In USA - BEST Hartford, Wisconsin
In CANADA - BEST Drummondville, QC, Canada
REGISTER YOUR PRODUCT ONLINE AT : www.BestRangeHoods.com/register
For additional Information visit www.BestRangeHoods.com
READ AND SAVE THESE INSTRUCTIONS
!
!
INTENDED FOR DOMESTIC COOKING ONLY
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE
THE FOLLOWING:
1. Use this unit only in the manner intended by the manufacturer. If you have questions, contact
the manufacturer at the address or telephone number listed in the warranty.
2. Before servicing or cleaning unit, switch power off at service panel and lock service panel to
prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
3. Installation work and electrical wiring must be done by a qualified person(s) in accordance with
all applicable codes and standards, including fire-rated construction codes and standards.
4. Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney)
of fuel burning equipment to prevent backdrafting. Follow the heating equipment manufacturer’s
guidelines and safety standards such as those published by the National Fire Protection Association (NFPA), and the American Society for Heating, Refrigeration and Air Conditioning Engineers
(ASHRAE), and the local code authorities.
5. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden
utilities.
6. Ducted fans must always be vented to the outdoors.
7. Do not use this unit with any separate solid-state speed control device.
8. To reduce the risk of fire, use only metal ductwork.
9. This unit must be grounded.
10. Type Non-IC Installation: Thermal insulation shall not cover top of range hood housing and must
be spaced 3-inches (76mm) from all sides. (Fig. 1)
3-INCH MINIMUM.
NO INSULATION
WITHIN THIS SHADED
AREA OF COMPONENTS.
FIG. 1
TO REDUCE THE RISK OF A RANGE TOP GREASE FIRE:
A. Never leave surface units unattended at high settings. Boilovers cause smoking and greasy
spillovers that may ignite. Heat oils slowly on low or medium settings.
B. Always turn hood ON when cooking at high heat or when flambeing food (i.e. Crepes Suzette,
Cherries Jubilee, Peppercorn Beef Flambe’).
C. Clean ventilating fans frequently. Grease should not be allowed to accumulate on fan or filter.
D. Use proper pan size. Always use cookware appropriate for the size of the surface element.
- 2 -
!
TO REDUCE THE RISK OF INJURY TO PERSONS IN THE EVENT OF A RANGE TOP GREASE
FIRE, OBSERVE THE FOLLOWING:*
1. SMOTHER FLAMES with a close-fitting lid, cookie sheet, or metal tray, then turn off the burner.
BE CAREFUL TO PREVENT BURNS. If the flames do not go out immediately, EVACUATE AND
CALL THE FIRE DEPARTMENT.
2. NEVER PICK UP A FLAMING PAN - You may be burned.
3. DO NOT USE WATER, including wet dishcloths or towels - violent steam explosion will result.
4. Use an extinguisher ONLY if:
A. You know you have a Class ABC extinguisher and you already know how to operate it.
B. The fire is small and contained in the area where it started.
C. The fire department is being called.
D. You can fight the fire with your back to an exit.
* Based on “Kitchen Fire Safety Tips” published by NFPA.
CAUTION
1. For indoor use only.
2. To reduce risk of fire and to properly exhaust air, be sure to duct air outside. Do not vent exhaust
air into spaces within walls or ceilings or into attics, crawl spaces, or garages.
3. Take care when using cleaning agents or detergents.
4. Avoid using food products that produce flames under the Range Hood.
5. For general ventilating use only. Do not use to exhaust hazardous or explosive materials and
vapors.
6. To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall spray,
construction dust, etc. off power unit.
7. Your hood motor has a thermal overload which will automatically shut off the motor if it becomes
overheated. The motor will restart when it cools down. If the motor continues to shut off and
restart, have the hood serviced.
8. For best capture of cooking impurities, the bottom of the hood should be a minimum of 48” and
a maximum of 72” above the cooking surface.
9. Two installers are recommended because of the large size and weight of this hood.
10. The light source is designed for this specific application and can overheat if serviced by untrained
personnel. If any servicing is required, the product should be returned to an authorized service
facility for examination or repair.
11. Please read specification label on product for further information and requirements.
12. To reduce the risk of fire and electric shock, install this range hood only with Best Exterior Blower
Models EB6, EB9, EB12, EB15, or Best In-Line Blower Models ILB3, ILB6, ILB9 or ILB11. Other
blowers cannot be substituted. (Blowers sold separately.)
13. This power pack is equipped with a RF receiver (optional remote control sold separately).
Changes or modifications not expressly approved by the party responsible for compliance could
void the user’s authority to operate this product. The remote control has been tested and found
to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules and
the Canadian ICES-003. These limits are designed to provide reasonable protection against
harmful interference in a residential installation. The remote control generates, uses and can
radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee
that interference will not occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by turning the equipment
off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver
is connected.
- 3 -
OPERATION
Controls (Fig. 1)
The hood is operated using the (5) push-buttons located on the hood and the remote control.
LED colors are displayed on hood control only.
• Your hood includes a 10 minute blower delay off switch. Press this switch once to activate the
timer and the LED Ring (L1) flashes blue. The blower will continue to operate for 10minutes.
After 10 minutes, the blower turns off automatically.
• To cancel the 10-minute delay, press the delay switch once again.
(P2) Filter Alarm Switch
• After 30 hours of blower operation, the filter alarm is activated and the LED ring (L1) turns
red/flashes. It indicates that the grease filters need to be cleaned.
• After cleaning the grease filters, reset the hour counter by pressing the Filter Alarm/Timer
Reset button (P2) during display of the alarm.
P3: Decreases fan motor speed until turned off (4>3>2>1>OFF)
P4: Turns fan motor on and increased speed (ON>1>2>3>4)
P5: Turns lights on/off
L1: LED Indicator Ring Signalling crown:
- Hood in standby: lights up 30 seconds after
the last key has been pressed the crown turns off
- Motor on: L1 lights up blue The
frequency is proportional to the speed setting.
- 10’ TIMER function : L1 lights up and flashes blue.
- Filter alarm active: L1 lights up red
FIG. 1
(P3) Blower Speed Decrease and Off Switch
• Press to decrease blower speed, high to low. The LED ring (L1) flashes blue at a speed
proportionate to the blower setting (i.e.: four flashes is high speed, one flash is low speed,
etc.)
• Continue pressing this switch to turn the blower off.
(P4) Blower Speed Increase and On Switch
• Press this switch to turn the blower on to low speed.
• Press again to increase blower speed, low to high. The LED ring (L1) flashes blue at a speed
proportionate to the blower setting (i.e.: four flashes is high speed, one flash is low speed,
etc.)
(P5) Light Switch
Turns the lights on and off.
Master On-Off Switch
Located behind one of the corner filters, this switch must be ON (indicated as “I”) before the
hood will operate. Turn the switch OFF (indicated as “O”) to disconnect power to the hood.
- 4 -
REMOTE CONTROL
P1:Activate/deactivate delay-off (10 minute)P2: Filter change indication timer resetP3:Decreases fan motor speed until turned off (4>3>2>1>OFF)P4:Turns fan motor on and increased speed (ON>1>2>3>4)P5: Turns lights on/offL1: LED Indicator Ring Signalling crown:
- Hood in standby: lights up 30 seconds after the last key has been pressed the crown turns off
- Motor on: L1 lights up blue
The
frequency is proportional to the speed setting.
- 10’TIMER function : L1 lightsupand flashes blue.
The remote control is linked to the hood at the factory.
If, for some reason, the link is lost - follow the directions below:
To Link Remote Control to Hood
1. Turn off hood motor and hood lights.
2. Press
light will light up. (Fig. 3)
3. Within 3 seconds - press ƒ (P2) on the hood control. (Fig. 4) The LED ring will light up for
approximately 10 seconds to confim that the linking process was successful.
on the remote control for at least 3 seconds and release the button. The indicator
Remote Control Functions (Fig.3)
Delay - Off
Blower Speed Decrease and Off
Blower Speed Increase and On
Light
Press
(Delay) and (Light) together to Reset Filter Alarm.
IMPORTANT: Holding
remote and hood to be lost.
Battery disposal
When the batteries need to be replaced, dispose of them only and exclusively in the numerous readily available
special waste bins, especially in shops selling electronic consumer goods. Observance of the regulations on
differentiated waste collection, in particular, proper disposal of used batteries, contributes to preventing possible
negative effects on the environment and health.
INDICATOR
LIGHT
FIG. 3
-
(P3)
HOOD
CONTROL
¤
(P1)
(P5)
(P2)
ƒ
(P4)
+
L1
LED
RING
FIG. 4
See “Controls” section on previous page for
more information on each function.
(Delay) for more than 3 seconds will cause the link between the
- 5 -
- 23A +
CLEANING AND MAINTENANCE
Proper maintenance of the Range Hood will assure proper performance of the unit.
Motor
The motor is permanently lubricated and never needs oiling. If the motor bearings make excessive or
unusual noise, replace the motor with the exact service motor. The impeller should also be replaced.
Grease Filters
The grease filters should be cleaned frequently. Use a warm detergent solution. Grease filters are
dishwasher safe.
Clean all-metal filters in the dishwasher using a non-phosphate detergent. Discoloration of the filter may
occur if using phosphate detergents, or as a result of local water conditions - but this will not affect filter
performance. This discoloration is not covered by the warranty.
See “INSTALL FILTERS” section for removal and installation instructions.
Stainless Steel Cleaning
DO:
• Regularly wash with clean cloth or rag soaked
with warm water and mild soap or liquid dish
detergent.
• Always clean in the direction of original polish
lines.
• Always rinse well with clear water (2 or 3 times)
after cleaning. Wipe dry completely.
• You may also use a specialized household
stainless steel cleaner.
DON’T:
•
Use any steel or stainless steel wool or any
other scrapers to remove stubborn dirt.
• Use any harsh or abrasive cleansers.
• Allow dirt to accumulate.
• Let plaster dust or any other construction
residues reach the hood. During construction/
renovation, cover the range hood to make sure
no dust sticks to the stainless steel surface.
Avoid: When choosing a detergent
• Any cleaners that contain bleach will attack stainless steel
• Any products containing: chloride, fluoride, iodide, bromide will deteriorate surfaces rapidly.
• Any combustible products used for cleaning such as acetone, alcohol, ether, benzol, etc., are highly
explosive and should never be used close to a range.
- 6 -
PREPARE THE HOOD
Unpack hood and check contents.
You should receive:
1 - Range Hood Body
1 - Remote Control
6 - Grease Filters
6 - Lag Bolts, 6 x 70 mm
6 - Washers
REMOTE
CONTROL
RANGE HOOD
BODY
EXTERIOR OR IN-LINE
BLOWER SELECTION
CAUTION: Either an exterior blower
or an in-line blower may be used with this
range hood. The Model CC34ESB range hood
must be installed only with Best Exterior
Blower Models EB6, EB12, or Best In-Line
Blower Models ILB3, ILB6, or ILB9. Other
blowers cannot be substituted. (Blowers
sold separately.)
The blower must be cULus Listed for
Canadian and U.S. use, and evaluated for
use with a solid-state speed control, rated
120V, 60Hz, 3.0A max.
6 WASHERS
6 LAG BOLTS
(6 x 70 mm)
6 GREASE
FILTERS
FIG. 2
- 7 -
INSTALL THE DUCTWORK
METAL
WARNING: To
reduce the risk of
fire, use only metal
ductwork.
1. Choose the loca-
WALL
CAP
DUCT
ELBOW
EXTERIOR BLOWER
8" ROUND TO 10” ROUND TRANSITION
8" ROUND
METAL DUCT
tion of the hood,
exterior or in-line
blower and any
roof or wall caps,
and decide where
the ductwork will
run. See Fig. 4 and
IN-LINE BLOWER
(Shown ducted through wall/gable.
See in-line blower instructions
for specific duct size &
ducting requirements.
HOOD
48" TO 72" ABOVE
COOKING SURFACE
exterior or in-line
blower instructions
for suggestions.
2. A straight, short
duct run will allow
FIG. 4
the hood to perform
most efficiently. Long duct runs, elbows, and transitions will reduce the performance of the
hood. Use as few of them as possible. Larger ducting may be required for best performance
with longer duct runs.
3. Install an exterior or in-line blower.
4. Connect metal ductwork to exterior or in-line blower and work back towards hood location.
Elbows and transitions may be necessary. See exterior or in-line blower instructions for
further information. Use duct tape to seal the joints between ductwork sections.
PREPARE THE CEILING
OPENING
The hood should always be centered over the
cooktop. Make sure there is adequate space
in the ceiling structure to install the hood and
ductwork. The hood should be mounted 48”
to 72” above the cook top for best removal of
cooking impurities. Fig 4.
Use joist size lumber to frame in around the
range hood opening. The ceiling structure
must be able to support the weight of the
hood (58 pounds). Fig 5.
min. 9-7/16”
max. 13-3/4”
DOUBLE HEADERS
- 8 -
26¾”
1
42
”
2
/
FIG. 5
PREPARE THE HOOD
SUPPORT
1. Construct a wood framing system as
shown in Fig. 6.
2. The structure must be capable of support-
ing its own weight, plus the weight of the
hood (58 pounds).
2 x 4
FRAMING
11”11”11”11”
42-1/2”
- 9 -
1/8” PILOT
1/8” PILOT
HOLE (6)
HOLE (6)
26-3/4”
37-1/4”
2-5/8”
9-5/8”
FIG. 6
INSTALL THE HOOD
CAUTION: At least two installers are
recommended because of the large size
and weight of this range hood.
1. Lift range hood into the ceiling opening.
2. Secure each support frame to the wooden
hood support frame using (6) 6 x 70 mm
lag bolts and washers provided. Fig. 7.
3. Adjust height of the telescoping support
frame to ensure a tight fit between the
hood and finished ceiling.
4. At the blower discharge collar, connect
ductwork that exhausts air to the outside
discharge. Fig. 8.
5. Duct tape all joints to ensure an air tight
seal.
2x4
WOODEN
FRAME
(6) LAG
BOLTS &
WASHERS
FIG. 7
8” ROUND
DUCT
- 10 -
FIG. 8
CONNECT THE WIRING
WARNING: All electrical wiring
should be done by a qualified person (s)
in accordance with all applicable codes
and standards. This range hood must be
properly grounded.
Do not turn blower on at the service panel until
all wires have been connected.
1. From the room interior, pull down both
closure panels. Fig. 9.
2. Remove (4) screws from the electrical
compartment access panel. Slide the panel
sideways to expose the electrical wiring box.
BLOWER CONNECTION AT THE HOOD
1. Run 2-wire plus ground power cable to a ¾”
knockout located on the back of the hood.
Fig. 10.
2. Remove a ¾” electrical knockout from the
back of the hood.
5. From the electrical box marked “MOTOR
CONNECTION”, remove (2) screws that
secure the cover to the metal wiring box.
Fi g. 11.
6. Pull 6” of cable into the box and secure with
an appropriate cable clamp.
7. Make electrical connections inside the “MO-
TOR CONNECTION” box. Connect red-
to-white, black-to-black and green-to-ground.
8. Replace the wiring box cover and the
screws. Make sure wires are not pinched
between the cover and box.
CONNECTIONS AT EXTERIOR OR IN-LINE
BLOWER
1. Make electrical connections at the exterior
or in-line blower (see blower instructions).
BLOWER CONNECTION AT THE HOOD
1. Run 2-wire plus ground, 120 VAC electrical
power cable to a ¾” knockout located on the
back of the hood. Fig. 10.
2. Remove a ¾” electrical knockout from the
back of the hood.
3. From the electrical box marked “120VAC
INPUT”, remove (2) screws that secure the
cover to the metal wiring box. Fig. 11.
4. Pull 6” of cable into the box and secure with
an appropriate cable clamp.
5. Make electrical connections inside the
“120VAC INPUT” box. Connect white-to-
white, black-to-black and green-to-ground.
6. Replace the wiring box cover and the
screws. Make sure wires are not pinched
between the cover and box.
7. Replace the electrical compartments ac-
cess panel and (4) screws.
CLOSURE PANELS
2-WIRE PLUS
2-WIRE PLUS
GROUND
120 VAC
LINE IN
CONNECTION
KNOCKOUTS
BLOWER AND POWER CONNECTION AT HOOD
POWER CONNECTION
CONNECT:
WHITE-TO-WHITE
BLACK-TO-BLACK
GREEN-TO-GROUND
120VAC 60Hz
LINE-IN
BOX MARKED
“120VAC INPUT”
BLOWER CONNECTION
CONNECT:
RED-TO-WHITE
BLACK-TO-BLACK
GREEN-TO-GROUND
FROM EXTERIOR
OR IN-LINE
BLOWER
BOX MARKED
CONNECTION”
“MOTOR
- 11 -
FIG. 9
GROUND
BLOWER
FIG. 10
FIG. 11
INSTALL THE FILTERS
P1:Activate/deactivate delay-off (10 minute)P2: Filter change indication timer resetP3:Decreases fan motor speed until turned off (4>3>2>1>OFF)P4:Turns fan motor on and increased speed (ON>1>2>3>4)P5: Turns lights on/offL1: LED Indicator Ring Signalling crown:
- Hood in standby: lights up green. 30 seconds after the last key has been pressed the crown turns off
- Motor on: L1 lights up blue
The
frequency is proportional to the speed setting.
- 10’TIMER function : L1 lightsupand flashes blue.
- Filter alarm active: L1 lightsupred
1. Pull down both closure panels as shown.
2. To install the grease filters, align rear filter
tabs with slots in the hood. Push latch tab
in, push filter into position and release.
Make sure filter is securely engaged after
installation. Fig. 12.
3. To remove the filters for cleaning, push
latch tab in to disengage filter from hood.
Tilt the filter downward and remove. Fig. 13.
PROGRAMMING MODE
PROCEDURE
FIG. 12
FIG. 13
The range hood is designed to work with
several different blower models. Before using, the control must first be programmed to
your blower model, in order to achieve proper
operating speeds.
From the chart below:
1. Find the SETUP number that corresponds
to the blower model that is installed with
your range hood.
2. The control is factory-preset to SETUP 3. If
your blower model is listed under SETUP
3, no programming is required. The range
hood is ready to use.
SETUP 1 SETUP 2 SETUP 3
BLOWER
MODEL
NUMBER
EB6
ILB3
ILB6
EB12
ILB9
EB15
(default)
EB9
ILB11
3. For blower models listed under SETUP 1
or 2 follow this program sequence:
A - Power at the service box must be ON
while programming. The blower and
lights must be turned off.
B - Press P2 for 3 seconds. The L1 LED
ring will flash at 3 different rates of
speed: slow flashing speed = SETUP
1; medium flashing speed = SETUP 2;
fastest flashing speed = SETUP 3 (the
factory-preset default).
C - To select the proper SETUP, press P3
(-) or P4 (+) to change to SETUP 1, 2
or 3.
D - Once the proper SETUP is found, press
P2 (f) to memorize the SETUP setting.
E - The range hood is now ready to use.
P1
¤
P3P4
P5
-
P2
+
ƒ
- 12 -
L1
LED
RING
WARRANTY
Broan-NuTone LLC (Broan-NuTone) warrants to the original consumer purchaser of Best products that such products
will be free from defects in materials or workmanship for a period of one year from the date of original purchase. THERE
ARE NO OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, IMPLIED WARRANTIES OR MERCHANT ABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
During this one-year period, Broan-NuTone will, at its option, repair or replace, without charge, any product or part which
is found to be defective under normal use and service.
THIS WARRANTY DOES NOT EXTEND TO FLUORESCENT LAMP STARTERS, TUBES, HALOGEN AND INCANDESCENT BULBS, FUSE, FILTERS, DUCTS, ROOF CAPS, WALL CAPS AND OTHER ACCESSORIES FOR DUCTING.
This warranty does not cover (a) normal maintenance and service or (b) any products or parts which have been subject
to misuse, negligence, accident, improper maintenance or repair (other than by Broan-NuTone), faulty installation or
installation contrary to recommended installation instructions.
The duration of any implied warranty is limited to the one-year period as specified for the express warranty. Some states
do not allow limitation on how long an implied warranty lasts, so the above limitation may not apply to you.
BROAN-NUTONE’S OBLIGATION TO REPAIR OR REPLACE, AT BROAN-NUTONE’S OPTION, SHALL BE THE
PURCHASER’S SOLE AND EXCLUSIVE REMEDY UNDER THIS WARRANTY. BROAN-NUTONE SHALL NOT BE LIABLE FOR INCIDENTAL, CONSEQUENTIAL OR SPECIAL DAMAGES ARISING OUT OF OR IN CONNECTION WITH
PRODUCT USE OR PERFORMANCE. Some states do not allow the exclusion or limitation of incidental or consequential
damages, so the above limitation or exclusion may not apply to you.
This warranty gives you specific legal rights, and you may also have other rights, which vary from state to state. This
warranty supersedes all prior warranties.
To qualify for warranty service, you must (a) notify Broan-NuTone at the address stated below or telephone number stated
below, (b) give the model number and part identification and (c) describe the nature of any defect in the product or part.
At the time of requesting warranty service, you must present evidence of the original purchase date.
In USA - Best®, 926 W. State Street, Hartford, WI 53027 (800-558-1711)
In Canada - Best®, 550 Lemire Blvd., Drummondville, QC J2C 7W9 (866-737-7770)
www.BestRangeHoods.com
ONE YEAR LIMITED WARRANTY FOR BEST PRODUCTS
- 13 -
SERVICE PARTS
Model CC34E6SB
KEY NO. PART NO. DESCRIPTION
1 B003102866 FRAME
9 B08087804 GREASE FILTER
56 B08092517 CONNECTION AIR OUTLET
57 B02011341 DAMPER FLAP
64 B03115251 BOTTOM BRACKET
67 B004203477 WIRES
115 BE3350233 FEEDER CABLE CONNECTION BOX
116 BE3334252 FEEDER CABLE CONNECTION BOX COVER
250 B02011389 RING NUT
282 BE3405320 MAIN SWITCH SUPPORT
283 B02300907 MAIN SWITCH
343 B08093078 CLOSURE PANEL
362 B080811027 DOOR MAGNETS WITH SCREWS474 B02300431 LED LAMP
477 B02011376 CLOSING
508 B02301035 FLAT CABLE CONTROL
998 B080810962 FITTING SET
999 B080813692 INSTALLATION INSTRUCTIONS SET
IME B06145262 ELECTRICAL INSTALLATION ASSEMBLY
AQI B06102644 SWITCH BOX ASSEMBLY
ARU B08092501 CONNECTION AIR OUTLET (INCLUDES KEY No. 56, 57)
ACR3 B08999186 REMOTE CONTROL
- 14 -
SERVICE PARTS
Model CC34E6SB
- 15 -
1
64
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.