Bettis Installation Guide: QC54 Foundation Fieldbus Control module | Bettis Manuals & Guides

Installation guide
DOC.IG.BQC54.1 Rev. 3
Bettis Q-Series Control Module
QC54 FOUNDATION Fieldbus™
Bettis Q-Series
October 2018
Bettis Q-Series
October 2018
Installation guide
DOC.IG.BQC54.1 Rev. 3
1 Applicable modules
QC54 - FOUNDATION Fieldbus™
- Weather Proof
- Non-incendive/Non-Sparking/FISCO ic
- Intrinsically safe/FISCO
Note:
These variations can be equipped with one or two pilot valves:
* One pilot valve is default and suitable for normal
operation of double acting or spring return actuators.
* Two pilot valves are required for Fail in Last
Position function on double acting actuators. The enclosures have a IP66 or NEMA 4X, ingress protected rating.
1
2
2 Before starting
* Actuator must be isolated both pneumatically and electrically before any (dis)assembly
is begun. * Hazards related to the control of external processes under measurement, are beyond the scope of of the content described in
this document. * Installation, adjustment, putting into service, use, assembly, disassembly and maintenance of the control module must be done by
qualified personnel. * Do not install, operate, or maintain a Q series control module without being fully trained and qualified in valve, actuator, and accessory installation, operation, and maintenance. * To avoid personal injury or property damage, it is important to carefully read, understand, and follow all of the contents of this manual, including all safety cautions and warnings. * Be sure that the actuator is correctly mounted before connecting air supply and electrical wiring (see Installation & Operation Manual Bettis Q-Series Valve Actuator, DOC.IOM.BQ.E) * Check the module label for the right execution (see figure 2.2) * Check the type of actuator: single or double acting (see figure 2.2). * For mechanical installation of the module see installation instruction leaflet DOC.QC4.MTI.1, as shipped with the module. * If you have any questions regarding these instructions, contact your Emerson sales office before proceeding as shipped with the module.
Control Module Type Label =
QC54..WP.. = FOUNDATION Fieldbus™
Weather Proof
QC54..x4..= FOUNDATION Fieldbus™ Non- incendive/Non Sparking/FISCO ic
OK
QC54..x1..= FOUNDATION Fieldbus™ intrinsically safe/FISCO
OK
Actuator Type Label =
QS xxxx = Single acting (Spring Return)
QD xxxx = Double acting
Note: x is variable based on the certification type.
Fig. 2.1 Check proper mounting before connecting air
2
Fig. 2.2 Identification
Installation guide
DOC.IG.BQC54.1 Rev. 3
Bettis Q-Series
October 2018
2.1 Mechanical alignment and mounting of the control module
The control module is equipped with an alignment­edge on top of the module. This allows easy alignment and mounting of the control module on to the actuator housing.
Procedure: (see figure 2.3)
1. First take care that both mating faces from the
actuator and control module are clean and free of dirt.
2. Check if the module has the required function
3. Remove the transparent film from the
control module.
4. Ensure seals are placed correctly.
5. Level the screws with the surface.
6. Place the alignment-edge (1) of the control
module at the top of the pneumatic interface.
7. Flip the module down taking care that the IPT
Probe (2) on the actuator fits in the mating hole on the control module and loosely place the screws.
8. Tighten screws according force in sequence.
Alignment-edge
(1)
Alignment-edge
IPT probe
(2)
Fig. 2.3 Alignment and mounting of control
module to actuator
Tightening moments
The Control Module should be fastened by using an Allen key and applying the following tightening moments:
- Allen Key No 5: 6.1 to 6.6 Nm (54 - 58.4 In.lbs)
Terminal compartment
Lockable Module cover
Fig. 2.4 Control module overview
Control Module Type Label
Option: Local Manual Control Option: Additional Local Manual
Control for “Fail in Last Position”
Option: 1 or 2 speed control throttles
3
Bettis Q-Series
October 2018
3 Pneumatic connections
Installation guide
DOC.IG.BQC54.1 Rev. 3
IMPORTANT
1 The actuator/valve combination can move
after connecting the air supply.
2 Ensure that the QC54 control modules are
mounted properly to the actuator to achieve good functioning and the required ingress protection, before connecting the air supply.
3 Check that the maximum supply pressure
P
= 8bar/116Psi
max
4 Be sure that the minimum required supply
pressure for the application is available at the actuator.
5 Take appropriate measures to prevent
condensation or moisture to entering the actuator or the control module. Condensation or moisture can damage these components and can result in failures.
6 The exhaust ports Ra and Rb on the module
(see figure 3.1) are shipped from the factory with transport protection.
* If ingress protection IP66 or NEMA 4X is
required, appropriate connections must be used in exhaust ports Ra & Rb.
3.1 Operating media :
* Air or inert gasses. * Air filtered at 5 micron. * Dew point 10 K below operating temperature. * For subzero applications take
appropriate measures.
3.2 Single acting (spring return) or Double acting actuator :
1 Remove the transport sticker from the
air supply (Ps).
2 Connect air supply to port (Ps).
Single acting
Control
Module cover
Double acting
Fig. 3.1 Pneumatic connections
Fig. 3.2 Install drip loops
OK
Ra
Ps
1/4” BSP or 1/4” NPT
Ra
Rb
Ps
1/4” BSP or 1/4” NPT
5µm
4
Installation guide
DOC.IG.BQC54.1 Rev. 3
4 Electric Connections
Bettis Q-Series
October 2018
Table 4.1 Electrical data QC54 - FF
Voltage range * 9~32V Maximum current 18 mA Reverse polarity
protection Required external protection
Environmental conditions :
Temperature *
Humidity
Altitude
Use In- and outdoor.
* The current restricted power supply meets NEC
Class 2, as described by the National Electrical Code® (ANSI/NFPA 70 (NEC®))
* In case the Control module is used in Hazardous
locations, check the chapters 10, 11 or 12 for detailed instructions.
Unit is not polarity sensitive.
Restrict the power supply current to <600mA.
-20°C to +50°C (-4°F to +122°F) 0 to 85% at 25°C(+77°F) derate to 50% above 40°C (104°F) (non-condensing). Operating full power available up to 2000 meter (6000 feet).
WARNING
!
* Do not put the Control module and the
Pneumatic module in direct contact with magnetic material. This can cause damage or malfunction of the position feedback.
* If the Control Module is used in a manner not
specified by the manufacturer, the protection provided by the equipment may be impaired.
* If required, mount earth wire (1) between top
(2) and bottom (3) ring of earth wire connection (see figure 4.1).
Fig. 4.1 Earth wire connections
5
Bettis Q-Series
October 2018
Installation guide
DOC.IG.BQC54.1 Rev. 3
4.1 Procedure
1. Remove control module cover (see figure 4.2)
2. Guide the cable(s) through the electrical
entry(ies).
- Use and mount cable glands as required by
national or local legislation.
- When IP65/NEMA4X ingress protection is
required, the electrical entries must be fitted with glands rated IP65/NEMA4X or higher.
- Apply minimum thread counts:
For NPT, at least 5 full threads For Metric, at least 8 full threads for Group A/B and 5 full threads of Group C/D
3. Connect the FOUNDATION Fieldbus™ signal
to the applicable terminals (see figure 4.3).
- For 7/8” or M12 quick connector pinout,
see figure 4.3 and 4.4.
- For hazardous area connections, see the
wiring instructions in 11.5 and 11.6.
4. Mount the function module cover to the housing
(see figure 4.2) or continue with chapter 5. Take care that the cover seal is in place to comply
to dust and water tightness according to
IP66/NEMA4X.
4.2 FOUNDATION Fieldbus installation and wiring guidelines
Please check www.fieldbus.org for various applica­tion guides like installation and wiring guidelines.
Table 4.2 Wiring dimensions
Wire type Dimensions
Cable range 0.33 to 2.5mm2 or 22 to 12 AWG
Table 4.3 Tools
Too l Dimensions
Cover lock screw Allen key 2mm Tool for terminals Screw driver 0.6 x 3.5
Terminal compartment
Lockable Module cover
Electrical entries:
3/4”NPT
or M20
1/2”NPT
or M20
Wiring Terminals
Control Module Type Label
Fig. 4.2 Installing wiring
Field wiring Actuator wiring
FF
Power supply
Fig. 4.3 Terminal connections
Quick connector pinouts:
(male chassis part)
1
3
4
3
2
1
4
2
M127/8" UNC
Button board
Blue
2 4
Brown
1
Green/Yellow
+
1 2
-
3
1
2
3
Quick connector
Terminal
Fig. 4.4 Quick connector pinouts
6