No.: KW-337A
Date: February, 2011
KSA, KSB
Models
Electric Heated
KSA/KSB1036E
# of Motors
KSA/KSB
Electric Heated
kW’s and Amp Draws
kW's AVAILABLE FOR KSA/KSB
kW @ 208 - 600/3
KSA/KSB1042E
KSA/KSB1048E
KSA/KSB1060E
KSA/KSB 2060E
KSA/KSB2072E
KSA/KSB2084E
KSA/KSB2096E
KSA/KSB2108E
KSA/KSB2120E
KSA/KSB3096E
KSA/KSB3108E
KSA/KSB3120E
KSA/KSB3132E
KSA/KSB3144E
KSA/KSB4144E 4 56 kW 40 kW 32 kW 24 kW
1 14 kW 10 kW 8 kW 6 kW
2 28 kW
20 kW 16 kW 12 kW
18 kW3 42 kW 30 kW 24 kW
HEATER AMP DRAWS FOR SELECTED kW
Heater kW
6 kW 28.9 25.1 16.7 14.5 7.2 6.0
8 kW 38.5 33.5 22.2 19.3 9.6 8.0
10 kW 48.1 41.9 27.8 24.1 12.0 10.0
12 kW 57.7 50.3 33.4 28.9 14.4 12.0
14 kW 67.3 58.7 38.9 33.7 16.8 14.0
16 kW 77.0 67.0 44.5 38.6 19.2 16.0
18 kW 86.6 75.4 50.0 43.4 21.6 18.0
20 kW 96.2 83.8 55.6 48.2 24.0 20.0
24 kW 115.4 100.6 66.7 57.8 28.8 24.0
28 kW 134.7 117.3 77.8 67.5 33.6 28.0
30 kW 144.3 125.7 83.4 72.3 36.0 30.0
32 kW 153.9 134.0 88.9 77.1 38.4 32.0
40 kW 192.4 167.6 111.2 96.4 48.0 40.0
42 kW 202.0 176.0 116.8 101.2 50.4 42.0
56 kW 269.4 234.6 155.7 135.0 67.2 56.0
Amps Per kW
208/1 240/1 208/3 240/3 480/3 600/3
4.81 4.19 2.78 2.41 1.20 1.00
Heater kW Am
Draws
Berner reserves the right to alter specifications without prior notice.
Berner International Corporation New Castle, PA 16101 / USA / Telephone (724) 658-3551 / FAX (724) 652-0682 / www.berner.com / airdoors@berner.com
MADE IN U.S.A. ©Copyright, 2011 Berner International Corporation

KSA/KSB
Electric Heated
No.: KW-337B
Date: February, 2011
kW, BTU/HR and Temperature Rise
KSA ELECTRIC HEATER kW AND TEMPERATURE RISE - 208-600/3
Heater
Model
KSA1036E* 14 47,782 30 10 34,130 21 8 27,304 17 6 20,478 13
KSA1042E* 14 47,782 28 10 34,130 20 8 27,304 16 6 20,478 12
KSA1048E* 14 47,782 28 10 34,130 20 8 27,304 16 6 20,478 12
KSA1060E* 14 47,782 29 10 34,130 21 8 27,304 17 6 20,478 13
KSA2060E* 28 95,564 31 20 68,260 22 16 54,608 18 12 40,956 13
KSA2072E* 28 95,564 30 20 68,260 21 16 54,608 17 12 40,956 13
KSA2078E* 28 95,564 29 20 68,260 21 16 54,608 17 12 40,956 13
KSA2084E* 28 95,564 28 20 68,260 20 16 54,608 16 12 40,956 12
KSA2096E* 28 95,564 28 20 68,260 20 16 54,608 16 12 40,956 12
KSA3096E* 42 143,346 31 30 102,390 22 24 81,912 18 18 61,434 14
KSA2108E* 28 95,564 29 20 68,260 21 16 54,608 17 12 40,956 13
KSA3108E* 42 143,346 30 30 102,390 21 24 81,912 17 18 61,434 13
KSA2120E* 28 95,564 29 20 68,260 21 16 54,608 17 12 40,956 13
KSA3120E* 42 143,346 29 30 102,390 21 24 81,912 17 18 61,434 13
KSA3132E* 42 143,346 28 30 102,390 20 24 81,912 16 18 61,434 12
KSA3144E* 42 143,346 28 30 102,390 20 24 81,912 16 18 61,434 12
KSA4144E* 56 191,128 30 40 136,520 21 32 109,216 17 24 81,912 13
kW @
208-600/3
BTU/HR
AIR
TEMP
RISE °F
Heater
kW @
208-600/3
BTU/HR
AIR
TEMP
RISE °F
Heater
kW @
208-600/3
BTU/HR
AIR
TEMP
RISE °F
Heater
kW @
208-600/3
BTU/HR
TEMP
RISE °F
AIR
KSB ELECTRIC HEATER kW AND TEMPERATURE RISE - 208-600/3
Heater
Model
KSB1036E* 14 47,782 19 10 34,130 14 8 27,304 11 6 20,478 8
KSB1042E* 14 47,782 18 10 34,130 13 8 27,304 11 6 20,478 8
KSB1048E* 14 47,782 18 10 34,130 13 8 27,304 10 6 20,478 8
KSB1060E* 14 47,782 19 10 34,130 13 8 27,304 11 6 20,478 8
KSB2060E* 28 95,564 20 20 68,260 14 16 54,608 12 12 40,956 9
KSB2072E* 28 95,564 19 20 68,260 14 16 54,608 11 12 40,956 8
KSB2078E* 28 95,564 19 20 68,260 13 16 54,608 11 12 40,956 8
KSB2084E* 28 95,564 18 20 68,260 13 16 54,608 11 12 40,956 8
KSB2096E* 28 95,564 18 20 68,260 13 16 54,608 10 12 40,956 8
KSB3096E* 42 143,346 20 30 102,390 14 24 81,912 11 18 61,434 9
KSB2108E* 28 95,564 18 20 68,260 13 16 54,608 11 12 40,956 8
KSB3108E* 42 143,346 19 30 102,390 14 24 81,912 11 18 61,434 8
KSB2120E* 28 95,564 19 20 68,260 13 16 54,608 11 12 40,956 8
KSB3120E* 42 143,346 18 30 102,390 13 24 81,912 11 18 61,434 8
KSB3132E* 42 143,346 18 30 102,390 13 24 81,912 11 18 61,434 8
KSB3144E* 42 143,346 18 30 102,390 13 24 81,912 10 18 61,434 8
KSB4144E* 56 191,128 19 40 136,520 14 32 109,216 11 24 81,912 8
kW @
208-600/3
BTU/HR
AIR
TEMP
RIS E °F
Heater
kW @
208-600/3
BTU/ HR
AIR
TEMP
RISE °F
Heater
kW @
208-600/3
BTU/ HR
AIR
TEMP
RISE °F
Heater
kW @
208-600/3
BTU/ HR
TEMP
RISE °F
*For reduced kW, the model number needs to include kW. Example: KSB3132EB-140 for 14 kW heat.
AIR
Berner reserves the right to alter specifications without prior notice.
Berner International Corporation New Castle, PA 16101 / USA / Telephone (724) 658-3551 / FAX (724) 652-0682 / www.berner.com / airdoors@berner.com