Besantek BESANTEK Corporation BST-3PT4 Manual

Page 1
99 Washington Street Melrose, MA 02176
Phone 781-665-1400
Visit us at www.TestEquipmentDepot.com
Toll Free 1-800-517-8431
BST-3PT4
3 PHASE TESTER
INSTRUCTION MANUAL
Page 2
Page
1. Introduction..........................................
2. Safety notes.........................................
3. Features..............................................
4. Specications......................................
5. Instrument layout.................................
6. Measuring methods.............................
7. Maintenance........................................
1
2
3
4
5
6-7
8-9
Page 3
1. Introduction
NOTE
This meter has been designed and tested according to EN61010-1.
WARNING
READ “SAFETY NOTES” (NEXT PAGE) BEFORE USING THE METER.
-1-
Page 4
2. Safety notes
● Read the following safely information carefully before attempting to operate or service the meter.
● Use the meter only as specied in this manual; otherwise the protection provided by the meter may be impaired.
● Rated environmental conditions: (1) Indoor use (2) Installation Category III. 500V (3) Pollution Degree 2 (4) Altitude up to 2000 Meter (5) Relative Humidity 80% Max. (6) Ambient Temperature 0°C~40°C
● Observe the international Electical symbols listed
below.
Meter is protected throughout by double insulation or reinforced insulation.
Warning ! Risk of electric shock.
Caution ! Refer to this manual before using the meter.
Alternating current.
-2-
Page 5
3. Features
● Two functions in one unit including open phase and phase sequence.
● This model is ideal for installing conveyor lines, pump systems and interconnected drivers.
● Identied 3-phase sequence and open phase
check.
● Meets EN61010-1 safety requirements.
● Complete with three large alligator clips.
-3-
Page 6
4. Specications
Input Voltage: 100Vac up to 500Vac Max.
Frequency Range: 45 to 70 Hz.
Circuit Structure: All electronic (not mechanical).
Power Consumption: AC power consumption approx.
7mA per phase rotation led of
indicator.
Dimension: 102(L) x 78(W) x 32.5(D)mm.
Weight: 228g Approx.
Accessories: Vinyl case
Instruction manual Test leads-Red, white & blue.
Safety Standard EN 61010-1
EN 61010-2-030 EN 61326-1
-4-
Page 7
5. Instrument layout
OPEN PHASE INDICATOR
PHASE ROTATION INDICATOR
-5-
Page 8
6. Measuring methods
● Operations 3 phase rotation tester : (1) Connect the test lead to 3-phase input terminals
by R-S-T.
(2) Connect color alligator clips to the terminals of
a 3-phase power source. Connecting order may be optional.
(3) Make sure that all of the three lamps for open
phase check are on. If so, there is no open phase. When any of the three lamps is not on, there is open phase.
Open phase check lamp “R”is not on
Open phase check lamp "S" is not on
Open phase check lamp “T” is not on
Open phase on terminal where RED (or BLACK) alligator clip is connected
Open phase on terminal where WHITE (or RED) alligator clip is connected
Open phase on terminal where BLUE alligator clip is connected
-6-
Page 9
(4) Check the rotating direction of the rotation
indicator. If lamp of counter clockwise is lit, alternate the connection of the two of the three alligator clips. If lamp of clockwise is lit, phase sequence is R, S, and T in order of the power source terminals where the RED (or BLACK), WHITE (or RED) and BLUE alligator clips are connected.
Fig.1
-7-
Page 10
7. Maintenance
● Fuse Replacement : (1) It is necessary to replace fuse, when lamp
indicator R or T show no connection, and Change R-S-T is the same.
(2) Use a screwdriver to unscrew the screws on
the back then open the case(Fig.2), take out the broken fuse and replace with new fuse (500mA/500V 5x20mm).
(3) Reinstall the case.
FUSE (X2)
Fig.2
-8-
Page 11
● Cleaning and Storage:
WARNING
To avoid electrical shock or damage to the meter, do not get water inside the case.
Periodically wipe the case with a damp cloth and
detergent; do not use abrasives or solvents.
CAT IV
Is for measurements performed at the
-
source of the low-voltage installation.
CAT III
Is for measurements performed in the
-
building installation.
CAT II
Is for measurements performed on circuits
-
directly connected to the low-voltage installation.
CAT I
Is for measurements performed on circuits
-
not directly connected to Mains.