Beretta Power Plus Box 1001 INT, Power Plus Box 1001 EXT Installation Manual

Installation Manual
CONDENSING
Power Plus Box 1001 INT-EXT
Installation Manual
EN
This manual, Code 20073959 - Rev. 4 (12/15) comprises 40 pages.
2
RANGE
MODEL CODE
Power Plus Box 1001 INT 20067835 Power Plus Box 1001 EXT 20067836
CERTIFIED COMPANY UNI EN ISO 9001:2008 UNI EN ISO 14001:2004
This manual, Code
- Rev. comprises pages.
ENGLISH
Contents
CONTENTS
The following symbols are used in this manual:
b
CAUTION! =
Identifies actions that require caution
and adequate preparation.
a
STOP! =
Identifies actions that you MUST NOT do.
1 GENERAL INFORMATION ................3
2 WARNINGS............................3
3 TECHNICAL FEATURES .................4
3.1 Main features ............................ 4
3.2 Advantages.............................. 5
3.3 Safety devices............................ 5
3.4 Components ............................. 6
4 INSTALLATION.........................9
4.1 Product packaging and identification.......... 9
4.2 Installation premises ....................... 9
4.3 System cleaning and water treatment ........ 10
4.4 General instructions ...................... 10
4.5 New heating systems ..................... 10
4.6 Upgrading existing systems ................ 10
4.7 Corrosion............................... 10
4.8 Positioning and preparation for installation..... 11
4.9 Condensate outlet........................ 11
4.10 Water circuit ............................ 12
4.11 Exhaust flue............................. 12
5 INSTALLATION DIAGRAMS .............12
6 ELECTRICAL SYSTEM .................14
6.1 Power supply ........................... 14
6.2 Electrical connections..................... 14
6.2.1 Connection to mains ...................... 14
6.2.2 Connection to thermoregulators .............15
6.2.3 Connection to pumps ..................... 15
6.2.4 Connection to room thermostats (on/off) ...... 15
6.2.5 Connection to weather temperature probe..... 15
6.2.6 Frost protection .......................... 16
6.2.7 Connection to 0-10v external thermoregulator ..17
6.2.8 Connection to alarm device ................ 17
6.3 Emergency mode ........................ 17
7 GAS VALVE CALIBRATION ..............18
8 USE AND ADJUSTMENT ................19
8.1 Control panel: description.................. 19
8.2 Display mode ........................... 20
8.3 Display mode ........................... 20
8.4 Changing the user parameters .............. 21
8.5 Monitor mode ........................... 21
8.6 Installer programming mode................ 22
8.7 Test mode .............................. 23
8.8 Error mode ............................. 23
8.9 Permanent block ......................... 23
9 SETTING FUNCTIONING PARAMETERS ...24
9.1 Setting the heating parameters.............. 24
9.2 Setting the DHW parameters ............... 25
9.3 Heat control setting....................... 26
10 LIST OF PARAMETERS .................31
11 ERROR LIST ..........................33
11.1 Master board errors ...................... 33
11.2 Slave board errors ....................... 33
12 WIRING DIAGRAMS....................35
13 TECHNICAL SPECIFICATIONS ...........37
3
1 GENERAL INFORMATION
Dear Customer, congratulations on your choice and thank you for placing your confidence in our products. With
Power Plus Box 1001
you have chosen technology that is the very essence of energy saving and functionality. Moreover, all B products conform to the strictest directives and European standards in force.
This product was produced, amongst others, in conformity to the following directives and standards:
- Directive 2009/142/EC - Gas Appliances
- Directive 92/42/EEC on efficiency requirements and Annex E and Pres. Republic Decree n. 412, 26 August 1993 (****)
- Electromagnetic Compatibility Directive 2004/108/EC
- Low Voltage Directive 2006/95/EC
- Ecodesign Directive 2009/125/CE for energy-related products
- Delegated Regulation (EU) N. 813/2013
- EN 15417 Gas-fired central heating boilers - Specific requirements for condensing boilers with a nominal heat input greater than 70 kW but not exceeding 1000 kW
- EN 13836 Gas fired central heating boilers - Type B boilers of nominal heat input exceeding 300 kW, but not exceeding 1000 kW.
The
Power Plus Box 1001
condensing modular systems moreover conform to the regulatory provisions pursuant to the INAIL “R” File, section R.3.B.
B has been certified with UNI EN ISO 9001/2000 since
22.07.2004.
Power Plus Box 1001
is furthermore a product having to its
credit:
- European Conformity Mark (based on Directive 92/42/CEE) issued by the authorized German certification organization ;
- Maximum energy efficiency class (according to Directive 92/42/EEC) identified by the symbol ****;
- Classified in the strictest class for nitrogen oxide­related pollution (fifth grade according to UNI EN
297)
- Patented heat exchanger.
2 WARNINGS
b
The heating unit must be used for the purpose for which it was specifically designed and produced. Any whatsoever contractual or extra-contractual liabilities for damages caused to persons, animals or objects due to errors in installation, adjustment, maintenance and improper usage are to be excluded.
b
Installation must fully comply with provisions of the law in force and instructions provided by the manufacturer to ensure safety and correct functioning, always calling upon professionally qualified technical personnel who will issue the declaration of conformity for the installation accomplished with good workmanship, in compliance to regulatory provisions in force and guidelines given in this handbook. The appliance must be installed in appropriate premises and together with the specific systems installed according to the law.
b
Commissioning will be carried out by personnel from the authorized Technical Assistance Centre only and
within 8 days from when the appliance was installed. After initial ignition the Technical Assistance Centre will fill in the warranty certificate, leaving the user their part to be kept, marking the beginning of the period of guarantee at the terms and conditions specified on the relative slip.
The appliance in its original packing may be exposed to temperatures between 4°C and 40°C. Do not expose the appliance to bad weather conditions after it has been unpacked, anyhow to temperatures below 4°C or above 40°C until it has been connected up to the water, gas and electricity mains so as to be able to activate the frost protection systems described in paragraph 6.2.6.
b
Check that the product is complete, undamaged and as ordered as soon as you receive it. Report any discrepancies or damage to the B dealer who sold it.
b
In case of leaks, disconnect the heating unit from the mains, close the water from the mains and promptly contact the Technical Assistance Centre.
b
Regularly check that the condensate drain is free from obstruction.
b
Regularly check that the working pressure of the water circulation system, when cold, is below the maximum limit specified for the appliance. If not, contact the Technical Assistance Centre.
b
Maintenance jobs on the heating unit must be carried out by personnel from the authorized Technical Assistance Centre. Maintenance must be performed at least once a year. Correct maintenance is essential for safety as well as for the efficiency and long working life of the product. Proper maintenance keeps consumption and emissions down, and ensures that the product continues to operate reliably over time. Analyse the combustion fumes before commencing maintenance. The results of fume analysis can give a clear idea of what servicing or repairs are needed.
b
We recommend cleaning inside the exchanger once a year, extracting jet and burner and removing any installation debris by suction. This operation will be done by personnel from the Technical Assistance Centre only.
b
The warranty slip endorsed during the course of commissioning will have to be produced for any servicing required during the guarantee period. The manufacturer shall not be held liable for any damages caused by mishandling, improper use or errors in installation, use and maintenance work on the appliance. In the event of breakdown or malfunction switch off the appliance, avoiding to make any attempt to repair it and contact the Technical Assistance Centre.
b
This manual must be read carefully for the boiler to be used rationally and safely, and must be kept with care so as to be on hand where required by the technician or installer, to facilitate the appropriate installation, running and maintenance of the boiler. B will not be held liable for any translations possibly giving rise to wrong interpretation. This manual is an integral part of the heating unit and must consequently be kept with care and must ALWAYS accompany the boiler even when passed on to another owner or user or transferred to another installation. Ask the Technical Assistance Centre for another copy if it should be lost or damaged.
4
a
Children and people with disabilities or without experience and specific knowledge are forbidden to use the heating unit unless they are assisted by a qualified person responsible for their safety.
It is forbidden to use electrical devices or equipment, such as switches, appliances, etc. if there is a smell of gas or un-burnt products. If so:
- ventilate the room, opening doors and windows;
- close the gas valve at the mains;
- immediately call in the Technical Assistance Centre or professionally qualified personnel.
a
It is forbidden to touch the heating unit with bare feet or parts of the body wet.
a
It is forbidden to start on any technical or cleaning jobs before disconnecting the heating unit from the power mains.
a
It is forbidden to alter the safety and adjustment devices without permission and instructions from the heating unit manufacturer.
a
It is forbidden to obstruct the condensate drain.
a
It is forbidden to pull, detach, twist the wiring coming out of the heating unit, even if unplugged from the power supply.
a
It is forbidden to obstruct or reduce the size of air vents.
a
It is forbidden to expose the boiler to atmospheric agents (if it is not a specific unit for outdoors).
a
It is forbidden to leave containers or flammable substances in the premises where the boiler is installed.
a
Do not dispose of packaging material into the environment, or leave it within the reach of children, since it can become a potential hazard. Dispose of packaging material in compliance with applicable legislation.
a
The user is forbidden to open the cupboard containing the heating unit. Any jobs on the inside of the latter must be done by the Technical Assistance Centre or by qualified personnel.
a
It is forbidden to discard the product as household waste. At the end of its service life, it can be consigned to specific selected waste centres provided by the local authorities or else to dealers providing this service. Disposing of a domestic appliance separately will prevent possible harmful consequences for environment and health derived from inappropriate disposal, likewise making it possible to recuperate the materials it is made of with substantial savings in energy and resources.
3 TECHNICAL FEATURES
3.1 Main features
Power Plus Box 1001
is a modular condensing, premixed, jet heating unit, comprising a modular unit at 26 to 128 kW equipped with weather adjustment device. The efficiency of the generators reaches 109% based on the lower heat potential of natural gas (Hi) making it possible to use a flue manifold entirely made of plastic (PP). The system also enables continual modulation of the gas and combustion air flow. The
Power Plus Box 1001
heating unit is the optimum as far
as operating costs (up to 109% efficiency per Hi, see Figure
1), reliability and flexibility is concerned. Rapid connection to any type of heating and domestic hot water system with accumulation is in fact possible owing to a special more powerful heat exchanger, new electronic control, modulating electronic circulator and high efficiency. Furthermore, the “master” board, supplied with each heating unit, ensures the latter a simple conFiguretion and enables it to be adapted to any type of system, optimizing its performance in terms of creating comfort and cutting down on consumption. All the safety devices provided in the INAIL “R” File for this particular application, have been installed on the flow manifold, downstream from the last combustion unit. A special water compensator is housed inside the hood with attachments for simple connection to the systems directly controlled by the master board which is supplied with the heating unit:
- Direct system (high temperature)
- Mixed system (low temperature)
- Hot water system.
Distribution units are available as an accessory for each of the above mentioned systems. The heating unit thus becomes a complete, versatile functional “system” to install in a variety of plant typologies. All the systems and relevant functional components (circulators, mixer valve and temperature probe) are entirely controlled by the master board and are connected up to the latter, without the help of additional boards. Room thermostats in the unit’s system-related areas can also be connected up to said board. The system can also be extended to numerous additional zones by a board called “zone master”, which is not included in this manual.
5
Figure 1
3.2 Advantages
- Totally pre-mixed micro-flame jet burner;
- condensing stainless steel exchanger, with efficiency up to 109% (see Figure 1);
- maximum exhaust flue exit temperature 80°C;
- PPS plastic exhaust flue manifold, self-extinguishing (see paragraph 4.11);
- modulating electronic primary circulator at low consumption;
- weather temperature adjustment device supplied;
- hot water and systems control at different temperatures, with or without function priority;
- automatic summer/winter switch-over;
- minimum flow capacity of thermal carrier fluid controlled by a differen-tial pressure switch;
- compensator with inner partition for connection to three systems;
- INAIL safety organs mounted in factory;
- appliance complete and ready to be connected up to the installation.
3.3 Safety devices
All the heating unit functions are electrically controlled and any fault will cause arrest of the heating unit and the gas valve to automatically close. The water circulation system includes:
- automatic resetting safety thermostat;
- differential water pressure switch acting as a flowmeter;
- temperature probe on flow and return controlled by a certified electronic device to carry out safety functions with dual-processor technology. The flow temperature is continually controlled by these devices as well as the Δt between flow and return by acting on the primary circulator modulation;
- modular flow temperature adjustment.
The combustion system includes:
- gas solenoid valve in B+C class with pneumatically compensated gas flow dependent on air intake flow capacity (air/gas ratio 1:1);
- ionization electrode for continual flame control;
- exhaust flue duct temperature control.
Protective actions and therefore closure of gas valves on each heating unit are activated in the following cases:
- flame burnt out;
- over-temperature in exchanger system;
- high temperature of exhaust fumes;
- reduced air flow.
a
The appliance must not be started up, even temporarily, where the safety devices have been mishandled or excluded.
b
Safety devices must be replaced by the authorized Technical Assistance Centre only, exclusively using original parts.
6
3.4 Components
Power Plus Box 1001
comprises a metal cupboard containing the condensing combustion unit connected to a separator, also acting as a distribution organ to three distinct systems (high T, low T and hot water), see diagram in Figure 2.
Figure 2
1
Heat exchanger
2
Burner
3
Jet
4
Venturi tubes
5
Gas valve
6
Vent valve
7
Safety thermostat
8
Min. and differential pressure
9
Flow temperature control
10
Return temperature control
11
Flue temperature control
12
Return pipe
13
Flow pipe
14
Gas pipe
15
Air inlet
16
Exhaust flue duct
17
Condensate outlet
18
Condensate manifold
19
Two-way gas valve
20
Fuel check valve
21
Separator
22
Separator drain cock
23
Separator vent valve
24
Modulating circulator
25
VIC probe pit
26
Safety valve
27
Max. INAIL pressure gauge
28
INAIL gauge
29
INAIL thermometer
30
Expansion tank opening
7
DIMENSIONS AND CONNECTION POSITIONS
Power Plus Box 1001 INT
Figure 3
Power Plus Box 1001 EXT
Figure 4
1
Flow low temperature
2
Return low temperature
3
Flow high temperature
4
Return high temperature
5
Return high temperature
6
Return hot water
7
Flow low temperature*
8
Return low temperature*
9
Return high temperature*
10
Return hot water*
11
Condensate outlet
12
Exhaust flue duct
13
Gas inlet
8
SYSTEM COMPONENTS
Figure 5
1
Hydraulic separator
2
Flow pipe
3
Return pipe
4
Gas pipe
5
Vent valve
6
Cock
7
Drain cock
8
Temperature gauge
9
Gauge fitting with cock
10
Damper device for gauge
11
Pressure gauge
12
Thermometer pit
13
Maximum pressure switch
14
Fuel check valve
15
5.4 bar safety valve
16
Expansion tank/filling fitting
17
Flow probe pit
18
Exchanger
19
Burner
20
Fan
21
Venturi tubes
22
Air inlet pipe
23
Gas valve
24
Exhaust flue duct
25
Condensate drainpipe
26
Vent valve
27
Ignition detection electrode
28
Safety thermostat
29
Gas cock
30
Diff. Pressure switch
31
Condensate drain manifold
32
Return probe
33
Exhaust flue probe
34
Master board
35
Slave board
36
Pump control board
37
Flow hot water system connection
38
Return hot water system connection
39
Flow high temperature connection
40
Return high temperature connection
41
Flow low temperature connection
42
Return low temperature connection
43
Modulating circulator
9
4 INSTALLATION
b
Power Plus Box 1001
heating units must be installed in conformity to the latest provisions of the law and standards in force concerning heating units, condensing boilers and/or other applicable regulatory provisions.
4.1 Product packaging and
identication
The
Power Plus Box 1001
heating unit is supplied, packed
and protected by a strapped carton.
Figure 6
1
Boiler
2
Control panel
3
EC marking/Symbol cartouche
4
Packaging
5
Polyester corners
6
Polyester protection panel
7
Strap
Details of the product are written on the outside: model, power, version and type of fuel. Contact your local dealer in case of any differences with the order. Ensure the goods are intact and complete after unpacking them.
b
Do not leave the packaging within the reach of children as it could be a potential source of danger.
The tag on the front side of the boiler’s electrical board, contains the following information:
- Product name
- Serial number
- Product identification code
- CE certification number
- Gas type and pressures from mains
- Power type from mains
- Rated heat capacity (Qn)
- Rated working power (Pn)
- Efficiency according to 92/42/EEC Directive (η)
- Max pressure and temperature (Pms)
- Primary system (T)
- NOx class (NOx)
Figure 7
a
It is forbidden to remove or mishandle the identification plates, markings and any other making it difficult to safely identify the product.
CONNECTION
DIMENSION
CONNECTION
TYPE
REMARKS
Water
distribution
2” Threaded
Flow/return
connections
for hot water,
high/low
temperature
systems
Gas fitting 1” Threaded
Exhaust flue
duct
Ø110 Socked
Piping in
plastic material allowed
Condensate
outlet
50 mm Socked
See
paragraph
4.1.8
4.2 Installation premises
The heating unit must be installed in premises used exclusively for the latter conforming to standards and legislation in force and where combustion exhaust products and combustion air intake is conveyed out of said premises. Where combustion air is instead taken from the installation premises then the latter must be equipped with suitably sized vents conforming to standards.
10
b
The space required to reach the safety and adjustment devices and to carry out maintenance must be considered. We recommend leaving a space of at least 500 mm at the back of the appliance.
b
Ensure that the degree of the heating unit’s electrical protection is compatible with the characteristics of the installation premises.
b
Electrical parts must be placed at a height of no less than 500 mm from the ground where heating units are supplied with fuel gas with specific weight exceeding that of air.
b
Heating units may not be installed out in the open (unless they are not specific outdoor units).
b
The heating unit is equipped with a frost protection function, useful for installations where the temperature of the environment could be below 0°C. Gas and electricity must be supplied for this system to work, apart from a correctly pressurized water circulation system and the system must not be in shutdown due to any type of error.
4.3 System cleaning and water treatment
It is ABSOLUTELY NECESSARY to treat the water system for the heating unit to work properly and to guarantee its service life together with all its components. This not only applies to jobs carried out on existing installations but also on new installations. Sludge, lime-scale and pollutants present in the water can cause permanent damage to the heating unit, also within a short time and regardless of the quality standards of the materials used.
Contact the Technical Assistance Centre for any further information on type and use of additives. Chemical-physical characteristics of the water must conform to the European CSN EN 14868 standard and to the table given here below:
Initial filling water
Regular
service
water (*)
ph 6-8 7,5-9,5 Hardness < 10° < 10° °fH Electrical
conductivity
< 150
μs/cm
Chlorides < 20 mg/l Sulphides < 20 mg/l Nitrides < 20 mg/l Iron < 0,5 mg/l
(*)
Value of water in circulation system after functioning for
8 weeks.
b
Where softened water is used it is compulsory to re-check conformity to tolerances for water in regular service after 8 weeks from topping up and in particular the electrical conductivity.
b
No controls are required when using de-mineralized water.
4.4 General instructions
b
An automatic filling system may not be used for topping up, which must be done manually and recorded in the unit handbook.
b
If there are more than one boiler, they must all be put into service either contemporarily or with a very low rotation time during the initial period of service, so as to evenly distribute the limited quantity of initial lime-scale.
b
A flushing cycle must be programmed after the plant has been installed to flush out any installation debris.
b
Water used for filling or for eventually topping up the system must always be filtered (synthetic or metal mesh filters with filtering capacity of no less than 50 micron) to avoid deposits possibly triggering off under-deposit corrosion.
b
The heating system must be flushed out and cleaned with good workmanship before filling up the existing systems. The boiler may not be filled until after the heating system has been flushed out.
4.5 New heating systems
b
The system must be filled up slowly the first time; once it is filled and the air expelled it should never need to be topped up again.
b
The system must be turned to maximum service temperature during the initial ignition to facilitate deaeration (a too low temperature prevents the gas from coming out).
4.6 Upgrading existing systems
Where the boiler has to be replaced it is not recommended to fill up again if the quality of the water in the existing systems conforms to specifications. If the quality of water fails to conform to specifications, we recommend either re-treating it or separating the systems (the water quality requirements must be respected in the boiler system).
4.7 Corrosion
Under-deposit corrosion
Under-deposit corrosion is an electrochemical process, due to the presence of sand, rust, etc., inside the mass of water. These solid substances generally deposit on the bottom of the boiler (sludge), on tube and pipe heads or in the gaps between pipes and tubes. Micro-corrosion phenomena may be triggered off owing to the difference in electrochemical potential coming to be created between the material in contact with the impurity and the surrounding one.
Corrosion from stray currents
Corrosion from stray currents can occur due to the differing electrical potentials between water in the boiler and the metallic mass of the boiler or piping. This process leaves unmistakeable traces i.e. small regular conical holes.
11
b
It is advisable to connect up the various metal parts to a good earthing system.
b
The systems must always be separated if oxygen is either continuously or occasionally introduced into the installations (e.g. floor heating without pipes in synthetic material resistant to diffusion, open vessel systems, frequent topping up).
From what we have seen it is therefore important to avoid two factors possibly leading to the above mentioned processes i.e. contact between air and water in the installation and regular topping up with fresh water. To eliminate contact between air and water (and to prevent the latter from becoming oxidized), it is necessary:
- for the expansion system to be a closed vessel type, correctly scaled and with the correct pre-loading pressure (to be regularly checked);
- for the installation to always be at a higher pressure than that of the atmosphere at any point (comprising the pump suction side) and under all running conditions (all the water sealing and couplings in the installation are designed to resist pressure towards outside, but not for depression);
- that the installation will not be made with materials permeable to gas (e.g. plastic pipes for floor systems without anti-oxygen barrier).
a
Please contact the B Technical Assistance Centre for flushing out the water circuit inside the exchanger. Do not use incompatible liquid detergents, including acids (e.g. hydrochloric acid and similar acids) at any whatsoever concentration.
b
Lastly we would remind you that the warranty does not cover breakdowns incurred by the boiler due to deposits and corrosion.
4.8 Positioning and preparation for installation
When positioning the appliance in the heating system, account for the fact that water, gas and condensate drainage connections must be made on the right-hand side of the cupboard; adequate room must therefore be left at the sides of the appliance for the space taken up by parts of the external systems and for mounting the latter, as shown in Figure 8.
Figure 8
4.9 Condensate outlet
The condensate water produced by
Power Plus Box 1001
a normal running conditions is evacuated into a special manifold. Drainage must be done at atmospheric pressure, i.e. by dripping into a connected drain-trap, as follows:
- install a drip at the condensate drainage manifold;
- connect the drip to the sewerage mains by a drain­trap;
- be ready to use a neutralizer where required (see project cig E.01.08.929.0; ATV A 115).
There is generally no need to take any special precautions for draining condensate. We advise using plastic (PP) piping for building the condensate drainage.
a
DO NOT for any reason use pipes in copper or in any other material not specifically used for this particular scope, as the condensing action could cause rapid degradation.
Condensate collector
(*) Fill the siphons with water.
(*)
(*)
(at atmospheric pressure)
i > 3%
Civil drain
i
i ≥ 3°
minimum distance 300 mm
minimum
distance
10 mm
Fig. 9
Furthermore, should the vertical part of the flue exhaust duct have to be prolonged by more than 4 metres the condensate drain-trap will have to be placed at the foot of the piping. The working height of the drain-trap must be at least 30 cm. The drain-trap outlet must then be connected up to the sewerage mains.
b
The condensate drain must be connected to the sewerage mains in such way as to prevent it from being frozen under any circumstances.
b
Always install a condensate drain in the exhaust flue duct at no more than 1 m from the boiler
12
4.10 Water circuit
WORKING PRESSURE The maximum working pressure of the boiler is 6 bar (600 kPa) whilst the minimum is 0.5 bar (50 kPa).
b
It is compulsory to install devices along the topping up/supply line as well as the water circulation system to protect the installation from pressures exceeding 550 kPa, in conformity to prescriptions given in the EN 60335-2-102.
b
Do not expose the exchanger to cyclic changes in pressure as fatigue stress does a lot of harm to the system components. Should the water system suddenly start generating changes in pressure it is compulsory to use the protection devices to make the boiler work at a regular pressure.
b
Installation pressure control must be done under cold conditions.
FILLING UP THE BOILER The boiler must be filled up by connecting the water from to the mains to any part of the installation.
b
It is compulsory to use a standard filling device (EN61770 type) for coupling up to the mains specifically preventing the back-flow of liquid from installation to water mains.
EMPTYING THE BOILER The boiler is emptied through special emptying cocks installed on the exchanger and water separator.
4.11 Exhaust ue
The exhaust flue duct and fitting to the flue duct must be made in conformity to standards, legislation in force and to local rules and regulations. It is compulsory for ducts to be stiff, resistant to temperature, condensate, mechanical stress and be sealed. The flue duct must be as straight as possible, sealed and insulated. It must not have any occlusions or narrowing. Maximum length of the exhaust flue duct (with a diameter of Ø110 mm) is 55 metres. Keep in mind that a 90° elbow equals 4 metres of straight pipe and a 45° elbow one metre of straight pipe.
b
The boiler’s total potential exceeds 35 kW and can therefore only be installed in premises with air vents opening towards the outside and made in conformity to provisions of the law in force (Ministerial Decree D.M. 12.04.1996).
a
DO NOT for any reason use piping not specifically designed for this specific scope as the condensing action could cause rapid degradation.
a
In the event of installation with air intake from the premises (both in the heating unit and externally) avoid obstructing the passage of air under the metal cupboard.
5 INSTALLATION DIAGRAMS
An installation diagram must generally be adapted to the manufacturing characteristics of the relevant heating unit, with the purpose of exploiting the boiler potentials to the full and maintain the entire installation efficient for as long as possible. The electronic modulating circulator placed inside the appliance is only for the primary system and works to keep the ΔT constant with changes in power modulation. The ΔT value is set at 20° in the factory and may be altered by specialized personnel only. The installation circulators must be scaled to the project flow capacity and load-loss of said installation only. If the distribution kits, provided as an accessory, are installed it will be necessary to check that the technical features of the low. system circulators and mixer valve are compatible with the installation. The Figure 10 shows the water diagram of the unit and a typical system connectable to the latter, with the three high, low temperature and hot water systems. Everything in the large box with dotted lines is in the interior of the unit. The circulation part in the shaded area is available as an accessory distribution kit; otherwise it will have to be installed on the outside of the system. The Figure 11 shows the accessory distribution kits installable inside the cupboard.
b
Distribution kits are equipped with shut-off valves. These must be installed in appropriate places on the installation.
Loading...
+ 28 hidden pages