• FieldQ Series actuators must be isolated both
pneumatically and electrically before (dis)
assembly.
• It is not permitted to connect a pressure vessel
with unreduced media to the FieldQ Series
pneumatic actuator.
• FieldQ Series actuators must not be connected to
an air supply greater than 8 bar g or 120 psig
• This manual does not provide instructions for
installations in hazardous areas.
• Installation, adjustment, putting into service, use,
assembly, disassembly and maintenance of the
pneumatic actuator must be done by qualified
personnel.
A1 Orientation (see fig� A1)
The FieldQ Series actuator is an integrated concept
for the automation of quarter turn valves, dampers
or other quarter turn applications. It can consists of
three basic parts:
1. Pneumatic actuator
2. Pneumatic Module or NAMUR Plate
3. Control Module
1
A2 Installation, operation and
maintenance reference documents
Before mounting, installing, commissioning or
(dis)assembling the actuator consult the following
documents:
- All chapters of this manual and
- Installation Guide of the supplied Control Module.
- For installation in hazardous area’s:
The applicable section of the Installation Guide, as
shipped with the Control Module.
- For Control Modules with bus communication
there may be an additional Reference Manual with
more detailed information.
(available from www.emerson.com/fieldq).
A3 Operating medium
• Air or inert gasses:
- Filtered to 50 micron (5 micron for QC54).
- Check the Installation Guide as shipped with the
module for the applicable air quality.
• Maximum pressure, 8 bar g / 120 psig
• Dew point 10 K below operating temperature.
• For subzero applications take appropriate
measures.
Fig A1 Orientation
3
50µm
2
(QC54 = 5µm)
OK
Fig A2 When needed, use Filter/Regulators with correct filter
specification.
A4 Product integrity
• Assembly or disassembly is only allowed for
replacing seals and guide bands (soft parts).
1
Installation, Operation and Maintenance Manual
DOC.IOM.Q.E Rev. C
April 2017
A5 Hazardous areas
Improper installation in a hazardous area can
cause an explosion.
• Assembly, disassembly and maintenance must be
done in safe area’s without a potential explosion
hazard.
• For information about installation in a hazardous
area, refer to the appropriate sections of the
Installation Guide, as shipped with the control
module.
A6 Warning ; Moving parts
Applying pressure to the actuator or
Applying a control signal to the Control
Module, may cause the actuator/valve
assembly to operate.
A7 Prevent moisture entering the
actuator
Condensation or moisture that enters the
actuator or the Control Module can damage these
components and can result in failures. Therefore:
• Try not to mount the actuator with the conduit
openings or the air entries, pointing upward.
• Ensure integrity of gaskets and o-rings.
• Install drip loops in conduit or cable. When
needed use Filter/Regulators with correct filter
specification.
• Seal all conduit openings whether used or not.
50µm
(QC54 = 5µm)
A8 Warehouse storage
• FieldQ Series Actuators and Control Modules
should be stored in a clean, dry warehouse, free
from excessive vibration and rapid temperature
changes.
• Actuators should not be stored on any floor
surface.
A9 On site storage
• FieldQ Series Actuators and Control Modules
should be stored in a clean, dry warehouse, free
from excessive vibration and rapid temperature
changes.
• Ensure all actuator covers are in place and
securely fastened.
• Replace plastic conduit plugs with appropriate
pipe plugs.
Failure to follow proper storage guidelines will void
warranty.
A10 Lifting instructions
• Use lifting equipement as required by national or
local legislation.
Table A1 Weight of Actuators with
control modules
ACTUATOR
TYPE
Q403.94.58.69.9
Q654.55.79.912.6
Q1005.26.711.514.8
Q1506.9915.219.8
Q2007.911.217.424.7
Q35012.51927.641.9
Q60021.529.747.465.5
Q95028.540.762.889.7
Q160044.867.998.8149.7
Double
acting
Spring
Return
in kg�in Ib
Double
acting
Spring
Return
OK
Fig A3 Install drip loops and use Filter/Regulators with correct filter
specification.
• It is strongly recommended to use lifting straps to
lift the actuator/valve assembly.
• If an actuator/valve assembly should be lifted, it
is strongly recommended to connect the lifting
straps in such way that the actuator and valve is
supported.
2
April 2017
Installation, Operation and Maintenance Manual
DOC.IOM.Q.E Rev. C
1 Introduction
1�1 Orientation (see fig� 1�1)
The FieldQ Series actuator is an integrated concept for the automation of quarter turn valves, dampers or
other quarter turn applications.
Factory setting:
Rotation 90°
±0.5°
1
2
3
7
Insert according
ISO 5211 or DIN 3337
4
Fig 1.1 Introduction
1. Pneumatic actuator
2. Visual Position Indication
3. Stroke adjustment bolts
4. Control Module
3
5
8
6
5. Entries for optional manual control
6. Exhausts
7. Supply air entry
8. Entries for optional speed control
Optional insert shapes
Installation, Operation and Maintenance Manual
DOC.IOM.Q.E Rev. C
2 Installation
2�1 Before you start
In case of an air or electrical failure, it is important to know the behavior of the actuator.
Before mounting the actuator on a valve consult the following paragraph’s.
2�2 Failure modes
April 2017
2�2�1 Valve rotation
Valves are normally manufactured so that:
- the valve is closed after a clock wise rotation
(viewed from above).
closed
Fig. 2.2.1
- the valve is open after a counter clock wise
rotation (viewed from above).
open
2�2�2 Position after a failure
The position of the actuator after a failure depends on
the:
- Operating principles (see §2.3)
- Assembly code (see §2.4)
- Kind of failure
Table 2�1 Position after a failure
Principle of
operation
Double
acting
actuator
Single
acting
actuator
(Spring
Return)
Assembly
code :
CW
CC
CW
CC
Kind of
failure :
Pressurenot defined
SignalClosed
Supply voltageClosed
Pressurenot defined
SignalOpen
Supply voltageOpen
PressureClosed
SignalClosed
Supply voltageClosed
PressureOpen
SignalOpen
Supply voltageOpen
Position :
Fig. 2.2.2
Table 2�2 Position after a failure with a Double
acting module with Fail-In-LastPosition function
Principle of
operation
Double
acting
actuator
Assembly
code :
CW
CC
Kind of
failure :
Pressurenot defined
Signalnot defined
Supply voltageClosed
Pressurenot defined
Signalnot defined
Supply voltageOpen
Position :
4
April 2017
2�3 Operating principle
Installation, Operation and Maintenance Manual
DOC.IOM.Q.E Rev. C
2�3�1 Double acting actuators
IMPORTANT
The operating principle, as explained here, is
applicable for actuators with assembly code CW
(direct acting).
- The outward stroke will move the valve to the
“Open” position.
- The inward stroke will move the valve to the
“Closed” position.
For assembly codes CC the operating principle is
reversed (reverse acting):
A-port
Option:
Throttle 1
5/2 Spool valve
Option: LMC
Ps
Pilot
valve 1
B-port
Option:
Throttle 2
Rb
Ra
See paragraph 2.4 for more information about
actuator assembly codes
* Electric control signals can be connected in the
Control Module (QC; see documentation supplied
with the Control Module). The Control Module is
equipped with a pilot valve which controls a 5/2
spool valve.
* Connect air supply to air inlet (Ps).
Outward stroke
1 Send control signal “Open” to the Control
Module.
2 Pilot valve 1 will be activated and the 5/2 spool
valve will pressurize the central air chamber.
3 The piston will move outwards to the “Open”
position.
4 The Control Module indicates the “Open” position
and activates feedback signal “Open”.
Fig. 2.3.1
Ps
Fig. 2.3.2
5
5/2 Spool valve
Option: LMC
Pilot
valve 1
A-port
Option:
Throttle 1
B-port
Option:
Throttle 2
Inward stroke
1 Send control signal “Close” to the Control
Module.
2 Pilot valve 1 will be deactivated and the 5/2 spool
valve will pressurize the end cap air chambers.
3 The piston will move inwards to the “Closed”
position.
4 The Control Module indicates the “Closed”
Rb
Ra
position and activates feedback signal “Closed”.
Optional controls:
LMC Local Manual Control
SC Speed Control throttles
IMPORTANT:
In case of an electric control signal failure, the
actuator will move to its “Closed” position.
Installation, Operation and Maintenance Manual
DOC.IOM.Q.E Rev. C
April 2017
2�3�2 Double acting actuators with Fail In
Last Position function
IMPORTANT
The operating principle, as explained here, is
applicable for actuators with assembly code CW
(direct acting).
- The outward stroke will move the valve to the
“Open” position.
- The inward stroke will move the valve to the
“Closed” position.
For assembly codes CC the operating principle is
reversed (reverse acting):
B-port
Option:
Throttle 2
Option:
LMC 2
5/2 Spool valve
Option: LMC 1
A-port
Option:
Throttle 1
See paragraph 2.4 for more information about
actuator assembly codes
* Electric control signals can be connected in the
Control Module (QC; see documentation supplied
with the Control Module). The Control Module is
equipped with a pilot valve which controls a 5/2
spool valve.
* Connect air supply to air inlet (Ps).
Outward stroke
1 Send control signal “Open” to the Control Module to
activate Pilot valve 1 and de-activate Pilot valve 2.
2 The 5/2 spool valve will pressurize the central air
chamber.
3 The piston will move outwards to the “Open”
position.
4 The Control Module indicates the “Open” position
and activates feedback signal “Open”.
Ps
Pilot valve 1
Fig. 2.3.3
Ps
Pilot valve 1
Pilot valve 2
A-port
Option:
Throttle 1
5/2 Spool valve
Option: LMC 1Option: LMC 2
B-port
Option:
Throttle 2
Pilot valve 2
Rb
Ra
Inward stroke
1 Send control signal “Close” to the Control Module
to activate Pilot valve 2 and
de-activate Pilot valve 1.
2 The 5/2 spool valve will pressurize the end cap air
chambers.
3 The piston will move inwards to the “Closed”
position.
4 The Control Module indicates the “Closed”
position and activates feedback signal “Closed”.
Rb
Optional controls:
LMC Local Manual Control
SC Speed Control throttles
Ra
Fig. 2.3.4
6
April 2017
Installation, Operation and Maintenance Manual
DOC.IOM.Q.E Rev. C
2�3�2 Single acting (spring return) actuators
IMPORTANT
The operating principle, as explained here, is
applicable for actuators with assembly code CW
(direct acting).
- The outward stroke will move the valve to the
“Open” position.
- The inward stroke will move the valve to the
“Closed” position.
For assembly code CC the operating principle is
reversed (reverse acting):
A-port
Option: Throttle 1
3/2 Spool valve
Option: LMC
Ps
Pilot
valve 1
B-port
Ra
See paragraph 2.4 for more information about
actuator assembly codes
* Electric control signals can be connected in the
Control Module (QC; see documentation supplied
with the Control Module). The Control Module is
equipped with a pilot valve controls a 3/2 spool
valve.
* Connect air supply to air inlet (Ps).
Outward stroke
1 Send control signal “Open” to the Control Module.
2 Pilot valve 1 will be activated and the 3/2 spool
valve will pressurize the central air chamber.
3 The piston will move outwards to the “Open”
position
4 The Control Module indicates the “Open” position
and activates feedback signal “Open”.
Inward stroke
Fig. 2.3.5
Ps
Fig. 2.3.6
Option: Throttle 1
3/2 Spool valve
Option: LMC
Pilot
valve 1
A-port
B-port
1 Send control signal “Close” to the Control Module.
2 Pilot valve 1 will be deactivated and the 3/2 spool
valve will vent the central air chamber
3 The springs will move the pistons inwards to the
“Closed” position
4 The Control Module indicates the “Closed”
position and activates feedback signal “Closed”.
Optional controls:
Ra
LMC Local Manual Control
SC Speed Control throttles
7
Installation, Operation and Maintenance Manual
3
1
2
4
DOC.IOM.Q.E Rev. C
April 2017
2�3�3 Position feedback
FieldQ Series patented, position sensing system
The FieldQ Series actuator (1) has a patented,
contactless position sensing system. This system
consists of a position probe (2) which is rides on a
special curve (4) in the pinion bottom.
The curve is shaped in such a way that the position
probe moves linearly and proportionally to the
rotation of the actuator pinion.
The linear movement of the position probe is used,
inside the control module (3) to operated the limit
switches.
WARNING:
Do not put the Control module in direct contact
with magnetic material. This can cause damage or
malfunction of the position feedback.
Installation of the FieldQ Series modules
For installation instructions of the modules see
chapter 4.
Installation Guides - Control modules
Each Control Module is shipped with an Installation
Guide, which contains more information on the
Fig. 2.3.5
pneumatic and electrical installation and operation
of the Module. Additionally, these Installation Guides
can be downloaded from.emerson.com/fieldq
Visual indicator mounted:
(= for Cross line position indication)
CC
I
CC
C
A = Pilot valve operated in Control Module - Central air chamber (1) pressurized
B = Pilot valve not operated in Control Module - End cap air chambers (2) pressurized
All views are from above. Pistons are shown in inner position
9
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.