11.2.3 Setting the Full Stroke Adjustment Screw to the Required Angle....... 66
II
Table of Contents
Installation, Operation and Maintenance Manual
DOC.IOM.Q.E Rev. D
Section 1: Before You Start
This section explains:
• Base safety procedures.
• Where to nd detailed information relating safety.
• Storage guidelines.
Installation, adjustment, putting into service, use, assembly, disassembly and maintenance
of the pneumatic actuator must be performed by qualied personnel.
NOTICE
Failure to follow the above guidelines will void warranty.
WARNING
Section 1: Before You Start
April 2019
Actuator must be isolated both pneumatically and electrically before any (dis)assembly starts.
Before mounting or (dis)assembly, the actuator consult the relevant sections of this manual.
1.1 Installation, Operation and Maintenance
Reference Documents
Before you start, read the following documents:
• All Sections in this manual.
• Safety Guide (Document No. DOC.SG.FQ.EN).
Mounted Control modules are shipped with the applicable installation guide:
QC41, QC42 or QC43: Document DOC.IG.QC41.1.
QC40: Document DOC.IG.QC40.1.
QC54: Document DOC.IG.QC54.1.
For Safety Instrumented Systems application, read the following document:
• SIL Safety Manual FieldQ (Document No. DOC.SILM.FQ.EN).
Before You Start
NOTICE
Failure to read the Safety Guide will void the warranty.
Not following the instructions of the Safety Guide can lead to failure of the product and
harm to personnel or equipment.
1
Section 1: Before You Start
April 2019
Installation, Operation and Maintenance Manual
1.2 Warehouse Storage
• All actuators should be stored in a clean, dry warehouse, free from excessive
vibration and rapid temperature changes.
• All actuators should not be stored directly to the oor surface - it must be placed in
racks/shelves or use a pallet.
1.3 On-Site Storage
• All actuators should be stored in a clean, dry warehouse, free from excessive
vibration and rapid temperature changes.
• Prevent moisture or dirt from entering the actuator. Plug or seal both air
connection ports.
NOTICE
Failure to follow the above guidelines (Warehouse and On Site Storages) will void warranty.
DOC.IOM.Q.E Rev. D
Before You Start2
Installation, Operation and Maintenance Manual
DOC.IOM.Q.E Rev. D
Section 2: Introduction
This section explains:
• How to identify the received product.
• The intended use of the product.
• Construction details.
• Actuator specications.
2.1 Identification
The FieldQ Rack and Pinion actuators are available as double-acting or spring-return
versions. 13 models are available, ranging from 40 Nm to 1600 Nm (354 to 14161 lbf.in)
nominal torque output.
The FieldQ package consists of an actuator with a module for control and position feed
back and forms an integrated concept for “On/Off” valve automation.
Section 2: Introduction
April 2019
1. Basic Actuators
The basic actuator supplies the torque, required to open and close valves and is
available in various sizes (rated 47 to 1676Nm at 5.5barg or 413 to 14874 In.lb. at 80pisg).
Double acting and spring return executions are available. The spring return execution can be
equipped with multiple spring sets to cover a pressure range from 2 to 8 barg (30 to 120 psig).
The springs in the spring-return version allow a fail action in case of loss of air supply
pressure (Fail-to-Close or Fail-to-Open). As from size FD150 double-acting versions have
at end caps to reduce actuator length and internal air volume.
The springs in the spring-return version allow a fail action in case of loss of air supply
pressure (Fail-to-Close or Fail-to-Open).
As from size 150 double-acting versions have at end caps to reduce actuator length and
internal air volume.
2. Control Modules
The Control Modules contain, next to the components for feedback switches, also all the
pneumatic control components.
Its compact and robust construction incorporates basic control and feedback functionality
and is suitable for indoor and outdoor use.
3. NAMUR Adaptation Plate
The top ange of the FieldQ actuator is equipped with a NAMUR (VDE/VDI 3845) drilling
pattern. The addition of a NAMUR plate makes the FieldQ actuator suitable for mounting
all kinds of NAMUR compatible control accessories like solenoids. For more info on NAMUR
plate, see sheet 1.605.03.
Introduction
3
Section 2: Introduction
e
April 2019
Figure 1 Identification
Installation, Operation and Maintenance Manual
DOC.IOM.Q.E Rev. D
1
2
34
SizeEnd cap design
SRDA
5
Spring design
Left
6
Right
Pinion bottom /
Insert design
2
40 100
Maximum 12
spring cartridges
SRLeftRightDA
150 -
600
Maximum 12
spring cartridges
LeftRightSRDA
950 -
1600
Notes:
1. Top auxilliaries according (VDI/VDE 3845; NAMUR). FieldQ comes with a proprietary pneumatic interface
for direct mounting of the Control modules. Option: NAMUR adaptation plate for direct mounting of solenoids.
2. Valve interface available according ISO5211 or DIN 3337. Actuator sizes 40 to 1600 can be fitted with driv
inserts with various inner shapes.
3. Spring-Return actuators: - with springs
4. Double-Acting actuators: - no springs
5. Actuator sizes 40 to 100 have high end caps for double-acting and spring-return models. Actuator sizes
150 to 1600 have low end caps for double-acting models and high end caps for spring-return models.
6. Actuator sizes 40 to 600 are fitted with a maximum of 12 spring cartridges. Actuator sizes 950 and 1600
are fitted with a maximum of 6 loose springs.
Maximum 6
loose springs
Introduction4
Installation, Operation and Maintenance Manual
DOC.IOM.Q.E Rev. D
2.2 Intended Use
The FieldQ Rack and Pinion actuators are intended for the automation and operation of
quarter-turn valves like Buttery, Ball and Plug valves.
Rack and Pinion actuators can also be used to operate dampers or any other quarter-turn
applications.
2.3 Specifications
Table 1. Pressure Range
Actuator TypePressure
Double-Acting0.2 to 8.3 barg (2.9 to 120 psig)
Spring-Return
6 to 8.3 barg (87 to 120 psig), with maximum spring set
3 to 8.3 barg (43.5 to 120 psig), reduced spring quantity
Section 2: Introduction
April 2019
Table 2. Operating Media
Actuator TypeOperating Media
Air, dry or lubricated and inert gases
Dew point at least 10K below ambient temperature
Double-Acting and Single-Acting
1. For the base actuator the recommended air quality for normal operation
(according ISO 8573-1) is: 7-5-4.
2. In case Q-Series Control Modules are used, the operating media specication as mentioned in the Installation Guide (shipped with each control module) are applicable.
QC41, QC42 or QC43: Document DOC.IG.QC41.1.
QC40: Document DOC.IG.QC40.1.
QC54: Document DOC.IG.QC54.1.
For sub-zero applications, take appropriate measures
Mentioned pressure levels are "gauge pressures".
Gauge pressure is equal to absolute pressure minus
atmospheric pressure.
NOTE:
Use of lters, pressure regulators, lubricator and an oil/water separator mounted in the air
supply line, will allow a smooth and durable operation of the actuator.
For lubricated supply air, it is recommended to use a non-detergent oil without aggressive
additives, VG32, group 2 (ISO 3448).
Table 3. Temperature Range
Introduction
Actuator TypeTemperature
Standard-20°C to +80°C (-4°F to +176°F)
Option: Low Temperature-40°C to +80°C (-40°F to +176°F)
Option: High Temperature-10°C to +120°C (+14°F to +250°F)
1. In case Q-Series Control Modules are used, the temperature range as mentioned in the Installation Guide (shipped with each control module) are applicable.
QC41, QC42 or QC43: Document DOC.IG.QC41.1.
QC40: Document DOC.IG.QC40.1.
QC54: Document DOC.IG.QC54.1.
1. The options, listed here, are all options available. Not all options apply to all
congurations. Check the actuator size page for valid congurations.
2. Valve Interface:
—Option "S"; Small Interface with Center Plate (DIN3337)
—Option "L"; Large Interface with Center Plate (DIN33337)
3. Contact your local FieldQ representative for additional insert options.
4. PED Group 1 Label only available up to size 950.
Installation, Operation and Maintenance Manual
DOC.IOM.Q.E Rev. D
is not available for sizes 0950.
is not available for sizes 1600.
8
Conguration Code
Installation, Operation and Maintenance Manual
DOC.IOM.Q.E Rev. D
Section 4: Installation
This section explains:
• The actuator rotation direction.
• In which position the actuator will end after a failure.
• Principles of operation:
—Solenoid operation.
—Double acting and Spring return operation.
• Assembly codes.
• Actuator to valve assembly.
4.1 Before You Start
Section 4: Installation
April 2019
SAFETY
In case of an air or electrical failure, it is important to know the behavior of the actuator.
Before mounting the actuator on a valve, consult the following sections below.
4.2 Actuator Rotation Direction
4.2.1 Valve Rotation
For the following paragraphs we assume that valves rotate as indicated in Figure 3.
Figure 3 Normal valve rotation
Installation
The valve is closed after
a clockwise rotation.
The valve is open after
a counterclockwise rotation.
9
Section 4: Installation
April 2019
4.2.2 Position After Failure
The position of the actuator after a failure depends on the:
1. Principle of operation (see paragraph 4.3)
2. Assembly codes (see paragraph 4.4)
3. Kind of failure. Refer to the table below.
Table 5. Position After Failure
Installation, Operation and Maintenance Manual
DOC.IOM.Q.E Rev. D
Principle of
Operation
Double-Acting
Actuator
Single-Acting
(Spring-Return)
Actuator
Assembly CodeKind of FailurePosition
PressureNot dened
CW
CW
SignalClosed
Supply VoltageClosed
PressureNot dened
SignalOpen
Supply VoltageOpen
PressureClosed
SignalClosed
Supply VoltageClosed
PressureOpen
SignalOpen
Supply VoltageOpen
Table 6. Position after a failure with a Double-Acting module with
Fail-In-Last-Position Function
FieldQ actuators can be either piped with solid or exible tubing with the solenoid valve
mounted remotely from the actuator or by mounting a VDI/VDE 3845 (NAMUR) designed
solenoid valve DIRECTLY onto the NAMUR adaptation plate on the side of the actuator.
Figure 4 Typical Solenoid Operation
Spring-Return Operation Double-Acting Operation
April 2019
The table below represents the cycle time (operating time) per different Actuator sizes:
Operating time is average with actuator under load and solenoid valve tted.
Test conditions:
1. Solenoid with ow capacity: 0.6 m3/hr
2. Pipe diameter: 6mm
3. Medium: clean air
4. Supply pressure: 5.5 bar (80psi)
5. Load: with average load
6. Stroke: 90°
7. Temperature: Room temperature
pressurized
Spring-ReturnDouble-Acting
A-port
Spring
stroke
A-port
pressurized
B-port
pressurized
Installation
11
Section 4: Installation
Installation, Operation and Maintenance Manual
April 2019
4.3.2 Ingress Protection (IP) Rating
FieldQ actuators are IP66 / NEMA4 rated. In case of IP66 or NEMA4 requirements, take
precautions that comply with the IP66 / NEMA4 requirements to prevent moisture or dust
from entering the actuator through the open air exhaust port(s), either directly on the
actuator or at the exhaust ports of the connected solenoid valve.
We recommend to connect tubing to the exhaust(s) and lead this into a dry and dust free
area, or to use check valves in the exhaust.
4.3.3 Control Module Operation
The operating principle, as explained here, is applicable for actuators with assembly code
CW (direct acting).
• The outward stroke will move the valve to the “Open” position.
• The inward stroke will move the valve to the “Closed” position.
• For assembly codes CC, the operating principle is reversed (reverse acting):
DOC.IOM.Q.E Rev. D
Figure 5 Double-Acting Operation
Outward Stroke
A-port
Option:
Throttle 1
5/2 Spool valve
Option: LMC
Ps
Pilot
valve 1
B-port
Option:
Throttle 2
Rb
Ra
1. Send control signal “Open” to the Control Module.
2. Pilot valve 1 will be activated and the 5/2spool valve will pressurize the central
air chamber.
3. The piston will move outwards to the “Open” position.
4. The Control Module indicates the “Open” position and activates feedback
signal “Open”.
12
Installation
Installation, Operation and Maintenance Manual
DOC.IOM.Q.E Rev. D
Figure 6 Double-Acting Operation
Inward Stroke
Section 4: Installation
April 2019
A-port
Option:
5/2 Spool valve
Option: LMC
Ps
Pilot
valve 1
Throttle 1
B-port
Option:
Throttle 2
Rb
Ra
1. Send control signal “Close” to the Control Module.
2. Pilot valve 1 will be deactivated and the 5/2 spool valve will pressurize the end cap
air chambers.
3. The piston will move inwards to the “Closed” position.
4. The Control Module indicates the “Closed” position and activates feedback
signal “Closed”.
Optional Controls:
LMC Local Manual Control
SC Speed Control throttles
Important
In case of an electric control signal failure, the actuator will move to its "Closed" position.
Installation
13
Section 4: Installation
April 2019
Installation, Operation and Maintenance Manual
DOC.IOM.Q.E Rev. D
4.3.4 Double-Acting Operation with Fail-In-Last Position Function
The operating principle, as explained here, is applicable for actuators with assembly code
CW (direct acting).
• The outward stroke will move the valve to the “Open” position.
• The inward stroke will move the valve to the “Closed” position.
• For assembly codes CC the operating principle is reversed (reverse acting):
Figure 7 Double-Acting Operation with Fail-In-Last Position Function
Outward Stroke
B-port
Option:
Throttle 2
Pilot valve 2
Option:
LMC 2
Rb
Ra
Ps
Option: LMC 1
Pilot valve 1
A-port
Option:
Throttle 1
5/2 Spool valve
1. Send control signal “Open” to the Control Module to activate Pilot valve 1 and
de-activate Pilot valve 2.
2. The 5/2 spool valve will pressurize the central air chamber.
3. The piston will move outwards to the “Open” position.
4. The Control Module indicates the “Open” position and activates feedback
signal “Open”.
14
Installation
Installation, Operation and Maintenance Manual
DOC.IOM.Q.E Rev. D
Figure 8 Double-Acting Operation with Fail-In-Last Position Function
Inward Stroke
Section 4: Installation
April 2019
A-port
Option:
Throttle 1
5/2 Spool valve
Option: LMC 1Option: LMC 2
Ps
Pilot valve 1
B-port
Option:
Throttle 2
Pilot valve 2
Rb
Ra
1. Send control signal “Close” to the Control Module to activate Pilot valve 2 and
de-activate Pilot valve 1.
2. The 5/2 spool valve will pressurize the end cap air chambers.
3. The piston will move inwards to the “Closed” position.
4. The Control Module indicates the “Closed” position and activates feedback
signal “Closed”.
Optional Controls:
LMC Local Manual Control
SC Speed Control throttles
Installation
15
Section 4: Installation
Installation, Operation and Maintenance Manual
April 2019
4.3.5 Spring-Return Actuators
The operating principle, as explained here, is applicable for actuators with assembly code
CW (direct acting).
• Applying supply pressure to port A will move the pistons outwards to the "Open"
position of the valve.
• Venting the supply pressure from port A will cause the springs to move the pistons
inwards to the "Close" position of the valve.
• For assembly codes CC, the operating principle is reversed (reverse acting):
Figure 9 Single-Acting Operation
Outward Stoke
DOC.IOM.Q.E Rev. D
A-port
Option: Throttle 1
3/2 Spool valve
Option: LMC
Ps
Pilot
valve 1
B-port
Ra
1. Send control signal “Open” to the Control Module.
2. Pilot valve 1 will be activated and the 3/2 spool valve will pressurize the central
air chamber.
3. The piston will move outwards to the “Open” position.
4. The Control Module indicates the “Open” position and activates feedback
signal “Open”.
16
Installation
Installation, Operation and Maintenance Manual
DOC.IOM.Q.E Rev. D
Figure 10 Single-Acting Operation
Inward Stroke
Section 4: Installation
April 2019
A-port
Option: Throttle 1
3/2 Spool valve
Option: LMC
Ps
Pilot
valve 1
B-port
Ra
1. Send control signal “Close” to the Control Module.
2. Pilot valve 1 will be deactivated and the 3/2 spool valve will vent the central
air chamber
3. The springs will move the pistons inwards to the “Closed” position.
4. The Control Module indicates the “Closed” position and activates feedback
signal “Closed”.
Optional Controls:
LMC Local Manual Control
SC Speed Control throttles
Installation
17
Section 4: Installation
April 2019
4.3.6 Position Feedback
The FieldQ Series actuator (1) has a patented, contact-less position sensing system.
This system consists of a position probe (2) which is rides on a special curve (4) in the
pinion bottom.
The curve is shaped in such a way that the position probe moves linearly and proportionally
to the rotation of the actuator pinion.
The linear movement of the position probe is used, inside the control module (3) to
operated the limit switches.
CAUTION
Do not put the Control module in direct contact with magnetic material. This can cause
damage or malfunction of the position feedback.
Installation of the FieldQ Series Control Modules
Installation, Operation and Maintenance Manual
DOC.IOM.Q.E Rev. D
Please refer to the Installation guides, as shipped with the product, for installation
instructions of the Control Module.
Installation Guides - Control modules
Each Control Module is shipped with an Installation Guide, which contains more
information on the pneumatic and electrical installation and operation of the Module.
Additionally, these Installation Guides can be downloaded from: www.emerson.com/eldq
Figure 11
1
3
2
4
18
Installation
Loading...
+ 50 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.