Berner CHD10-1036, CHD10-1042, CHD10-1048, CHD10-1060, CHD10-2060 Manual

...
Page 1
www.Berner.com
Air Curtain Series #CHD10
Sanitation Certied High Performance 7
Air Curtain Series #SHD07
ANSI/NSF 37
Air Curtain Fans
for Customer Entry
12CS
SHD07
for outdoor use
SHD07
FDA
RECOMMENDED
USDA
COMPLIANCE
SHD07
Installation & Maintenance Instructions
TABLE OF CONTENTS
I. UNCRATING............................................................................................................................................................ ........................................................ 2
II. GENERAL MOUNTING INSTRUCTIONS ................................................................................................................................. ................................... 4
III. WALL MOUNTING ...................................................................................................................................................................................................... 5
IV. SUSPENDED MOUNTING ....................................................................................................................................... ................................................... 6
V. ELECTRICAL CONNECTIONS ..................................................................................................................................................................................... 7
VI. FIELD CONNECTIONS ................................................................................................................................................................................................ 7
VII. OPERATING INSTRUCTIONS .................................................................................................................................................................................... 8
VIII. MAINTENANCE AND CLEANING ............................................................................................................................................................................ 9
IX. SERVICE ............................................................................................................................................................... ........................................................ 9
X. TROUBLESHOOTING ................................................................................................................................................................................................. 10
XI.WARRANTY ................................................................................................................................................ ................................................................ 12
Thank you for choosing Berner.
Berner International has been saving energy and creating healthy, comfortable environments for our customers for over 60 years.
Berner oers unmatched quality, performance, and dependability—not to mention our service. At Berner, we stand behind our products.
READ ALL INSTRUCTIONS BEFORE INSTALLING OR USING AIR CURTAIN
1
©Copyright, 2017 Berner International
September, 2017
II-123
Page 2
Commercial High
Sanitation Certied
Performance 10
Air Curtain
(Air Door)
High Performance 7
Air Curtain
(Air Door)
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
A. Read all instructions before installing or using this air curtain. B. Use this unit only in the manner intended by the manufacturer and described in this manual. Any other use not recommended by the manufacturer may cause re, electric shock, or injury to persons. If you have any questions, contact the manufacturer. C. Before servicing or cleaning unit, switch power o at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel. D. Installation work and electrical wiring must be done by qualied person(s) in accordance with all applicable national and local codes having jurisdiction, including re-rated construction. See page 7, ELECTRICAL CONNECTIONS (NEC Code ANSI/NFPA No. 70). E. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities. F. To reduce the risk of re, do not store or use gasoline or other ammable vapors and liquids in the vicinity of the air curtain. G. This air curtain is hot when in use. To avoid burns, do not let bare skin touch hot surfaces. Keep combustible materials, such as furniture, pillows, bedding, papers, clothes, etc. and curtains at least 1 inch from the top, back, front, sides and at least 6 feet from the discharge of the air curtain. H. Extreme caution is necessary when any air curtain is used by or near children or invalids, and whenever the heater is left operating unattended. I. Do not operate any air curtain after it malfunctions. Disconnect power at the service panel and have the air curtain inspected by a reputable electrician before reusing. J. To disconnect the air curtain, turn controls to "o", and turn o power to the air curtain circuit at main disconnect panel. K. Do not insert or allow foreign objects to enter any ventilation or discharge opening as this may cause an electric shock or re, or damage the air curtain. L. To prevent a possible re, do not block the air intake or discharge of the air curtain in any manner. M. The air curtain has hot and arcing or sparking parts inside. Do not use it in areas where gasoline, paint, or ammable vapors or liquids are used or stored. N. This heater may include an audible or visual alarm to warn that parts of the heater are getting excessively hot. If the alarm sounds (or illuminates), immediately turn the heater o and inspect for any objects on or adjacent to the heater that may have blocked the airow or otherwise caused high temperatures to have occurred. DO NOT OPERATE THE HEATER WITH THE ALARM SOUNDING (OR ILLUMINATING).
I. UNCRATING
Carefully examine the carton(s) for damage. If the carton is damaged, immediately notify the shipping company. Do not delay in ling claim. If the air curtain(s) were shipped on wooden skids, remove protective wood and banding straps securing the carton(s) to the skid. Open the carton(s) and remove all protective packaging.
Immediately verify that the electrical rating nameplate located on the cover matches electrical power supply available. Retain the shipping carton(s) until the air curtain(s) are installed and properly operating.
ACCESSORIES: If the air curtain was ordered with a wall mounting plate, remove and save the two (2) locking screws from the back corners and detach the wall mounting plate. See Figure 1.
If the air curtain(s) were ordered with optional electrical acces­sories, the accessories will be found in the carton containing the air curtain or in a separate carton(s) accompanying the air curtain(s). Check all of the cartons/skids for accessories before discarding.
Figure 1
2
Page 3
Simple to Install
Easy to operate & maintain
1
3
4" minimum
side clearance
from
combustible
material*
20˚
EXTERIOR
R
I
A
*Electrically Heated Units Only
For more information see page 4
The keyhole slots are spaced 1” from the ends, and 3/4” and 7” from the top.
Discharge Nozzle
A
I
R
4" minimum*
6' minimum*
Mark the wall according to the length of the air curtain. If the keyhole slots are not located where suitable support is available, drill new holes in
Keyhole
Mounting
Slots
the back plate where space is available.
For more information see page 5 For more information see page 5
AIR
Before hanging, check to see what the clearance is above the door.
INTERIOR
3/4"
1"
7"
2
Flush Mounting
AIR CURTAIN
Top of Doorway
Spacer
Seal
AIR CURTAIN
1"
Spacer
3/8"
3/4"
3"
2"
Rule of thumb – If the unit must be mounted higher than 1” above the opening, it must be spaced out from the wall 3/8” for every inch the unit is above the door opening.
For more information see page 4
4
1/4"
Line-up
Keyholes on
All Screws
Push Backplate Toward Wall
Slide
Backplate
Down
Tighten All Screws
After installing the mounting hardware, lift and slip the air curtain over the mounting hardware by grasping the inlet rings. Tighten the mounting hardware.
5
To use threaded rod to hang from the ceiling instead of the wall - use the factory installed threaded inserts.
For more information see page 6 For more information see page 7
6
Suspension Rods
1/4” Threaded Insert
To wire – follow the wiring diagram (found inside wiring compartment).
Side View
www.berner.com Berner International 800.245.4455
111 Progress Ave. / New Castle / PA / 16101 / USA
The controls ship in the same box as the air curtain.
3
Page 4
II. MOUNTING INSTRUCTIONS (General)
INDOOR MOUNTING - Environmental/ Insect/ Dust Control
OUTDOOR MOUNTING (Unheated Only) - Insect/Dust Control
4" minimum
side clearance
from combustible
material*
4" minimum*
AIR
The Commercial High Performance 10 & the Sanitation
Certied High Performance 7 Air Curtains are designed to be
an eective barrier against cold drafts in the winter and hot air in the summer, ying insects and airborne contaminants.
To achieve optimum protection, the air curtain should be
mounted on the inside of the building, ush to the wall and as close to the top of the door opening as possible. To ensure peak performance, keep the air stream free of obstructions.
The air curtain will not perform properly if negative air
pressure exists in the building. Under these conditions, a means for makeup air to the building must be provided so that the air pressure on both sides of the opening is in balance.
Before mounting the air curtain, check the supporting structure
to verify that it has sucient load-carrying capacity to support the weight of the air curtain(s). The mounting hardware (supplied by others) should be capable of supporting a minimum of three (3) times the weight of the air curtain.
See Table 1 or Table 2.
IMPORTANT: A minimum of 4” is required above the top of the
air curtain for the installation and removal of the inlet screen and access to electrical compartment.
A. When determining the mounting location for the air
curtain(s), make sure that nothing interferes with the curtain of air developed when the discharge vanes are directed from 0° to 20° toward the door opening. If the air stream strikes any obstruction (the top edge of the doorway, a door opening device, etc.), the eectiveness of the air curtain will be greatly reduced. See Figure 2.
B. For optimum performance, the bottom of the air curtain
(discharge nozzle) should be no more than 1” above the top of the door opening with the air curtain(s) mounted ush to the wall. If the air curtain must be mounted higher, it must be spaced out from the wall 3/8” for every inch the air curtain is above the door opening. See Figure 3. For optimum protection, any void between the air curtain and the wall should be sealed along the full length of the air curtain.
C. Do not block (obstruct) the air intake grill. Insucient
airow can cause the unit to overheat.
D. Electric heated air curtain(s) shall:
1. Have a minimum clearance of at least 4” between
the sides and top of the air curtain and any combustible material.
2. Have a minimum clearance of at least 6’ between
the bottom of the air curtain and the oor.
3. Be installed Indoors Only.
E. Proceed to either Section III - Wall Mounting or Section
IV - Suspended Mounting
Discharge Nozzle
20˚
6' minimum*
EXTERIOR
A
R
I
I
A
R
*Electrically Heated Units Only
Figure 2
Net Weight
MODEL
CHD10-1036 50 52 SHD07-1036 50
CHD10-1042 52 55 SHD07-1042 52
CHD10-1048 53 56 SHD07-1048 53
CHD10-1060 54 63 SHD07-2060 70
CHD10-2060 70 96 SHD07-2072 84
CHD10-2072 84 104 SHD07-2084 104
CHD10-2084
CHD10-2096
CHD10-3096
CHD10-2108
CHD10-3108
CHD10-2120
CHD10-3120
CHD08
Ambient
CHD08
Electric
104 110 SHD07-2096 106
106 112 SHD07-3108 150
120 148 SHD07-3120 152
107 119
150 156
108 126
152
159
MODEL
TABLE 2 ­SHD07 Unit Weight
Weight
SHD07
Ambient
TABLE 1 - CHD10 Unit Weight
Flush Mounting
AIR CURTAIN
1"
Top of Doorway
Figure 3
Net
Spacer
Seal
AIR CURTAIN
Spacer
3/8"
3/4"
INTERIOR
3"
2"
4
Page 5
III. WALL MOUNTING
If a wall mounting plate was ordered with the air curtain, proceed to B. Wall Mounting – using the wall mounting plate
(sold separately), otherwise proceed:
A. WALL MOUNTING - without wall mounting plate
1. Making sure that the air curtain is centered over the opening, determine the exact mounting location of the air curtain.
3/4"
1"
7"
NOTE: A minimum of 4” is recommended above the air curtain to provide clearance for installation and removal of the cover housing.
2. Remove the screen by removing screws from the top, bottom and front of the air curtain, and slide the screen away from the blower assembly.
3. The air curtain is equipped with four 1⁄4” keyhole mounting slots on the back of each unit for wall mounting. The slots are spaced 1” from the ends, and 3/4” and 7” from the top. See Figure 4.
4. Mark the wall according to the length of the air curtain. The wall must provide sucient support for the air curtain. If the keyhole slots are not located where suitable support is available, drill new holes in the unit back plate where space is available.
5. The mounting hardware (supplied by others) must be capable of supporting a minimum of three times the net weight of the air curtain. See Weight Chart, Table
1 or Table 2.
6. Keyhole Mounting: Install the mounting hardware (supplied by others), allowing for space to hang the air curtain by not fully tightening. Without touching the blower wheels, lift and slip the air curtain over the mounting hardware by grasping the inlet rings of the blower housing. Tighten the mounting hardware. See
Figure 5.
Keyhole
Mounting
Slots
1/4"
Line-up
Keyholes on
All Screws
Figure 4
Push Backplate Toward Wall
Figure 5
Tighten All Screws
Slide
Backplate
Down
7. Drilled Mounting Holes: Lift the air curtain by grasping the inlet rings on the blower housing, without touching the blower wheels, and install the mounting hardware (supplied by others) through the drilled holes.
8. Reinstall the screen using hardware removed in Step 2.
9. Proceed to Section V - Electrical Connections.
5
Page 6
B. WALL MOUNTING – using the wall mounting plate (sold separately)
1. PREPARATION a. Position and center the mounting plate over
the door opening. The mounting plate must be positioned with the “Z” lip on top. Drill mounting holes on the mounting plate. See
Figure 6.
b. Mark the wall in the center of each mounting
plate hole. The wall must provide sucient support for the air curtain. The mounting hardware (supplied by others) must be capable of supporting a minimum of three times the net weight of the air curtain. See Weight Chart, Table 1 or Table 2. If the location of the marks on the wall do not provide suitable support, mark and drill additional holes.
c. Drill the four holes as marked on the wall and
attach the mounting plate with anchors (if used) and the four mounting screws (provided by others).
2. ATTACHING THE AIR CURTAIN
TO THE MOUNTING PLATE
a. Raise the air curtain over the door (air
discharge nozzle facing down) and on to the mounting plate. First, tilt the unit upward matching the rectangular openings to the “Z” lip on the mounting plate. See Figure 7.
b. Lower the air curtain into place, allowing it to
rest on the lower lip of the mounting plate.
c. After the air curtain is securely attached to the
mounting plate, re-install the two (2) locking screws at the bottom corners. See Figure 7.
Recommended Mounting
Plate Holes
Doorway Opening
1" max.
Doorway
Opening
FIGURE 6 - Positioning of Mounting Plate
Mounting Plate
Lower Lip
IV. SUSPENDED MOUNTING
A. For top mounting using suspension rods, four (4) factory
installed 1/4” threaded inserts are located in the top of the air curtain. See Figure 8.
B. Install 1/4” threaded rods, or other suitable hardware at
a location with sucient support for the air curtain. The mounting hardware (supplied by others) must be capable of supporting a minimum of three times the net weight of the air curtain. See Weight Chart, Table 1 or Table 2.
C. Attach threaded rods, or other suitable hardware to the top
mounted threaded inserts.
D. Proceed to Section V – Electrical Connections
Locking Screws
FIGURE 7
Suspension Rods
1/4” Threaded Insert
Side View
FIGURE 8 - Suspended Mounting
6
Page 7
V. ELECTRICAL CONNECTIONS
All electrical wiring and connections MUST be performed by qualied personnel in accordance with the latest edition of the National Electrical Code ANSI/NFPA No. 70 or, in Canada, the Canadian Electrical Code, Part 1-C.S.A. Standard C22.1 and local codes and regulations.
MAKE SURE THE CORRECT VOLTAGE AS MARKED ON THE UNIT IS USED.
A. A separate line voltage supply with a suitable branch
circuit protection device should be run directly from the main electrical panel to the unit. A disconnect switch for each branch circuit is a required part of this installation. See the voltage label on the unit for circuiting and total electrical load. The wiring diagram is located in the wiring compartment.
B. All eld wiring must be copper with a minimum
insulation of 60°C within approved conduit. If any of the wire supplied with the unit must be replaced, it must be replaced with copper wiring with a minimum insulation of 90°C.
C. Remove the wiring compartment cover on top of the air
curtain. See Figure 9.
D. The top of the air curtain has knockouts on each side of
the wiring compartment. Remove the required knockout and connect the power supply to the air curtain. Connect all supply and control circuit wires according to the wiring diagram provided.
NOTE: For Electrically heated air curtains provided with
the optional remote thermostat, mount and wire the thermostat according to thermostat instructions and wiring diagram.
FIGURE 9
For Electrically heated air curtains proceed to Section
V - Field Connections, otherwise proceed to Section VI ­Airow Adjustments
VI. FIELD CONNECTIONS
A. ELECTRICALLY HEATED MODELS
The heater circuit may be controlled by a remote thermostat,
manually through a unit mounted or remote mounted three position - fan only/o/fan with heat switch. Overheating protection is provided by auto reset thermal cutouts built into the blower assembly (see wiring diagram). Proceed to
Section VII - Operating Instructions.
7
Page 8
VII. OPERATING INSTRUCTIONS
A. GENERAL OPERATION
Air curtain operation may be divided into four areas: control
package, fan activation, fan speed selection, and heat activation. Depending on the type of controls ordered one or more of the following may be applicable. The air curtain must be properly installed before it is used.
1. Control packages control the air curtain’s sequence of operation. Unit modes/control packages are built into the unit and may not be changed in the eld. Refer to your wiring diagram for specics about activation connections and sequence of operation.
a. Basic Control Package – The unit is activated by a door or selector switch. Either switch may be line
voltage or low voltage (24V).
b. Deluxe Control Package – The unit is activated
by a door or selector switch, but has a factory installed time delay allowing the unit to keep running for a period of time after the door closes.
c. Comfort Plus Control Package – Available only on
heated units, the unit is activated by a door or selector switch AND a thermostat to provide supplemental heating. NOTE: Not available with 575V motors.
2. Unheated air curtains will have the fans activated by a door or selector switch or sensor. The unit may be single speed and require no fan speed selector (On/O), or may have three fan speeds which require either a unit or remote mounted switch (O, High, Med, Low).
AIR
INTERIOREXTERIOR
A
R
I
I
A
R
12"
AIR
INTERIOREXTERIOR
R
I
A
A
I
R
FIGURE 10
3. Heated air curtains will have fans activated by a door or selector switch or sensor, but may also be activated by the thermostat in Comfort Plus Mode. The unit has three fan speeds which can be set by either a unit or remote mounted switch (Low, Med, High, O, Low heat, Med Heat, High Heat).
4. Heat activation is controlled by either a unit or remote mounted thermostat, and a unit or remote mounted switch.
B. AIR STREAM ADJUSTMENT
1. With the air curtain operating and the door in its full open position, check to see that nothing is obstructing the airow at the discharge nozzle vanes.
2. Find the air stream split location. Hold a handkerchief by its corners, approximately 12” above the oor. Gently move the handkerchief back and forth in the doorway. Make sure the air is being directed to both the inside and the outside. See Figure 10. The split location is indicated where the handkerchief is vertical with minimal or no uttering.
3. The split location should be approximately 3” outside the
doorway. If necessary adjust the discharge nozzle vanes by de-energizing the unit, loosening the nozzle vane locking screws and adjusting vanes.
8
Page 9
VIII. MAINTENANCE & CLEANING
CAUTION: ELECTRIC SHOCK HAZARD Disconnect power whenever servicing unit. More than one disconnect may be required to de-energize unit.
Keep your air curtain operating at peak eciency by cleaning the blower wheels, motor(s) and intake grill. Buildup of dust on the blower wheels can cause vibration, noise and excessive wear on the motor bearings. The frequency of cleaning will depend on the environment where the unit is operating.
Dirty, dusty or greasy environments could require a cleaning schedule of once every two months. If the environment is not that dirty, the unit(s) should be scheduled for cleaning a mini­mum of once every (6) months.
A. PERFORMING PREVENTIVE MAINTENANCE
1. Disconnect and lockout power to the unit.
2. Remove the intake screen by removing the machine screws located around the bottom, front and top of the screen See Figure 11.
3. Vacuum and scrape (if necessary) to remove the build-up of dirt and debris. The motor(s) are permanently lubricated and require no additional lubrication. Re-install the cover and intake grill.
4. Switch the power on af ter cleaning.
FIGURE 11
CAUTION: STAND CLEAR OF THE UNIT OR WEAR SAFETY GOGGLES AS LOOSE DEBRIS MAY BE PRESENT AND MAY EXIT THE NOZZLE.
IX. SERVICE
Any service performed on the air curtain MUST be done by
qualied personnel.
Berner air curtains require very little servicing. All parts are
easily accessible for periodic inspection and maintenance. Units should be cleaned at least twice a year. Your particular application (the amount of dirt and dust in the air) and location of the unit(s) will determine how often your unit(s) will need to be cleaned and serviced. All motors have permanently lubricated, sealed, sleeve bearings and require no maintenance.
9
Page 10
X. TROUBLESHOOTING
SYMPTOMS CAUSE REMEDY
NO AIR • Electrical Power supply line open (no power) • Check power source, check method of control in
ON position
• Fuse blown/circuit breaker tripped • Replace fuse(s)/reset breaker
• Motor overload tripped • Internally protected motor - should reset
• Failed switch • Replace switch
MOTOR RUNNING/FANS ARE NOT ROTATING
• Broken or fan hub • Replace fan
• Shaft rotating inside fan • Tighten set screws/tighten fan on shaft
• Broken/Loose coupling • Replace/Tighten coupling
ELECTRICAL CONTROLS NOT FUNCTIONING WHEN DOOR IS OPEN
• Selector switch is in o position • Turn switch to “ON” position
• Door limit switch not operating • Repair or replace limit switch
MINIMUM • Air directional discharge vanes misadjusted • Adjust vanes to proper position, see instructions
• Inadequate intake clearance • Move air curtain or remove obstruction Provide adequate space for air curtain
• Blower motor operates below speed • Improve voltage
• Fan rubbing against housing • Free fan from housing
• Fan wheels clogged with dirt • Clean and vacuum fan wheels
• Air stream too weak •
AIR IS NOT HITTING
see installation instructions
FLOOR
• Air stream hits obstruction • Remove obstruction or reposition air curtain (move out
• Negative pressure • Relieve negative pressure by providing make-up air
• Shaft rotating inside fan • Tighten set screws/Replace fan
UNEVEN AIR
• One motor not operating • Repair or replace motor/Check electrical connections
• Nozzle not angled out far enough • Adjust nozzle angle to outside
EXCESSIVE AIR
• Air movement too cold • Add auxiliary heat to overcome wind chill
MOVEMENT AT
• Pushing air outside building • Adjust discharge angle back into building
DOORWAY
SEE AIR IS NOT HITTING FLOOR SYMPTOMS
automatically after cool-down, if not replace motor.
Adjust nozzle to proper position, adjust motor speed;
3
/8” for every 1” up from the door)
ELECTRICALLY HEATED MODELS
NO HEAT • Switch turned to “OFF” position • Turn switch on
• Thermostat not set properly • Change thermostat setting
• Coils burned out due to lack of air • Correct airow problem; replace coils
• Automatic reset thermal cutout failed in open position • Replace automatic thermal cutout
• Manual reset thermal cutout tripped • Reset manual thermal cutout
• Defective switch • Replace switch
NOT ENOUGH • Thermostat in wrong location - thermostat too • Move thermostat away from air stream HEAT close to discharge
• Improper voltage • Supply proper voltage
• Thermostat not set properly • Change temperature setting
TOO MUCH • Thermostat in wrong location • Move thermostat closer to air stream HEAT • Thermostat not set properly • Change temperature setting
• Insucient air over coil • Remove restriction on intake
• Improper voltage • Supply proper voltage
10
Page 11
11
Page 12
XI. WARRANTY
Berner International (“The Company”) warrants all new equipment to be free of defects in workmanship and material for a period of ve years (5 years) on unheated models and two years (2 years) on heated models from the original date of shipment, provided the equipment has been properly cared for, installed and operated in accordance with the limits specied on the nameplate and The Company’s instructions.
The Company will correct by repair or replacement, at its option and expense, any proven defects in said apparatus, subject to the above conditions, provided that immediate written notice of such defects is given to The Company. The warranty does not include any labor incurred for the removal or installation of defective part(s). The Company reserves the right to inspect, or have inspected by a qualied representative, any apparatus at the place of installation before authorizing repair or replacement. Repair or replacement will be made F.O.B. factory with any applicable transportation charges to be borne by the customer. Merchandise not of The Company’s manufacture supplied in piece, or in component assemblies, is not covered by the above warranty, but The Company will give the customer the benet of any adjustment as made with the Manufacturer.
This warranty is void if the apparatus has been tampered with in any way or shows evidence of misuse.
The Company will not assume any expense or liability for repairs made outside its factory without proper written consent from its service manager, nor for any transportation charges on apparatus returned to the factory without written authorization by The Company.
Nothing in the above warranty provisions, however, shall impose any liability or obligation of any type, nature or description upon Berner International if Berner has not received payment in full for the apparatus in question.
THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HERE OF INCLUDING
THE IMPLIED WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
LIMITATION OF DAMAGES Notwithstanding anything to the contrary above, customer’s exclusive remedy for any and all losses or damages resulting from the sale of The Company’s equipment under this agreement, including but not limited to, any allegations of breach of warranty, breach of contract, negligence or strict liability, shall be limited, at The Company’s option, to either the return of the purchase price or the replacement of the particular equipment for which a claim is made and proved. In no event shall The Company be liable for any special, consequential, incidental or indirect losses or damages from the sale of The Company’s equipment under this agreement.
SERIAL NUMBER MODEL NUMBER DATE PURCHASED
Saving energy and creating healthy, comfortable environments
BERNER INTERNATIONAL
New Castle, Pennsylvania
724-658-3551 • 1-800-245-4455 • www.Berner.com
Berner reserves the right to alter specifications without prior notice.
© Copyright 2017 Berner International MADE IN U.S.A.
12
Loading...