Bernstein 604.2903.112 Technical Data

Technical Data
Metal Switches
Series D
D-A3Z W
Article number
Operating symbol
Operating diagram
ON OFF
Tolerances Operating point: ± 0,25mm; Actuating force: ± 10%
Electrical data
Rated insulation voltage U Conv. thermal current I Rated operational voltage U
i
the
e
400 VAC 10A
240V Utilization category AC-15, Ue /Ie 240V/3A Direct opening action acc. to IEC/EN 60947-5-1, Annex K Short-circuit protective device Fuse 10A gG Protection class
I
6042903112
This document will not become the contractual basis; the details included herein do not constitute any descriptions of expected conditions, so that warranties/claims for defects on account of possible variations of the actual qualities from the qualities described herein are explicitly excluded. All rights reserved. Specifications subject to change without notice!
Document: 6042903112_en / Last update: 3 / 2133-11
Date of issue: 30.03.2011 / Page 1 of 2
Bernstein AG, Tieloser Weg 6, D-32457 Porta Westfalica, Germany / www.bernstein.eu
Vorlage : 0850174282 Orig. 1
Technical Data
Metal Switches
Mechanical data
Enclosure Die-cast aluminium Cover Sheet aluminium Actuator Push bolt (st) Ambient air temperature -30°C ... +80°C Contact type 3 NC (Zb) Mechanical life 10 x 106 operating cycles Switching frequency 100 / min. Assembly 4 x M5 Connection 6 screw terminals (M4) Conductor cross-sections Solid: 0.5 ... 1.5mm² Litz wire with ferrules: 0.5 ... 1.5mm² Cable entrance 2 x M20x1.5 Weight 0,43 kg Installation position Operator definable Protection type IP65 acc. to IEC/EN 60529
Actuation
The push bolt actuator is mainly intended to be actuated along its axis. Side actuation will considerably reduce switch life.
Standards
VDE 0660 T200, DIN EN 60947-5-1, IEC 60947-5-1
EU Conformity
Approvals
Notes
The degree of protection specified (IP code) applies only to a properly closed cover and the use of an equivalent cable gland with adequate cable.
VDE 0660 T100, DIN EN 60947-1, IEC 60947-1
acc. to directive 2006/95/EC
CSA
C
A300 (same polarity)
US
This document will not become the contractual basis; the details included herein do not constitute any descriptions of expected conditions, so that warranties/claims for defects on account of possible variations of the actual qualities from the qualities described herein are explicitly excluded. All rights reserved. Specifications subject to change without notice!
Document: 6042903112_en / Last update: 3 / 2133-11
Date of issue: 30.03.2011 / Page 2 of 2
Bernstein AG, Tieloser Weg 6, D-32457 Porta Westfalica, Germany / www.bernstein.eu
Vorlage : 0850174282 Orig. 1