Bettis Bettis 2000 Series M2CP Digital Futronic Manuals & Guides

Page 1
Installation, Operation and Maintenance Manual
MAN-02-04-55-0735-EN Rev. 0
Bettis 2000 Series M2CP User Manual
July 2019
Page 2
Page 3
Installation, Operation and Maintenance Manual
MAN-02-04-55-0735-EN Rev. 0
Table of Contents
Section 1: Introduction
Section 2: Features and Specifications
Section 3: Installation and Wiring
Section 4: Module Setup and Calibration
4.1 Indicator Lights ............................................................................................. 6
4.1.1 LED 1 .................................................................................................. 6
4.1.2 LED 2 .................................................................................................. 6
4.2 Number Display (Firmware Version and Digital Futronic Type) ....................... 6
4.2.1 Firmware Version Number Display ...................................................... 6
4.2.2 Digital Futronic Number Type Display (New for Ver 4.6) ...................... 7
4.3 Setup ............................................................................................................ 7
4.3.1 Normal Run Mode (S1, S2, S3, S4 OFF) ............................................... 7
4.3.2 Cal Analog Input (S1 ON) .................................................................... 8
4.3.3 Cal Analog Output Zero (S2 ON) ......................................................... 8
4.3.4 Cal Analog Output Span (S3 ON) ........................................................ 8
4.3.5 Set Modulation Delay (S1, S2 ON) ....................................................... 9
4.3.6 Set Default Position (S2 & S3 ON) ....................................................... 9
4.3.7 Invert Analog I/O (S1, S2 & S3 ON) .................................................... 10
4.3.8 Double Deadband (S1 & S3 ON)........................................................ 10
4.3.9 2% Deadband (S1, S3, S4 ON) ........................................................... 11
4.3.10 Pulsing Control (S1, S2, S3, S4, S6 ON & S5 OFF) ...............................12
4.4 Mode Selection ........................................................................................... 13
4.5 Calibration Procedures ................................................................................ 14
4.5.1 Calibrate Analog Input (Position Command Signal) .......................... 14
4.5.2 Calibrate Analog Output (Position Feedback) ................................... 15
4.5.3 Select Modulation Delay Time .......................................................... 15
4.5.4 Enable/Disable Go-To-Position on Loss of Signal ............................... 16
4.5.5 Set Default Position (Position of valve on
loss of analog input signal when S4 enabled) .................................... 16
4.5.6 Assign Digital Futronic Type (New for Ver 4.6) .................................. 17
4.5.7 Calibrate To Limits (New for Ver 4.6) ................................................. 17
Table of Contents
Table of Contents
Appendix A: Definitions
I
Page 4
Section 1: Introduction
This document covers the current Digital Futronic firmware version (Ver 4.6 released July 2019) and also references previous versions where applicable.
Section 1: Introduction
The Digital Futronic module uses the latest integrated microcontroller technology to enable one electronics module to perform valve actuator modulating and positioning control from analog control signals. The control module uses Bettis’s M2CP TBM01 termination panel for interface of all analog control types. The Digital Futronic module converts 4-20mA analog input to digital for processing and from digital to 4-20mA analog output for position feedback. The Digital Futronic module controls four Bettis motor control starter types.
1. Futronic II Electro-mechanical AC motor starter
2. Futronic III SCR H-Bridge Solid-state DC motor starter (Powered by 115VAC, 1-Ph)
3. Futronic IV Triac Solid-state (SSR) AC motor starter
4. Futro nic VII MOSFET Solid-state pure DC motor starter (Powered by 24VDC or 48VDC)
Installation, Operation and Maintenance Manual
MAN-02-04-55-0735-EN Rev. 0
CAUTION
When downloading rmware to the Digital Futronic circuit board using the Programming
Header device, part number VA37696 (See Figure 1 below) or reading EEPROM, the following conditions are required to validate rmware download.
1. Actuator is NOT fully closed (LSC is not active)
2. Actuator is NOT fully open (LSO is not active)
3. Selector Switch must be in OFF Position
4. DIP 1 is OFF
5. DIP 2 is OFF
6. DIP 3 is OFF
7. DIP 4 is OFF
When calibrating and/or conguring the Digital Futronic circuit board, the following conditions are required to validate the conguration calibration process.
1. Programming Header device must NOT be connected to the board
2. Selector switch must NOT be in REMOTE position.
Figure 1
1
Introduction
Page 5
Installation, Operation and Maintenance Manual
MAN-02-04-55-0735-EN Rev. 0
Section 2: Features and Specifications
Section 2: Features and Specications
Digital microcontroller adapts to any actuator and valve size, speed/stroke-time, process pressure, etc. by automatically tuning controls to obtain maximum accuracy without any user adjustments for deadband, delay time, etc.
Automatic calibration of position input to valve travel limits when selector switch is position at LOCAL MODE.
Built-in protection for motor and motor controls.
DC motor speed control for Futronic III and Futronic VII.
Easy setup and calibration to user’s external analog control signal input and analog feedback output. All setup and calibration adjustments by on-board DIP switches and two miniature push buttons. When selector switch is at OFF position only.
LED indicators for normal/fault operating conditions, setup mode, loss of analog signal, and solid-state motor control output.
Isolated Analog Input: 4-20mA with 12-bit (.025%) resolution (calibration range of 0-24mA). 210 Ohms input resistance. Operates from 10V to 32V loop supply. Allows up to 750 Ohms loop resistance at 24V.
Isolated Analog Output: 4-20mA with 16-bit (.0015%) resolution (calibration range of 0-24mA). Drive loop resistance up to 750 Ohms. True current source with internal 24VDC power supply. No external power source required to power loop. Internal automatic resetting fuse for 24VDC power supply.
Isolation dielectric strength: 2500V AC for 1 Minute (Input to output and I/O to ground).
Inverted Analog I/O Option: where 20mA = close valve position and 4mA = open valve position.
Go To Default Position Option: On loss of control signal, user selected default valve position anywhere between 0 and 100%.
Table 1.
Futronic II mode +/- 1.0% @ 15 second stroke time or greater
Control Accuracy
Nonlinearity <0.05% of calibrated analog input and output over full range of 0-100%. Operating
Temperature Range
Humidity 10% - 95% (Non-condensate)
Futronic III mode +/- 0.25% @ 15 second stroke time or greater Futronic IV mode +/- 0.5% @ 15 second stroke time or greater Futronic VII mode +/- 0.25% @ 15 second stroke time or greater
-40 °C to +85 °C (-40F to +185F)
Features and Specifications
2
Page 6
Section 3: Installation and Wiring
Installation, Operation and Maintenance Manual
Section 3: Installation and Wiring
Refer to the wiring diagram supplied with the actuator for wiring details and options supplied with the system. Figure 2 below is generic and provided primarily for wiring 4-20mA analog input and output signals. Refer to Figure 2 for proper wiring of analog I/O and associated polarities relative to external equipment and power supplies. Use the following rules when wiring analog I/O signals.
1. Route analog I/O cables into actuator enclosure through separate conduit entries from power wiring.
2. Always use twisted-pair instrumentation cable for wiring 4-20mA analog input and output signals.
3. Use shielded cable when analog signals are being installed in or routed through high noise areas.
4. If shielded cable is used, earth ground the shield by connecting only one end of the shield to earth.
5. Instruments or control equipment must source current to the analog input of the Digital Futronic.
6. Remote current source to analog input must have own power source, or an external supply is required.
7. Do not connect an external power source to the 4-20mA analog output of the Digital Futronic module.
8. The Digital Futronic module contains its own internal 24VDC power supply for the 4-20mA output and sources current to external instruments or control equipment.
MAN-02-04-55-0735-EN Rev. 0
3
Installation and Wiring
Page 7
Installation, Operation and Maintenance Manual
MAN-02-04-55-0735-EN Rev. 0
Figure 2 TBM01 Futronic Wiring
Section 3: Installation and Wiring
NOTE:
Refer to wiring diagram supplied with actuator for wiring details and options.
Important
Jumper J8 located on the bottom of TBM01 must be in the 24V position before the Digital Futronic card will operate.
Installation and Wiring
4
Page 8
Section 4: Module Setup and Calibration
Installation, Operation and Maintenance Manual
MAN-02-04-55-0735-EN Rev. 0
Section 4: Module Setup and Calibration
DIP Switch SW3 has 6 switches designated as S1-S6 for calibration and mode selection as summarized below. There are two miniature push buttons labeled UP and DOWN. Refer to Figure 3 for location of DIP switches and push buttons. Switches S1-S4 are used for setup and calibration and switches S5-S6 are used for mode selection. If any one or more of switches S1, S2, S3, S4 are on, the actuator is in setup mode. The actuator returns to normal operating mode when all three switches S1-S3 are turned off. When changing from setup mode to normal operating mode, do not turn off power to the actuator for at least 120 seconds to allow the controller to store the new setup values to EEPROM nonvolatile
memory. Setup and normal operating modes are designated by LED 1 as dened below.
Figure 3 Locations of DIP switches and Push-buttons
5
Module Setup and Calibration
Page 9
Installation, Operation and Maintenance Manual
MAN-02-04-55-0735-EN Rev. 0
Section 4: Module Setup and Calibration
4.1 Indicator Lights
4.1.1 LED 1
Slow Flash = Normal Operating Mode.
Rapid Flash = Setup mode (any one of switches S1 through S3 are on).
Alternating Between Slow and Rapid Flash = Lost Analog Input (Command) Signal.
Steady On or Steady Off = Module failure.
4.1.2 LED 2
On when Solid State Relay (SSR or SCR) is On (control power applied to output).
4.2 Number Display (Firmware Version and
Digital Futronic Type)
4.2.1 Firmware Version Number Display
Each time the actuator is powered up, the rmware version number is displayed by LED1 with the following sequence of ashes.
At power up, LED1 stays on for 4 seconds and then begins to ash. Count the number of times the LED ashes on before it turns on solid again for 2 seconds. The number of ashes is the high order rmware version number.
After a 2-second solid on delay, the LED will begin to ash again. Count the number of ashes until the LED turns on solid again for 4 seconds. The number of ashes is the low order rmware version number. After the 4-second delay, LED1 will then ash at the normal rate dened under Indicator Lights above.
If unable to correctly count the number of ashes to properly determine the rmware
version number, then cycle power to the actuator and the display process will repeat.
Module Setup and Calibration
6
Page 10
Section 4: Module Setup and Calibration
Installation, Operation and Maintenance Manual
MAN-02-04-55-0735-EN Rev. 0
4.2.2 Digital Futronic Number Type Display (New for Ver 4.6)
Digital Futronic rmware Ver 4.6 will display additional information on LED1 following ash
sequence shown in 4.2.1. On power up, LED1 will display Actuator Type which is currently
congured after it displays rmware version.
The LED ashes the actuator type as shown below before it turns on solid again for 2 seconds.
DF II, 2 Flashes
DF III, 3 Flashes
DF IV, 4 Flashes
DF VIII, 7 Flashes
NOTE
LED1 ash sequence for Firmware Version and Digital Futronic type will display every
startup (or power cycle).
4.3 Setup
4.3.1 Normal Run Mode (S1, S2, S3, S4 OFF)
Turn off S1, S2, S3 & S4 for Normal Run Mode - Figure 4.
Figure 4
7
Module Setup and Calibration
Page 11
Installation, Operation and Maintenance Manual
MAN-02-04-55-0735-EN Rev. 0
Section 4: Module Setup and Calibration
4.3.2 Cal Analog Input (S1 ON)
Press UP to set Span (20mA) Input - Figure 5.
Press DOWN button to set Zero (4mA) Input - Figure 5.
Figure 5
4.3.3 Cal Analog Output Zero (S2 ON)
Press UP to increase (4mA) Output - Figure 6.
Press DOWN to decrease (4mA) Output - Figure 6.
Figure 6
4.3.4 Cal Analog Output Span (S3 ON)
Press UP to increase (20mA) Output - Figure 7.
Press DOWN to decrease (20mA) Output - FIgure 7.
Figure 7
Module Setup and Calibration
8
Page 12
Section 4: Module Setup and Calibration
Installation, Operation and Maintenance Manual
4.3.5 Set Modulation Delay (S1, S2 ON)
Press UP to select 3-Ph motor (delay = 2 sec) - Figure 8.
Press DOWN to select 1-Ph motor (delay = 12 sec) - Figure 8.
Figure 8
4.3.6 Set Default Position (S2 & S3 ON)
Press UP or DOWN to accept applied analog input (setpoint) as default position - Figure 9.
Figure 9
MAN-02-04-55-0735-EN Rev. 0
9
Module Setup and Calibration
Page 13
Installation, Operation and Maintenance Manual
MAN-02-04-55-0735-EN Rev. 0
Section 4: Module Setup and Calibration
4.3.7 Invert Analog I/O (S1, S2 & S3 ON)
Press UP to Select Inverted Mode - Figure 10.
Press DOWN to Disable Inverted Mode - Figure 10.
Figure 10
4.3.8 Double Deadband (S1 & S3 ON)
Press UP to Double control deadband dened. See Note (1) - Figure 11.
Press DOWN to Return deadband to default values - Figure 11.
Figure 11
NOTE
New for rmware Ver 4.6, default Double Deadband setting is 1%.
Module Setup and Calibration
10
Page 14
Section 4: Module Setup and Calibration
Installation, Operation and Maintenance Manual
4.3.9 2% Deadband (S1, S3, S4 ON)
Press UP to Select 2% control deadband. See Note (2) - Figure 12.
Press DOWN to Select 1.5% control deadband - Figure 12.
Figure 12
NOTE:
(1) Doubling the control deadband (bandwidth) reduces control accuracy by twice the
values stated on Page 1. Use this function only for difcult to control applications. Doubling
the deadband affects accuracy of all four versions of actuator operating controls, as follows:
Default Double
Futronic II mode +/- 1.0% +/- 2.0% Futronic III mode +/- 0.25% +/- 0.5% Futronic IV mode +/- 0.5% +/- 1.0% Futronic VII mode +/- 0.25% +/- 0.5%
MAN-02-04-55-0735-EN Rev. 0
(2) 2% Deadband (bandwidth) affects accuracy of Futronic III, IV & VII only, as below.
UP button DOWN button
Futronic II mode NA NA Futronic III mode +/- 2% +/- 1.5% Futronic IV mode +/- 2% +/- 1.5% Futronic VII mode +/- 2% +/- 1.5%
11
Module Setup and Calibration
Page 15
Installation, Operation and Maintenance Manual
MAN-02-04-55-0735-EN Rev. 0
Section 4: Module Setup and Calibration
4.3.10 Pulsing Control (S1, S2, S3, S4, S6 ON & S5 OFF)
Press UP to Select Pulsing Control - Figure 13.
Press DOWN to Disable Pulsing Control to default values - Figure 13.
Figure 13
NOTE
New for rmware Ver 4.6, default setting for Pulsing Control is OFF/Disabled. ON/Enabled Pulsing Control not recommended for Digital Futronic II, III and VII for any operating condition, or Futronic IV when either the input command signal is constantly changing, or stroke time is greater than one (1) minute. ON/Enabled Pulsing Control directs actuator to continue operation (motor power cycles on and off) within the control bandwidth of setpoint.
Module Setup and Calibration
12
Page 16
Section 4: Module Setup and Calibration
4.4 Mode Selection
S4 ON = Go to Default Position on loss of analog input control signal - Figure 14. S4 OFF = Stay put on loss of analog input control signal - Figure 14.
Figure 14
S5 OFF and S6 OFF > Select Futronic II mode - Figure 15.
(Electromechanical motor starter) - Figure 15.
Figure 15
Installation, Operation and Maintenance Manual
MAN-02-04-55-0735-EN Rev. 0
S5 ON and S6 OFF > Select Futronic III mode - Figure 16. (SCR solid-state DC motor starter) - Figure 16.
Figure 16
S5 OFF and S6 ON > Select Futronic IV mode - Figure 17.
(Triac solid-state (SSR) motorstarter) - Figure 17.
Figure 17
S5 ON and S6 ON > Select Futronic VII mode - Figure 18.
(MOSFET solid-state (SSR) motor starter) - Figure 18.
Figure 18
13
Module Setup and Calibration
Page 17
Installation, Operation and Maintenance Manual
MAN-02-04-55-0735-EN Rev. 0
Section 4: Module Setup and Calibration
4.5 Calibration Procedures
CAUTION
Place selector switch in “OFF” position before calibrating actuator.
4.5.1 Calibrate Analog Input (Position Command Signal)
1. Connect 4-20mA calibration source to TBM Terminals 52 (-) and 53 (+).
2. Set S1 to ON (up) position. Apply 4mA zero calibration signal and then press DOWN push button.
3. Apply 20mA full-scale (span) calibration signal and then press UP push button.
4. Return S1 to OFF (down) position.
NOTE:
When S1 is ON, the analog input signal is fed to the analog output. A current meter may be connected to TBM terminals 50(-) and 51(+) to monitor the analog input at the output.
Module Setup and Calibration
14
Page 18
Section 4: Module Setup and Calibration
Installation, Operation and Maintenance Manual
MAN-02-04-55-0735-EN Rev. 0
4.5.2 Calibrate Analog Output (Position Feedback)
1. Connect calibrated 4-20mA meter to TBM Terminals 50 (-) and 51 (+).
2. Set S2 to ON (up) position.
3. Press UP or DOWN push button to increase or decrease zero (4mA) analog output signal.
4. Return S2 to OFF (down) position.
5. Set S3 to ON (up) position.
6. Press UP or DOWN push button to increase or decrease full-scale (20mA) analog signal.
7. Return S3 to OFF (down) position.
4.5.3 Select Modulation Delay Time
1. Set S1 and S2 to ON (up) position.
2. Press UP push button to select 3-Phase motor (Modulation delay = 2 seconds).
3. Press DOWN push button to select 1-Phase motor (Modulation delay = 12 seconds).
4. Return S1 and S2 to OFF (down) position.
15
Module Setup and Calibration
Page 19
Installation, Operation and Maintenance Manual
MAN-02-04-55-0735-EN Rev. 0
Section 4: Module Setup and Calibration
4.5.4 Enable/Disable Go-To-Position on Loss of Signal
1. Set S4 ON (up) to Enable Go-To-Position on loss of signal.
2. Set S4 OFF (down) to Disable Go-To-Position on loss of signal, i.e. Stay in last position on loss of signal.
4.5.5 Set Default Position (Position of valve on loss of analog input signal when S4 enabled)
NOTE:
If it is desirable for the valve to move to position while setting the default position then place the selector switch in the “REMOTE” position, else leave the selector in the “OFF” position to prevent the valve from moving.
1. Connect 4-20mA calibration source to TBM Terminals 52 (-) and 53 (+).
2. Set S2 and S3 to ON (up) position.
3. Apply calibration signal for the desired position (4-20mA or 0-100%).
4. Press either UP or DOWN push button to accept the analog input as the default position.
5. Return S2 and S3 to OFF (down) position.
Calibrate To Limits: (firmware Ver 4.2 and below only, see 4.5.7 for firmware Ver 4.6: When setup is complete, place selector switch in “Local” mode and stroke valve from limit to limit for two full strokes. This allows the controller to calibrate the analog position feedback to the position limits before operation in remote control mode.
Module Setup and Calibration
16
Page 20
Section 4: Module Setup and Calibration
Installation, Operation and Maintenance Manual
MAN-02-04-55-0735-EN Rev. 0
4.5.6 Assign Digital Futronic Type (New for Ver 4.6)
Firmware Ver 4.6 requires the Digital Futronic type to be actively congured. Previous rmware Ver 4.2 and below only require setting the DIP Switches S5 and S6.
1. Set DIP Switches S5 and S6 (See Table 1) to assign Digital Futronic type.
2. Set S1 and S4 to ON (up) position.
3. Set S2 and S3 to OFF (down) position.
4. Selector Switch in OFF
5. Press UP push button to accept the actuator type conguration.
Digital Futronic Type DIP Switch Position Reference Section 4.4 (Figure)
DF III 5 ON, 6 OFF Fig 16
DF IV 5 OFF, 6 ON Fig 17
DF VII 5 ON, 6 ON Fig 18
4.5.7 Calibrate To Limits (New for Ver 4.6)
Firmware Ver 4.6 requires the Digital Futronic actuator position limits to be congured and veried by using a push button.
6. Set S1, S2, S3, and S4 to OFF (down) position.
7. Place selector switch in Local.
8. Stroke Valve to fully open and fully close at least once.
Analog Position Feedback Fully Open (LSO Active)
1. Stroke Valve a second time to Fully Open
2. Press UP Push Button until LED1 display pattern ash rate changes
Analog Position Feedback Fully Close (LSC Active)
1. Stroke Valve to Fully Close a second time
2. Press DOWN Push Button until LED1 display pattern ash rate changes
17
Module Setup and Calibration
Page 21
Installation, Operation and Maintenance Manual
MAN-02-04-55-0735-EN Rev. 0
Appendix A: Denitions
Command = 4-20mA analog input position command signal generated by remote
control equipment. Same as position command setpoint. Zero and Full-scale calibrated by user.
Position = 0-5V valve position analog input signal generated by Hall-effect
Position Sensor (HPS). Zero and Full-scale automatically calibrated by controller based on LSC and LSO valve travel limit switches.
Feedback = 4-20mA analog output signal for feedback of valve position to remote
control equipment. Zero and Full-scale calibrated by user.
Invert = Inverted calibration of 4-20mA command where close position = 20mA,
and open position = 4mA. Feedback is also inverted.
Deadband = Allowable error tolerance to keep valve stopped, i.e. do not turn on
motor control outputs. Deadband can be congured by the user as the dened
default values or double the default values or 2% or 1.5%. Deadband has a beginning default value based on selected operating mode (motor starter type) and then controller automatically adjusts the deadband to obtain the best accuracy.
Default deadband based on motor starter type:
a. Futronic II = +/-1.0% deadband
b. Futronic III = +/-0.25% deadband
c. Futronic IV = +/-0.50% deadband
Appendix
Error = Difference between Command and Position.
Error = Command-Position If not Invert and Error = Positive then open valve If not Invert and Error = Negative then close valve If Invert and Error = Positive then close valve If Invert and Error = Negative then open valve
Nonlinearity = Difference between analog input and analog output at current
valve position over the full valve operating range.
Close Coast = Difference between Position when the motor is turned off and
Position when the valve stops moving in the close direction. Coast is caused by both inertia of the motor and latency of Position update due to analog input
ltering. The controller measures close coast to automatically tune control for
maximum accuracy.
Appendix
18
Page 22
Appendix
Installation, Operation and Maintenance Manual
MAN-02-04-55-0735-EN Rev. 0
Open Coast = Difference between Position when the motor is turned off and
Position when the valve stops moving in the open direction. The controller measures open coast to automatically tune control for maximum accuracy.
Modulation Delay = Time between when the motor is turned off until the motor
can be started again. This delay prevents excessive number of starts of the motor, preventing overheating the motor and premature burnout of the reversing contactor. Modulation delay also prevents valve plugging when the actuator reverses direction. If a three phase motor is used, the delay time is 2 seconds or 1800 starts per hour. If a single phase, capacitor start, AC motor is used, then the delay is 12 seconds or 300 starts per hour. The delay between motor control pulses while the valve is being jogged to position is automatically reduced to one second.
Turn-off Delay = 10 Seconds = Delay after motor stops before turning off Open
or Close reversing contactor outputs unless a reversal in direction is required. If reversal in direction, then Modulation Delay time is used. Valid only when Futronic III or Futronic IV modes are selected. This delay prevents excessive operation of the contactor while modulating or the 4-20mA command signal is being ramped by a PID control loop.
Accel = Time required to accelerate motor speed from zero to full speed when
motor is started due to Error greater than Deadband. The purpose of Accel is to soft-start the motor and to help prevent control overshoot when making small position changes. Accel is inversely proportional to Error and is automatically adjusted by the controller.
Decel = Time required to decelerate motor speed from full speed to zero while
Position is approaching Command position setpoint. Valid only when Futronic III or Futronic IV modes are selected. Decel is proportional to Error. If motor is at full speed (Accel time expired) and Error is less than tuned parameter then the controller begins decelerating motor speed over a period of time where Decel = (Error-Deadband)*T Sec. Decel is activated only when Accel time has expired. This prevents motor stall when making small position changes. If Error is less than Deadband then Decel = 0.
DC Motor Speed Control = Full speed of the motor is set at the factory using a
potentiometer on the SCR motor control module. The Digital Futronic module regulates full speed of the motor, maintaining accurate speed/valve travel time regardless of high or low power line conditions and varying load conditions. Valid only for Futronic III.
19
Appendix
Page 23
Page 24
World Area Configuration Centers (WACC) offer sales support, service, inventory and commissioning to our global customers. Choose the WACC or sales office nearest you:
NORTH & SOUTH AMERICA
19200 Northwest Freeway Houston TX 77065 USA T +1 281 477 4100
Av. Hollingsworth 325 Iporanga Sorocaba SP 18087-105 Brazil
MIDDLE EAST & AFRICA
P. O. Box 17033 Jebel Ali Free Zone Dubai T +971 4 811 8100
P. O. Box 10305 Jubail 31961 Saudi Arabia T +966 3 340 8650
T +55 15 3413 8888
24 Angus Crescent
ASIA PACIFIC
Longmeadow Business Estate East
P.O. Box 6908 Greenstone No. 9 Gul Road #01-02 Singapore 629361 T +65 6777 8211
No. 1 Lai Yuan Road
1616 Modderfontein Extension 5
South Africa
T +27 11 451 3700
EUROPE
Wuqing Development Area Tianjin 301700 P. R. China T +86 22 8212 3300
Holland Fasor 6
Székesfehérvár 8000
Hungary
T +36 22 53 09 50
Strada Biffi 165
29017 Fiorenzuola d’Arda (PC)
Italy
T +39 0523 944 411
For complete list of sales and manufacturing sites, please visit
www.emerson.com/actuationtechnologieslocations or contact us at info.actuationtechnologies@emerson.com
www.emerson.com/bettis
©2019 Emerson. All rights reserved.
The Emerson logo is a trademark and service mark of Emerson Electric Co.
TM
is a mark of one of the Emerson family of companies.
Bettis All other marks are property of their respective owners.
The contents of this publication are presented for information purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available on request. We reserve the right to modify or improve the designs or specifications of our products at any time without notice.
Loading...