Best UT340, UT3100, UT360, UT380 Installation Manual

U N I T Y / I
Three-Phase Uninterruptible Power Systems
UT340, UT360, UT380, UT3100
60 Hz
Planning and
Installation Manual
LTM-0357A Copyright 1995, Best Power Technology, Inc.
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions for your
The installation and use of this product must comply with all national, federal, state, municipal, or local codes that apply. If you need help, please call BEST’s Technical Support Center at
1-800-356-5737
WARNING!
UPS units contain hazardous AC and DC voltages. A qualified electrician must install the UPS, AC line service, and external batteries according to local and national codes and must be familiar with batteries and battery installation.
Before installing, maintaining, or servicing the UPS, shut off the UPS and disconnect all sources of AC and DC power.
Whenever AC and/or DC voltage is applied, there may be AC voltage at the UPS output; this is true because the UPS can supply output power from mains or from its batteries. To avoid equipment damage or personal injury, always assume that there may be voltage at the UPS output.
(U.S.A. or Canada; elsewhere, call your local BEST office).
UNITY
/I™ UPS.
TEST BEFORE TOUCHING!
To reduce the risk of fire or electric shock, install the UPS and external batteries in a temperature and humidity controlled indoor area, free of conductive contaminants.
UPS batteries are high current sources. Shorting battery terminals or DC terminal strips can cause severe arcing, equipment damage and injury. A short circuit can cause a battery to explode. Always wear protective clothing and eye protection and use insulated tools when working near batteries.
This unit contains components that are sensitive to electrostatic discharge (ESD). If you do not follow proper ESD procedures, you may cause severe damage to electronic components.
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
Table of Contents
List of Tables and Figures...............................................ii
100: Introduction...........................................................1
101: UPS Footprint.....................................................2
102: Specifications for the UT340 and UT360................................3
103: Specifications for the UT380 and UT3100...............................5
104: Receiving and Moving the UPS.......................................7
105: Storing the UPS and Batteries........................................8
106: Finding a Location for the UPS.......................................8
107: Technical Support..................................................9
200: Installation............................................................9
201: Installing the Maintenance Bypass Cabinet (MBC) and UPS...............10
202: Installing the External Batteries and DC Disconnect (DCD)................18
300: Initial Startup and Phase Check..........................................22
301: Initial Startup and Phase Check
for Units with a BEST-Supplied Rotary Switch MBC.....................23
302: Initial Startup and Phase Check
for Units with a BEST-Supplied Three-Breaker MBC.....................26
400: Clearing the Events Log................................................29
500: Shutdown Procedures..................................................29
501: Shutdown Procedure for Units with a BEST-Supplied Rotary Switch MBC....30
502: Shutdown Procedure for Units with a BEST-Supplied Three-Breaker MBC...30
600: Startup from Maintenance Bypass........................................31
601: Startup from Maintenance Bypass with a BEST-Supplied Rotary Switch MBC.31 602: Startup from Maintenance Bypass with a BEST-Supplied Three-Breaker MBC.32
700: Glossary of Terms and Abbreviations......................................33
701: Glossary of Terms.................................................33
702: Abbreviations....................................................34
i
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
List of Tables and Figures
Tables
1 AC Input Specifications, UT340 and UT360.....................................3
2 AC Output Specifications, UT340 and UT360...................................3
3 DC Input/Battery Specifications, UT340 and UT360..............................4
4 General Specifications, UT340 and UT360......................................4
5 AC Input Specifications, UT380 and UT3100....................................5
6 AC Output Specifications, UT380 and UT3100..................................5
7 DC Input/Battery Specifications, UT380 and UT3100.............................6
8 General Specifications, UT380 and UT3100.....................................6
Figures
1 Footprint of the UT340, UT360, UT380, UT3100
with Conduit Connection Kit (Top View)...................................2
2 Front View (Covers Removed)..............................................11
3 UT340 - UT3100 Installation Wiring Diagram,
Typical Installation With No Maintenance Bypass Cabinet.....................12
4 UT340 and UT360 Installation Wiring Diagram, Typical Installation................13
5 UT380 and UT3100 Installation Wiring Diagram, Typical Installation...............14
6 External Connection Board.................................................15
7 Communication Interface Board (Option)......................................16
8 Relay Board (Option)......................................................17
ii
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
Section 100: Introduction
An uninterruptible power system (UPS) protects sensitive equipment against unacceptable disturbances from the mains (AC line) supply. The to serve a wide variety of electrical equipment— from mainframe computers to enterprise-wide EDP installations to production lines. The single-conversion technology and harmonics isolation.
UNITY
UNITY
/I three-phase UPS provides true on-line,
/I™ three-phase UPS has the capacity
Only a the electrician guidelines for:
If you need assistance, please have the UPS model number and serial number available and call BEST’s Technical Support Center at 1-800-356-5737 (U.S.A. or Canada) or call your local BEST office.
qualified electrician
installation wiring. external battery installation. UPS startup procedures. phase check for the maintenance bypass cabinet (MBC). UPS shutdown procedures.
should install this unit. The planning and installation manual gives
1
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
101 UPS Footprint
Figure 1: Footprint of the UT340, UT360, UT380, UT3100
with Conduit Connection Kit (Top View)
CONDUIT
CONNECTION
BOX
CABLE ENTRY
Inches Millimeters A B C D E F
39.4 1000
17.9 455
19.8 504
27.9 708
31.7 804
2.4 60
Allow a minimum of 3 feet (914 mm) at the front of the unit, 3 feet (914 mm) at the top of the unit, and 6 inches (152 mm) at the back of the unit for service clearance and for air flow.
Cable entry from bottom only. The conduit connection kit includes a conduit connection
box and three pedestals, shipped separately. See installation instructions shipped with kit.
2
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
102 Specifications for the UT340 and UT360
Tables 1 - 4 contain specifications for UPS models UT340 and UT360.
Table 1: AC Input Specifications, UT340 and UT360
UT340 UT360
Voltage 3 x 208Y/120 3 x 480Y/277 3 x 208Y/120 3 x 480Y/277 Rated input current - Amps 146 63 219 95 Mains tolerance % (programmable) +10, -15 +10, -15 +10, -15 +10, -15 Bypass tolerance % (programmable) ±10 ±10 ±10 ±10 Frequency - Hz 60 ±6% 60 ±6% 60 ±6% 60 ±6% Current distortion % - THD 0 - 5 0 - 5 0 - 5 0 - 5 Acceptable cable size range - AWG
1, 2, 3
Recommended overcurrent protection -
3, 4
Amps
3/0 - 250 kcmil 4 - 2 300 - 500 kcmil 1 - 2/0
200 80 300 125
Table 2: AC Output Specifications, UT340 and UT360
UT340 UT360
Voltage 208Y/120 480Y/277 208Y/120 480Y/277 Rated output current - Amps 111 48 167 72 Tolerance % - symmetrical load
- asymmetrical load
- load step 0-100%
5
±3 ±5
±1
±1 ±3 ±5
±1 ±3
±5 Distortion % - linear load 0 - 3 0 - 3 0 - 3 0 - 3 Frequency - Hz
- mains synchronized
- free running %
60 ±6%
±0.1
60 ±6%
±0.1
60 ±6%
±0.1
Overload capacity %, mains operation
- 1 minute
- 10 minutes
250 150
250 150
250 150
Overload capacity %, battery operation
- 1 minute
- 10 minutes
Acceptable cable size range - AWG
1, 2, 3
Recommended overcurrent protection -
3, 4
Amps
150 125
150 125
150 125
1/0 - 3/0 6 - 3 4/0 - 300 kcmil 3 - 1
150 60 225 90
±1 ±3 ±5
60 ±6%
±0.1
250 150
150 125
Notes for Tables 1 and 2:
1 Based upon UL rating of termination connector and upon 75 Conductor size may vary based on installation requirements. 2 For a 100% switch mode load, it is recommended that you size the neutral conductor for 1.732 times the phase current. 3 For units with external bypass, see Figures 4 and 5. 4 For UPS module only (UPS input breaker). 5 100% imbalance, provided output current rating is not exceeded.
o
C copper conductors at 30o C ambient from NEC Table 310-16.
3
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
Table 3: DC Input/Battery Specifications, UT340 and UT360
UT340 UT360
Acceptable external battery cable size range -
1
AWG Nominal DC current - Amps 200 300 Nominal DC voltage 216 216 Nominal number of cells 108 108 Factory-set float charge voltage Charger current limit - Amps
2
3
250 kcmil or 2 x 1/0 500 kcmil or 2 x 3/0
246 246
20 30
Inverter % efficiency - 100% load
- 75% load
- 50% load
- 25% load
Notes for Table 3:
1 Based on 75 based on installation requirements. 2 Adjust the float charge voltage setting per the battery manufacturer’s recommendations. 3 Programmable to lower level.
o
C copper conductors at 30o C ambient, intermittent duty, from NEC Table 310-16. Conductor size may vary
91 91 89 86
Table 4: General Specifications, UT340 and UT360
UT340 UT360
Noise attenuation - dB - differential mode
- common mode
1
60
120
Typical heat dissipation - kW (BTU)
- At full rated load, normal operation
- At full rated load, economy mode
- At 0.8 PF load, normal operation
- At 0.8 PF load, economy mode
Efficiency %, AC to AC - normal operation
- economy mode
2.11 (7185)
1.67 (5688)
1.68 (5748)
1.33 (4551) 95
96
Humidity %, non-condensing maximum 95 95 Ambient UPS and battery temperature ­Ideal UPS and battery temperature ­Air flow - CFM (m
3
/hour) 706.8 (1200) 706.8 (1200)
o
F (o C) 32 - 104 (0 - 40) 32 - 104 (0 - 40)
o
F (o C) 77 (25) 77 (25)
60
120
3.16 (10,778)
1.86 (6333)
2.53 (8622)
1.48 (5067) 95
97
92 92 90 87
Audible noise, typical - dBa 55 55 UPS dimensions, with conduit connection kit
H x W x D - inches (mm)
59.1 x 39.4 x 31.5
(1500 x 1000 x 800)
59.1 x 39.4 x 31.5
(1500 x 1000 x 800) UPS total weight - lbs (kg) 1741 (790) 2160 (980) Conduit connection kit weight - lbs (kg) 54 (24.49) 54 (24.49) Floor loading, UPS with conduit connection kit -
14.93 (102.94
)
18.42 (127)
pounds per square inch (kPa)
Note for Table 4:
1 With isolation transformer and the UPS wired as a separately derived system.
4
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
103 Specifications for the UT380 and UT3100
Tables 5 - 8 contain specifications for UPS models UT380 and UT3100.
Table 5: AC Input Specifications, UT380 and UT3100
UT380 UT3100
Voltage 3 x 480Y/277 3 x 480Y/277 Rated input current - Amps 127 159 Mains tolerance % (programmable) +10, -15 +10, -15 Bypass tolerance % (programmable) ±10 ±10 Frequency - Hz 60 ±6% 60 ±6% Current distortion % - THD 0 - 5 0 - 5 Acceptable cable size range - AWG Recommended overcurrent protection - Amps
1, 2, 3, 4, 5
4, 5
2/0 - 4/0 3/0 - 250 kcmil
175 200
Table 6: AC Output Specifications, UT380 and UT3100
UT380 UT3100
Voltage 480Y/277 480Y/277 Rated output current - Amps 96 120 Tolerance % - symmetrical load
- asymmetrical load
6
- load step 0-100% Distortion %, linear load 0 - 3 0 - 3 Frequency - Hz - mains synchronized
- free running % Overload capacity % mains operation - 1 minute
- 10 minutes Overload capacity % battery operation- 1 minute
- 10 minutes Acceptable cable size range - AWG Recommended overcurrent protection - Amps
Notes for Tables 5 and 6:
1 Bus bar can accept up to 2 cables per terminal. 2 Based upon UL rating of termination connector and upon 75 Conductor size may vary based on installation requirements. 3 For a 100% switch mode load, it is recommended that you size the neutral cable for 1.732 times the phase current. 4 For units with external bypass, see Figures 4 and 5. 5 For UPS module only (UPS input breaker). 6 100% imbalance, provided output current rating is not exceeded.
1, 2, 3, 4, 5
4, 5
o
C copper conductors at 30o C ambient from NEC Table 310-16.
±1 ±3 ±5
60 ±6%
±0.1
250 150
150 125
±1 ±3 ±5
60 ±6%
±0.1
250 150
150 125
1 - 2/0 1/0 - 3/0
125 150
5
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
Table 7: DC Input/Battery Specifications, UT380 and UT3100
UT380 UT3100
Acceptable external battery cable size range - AWG
1
Nominal DC current - Amps 245 310 Nominal DC voltage 360 360 Nominal number of cells 180 180 Factory-set float charge voltage Charger current limit - Amps
2
3
250 kcmil or 2 x 1/0 500 kcmil or 2 x 3/0
410 410
25 30
Inverter % efficiency - 100% load
- 75% load
- 50% load
- 25% load
Notes for Table 7:
1 Based on 75 based on installation requirements. 2 Adjust the float charge voltage setting per the battery manufacturer’s recommendations. 3 Programmable to lower level.
o
C copper conductors at 30o C ambient, intermittent duty, from NEC Table 310-16. Conductor size may vary
92 92 90 87
Table 8: General Specifications, UT380 and UT3100
UT380 UT3100
Noise attenuation - dB - differential mode
- common mode
1
Typical heat dissipation - kW (BTU)
- At full rated kW load, normal operation
- At full rated kW load, economy mode
- At 0.8 PF load, normal operation
- At 0.8 PF load, economy mode
Efficiency %, AC to AC - normal operation
- economy mode Humidity %, non-condensing maximum 95 95 Ambient UPS and battery temperature ­Ideal UPS and battery temperature ­Air flow - CFM (m
3
/hour) 706.8 (1200) 706.8 (1200)
o
F (o C) 32 - 104 (0 - 40) 32 - 104 (0 - 40)
o
F (o C) 77 (25) 77 (25)
60
120
3.33 (11,377)
2.47 (8445)
2.67 (9101)
1.98 (6756) 96
97
4.17 (14,221)
3.09 (10,556)
3.33 (11,377)
2.47 (8445)
93 93 91 88
60
120
96 97
Audible noise, typical - dBa 55 55 UPS dimensions, with conduit connection kit
H x W x D - inches (mm)
59.1 x 39.4 x 31.5
(1500 x 1000 x 800)
59.1 x 39.4 x 31.5
(1500 x 1000 x 800) UPS total weight - lbs (kg) 2425 (1100) 2634 (1195) Conduit connection kit weight - lbs (kg) 54 (24.49) 54 (24.49) UPS weight with conduit connection kit -
20.62 (142.17) 22.36 (154.17)
pounds per square inch (kPa)
1 With isolation transformer and the UPS wired as a separately derived system.
6
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
104 Receiving and Moving the UPS
WARNING!
The UPS and related equipment are very heavy. To prevent personal injury or equipment damage, use extreme care when handling and transporting the UPS cabinet and related equipment.
1. While the UPS system is still on the truck, inspect the equipment and shipping container(s) for any signs of damage. Do not install the system if damage is apparent. If damage has occurred, notify BEST as soon as possible.
2. Compare the shipment with the bill of lading. Report any missing items to the carrier and to BEST immediately.
3. Remove the screws on the bottom part of the packaging side plates.
4. Lift the main package up and off the unit and remove the packing materials from the unit.
5. Check that the label inside the UPS front door corresponds to the system ordered, especially the input/output voltages.
6. Unbolt the unit from the pallet.
7. Remove the unit from the pallet with a fork lift.
8. Use a fork lift or hand truck to transport the unit to the installation site or storage site. Study the footprint to decide how you will move the UPS through doorways and into position.
9. Install the separately shipped conduit connection kit. See the conduit connection kit for installation instructions.
7
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
105 Storing the UPS and Batteries
You can store the recommends that the unit and batteries be stored between 59o and 77o F (15o and 25o C). This temperature range or cooler allows batteries to have a longer shelf life. Recharge stored batteries every 90 to 120 days.
UNITY
/I UPS between -4o and 104o F (-20o and 40o C). However, BEST
106 Finding a Location for the UPS
Keep these guidelines in mind when you choose the location for the UPS system and the batteries.
Place the UPS in a clean, dust-free environment, free of contaminants. The air must be free
to circulate around the UPS cabinet and any battery cabinets or racks.
Avoid placing the unit in direct sunlight or near other heat sources.
Make sure that the ambient temperature is 32o to 104o F (0o to 40o C).
Ideal temperature is 77o F (25o C).
NOTE:
At 95o F (35o C), battery life will be about one-half of what it would be at a normal temperature of 77o F (25o C). At 113o F (45o C), battery life will be about one­fourth of normal.
Make sure that the floor can support the weight of the UPS, external batteries, and any other
necessary equipment. See Table 4 in Section 102 or Table 8 in Section 103 for weights and floor loading specifications.
The unit can be placed close to walls as long as there is enough clearance for the front doors
to open. Required service clearance is 3 feet (914 mm) at the front and 3 feet (914 mm) at the top of the unit. If possible, allow a minimum of 3 feet (914 mm) of clearance around the entire unit for easier servicing.
All service access is from the front and top of the unit. Cable entry is from the bottom of the
unit.
Do not operate the UPS or batteries in a sealed room or container.
8
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
107 Technical Support
Best Power Technology, Incorporated is committed to outstanding customer service. Our Technical Support Center is happy to help you with any problems or answer any questions you may have. A service technician is available 24 hours a day, 365 days a year.
Please have the label located inside the front door of the UPS.
Technical Support: 1-800-356-5737 (U.S.A. and Canada) or 1-608-565-2100
Technical Support Fax: 1-608-565-7642 or 1-608-565-2509
Bulletin Board Service: 1-608-565-7424
CompuServ: Type “Go BEST” at any ! prompt
UPS model number
and
serial number
available when you call. See the ID
Section 200: Installation
WARNING!
Before continuing, read the warnings on the inside front cover of this manual.
Insulated Tools and Other Equipment Needed:
Torque wrench in inch-pounds or
newton-meters Standard U.S. and metric wrenches
Petroleum jelly or conductive grease
Mallet
Volt-Ohm meter (True RMS - Digital)
Pliers
Ratchet and sockets
The customer must provide all cabling and interconnection hardware.
9
Electrical tape
Standard and Phillips screwdrivers
Torx head screwdriver set
Brush (for applying petroleum jelly or
conductive grease to battery terminals)
UNITY
Phase rotation meter
/I User Manual
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
201 Installing the Maintenance Bypass Cabinet (MBC) and UPS
IMPORTANT!
If you do not have a BEST maintenance bypass cabinet (MBC), you must provide overcurrent protection and a UPS input AC disconnect means.
BEST provided for maintenance.
Follow these guidelines when installing the MBC and UPS:
strongly recommends
Use the information in Section 106 to find an appropriate location for the UPS. Install the conduit connection kit per the instructions provided with the conduit connection kit.
Install the MBC within sight of the UPS. When installing the MBC, see Figure 4 or 5 and any instructions provided with the MBC.
Install the AC input and UPS output in separate conduits.
installed in dedicated conduit systems
Control wiring must be installed in separate conduit.
Good ground connections are necessary to reduce electrical noise and make the operation of the UPS and the loads safe. Follow the grounding guidelines in the installation wiring diagram. Refer to the National Electrical Code (NEC), appropriate IEEE documents, and all applicable codes.
that a means of bypassing the UPS from the critical load be
UPS output cabling shall be
and not shared with other electrical circuits.
When installing the AC wiring, refer to Figure 3, 4, or 5 and to any additional diagrams
provided with the UPS.
Figures 3, 4, and 5 show
•If you are installing the UPS with
•If you have a UT340 or UT360 with a BEST-supplied rotary switch MBC, see Figure 4.
•If you have a UT380 or UT3100 with a BEST-supplied three-breaker MBC, see Figure 5.
See Figure 2 for a front view of the UPS with the covers removed. See Figure 6 for
information on the external connection board. See Figure 7 for information on the optional communication interface board. See Figure 8 for information on the optional relay board.
If you have any questions, contact BEST’s Technical Support Center for assistance (see
Section 107).
typical installations
no maintenance bypass cabinet
. Your installation may differ.
, see Figure 3.
10
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
Figure 2: Front View (Covers Removed)
11
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
Figure 3: UT340 - UT3100 Installation Wiring Diagram, Typical Installation,
No External Maintenance Bypass Cabinet
NOTE 1:
Section 102 for recommended input overcurrent protection. (b) For a UT380 or UT3100, see Table 5 in Section 103 for recommended input overcurrent protection.
NOTE 2:
Section 102 for recommended output overcurrent protection. (b) For a UT380 or UT3100, see Table 6 in Section 103 for recommended output overcurrent protection.
NOTE 3:
UPS input AC disconnect means.
NOTE 4:
DC disconnect (DCD) and pre-charge/discharge switch. (b) The pre-char than 10 feet (3 m) from the DC disconnect.
(a) For a UT340 or UT360, see Table 1 in
(a) For a UT340 or UT360, see Table 2 in
You must provide overcurrent protection and (a) Refer to an
ge/discharge box must be located less
y instructions provided with the
ADDITIONAL NOTES:
A qualified electrician must install the UPS accordin
to all applicable codes.
All power and control wires must be in separate
conduits.
grounding electrode conductor (protective
The earth—PE) must be the same size (ampacit UPS input conductors. Conduit is not an acceptable grounding electrode conductor—see National Electrical Code Section 250-91(a).
A UT340 or UT360 unit is wired from the factor separatel equipment the UPS. See National Electrical Code Article 250-5(d) and 250-26 for proper installation
y derived system. Output neutral is bonded to
ground through main bonding jumper inside
grounding.
y) as the
12
g
y as a
UT340, UT360, UT380, and UT3100
g
y
g
g
g
y
g
y
y
g
g
y
y
y
y
y
Planning and Installation Manual
Figure 4: UT340 and UT360 Installation Wiring Diagram, Typical Installation
NOTE 1:
device per applicable codes. See the table below for mains input volta
NOTE 2:
DC disconnect (DCD) and pre-charge/discharge box. (b) The pre-char than 10 feet (3 meters) from the DC disconnect.
Size the mains input overcurrent protection
e and current ratings.
Mains Input
UPS Model VAC Maximum Amps
UT340 208 200 UT340 480 86 UT360 208 301 UT360 480 130
(a) Refer to an
e/discharge box must be located less
instructions provided with the
ADDITIONAL NOTES:
A qualified electrician must install the UPS accordin to all applicable codes.
All power and control wires must be in separate conduits.
earth—PE) must be the same size (ampacit UPS input circuit conductors. Conduit is not an acceptable National Electrical Code Section 250-91(a).
separatel equipment the UPS. See National Electrical Code Article 250-5(d) and 250-26 for proper installation
b protection and UPS input AC disconnect means.
device which switches all three phases and neutral. If Technical Support Center for instructions to convert the
unit to a not-separatel
rounding electrode conductor (protective
The
) as the
rounding electrode conductor—see
A UT340 or UT360 unit is wired from the factor
derived system. Output neutral is bonded to
round through main bonding jumper inside
rounding.
ou do not have a BEST-supplied maintenance
If
pass cabinet (MBC), you must provide overcurrent
The maintenance b
ou are using a 3-pole device, contact BEST’s
pass switch must be a 4-pole
derived system.
as a
13
UT340, UT360, UT380, and UT3100
g
y
g
g
y
y
Planning and Installation Manual
Figure 5: UT380 and UT3100 Installation Wiring Diagram, Typical Installation
NOTE 1:
device per applicable codes. See the table below for mains input volta
NOTE 2:
DC disconnect (DCD) and pre-charge/discharge box. (b) The pre-char than 10 feet (3 meters) from the DC disconnect.
Size the mains input overcurrent protection
e and current ratings.
Mains Input
UPS Model VAC Maximum Amps
UT380 480 173
UT3100 480 216
(a) Refer to an
e/discharge box must be located less
instructions provided with the
ADDITIONAL NOTES:
A qualified electrician must install the UPS accordin to all applicable codes.
All power and control wires must be in separate conduits.
ou do not have a BEST-supplied maintenance
If b
pass cabinet (MBC), you must provide overcurrent
protection and UPS input AC disconnect means.
14
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
Figure 6: External Connection Board
Use Class 1 wiring methods.
NOT USED
NOT USED
NOT USED
SUMMARY ALARM IF 1-3 CONNECTED
BATTERY OPERATION (30 SECS. DELAY) BATTERY OPERATION IF 1-3 ARE CONNECTED
EXTERNAL BYPASS CONTACT
1-3 CONNECTED IF SYSTEM IS
IN STATIC BYPASS OPERATION
NOT USED
MBC INHIBIT; IF SYSTEM OUTPUT IS OUTSIDE LIMITS
THEN 1-3 ARE CONECTED
1
3 1
X005
X006
3
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
X001
X002
X007
X008
X009
X010
X011
NOT USED
NOT USED
NOT USED
POSITION INDICATOR OF DCD IN OPTIONAL BATT. CABINET
A JUMPER MUST BE USED IF THE UNIT HAS INTERNAL BATTERIES
BATTERY TEMPERATURE COMPENSATION PROBE
POSITION INDICATOR OF EXTERNAL UPS BYPASS SWITCH
NOT USED
REMOTE START/STOP
13 COMMON, 11 "ON", 12 "OFF" (CLOSING CONTACTS)
EMERGENCY SHUT DOWN IF 12VDC (10mA) EXTERNAL SUPPLY IS REMOVED FROM TERMINALS. TO USE THIS FUNCTION REMOVE JUMPER SWO1
EMERGENCY SHUT DOWN IF DISCONNECTED (12V CIRCUIT)
X007-X011 ARE CHANGE OVER RELAY CONTACTS (NOT TO EXCEED NEC ART. 725 C CLASS 2 LIMITS)
BROWN BLUE
15
110
111
1 2
3 4 5 6 7 8 9
10 11
12 13 14 15 16 17
X012
X003
SW01
X004
TO CONTROLLER
BOARD
NOT USED
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
Figure 7: Communication Interface Board (Option)
Use Class 1 wiring methods.
Not Used
X002
X005
COMMUNICATION
INTERFACE BOARD
COM-PORT
To Controller
X001
X003 25 PIN SUB D MALE X004 25 PIN SUB D MALE X005 25 PIN SUB D FEMALE
X004 X003
Serial Port RS232
Serial Port 0 - 20 mA current loop
RELAY CONTACTS: 30 VAC, 60 VDC Maximum 0.5 A, Minimum 0.05 mA
14 15 “UPS on” (shown with UPS off) 2
16 17 “Static bypass operation” (shown with static bypass operation off) 4
18 19 “Battery operation” (shown with battery operation off) 6
20 21 “Battery low warning” (shown with “battery low” warning off) 8
13 + Remote UPS shut down input (3.5 - 25 VDC pulse for 1 second minimum) 25 –
16
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
Figure 8: Relay Board (Option)
The relays are shown in the alarm position and correspond to non-energized coils.
RELAY BOARD
X002:1
X003:1
X004:1
X005:1
X006:1
X007:1
X008:1
X009:1
X010:1
X011:1
X012:1
X013:1
X014:1
X015:1
X016:1
X017:1
2
MAINS FAILURE
3
2
BATTERY CHARGING FAILURE
3
2
OVERLOAD
3
2
FAN FAILURE
3
2
INVERTER FUSE FAILURE
3
2
LOW BATT. VOLTA G E
3
2
HIGH TEMPERATURE
3
2
BATTERY DCD OFF
3
2
OUTPUT VOLTAGE OUTSIDE LIMITS
3
2
UPS ON STATIC BYPASS
3
2
EXTERNAL MANUAL BYPASS ON
3
2
NORMAL OPERATION
3
2
COMMON FAULT
3
2
BYPASS VOLTAGE OUTSIDE LIMITS
3
2
BATTERY OPERATION
3
2
NOT USED
3
Description Minimum Maximum
Contact voltage - AC 6 V 250 V Contact current - AC * 50 mA 8 A Contact voltage and
current - DC *
6 V / 50 mA 250 V / 0.3 A
6 V / 8 A
* Resistive load
17
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
202 Installing the External Batteries and DC Disconnect (DCD)
External batteries must be installed and connected to the UPS by a qualified service person who is familiar with UPS battery installations and applicable building and electrical codes. The qualified service person should read this entire section before the UPS and batteries arrive.
DANGER!
Full voltage and current are always present at the battery terminals. The batteries used in this system can produce dangerous voltages, extremely high currents, and a risk of electric shock. They may cause severe injury if the terminals are shorted together or to ground (earth). You must be extremely careful to avoid electric shock and burns caused by contacting battery terminals or shorting terminals during battery installation. Do not touch uninsulated battery terminals.
A qualified service person who is familiar with battery systems and required precautions must install and service the batteries. The installation must conform to national and local codes. Keep unauthorized personnel away from batteries.
The qualified service person must take these precautions:
1. Wear protective clothing, such as rubber gloves and boots and protective eye wear. Batteries contain caustic acids and toxic materials and can rupture or leak if mistreated. Remove rings and metal wristwatches or other metal objects and jewelry. Do not carry metal objects in your pockets where the objects can fall into the battery cabinet.
2. Tools must have insulated handles and must be insulated so that they will not short battery terminals. Do not allow a tool to short between individual or separate battery terminals or to the cabinet or rack. Do not lay tools or metal parts on top of the batteries, and do not lay them where they could fall onto the batteries or into the cabinet.
3. Install the batteries as shown on the drawing provided with the batteries. When connecting cables, never allow a cable to short across a battery’s terminals, the string of batteries, or to the cabinet or rack.
4. Align the cables on the battery terminals so that the cable lug will not contact any part of the cabinet or rack, even if the battery is moved. Keep the cable away from any sharp metal edges.
5. Install the battery cables so they cannot be pinched by the UPS or battery cabinet doors.
18
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
DANGER!
6. Do not connect the battery terminal to ground (earth). If any battery terminal is inadvertently grounded, remove the source of the ground. Contacting any part of a grounded battery can cause a risk of electric shock.
7. To reduce the risk of fire or electric shock, install the batteries in a temperature and humidity controlled indoor area, free of contaminants.
8. Battery system chassis ground (earth) must be connected to the UPS chassis ground (earth). If you use conduit, this ground conductor must be routed in the same conduit as the battery conductors.
9. Where conductors may be exposed to physical damage, protect the conductors in accordance with all applicable codes.
10. If you are replacing batteries or repairing battery connections, shut off the UPS and remove both AC and DC power.
Follow these guidelines when installing the batteries:
Refer to any instructions provided with the batteries.
Refer to any instructions provided with the DC disconnect (DCD) and pre-charge/discharge
switch.
External batteries require a fused disconnect or a DC circuit breaker. There should be a
disconnecting means for each battery string. The external battery fuse protects the battery cables. Size the cables based on the overcurrent protection device.
The battery cables must be sized for a total maximum voltage drop of 2.0 VDC at the rated
DC current.
Wherever conductors may be exposed to physical damage, protect the conductors in
accordance with any applicable codes. This includes battery cables between the UPS and the battery system and cables between battery cabinets or racks.
BEST recommends routing battery cables through flexible conduit. Install flexible conduit
for battery cables according to local or national code.
The battery system ground (earth) must be connected to the UPS chassis ground (earth). This
ground conductor must be routed with the battery cables.
19
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
Clean the cables and battery terminals before making the battery connections. Apply a thin
coating of conductive grease before making the battery connections, or apply petroleum jelly to the entire connection after it has been made.
Torque battery connections to the battery manufacturer’s specifications.
Follow the steps below and any instructions provided with the battery system:
1. Connect the cables
between batteries
.
a. In each battery string, connect the cables between batteries as shown in the battery
installation diagram provided with the batteries.
b. Meter the positive (+) and negative (–) terminal on each battery string to verify proper
nominal voltage and polarity.
2. Connect the battery cables
between battery strings
.
a. Connect the negative () cables between battery strings as shown in the battery
installation diagram provided with the batteries.
b. Meter the DC voltage between the positive terminals of the strings. The voltage should
measure less than 5 volts. If it measures greater than 5 volts, correct any wiring errors before you continue.
c. Connect the positive (+) cables between battery strings as shown in the battery
installation diagram provided with the batteries.
3. Install the DC disconnect (DCD) and pre-charge/discharge switch. Refer to Figure 3, 4 or 5 and to any instructions provided with the DCD and pre-charge/discharge switch.
4. Connect the external batteries to the UPS.
a. Connect the positive (+) cable(s) to the UPS first. Install ring connectors for 10 mm
bolts as required.
b. To prevent short circuits, insulate the UPS end of the negative (–) cable(s).
Do not connect the negative (–) cables to the UPS yet.
c. Connect the positive (+) cable(s) to the battery system and tighten to the proper torque
specifications.
d. Connect the negative () cable(s) to the battery system and tighten to the proper torque
specifications.
20
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
5. Check the DC voltage.
a. Connect the DC fuse(s) as shown in the battery installation diagram provided with the
batteries. Verify proper voltage and polarity at the battery pack. See Table 3 in Section 102 or Table 7 in Section 103 for nominal DC voltage.
b. Turn the DC disconnect (DCD) “ON.”
c. Meter for proper nominal DC voltage at the UPS end of the cables. Make sure the
polarity agrees with the markings on the UPS battery input terminals.
d. After checking the DC voltage, turn the DC disconnect (DCD) “OFF.”
6. Connect the negative (–) cable(s) to the UPS. Tighten to the proper torque specifications.
7. Replace all covers.
8. Continue with Section 300, “Initial Startup and Phase Check.”
Battery Replacement Information
Only a qualified service person familiar with battery systems should replace batteries. See
Section 500, “Shutdown Procedures,” to bypass and shut down the UPS.
Review all of the warnings at the beginning of Section 202 before replacing the batteries.
Use the Same Number and Type of Battery:
To ensure continued superior performance of your UPS and to maintain proper battery charger operation, you must replace the batteries with the same number of batteries. The batteries must be the same manufacturer type as the original batteries and have the same voltage and ampere-hour rating as the original batteries.
Verify that the Battery Terminal is Not Grounded:
If any battery terminal is inadvertently grounded, you must remove the connection from the terminal to ground (earth) before you service the batteries. Contacting any part of a grounded battery can cause a risk of electric shock. An electric shock will be less likely if you disconnect the ground connection before you service the batteries.
Handle Used Batteries with Care:
Assume that old batteries are fully charged. Use the same precautions you would use when handling a new battery. Do not short battery terminals or the battery string with a cable or tool when you disconnect the batteries.
21
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
Dispose of Batteries Properly:
1-800-356-5737 (U.S.A. or Canada) or call your local BEST office.
WARNING!
Do not dispose of batteries in a fire because the batteries could explode.
Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes and may be toxic.
Batteries contain lead. Many state and local governments have regulations about disposing of used batteries. Dispose of batteries properly. For assistance, call BEST’s Technical Support at 1-800-356-5737 or call your local BEST office.
For assistance, call BEST’s Technical Support Center at
Section 300:Initial Startup and Phase Check
WARNING!
Some units have been programmed at the factory for “autostart.” If programmed for “autostart,” the unit will turn on delay). For more information or to change this feature, see the user manual.
Before continuing, read the warnings on the inside front cover of this manual.
After installing the unit, use this section to perform the initial startup and the phase check for the maintenance bypass cabinet (MBC).
The steps in this section are for a unit with a BEST-supplied maintenance bypass cabinet (MBC).
If you have a unit with a BEST-supplied
If you have a unit with a BEST-supplied
any time
mains (AC line) is applied (after a 60-second
rotary switch three-breaker
MBC, see Section 301.
MBC, see Section 302.
22
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
301 Initial Startup and Phase Check
for Units with a BEST-Supplied Rotary Switch MBC
Follow this Procedure Exactly! No Load Should Be Connected!
1. Make sure that all AC and DC power is off.
2. Switch the UPS bypass switch to “UPS.”
3. Make sure that the main circuit breaker in the load panel is off so that the loads cannot receive power from the UPS.
4. At the mains AC input panel, switch on the input power to the UPS and maintenance bypass cabinet (MBC).
5. Switch the UPS AC disconnect switch “ON.” The UPS display should show
type xxkVA xxxV
6. Within 20 seconds, the display should show
7. Turn the pre-charge/discharge switch to the pre-charge position and hold it until the LED turns off.
8. Switch the battery DC disconnect (DCD) “ON.”
9. Check the phase rotation at the service panel and the unit. The unit will not start if the phase rotation is incorrect.
10. When the audible alarm stops, push the green “on” button located inside the UPS front door. The display will show
NOTE:
11. If the UPS is connected to a generator, verify that the unit operates properly on generator power before continuing. If the UPS operates properly on generator power, continue this procedure. If the UPS does not operate properly on generator power, phone BEST’s Technical Support Center for assistance.
One or more alarms may occur. If the alarm(s) persists for more than 20 seconds, refer to the “Alarms” section of the user manual. If the unit activates a “battery monitor alarm,” you should set the user parameter “battery monitor reset” to “ON.”
, and an audible alarm should sound.
**Stand-by**
The phase rotation must be A, B, C and clockwise
Normal operation load power xx%
.
.
System
.
23
CAUTION
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
Before
check for correct voltage, phasing, and system operating mode.
12. Program the unit into static bypass operation:
13. At the maintenance bypass cabinet (MBC), make sure the UPS output voltage is
you switch the UPS bypass switch from “UPS” to “LINE”, use the steps below to
a. Press to access the user parameters. b. Press the or key until the display shows c. Press to turn static bypass operation on. The display should show
to to to
.
neutral neutral neutral
_______VAC _______VAC _______VAC
L1 L2 L3
to to to
neutral neutral neutral
operation
approximately the same as the AC line input voltage (there may be slight differences). Use a true RMS voltmeter to measure the phase-to-neutral voltage at the MBC AC line input and the MBC output:
MBC AC Line Input MBC Output
a.
L1
b.
L2
c.
L3
Bypass operation: OFF
Bypass
_______VAC _______VAC _______VAC
.
The voltages in the first column should be similar to the voltages in the second column. If the voltages are more than 10 volts apart for 208 V nominal or 25 volts apart for 480 V nominal, check the connections and correct any wiring problems before continuing.
14. At the maintenance bypass cabinet (MBC), make sure the UPS output voltage and the AC line input voltage are in phase. To do this, measure the AC voltages between the following points at the MBC AC line input and the MBC output:
MBC AC Line Input MBC Output
a.
L1 input
b.
L2 input
c.
L3 input
These readings must not be more than 10 VAC!
Support Center or your local BEST office.
to to to
L1 output L2 output L3 output
_______VAC _______VAC _______VAC
If they are, call BEST’s Technical
24
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
15.At the maintenance bypass cabinet (MBC), measure the following:
a. b. c.
N input
N input N output N input
to
to
to
N output
Ground
to
Ground
N output
” should not exceed “
_______VAC _______VAC _______VAC
N input
to
Ground
.” If it does, call BEST’s
Technical Support Center.
16.Check for proper voltages at the bypass switch load output terminals and the load distribution panel(s).
Bypass Switch Load Output Load Panel Input
a. L1 to b.
L2
to
c. L3 to
neutral neutral
neutral
_______VAC L1 to _______VAC L2 to _______VAC
L3
to
neutral neutral neutral
_______VAC _______VAC _______VAC
17.Switch the UPS bypass switch to “BYPASS.”
18.Recheck for proper voltages at the bypass switch load output and the load distribution panel(s).
Bypass Switch Load Output Load Panel Input
a. L1 to b.
L2
to
c. L3 to
neutral neutral
neutral
_______VAC L1 to _______VAC L2 to _______VAC
L3
to
neutral neutral neutral
_______VAC _______VAC _______VAC
19.Switch the UPS bypass switch to “UPS.”
20.Return the UPS to normal operation mode: a. Press to access the user parameters. b. Press the or key until the display shows
Bypass operation: ON
c. Press to turn static bypass operation off. The display should show
operation load power xx%
.
Normal
.
You can now apply loads to the system. As the last step of the installation, BEST recommends that you clear the events log. See Section 400, “Clearing the Events Log.”.
25
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
302 Initial Startup and Phase Check
for Units with a BEST-Supplied Three-Breaker MBC
Follow this Procedure Exactly! No Load Should Be Connected!
1. Make sure that all AC and DC power is off.
2. Switch the maintenance bypass breaker (MBB) “OFF.”
3. Switch the UPS output breaker (UOB) “OFF.”
4. At the mains AC input panel, switch on the input power to the UPS and maintenance bypass cabinet (MBC).
5. Switch the UPS input breaker (UIB) “ON.” The display should show
xxkVA xxxV
6. Within 20 seconds, the display should show
7. Turn the pre-charge/discharge switch to the pre-charge position and hold it until the LED turns off.
8. Switch the battery DC disconnect (DCD) “ON.”
9. Check the phase rotation at the service panel and the unit. The unit will not start if the phase rotation is incorrect.
10. When the audible alarm stops, press the green “on” button located inside the UPS front door. The UPS display will show
NOTE:
11. If the UPS is connected to a generator, verify that the unit operates properly on generator power before continuing. If the UPS operates properly on generator power, continue this procedure. If the UPS does not operate properly on generator power, phone BEST’s
Technical Support Center for assistance.
, and an audible alarm should sound.
**Stand-by**
The phase rotation must be A, B, C and clockwise
Normal operation load power xx%
One or more alarms may occur. If the alarm(s) persists for more than 20 seconds, refer to the “Alarms” section of the user manual. If the unit activates a “battery monitor alarm,” you should set the user parameter “battery monitor reset” to “ON.”
.
System type
.
.
26
CAUTION
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
Before
check for correct voltage, phasing, and system operating mode.
12. Program the unit into static bypass operation:
13. Switch the UPS output breaker (UOB) “ON”.
14. At the maintenance bypass cabinet (MBC), make sure that the UPS output voltage is
you switch the maintenance bypass breaker (MBB) “ON,” use the steps below to
a. Press to access the user parameters. b. Press the or key until the display shows c. Press to turn static bypass operation on. The display should show
to to to
.
neutral neutral neutral
_______VAC _______VAC _______VAC
L1 L2 L3
to to to
neutral neutral neutral
operation
approximately the same as the AC line input voltage (there may be slight differences). Use a true RMS voltmeter to measure the phase-to-neutral voltage at the MBC AC line input and the MBC output.
MBC AC Line Input MBC Output
a.
L1
b.
L2
c.
L3
Bypass operation: OFF
Bypass
_______VAC _______VAC _______VAC
.
The voltages in the first column should be similar to the voltages in the second column. If the voltages are more than 10 volts apart for 208V nominal or 25 volts apart for 480 V nominal, check the connections and correct any wiring problems before continuing.
15. At the maintenance bypass cabinet (MBC), make sure the UPS output voltage and AC line input voltage are in phase. To do this, measure the AC voltage between the following points at the MBC AC line input and the MBC output:
MBC AC Line Input MBC Output
a.
L1 input
b.
L2 input
c.
L3 input
These readings must not be more than 10 VAC!
Support Center or your local BEST office.
to to to
L1 output L2 output L3 output
27
_______VAC _______VAC _______VAC
If they are, call BEST’s Technical
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
16.At the maintenance bypass cabinet (MBC), measure the following:
a. b. c.
N input
N input N output N input
to
to
to
N output
Ground
to
Ground
N output
” should not exceed “
______VAC ______VAC ______VAC
N input
to
Ground
.” If it does, call BEST’s
Technical Support Center.
17.Check for proper voltages at the maintenance bypass cabinet (MBC) load output terminals and the load distribution panel(s).
MBC Load Output Load Panel Input
a. L1 to b.
L2
to
c. L3 to
neutral neutral
neutral
______VAC L1 to ______VAC L2 to ______VAC
L3
to
neutral neutral neutral
______VAC ______VAC ______VAC
18.Switch the maintenance bypass breaker (MBB) “ON.”
19.Switch the UPS output breaker (UOB) “OFF.”
20.Recheck for proper voltages at the MBC load output terminals and load distribution panel(s).
MBC Load Output Load Panel Input
a. L1 to b.
L2
to
c. L3 to
neutral neutral
neutral
______VAC L1 to ______VAC L2 to ______VAC
L3
to
neutral neutral neutral
______VAC ______VAC ______VAC
21.Switch the UPS output breaker (UOB) “ON.”
22.Switch the maintenance bypass breaker (MBB) “OFF.”
23.Return the UPS to normal operation: a. Press to access the user parameters. b. Press the or key until the display shows
Bypass operation: ON
c. Press to turn static bypass operation off. The display should show
operation load power xx%
.
Normal
.
You can now apply loads to the system. As the last step of the installation, BEST recommends that you clear the events log. See Section 400, “Clearing the Events Log.”
28
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
Section 400: Clearing the Events Log
The events log contains the 250 most recent UPS events, including alarms. To clear the events log, follow the steps below:
1. Simultaneously press and . The display should show
2. Using the key pad, enter “920701.” The display should show
reset
3. Press . The display should show
If the unit will not be used immediately, go to Section 500, “Shutdown Procedures.”
. The events log is now cleared.
Normal operation load power xx%
Key in password
Logging stack is
Section 500: Shutdown Procedures
WARNING!
After shutting down the unit, or covers. Access panels should be removed only by
wait at least five minutes
before removing any access panels
qualified service personnel
.
.
.
After shutting down the UPS, there may still be high voltage inside the unit.
TEST BEFORE TOUCHING!
Before continuing, read the warnings on the inside front cover of this manual.
This section tells how to shut down the UPS from normal operation mode.
This procedure is for a unit with a BEST-supplied maintenance bypass cabinet (MBC).
If you have a unit with a BEST-supplied
If you have a unit with a BEST-supplied
rotary switch three-breaker
29
MBC, see Section 501.
MBC, see Section 502.
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
501 Shutdown Procedure for Units
with a BEST-Supplied Rotary Switch MBC
1.
If you have shut the loads down:If the loads are to remain powered:
a. Press to access the user parameters. b. Press the or key until the display shows c. Press to turn static bypass operation on. The display should show
operation
2. Switch the UPS bypass switch to “BYPASS.”
3. Press the red “off” button located inside the UPS front door.
4. Switch the UPS AC disconnect switch “OFF.”
5. Switch the DC disconnect (DCD) “OFF.”
6. Turn the pre-charge/discharge switch to the discharge position and hold it until the LED turns off. The UPS display should now be blank.
To restart the unit, see Section 601, “Startup from Maintenance Bypass for Units with a BEST-Supplied Rotary Switch MBC.”
.
Skip to step 3.
Program the unit into static bypass operation:
Bypass operation: OFF
Bypass
.
7. (Optional) If the loads are and maintenance bypass cabinet (MBC).
to be powered, turn off all AC power sources to the UPS
not
502 Shutdown Procedure for Units
with a BEST-Supplied Three-Breaker MBC
1.
If you have shut the loads down:If the loads are to remain powered:
a. Press to access the user parameters. b. Press the or key until the display shows c. Press to turn static bypass operation on. The display should show
operation
.
Skip to step 4.
Program the unit into static bypass operation:
Bypass operation: OFF
Bypass
30
.
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
2. Switch the maintenance bypass breaker (MBB) “ON.”
3. Switch the UPS output breaker (UOB) “OFF.”
4. Press the red “off” button located inside the UPS front door.
5. Switch the UPS input breaker (UIB) “OFF.”
6. Switch the DC disconnect (DCD) “OFF.”
7. Turn the pre-charge/discharge switch to the discharge position and hold it until the LED turns off. The UPS display should now be blank.
To restart the unit, see Section 602, “Startup from Maintenance Bypass for Units with a BEST-Supplied Three-Breaker MBC.”
8. (Optional) If the loads are and maintenance bypass cabinet (MBC).
to be powered, turn off all AC power sources to the UPS
not
Section 600:Startup from Maintenance Bypass
This section tells how to start the UPS from maintenance bypass. The steps in this procedure are for a unit with a BEST-supplied maintenance bypass cabinet (MBC).
If you have a unit with a BEST-supplied
If you have a unit with a BEST-supplied
rotary switch three-breaker
601 Startup from Maintenance Bypass
for Units with a BEST-Supplied Rotary Switch MBC
1. Make sure that the following switches are in the following positions:
MBC, see Section 601.
MBC, see Section 602.
The UPS AC disconnect switch should be “OFF.”
The UPS bypass switch should be on “LINE.”
The DC disconnect (DCD) should be “OFF.”
2. Switch the UPS AC disconnect switch “ON.” The UPS display should show
type xxkVA xxxV
and an audible alarm should sound.
31
System
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
3. Within 20 seconds, the UPS display should show
4. Turn the pre-charge/discharge switch to the pre-charge position and hold it until the LED turns off.
5. Switch the DC disconnect (DCD) “ON.”
6. Press the green “on” button located inside the front door of the UPS. The UPS display should show
7. Program the unit into static bypass operation: a. Press to access the user parameters. b. Press the or key until the display shows c. Press to turn static bypass operation on. The display should show
operation
8. Switch the UPS bypass switch to “UPS.”
9. Program the unit to normal operation:
Normal operation load power xx%
.
**Stand-by**
.
Bypass operation: OFF
.
.
Bypass
a. Press to access the user parameters. b. Press the or key until the display shows c. Press to switch the bypass operation off. The display should show
operation load power xx%
.
Bypass operation: ON
602 Startup from Maintenance Bypass
for Units with a BEST-Supplied Three-Breaker MBC
1. Make sure that the following switches are in the following positions:
The UPS input breaker (UIB) should be “OFF.”
The UPS output breaker (UOB) should be “OFF.”
The UPS maintenance bypass breaker (MBB) should be “ON.”
The DC disconnect (DCD) should be “OFF.”
2. Switch the UPS input breaker (UIB) “ON.” The UPS display should show
xxkVA xxxV
, and an audible alarm should sound.
.
Normal
System type
3. Within 20 seconds, the display should show
**Stand-by**
32
.
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
4. Turn the pre-charge/discharge switch to the pre-charge position and hold it until the LED turns off.
5. Switch the DC disconnect (DCD) “ON.”
6. Press the green “on” button located inside the UPS front door. The UPS display should show
Normal operation load power xx%
.
7. Program the UPS into static bypass operation: a. Press to access the user parameters. b. Press the or key until the display shows c. Press to turn bypass operation on. The display should show
operation
.
Bypass operation: OFF
Bypass
8. Switch the UPS output breaker (UOB) “ON.”
9. Switch the maintenance bypass breaker (MBB) “OFF.”
10.Program the unit to normal operation: a. Press to access the user parameters. b. Press the or key until the display shows
Bypass operation: ON
c. Press to switch the bypass operation off. The display should show
operation load power xx%
.
Section 700: Glossary of Terms and Abbreviations
.
.
Normal
See Section 701 for the glossary of terms. See Section 702 for a list of abbreviations.
701 Glossary of Terms
Ampere (Amp):
resistance of one ohm.
British thermal unit (BTU):
of air-free water from 60
Decibel adjusted (dBa):
sound power level of
A unit of electric current equivalent to a steady current produced by one volt applied across a
A unit of heat energy equal to the heat needed to raise the temperature of one pound
85 dBm.
to 61
F at a constant pressure of one standard atmosphere.
A unit used to show the relationship between an acoustic noise source and a reference
33
UT340, UT360, UT380, and UT3100
Planning and Installation Manual
Ground (Earth):
equipment is connected to earth or to some conducting body that serves in place of earth.
Load tolerance - symmetrical:
Load tolerance - asymmetrical:
Mains:
center in interior wiring. Synonymous with power source.
Noise attenuation - differential mode:
Noise attenuation - common mode:
Nominal voltage:
Power factor (PF):
times RMS current of an alternating current circuit.
Protective earth (PE):
Static switch:
The conductors extending from the service switch, generator bus, or converter bus to the main distribution
A conducting connection, whether intentional or accidental, by which an electric circuit or
Equally balanced loads on a three-phase system.
Unbalanced loads on a three-phase system.
The ability to attenuate noise, line to line.
The ability to attenuate noise, line to ground and neutral to ground.
The voltage at which a device operates under ideal conditions.
The ratio of the true (real) power to the apparent power: root means-square (RMS) voltage
Synonymous with grounding electrode conductor.
An electronic switch that has no moving parts.
702 Abbreviations
BCA Battery cabinet assembly DCD DC disconnect switch (may be a separate switch or a switch located on the battery cabinet/rack) MBB Maintenance bypass breaker MBC Maintenance bypass cabinet MIB Main input breaker MOB Main output breaker SKRU Solenoid key release unit UIB UPS input breaker UOB UPS output breaker
Best Power Technology, Incorporated, reserves the right to change specifications without prior notice.
34