Berker 8536 51 00, 8536 51 99 Operation Instructions Manual

Page 1
2 6T 7972-31a
T
est and validation of detection
zone
Set potentiometer2to mode "auto test".
O
The Test mode is available for 3 minutes time and does not take brightness level into account. Each detected movement turns LED A on for 2 seconds. The associated receiver is not under control.
After 3 minutes without detection, the product is set back to auto mode. Limitation of detection zone: You can limit the detection zone using the shutters supplied or by inclining the head.
Mounting
Projection or ceiling mount:
- Fix the wall plate using the supplied screws.
- Clip the detector onto the wall plate
- Tighten the screws to close. For angle mounting, the wall fixing plate is
fitted between the accessory and the detector.
Precautions for installation
For optimum detection conditions, please follow these recommendations:
- Keep the detector protected from solar radiation and bad weather, as it is sensitive to these conditions.
- Maintain 1m distance between the light source and the detector and keep the detector out of the light source.
P
roduct Description and working
principles
This detector allows remotely control of one or more receivers for a given time when a movement is detected in its detection zone. This product can be used in two types of configuration: one detector controls one/several receiver(s); several transmitters control the receiver(s).
O
peration
The receiver(s) is(are) under control as soon as the brightness level as set by potentiometer
2
is considered too low and a movement is detected. Upon detection, the time delay is restarted.
If LED A flashes quickly during configuration, the position of potentiometer
1
is not compa-
tible with the selected function. If LED B flashes quickly or nothing occurs
when starting configuration, check that the batteries are correctly installed and replace them if necessary. Product factory reset is recommended before any new configuration.
Factory reset
Maintain J button down until LED cfg flickers > 10 s, then release. cfg LED turns OFF to signal reset to factory settings end. This operation removes the entire product configuration in any configuration mode. After power switch-on or reset to factory settings, wait for 15 s before to do a new configuration.
Action Adjustments Potentiometer
Use Auto (factory) settings to set automatic lighting turn-on for a given time. Only available when a detector’s time delay is set.
Auto Settings
Put the Lux potentiometer on “auto test”. The settings are predefined:
Lux = , (operating at night only) time = 3 min, sensitivity = max
auto
lux
test
Turn automatic lighting on for a given time. Only available when a detector’s time delay is set.
Installer settings
15 min
30 s
5 min
auto
-
+
lux
test
Adjust sensitivity. Allows setting the range
to avoid disturbance.
-
+
Hereby,Berker GmbH &Co. KGs,declares thatthis motion detector outputis in compliancewith theessential require­ments andother relevant provisionsof Directive1999/5/EC.
The CEdeclaration can beconsulted onthe site:
www.hagergroup.net
Usable in all Europe and inSwitzerland
I
nstalling batteries
J Button
c
fg
c
f
g
LED cfg
Button J
Configuration (button J )
These detectors can be configured in 3 different ways:
quicklink& : configuration without tool, directly
on the device via J button and LED (see configuration instructions quicklink& ).
• tebis TX: configuration using connection device from Hager
• ETS3/ETS4 via KNX-RF/TP gateway: database and description of application software available from the manufacturer.
Configuration by ETS
Press J button for addressing by means of radio/KNX gateway
O
Product factory reset is required to change the configuration mode.
1 6T 7972-31a
6T 7972-31a
1
5 min
s
5 min
a
uto
-
+
lux
test
30
α
I
P
5
5
+ 90°/- 30°
+/-80°
Description
Detection zone
Installation
Wall fixing plate
Adjustment potentiometers
Directional detection head
Adjustments
Shutters
Angle fixing support 8590 02 00
Vertical adjustment
Optimal installation height is 2.5m. The detection zone shall remain free of obstacle.
8 m 16 m
2,5 m
0,5 m
16 m
4 m
LED A LED B
Delay (lighting time)
Brightness
level
Sensitivity (change of range)
1
2
Caution:
-
This device must beinstalled only by a qualified electrician accordingto the i
nstallation standards in forcein the
c
ountry.
O
rder no.
8536 51 00, 8536 51 99
Berker GmbH & Co. KG
Klagebach 38
5
8579 Schalksmühle/Germany Telefon: + 49 (0) 23 55/90 5-0
Telefax: + 49 (0) 23 55/90 5-111
www.berker.com
05/2012
97-85365-100
§
Operation instructions
KNX-RF controller 220° surface-mounted
KNX-RF controller 220°/switch actuator 1 gang surface-mounted
Page 2
3 6T 7972-31a
D
escription of the set 8536 51 99
T
he detector and the receiver must bepreset in
o
rder to operate together. These two products are pre-configuredto operate t
ogether. Only delay, brightness level and
d
etection zones are to be set byuser.
Setting detector’s delay Setting receiver’s delay
15 min
30 s
5 min
15 min
s
5 min
30
Set 8536 51 99 Pre-configured
(
ON/OFF switch function)
1. Clear the previous pre-configuredfunction i
f Set 8536 51 99 is used (seeconfiguration
i
nstructions
quicklink& )
2. Set the potentiometer to position
3
. Configure the "timer"
(
see configuration instructions
quicklink& )
1
detector 8536 51 00
+
1 receiver
R
ecommended configuration:
1. Set the potentiometer to a value different f
rom
2
. Configure ON/OFF switch function (see
configuration instructions
quicklink& )
S
et 8536 51 99
+
1 or several
other receivers
I
n order to have the same delayon each receiver :
1. Set the potentiometer to a value different from
2
. Configure the ON/OFF switch function (see
c
onfiguration instructions
quicklink& )
on other
receivers
I
n order to have a differentdelay on each receiver :
1
. Clear the previous pre-configuredfunction if
Set 8536 51 99 is used (See theConfiguration Instructions)
2
. Set the potentiometer to position
3. Configure the "timer" function (see configuration instructions
quicklink& )
1
detector 8536 51 00
+
several receivers
S
everal detectors
8536 51 00
+
1
or several
r
eceivers
Not recommended (conflict of delays)
1
. Clear the previous pre-configuredfunction if
Set 8536 51 99 is used (See theConfiguration Instructions)
2
. Set the potentiometer to position on both
detectors.
3. Configure the "timer" function (see configuration instructions
quicklink& )
on each receiver
Set 8536 51 99
or
1 detector 8536 51 00
+ 1 or several transmitters
other than detectors
+ 1 or several
receivers
Timer function being not used on the other transmitter(s):
1. Set the potentiometer to a value different from
2. Configure the other transmitter(s) (see configuration instructions
quicklink& )
with a function other than timer
Timer function used on the other transmitters:
1. Clear the previous pre-configuredfunction if Set 8536 51 99 is used (See theConfiguration Instructions)
2. Set the potentiometer to position
3. Configure the "timer" function (see configuration instructions
quicklink& ) on
each receiver for each transmitter involved
Note: During configurationof a detector, Step 2 of the configurationinstructions quicklink& shall be ignored.
TROUBLESHOOTING...
PROBLEM CAUSES SOLUTIONS
Unwanted lamp switch on.
- Permanentheat source is active in thedetection area (trees,bushes shook by wind or presence of dogs,cats in the detectionarea).
- The detector is located on top aventilation grill.
- Limit detector’s rangeby adjusting its inclinationor by fitting shuttering blades to the lens, or by loweringsensitivity using the adjustment knob.
- Move the detector to another location.
The range of the detector is too narrow.
- Detector’s installation heightis not suitable (toohigh or toolow).
- Sloppy ground.
- Modify installation height (2.5 m is optimal).
- Adjust detector’s direction.
Moving vehicle or person is not detected.
- Vehicle’smotor is notenough yet (heat radiationis too weak).
- People move forwards in frontof detector.
- Detector energy too low.
- Install the detector in such away that objects movewithin the area in transverse direction.
- Replace power cells.
Technical specifications
Electrical specifications
Power Supply: 3 x 1,5 V AAA
Operational characteristics
Dimensions (L x w x h): 153 x 91 x 130 mm Luminosity threshold: 5… 1000 Lux Fixed time: 30s … 15min
Sensitivity: min. 20%,max. 100% Limiting the detection zone: adjustable shutters supplied Transmission frequency: 868.3 MHz Transmitter duty cycle: 1% Receiver category: II Range: 100 mon open field Fixing accessories: cornersupport (sold separately) Order no. 8590 02 00
Environment
Operating temperature: -20 … +55°C Storage temperature: -20 … +60°C IK: 04 Protection class: IP55 Resistance to fire : 750 °C
Standards: EN60950-1 ; EN301489-3 ;
EN 300220-2 ; EN 50491-3
(
Please refer to Detector User's Instructions). Other devices can be added to the kit.
Various configuration options are available
When a detector is associated with a receiver, only 2 f
unctions are available, depending on potentiometer’s
p
osition:
- (Red/Green LED)or timer (Red flashing L
ED) according to the case
-
Delete (LED is OFF)
The receiver will offer only thefunction set by the p
otentiometer.
When a product is factory reset, p
re-configuration is removed.
I
t should then be configured again.
4 6T 7972-31a
OCOM 113657
Loading...