Bettis Installation Instructions: Switch Adjustment: QC41, QC42 QC43 | Bettis Manuals & Guides

Switch Adjustment Instruction QC41, QC42 and QC43 Module Q-series
DOC.SAI.QC4X.EN Rev. 0 July 2015
Setting the switch points from factory settings to a more accurate setting.
• Use these instructions when a more accurate setting of the switch points is required after receiving the module from the manufacturing site.
Factory setting of switch points
±15°
±15°
90°
To more accurate setting of switch points
90°
±4°
±4°
• Make pneumatic and electrical connections before adjusting the limit switch setting. See chapter 3 and 4 of QC40 Installa­tion guide.
4
H
E
W
N
N
E
E
N
N
I
P
N
R
G
A
E
O
!
W
R
-
-
T
G
O
I
Z
N
E
O
D
1
15
11
12
D
Shield screw: Cross slotted Phillips
nr. PH2
• Remove main round cover (15) and loosen the screw (11) of the shield (12) and turn the shield down.
2
Closed Position:
• Move the actuator/valve assembly to the closed position.
Close
3
Closed Position:
• Turn top screw (10) counter clock wise (do not force the adjust-
• For normal double acting or spring return modules, remove the control signal from pilot valve terminal 8 and 9.
• In case of a double acting “Fail-in-Last-Position” module, apply a control signal to terminal 11 and 12 and remove the control signal from terminal 8 and 9.
5 6 7
Open
10
Adjustment screws
0.6 x 3.5 or
Cross slotted Phillips nr. PH2
ment screw) until the switch trips to the “off state” (no signal)..
10
Closed Position:
• Turn top screw (10) clock wise (do not force the adjustment screw) until the switch trips to the “on state”.
• This position represents the actual, mechanical “closed” position of the valve.
Closed Position:
• Turn the screw minimal a 1/2 turn clock wise. The “closed” posi-
Preliminary Field Trial Documentation
8 9
9
tion switch point is now set.
1/2 turn
1/2 turn
10
9
Open Position:
Preliminary Field Trial Documentation
• Move the actuator/valve assembly to the open position.
• For normal double acting or spring return modules, apply the control signal to pilot valve terminal 8 and 9.
• In case of a double acting “Fail-in-Last-Position” module, remove the control signal to terminal 11 and 12 and apply the control signal to terminal 8 and 9.
H
E
W
N
N
E
E
N
N
I
P
N
R
G
A
E
O
!
W
R
-
-
T
G
O
I
Z
N
E
O
D
10
15
11
12
D
9
Adjustment screws
0.6 x 3.5 or
Cross slotted Phillips nr. PH2
Open Position:
• Turn bottom screw (9) clock wise (do not force the adjustment screw) until the switch trips to the “off state” (no signal).
CAUTION: DO NOT FORCE THE ADJUSTMENT SCREWS (9 & 10) WHEN RESISTANCE IS FELT.
During adjustment there are three situations that can damage the adjustment screw head and internal mechanisms when forcing the adjustment screws.
1. When adjustment screw (10) is rotated too much counter clock
wise.
2. When adjustment screw (9) is rotated too much clock wise.
3. When the adjustment screws (9 & 10) are rotated too much in
the direction according to their related arrows.
Situation 1 and 2 may happen in combination with situation 3.
Open Position:
• Turn bottom screw (9) counter clock wise (do not force the adjust­ment screw) until the switch trips to the “on state”.
Open Position:
• Turn the screw minimal a 1/2 turn counter clock wise.
• The “open” position switch point is now set.
• Turn the shield (12) back over the adjustment screws and fasten it with the screw (11) and mount the main round cover (15) back in place.
• This position represents the actual, mechanical “open” position of the valve.
All rights reserved. Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website www.Fieldq.com or from your nearest Valve Automation Center: America’s: +1 813 630 2255 (fax +1 630 9449) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacic: +65 626 24 515 (fax +65 626 80 028)
Copyright © 2008 Emerson Electric Co.
Important
• If the switch adjustment screws block or it is unknown what the swith point setting is, use the instructions as shown at the back of this page.
Switch Adjustment Instruction QC41, QC42 and QC43 Module Q-series
DOC.SAI.QC4X.EN Rev. 0 July 2015
Setting the switch point back to factory settings.
• If the switch adjust­ment screws block or it is unknown what the swith point setting is, use these instructions to set the switch point back to the factory set­tings. (±15° before each end of stroke), assuming a mechanical stroke of 90°±0.5° of the actuator.
• Make pneumatic and electrical connections before adjusting the limit switch setting. See chapter 3 and 4 of QC40 Installa­tion guide.
• If there is trouble with setting the Close Position, set Open
Position rst (steps 5 to 7) and set the Close Position (steps
2 to 4) after Open Position is set.
15
Factory setting of switch points
H
E
W
N
N
E
E
N
N
I
P
N
R
G
A
E
O
!
W
R
-
-
T
G
O
I
Z
N
E
O
D
D
±15°
90°
±15°
CAUTION: DO NOT FORCE THE ADJUSTMENT SCREWS WHEN RESISTANCE IS FELT.
During adjustment there are three situations that can damage the adjustment screw head and internal mechanisms when forcing the
10
adjustment screws.
1. Pivot block (2) will be blocked at bottom if screw (10) is rotated too much counter clock wise.
8
9
2. Pivot block (4) will be blocked at top if screw (9) is rotated too much clock wise.
3. Pivot blocks (2 & 4) will interfere with each other, if the adjust­ment screws (9 & 10) are rotated too much in the direction ac­cording to their related arrows.
Situation 1 and 2 may happen in combination with situation 3.
6
7
4
3
2
5
21 3 4
Close
1
15
10
11
12
H
E
W
N
N
E
E
N
N
I
P
N
R
G
A
O
T
O
N
O
D
E
!
W
R
-
-
G
I
Z
E
D
9
11
12
Shield screw: Cross slotted Phillips
nr. PH2
• Remove main round cover (15) and loosen the screw (11) of the shield (12) and turn the shield down.
Preliminary Field Trial Documentation
5
Open Position:
• Move the actuator/valve assembly to the open position.
• For normal double acting or spring return modules, apply the control signal to pilot valve terminal 8 and 9.
• In case of a double acting “Fail-in-Last-Position” module, remove the control signal to terminal 11 and 12 and apply the control signal to terminal 8 and 9.
Open
Closed Position:
• Move the actuator/valve assembly to the closed position.
• For normal double acting or spring return modules, remove the control signal from pilot valve terminal 8 and 9.
• In case of a double acting “Fail-in-Last-Position” module, apply a control signal to terminal 11 and 12 and remove the control signal from terminal 8 and 9.
6
9
Open Position:
• Turn bottom screw (9) clock wise maximum 20 turns, (do not force the adjustment screw) until the switch trips to the “on state” (no signal).
Max. 20x
10
Adjustment screws
Max. 20x
0.6 x 3.5 or
Cross slotted Phillips nr. PH2
Closed Position:
• Turn top screw (10) counter clock wise maximum 20 turns, (do not force the adjustment screw) until the switch trips to the “off state”
Preliminary Field Trial Documentation
Closed Position:
• Turn top screw (10) clock wise 1 3/4 turn (do not force the adjust-
(no signal).
7 8
9
Open Position:
• Turn bottom screw (9) counter clock wise 1 3/4 turn (do not force the adjustment screw)
• The “open” position switch point is now set to factory setting.
1 3/4 turn
• Turn the shield (12) back over the adjustment screws and fasten it
10
1 3/4
turn
ment screw). The “closed” position switch point is now set to factory setting.
H
E
W
N
N
E
E
N
N
I
P
N
R
G
A
E
O
!
W
R
-
-
T
G
O
I
Z
N
E
O
D
15
D
11
12
with the screw (11).
All rights reserved. Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website www.Fieldq.com or from your nearest Valve Automation Center: America’s: +1 813 630 2255 (fax +1 630 9449) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacic: +65 626 24 515 (fax +65 626 80 028)