Installation Instruction
DOC.QC4.MC.1 Rev. A February 2012
FieldQ XP Control Modules
For commissioning, emergency or maintenance purposes, the FieldQ can be supplied with one or two Manual Con­trol options. These can operate the pilot valve(s) inside the module and as such operate the actuator, when there is air pressure available, but no control signal or power supply.
1 Mounting Manual Control
1 To add a Manual Control, remove the plug(s) in front of
the module and turn in the Manual Control.
- For normal operation the module should be tted with one Manual Control.
- For Double Acting with a Fail-in-Last-Position function, two Manual Control can be tted.
2 Manual Control operation
1 The Manual Control has a “Push & Lock” function:
- To operate the Manual Control, use a screw driver, push to activate and release to de-activate the pilot valves.
- If required turn it 45°, to lock it in position and keep the actuator in its operated state.
2 In case of a Fail in Last Position conguration with two
manual controls:
- The manual control on the right side (default location) will pressurize the central air chamber and cause the actuator to rotate counter clock wise. For reverse act­ing FieldQ actuators (Assembly code CC) the actuator will rotate clock wise.
- The manual control on the left side (Location for 2nd Manual Control) will pressurize the end cap air cham­bers and cause the actuator to rotate clock wise. For reverse acting FieldQ actuators (Assembly code CC) the actuator will rotate counter clock wise.
- In order to operate one of the manual control, be sure the opposite manual control is de-activated and un­locked.
3 It is possible to rotate the screw multiple cycles. The unit
will than toggle every 90° between “locked” (1) and “un­locked” (0).
Manual Control option
O-ring seal
Manual control
Nut cover
Lock
45°
Unlock
Off
On
Figure 1 Local Manual Control option
Location for 2nd Manual Control
Default location of Manual Control