Bettis Bettis RPE-Series Installation, Operation and Maintenance Manual Manuals & Guides

Installation, Operation and Maintenance Manual
Bettis RPE-Series
Rack and Pinion Pneumatic Actuators
DOC.IOM.BE.EN Rev. 9
March 2019
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
Table of Contents
Section 1: Before You Start
1.1 Installation, Operation and Maintenance Reference Documents ................... 1
1.2 Warehouse Storage ...................................................................................... 1
1.3 On-Site Storage ............................................................................................ 2
Section 2: Introduction
2.1 Identification ................................................................................................ 3
2.2 Intended Use ................................................................................................. 5
2.3 Specifications ................................................................................................ 5
Section 3: Configuration Code
Table of Contents
Section 4: Installation
4.1 Before You Start ............................................................................................9
4.2 Actuator Rotation Direction .......................................................................... 9
4.2.1 Valve Rotation .................................................................................... 9
4.2.2 Position After Failure ........................................................................ 10
4.3 Principles of Operation ................................................................................ 10
4.3.1 Solenoid Valve .................................................................................. 10
4.3.2 Ingress Protection (IP) rating ............................................................ 11
4.3.3 Double-Acting Actuators .................................................................. 12
4.3.4 Spring-Return Actuators ................................................................... 13
4.4 Actuator Assembly Codes ........................................................................... 14
4.5 Actuator to Valve Installation ...................................................................... 15
4.6 Mounting of control and feedback accessories ............................................ 18
4.7 Recommended Tubing Sizes ....................................................................... 18
Section 5: Mechanical Stroke Adjustment
5.1 Travel Stop Adjustment ............................................................................... 20
5.1.1 Double-Acting Actuators .................................................................. 20
5.1.2 Spring-Return Actuators ................................................................... 20
5.1.3 Angular Displacement ......................................................................21
Section 6: Maintenance
6.1 Normal Maintenance .................................................................................. 22
6.2 Inspection and Repair .................................................................................. 23
6.2.1 Service Kits .......................................................................................23
6.2.2 Spring-Return Actuator ....................................................................23
Table of Contents
Section 7: Decommission (Out of Service)
7.1 Before You Start ..........................................................................................24
7.2 Removing the actuator from the valve ........................................................ 25
I
Table of Contents
Section 8: Disassembly
Section 9: Reassembly
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
8.1 Removing End Caps (Sizes 25 to 600) .......................................................... 27
8.2 Removing End Caps (Sizes 950 to 4000) ...................................................... 29
8.3 Removing Spring Cartridges or Springs ....................................................... 30
8.4 Removing of Limit Stop ...............................................................................31
8.5 Removing Pistons ....................................................................................... 31
8.6 Removing Pinion .........................................................................................32
8.7 Cleaning the Components .......................................................................... 33
9.1 Grease Instructions .....................................................................................35
9.2 Reassembly of the pinion ............................................................................ 36
9.3 Reassembly of the pistons ........................................................................... 37
9.4 Reassembly and settings of the limit stops .................................................. 39
9.5 Reassembly of the end caps ........................................................................ 40
9.5.1 Double-Acting actuators .................................................................. 40
9.5.2 Spring-Return actuators ................................................................... 41
9.5.3 Spring-Return actuators - Size 950 to 4000 ...................................... 42
9.6 Basic function and Air Leak Test .................................................................. 45
Section 10: Troubleshooting
10.1 Mechanical Problems ..................................................................................46
10.2 Pneumatic Problems ...................................................................................47
10.3 Electrical Problems ...................................................................................... 48
Section 11: Parts List and Spare Parts Recommendations
11.1 Actuator sizes RPE25 to RPE600 ..................................................................49
11.2 Actuator sizes RPE950 to RPE2500 .............................................................. 50
11.3 Actuator size RPE4000 ................................................................................ 51
Appendix A: Spring Load Removal
A.1 Spring load relief ......................................................................................... 52
Appendix B: Tool & Torque Table
Appendix C: Full Stroke Adjustment Option
C.1 Full Stroke Adjustment Option .................................................................... 56
C.2 Convert a Standard Actuator into a Full Stroke Adjustment Version ............ 57
11.3.1 Procedure ........................................................................................ 58
C.3 Full Stroke Adjustment Setting .................................................................... 59
11.3.2 Factory Setting Procedure ................................................................ 59
11.3.3 Setting the Full Stroke Adjustment Screw to the Required Angle ...... 60
II
Table of Contents
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
Section 1: Before You Start
This section explains:
Base safety procedures.
Where to find detailed information relating safety.
Storage guidelines.
Installation, adjustment, putting into service, use, assembly, disassembly and maintenance of the pneumatic actuator must be performed by qualified personnel.
NOTICE
Failure to follow the above guidelines will void warranty.
WARNING
Section 1: Before You Start
Actuator must be isolated both pneumatically and electrically before any (dis)assembly starts. Before mounting or (dis)assembly, the actuator consult the relevant sections of this manual.

1.1 Installation, Operation and Maintenance Reference Documents

Before you start, read the following documents:
All chapters in this manual.
Safety Guide (Document No. DOC.SG.BE.1).
For Safety Instrumented Systems application, read the following document:
SIL Safety Manual Bettis RPE-Series (Document No. DOC.SILM.BE.EN).
NOTICE
Failure to read the Safety Guide will void the warranty.
Not following the instructions of the Safety Guide can lead to failure of the product and harm to personnel or equipment.

1.2 Warehouse Storage

All actuators should be stored in a clean, dry warehouse, free from excessive
vibration and rapid temperature changes.
All actuators should not be stored directly to the floor surface - it must be placed
in racks/shelves or use a pallet.

Before You Start

1
Section 1: Before You Start

1.3 On-Site Storage

All actuators should be stored in a clean, dry warehouse, free from excessive vibra-
tion and rapid temperature changes.
Prevent moisture or dirt from entering the actuator. Plug or seal both air connec-
tion ports.
NOTICE
Failure to follow the above guidelines (Warehouse and On Site Storages) will void warranty.
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
2
Before You Start
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
Section 2: Introduction
This section explains:
How to identify the received product.
The intended use of the product.
Construction details.
Actuator specifications.
2.1 Identification
The Bettis™ RPE-Series Rack and Pinion actuators are available as double-acting or spring-return versions. 12 models are available, ranging from 23 Nm to 4041 Nm (206 to 35765 lbf.in)nominal torque output.
The Bettis RPE-Series uses standardized interfaces for solenoid, switchbox or positioner mounting (VDI/VDE3845; NAMUR). The valve interface is equipped with an insert in the pinion bottom that allows both ISO5211 or DIN3337 mounting.
Section 2: Introduction
The springs in the spring-return version allow a fail action in case of loss of air supply pressure (Fail-to-Close or Fail-to-Open).
As from size RPED150 double-acting versions have flat end caps to reduce actuator length and internal air volume.

Introduction

3
25 ­100
150 -
600
4000
Size End cap design
5
Spring design
6
Pinion bottom / Insert design
2
950 -
2500
SR
Maximum 12
spring cartridges
Maximum 6
loose springs
Left
Right
Left Right
Left Right
DA
SR DA
SR DA
SR DA
Maximum 12
spring cartridges
Maximum 6
loose springs
Left Right
Notes
1. Top auxilliaries and Solenoid interface (VDI/VDE 3845; NAMUR) for size 25 to 4000.
2. Valve interface availalable according ISO5211 or DIN 3337. Actuator sizes 25 to 2500 can be fitted with drive inserts with various inner shapes. Actuator size 4000 is fitted with a double square; parallel and diagonal.
3. Spring-Return actuators: - with springs
4. Double-Acting actuators: - no springs
5. Actuator sizes 25 to 100 have high end caps for double-acting and spring-return models. Actuator sizes 150 to 4000 have low end caps for double-acting models and high end caps for spring return models.
6. Actuator sizes 25 to 600 are fitted with a maximum of 12 spring cartridges. Actuator sizes 950 to 4000 are fitted with a maximum of of 6 loose springs.
1
2
3 4
Section 2: Introduction
Figure 1 Identification
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
4
Introduction
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9

2.2 Intended Use

The Bettis RPE Rack and Pinion actuators are intended for the automation and operation of quarter-turn valves like Butterfly, Ball and Plug valves.
Rack and Pinion actuators can also be used to operate dampers or any other quarter-turn applications.
2.3 Specifications
Table 1. Pressure Range
Actuator Type Pressure
Double-Acting 0.2 to 8 bar (2.9 to 116 psi)
Spring-Return
Table 2. Operating Media
6 to 8 bar (87 to 116 psig), with maximum spring set 3 to 8 bar (43.5 to 116 psig), reduced spring quantity
Section 2: Introduction
Actuator Type Operating Media
Air, dry or lubricated and inert gases Dew point at least 10K below ambient temperature
Double-Acting and Single Acting
1. Recommended air quality according ISO 8573-1 for normal operation: 7-5-4.
For sub-zero applications, take appropriate measures Mentioned pressure levels are "gauge pressures".
Gauge pressure is equal to absolute pressure minus atmospheric pressure.
NOTE:
Use of filters, pressure regulators, lubricator and an oil/water separator mounted in the air supply line, will allow a smooth and durable operation of the actuator.
For lubricated supply air, it is recommended to use a non-detergent oil without aggressive additives, VG32, group 2 (ISO 3448).
Table 3. Temperature Range
Actuator Type Temperature
Standard -20°C to 80°C (-4°F to +176°F) Option: Low Temperature -40°C to +80°C (-40°F to +176°F) Option: High Temperature -10°C to +120°C (+14°F to +250°F)
Introduction
5
A
B
Section 2: Introduction
Table 4. Air Volumes and Consumption
Actuator
model
RPE 0025 0.14 0.20 0.08 0.36 0.64 1.2 0.48 0.88 1.7 RPE 0040 RPE 0065 0.40 0.56 0.22 1.02 1.8 3.4 1.3 2.4 4.7 RPE 0100 0.6 0.9 0.3 1.5 2.7 5.0 2.0 3.8 7.2 RPE 0150 1.0 0.8 0.5 2.4 4.3 8.1 2.1 3.6 6.7 RPE 0200 RPE 0350 RPE 0600 3.6 3.3 2.1 9.4 17 31 8.7 15 28 RPE 0950 RPE 1600 7.9 7.3 5.4 21 37 69 20 35 64 RPE 2500 12.6 11.9 8.3 34 59 109 32 56 104 RPE 4000 21.7 19.0 13.5 57 100 187 52 89 165
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
Actuator volumes:
Maximum volume (in liters) Outward Stroke Inward Stroke
Central
chamber
1
End cap
chamber
2
Displaced
3
volume
Double-Acting
and Spring-Return
2 4 8 2 4 8
0.26 0.37 0.15 0.67 1.2 2.2 0.89 1.6 3.1
1.3 1.0 0.7 3.2 5.7 11 2.8 4.9 9.1
2.1 1.9 1.2 5.5 9.8 18 5.0 8.8 16
4.9 4.6 3.2 13 23 43 12 22 40
Consumption per stoke
(in liters, pressure in barg)
Double-Acting only
Consumption per stoke
(in Cu.in., pressure in psig)
Double-Acting only
Actuator
model
Actuator volumes:
Maximum volume (Cu.in.) Outward Stroke Inward Stroke
Central
chamber
1
End cap
chamber
2
Displaced
3
volume
Double-Acting
and Spring-Return
40 80 120 40 80 120
RPE 0025 8.5 12.2 4.7 28 52 75 38 72 106 RPE 0040 RPE 0065
15.9 23 8.9 53 96 140 71 133 196 24 34 13.5 81 148 215 107 200 294
RPE 0100 36 53 19.9 118 216 314 165 310 455 RPE 0150 58 47 32 192 352 512 163 293 424 RPE 0200 76 64 44 255 466 676 220 397 573 RPE 0350 131 115 76 436 796 1157 392 709 1025 RPE 0600 222 201 129 742 1354 1967 683 1237 1790 RPE 0950 301 279 196 1025 1854 2682 966 1735 2505 RPE 1600 484 447 328 1662 2997 4331 1560 2792 4024 RPE 2500 769 728 508 2630 4751 6873 2515 4523 6530 RPE 4000 1324 1159 825 4477 8130 11782 4022 7219 10416
Notes:
1. Pistons at 90° outward position.
2. Pistons at 0° inward position.
3. Stroke is 90°.
Figure 2 Actuator air volumes
Central air chamber volume
Double-Acting and Spring-Return
6
End cap air chamber volume
Double-Acting only
Introduction
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
Section 3: Configuration Code
This section explains:
How to create the configuration code for a actuator.
RPES 0150 - N U 40 CW AL TN - L19 S K A - 00 XX
Type
Size
Rotation angle
Threads
Spring set
Rotation
Pinion material
Valve interface
Section 3: Configuration Code
Miscellaneous options Internal code 1 Color / finish Visual indicator Temperature Valve stem connection
Type
RPED Double Acting
RPES Spring Return
Size
0025 Size 0025 0350 Size 0350 0040 Size 0040 0600 Size 0600 0065 Size 0065 0950 Size 0950 0100 Size 0100 1600 Size 1600 0150 Size 0150 2500 Size 2500 0200 Size 0200 4000 Size 4000
Rotation angle
N 90° rotation angle
Threads
M Metric ISO 5211
U UNC/NPT/Imperial
Spring Set
00 Double Acting (no springs) 10 Spring Set 10 40 Spring Set 40 20 Spring Set 20 50 Spring Set 50 30 Spring Set 30 60 Spring Set 60
Rotation direction
CW Spring to Close/Clock Wise
CC Spring to Open/Counter Clock Wise
Pinion Material
AL High Grade Aluminium, Hard anodized SS Stainless steel ASI 316 (+ A4-70 SS fasteners)
Valve Interface
TN Standard ISO 5211 interface SY Small interface with center plate (DIN3337) LY Large interface with center plate (DIN3337)
(2
Notes: See next page.
Valve Stem Connection
Actuator
size
0025 11mm / 0.433" L11 D11 Q11
0040 &
0065
0100
0150
0200 22mm / 0.866" L22 D22 Q22
0350
0600 27mm / 1.063" L27 D27 Q27 0950 36mm / 1.417" L36 D36 Q36
1600 &
2500
4000 (355mm / 2.165" Q55 Q55 Q55
Temperature Range
S Standard: -20°C to +80°C (-4°F to +176°F)
H High: -10°C to +120°C (+14°F to +250°F)
L Low: -40°C to +80°C (-40°F to +176°F)
Visual Indication Code
K Standard (Knob) N No Visual Indication
Finish
(7
B Standard coating (Bettis Orange)
Internal code 1
00 Standard 10 Stainless steel AISI316 (A4-70) end cap screws
Miceleanuous options
XX Standard H1 1/2" High Flow plate P1 1/2" Porting according EN 15714-3 (only sizes 950-4000)
Square
No insert 000 Not applicable
14mm / 0.551" L14 D14 Q14
17mm / 0.669" D17 Q19 19mm / 0.748" L19 17mm / 0.669" D17 Q22 19mm / 0.748" L19
22mm / 0.866" D22 Q27 27mm / 1.063" L27
46mm / 1.811" L46 D46 Q46
Aluminum Stainless Steel Parallel drive
Diagonal
drive
Star drive
(7
(4
Configuration Code
7
Section 3: Configuration Code
Notes:
1. The options, listed here, are all options available. Not all options apply to all con­figurations.
2. Valve Interface: Option "S"; Small Interface with Center Plate (DIN3337) is not available for size 0025, 0950 and 4000. Option "L"; Large Interface with Center Plate (DIN3337) is not available for size 1600 and 2500.
3. Size 4000 does not have inserts but has two inner squares (diagonally and parallel oriented) directly in the bottom of the pinion.
4. Actuators with stainless steel pinions do not have inserts but have two inner squares (diagonally and parallel oriented aka "Star Drive") directly in the bottom of the pinion.
5. Contact you local Bettis representative for additional insert options.
6. PED Group 1 Label only available up to size 950.
7. Actuators with the default hard anodized pinions, come with stainless steel grade A2 (AISI304) end cap screws. Optional, the actuator is available with stainless steel grade A4-70 (AISI316) end cap screws. Select option 10 in the "Internal code 1" segment in case stainless steel grade A4 (AISI316) end cap screws are required.
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
8
Configuration Code
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
Section 4: Installation
This section explains:
The actuator rotation direction.
In which position the actuator will end after a failure.
Principles of operation:
Solenoid operation.
Double acting and Spring return operation.
Assembly codes.
Actuator to valve assembly.

4.1 Before You Start

Section 4: Installation
SAFETY
In case of an air or electrical failure, it is important to know the behavior of the actuator. Before mounting the actuator on a valve, consult the following sections below.

4.2 Actuator Rotation Direction

4.2.1 Valve Rotation

For the following paragraphs we assume that valves rotate as indicated in figure 3.
Figure 3 Normal valve rotation

Installation

The valve is closed after
a clockwise rotation.
The valve is open after
a counterclockwise rotation.
9
A
BA
Section 4: Installation

4.2.2 Position After Failure

The position of the actuator after a failure depends on the:
1. Principle of operation (see paragraph 4.3)
2. Assembly codes (see paragraph 4.4)
3. Kind of failure. Refer to the table below.
Table 5. Position After Failure
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
Principle of
Operation
Assembly Code Kind of Failure Position
CW
Double-Acting
Actuator
Single-Acting
CW
(Spring-Return)
Actuator

4.3 Principles of Operation

4.3.1 Solenoid Valve

All actuators can be either piped with solid or flexible tubing with the solenoid valve mounted remotely from the actuator or by mounting a VDI/VDE 3845 (NAMUR) designed solenoid valve DIRECTLY onto the NAMUR mounting pad on the side of the actuator.
Pressure Not defined
Signal Closed
Supply Voltage Closed
Pressure Not defined
Signal Open
Supply Voltage Open
Pressure Closed
Signal Closed
Supply Voltage Closed
Pressure Open
Signal Open
Supply Voltage Open
10
Figure 4 Typical solenoid operation
Spring-Return Operation Double-Acting Operation
Installation
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
The table below represents the cycle time (operating time) per different Actuator sizes:
Table 6. Operating Speed
Cycle time in seconds
Actuator
size
25 0.5 0.4 0.5 0.4 40 0.6 0.5 0.6 0.5
65 0.7 0.5 0.6 0.6 100 0.8 0.6 0.8 0.7 150 1.0 0.8 0.9 0.8 200 1.3 0.9 1.0 1.0 350 600 3.2 1.9 2.2 2.2 950 6.6 2.2 2.4 2.0
1600 10.6 3.5 3.6 3.3 2500 16.9 5.7 5.8 5.2 4000 29.1 9.2 9.2 9.0
Operating time is average with actuator under load and solenoid valve fitted.
pressurized
Spring-Return Double-Acting
A-port
1.9 1.3 1.4 1.5
Spring stroke
Section 4: Installation
A-port
pressurized
B-port
pressurized
Test conditions:
1. Solenoid with flow capacity: 0.6 m3/hr
2. Pipe diameter: 6mm
3. Medium: clean air
4. Supply pressure: 5.5 bar (80psi)
5. Load: with average load
6. Stroke: 90°
7. Temperature: Room temperature

4.3.2 Ingress Protection (IP) rating

Bettis RPE actuators are IP66/IP67 rated. In case of IP66 or IP67 requirements, take precautions that comply with the IP66/IP67 requirements to prevent moisture or dust from entering the actuator through the open air exhaust port(s), either directly on the actuator or at the exhaust ports of the connected solenoid valve.
We recommend to connect tubing to the exhaust(s) and lead this into a dry and dust free area, or to use check valves in the exhaust.
Installation
11
A
BA
A
B
B
Section 4: Installation
Installation, Operation and Maintenance Manual

4.3.3 Double-Acting Actuators

The operating principle, as explained here, is applicable for actuators with assembly code CW (direct acting).
Applying supply pressure to port A will move the pistons outward to the "Open"
position of the valve.
Applying supply pressure to port B will move the pistons inward to the "Close"
position of the valve.
For assembly codes CC, the operating principle is reversed (reverse acting).
Figure 5 Double-Acting Operation
Outward Stroke
DOC.IOM.BE.EN Rev. 9
12
Inward Stroke
Installation
Installation, Operation and Maintenance Manual
A
A
B
A
DOC.IOM.BE.EN Rev. 9

4.3.4 Spring-Return Actuators

The operating principle, as explained here, is applicable for actuators with assembly code CW (direct acting).
Applying supply pressure to port A will move the pistons outwards to the "Open"
position of the valve.
Venting the supply pressure from port A will cause the springs to move the pistons
inwards to the "Close" position of the valve.
For assembly codes CC, the operating principle is reversed (reverse acting).
Figure 6 Stroke Movements
Outward Stoke
Section 4: Installation
Installation
Inward Stroke
13
AB
A
B
A
B
A B
Pinion and cam position
Dot in pinion slot
Default
pistons position
Reversed pistons position
Pinion 90° rotated
AB
A
B
A
BA
B
Pinion and cam position
Dot in pinion slot
Default
pistons position
Reversed pistons position
Springs
Pinion 90° rotated
Section 4: Installation
Installation, Operation and Maintenance Manual

4.4 Actuator Assembly Codes

Figure 7 Assembly Code - Double-Acting
Assembly code: CW Assembly code: CC
= Standard, Clockwise-to-Close rotation = Reverse, Counterclockwise-to-Open
= Fail-to-Close = Fail-to-Open
DOC.IOM.BE.EN Rev. 9
A = Rotation when central air chamber is pressurized.
B = Rotation when end cap air chambers are pressurized.
All views are from above. Pistons are shown in inward position.
Figure 8 Assembly Code - Spring-Return
Assembly code: CW Assembly code: CC
= Standard, Clockwise-to-Close rotation = Reverse, Counterclockwise-to-Open
= Fail-to-Close = Fail-to-Open
14
Installation
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9

4.5 Actuator to Valve Installation

WARNING: MOVING PARTS
Actuator must be isolated pneumatically and electrically before any (dis)assembly starts.
Stay away from moving parts to prevent serious injuries. When test cycling the actuator and valve assembly by applying pressure to the A or B port, be aware that there are moving parts like pinion top, actuator to valve coupling and the valve- blade, ball, plug, etc.
NOTICE
The actuator is designed to be installed, commissioned and maintained using generic tools like wrenches, Allen keys and screwdrivers. For the removal of inserts, a special extractor tool can be supplied on request.
During assembly to the valve, do not hit with hammer on pinion top. This can damage the pinion top washer and cause premature failure.
Section 4: Installation
Before mounting the actuator on the valve or valve bracket, be sure that both the actuator and the valve are in the same closed or open position.
Refer to Appendix B, Tool and Torque tables, for using the right size tool.
Table 7. Tool Table
Symbol Tool Symbol Tool
Wrench – All types and sizes.
Metric and Imperial
Circlip Pliers
1. Remove handle nut, handle, lock washer, and etc. from the valve if required.
2. Visually check to make sure the valve is CLOSED.
Figure 9 Valve handle removal
Allen key
Installation
15
Section 4: Installation
3. When required, check if the insert drive (23) is mounted. If not, use a plasticmallet
Figure 10 Insert drive Installation
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
and tap slightly until the reducer square is in the required position.
90°
90°
Parallel
square
45°
Flat head
90°
23
Diagonal
square
Round with
key way
4. Install the bracket to the valve flange. Tighten all bolts and nuts and apply the cor­rect torque.
Figure 11 Bracket Installation
16
Installation
Installation, Operation and Maintenance Manual
Indicator mounting “In-line”
DOC.IOM.BE.EN Rev. 9
5. Install the actuator to the bracket. Tighten all bolts and apply the correct torque (refer to Table 8).
Table 8. Bottom flange torque values
Section 4: Installation
Actuator size ISO Pattern
25
40, 65, 100
150, 200, 350
600
950
1600, 2500
4000
F03 inner pattern M5 2.0 3.0 10-24UNC 1.5 2.2 F05 outer pattern M6 4.5 5.0 1/4"-20 3.3 3.7 F05 inner pattern M6 4.5 5.0 1/4"-20 3.3 3.7 F07 outer pattern M8 10.5 12.5 5/16"-18 7.7 9.2 F07 inner pattern M8 10.5 12.5 5/16"-18 7.7 9.2 F10 outer pattern M10 21.0 24.5 3/8"-16 15.5 18.1 F10 inner pattern M10 21.0 24.5 3/8"-16 15.5 18.1 F12 outer pattern M12 34.5 43.0 1/2"-13 25.4 31.7 F10 inner pattern M10 21.0 24.5 3/8"-16 15.5 18.1 F14 outer pattern M16 90.0 104.0 5/8"-11 66.4 76.7 F16 inner pattern M20 170.0 204.0 3/4"-10 125.4 150.5
F25* outer pattern 4x M16 90.0 104.0 4x 5/8"-11 66.4 76.7
F16 inner pattern M20 170.0 204.0 3/4"-10 125.4 150.5 F25 outer pattern 8x M16 90.0 104.0 8x 5/8"-11 66.4 76.7
Torque (Nm) Torque (lbf.ft)
Thread Min. Max. Thread Min. Max.
6. When required, mount or adjust the visual indicator (26).
Figure 12 Actuator to valve mounting
Size 12 - 350 Size 600 - 4000
26 26
90°
90°
Indicator mounting “Across Line”
90°
Installation
17
Section 4: Installation
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9

4.6 Mounting of control and feedback accessories

Solenoid valve and or switch boxes can now be mounted to the actuator. Check the instructions as shipped with these components for installation, operating and maintenance instructions.
We recommend to test-cycle the complete assembly to check correct operation.

4.7 Recommended Tubing Sizes

In case the solenoid valve is mounted remotely (i.e. in a central solenoid cabinet) and in order to supply sufficient flow of air supply to the actuator, the following tubing sizes are recommended.
Table 9. Tubing Sizes
Actuator size
1.2 meters 4 feet 1.2 meters 4 feet
25, 40, 65 6 mm 1/4 inch 6 mm 1/4 inch
100, 150, 200,
350, 600
950, 1600, 2500,
4000
Runs up to Runs over to
6 mm 1/4 inch 8 mm 5/16 inch
6 mm 1/4 inch 10 mm 3/8 inch
18
Installation
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
Section 5: Mechanical Stroke Adjustment
Section 5: Mechanical Stroke Adjustment
This section explains:
What mechanical stroke adjustment is.
What the factory settings are.
How to adjust the travel stops.
Bettis RPE actuators have two stroke adjustment stops for adjusting accurately the stroke of the actuator/valve assembly in open and closed position.
The factory setting of the stroke is 90°. Most quarter-turn valve applications will not require readjustment of these settings.
If required the stroke can be adjusted by means of two-stroke adjustment bolts.
Figure 13 Factory Setting
80°
95°
Open
90°
Closed
Size 950 - 4000Size 25 - 600
Closed
-5°10°
90°
80°
93°
Open
-3°10°
Limit Stop 2Limit Stop 1

Mechanical Stroke Adjustment

19
Stop 1
Stop 2
Stop 1
Stop 2
Section 5: Mechanical Stroke Adjustment
Installation, Operation and Maintenance Manual

5.1 Travel Stop Adjustment

CAUTION: PRESSURIZED ACTUATOR
Do not turn out the travel stops completely when the actuator is pressurized.
When adjusting the travel stops and the actuator is still pressurized, the travel stops can be “shot” away when completely turned out.

5.1.1 Double-Acting Actuators

1. Operate valve/actuator assembly to the required "Closed" position.
2. Remove air supply.
3. Slacken locknut on the “closed” stop (2).
DOC.IOM.BE.EN Rev. 9
Figure 14
4. Turn the “closed” stop clockwise to reduce or counterclockwise to increase the travel. Consult chapter 5.1.3 (angular displacement of the pinion), to define how far the limit stop must be turned in or out.
5. Tighten the lock nut.
6. Connect air and cycle the actuator to check that the position is correct. If not repeat from 2.
7. Remove air supply.
8. For adjusting the open position repeat steps 1 to 7, but now for the open position and “open” stop (1).

5.1.2 Spring-Return Actuators

20
1. Connect air supply to the A port. Actuator will move to the open position.
2. Slacken locknut (24) on the “closed” stop (2).
Figure 15
Mechanical Stroke Adjustment
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
3. Turn the “closed” stop clockwise to reduce or counterclockwise to increase the travel. Consult chapter 5.1.3 (angular displacement of the pinion), to define how far the limit stop must be turned in or out.
4. Remove air supply. Actuator will move to the closed position.
5. Check whether the actuator valve assembly is in the required position. If not repeat steps 1 to 5.
6. Remove air supply.
7. For adjusting the open position repeat steps 1 to 6, but now for the open position and "open" stop (1).
Table 10. Limit stop dimensions
Actuator size Thread Bolt wrench size (mm) Nut wrench size (mm)
25 M6 10 10 40 M8 13 13
65 M10 17 (16)* 17 (16)* 100 M10 17 (16)* 17 (16)* 150 M10 17 (16)* 17 (16)* 200 M12 19 (18)* 17 (18)* 350 M16 24 24 600 M20 950 M 22
1600 M 24 14 36 2500 M 27 17 41 4000 M 22 12 32
1. Default dimension according DIN933 standard.
2. Dimensions in brackets according ISO4017 standard.
Section 5: Mechanical Stroke Adjustment
30 12
30 32

5.1.3 Angular Displacement

Below table identifies, per actuator size, what the angular displacement of the pinions is, when using the limit stop screws.
Turn the limit stop clockwise reduces the stroke.
Turn the limit stop counteclockwise to increase the stroke.
Table 11. Angular Displacement limit stops
Actuator size
25 0.7 7.1° 40 0.8 6.3°
65 0.6 8.3° 100 0.7 7.1° 150 1.2 4.2° 200 1.0 5.0° 350 0.8 6.3° 600 0.8 6.3° 950 1.1 4.7°
1600 1.3 4.1° 2500 1.5 3.4° 4000 3.2 1.6°
NOTICE
Turns for 5° adjustment of
the pinion:
360° revolution of limit
stop screw will adjust
In case of air leakage over the limit stop bolts, turn the lock nut of the limit stop bolts tighter, until leakage stops.
Mechanical Stroke Adjustment
21
Section 6: Maintenance
Installation, Operation and Maintenance Manual
Section 6: Maintenance
This section explains:
When and how to do maintenance.
Normal maintenance.
Extraordinary maintenance.
What to do when replacing springs.
What the availability is of spare parts, action conversion kits and temperature
conversion kits.
WARNING
Actuator must be isolated pneumatically and electrically before any (dis)assembly starts. Be­fore mounting or (dis)assembling the actuator, consult the relevant sections of this manual.
DOC.IOM.BE.EN Rev. 9

6.1 Normal Maintenance

Bettis RPE actuators are designed to operate without maintenance for their normal working life. Normal working life is 500,000 cycles* for sizes up to RPE1600 and 250,000 for sizes RPE2500 and RPE4000.
For actuators with the optional low temperature silicon seals, we advise to replace these seals after 250.000 cycles*.
NOTE:
* 1 Cycle = one open stroke and one close stroke.
We recommend regular inspections to make certain that the actuator / valve assembly operates smoothly and to check that there are no visible or audible defects. We advise to perform the following checks upon each proof test interval complying with the rules and regulations of the country of final installation:
Visually check the entire actuator as well as the control system (where foreseen).
Ensure there are no leaks on the actuator parts under pressure.
Check pneumatic connections for leaks. Tighten tube fittings as required.
22
Check if manual override (where foreseen) is regular.
Check if pneumatic filter cartridge (where foreseen) is sound and filter bowl
(where foreseen) has been cleaned properly.
Check the setting of the relief valves (where foreseen).
Verify that the power fluid supply pressure value is within the required range.
Remove built-up dust and dirt from all actuator surfaces.

Maintenance

Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
Inspect actuator paint work for damages to ensure continued corrosion protection.
Touch-up as required in accordance with the applicable paint specification.
Operate the Actuator/Valve assembly for 2 complete open/close cycles with com-
plete closing of the valve.
Verify the correct performing of open – close operations (e.g. check locally,
or automatically via Logic solver, the correct movement of the actuator).
All actuators are supplied with sufficient lubrication for their normal working life. If required, see Section 9.1 (Grease instructions) for the recommended grease.
For mounting the parts of the repair kit follow the instruction of the Decommission, Disassembly and Reassembly chapters of this manual.

6.2 Inspection and Repair

Replacement of internal seals and bearings allows to you extend the normal working life. Service kits, containing all necessary spare parts (like seals, bearings, grease and instructions) can be obtained through authorized Emerson – Actuation Technologies distributors.
Section 6: Maintenance

6.2.1 Service Kits

All soft seals, bearings, and nonreusable parts are included in the recommended service kit. The service kit is identical for both the double-acting and the spring-return models.

6.2.2 Spring-Return Actuator

For the spring-return models, we recommend a set of spare springs for each different model in addition to the recommended spare parts kit.
On spring-return actuators, the spring cartridges can be replaced. SPRING CARTRIDGES SHOULD ALWAYS BE REPLACED IN COMPLETE SETS. Spring kits are available through authorized Emerson – Actuation Technologies distributors.
Maintenance
23
Section 7: Decommission (Out of Service)
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
Section 7: Decommission (Out of Service)
This section explains:
How to decommission an actuator in a safe way.

7.1 Before You Start

WARNING: MOVING PARTS
Actuator must be isolated pneumatically and electrically before any (dis)assembly starts. Before mounting or (dis)assembling the actuator consult the relevant sections of this manual.
Actuator can move when removing supply pressure and/or electrical control signal of actuators. If not already there, a spring-return actuator will cycle to its fail position.
When removing any ball valve or plug valve assemblies from a pipe system, isolate the piping system on which the Actuator is installed and relieve any media pressure that may be trapped in the valve cavities before removing the actuator for maintenance.
A spring-return actuator mounted on a valve, which is stuck in mid stroke, contains a high spring load which will cause a sudden rotation of the actuator versus the valve or valve bracket during disassembly. This can cause serious injury to personnel or damage to property.
Refer to Appendix A for instructions to safely remove the spring load before disassembling the spring-return actuator from valve or bracket.
Important
Refer to the Safety Guide for Lifting Instructions.
24

Decommission (Out of Service)

Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
Section 7: Decommission (Out of Service)

7.2 Removing the actuator from the valve

1. Disconnect all air supply hoses (Ports A and B or solenoid).
2. Disconnect all electrical wirings of the switch box.
3. Disconnect the electrical wiring of the solenoid valve.
4. Remove the bolts and nuts from the valve flange.
5. Remove the bracket from the actuator.
6. Remove the switch box and solenoid valve. Refer to the documentation of the switch box and solenoid valve for safe disassembly.
Figure 16 Removing actuator from valve
3
1
2
4
Decommission (Out of Service)
25
Section 8: Disassembly
Installation, Operation and Maintenance Manual
Section 8: Disassembly
This section explains:
How to disassemble an actuator safely.
Tip
The instructions of this section can be used for maintenance or reconfiguration like spring set change or maintenance.
Reference numbers for components refer to the exploded view in section 11.
In case of maintenance, discard all the used soft parts like O-ring seals, guide bands, wear strips and circlip.
WARNING
Actuator must be isolated pneumatically and electrically before any (dis)assembly starts.
DOC.IOM.BE.EN Rev. 9
Before mounting or (dis)assembling the actuator consult the relevant sections of this manual.
CAUTION: PRESSURIZED ACTUATOR
Spring-return actuators contain springs in a compressed state. Follow these instructions to release the spring force safely.
The end caps of spring-return actuators sizes 25 to 600 should be free of the spring load after 10 full turns (crosswise relaxing) of the end cap screws. If there is still spring load on the end cap, this might indicate a broken spring cartridge. Stop this disassembly procedure immediately. Continuing might cause the end cap to be “shot” away causing serious injury.
Spring return actuator size 950 to 4000 have long end cap screws to release the spring load safely.
Refer to Appendix A for instructions to safely remove the spring load before disassembling the end cap of a spring-return actuator with a broken spring cartridge.
NOTICE
The actuator is designed to be installed, commissioned and maintained using generic tools like wrenches, Allen keys and screwdrivers.
26

Disassembly

Installation, Operation and Maintenance Manual
2
6
8
6
11
6
5
10
8
10
11
2
DOC.IOM.BE.EN Rev. 9
Section 8: Disassembly
Refer to the tables in this section or refer to Appendix B Tool and Torque tables.

8.1 Removing End Caps (Sizes 25 to 600)

1. For Double-Acting actuators, do the following:
a. Remove the screws (8) and washers (10) of the end caps (6).
b. Remove the o-ring (11) and "B" port seal (2). Discard these parts.
Figure 17 Double-Acting End Caps Removal
Double acting end caps (6) are fitted with a white warning sticker. Spring return end caps (5) are fitted with a black warning sticker.
Actuator sizes 25 to 100 have high end caps for double-acting and spring-return models.
Disassembly
27
Section 8: Disassembly
Actuator sizes 150 to 4000 have low end caps for double-acting models and high end caps for spring return models.
2. For Spring-Return actuators, do the following:
Figure 18 Spring-Return End Caps Removal
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
a. Tip: For actuators with assembly code CW, turn back the right hand limit
stop screw (30) 2 full turns. For actuators with assembly code CC, turn back the left hand limit stop screw (30) 2 full turns. This will lower the spring force on the end cap and reduces the screw out length of the end cap screws.
b. Uniformly loosen the screws (9) of the end caps (5) 1/4-1/2 turns at a
time, in sequence, as per figure 18, to relieve the pre-load of the springs.
c. Remove the o-rings (11) and "B" port seals (2). Discard these parts.
28
Disassembly
Installation, Operation and Maintenance Manual
3
1
4
5
11
2
30
5
9
11
10
2
9
10
2
6
2
11
6
8
10
8
10
2
11
DOC.IOM.BE.EN Rev. 9
Section 8: Disassembly

8.2 Removing End Caps (Sizes 950 to 4000)

1. For Double-acting actuators, do the following:
a. Remove the screws (8) and washers (10) of the end caps (6).
b. Remove the o-ring (11) and "B" port seal (2). Discard these parts.
Figure 19 Double-Acting End Caps Removal sizes 950 to 4000
2. For Spring-return actuators, do the following:
a. Tip: For actuators with assembly code CW, turn back the right hand limit
stop screw (30) 2 full turns. For actuators with assembly code CC, turn back the left hand limit stop screw (30) 2 full turns. This will lower the spring force on the end cap and reduces the screw out length of the end cap screws.
b. Uniformly loosen the screws (9) of the end caps (5) 1/4-1/2 turns at a
time, in sequence, as per figure 20, to relieve the pre-load of the springs.
c. Remove the o-rings (11) and "B" port seals (2). Discard these parts.
Disassembly
29
7
7
Section 8: Disassembly
Figure 20 Spring-Return End Caps Removal sizes 950 to 4000
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
10
9
3
6
1
4
5
2
5
11
2
11
2
30

8.3 Removing Spring Cartridges or Springs

3. Remove the spring cartridges or springs (7).
Figure 21 Removing Spring Cartridges size 25 to 600
5
10
9
30
Disassembly
Installation, Operation and Maintenance Manual
7
7
DOC.IOM.BE.EN Rev. 9
Figure 22 Removing Springs size 950 to 4000

8.4 Removing of Limit Stop

1. Remove the limit stop screws (30), limit stop nuts (31), limit stop washers (32) and limit stop o-rings (33). Discard the o-rings.
Section 8: Disassembly
Figure 23 Limit Stop Removal
33 30
32

8.5 Removing Pistons

1. Use a wrench and turn the pinion counterclockwise until the pistons (14) come out of the body.
2. Remove the piston bearings (15), piston rack bearing strips (17) and piston o-ring seals (16). Discard these parts.
31
Disassembly
31
Section 8: Disassembly

8.6 Removing Pinion

1. Remove the circlip (27) and thrust bearing (23) on top of the pinion assembly. For sizes 950 to 4000 remove also the top pinion bearing (19).
2. Remove the pinion (18) by pushing it downwards. For Size 4000, remove the backup ring (29), O-ring pinion top (21) the cam (24) and cam thrust washer (25) through the main bore of the housing.
3. Remove the pinion O-ring seals (21/22) and the pinion bearings (19/20). For Size 950 to 2500, remove also the backup ring (29).
4. Discard all of these parts.
Figure 25 Pinion Removal
Sizes 25 to 600
23
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
19
19
27
Sizes 950, 1600, and 2500
23
27
19
Size 4000
23
27
19
21
29 25
25
18
29 19 18
24
18
21
2221
20
22
20
32
Table 12. Recommended circlip pliers according DIN 5254 (or equal) for circlips.
Actuator
size
25 - 100 22 mm 0.866" A2 1600 75 mm 2.953" A3
150 - 350 36 mm 1.417" A3 2500 95 mm 3.74" A4
600 55 mm 2.165" A3 4000 96 mm 3.78" A4 950 65mm 2.559" A3
Pinion top
diameter
Pliers according
DIN 5254
Actuator
size
Pinion top
diameter
Pliers according
DIN 5254
Disassembly
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9

8.7 Cleaning the Components

In case of maintenance, use a clean dry cloth and thoroughly wipe clean and remove old grease from:
The inside and outside of the body including thread holes and crevices/grooves
The pinion gears.
The pistons.
Figure 24 Removing Pistons
14
17
14
16
15
16
17
Section 8: Disassembly
15
Disassembly
33
Section 9: Reassembly
Section 9: Reassembly
This section explains:
Which parts and how to grease them.
How to reassemble a complete actuator.
How to set the stroke adjustment bolts after reassembly.
How to do a basic function and air leak test.
Tip
The instructions of this section can be used for maintenance or reconfiguration like spring set change or maintenance.
Reference numbers for components refer to the exploded view in section 11.
In case of maintenance, discard all used soft parts like O-ring seals, guide bands and wear strips and circlip and replace them with the parts as supplied in the repair kit.
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
In case of reconfiguration replace the parts as supplied in the conversion kit (see also chapter 6).
Refer to the Safety Guide for Lifting Instructions.
NOTICE
The actuator is designed to be installed, commissioned and maintained using generic tools like wrenches, Allen keys and screwdrivers.
Refer to the tables in this section or refer to Appendix B Tool and Torque tables.
34

Reassembly

Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9

9.1 Grease Instructions

Check the product coding on the product labels and chapter 3 of this manual, to define which type of grease to use.
For standard actuators (-20°C to +80°C / -4°F to +176°F):
Castrol High Temperature grease (or equivalent).
For low temperature operation (-40°C to +80°C / -40°F to +176°F):
Castrol Tribol GR TT 1 PD (previously known as Castrol OPTITEMP TT1) or LG2 grease (or equivalent).
For high temperature operation (-10°C to +120°C / +14°F to +250°F):
Castrol High Temperature grease (or equivalent).
We recommend using a suitable sized paint brush to apply the required amount of grease on the parts as per Table 12 and Figure 23.
Table 13. Grease Instructions
Part Section of part Amount of grease
O-rings:
Housing Parts:
Piston Parts:
Piston Parts:
A Completely B Piston bore Light film C Top pinion bore Light film D Bottom pinion bore Light film E
O-ring & bearing groove F Rack teeth Half the teeth depth full with grease G Piston bearing Light film on outside H Piston rack bearing strip Light film
J
Pinion bottom & O-ring groove Light film
K Pinion top & O-ring groove Light film
L Gear teeth Half the teeth depth M Pinion top bearing Light film (inside and out) N Pinion bottom bearing Light film (inside and out)
Section 9: Reassembly
Light film
Light film
Reassembly
Figure 26 Grease Instructions
A
M
K
L
J
N
A
B
A
E
C
F
G
A
H
A
A
D
35
Section 9: Reassembly
Installation, Operation and Maintenance Manual

9.2 Reassembly of the pinion

1. Grease the pinion parts according to chapter 9.1.
2. Install the pinion bearings (19/20) and the O-ring seals (21/22) on the pinion (18). For Size 950 to 2500, install also the the backup ring (29).
3. Insert the pinion (18) in the housing. For size 4000: mount first the cam (24), cam thrust washer (25), pinion top O-ring (21) and backup ring (29) through the main­bore onto the pinion (18).
4. For sizes 950 to 4000 install first the top pinion bearing (19). For all sizes, install the thrust washer (23) and mount the circlip (27) on the pinion top.
Install the new circlip onto its mating groove on the top shaft extension
and with the non-sharp edge (2) towards the housing and the sharp edge (1) towards the top of the shaft.
Figure 27 Reassemble the pinion
2
Sizes 25 to 600
23
1
19
DOC.IOM.BE.EN Rev. 9
19
27
1
1
Sizes 950, 1600, and 2500
2
23
27
19
Size 4000
2
23
27
19
21
29 19
24
29 25
21
18
18
18
21
2221
20
22
20
36
Table 14. Recommended circlip pliers according DIN 5254 (or equal) for circlips.
Reassembly
Installation, Operation and Maintenance Manual
17
14
16
16
17
14
15
15
DOC.IOM.BE.EN Rev. 9
Section 9: Reassembly
Actuator
size
25 - 100 22 mm 0.866" A2 1600 75 mm 2.953 A3
150 - 350 36 mm 1.417" A3 2500 95 mm 3.74 A4
600 55 mm 2.165" A3 4000 96 mm 3.78 A4 950 65mm 2.559" A3
Pinion top
diameter
Pliers according
DIN 5254
Actuator
size

9.3 Reassembly of the pistons

NOTICE
Before reassembling the pistons, check the required assembly code (see section 4.2).
1. Grease the piston parts according to step 9.1.
2. Install the piston rack bearing strips (17) and piston O-ring seals (16) on the pis­tons (14). Ensure all these parts are kept in place during assembly.
Figure 28 Reassemble the pistons
Pinion top
diameter
Pliers according
DIN 5254
Reassembly
3. Align the pinion (see Figure 26) so that the teeth on the pinion will pick up the pis­tons rack teeth when turning the pinion. Note the position of the pinion top slot and the cam on the pinion top:
For standard or Spring-to-Close: Assembly Code CW.
For reverse or Spring-to-Open: Assembly Code CC.
37
90°
90°
Assembly code CW Assembly code CC
(Standard; Spring-to-Close) (Reverse; Spring-to-Open)
A
B
A
B
C
C
Section 9: Reassembly
4. Slightly push the pinion inward to engage with the pinion.
5. When the pistons are moved 90° inwards (see figure 26), check that the pinion slot
6. If not, turn pinion to move the pistons outward until they disengage from the
7. Move the pistons outward so that just the bearing groove sticks out of the hous-
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
Ensure that smooth movement and 90-degree operation can occur with-
out moving the pistons out of the actuator body.
For larger pistons, use a rubber mallet and slightly hitting the pistons
inward to engage with the pinion.
on the pinion top is:
Perpendicular to the length centre line of the house for assembly code CW.
In line to the length centre line of the house for assembly code CC.
pinion. Shift one tooth of the pinion, reassemble and check again.
ing. Fold the piston bearings (15) around the piston and hold the bearing ends in place while moving the pistons inwards.
For larger pistons, use a rubber mallet and slightly hitting the pistons
inward to engage with the pinion.
Figure 29 Position of the slot and the cam on the pinion top
38
A = Position of cam
B = Position of slot and dot in pinion.
C = Final position of pinion dot.
Reassembly
Installation, Operation and Maintenance Manual
33 30
31
32
DOC.IOM.BE.EN Rev. 9
NOTE:
When the pistons are completely moved inwards, the pinion top will show a 5° over travel.
Section 9: Reassembly

9.4 Reassembly and settings of the limit stops

1. Install the limit stop screws (30), limit stop nuts (31), limit stop washers (32) and limit stop O-rings (33).
Figure 30 Install Limit Stop Bolts
2. Move the pistons inward until the slot in the top of the pinion is perpendicular to
3. Double check if the position of the slot and the cam on the pinion top is in the cor-
4. Move the pistons outward until the slot in the top of the pinion is in line with the
5. Screw in the left hand travel stop until it comes into contact with the pinion stop
centerline of the housing.
rect position (see figure 26). Screw in the right hand travel stop until it comes into contact with the pinion stop face.
centerline of the housing.
face.
For accurate travel stop adjustment of the actuator on the valve,
see section 5.
Reassembly
39
2
6
9
6
11
6
5
10
9
10
11
2
Section 9: Reassembly
Installation, Operation and Maintenance Manual

9.5 Reassembly of the end caps

9.5.1 Double-Acting actuators

1. Grease the O-ring seals (11) and B port seals (2) according to step 9.1.
2. Ensure that O-ring seals (11) and B port seals (2) are kept in place during assembly.
3. Install the end caps (6) and tighten the end cap screws (8). Refer to Table 15 for the correct torque.
Figure 31 Double-Acting end cap assembly
DOC.IOM.BE.EN Rev. 9
Double acting end caps (6) are fitted with a white warning sticker. Spring return end caps (5) are fitted with a black warning sticker.
Actuator sizes 25 to 100 have high end caps for double-acting and spring-return models.
Actuator sizes 150 to 4000 have low end caps for double-acting models and high end caps for spring return models.
Table 15. End cap Screw Torque
Actuator
size
25 M5 40 M5 SW 4 2.0 1.6 3.0 1.5 1.2 2.2
65 M5 SW 4 2.0 1.6 3.0 1.5 1.2 2.2 100 M5 SW 4 2.0 1.6 3.0 1.5 1.2 2.2 150 M6 SW 5 3.3 2.6 5.1 2.4 1.9 3.8 200 M6 SW 5 3.3 2.6 5.1 2.4 1.9 3.8 350 M8 SW 6 8.4 6.7 12.2 6.2 4.9 9.0 600 M10 SW 8 15.3 12.2 24.8 11.3 9.0 18.3 950 M12 SW10 24.3 19.4 41.6 17.9 14.3 30.7
1600 M12 SW10 24.3 19.4 41.6 17.9 14.3 30.7 2500 M12 SW10 24.3 19.4 41.6 17.9 14.3 30.7 4000 M14 SW12 43.5 34.8 66.4 32.1 25.7 49.0
Thread Tool Size
Allen Key
SW 4 2.0 1.6 3.0 1.5 1.2 2.2
Torque (Nm) Torque (lbf.ft)
Target Min. Max. Target Min. Max.
40
Reassembly
Installation, Operation and Maintenance Manual
1
2 3
4
56
A
B
1
2
3
4
56
1
23
4
56
N = 10
N = 20
N = 30
1
2 3456
1
23
4
5
6
1
23
4
5
6
N = 40
N = 50
N = 60
DOC.IOM.BE.EN Rev. 9

9.5.2 Spring-Return actuators

Important
Bettis RPE-Series Spring return actuators are supplied with springs on each side of the actuator. Throughout the RPE-Series size range, there are two different spring designs:
Sizes RPE25 to RPE600 have 6 springs on each side (see figure below).
Sizes RPE950 to RPE4000 have 3 springs on each side (see chapter 9.5.3).
Check below figures to see where to place the spring cartridges in case of spring set conversion.
When replacing spring cartridges in a spring-return actuator, ensure that the cartridges are replaced in their identical position from where they were removed.
Before assembling the spring cartridges and end caps, make sure that the pistons are completely inwards.
Figure 32 Spring cartridge placement
Section 9: Reassembly
Reassembly
A = Piston top view B = Position of piston gear rack
1. Grease the O-ring seals (11) and B port seals (2) according to step 9.1.
2. Ensure that O-ring seals (11) and B port seals (2) are kept in place during assem­bly.
3. Place the spring cartridges in actuator as per required spring set (see Figure 32).
4. Put the end cap screw washer (10) on the end cap screw (9) and tighten each end cap screw in small equal turns and in the sequence as per Figure 33. Refer to Table 15 for the correct torque. We recommend to use some grease on the screws for easier fastening.
41
3
1
4
5
11
2
30
5
9
11
10
2
9
10
2
Section 9: Reassembly
Installation, Operation and Maintenance Manual
Figure 33 Spring Return End cap assembly size 25 to 600

9.5.3 Spring-Return actuators - Size 950 to 4000

DOC.IOM.BE.EN Rev. 9
Important
Bettis RPE-Series Spring return actuators are supplied with springs on each side of the actuator. Throughout the RPE-Series size range, there are two different spring designs:
Sizes RPE25 to RPE600 have 6 springs on each side (Chapter 9.5.2).
Sizes RPE950 to RPE4000 have 3 springs on each side (see figure below).
Check below figures to see where to place the springs in case of spring set conversion.
When replacing springs in a spring-return actuator, ensure that the springs are replaced in their identical position from where they were removed.
Before assembling the springs and end caps, make sure that the pistons are completely inwards.
42
Reassembly
Installation, Operation and Maintenance Manual
N = 10 N = 20 N = 30
DOC.IOM.BE.EN Rev. 9
Figure 34 Spring placement size F950 to F4000
Left RightLeftRight Left Right
B
A
1 spring 0 spring 1 spring 1 spring 2 springs1 spring
N = 40 N = 50 N = 60
Section 9: Reassembly
Left
2 springs
Right Left RightLeft Right
2 springs 3 springs2 springs3 springs3 springs
Reassembly
43
Section 9: Reassembly
A = Piston top view B = Position of gear rack
1. Grease the O-ring seals (11) and B port seals (2) according to step 9.1.
2. Ensure that O-ring seals (11) and B port seals (2) are kept in place during assembly.
3. Place the spring in actuator as per required spring set (see Figure 29).
4. Put the end cap screw washer (10) on the end cap screw (9) and tighten each end
Figure 35 Spring Return end cap assembly size 950 to 4000
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
cap screw in small equal turns and in the sequence as per Figure 35. Refer to Table 15 for the correct torque. We recommend to use some grease on the screws for easier fastening.
10
9
3
6
1
4
5
2
5
11
2
11
2
30
5
10
9
44
Reassembly
Installation, Operation and Maintenance Manual
AB
DOC.IOM.BE.EN Rev. 9

9.6 Basic function and Air Leak Test

CAUTION: MOVING PARTS
Applying pressure to the actuator will cause the actuator/valve assembly to operate.
1. Apply pressure (max. 8 bar/120 psi) to ports A and B. Use some soap suds at the indicated points: around pinion top (1), pinion bottom (2), the end caps (3) and limit stops (4).
2. In case of leakage around:
a. The limit stop bolts: Turn the lock nut of the bolts tighter, until the leak-
age stops.
b. The end caps: Disassemble the end caps, replace o-rings and reassemble.
c. The pinion top or bottom and A- or B- port: Disassemble the complete
actuator, replace o-rings and reassemble.
Section 9: Reassembly
Figure 36 Basic function and air leak test
1
4
B
A
3
2
3
Reassembly
45
Section 10: Troubleshooting
Installation, Operation and Maintenance Manual
Section 10: Troubleshooting

10.1 Mechanical Problems

Problem Possible error Solution Where to find
Feedback position and actual position are not the same.
Valve is in “Closed” position, actuator is in “Open” position and will not move anymore.
Actuator and valve are mounted 90° rotated in relation to each other.
Limit stop screws are not set correctly.
Remove actuator from valve. Check assembly code of actuator. Put both valve and actuator in “Closed” position. Mount actuator on valve.
Readjust the limit stop screws.
DOC.IOM.BE.EN Rev. 9
Section 4
Section 5
Valve does not reach the completely “Closed” or “Open” position.
Actuator rotates, valve does not.
Actuator does not rotate or does not rotate smoothly.
Limit stop screws cannot be turned out anymore.
Insert is not mounted properly.
Pressure to low. Apply pressure as per sizing.
Sizing is wrong.
Pinion is mounted in the wrong position.
No coupling between actuator shaft and valve spindle.
Broken gearing on pistons or pinion.
Spring or Spring cartridge is broken.
Limit stop screws is bend.
Mount the insert in the right position. Remark: Rotate insert to one cam = 22.5°.
Check valve torque data with actuator torque data.
Re assemble actuator. Section 9
Install a coupling between actuator shaft and valve spindle.
Contact nearest Bettis representative to replace actuator.
Contact nearest Bettis representative to replace actuator.
Contact nearest Bettis representative to replace actuator.
Section 4.5
Section 4.5
Appendix A.
46

Troubleshooting

Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9

10.2 Pneumatic Problems

Problem Possible error Solution Where to find
Actuator does not react to electrical control signal.
Actuator does not react good to electrical control signal.
Air leakage between actuator and solenoid valve.
There is no supply pressure at the actuator.
There is sufficient supply air pressure but insufficient supply air capacity.
Supply pressure too low, causing pilot operated solenoid valve to fail.
Solenoid valve is not mounted properly.
Speed control throttle (if present) blocks air flow.
Manual override (if present) on the Solenoid Valve is locked.
Sealing between solenoid valve and actuator is not mounted air tight.
Section 10: Troubleshooting
Supply the right pressure to the actuator.
Take care the supply air tubing has the right dimensions.
Check that supply pressure at the actuator and solenoid is sufficient to operate the actuator.
Check the solenoid valve mounting.
Turn the speed control more open.
Unlock manual override on the solenoid valve.
Reassemble solenoid valve taking care, that all seals are in place.
Section 2.3 Check that the actual supply pressure is higher than the sizing pressure.
Section 4.6
Section 2.3 Check that the actual supply pressure is higher than the sizing pressure.
Instructions shipped with the solenoid valve.
Instructions shipped with the speed control valve.
Instructions shipped with the manual override.
Instructions shipped with the solenoid valve.
Double-acting actuator will only move to “open” position.
Leakage notice on the actuator.
Actuator has wrong solenoid valve configuration.
Seals on the limit stops screws are not air tight.
Seals on the end caps are not air tight.
Seals on the pinion top and bottom are not air tight.
Mount a solenoid valve suitable for double­acting actuators (4/2 or 5/2 function).
Check that conversion plate on solenoids, that have both 3/2 and 5/2 functions, is in the right position.
Turn the lock nut of the bolts tighter; until the leakage stops.
Disassemble the end caps, replace O-rings and reassemble. Consider to replace all O-ring seals and bearings.
Disassemble the complete actuator, replace O-rings and reassemble. Consider to replace all O-ring seals and bearings.
Instructions shipped with the solenoid valve.
Instructions shipped with the solenoid valve.
Section 9.6
Section 9.6 or Section 6
Section 9.6 or Section 6
Troubleshooting
47
Section 10: Troubleshooting
Installation, Operation and Maintenance Manual

10.3 Electrical Problems

Problem Possible error Solution Where to find
Control wiring. Power supply wiring or feedback wiring are not
Actuator does not react to control signals.
There are problems with position feedback after sending the actuator to either the “Open” or “Closed” position.
right connected. The power supply
voltage is not is not the same as the voltage of the applicable solenoid valve.
The wiring of the feedback signals may be switched.
Connect all wiring in the right way.
Connect the right power supply voltage.
Connect the feedback wiring in the right way.
DOC.IOM.BE.EN Rev. 9
Instructions of the control or feedback accessories.
Instructions of the solenoid valve.
Instructions of the feedback device.
48
Troubleshooting
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
Section 11: Parts List and Spare Parts
Section 11: Parts List and Spare Parts
Recommendations

11.1 Actuator sizes RPE25 to RPE600

23
27
26
21
19
18
6
30
33
31
32
1
16
15
14
17
19
21
3
28
2
7
11
12
8
10
5
13
9
10
Table 16. Parts List
Pos. Qty Notes Description Material
1 1 House Cast Aluminium alloy 2 2 1 B-port seal Nitrile rubber 3 1 Center plate (optional) Nylon PA6, Black 5 2 2 End cap SR (DA) Cast Aluminium alloy 6 2 2 End cap DA Cast Aluminium alloy 7 Max. 12 Spring cartridge Spring steel 8 8 End cap screw DA Stainless Steel
9 8 End cap screw SR Stainless Steel 10 8 End cap screw washer Stainless Steel 11 2 1 O-ring end cap Nitrile rubber 12 2 Warning sticker DA Polyester 13 2 Warning sticker SR Polyester 14 2 Piston Cast Aluminium alloy 15 2 1 Bearing piston PTFE 25% carbon-filled 16 2 1 O-ring piston Nitrile rubber 17 2 1 Bearing strip piston rack POM 18 2 Pinion High grade aluminium 19 2 1 Bearing pinion POM 21 2 1 O-ring pinion Nitrile rubber 23 1 1 Thrust bearing pinion POM, black UV stabilized 26 1 Indicator assembly ABS + stainless steel screw 27 1 1 Circlip Spring steel 28 1 Drive insert Aluminium 30 2 Limit stop screw Stainless steel 31 2 Limit stop nut Stainless steel 32 2 1 Limit stop washer PA66 33 2 1 O-ring limit stop Nitrile rubber
Notes:
1 Included in Service Kit.
2 Actuator sizes 25 to 100 have high end caps for double-acting and spring-return models. Actuator sizes
150 to 4000 have low end caps for double-acting models and high end caps for spring-return models.
Parts List and Spare Parts
49
Section 11: Parts List and Spare Parts
Installation, Operation and Maintenance Manual

11.2 Actuator sizes RPE950 to RPE2500

26
30
31
32
33
19
1
27
23
29
21
18
16
15
DOC.IOM.BE.EN Rev. 9
6
8
10
12
9
10
5
17
14
20
22
28
4
3
2
11
7
Table 17. Parts List
Pos. Qty. Notes Description Material
1 1 House Cast Aluminium alloy
2 2 1 B-port seal Nitrile rubber
3 1 Center plate (option) Nylon PA6, Black
4 12 Thread insert Steel
5 2 End cap SR Cast Aluminium alloy
6 2 End cap DA Cast Aluminium alloy
7 Max. 6 Springs Spring steel
8 12 End cap screw DA Stainless Steel
9 12 End cap screw SR Stainless Steel 10 12 End cap screw washer Stainless Steel 11 2 1 O-ring end cap Nitrile rubber 12 2 Warning sticker DA Polyester 13 2 Warning sticker SR Polyester 14 2 Piston Cast Aluminium alloy 15 2 1 Bearing piston PTFE 25% carbon-filled 16 2 1 O-ring piston Nitrile rubber 17 2 1 Bearing strip piston rack POM 18 1 Pinion High grade aluminium 19 2 1 Bearing pinion top POM 20 1 1 Bearing pinion bottom POM 21 1 1 O-ring pinion top Nitrile rubber 22 1 1 O-ring pinion bottom Nitrile rubber 23 1 1 Thrust bearing pinion POM, black UV stabilized 26 1 Indicator assembly ABS + stainless steel screw 27 1 1 Circlip Spring steel 28 1 Drive insert Aluminium 29 1 1 Backup ring POM 30 2 Limit stop screw Stainless steel 31 2 Limit stop nut Stainless steel 32 2 1 Limit stop washer PA66 33 2 1 O-ring limit stop Nitrile rubber
Notes:
1 Included in Service Kit.
13
50
Parts List and Spare Parts
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9

11.3 Actuator size RPE4000

Section 11: Parts List and Spare Parts
26
27
23
30
25
24
31
32
17
14
133
20
22
19
29
21
18
4
3
16
15
11
2
7
Table 18. Parts List
Pos. Qty. Notes Description Material
1 1 House Cast Aluminium alloy
2 2 1 B-port seal Nitrile rubber
3 1 Center ring (option) Stainless Steel AISI 304
4 12 Thread insert Steel
5 2 End cap SR Cast Aluminium alloy
6 2 End cap DA Cast Aluminium alloy
7 Max. 6 Springs Spring steel
8 12 End cap screw DA Stainless Steel
9 12 End cap screw SR Stainless Steel 10 12 End cap screw washer Stainless Steel 11 2 1 O-ring end cap Nitrile rubber 12 2 Warning sticker DA Polyester 13 2 Warning sticker SR Polyester 14 2 Piston assembly Cast Aluminium alloy 15 2 1 Bearing piston PTFE 25% carbon-filled 16 2 1 O-ring piston Nitrile rubber 17 2 1 Bearing strip piston rack POM 18 1 Pinion High grade aluminium 19 2 1 Bearing pinion top POM 20 1 1 Bearing pinion bottom POM 21 1 1 O-ring pinion top Nitrile rubber 22 1 1 O-ring pinion bottom Nitrile rubber 23 1 1 Thrust washer pinion POM, black UV stabilized 24 1 Cam stroke adjustment Steel 25 1 1 Cam thrust washer POM, black UV stabilized 26 1 Indicator assembly ABS + stainless steel screw 27 1 1 Circlip Spring steel 29 1 1 Backup ring POM 30 2 Limit stop screw Stainless steel 31 2 Limit stop nut Stainless steel 32 2 1 Limit stop washer PA66 33 2 1 O-ring limit stop Nitrile rubber
Notes:
1 Included in Service Kit.
6
12
8
10
9
10
5
13
Parts List and Spare Parts
51
Crush / Amputaion Hazard
Failure to follow instructions for removal of spring loaded actuator may result in surious personal injury
WARNING
1
2
3
4
Appendix
Installation, Operation and Maintenance Manual

Appendix A: Spring Load Removal

This section explains:
How to remove the spring load safely of spring-return actuators in case:
The valve gets “stuck” in mid position.
One of the spring cartridges is broken.
WARNING: MOVING PARTS
A Spring-return actuator mounted on a valve, which is stuck in mid stroke, contains a high spring load which will cause a sudden rotation of the actuator versus the valve during disassembly. This can cause serious injury to personnel or damage to material.
On Spring-return actuators with a broken spring cartridge, the end cap can be “shot” away during disassembly of the actuator. This can cause serious injury to personnel or damage to material.
DOC.IOM.BE.EN Rev. 9
A.1 Spring load relief
CAUTION: ROTATING ACTUATOR
In case of an actuator/valve assembly “stuck” in mid position, leave the actuator on the valve and/or mounting bracket during this procedure.
Figure A-1 Spring load removal
52
Appendix
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
1. Depressurize the actuator completely.
2. Based on the actuator size, choose the correct threaded rod kit from Table A-1.
3. Replace one by one each end cap screw for the threaded rod kit and turn down the adjusting nut until it touches the end cap.
4. Once all for end cap screws have been replaced, gradually turn the adjustment nuts on threaded rod in CCW direction by turning the nuts half turn at a time. Make sure the rod itself does not turn. Continue this until the load of springs are relieved.
5. Repeat the same procedure for the end cap screws on the other size of the actua­tor as shown in figure A-1.
6. In case of an actuator/valve assembly “stuck” in mid position: The actuator now can be disassembled from Valve, by removing the mounting studs / bolts.
Table A-1. Threaded rod dimensions in mm
Appendix
Actuator size Thread
25 M5 140 5.5 40 M5 140 5.5
65 100 M5 140 5.5 150 M6 145 5.7 200 M6 145 5.7 350 M8 185 7.3 600 M10 950
1600 M12 498 19.6 2500 M12 498 19.6 4000 M14 600 23.6
M5 140
M12 498 19.6
Figure A-2 Spring load removal rod dimensions
Length
Thread
Washer
Threaded Rod
Threaded rod length
(mm) (inch)
5.5
185 7.3
Holding nuts
Adjusting nut
Appendix
53
Appendix
Installation, Operation and Maintenance Manual
Appendix B: Tool & Torque Table
This section explains:
Which tools to use for the indicated fasteners.
The recommended amount of torque to apply on the indicated fasteners.
Table B-1. End cap bolts
DOC.IOM.BE.EN Rev. 9
Actuator
size
25 M5 40 M5 SW 4 2.0 1.6 3.0 1.5 1.2 2.2
65 M5 SW 4 2.0 1.6 3.0 1.5 1.2 2.2 100 M5 SW 4 2.0 1.6 3.0 1.5 1.2 2.2 150 M6 SW 5 3.3 2.6 5.1 2.4 1.9 3.8 200 M6 SW 5 3.3 2.6 5.1 2.4 1.9 3.8 350 M8 SW 6 8.4 6.7 12.2 6.2 4.9 9.0 600 M10 SW 8 15.3 12.2 24.8 11.3 9.0 18.3 950 M12 SW10 24.3 19.4 41.6 17.9 14.3 30.7
1600 M12 SW10 24.3 19.4 41.6 17.9 14.3 30.7 2500 M12 SW10 24.3 19.4 41.6 17.9 14.3 30.7 4000 M14 SW12 43.5 34.8 66.4 32.1 25.7 49.0
Thread Tool Size
SW 4 2.0 1.6 3.0 1.5 1.2 2.2
Allen key
Torque (Nm) Torque (lbf.ft)
Target Min. Max. Target Min. Max.
Table B-2. Bottom Flange
Actuator
size
25
40, 65, 100
150, 200, 350
600
950
1600, 2500
4000
1. For actuator sizes 1600 and 2500 only 4 holes of the ISO5211 F25 drilling pattern are available.
ISO Pattern
F03 inner pattern M5 2.0 3.0 10-24UNC 1.5 2.2
F05 outer pattern M6 4.5 5.0 1/4"-20 3.3 3.7
F05 inner pattern M6 4.5 5.0 1/4"-20 3.3 3.7
F07 outer pattern M8 10.5 12.5 5/16"-18 7.7 9.2
F07 inner pattern M8 10.5 12.5 5/16"-18 7.7 9.2
F10 outer pattern M10 21.0 24.5 3/8"-16 15.5 18.1
F10 inner pattern M10 21.0 24.5 3/8"-16 15.5 18.1
F12 outer pattern M12 34.5 43.0 1/2"-13 25.4 31.7
F10 inner pattern M10 21.0 24.5 3/8"-16 15.5 18.1
F14 outer pattern M16 90.0 104.0 5/8"-11 66.4 76.7
F16 inner pattern M20 170.0 204.0 3/4"-10 125.4 150.5
F25* outer pattern 4x M16 90.0 104.0 4x 5/8"-11 66.4 76.7
F16 inner pattern M20 170.0 204.0 3/4"-10 125.4 150.5
F25 outer pattern 8x M16 90.0 104.0 8x 5/8"-11 66.4 76.7
Metric Torque (Nm) Imperial Torque (lbf.ft)
Thread Min. Max. Thread Min. Max.
54
Table B-3. NAMUR (VDE/VDI 3845) flanges
Flange
Solenoid flange screw threads M5 2.0 3.0 10-24UNC 1.5 2.2
Top flange screw threads M5 2.0 3.0 10-24UNC 1.5 2.2
Metric Torque (Nm) Imperial Torque (lbf.ft)
Thread Min. Max. Thread Min. Max.
Appendix
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
Table B-4. Limit stop screws and nuts
Actuator size Thread
25 M 6 10 10 40 M 8 13 13
65 M 10 17 (16) 100 M 10 17 (16) 150 M 10 17 (16) 200 M 12 19 (18) 350 M 16 24 24 600 M 20 30 30 950 M 22 12 32
1600 M 24 14 36 2500 M 27 17 41 4000 M 22 12 32
1. Default dimension according DIN933 standard.
2. Dimensions in brackets according ISO4017 standard.
Table B-5. Recommended circlip pliers according DIN 5254 (or equal) for shaft circlips
Appendix
Bolt Wrench Nut wrench
size (mm) size (mm)
1
1
1
1
17 (16) 17 (16) 17 (16) 19 (18)
1
1
1
1
Actuator
size
Pinion top
diameter
Pliers
according DIN
Actuator
size
Pinion top
diameter
according DIN
25 - 100 22 mm 0.866" A2 1600 75 mm 2.953" A3
150 - 350 36 mm 1.417" A3 2500 95 mm 3.74" A4
600 55 mm 2.165" A3 4000 96 mm 3.78" A4 950 65 mm 2.559" A3
Table B-6. Angular Displacement Limit Stops
Actuator size
Turns for 5° adjustment of
the pinion:
25 0.7 7.1° 40 0.8 6.3°
65 0.6 8.3° 100 0.7 7.1° 150 1.2 4.2° 200 1 5.0° 350 0.8 6.3° 600 0.8 6.3° 950 1.1 4.7°
1600 1.3 4.1° 2500 1.5 3.4° 4000 3.2 1.6°
360° revolution of limit
stop screw will adjust
Pliers
Appendix
55
Appendix
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
Appendix C: Full Stroke Adjustment Option
This section explains:
How to mount the Full Stroke Adjustment option to an actuator
How to adjust the Full Stroke Adjustment option to a required rotation angle.
C.1 Full Stroke Adjustment Option
The Full Stroke Adjustment option is available as a complete actuator or as an end cap con­version kit in order to upgrade a standard actuator into a Full Stroke Ajdustment version.
The option is available for sizes 25 to 600 and both the double acting kit and spring return kit use the spring return end cap.
Figure C-25 Availability formats of the full Stroke Adjustment option
56
Appendix
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
C.2 Convert a Standard Actuator into a
Full Stroke Adjustment Version
Before starting to assemble the Full Stroke adjustment kit, please check the kit for com­pleteness. See figure C-2.
Figure C-26 Full Stroke adjustment kit content
13
12
Appendix
45 46 11
41 42 43 44
40
9 10
Table C-7 Content Full Stroke Adjustment Kit
Pos. Description Material Qty. Notes
40 End cap - Full stroke adjustment Cast Aluminium alloy 2 1 41 Full Stroke adjustment screw Stainless steel 2 42 Full Stroke adjustment Nut Stainless steel 2 43 Full Stroke adjustment washer PA66 2 44 O-Ring - Full Stroke adjustment screw Nitrile rubber 2 45 O-Ring - Thread bush Nitrile rubber 2 46 Thread bush Aluminium 2
9 End cap screw Stainless steel 8 10 Washer end cap screw Stainless steel 8 11 O-ring end cap Nitrile rubber 2 12 Warning sticker DA Full Stroke adjustment Polyester 2 13 Warning sticker SR Full Stroke adjustment Polyester 2
1. The same Full Stroke adjustment end cap is used for both double acting and spring return actuators (flat double acting actuator end caps with Full Stroke Adjustoment options are not available).
Appendix
57
Appendix
C.2.1 Procedure
1. Remove the existing end caps of a standard actuator.
Follow the instructions of Section 8 to remove both the end caps of the
For spring return actuators; note the original positions of the spring car-
2. Mount the Full Stroke Adjustment End cap kit to the actuator.
3. Grease the O-ring seals (11) according to section 9.1.
4. Ensure that O-ring seals (11) are kept in place during assembly.
5. For spring return actuators; place the spring cartridges (7) back in their original
positions.
6. Install the Full Stroke end cap kits and tighten the end cap screws (9,10). For
spring return units; tighten each endap screw (9,10) in small equal turns and in the sequence as per Figure C-3. Refer to Appendix B, Table B-1 for the correct torque.
7. For Spring Return units, place the black warning sticker (13) on the end cap. For
Double Acting units, place the white warning sticker (12) on the end cap.
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
actuator.
tridges.
Figure C-27 Assembly of Full Stroke adjustment end cap kit
11
11
11
11
7
12
13
10
40
9
40
2
9
10
3
9
10
40
9
10
40
58
1
4
Appendix
Installation, Operation and Maintenance Manual
DOC.IOM.BE.EN Rev. 9
C.3 Full Stroke Adjustment Setting
Note:
Standard actuators or actuators with the Full Stroke Adjustment option are shipped by default with a rotation setting of 90° +/-0.5°.
The stroke adjustment setting procedure can be two steps:
1. Setting the Full Stroke Adjustment screw to the 90° (factory) positon.
This step is applicable if a standard actuator is converted with a Full Stroke
Adjustment end cap kit or if the position of the Full Stroke Adjustment screw is somehow lost.
2. Setting the Full Stroke Adjustment screw to the required angle.
C.3.1 Factory Setting Procedure
Appendix
1. In order to set the Full Stroke Adjustment Screws accurately to the outward posi-
tion:
Do not change the setting of the DSA limit stop screws (A and B) located
above the air connection interface.
Move the pistons of the actuator outwards by applying pressure to the
A-port.
2. Screw in both the Full Stroke Adjustment Screws (41) until the screws touch the
pistons. You will feel an obstruction.
Important: Do not overtighten the screws.
Figure C-28 DSA limit stop screw setting
A
41
B
41
A-port
Appendix
You have now set the adjustment screw to the factory setting
Notes:
1. Only the outward stroke can be adjusted with the Full Stroke Adjustment screws.
In case of assembly code CW, the left side limit stop (A) is redundant.
In case of assembly code CC, the right side limit stop (B) is redundant.
2. For the inward stroke the standard limit stops can be used:
The right side limit stop (B) for assembly code CW
The left side limit stop (A) for assembly code CC
59
Appendix
Installation, Operation and Maintenance Manual
C.3.2 Setting the Full Stroke Adjustment Screw
to the Required Angle
1. Move the pistons of the actuator inwards.
For Spring Return actuators this happens automatically when the actuator
is vented.
For double acting actuators vent the A-port and apply pressure to
the B-port.
2. In order to set the actuator to the required angle, use next table to define the
number of revolutions which you have to turn in the Full Stroke Adjustment Screws.
3. Turn in both the adjustment screws (41) as defined in step 2. Both the adjustment
screws should be turned in with the same length or number of revolutions.
CAUTION: DO NOT SET SCREWS UN-EQUAL
DOC.IOM.BE.EN Rev. 9
Screwing in only one adjustment screw or un-equal setting of both the screws will lead to high point loads on the pistons and can cause premature failure of the actuator.
4. Test cycle the actuator to check if the correct rotation angle is set. If required,
repeat steps 1 to 3 to adjust the rotation angle to the required angle.
Table C-8 Actuator angle rotation per full revolution of Full Stroke adjustment screw
Actuator
size
25 15.7 0.62 1.0 x 5.5 M6 1 5.7° 40 18.8 0.74 1.2 x 6.5 M8 1.25 6.0° 65 22.0 0.87 1.2 x 6.5 M8 1.25 5.1°
100 25.1 0.99 1.2 x 6.5 M10 1.5 5.4° 150 31.4 1.24 1.2 x 6.5 M10 1.5 4.3° 200 37.7 1.48 1.2 x 6.5 M10 1.5 3.6° 350 37.7 1.48 1.2 x 6.5 M12 1.75 4.2° 600 44.0 1.73 1.2 x 6.5 M16 2 4.1°
Stroke
mm inch Thread Pitch (mm)
Flathead
screw driver
Screw
Actuator angle rotation per
full revolution of screw
60
Appendix
World Area Configuration Centers (WACC) offer sales support, service, inventory and commissioning to our global customers. Choose the WACC or sales office nearest you:
NORTH & SOUTH AMERICA
19200 Northwest Freeway Houston TX 77065 USA T +1 281 477 4100
Av. Hollingsworth 325 Iporanga Sorocaba SP 18087-105 Brazil T +55 15 3413 8888
ASIA PACIFIC
No. 9 Gul Road #01-02 Singapore 629361 T +65 6777 8211
No. 1 Lai Yuan Road Wuqing Development Area Tianjin 301700 P. R. China T +86 22 8212 3300
For complete list of sales and manufacturing sites, please visit
www.emerson.com/actuationtechnologieslocations or contact us at info.actuationtechnologies@emerson.com
MIDDLE EAST & AFRICA
P. O. Box 17033 Jebel Ali Free Zone Dubai T +971 4 811 8100
P. O. Box 10305 Jubail 31961 Saudi Arabia T +966 3 340 8650
24 Angus Crescent Longmeadow Business Estate East P.O. Box 6908 Greenstone 1616 Modderfontein Extension 5 South Africa T +27 11 451 3700
EUROPE
Holland Fasor 6 Székesfehérvár 8000 Hungary T +36 22 53 09 50
Strada Biffi 165 29017 Fiorenzuola d’Arda (PC) Italy T +39 0523 944 411
www.emerson.com/bettis
©2019 Emerson. All rights reserved.
The Emerson logo is a trademark and service mark of Emerson Electric Co. BettisTM is a mark of one of the Emerson family of companies. All other marks are property of their respective owners.
The contents of this publication are presented for information purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available on request. We reserve the right to modify or improve the designs or specifications of our products at any time without notice.
Loading...