Beretta SCF-20N, SCN-20S, SCI-25N Installation Manual

Page 1
SOLAR
COLLECTOR
SCF-20N
INSTALLATION MANUAL
SOLAR
Page 2
This manual, Code 20051442 - Rev. 2 (01/14) comprises 12 pages.
Conformity
CONFORMITY
Solar collectors conform to EN 12975 standard and to Solar Keymark certification standard.
b
This product must only be used for the purpose for which it is designed and made, as specified by B. B declines all responsibility, contractual or other, for damage to property or injury to persons or animals caused by improper installation, adjustment, maintenance or use.
Range
MODEL CODE
SCF-20N 20050326 SCF-20N (pack of 2) 20050328 SCF-20N (pack of 7) 20050329
RANGE
Contents
CONTENTS
The following symbols are used in this manual:
b
CAUTION! =
Identifies actions that require caution
and adequate preparation.
a
STOP! =
Identifies actions that you MUST NOT do.
This manual, Code
- Rev. comprises pages.
System layout .................................. 3
Identification...................................3
Technical specifications ..........................4
Connections ...................................5
Water circuit ...................................6
Unpacking the product ..........................7
Handling......................................7
Installation .................................... 8
Filling the circuit ................................9
Checks ......................................10
Maintenance.................................. 10
Page 3
System layout
SYSTEM LAYOUT
1120
1086
1856
68
90
(*)
(**)
(*) Alternative collector return (**) Alternative collector outlet
b The outlet and the
return must be connected to opposite sides.
Collector
probe socket
Collector
outlet
Collector return
Direction of flow of
heat transfer liquid
Glass 3,2 mm.
Connector Ø 22 mm.
Identication
IDENTIFICATION
Code
Year of production
Serial Number
Description
Made in Italy
by Riello S.p.A.
Flat plate
solar collector
Dimensions
Gross area
Aperture area
Absorber area
Empty weight
Maximum operating pressure Stagnation temperature Liquid content Max glycol concentration Heat transfer fluid: water+propylene glycol
Data plate
Serial number plate
CODICE : 20038360
FABBRICATO IN ITALIA
DESCRIZIONE : CP20TSA
S/N :
COLLETTORE SOLARE PIANO
DIMENSIONI: 1856X1087X90 mm SUPERFICIE LORDA: 2,02 m
2
TEMPERATURA DI STAGNAZIONE: 198 °C
SUPERFICIE DI APERTURA: 1,81 m
2
CONTENUTO LIQUIDO: 1,5 l
SUPERFICIE ASSORBITORE: 1,77 m
2
PESO A VUOTO: 30 kg LIQUIDO TERMOVETTORE:
ACQUA+GLICOLE PROPILENICO
MAX CONCENTRAZIONE GLICOLE: 50%
MAX PRESSIONE ESERCIZIO: 10 bar
da Riello S.p.A.
20038499_E1
EN 12975
Certif. 011-7S1765 F
12000025
Anno di produzione
SERIALE PROGRESSIVO
Cod.
Mod.
Serial number
b
If these plates or any other means of clearly identifying the product are defaced, removed or lost, proper installation and servicing may be rendered difficult.
Page 4
Technical specications
DESCRIPTION
Total area 2,02 m
2
Exposed area 1,81 m
2
Effective absorption area 1,77 m
2
Connections (copper pipe) 4 x Ø 22 mm Empty weight 30 kg Liquid content 1,5 l Recommended flow rate for each line per m
2
of collector 30 l/(h x m2)
Minimum flow rate for each line per m
2
of collector 20 l/(h x m2)
Maximum flow rate for each line per m
2
of collector 200 l/(h x m2) Glass thickness 3,2 mm Absorption (α)
~ 95 %
Emissions (ε)
~ 5 % Maximum permitted pressure 10 bar Stagnation temperature 198 °C Maximum number of collectors in a line 6
Efficiency curve
0,75
0,80
0,65
0,70
0,55
0,60
0,45
0,50
0,40
0,35
0 0,01 0,02 0,03 0,04 0,05 0,06 0,07
0,08
Tm[m2K/W]
*
Optical efficien-
cy of absorber
(ηο)
Thermal dispersion factor of
absorber
a1 W/(m
2
K) a2 W/(m2K2)
0,764 4,33 0,0069
Tested according to EN 12975, referred to a 33.3% wa­ter-glycol mix, flow rate of 75 l/h, and irradiation G = 800W/m
2
.
Tm = (Coll._inlet _temp.+Coll._outlet_temp.)/2
T*m =
(Tm-T_ambient)/G
WIND AND SNOW LOADS ON COLLECTORS
Installation
height above
ground
Wind speed
Mass in kg to secure collector
against lifting by wind
Load on roof from wind, snow, and
collector weight
At angle of
45
° At angle of 20° At angle of 45° At angle of 20°
0 - 8 m 100 km/h 80 kg 40 kg 320 kg 345 kg
8 - 20 m 130 km/h 180 kg 90 kg 470 kg 430 kg
20 - 100 m 150 km/h 280 kg 150 kg 624 kg 525 kg
Maximum permitted load from wind and snow (including combined loads) on surface of collector: 1500 Pa (175 km/h).
TECHNICAL SPECIFICATIONS
Page 5
Connections
sensor pocket
toward the
heat transfer circuit
from the
heat transfer circuit
ring nut
ring nut
olive
straight union
olive
plugs
olive
plugs
olive
straight
union
pipe
installation
ring nut
ring nut
olive
straight
union
ring nut
ring nut
ring nut
ring nut
olive
straight union
pipe installation
The collectors in a line are connected so that the heat transfer fluid goes through them in parallel. Therefore the four copper tubes between the collectors are connected between them by brass compression fittings for copper pipes. Two out of four of the copper tubes of the extreme collectors of the line must be sealed with brass compression stop ends. The connection with the heat transfer circuit that goes toward the heat exchanger must be the one near the sensor pocket of the last collector of the line. The connection with the circuit that comes back from the heat exchanger must be at the bottom of the first collector of the line (see the picture above). It is also possible to connect more then one line of solar collectors using brass compression elbows or welding the tubes of the circuit. Multi-collector installations must consist of strings of the same number of collectors (see the following sample diagrams).
Two lines in series Two lines in parallel
T T
Diameter of connection pipes for a specic ow rate of 30 lt/m2h
Total surface area (m2) 2 - 4 6 - 12 14 - 20
Diameter of copper pipe
(mm)
10 - 12 14 18
Diameter of steel pipe (inch) 3/8" - 1/2" 1/2" 3/4"
CONNECTIONS
Page 6
Water circuit
WATER CIRCUIT
1
Solar collector
2
Storage cylinder
3
Collector probe
4
Disconnect valves
5
Non-return valve
6
Temperature gauge
7
Vent valve
8
Safety valve
9
Pressure gauge
10
Drain
11
Expansion vessel
12
Pump
13
Flow regulator
14
Flow meter
15
Vent cock
16
Manual bleed valve (acces­sory)
17
Plugs
18
Heat transfer fluid recovery
M
Collector outlet
R
Collector return
3
11
R
M
°C
M
4
4
4
9
8
11
10
13
14
2
6
12
Water control system
5
7
15
16
17
17
18
b
If copper pipes are used, joints must be hot brazed.
b
We recommend the use of stainless steel pipes spe­cially made for solar collectors for the outlet, return and probe pipes. The probe cable should be of the shielded type.
b
Do not use plastic or multistrate pipes. Operating temperature can exceed 180°C.
b
Pipe lagging must be able to resist high temperatures (180°C).
Pressure drop in solar collectors (*)
Pressure drop (mbar)
Flow rate (l/h)
15
12,5
10
7,5
5
2,5
0
0 50 100 150 200 250 300 350
400
(*) With antifreeze-water mix of 33,3% / 66,7% and heat transfer medium temperature = 20°C.
Page 7
Unpacking the product
UNPACKING THE PRODUCT
The solar collectors are packed in various ways depending on the number of units supplied:
A Packages of 1 or 2 collectors B
Packages of 7 collectors
Pallet contents:
- collector
- document envelopes containing instruction manuals, test certificate and bar code label.
b
The instruction manual is an integral part of the solar connector. Once located, read it thoroughly and keep it safe.
b
STORE IN A DRY PLACE AND DO NOT EXPOSE TO DI­RECT SUNLIGHT UNTIL THE TIME OF INSTALLATION!
The packaging is not designed to protect the prod­uct against rain or humidity. It can also degrade if ex­posed to direct sunlight. Failure to comply with these precautions could lead to irreparable damage to the product.
A B
Handling
HANDLING
Once you have removed the outer packaging, proceed as follows to unpack and handle the solar collector:
- Remove the PVC wrapping to free the solar collector from the pallet.
- Tilt the solar collector slightly and grip it at the four points shown (A) to lift it.
- Use a hoist or other suitable lifting equipment to hoist the solar collector on to the roof.
b
Wear suitable personal protective equipment and use suitable safety devices.
a
Do not dispose of packaging material into the envi­ronment, or leave it within the reach of children, since it can become a potential hazard. Dispose of packag­ing material in compliance with applicable legislation.
a
Do not lift the solar collector by its water fittings.
A
A
A
A
Page 8
Installation
INSTALLATION
GENERAL INSTRUCTIONS
Assembly
The system must be installed by specialist personnel. Use only the assembly material supplied with the solar collec­tor. The supporting framework and all masonry or brick­work fixing points must be checked by a person expert in static loading, and must be suitable for the nature of the installation site.
Static load
The solar collector must only be installed on roofs or frames that are strong enough to support its weight. The strength of the roof or frame must be verified on site by a person ex­pert in static loading before the solar collector is installed. During this process, it is important to verify the suitability of the supporting frame to hold the screw fasteners that fix the solar collector in place. An expert in static loading must verify that the entire frame complies with relevant stand­ards, especially in areas liable to snow and areas exposed to high winds. Conditions (gusts of wind, formation of wind vortices, etc.) at the point where the solar collector is to be installed must be carefully considered since these can increase the loads on the supporting structure.
Lightning protection
The metal piping of the solar heating circuit must be con­nected to the main potential compensation bar by a (yel­low-green) copper wire (H07 V-U or R) of at least 16 mm
2
. If a lightning conductor system is already installed, the solar collectors may be connected to the existing system. Alter­natively, the solar collector piping may be connected to ground via a ground wire sunk into the earth. Ground wires must be sunk outside the house. The ground wire must be connected to the potential compensation bar through a wire of the same diameter.
Water connections
The solar collectors must be connected in series using the fittings and seal rings provided. If flexible hoses are not used to connect up the ends of solar collector lines, we recommend that you fit devices in the connecting pipes to permit thermal expansion (U-type expansion joints, sec­tions of flexible hose or dedicated expansion joints). Pro­vided adequate expansion joints are used, up to 6 solar collectors may be connected in series. Make sure that the seal rings are correctly positioned in their seats. When tightening a fitting with a pipe wrench or spanner, always hold the opposite fitting steady with a second tool to avoid damaging the absorber.
b
All pipes in the water circuit must be insulated in con­formity to relevant standards. Lagging and insulation must be protected against damage by the weather and birds and animals.
Angle of collectors / General
Solar collectors are designed to be installed at angles of between 15° (minimum) and 75° (maximum). Make sure that the bleed and vent valves of the collectors remain open while the collectors are being installed. Take care to protect all fittings, connections, bleed and vent valves against dirt and dust etc. In installations which serve pri­marily to produce domestic hot water in the summer, install the collectors facing from east to west at an angle of be­tween 20 and 60°. The ideal orientation is southwards, at an angle equal to the latitude of the location minus 10°. If
the system sustains the greatest thermal load in the winter (as in systems that combine domestic hot water production with central heating), install the collectors facing south (or south-east or south-west) at an angle greater than 35°. The ideal orientation is southwards, at an angle equal to the latitude of the location plus 10°.
b
Work near uncovered and live electrical wires, with which it is possible to come into contact, is only per­mitted under the following conditions: wires must be free from voltage for the entire duration of the work; parts remaining live must be covered or accidental contact prevented; the following minimum safety dis­tances must be respected: 1m (for voltages of up to 1000 Volts), 3m (for voltages from 1000 to 11000 Volts), 4m (for voltages from 11000 to 22000 Volts), 5m (for voltages from 22000 to 38000 Volts), >5m (if the voltage is not known). Contact with open, live electrical wires may lead to electrocution and may even be fatal.
b
Always wear safety goggles when drilling. Always wear safety shoes, cut-proof protective gloves and a safety helmet when performing installation work.
b
Before beginning installation work on roofs, install the necessary fall prevention and fall arrest devices and ensure that all applicable safety standards are ap­plied. Use only tools and materials that conform to the safety standards that are applicable in the place of work.
b
Only wear overalls that have a safety harness (with a suitable safety or fall-arrest belt, ropes or slings, fall dampers or dissipaters). In the absence of adequate fall prevention and security devices, failure to use a proper safety harness may lead to falls from great heights with serious or even fatal consequences.
b
The use of ladders leaned against walls can lead to serious falls if the ladder slips, slides of falls. When using ladders, always ensure that they are stable, and that suitable ladder stops are present. If possible secure the ladder with hooks. Make sure that there are no live electrical wires near the ladder.
Page 9
Filling the circuit
FILLING THE CIRCUIT
Perform the following steps before starting up the system.
1 - FLUSHING AND SEAL TESTING THE SYSTEM
If copper piping has been used and joints have been hot brazed, flush out the system to remove any brazing resi­dues. Seal test the system after you have flushed it out.
b
Fill the solar collector with glycol/water mix immedi­ately after flushing it out, because flushing water may remain trapped in the circuit (with a consequent risk of freezing).
2 - PREMIXING WATER + GLYCOL
Glycol anti-freeze is supplied separately in standard vol­umes and must be premixed with water in a suitable con­tainer before being used to fill the system. For example, a mix of 40% glycol and 60% water provides anti-freeze protection down to a temperature of -21°C.
b
The propylene glycol supplied is specially formulat­ed for solar collector applications and remains fully efficient throughout the -32 to +180°C temperature range. It is also non-toxic, biodegradable and bio­compatible.
b
Do NOT part fill the circuit with pure glycol then add water later.
3 - FILLING
b
Only ll and bleed the solar circuit at ambient temper­ature, with the collectors shielded from the sun’s rays.
1 Open the non-return valve (A) 2 Open the air vent at the highest point in the system (see
figure alongside) and keep it open throughout the filling
operation 3 Open the vent valve (7) 4 Pump the heat transfer fluid around the circuit with an
external filling pump until all air bubbles have been
eliminated. Close the manual bleed valve 5 Temporarily raise the pressure in the system to 4 bar 6 Start up the system for about 20 minutes 7 Bleed the circuit again from step 2 until all the air has
been removed 8 Set the circuit pressure according to the table on the
next page in order to ensure a minimum pressure of 1.5
bar at the height of the collector field 9 Close the non-return valve (A) and any open vent valves
to prevent the heat transfer fluid from evaporating.
b
Make sure that you have bled all the air out of the sys­tem, using the water control system vent too.
Heat transfer fluid filling pump (accessory). A manual bleed valve is not required if this pump is used.
Anti-freeze Temperature Density
50% -32 °C 1.045 kg/dm
3
40% -21 °C 1.037 kg/dm
3
30% -13 °C 1.029 kg/dm
3
°C
M
A
R
M
7
Anti-freeze mix
Water control system
Heat transfer fluid filling pump
Solar collector
Manual
bleed valve
(accessory)
Heat e
xchanger
of solar
Page 10
10
H
H Pressure at boiler
up to 15 m 3 bar
15 - 20 m 3,5 bar 20 - 25 m 4 bar 25 - 30 m 4,5 bar
General rule: p [bar] = 1.5 + H [m] / 10
Checks
On completion of the installation, perform the checks listed in the table below.
CHECKS
Collector circuit
Cold circuit pressure:____bar (see table
above)
Collector circuit seal test
Safety valve check
Anti-freeze checked to - ___ °C
pH of heat transfer fluid = ____
Collector circuit bled
Flow rate of 30 l/h per m
2
checked
Non-return valve functioning
Solar collectors
Visual check of collectors
Collectors cleaned if necessary
Visual check of collector fixing points
Visual check of roof impermeability
Visual check of insulation/lagging
Maintenance
Service the system and perform the checks listed in the tables below at least once every two years.
MAINTENANCE
Collector circuit
Cold circuit pressure:____bar (see table
above)
Collector circuit seal test
Safety valve check
Anti-freeze checked to - ___ °C
pH of heat transfer fluid = ____
Collector circuit bled
Flow rate of 30 l/h per m
2
checked
Non-return valve functioning
Solar collectors
Visual check of collectors
Collectors cleaned if necessary
Visual check of collector fixing points
Visual check of roof impermeability
Visual check of insulation/lagging
Checking the heat transfer liquid
Check the anti-freeze effect and the pH level of the heat transfer liquid every 2 years.
- Use an instrument like a refractometer or densimeter to check the anti-freeze effect (which must have a nominal pro­tection value of approx. -30°C). If the protection threshold is higher than -26°C, replace the mix, or add anti-freeze as required.
- Use litmus paper to check the pH (nominal value approx. 7.5). If the measured value is below 7, change the heat transfer liquid.
Page 11
11
Page 12
20051442 - Rev. 2 (01/14)
Via Risorgimento, 13 - 23900 Lecco (LC) - Italy
Customer Service 199.13.31.31
www.berettaclima.it
The manufacturer strives to continuously improve all products. Appearance, dimensions, technical specications, standard equipment
and accessories are therefore liable to modication without notice.