Bettis Bettis RPE-Series SIL Manual Manuals & Guides

Page 1
Bettis RPE-Series
SIL Safety Manual
SIL Safety Manual
DOC.SILM.BE.EN Rev. 1
March 2019
Page 2
Page 3
SIL Safety Manual
DOC.SILM.BE.EN Rev. 1
Table of Contents
Section 1: Introduction
Section 2: Functional Specification
Section 3: Configuration of the Product
Section 4: Service Condition Limitations (Limitation of Use)
Section 5: Expected Lifetime
Section 6: Failure Modes and Estimated Failure Rates
Table of Contents
Section 7: Installation and Site Acceptance Procedure
Section 8: Periodic Test and Maintenance Requirements
8.1 General ........................................................................................................................................9
8.2 Full-Stroke Test ..........................................................................................................................9
8.3 Partial-Stroke Test ................................................................................................................. 12
8.4 Proof Test and Periodic Maintenance ............................................................................ 15
Section 9: Architectural Constraints
Section 10: Common Cause Factors
Section 11: Mean Repair Time
Section 12: Systematic Capability
ITable of Contents
Page 4
Section 1: Introduction
Section 1: Introduction
Purpose of this Safety Manual, written in compliance with IEC 61508-2, Annex D, is to give all the necessary information to the system integrator for a correct use of the product in Safety Instrumented Systems for SIL classied applications.
SIL Safety Manual
DOC.SILM.BE.EN Rev. 1
1
Introduction
Page 5
SIL Safety Manual
DOC.SILM.BE.EN Rev. 1
Section 2: Functional Specification
Section 2: Functional Specication
The safety function for Bettis RPE-Series pneumatic actuator is dened as follows:
Double-Acting Scenario:
a. When an unsafe condition is detected in a plant by a process sensor, the
controller, via actuator control system, drives the Actuator to close the shut-down valve, depressurizing (if under pressure) the Opening side of the actuator and pressurizing the Closing side of the actuator.
b. When an unsafe condition is detected in a plant by a process sensor, the
controller, via actuator control system drives the Actuator to open the blow-down valve, depressurizing (if under pressure ) the Closing side of the pneumatic actuator and pressurizing the Opening side of the pneumatic actuator.
Single-Acting Scenario:
a. When an unsafe condition is detected in a plant by a process sensor, the
controller, via actuator control system drives the Actuator to rotate with sucient torque to move a valve to its fail-safe state when hold-position air pressure is released.
The Bettis brand Actuator Selection Procedure provides functional denition with specics on input variables and performance.
In any case, the choice of the safety function to be implemented is responsibility of the system integrator.
Functional Specification
2
Page 6
Section 3: Configuration of the product
SIL Safety Manual
DOC.SILM.BE.EN Rev. 1
Section 3: Conguration of the Product
The Bettis RPE-Series are pneumatically operated actuators designed to operate Ball / Plug / Buttery valves, automation of louvers and dampers & automation of any quarter-turn mechanism. Both the double-acting and single-acting (spring-return) versions of the Bettis RPE-Series pneumatic actuators are designed in such a way that there are no moving parts on the outside (with the exception of the position indicator). This makes them safe, easy to install and virtually maintenance free.
For further details about actuator congurations, please refer to the Bettis RPE-Series product data sheets, Safety guide and Installation, Operation and Maintenance manual.
3
Configuration of the product
Page 7
SIL Safety Manual
AB
A
B
A
B
A
B
Pistons Pistons
Pinion
DOC.SILM.BE.EN Rev. 1
Section 4: Service Condition Limitations (Limitation of Use)
Section 4: Service Condition Limitations
(Limitation of Use)
The operating capabilities are listed below:
Maximum Operating Pressure:
Pneumatic Service
Up to 120 psig (8.3 barg)
Ambient Temperature:
Temperature extremes require dierent solutions to maintain actuator operational integrity and reliability. For each Bettis RPE-Series actuator is available in three dierent temperature executions.
-20°C to +80°C (-4°F to +176°F) Standard temperature
-10°C to +120°C (+14°F to +250°F) High Temperature
-40°C to +80°C (-40°F to +176°F) Low Temperature
Torque Output Range:
Double-Acting Bettis RPE-Series actuators, requiring pressure to rotate in
either direction, are available with a torque range between 4.8 Nm (44 lbf.in) and 6,490 Nm (59000 lbf.in)
The Bettis RPE-Series spring-return models require pressure in only one
direction of travel and are suitable for air-fail close and air-fail to open applications without modication. These models are available with a spring end torque between 2 Nm (20 lbf.in) and 2394 Nm (21000 lbf.in)
Safety Function:
For spring-return models, the safety function is self-evident performed by the springs. The safety function of double-acting models should be performed by the A-chamber for safety related systems.
Figure 1 Use the A-Chamber for Safety Related Systems on Double-Acting Actuators
Assembly Code: CW Assembly Code: CC
= Safety Function is = Safety Function is Counterclockwise Rotation Clockwise Rotation
Service Condition Limitations (Limitation of Use)
4
Page 8
Section 4: Service Condition Limitations (Limitation of Use)
Use of manual override:
The use of a manual override is not recommended in a SIL classied application, as it results in a bypass of the safety function. In case the manual override is used, the following requirements must be fullled, or the Functional Safety Certication will become invalid:
The manual override shall be protected to prevent unauthorized use.
(e.g. by key locks in conjunction with eective management controls.).
The users authorized to operate on the actuator shall be skilled personnel;
The maximum duration of the manual override shall be dened.
If necessary, compensatory measures to allow the safe operation of the
process shall be dened (responsibility of the nal user).
When test or bypass facilities are included in the SIS (safety integrated system),
they shall conform with the following:
The SIS shall be designed in accordance with the maintenance and testing
requirements dened in the SRS (safety requirement specication).
The operator shall be alerted to the bypass of any portion of the SIS via an
alarm or operating procedure.
Before selecting remote operating mode control of actuator, the manual override must be disengaged according to the relevant Installation, Operation and Maintenance Manual.
SIL Safety Manual
DOC.SILM.BE.EN Rev. 1
The position selected (remote/automatic control or local /manual control) can be achieved with a specic technical solution that does not allow to reach an intermediate position lever’s and avoids unintentional activation.
The engagement of the manual override shall be signaled, at least locally, according to IOM. As optional request from nal user, to determine if the manual override is engaged, an electrical signal using contact switching can be provided to communicate the status to the control room.
Loss of utility:
For double acting congurations that on loss of utility (e.g., electrical power, or pneumatic supply) does not fail to the safe state a system for detecting and alarming of loss of utility and SIS circuit integrity shall be implemented. (e.g., end­of-line monitoring, supply pressure measurement), and action taken according to par. 11.3 of IEC. 61511-1.
5
Service Condition Limitations (Limitation of Use)
Page 9
SIL Safety Manual
DOC.SILM.BE.EN Rev. 1
Section 5: Expected Lifetime
Actuator lifetime (for which failure rates indicated in Section 6 are ensured) strongly depends on operating conditions.
For normal service conditions, Bettis RPE-Series actuators can be in good conditions also after more than 10 years with planned minimum maintenance. Normal working life is
500.000 cycles. Bettis RPE-Series carry a warranty period of:
18 months after delivery if properly stored in conditions that we declare or
12 months after installation on site.
Section 5: Expected Lifetime
Expected Lifetime
6
Page 10
Section 6: Failure Modes and Estimated Failure Rates
SIL Safety Manual
DOC.SILM.BE.EN Rev. 1
Section 6: Failure Modes and Estimated
Failure Rates
Table 1. Failure Modes and Estimated Failure Rates – Bettis RPE-Series Actuator
Configuration Safety Function λDU [1/h] λDD [1/h] λS [1/h]
RPE- No PST 1
RPE - With PST 1
NOTE:
No internal diagnostics is included in the product.
The above failure rates are guaranteed:
- For the service conditions listed in Section 4.
- For the expected lifetime declared in Section 5.
- Considering the periodic test and maintenance included in Section 8.
The failure rates are determined performing a FMEDA based on the failure rates of components taken from industrial databases (NPRD-2016/FMD97/2016, EXIDA E&MCRH and NSWC-2011), integrated with eld feedback using the Bayesian statistical approach mentioned in IEC 61508-2 Par. 7.4.4.3.3.
The system for reporting failures is based on eld feedback from end users, with:
- Identication of the claim/failure
- Root cause analysis to identify cause and responsibility of the failure
- Identication of the possible eect of the failure on the Safety Function
- Classication of the failure considering the failure categories of IEC 61508-2
(Safe, Dangerous, No Eect) Customer Service, Quality and Technical Department are responsible for the procedure, according to the respective role.
2,55E-08 0,00E+00 0,00E+00 2,29E-09 2,.32E-08 0,00E+00
7
Failure Modes and Estimated Failure Rates
Page 11
SIL Safety Manual
DOC.SILM.BE.EN Rev. 1
Section 7: Installation and Site Acceptance Procedure
Section 7: Installation and Site
Acceptance Procedure
Any necessary installation and site acceptance procedures are discussed in the Bettis RPE-Series actuators Installation, Operation and Maintenance manual. The Installation, Operation and Maintenance manual denes exercising of the actuator after installation and denes testing after maintenance.
Installation and Site Acceptance Procedure
8
Page 12
Section 8: Periodic Test and Maintenance Requirements
Section 8: Periodic Test and
Maintenance Requirements
8.1 General
Please consider that the information in this paragraph are relevant only in regards of Reliability Tests; please refer to the Installation, Operation and Maintenance manual for detailed information about product maintenance, handling and storage. Diagnostic tests may be made to increase the system reliability (Full-Stroke or Partial-Stroke Test). “On site” tests depend on Project/Plant facilities requirements; however, a functional test must be executed on site, prior actuator operation.
8.2 Full-Stroke Test
SIL Safety Manual
DOC.SILM.BE.EN Rev. 1
The “Full Stroke Test” (“On-line”) must be performed to satisfy the PFD (average probability of failure on demand) value.
The full test frequencies will be dened by the nal integrator in relation to the dened PFD
to be achieved.
AVG
Procedure:
Operate the Actuator/Valve assembly for 2 complete open/close cycles
with complete closing of the valve.
Verify the Correct performing of open – close manoeuvre and within the
required operating times (eg. check locally, or automatically via Logic solver, the correct movement of the actuator/valve).
Compare the results with the ones stored during SAT
(site acceptance test) activities.
Record the test results in your company’s SIF
(safety instrumented function) database.
Restore normal operation.
Considering the application of the above described Full Stroke Test procedure, the “Test Coverage”, in case of automatic procedure, can be considered > 99%.
In case of manual procedure the “Test Coverage” shall take into account also the test imperfection and the reliability/competence of the operator.
AVG
9
Periodic Test and Maintenance Requirements
Page 13
SIL Safety Manual
DOC.SILM.BE.EN Rev. 1
Section 8: Periodic Test and Maintenance Requirements
NOTE:
If the test is automatic, then the Test Coverage is PTC (proof test coverage), but can
also considered as DC (diagnostic coverage).
If the test is manual, then the Test Coverage is PTC, but cannot be considered as DC.
The procedure can be performed manually or automatically. In the following, for both cases, the following points are listed:
Parameters to be measured
Instruments to be used
Failure modes detected
Diagnostic Coverage/Proof Test Coverage
Parameters to be measured: The following parameters have to be measured for an eective Full Stroke Test:
Angular position of the shaft;
Time necessary to reach to nal position;
Output torque (as indirect measure, by means of the of pressure measurement in the
cylinder chamber)
NOTE:
Not all parameters are needed, but the following combinations can be used:
1. Measurement of angular position as function of time
(pressure measurement is optional)
2. Measurement of cylinder chamber pressure as function of time
3. Verication of nal position achievement in the established maximum time.
Periodic Test and Maintenance Requirements
10
Page 14
Section 8: Periodic Test and Maintenance Requirements
Table 2. Instruments/equipment to be used for the test
SIL Safety Manual
DOC.SILM.BE.EN Rev. 1
Quantity
Angular position of the shaft
Time necessary to reach the nal position
Output torque (Pressure in the cylinder)
Instruments/equipment
Automatic Procedure Manual Procedure
Case A
Use of a Logic Solver:
1. Limit switches box, or 4÷20 mA position transmitter
2. Digital Input Module / Analog Input Module included in the Logic Solver
3. Application Software function (to compare the actual trend with the one stored during SAT ) Case B Use of a Partial stroke testing device:
1. Limit switches box, or 4÷20 mA position transmitter
2. Partial stroke testing device with integrated Software function
As above
Case A Use of a Logic Solver:
1. Pressure transmitter connected to the cylinder chamber
2. Analog Input Module included in the Logic Solver
3. Application Software function (to compare the actual trend with the one stored during SAT ) Case B Use of a Partial stroke testing device:
1. Pressure transmitter connected to the cylinder chamber
2. Partial stroke testing device with inte­grate Software function
1. Limit switches box, and/or visual indication
2. Skilled and trained personnel
1. Limit switches box, and/or visual indication
2. Chronometer
3. Skilled and trained personnel
Skilled and trained personnel (to check audible partial sticking)
11
Table 3. Failure mode detectable by the test
Component
Automatic Procedure Manual Procedure
Detectable failure modes
Housing Breakage End cap Breakage
Piston
Rack
Pinion
Spring
Stroke adjustment
Breakage Sticking
Breakage Binding
Breakage Binding
Breakage Weakened
Breakage Bended
As per automatic procedure
Periodic Test and Maintenance Requirements
Page 15
SIL Safety Manual
DOC.SILM.BE.EN Rev. 1
Section 8: Periodic Test and Maintenance Requirements
NOTE:
The ones listed above are the major failure modes of the main components
In case of manual procedure, the detectable failure modes are the same as per
automatic procedure. The test coverage is lower than the one for automatic mode, due to the human factor.
The manual procedure cannot be considered as diagnostic.
8.3 Partial-Stroke Test
The “Partial Stroke Test” (“On-line”) can be performed to improve the PFD
AVG
value.
For the execution of a partial stoke test the actuator performs a partial open-close cycle operation, typically a 15-25 degrees rotation of the valve, in order to check the correct functioning of the actuator and the correct movement of the valve (not sticking and able to move).
The “Partial Stroke Test” (“On line”) can be performed to satisfy PFD
(average probability
AVG
of failure on demand) value.
Recommended Test Interval = 1 to 3 months.
Procedure:
Operate the actuator to perform N°2 partial open/close cycles, to verify
the correct functioning of the actuator/valve assembly;
Verify that the partial stroke manoeuvre was performed correctly and
within the expected time;
Verify the Correct performing of partial stroke operation and within the
expected time; (eg. check locally, or automatically via Logic solver, or via the Partial stroke testing system the correct movement of the actuator/ valve assembly)
Inspect the actuator components for any leakages (internal and external).
The procedure can be performed manually or automatically. In the following, for
both cases, the following points are listed:
Parameters to be measured
Instruments to be used
Failure modes detected
Diagnostic Coverage/Proof Test Coverage
The above parameters to check will depend from the partial stroke test system available. Considering the application of the above described Partial Stroke Test procedure, the “Diagnostic Coverage” is >90 %. In case of manual procedure the “Test Coverage” shall take into account also the test imperfection and the reliability/competence of the operator.
Periodic Test and Maintenance Requirements
12
Page 16
Section 8: Periodic Test and Maintenance Requirements
NOTE:
If the test is automatic, then the Test Coverage can also considered as DC.
If the test is manual, then the Test Coverage cannot be considered as DC.
Parameters to be measured: The following parameters have to be measured for an eective Partial Stroke Test:
Angular position of the shaft;
Time necessary to reach to nal position;
Output torque (as indirect measure, by means of the of pressure measurement in the
cylinder chamber)
NOTE:
Not all parameters are needed, but the following combinations can be used:
1. Measurement of angular position as function of time
(pressure measurement is optional).
2. Measurement of cylinder chamber pressure as function of time.
3. Verication of nal position achievement in the established maximum time.
The parameters to be measured depend upon the partial stroke test system available. Instruments / equipment to be used for the test:
The Partial Stroke Test can be executed in the following way:
1. Using commercial Partial stroke testing device, measuring/verifying:
a. Measurement of angular position as function of time. b. Measurement of cylinder chamber pressure as function of time (optional). c. Verication of nal position achievement in the established maximum time.
2. By means of Logic Solver, measuring/verifying:
a. Measurement of angular position as function of time. b. Measurement of cylinder chamber pressure as function of time (optional). c. Verication of nal position achievement in the established maximum time.
SIL Safety Manual
DOC.SILM.BE.EN Rev. 1
13
Periodic Test and Maintenance Requirements
Page 17
SIL Safety Manual
DOC.SILM.BE.EN Rev. 1
Section 8: Periodic Test and Maintenance Requirements
Table 4. Instruments/equipment to be used for the test
Quantity
Angular position of the shaft
Time necessary to reach the nal position
Output torque (Pressure in the cylinder)
Instruments/equipment
Automatic Procedure Manual Procedure
Case A
Use of a Logic Solver:
1. Limit switches box, or 4÷20 mA position transmitter
2. Digital Input Module / Analog Input Module included in the Logic Solver
3. Application Software function (to compare the actual trend with the one stored during SAT ) Case B Use of a Partial stroke testing device:
1. Limit switches box, or 4÷20 mA position transmitter
2. Partial stroke testing device with integrated Software function
As above
Case A Use of a Logic Solver:
1. Pressure transmitter connected to the cylinder chamber
2. Analog Input Module included in the Logic Solver
3. Application Software function (to compare the actual trend with the one stored during SAT ) Case B Use of a Partial stroke testing device:
1. Pressure transmitter connected to the cylinder chamber
2. Partial stroke testing device with inte­grate Software function
1. Limit switches box, and/or visual indication
2. Skilled and trained personnel
1. Limit switches box, and/or visual indication
2. Chronometer
3. Skilled and trained personnel
Skilled and trained personnel (to check audible partial sticking)
Table 5. Failure mode detectable by the test
Component
Housing Breakage End cap Breakage
Piston
Rack
Pinion
Spring
Stroke adjustment
Periodic Test and Maintenance Requirements
Detectable failure modes
Automatic Procedure Manual Procedure
Breakage Sticking
Breakage Binding
Breakage
As per automatic procedure
Binding Breakage
Weakened Breakage
Bended
14
Page 18
Section 8: Periodic Test and Maintenance Requirements
NOTE:
The ones listed above are the major failure modes of the main components
In case of manual procedure, the detectable failure modes are the same as per
automatic procedure. The test coverage is lower than the one for automatic mode, due to the human factor.
The manual procedure cannot be considered as diagnostic. The test can be
considered as “non-perfect Proof Test”, and can be considered in the estimation of PFD
, while it is not considered for the estimation of the SFF (safe failure fraction).
AVG
8.4 Proof Test and Periodic Maintenance
We advise to perform the following checks upon each proof test interval complying with the rules and regulations of the country of nal installation:
Visually check the entire valve operating system.
Ensure there are no leaks on the pressurized parts.
SIL Safety Manual
DOC.SILM.BE.EN Rev. 1
Check pneumatic connections for leaks. Tighten tube ttings as required.
Check if manual override (where foreseen) is regular.
Check if pneumatic lter cartridge (where foreseen) is sound and lter bowl (where
foreseen) has been cleaned properly.
Check the setting of the relief valves (where foreseen).
Verify that the power uid supply pressure value is within the required range.
Remove built-up dust and dirt from all actuator surfaces.
Inspect actuator paint work for damages to ensure continued corrosion
protection. Touch-up as required in accordance with the applicable paint specication.
Operate the Actuator/Valve assembly for 2 open/close complete cycles with
complete closing of the valve.
Verify the correct performing of open – close operations (for example, check
locally, or automatically via Logic solver, the correct movement of the actuator).
The Installation, Operation and Maintenance manual denes a minimum maintenance interval after 500.000 cycles for the Bettis RPE-series actuators. This addresses components that may have age related degradation. When the maintenance interval has elapsed a complete overhaul of the actuator is required.
15
Periodic Test and Maintenance Requirements
Page 19
SIL Safety Manual
DOC.SILM.BE.EN Rev. 1
Section 9: Architectural Contraints
Section 9: Architectural Constraints
For the evaluation of the conformity to the requirement of Hardware safety integrity architectural constraints of the standard IEC 61508, both Route 1H and Route 2H are used.
Route 1H
• The product has a single channel conguration, HFT (hardware fault tolerance)=0
• Safe failure rate λS:
Single Acting Actuators: According to IEC 65108 denitions (in particular
denitions 3.6.8 and 3.6.13 of IEC 61508-4), no Safe Failures are possible in a Single Acting actuator. Each failure mode of the actuator itself shall be classied as “Dangerous” or “No Eect” (failures which can generate the spurious operation of the safety function are only external to the actuator itself, or are related to components that “plays no part in implementing the safety function”, e.g. components of the pneumatic cylinder. Therefore, according to denition 3.6.13 of IEC 61508- 4, they cannot be used for the calculation of the SFF. Hence λS=0 for each type of single acting actuator.
Double Acting Actuators: According to IEC 65108 denitions (in particular
denitions 3.6.8 and 3.6.13 of IEC 61508-4), no Safe Failures are possible in a Double Acting actuator. Each failure mode of the actuator itself shall be classied as “Dangerous” or “No Eect” (failures which can generate the spurious operation of the safety function are only external to the actuator itself, and in the case of loss of power supply the actuator “stays put”). Therefore, according to denition 3.6.13 of IEC 61508- 4, they cannot be used for the calculation of the SFF. Hence λS=0 for each type of Double Acting actuator.
For this reason, according to denition 3.6.15 of IEC 61508-4, we have:
SFF=0 without external diagnostic tests;
SFF>0 with external diagnostic tests, carried out according to denition 3.8.7 of IEC
61508-4, and according to what written in Section 6 above (see the same paragraph for the SFF / DC reachable).
Route 2
The application of Route 2H (“eld feedback”) is assessed.
As the product is classied as “Type A”, no requirements for SFF are
In conclusion:
The product can be used in single channel conguration up to:
SIL 2 without external diagnostic tests
SIL 3 considering external diagnostic tests
H
given for Route 2H.
Architectural Constraints
16
Page 20
Section 10: Common Cause Factors
Section 10: Common Cause Factors
The product has a single channel conguration, HFT=0.
SIL Safety Manual
DOC.SILM.BE.EN Rev. 1
The β factors can be used when performing PFD architectures.
The Common Cause factors, relevant when the product is used in redundant conguration, are: β=βD=0,05
NOTE:
The above value is the value for 1oo2 architecture. The values for other architectures
shall be calculated according to IEC 61508 Part 6, Table D.5.
The above value is calculated in the hypothesis of redundancy without diversity.
calculations for redundant
AVG
17
Common Cause Factors
Page 21
SIL Safety Manual
DOC.SILM.BE.EN Rev. 1
Section 11: Mean Repair Time
The Mean Repair Time of the device is 1 hour.
NOTICE
The Mean Repair Time is estimated considering availability of skilled personnel for maintenance, spare parts and adequate tools and materials on site (that is, it encompasses the eective time to repair and the time before the component is put back into operation).
Procedures to repair or replace the Bettis RPE-Series actuators are provided in the respective Installation, Operation and Maintenance manual. Please refer to the Installation, Operation and Maintenance manual for any tools required for repair and replacement and required competency of technicians. Maintenance and subsequent test procedures are also covered in the Installation, Operation and Maintenance manual. Any failures, identied by the end-user during maintenance, repair or proof testing, that potentially impact the functional safety of the Bettis RPE-Series actuators should be reported back to Actuation Technologies Customer Service Coordinator.
Section 11: Mean Repair Time
Mean Repair Time
18
Page 22
Section 12: Systematic Capability
Section 12: Systematic Capability
The systematic capability of the device is 3.
This systematic capability is guaranteed only if the user:
1. Use the device according to the instructions for use and to the present Manual.
2. Use the device in the appropriate environment (limitation of use).
SIL Safety Manual
DOC.SILM.BE.EN Rev. 1
19
Systematic Capability
Page 23
Page 24
World Area Configuration Centers (WACC) offer sales support, service, inventory and commissioning to our global customers. Choose the WACC or sales office nearest you:
NORTH & SOUTH AMERICA
19200 Northwest Freeway Houston TX 77065 USA T +1 281 477 4100
Av. Hollingsworth 325 Iporanga Sorocaba SP 18087-105 Brazil
MIDDLE EAST & AFRICA
P. O. Box 17033 Jebel Ali Free Zone Dubai T +971 4 811 8100
P. O. Box 10305 Jubail 31961 Saudi Arabia T +966 3 340 8650
T +55 15 3413 8888
24 Angus Crescent
ASIA PACIFIC
Longmeadow Business Estate East
P.O. Box 6908 Greenstone No. 9 Gul Road #01-02 Singapore 629361 T +65 6777 8211
No. 1 Lai Yuan Road
1616 Modderfontein Extension 5
South Africa
T +27 11 451 3700
EUROPE
Wuqing Development Area Tianjin 301700 P. R. China T +86 22 8212 3300
Holland Fasor 6
Székesfehérvár 8000
Hungary
T +36 22 53 09 50
Strada Biffi 165
29017 Fiorenzuola d’Arda (PC)
Italy
T +39 0523 944 411
For complete list of sales and manufacturing sites, please visit
www.emerson.com/actuationtechnologieslocations or contact us at info.actuationtechnologies@emerson.com
www.emerson.com/bettis
©2019 Emerson. All rights reserved.
The Emerson logo is a trademark and service mark of Emerson Electric Co.
TM
is a mark of one of the Emerson family of companies.
Bettis All other marks are property of their respective owners.
The contents of this publication are presented for information purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available on request. We reserve the right to modify or improve the designs or specifications of our products at any time without notice.
Loading...