• Precaution shall be taken to avoid danger of ignition due to electrostatic charges on the marking plate of the enclosure.
Table 11.2 QC44 Intrinsically Safe Entity Parameters
Circuit Terminal Ui Ii Pi Ci Li
Pilot
8 - 9 28Vdc 300mA 1.6W 0 0
valve
Type 1 1 – 2, 4 - 5 16Vdc 25mA 34mW 150nF 150uH Type 2 1 – 2, 4 - 5 16Vdc 25mA 64mW 150nF 150uH Type 3 1 – 2, 4 - 5 16Vdc 52mA 169mW 150nF 150uH
Feedback switches 1 & 2
16
Page 17
Installation Guide Bettis Q-Series
DOC.IG.BQC44.1 Rev. 1 February 2017
11.1.3 Dielectric strength
Control Module QC44 complies to the dielectric strength requirement according IEC- 60079-11
11.1.4 Wiring instructions QCQC44.xP1Nxx1
Intrinsically safe Control Module with the N-type switches.
Unclassified or Non
Hazardous Location
Terminal connections
Solenoid 1
Solenoid 2*
* Solenoid 2 only available with
Fail in Last Position function
Cable range:
Solid / Stranded wire: 0.2-2.5mm2 or 30-12 AWG
IS Approved Barrier
IS Approved Barrier
-
+
-
+
Hazardous or
Classified Location
L-
2
1
2
1
7
8
9
10
11
12
3
5
L+
6
L-
4
L+
2
1
Hazardous or
Classified Location
Unclassified or Non
+
-
IS Approved
Barrier
-
IS Approved
Barrier
Switch 1 Switch 2
Note:
* Use intrinsically safe approved barrier with signal levels according
EN60947-5-6 (NAMUR)
The barrier needs to limit the switch energy to the max. specified
values in table 11.2.
Hazardous Location
+
Table 11.3
Notes: CSA ATE X
Installation must be inaccordance
1
with:
2 Before operation:
3 Barriers:
4 Intrinsically safe equipement Must be CSA Approved Must be ATEX Approved
Barrier I.S. Entity Parameters must
5
meet the following conditions:
6 When multiple barriers are used:
Canadian Electrical Code,
The control module in combination with the pneumatic module must be mounted
Must be CSA approved and installed in an enclosure that meets the requirements of
Control equipment connected to the bar-
rier must not use or generate more than
Part1
properly on the actuator.
CEC part1.
250Vrms or Vdc.
The national wiring practices of the country
Must be certified by an European Notified
body and installed per manufacturer’s
of use
installation instructions.
Uo =< Ui Io =< Ii Po =< Pi
Co >= Ci + C cable Lo >= Li + L cable
* Each I.S. Circuit must use shielded, twisted pairs
* Cable insulation and shielding must extend to within paritioned area of terminals
17
Page 18
Bettis Q-Series Installation Guide
February 2017 DOC.IG.BQC44.1 Rev. 1
11.2 Product QC44.xP1*xx1
This section is about intrinsically safe connections for the QC44 control module with the switch types M and G where * is M or G
Type Label
Control Module Cover
Terminals
Fig 11.2 Product marking
ATEX Hazardous or Classied Location
0344 Certificate: Pending
II 1 G Ex ia IIC T4...T6
II 1 D Ex tD A20 T80°C
Hazardous or Classied Location
Intrinsically safe, Class I, II, III, Div. 1,
Groups ABCDEFG T4...T6, Type 4X
Ex ia IIC, T6, IP65
DIP A20 TA 80°C
Certificate: Pending
The pneumatic actuator part, together with the pneumatic Module part of the Bettis Q-Series pneu­matic actuators is a Group II category 2 equipment and intended for use in areas in which explosive atmospheres caused by mixtures of air and gases, vapours, mists or by air/dusts are likely to occur.
Therefore it may be used in (ATEX) classified Zones 1, 2 (Gasses) and/or 21, 22 (Dust).
11.2.2 Special conditions for safe use
• The material for the Control Module housing is an aluminum alloy. When the unit is used in a potentionally explosive atmosphere, requiring ATEX equipment category 1 G, the unit must be installed in such a way, that even in the event of rare incidents, an ignition source due to impact or friction between the enclosure and iron/steel is prevented.
• Only non-combustible fluids may be used in the pneumatic circuit.
Note: the surface temperature of the module has
been determined without a dust layer.
• Potential electrostatic charging hazard, clean only with a damp cloth - danger of propagating discharge.
• The apparatus shall be installed in such a way that the risk from electrostatic discharges and propagating brush discharges caused by rapid flow of dust is avoided.
• Precaution shall be taken to avoid danger of ignition due to electrostatic charges on the marking plate of the enclosure.
Table 11.4 QC44 Intrinsically Safe Entity Parameters
Temperature range :
T4...T6 @ Ta = -20°C...+50°C (-4°F...122°F)
11.2.1 ATEX Intended use
The Control Module QC44.xP1*xx1 of the Bettis Q-Series pneumatic actuator is Group II category 1 equipment and intended for use in areas in which explosive atmospheres caused by mixtures of air and gases, vapours, mists or by air/dusts are likely to occur.
18
Circuit Terminal Ui Ii Pi Ci Li
Pilot
8 - 9 28Vdc 300mA 1.6W 0 0
valve
M-
type
G-type 1 - 2 - 3,
Feedback switches 1 & 2
1 - 2 - 3,
30Vdc 300mA 1.2W 0 0
4 - 5 - 6
30Vdc 100mA 1.2W 0 0
4 - 5 - 6
11.2.3 Dielectric strength
Control Module QC44 complies to the dielectric strength requirement according IEC- 60079-11.
Page 19
Installation Guide Bettis Q-Series
DOC.IG.BQC44.1 Rev. 1 February 2017
11.2.4 Wiring instructions QC44.xP1Nxx1
Intrinsically safe Control Module with the switch types M and G where * is M or G
Unclassified or Non
Hazardous Location
Terminal connections Solenoid 1
Solenoid 2*
* Solenoid 2 only available with
Fail in Last Position function
IS Approved Barrier
IS Approved Barrier
-
+
-
+
Hazardous or
Classified Location
2
1
7
8
9
10
11
12
3
5
6
4
Hazardous or
Classified Location
Cable range:
Solid / Stranded wire: 0.2-2.5mm2 or 30-12 AWG
+
-
IS Approved
Barrier
-
IS Approved
Barrier
Switch 1 Switch 2
+
Unclassified or Non
Hazardous Location
Table 11.5
Notes: CSA ATE X
Installation must be inaccordance
1
with:
2 Before operation:
3 Barriers:
4 Intrinsically safe equipement Must be CSA Approved Must be ATEX Approved
Barrier I.S. Entity Parameters must
5
meet the following conditions:
Uo =< Ui Io =< Ii Po =< Pi
Co >= Ci + C cable Lo >= Li + L cable
6 When multiple barriers are used:
Canadian Electrical Code,
The control module in combination with the pneumatic module must be mounted
Must be CSA approved and installed in an enclo-
sure that meets the requirements of CEC part1.
Control equipment connected to the barrier
must not use or generate more than 250Vrms
Part1
properly on the actuator.
or Vdc.
The national wiring practices of the
country of use
Must be certified by an European Noti-
fied body and installed per manufac-
turer’s installation instructions.
* Each I.S. Circuit must use shielded, twisted pairs
* Cable insulation and shielding must extend to within paritioned area of terminals
19
Page 20
Bettis Q-Series Installation Guide
February 2017 DOC.IG.BQC44.1 Rev. 1
10 EC - Declaration of Conformity
ROC nr 8480
Legal representative entity for the European Union:
Emerson Process Management, Valve Automation
Asveldweg 11, 7556 BR Hengelo Netherlands
EC DECLARATION OF CONFORMITY
Issued in accordance with the
EMC Directive 2004/108/EC, Appendix 1
ATEX Directive 94/9/EC
above mentioned European Directives. Before the Control Module is put into operation, the machine into or onto which the Control Module will be installed, must comply with the stipulations of the machinery directive.
Product description : Bettis Q-Series Control module QC44 Serial number : Year of Construction :
ATEX DIRECTIVE
Types : QC44...P1*xx1... (x = M, G, or N) ATEX Certificate No. : Pending Marking :
Applicable standards : EN 60079-0 : 2006 EN 60079-11 : 2007 EN 60079-26 : 2007
Notified body :
II 1 G Ex ia IIC T4...T6 II 1 G Ex d+ib IIC T4...T6
EN 61241-0 : 2004 EN 61241-1 : 2004
Meander 1051, 6825 MJ Arnhem, The Netherlands
resp. II 1 D Ex tD A20 T80°C IP65 resp. II 1 D Ex tD A20 T80°C IP65
Rev. 0
EMC Directive
Types : QC44...P1*xx1... (* = M, G, or N) Applicable standards : IEC61326-1 :1998 NAMUR Recommendations : NE21 Note :
Directive 2006/95/EC
Signed:
_____________________________ Name:
S. Ooi Position:
Vice President, Rack & Pinion SBU & Global Marcom Emerson Process Management, Valve Automation Group Date:
2015-12-08 Place:NL
Houston TX, U.S.A.
20
Page 21
World Area Con guration Centers (WACC) offer sales support,
service, inventory and commissioning to our global customers.
Choose the WACC or sales of ce nearest you:
NORTH & SOUTH AMERICA
19200 Northwest Freeway Houston TX 77065 USA T +1 281 477 4100
Av. Hollingsworth 325 Iporanga Sorocaba SP 18087-105 Brazil T +55 15 3413 8888
ASIA PACIFIC
No. 9 Gul Road #01-02 Singapore 629361 T +65 6777 8211
No. 1 Lai Yuan Road Wuqing Development Area Tianjin 301700 P. R. China T +86 22 8212 3300
For complete list of sales and manufacturing sites, please visit www.emerson.com/actuationtechnologieslocations or contact us at info.actuationtechnologies@emerson.com
MIDDLE EAST & AFRICA
P. O. Box 17033 Jebel Ali Free Zone Dubai T +971 4 811 8100
P. O. Box 10305 Jubail 31961 Saudi Arabia T +966 3 340 8650
24 Angus Crescent Longmeadow Business Estate East P.O. Box 6908 Greenstone 1616 Modderfontein Extension 5 South Africa T +27 11 451 3700
EUROPE
Holland Fasor 6 Székesfehérvár 8000 Hungary T +36 22 53 09 50
Strada Biffi 165 29017 Fiorenzuola d’Arda (PC) Italy T +39 0523 944 411
www.emerson.com/bettis
©2018 Emerson. All rights reserved.
The Emerson logo is a trademark and service mark of Emerson Electric Co. Bettis companies. All other marks are property of their respective owners.
The contents of this publication are presented for information purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available on request. We reserve the right to modify or improve the designs or specifications of our products at any time without notice.
TM
is a mark of one of the Emerson family of
Loading...