Beretta Power Plus User Manual

Page 1
REFERENCE GUIDE FOR THE BOILERS
Relè interposti sui circuiti di potenza (c
1
Se allentato può allagare la camera di
combustione
Tenuta dello
scambiatore
POWER PLUS
Page 2
Page 3
CONTENTS
CONTENTS
1 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 1
1.1 GENERAL WARNINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 1
1.2 GENERAL SAFETY MEASURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 1
1.3 GENERAL WARRANTY CONDITIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 2
1.4 BOILER IDENTIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 2
1.5 MAIN COMPONENTS IDENTIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 3
1.5.1 Burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 3
1.5.2 Main heat exchanger. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 3
1.5.3 Combustion chamber . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 3
1.5.4 Flame ignition and detection electrode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 3
1.5.5 Flow and return probes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 4
1.5.6 Safety thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 5
1.5.7 Flue probe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 5
1.5.8 Fan. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag.5
1.5.9 Gas valve. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 5
1.5.10 Venturi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 5
1.5.11 Condense collection siphon . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 5
1.5.12 Control panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 6
1.5.13 Water differential pressure switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 6
1.5.14 Safety valve. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 6
1.6 CONTROL PANELS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 7
1.7 DISPLAY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 8
1.7.1 Display mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 9
1.7.2 Readout mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 9
1.7.3 Monitor mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 10
2 FIRST START-UP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 12
2.1 PRELIMINARY OPERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 12
2.2 SYSTEM FILLING AND DRAIN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 12
2.2.1 Filling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 12
2.2.2 Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 13
2.3 FIRST IGNITION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 13
2.4 CHECKS DURING AND AFTER THE FIRST IGNITION . . . . . . . . . . . . . . . . . . . . . pag. 15
3 BOILER FUNCTIONING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 16
3.1 FACTORY SETTINGS AND FUNCTIONAL PARAMETERS ADJUSTMENT . . . . pag. 16
3.2 CENTRAL HEATING PARAMETERS SETTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 16
3.2.1 Setpoint_T_CH_High . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 16
3.2.2 Setpoint_T_CH_Low . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 17
3.2.3 CH_Priority. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 17
3.3 DOMESTIC HOT WATER PARAMETERS SETTING . . . . . . . . . . . . . . . . . . . . . . . . pag. 17
3.3.1 Setpoint_DHW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 17
3.3.2 DHW_Type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 17
3.3.3 DHW_Priority. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 17
I
Page 4
CONTENTS
3.4 MAIN FUNCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 17
3.4.1 Domestic Hot Water Priority function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 17
3.4.2 Anti-frost function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 17
3.4.3 Dispersion function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 18
3.4.4 Cascade management function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 18
3.4.5 Switch ON/OFF management function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 18
3.4.6 Emergency function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 18
3.5 PARAMETERS SETTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 19
3.5.1 Password setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 19
3.5.2 Parameters list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 19
3.6 SETTINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 23
3.6.1 Maximum power CO2 setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 23
3.6.2 Minimum power CO2 setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 24
3.6.3 Adjustments verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 24
3.7 GAS CONVERSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 24
3.8 BURNER PRESSURES SETTINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 25
3.8.1 Gas supply pressure check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 25
3.9 COMBUSTION CHECK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 26
3.10 FAN SPEEDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 26
3.11 THERMOREGULATION SETTINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 26
3.11.1 Central heating high temperature circuit functioning. . . . . . . . . . . . . . . . . . . . pag. 26
3.11.2 Attenuation_High . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 26
3.11.3 Central heating low temperature circuit functioning . . . . . . . . . . . . . . . . . . . . pag. 27
3.11.4 Attenuation_Low . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 27
3.11.5 T_out_correct . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 28
3.11.6 T4_frost_protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 28
3.11.7 Power_control_mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 29
3.11.8 Slave PCBs safety functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 30
3.11.9 Mix valve management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 30
3.11.10 Gas type (fan speeds) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 30
3.11.11 Burner ignition procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 31
3.11.12 Factory settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 31
3.12 ADDRESSES SETTINGS FOR CASCADE CONNECTIONS. . . . . . . . . . . . . . . . . . . . pag. 31
3.12.1 Master PCB data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 31
3.12.2 Slave PCBs data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 32
3.12.3 Slave PCB user interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 32
3.12.4 Slave PCBs access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 32
3.12.5 Addresses settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 32
4 BOILER SHUTDOWN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 34
4.1 TEMPORARY SHUTDOWN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 34
4.2 EXTENDED PERIODS SHUTDOWN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 34
5 MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 35
5.1 ORDINARY MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 35
5.2 EXTRAORDINARY MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 35
5.3 PERIODICAL PROGRAMMED MAINTENANCE TABLE . . . . . . . . . . . . . . . . . . . . .pag. 36
5.4 NECESSARY TOOLS FOR MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 36
5.5 SAFETY RULES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 36
II
Page 5
CONTENTS
5.6 COMPONENTS ACCESSIBILITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 36
5.6.1 Casing disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 37
5.6.2 Control panel disassembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 38
5.6.3 PCBs disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 39
5.6.4 Ignition electrode disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 40
5.6.5 Venturi disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 41
5.6.6 Fan disassembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 42
5.6.7 Burner disassembly and combustion chamber cleaninge . . . . . . . . . . . . . . . . . . pag. 43
5.6.8 Siphon disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 44
5.6.9 NTC probes disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 45
5.6.10 Safety thermostat disassembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 46
5.6.11 Flue probe disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 47
5.6.12 Gas valve disassembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 48
5.6.13 Water differential pressure switch disassembly . . . . . . . . . . . . . . . . . . . . . . . . . pag. 49
6 FAULT FINDING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 50
6.1 ERROR MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 50
6.2 PERMANENT LOCKOUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 50
6.3 LOCKOUTS CODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 50
6.3.1 Master PCB lockouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 50
6.3.2 Slave PCB lockouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 51
6.4 EVENTUAL ANOMALIES AND REMEDIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 52
7 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 54
7.1 HANDLING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 54
7.2 BOILER INSTALLATION ROOM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 54
7.3 INSTALLATION ON OLD SYSTEMS OR SYSTEMS TO BE UPGRADED. . . . . . . pag. 54
7.4 FITTING THE BOILER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 54
7.5 HYDRAULIC CONNECTIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 55
7.5.1 Hydraulic kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 55
7.6 FUEL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 61
7.7 ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 61
7.7.1 Master control panel internal connection block . . . . . . . . . . . . . . . . . . . . . . . pag. 62
7.8 SYSTEMS FILLING AND DRAINING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 62
7.8.1 Filling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 62
7.8.2 Draining . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 63
7.9 FLUE DRAIN AND COMBURENT AIR INTAKE . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 63
7.9.1 Ducts maximum length. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 63
7.9.2 Condense drain arrangement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 64
7.9.3 Kit flue collector with clapet valves (FIG. 7.11). . . . . . . . . . . . . . . . . . . . . . . pag. 65
7.10 OUTDOOR PROBE CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 65
7.10.1 Outdoor probe wall fitting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 65
III
Page 6
CONTENTS
APPENDIX A - Main components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 68
APPENDIX B - Dimensions and weight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 69
APPENDIX C - Technical data table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 70
APPENDIX D - Hydraulic circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 71
D.1 Water side head losses. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 71
APPENDIX E - NTC probes positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 72
APPENDIX F - Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 73
F.1 Configuration with distribution pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 73
F.2 Configuration with injection pumps (accessory cod. 1102419) . . . . . . . . . . . . . . . . . . . . pag. 73
F.3 Configuration with ring pump and valves on the units . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 74
F.4 Configuration with mixed system and solar system with double-coil storage tank . . . . .pag. 74
F.5 Pumps performance graphics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 75
APPENDIX G - Electrical schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 76
G.1 Power Plus 50 M – 100 M (master board code R105920) . . . . . . . . . . . . . . . . . . . . . . . . pag. 76
G.2 Power Plus 50 M - 100 M (master board code R107584). . . . . . . . . . . . . . . . . . . . . . . . .pag. 78
G.3 Power Plus 100 S. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 80
APPENDIX H - Electrical connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 82
H.1 Outdoor probe connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag.83
H.2 External 0-10 V thermoregulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 83
H.3 Connection of an external alarm device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 83
H.4 Remote control kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 84
APPENDIX I - Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 93
IV
Page 7
1 GENERAL
GENERAL
1.1 GENERAL WARNINGS
The boilers produced in our factory are built with
care down to the last component to protect both the user and installer from eventual accidents. We there­fore recommend qualified personnel that after work­ing on the product they should pay particular attention to the wiring, especially the bare wires, that must not be exposed outside the terminal board for any reason to prevent any contact with the live parts of the wiring.
This instructions manual is integral parts of the
product. Make sure they remain with the boiler, even if it is transferred to another owner or user or moved to another heating system. In case of loss or damage, please contact your local Technical Assistance Ser­vice for a new copy.
This boiler may only be installed and serviced by
qualified personnel who satisfy the requirements of local rules. Work must be done in compliance with regulations in force and subsequent updates.
The boiler must be serviced at least once a year. This
should be booked in advance with the Technical Assistance Service.
The installer shall instruct the user in the operation
of the boiler and the safety devices.
This boiler may only be used for what it was
expressly built to do. The manufacturer declines all contractual and non-contractual liability for injury to persons or animals or damage to property deriving from errors made during installation, adjustment and servicing and from improper use.
This appliance is used to produce hot water and must
therefore be connected to a heating and/or a domestic hot water system, according to its performance and power.
After removing the packaging, make sure the con-
tents are undamaged and complete. If this is not the case, contact your dealer.
The safety valve outlet must be connected to a suit-
able collection and venting system. The manufac­turer declines all liability for any damage caused by the safety valve.
The safety and automatic adjustment devices on the
appliance must never be modified during its lifetime, except by the manufacturer or dealer.
Should the appliance develop any faults and/or work
badly, switch it off and do not attempt to repair it yourself.
Immediately after installation, inform the user that:
- in the event of leaks, he/she must shut off the water supply and promptly inform the Technical Assis­tance Service;
- he/she must make regular checks to verify that the operating pressure of the system ranges between 1 and 1,5 bar, and must never be greater than 3 bar. If necessary he/she must call in professionally qual­ified personnel from the Technical Assistance Ser­vice;
- if the boiler is not planned to be used for a long period, he/she should call in the Technical Assis­tance Service to perform the following operations:
- turn off the boiler and system main switches;
- close the gas and water taps on the heating cir-
cuit;
- drain the heating circuit to prevent freezing.
Connect the outlet collector to a suitable outlet sys-
tem.
1.2 GENERAL SAFETY MEASURES
The use of products that operate on fuel, electricity and water requires a number of fundamental safety rules to be observed, including.
( The boiler must not be used by children or invalid per-
sons without supervision.
( Electrical devices or appliances, such as switches,
household appliances, etc. must not be used if there is the smell of gas or unburned fuel. In this case:
- ventilate the room by opening doors and windows;
- close the fuel stoptap;
- promptly contact Technical Assistance Service, your gas supplier or other professionally qualified per­sonDo not touch the boiler when barefoot or with wet parts of the body.
- No service or cleaning operations may be performed without first having disconnected the boiler from the mains power supply, moving the main system switch to “OFF”.
- The safety or control devices must not be adjusted without the authorisation and written instructions from the manufacturer of the boiler.
- The condensate drain must not be plugged.
- Do not pull, remove or twist the electrical cables com­ing out of the boiler, even if the appliance is discon­nected from the mains power supply.
- The ventilation openings in the room where the appli­ance is installed must not be plugged or reduced in size and must comply with any current standards and law applicable.
- Do not expose the boiler to the elements. It is not designed to operate outdoors and does not have suffi­cient frost protection systems.
- Do not switch the boiler off if the outside temperature may fall below ZERO (risk of freezing).
1
Page 8
GENERAL
- Do not leave containers and flammable substances in the room where the boiler is installed.
- The packaging material must not be dispersed in the environment or left within the reach of children as it is a potential source of hazard. It must be disposed of according to the legislation in force.
1.3 GENERAL WARRANTY CONDITIONS
The warranty covers all the parts of the products. It is intended as a free of charge repair and eventual free of charge changeover of every part that should, in the manufacturer judgement, any manufacturing defect.
The first ignition of the product must be carried out by autho­rised technical personnel, which will then redact an ignition report, that must be signed also by the customer.
The warranty becomes invalid if:
- the cause of the malfunctioning is external to the product;
- not original components, spare parts, tear and wear materi­als have been used;
- the repairing or maintenance interventions have been carried out by not authorised personnel;
- the environmental or installation conditions differ from what reported in S
The warranty does not cover parts subject to normal tear and wear, such as: filters, gaskets, handles, etc.
ECT.7, PAGE 54.
1.4 BOILER IDENTIFICATION
The boilers can be easily identified by:
- Packaging label (F
This shows the code, the serial number and the barcode.
IG. 1.1)
Fig. 1.1
2
1
2
Page 9
GENERAL
- Rating plate (FIG. 1.2)
This shows the technical and performance specifications.
100 M 100 M
100 M DEP
models
100 S
100 S DEP
models
- Gas label (FIG. 1.3)
This is applied on the side of the frame, and describes the type of fuel used by the boiler, and the country of destina­tion.
Paese di destinazione:
ITALIA
Tipo di apparecchio Caldaia categoria::
Regolazione effettuata dal costruttore:
Leggere attentamente il libretto istruzioni prima di installare e mettere in servizio l'apparecchio.
(Later
B23, C63
II2H3+
Pressioni di alimentazione gas:
G20
20 mbar
G30+G31
28-30/37 mbar
G20 - 20 mbar - 2H METANO
ale DX)
ATTENZIONE
068120_1_E0
Fig. 1.3
If the plates or other means for clearly identifying the
product have been tampered with, removed or are missing, the installation and servicing operations will be much more difficult.
Fig. 1.2
Boiler regulated for:
G31 37 mbar
Destination Country:
IT
TXXXXXXXX
1.5 MAIN COMPONENTS IDENTIFICATION
To identify the position of the described components, please refer to the exploded diagrams reported in APPENDIX A -
PAGE 68.
For the disassembly operations, please refer to S
PAGE 35.
1.5.1 Burner
The burner (F
IG. 1.4) is completely premix, micro-flame, with
very low polluting emissions. It is inserted inside the heat ex­changer to which it is mechanically assembled underneath the fan group, by means of 4 screws.
1.5.2 Main heat exchanger
The main heat exchanger (F
IG. 1.5) is constituted by a wrin-
kled bi-metallic coil, whose external surface is made of stain­less steel AISI 316L (flue side), while the inner surface is made in copper (water side). It doesn’t need any specific main­tenance operation.
1.5.3 Combustion chamber
The combustion chamber (F
IG. 1.6) has a cylindrical shape
with aluminium made headers. According to the boiler power 1 (50 kW models) or 2 (100 kW models) units are used.
ECT.5,
1.5.4 Flame ignition and detection electrode
The electrode (F tion chamber (S
IG. 1.7) is on the left-top part of the combus-
ECT. 1.5.3, PAGE 3) and its function is to pro-
duce an high voltage spark in the proximity of the burner (S
ECT. 1.5.1, PAGE 3) and to detect when the flame is present.
3
Page 10
GENERAL
Fig. 1.4
Burner
Fig. 1.6
Electrode
Fig. 1.5
1.5.5 Flow and return probes
The flow and return probes (F
IG. 1.8) are of NTC type and are
placed the first in the flow pipe closed to the automatic venting device, while the second one is in the lower part of the return pipe, closed to the draining tap. The probes allow the PCB to read the temperature on the return and flow of the combustion unit.
Fig. 1.7
Flow NTC
probe
Return NTC
probe
Fig. 1.8
4
Page 11
GENERAL
1.5.6 Safety thermostat
The safety thermostat (F
IG. 1.9) is manually resettable, is
placed in the upper part of the flow pipe and intervenes if the flow temperature is above 90°C, shutting down the burner.
Safety
Thermostat
Fig. 1.9
1.5.7 Flue probe
The flue probe (F
IG. 1.10) is placed in the lower part of the
heat exchanger, intervening whenever the drained flue temper­ature rises above 80°C.
1.5.9 Gas valve
The gas valve (F
IG. 1.12) is placed in the upper part of the
combustion chamber, is connected to the venturi and is the component that manages and checks the gas flow to the burn­er. The valve is made by an aluminium die-cast part with two safety electrical valves, which are mechanically in series, but electrically in parallel. This configuration guarantees that, in every anomalous situation, the gas supply to the burner is in­terrupted in the shortest time. Removing the venturi from the gas valve by its screws, it possible to gain accessibility to the gas flow hole and its gasket (in case of gas supply being nat- ural gas no injector is present).
Fig. 1.12
1.5.10 Venturi
The venturi (F
IG. 1.13) is a body made of die-cast aluminium
through which the air-gas mixture is convoyed towards the fan and hence inside the combustion chamber.
Flue probe
Fig. 1.10
1.5.8 Fan
The fan (F
IG. 1.11) is placed in the upper part of the combus-
tion chamber and is fastened by means of screws-nuts to the venturi (air-gas mixer) and to the body of the combustion chamber, in which the burner is. It is used to push the air-gas mixture towards the burner and to push the combustion prod­ucts towards the flue drain collector.
Fig. 1.11
Venturi
Fig. 1.13
1.5.11 Condense collection siphon
The siphon (F
IG. 1.14) is made of composite material, is
placed in the right-bottom part of the combustion chamber, has the function to collect and drain the condense generated by the thermal exchange between the combustion products and the primary water circuit, maintaining the combustion circuit sep­arated from the condense drain circuit. Inside the siphon there is a float that keeps separated the two described circuits even in the case no water is present in the siphon body.
Fig. 1.14
5
Page 12
GENERAL
1.5.12 Control panel
The control panel (F
IG. 1.15) of the models Power Plus 50 M
– 100 M – 100 M DEP contains a master PCB and one or two slave PCBs, according to the boiler power. The models 100 S and 100 S DEP contain only the two slave PCBs. In the case of cascading connection among different thermal groups, the master PCB of the thermal unit Power plus 50 M – 100 M – 100 M DEP is able to manage via a BUS connection all the PCBs of the units Power Plus 100 S and 100 S DEP. The man­agement is based on a microprocessor and the self-diagnosis is displayed by a combination of LED and display alphanumeric digits. It is possible to cascade up to 60 thermal units managed by the Master version thermal group with sequence rotation and cascade strategy selection. Thanks to the versatility of the PCB it is possible to make a very quick connection to every kind of system for the production of hot water for the central heating or domestic water purposes with storage tank manag­ing, in the same time, up to three circuits working at a different temperature.
Master PCB
Slave PCB
Slave PCB
Fig. 1.16
Fig. 1.15
1.5.13 Water differential pressure switch
The water differential pressure switch (F
IG. 1.16) is placed in
the bottom part of the thermal unit and it has the function to check and grant a minimum flow rate of at least 500 l/h for each thermal unit.
The boiler is brought in a safety lock-out condition whenever the water is not present, shutting down and keeping off the burner.
The intervention thresholds are:
- ON with system flow rate > 700/720 l/h (p 50/55 mbar)
- OFF with system flow rate < 540/560 l/h (p 35/40 mbar).
1.5.14 Safety valve
The safety valve (F
IG. 1.17) is placed on the flow pipe and is
connected to a drain pipe.
It has the task of protecting the hydraulic circuit from eventual over-pressures consequent, for instance, to the primary fluid volume increase caused by its heating. The valve is adjusted to intervene at a value of 5.5 bar.
Fig. 1.17
6
Page 13
1.6 CONTROL PANELS
Power Plus 50 M
1235768109
4
GENERAL
15 1612 13 14
Power Plus 100 M
1
4
23 5 7681091 1
1 - FIRST heating unit switch 2 - Button for selecting the operating mode 3 - Reset button (Master) 4 - Electrical supply presence signal 5 - Boiler lockout signal 6 - Button for selecting the parameters 7 - Display 8 - Save button 9 - Button to increase values 10 - Button to decrease values 11 - SECOND heating unit switch 12 - Slave power supply signal:
slow flashing = stand-by rapid flashing = ignition cycle
solid light = flame detected 13 - Slave lockout signal 14 - Reset button (Slave) 15 - Instruments panel
12
131415 1612 13 14
16 - Main boiler switch
Power Plus 100 S
1
1211131415 1612 13 14
7
Page 14
GENERAL
1.7 DISPLAY
The buttons on the Beretta POWER PLUS control panel have different functions in different modes. For example, the combina­tion of two buttons corresponds to one specific function. Alternatively, a function can be activated by pressing the button briefly or by holding it for around 5 seconds.
Red LED
This switches on only in case of anomalies that
imply the permanent lockout of a thermal unit (re-
settable only by pressing the Master or Slave Re-
set button).
7-digits display
RESET
This resets the electronic board
after a permanent lockout.
+ and -
These increase or decrease a cer-
tain value.
Set/esc
This is used to enter parameter
setting mode and monitor mode
on the individual units.
8
OK
This is used to save the new values.
This is used to display the oper-
ating status of the various cir-
cuits managed by the Master
board.
Page 15
GENERAL
1.7.1 Display mode
The red LED comes on in the event of faults that cause the permanent lockout of a heating unit (normal operation is reset only by pressing the Master or Slave reset button).
The 3 digits with seven segments display the status of the system:
Status of the system Display
No central heating or DHW demand. (The two digits on the right display the flow temperature T1. E.g.: T1 = 30°C)
Demand from circuit no.1 or from circuits 1 and 2 together. The two digits on the right display the flow temperature T1. E.g.: T1 = 80°C.
Demand from the DHW circuit or simultaneous operation. The two digits on the right display the flow temperature T1 E.g.: T1 = 80°C. The decimal point after the 1st digit on the left flashes.
Demand from the 2nd circuit The two digits on the right display the flow temperature T1. E.g. T1 = 80°C.
Anti-frost function.
No request of CH or DHW. (the two digits in the right display the flow temperature T1. E.g. T1 = 30°C)
1.7.2 Readout mode
(T
EMPERATURE VALUES AND OPERATING STATUS OF THE VARIOUS CIRCUITS)
Press the button to scroll forwards and display the values set for the individual circuits. The values listed below will be displayed in sequence when pressing the button.
Value displayed Display
Flow temperature T1 in the high temperature circuit.
1
E.g.: T1 = 80°C.
DHW temperature T3.
2
E.g.: storage heater temperature = 50°C.
Outdoor sensor temperature T4.
3
E.g.: T4 = 7°C.
4 Flow temperature in 2nd circuit or low temperature circuit T6.
Room thermostat in the 1st circuit, closed or open.
5
OFF = contact open. ON = contact closed.
Room thermostat in the 2nd circuit, closed or open.
6
OFF = contact open. ON = contact closed.
0-10 V analogue input.
7
E.g.: 5.5 V, 10 V.
Operating status of the mixing valve.
8
E.g.: closing, opening, standby.
9
Page 16
GENERAL
Value displayed Display
Operating status of the main pump.
9
E.g.: pump not working, pump working.
Operating status of the DHW pump.
10
E.g.: pump not working, pump working.
Operating status of the secondary pump.
11
E.g.: pump not working, pump working.
To exit the display of the values, press the “OK” button. If no operation is performed for 5 minutes, the PCB automatically returns to Display mode.
1.7.3 Monitor mode
From the Readout mode, press “Set/Esc” for 5 seconds to access “Monitor” mode. This mode is used to check the operating values of each individual unit in the system (addresses from 1 to 60).
Operation Display
1 The boiler is operating with the high temperature circuit at 80°C.
Press “Set/Esc” for 5 seconds.
2
The display indicates that the values and the operating status of unit 1 can be read.
3 Press “+” or “-” to scroll and read the values for the desired unit.
Pressing the display shows the 1st value for the selected unit.
4
Pressing the button again displays the following values. E.g.: outlet temperature 70°C.
To exit Monitor mode, press “MODE”.
5
If within 5 minutes no button is pressed or no operation is performed, Display mode resumes.
Press to display the following values for the individual unit:
Value Display
1 Flow temperature E.g.: 70°C.
2 Return temperature E.g.: 50°C.
3 Flue gas temperature E.g.: 60°C.
Ionisation current (index from 0 to 99).
4
E.g.: ionisation current index 44.
Fan PWM signal (%).
5
If PWM = 100%, this corresponds to 99 on the display. E.g.: 66 %.
10
Flow switch open/closed (not active).
6
E.g.: contact open.
Pump or motorised valve on the individual unit on/off.
7
E.g.: Pump ON. E.g.: Pump OFF.
Page 17
GENERAL
Value Display
Maximum ionisation current (range from 0 to 99) at first attempt.
8
E.g.: maximum ionisation current 80.
Hours of unit functioning (from 0 to 9999 hours).
9
E.g.: 8050 hours: the display reads out paired figures showing the hours in a sequence of thousands, hundreds, tens and units.
11
Page 18
FIRST START-UP
2 FIRST START-UP
2.1 PRELIMINARY OPERATIONS
Before starting the system and running the functional tests on the Beretta POWER PLUS boiler, check that:
- The fuel valve and valves in the central heating system are open.
- The type of gas and the supply pressure are correct for the boiler.
Fig. 2.1
- The system is filled, i.e. the pressure in the water circuit, when cold, is around 1.5 bar and the circuit has been vented.
2.2.1 Filling
- Open the valves (1 - F fittings.
ILLUSTRATIVE SCHEME
Fig. 2.4
- Open the caps on the automatic vent valve/valves (2 - F
2.5) by two or three turns.
IG. 2.4) installed on the boiler water
1
MI
RI
GAS
2
IG.
Fig. 2.2
- The system expansion vessel is suitably pre-charged.
- The electrical connections have been performed correctly.
The pumps should be connected by installing suitable
contactors with manual emergency operation.
- Check that the cap on the vent valve/valves is unscrewed.
- The pumps turn freely: loosen the inspection screw and check with a flathead screwdriver that the motor shaft is ro­tating without impediments.
Fig. 2.3
Before loosening or removing the seal cap on the
pump, protect the electrical devices underneath against water spillage.
- The flues have been properly made and installed.
2.2 SYSTEM FILLING AND DRAIN
The Beretta POWER PLUS Boiler is not fitted with a filling valve, which must be installed on the system return.
Fig. 2.5
- If present, open the two-ways valve of each thermal engine, setting the lever (3 - F This lever is placed underneath the two-ways valve.
Fig. 2.6
- Open the filling valve on the system until the pressure shown on the pressure gauge is 1,5 bar.
- Close the filling valve again.
- Bring back the two-ways valve lever (3 - F thermal unit to its position “AUTOMATIC”.
IG. 2.6) in its position “MANUAL”.
3
AU
TO
MAN
IG. 2.6) of each
12
Page 19
The air is vented from the POWER PLUS boiler
automatically through the automatic vent valve/ valves installed on the top of the heating units. Check that the cap on the valve is open.
2.2.2 Drain
Before starting to empty the system, disconnect the power sup­ply by moving the main system switch to “OFF” (F
IG. 2.7).
FIRST START-UP
1
5
MI
RI
GAS
Fig. 2.7
Emptying the BOILER
- Close the valves (1 - F fittings.
ILLUSTRATIVE SCHEME
ON
OFF
IG. 2.8) installed on the boiler water
1
MI
RI
GAS
ILLUSTRATIVE SCHEME
Fig. 2.10
setting the lever (3 - F
IG. 2.11) in its position “MANUAL”.
This lever is placed underneath the two-ways valve.
3
AU
TO
MAN
Fig. 2.11
- Once the system has been drained bring back the two-ways valve lever (3 - F
IG. 2.11) of each thermal unit to its position
“AUTOMATIC”.
Fig. 2.8
- Connect a plastic hose to the drain tap (4 - F
IG. 2.9), on each
heating unit, and open the tap.
4
Fig. 2.9
Before opening the drain tap (4 - FIG. 2.9) protect the
electrical devices underneath against water spillage.
Emptying the SYSTEM
- Check that the valves (1 - F
IG. 2.10), installed on the water
circuit, are open.
- Connect a plastic hose to the drain tap (5 - F
IG. 2.10), fitted
on the system return line, and open the tap.
- If present, open the two-ways valve of each thermal engine,
2.3 FIRST IGNITION
- Move the main system switch to “ON” (FIG. 2.12).
ON
OFF
Fig. 2.12
- Move the boiler main switch (1 - F (2 - F
IG. 2.13) on each heating unit to “ON”. The green
SLAVE power supply signal (3 and 4 - F boiler performs a self-diagnosis cycle, after which it will en­ter DISPLAY mode. The display (5 - F status of the system and the temperature measured by the probe in the “high temperature” circuit. If there are more than two boilers installed, it is necessary to configure the ad­dresses from the third thermal unit on. To do this, see
S
ECT. 3.12, PAGE 31 - “ADDRESSES SETTINGS FOR CAS-
CADE CONNECTIONS”.
- Set the room thermostats in the high and low temperature zone to the desired temperature (20°C) or if the systems are fitted with a timer-thermostat or timer, check that this is on and set (20°C).
- Press the : button: the maximum temperature of the boiler
IG. 2.13) and the switches
IG. 2.13) flash. The
IG. 2.13) shows the
13
Page 20
FIRST START-UP
25 2
3
14
Fig. 2.13
will be displayed, that is, the maximum temperature in the high temperature circuit, preceded by the symbol “1” (F
IG.
2.14).
Fig. 2.14
- Press “Set/Esc”: the corresponding set point will be dis­played and the two digits on the right will flash. To change the value, press “+” or “-”. To confirm press “OK” (F
IG.
2.15).
-Press “Set/Esc”: the correspondent set point will be dis- played and the two digits on the right will flash. To change the value, press “+” or “-”. To confirm press “OK” (F
IG.
2.17).
Fig. 2.17
For low temperature systems, select a temperature
between 20°C and 45°C. When setting the system as “Low temperature” type, the maximum flow temper­ature will be automatically limited at 50°C (Parame­ter 23=T_CH_Low_limit).
Changing the flow temperature implies a modifica-
tion of the climatic control curve (see S
PAGE 26). These settings must only be performed by
ECT.3.11,
the Technical Assistance personnel or a suitably qual­ified person.
If the boiler is connected to a storage tank, set parameter 6 (pre-set to 0=no DHW service). To do this, access the “Install­er programming” mode and set parameter 6 to:
- 2 = for storage heater with probe.
- 6 = for storage heater with thermostat.
In addition, set parameter 9 (DHW_Priority) to 2 for absolute priority. If the storage tank is fitted with an NTC probe, the de­sired temperature can be set on the display, from 10°C to 50°C. If the storage tank is fitted with a thermostat, the desired temperature should be set directly on the storage heater, while the parameter 3 must be left at 50°C.
- Press button twice: the DHW temperature will be dis­played, preceded by the symbol “3” (F
IG. 2.18).
Fig. 2.15
- Press the button four times: the maximum temperature in the low temperature circuit will be displayed, preceded by the symbol “6” (F
IG. 2.16).
Fig. 2.16
14
Fig. 2.18
-Press “Set/Esc”: the corresponding set point will be dis- played and the two digits on the right will flash. To change the value, press “+” or “-”. To confirm press “OK” (F
IG.
2.19). The boiler will start in DHW mode, until the demand
is satisfied.
- When the boiler is in Standby, the display on the Master unit is in Readout mode and the three digits show the number “1”, followed by the value of the flow temperature. The
Page 21
Fig. 2.19
green LED (Ref. 11, SECT. 1.6, PAGE 7) flashes.
FIRST START-UP
set correctly:
2 = storage tank with probe
6 = storage tank with thermostat
and check that its operation is correct, by opening a hot wa­ter tap.
- Check the complete shutdown of the thermal unit by moving the main system switch to “OFF”.
- Generate an heat request operating on the Room Thermostat or on the Time Programmer (external).
- Verify, if a storage tank is present, the DHW operation by opening a hot water tap.
- Check the complete shutdown of the thermal unit by moving the main system switch to “OFF”.
ON
OFF
Fig. 2.22
Fig. 2.20
- If ignition or operating faults occur on any heating unit, the display on the Master boiler starts flashing and the red LED (4) comes on.
Fig. 2.21
There are two possible types of errors:
- Type A errors, which can only be deactivated by pressing the RESET button.
- Type E errors, which are deactivated when the causes are no longer present (see S
PAGE 50).
ECT. 6.1, PAGE 50 and SECT.6.3,
After a few minutes of continuous operation controlled by the room thermostat, the adhesives and the processing residues will have evaporated, and the following checks can be com­pleted:
- gas supply pressure check;
- combustion check.
2.4 CHECKS DURING AND AFTER THE
FIRST IGNITION
When ignition is complete, check that the Beretta POWER PLUS boiler correctly:
- Starts and stops, closing the contacts on the zone thermo­stats.
- Displays the DHW temperature (only if the storage tank is fitted) and central heating temperature, pressing the but­ton twice. Check, if the storage heater is fitted, that parameter “6” is
15
Page 22
BOILER FUNCTIONING
T_out_max
Outdoor Temperature (°C)
Flow temperature (°C)
CLIMATIC CURVE
HIGH TEMPERATURE Circuit
T_CH_High
maximum heat need
T_CH_High_foot
T_out_min
25 20 15 10 5 0 -5 -10 -15 -20
0
10
20
30
40
50
60
70
80
90
100
3 BOILER FUNCTIONING
3.1 FACTORY SETTINGS AND FUNCTIONAL PARAMETERS ADJUSTMENT
Each Master PCB for each thermal group Power Plus 50 M ­100 M - 100 M DEP needs to be configured according to the system characteristics. The factory settings allow to manage the kind of system described hereafter. In case of different kind of systems, modify the following parameters during the boiler installation:
- Mixed system with 2 circuit (one high temperature, one low
temperature) with thermoregulation managed by the out­door probe (Par. 14 = 1).
- Configuration with “ring” system pump modulating on the
primary circuit (Par. 34 = 0).
- No DHW functioning (Par. 6 = 0).
- No priority between high and low temperature circuit (Par.
16 = 0)
- Maximum temperature on the high temperature circuit 70°C
(Parameter 1 user) and 40°C (Parameter 3 user) on the low temperature one.
- Functioning with Natural gas with flues running for less
than 15 metres (Par. 31 = 1).
The functions of the central heating high temperature and low temperature circuits and the DHW circuits can be set based on the system requirements, by setting the functional parameters.
The first three parameters are accessible at a user level, while the remaining parameters require the password to be entered (“22”, vedi S ters, press the button, after which the following values will be displayed:.
Flow temperature in the high temperature circuit T1
Temperature in the circuit T3
Flow temperature in the low temperature circuit T6
To change the corresponding set points:
- Press “Set/Esc”, the corresponding value will be displayed
and the two digits on the right will flash.
- Press “+/-” until reaching the desired value. Press “OK” to
save the new value. The value displayed will stop flashing and will be valid after 3 seconds.
EXAMPLE
Changing the low temperature Set-point from 50°c to 40°C.
ECT. 3.5.1, PAGE 19). To access the user parame-
Procedure Display
3 Press “Set/Esc”.
Press “-” to bring the set-point to the
4
intended value of 40°C.
Press “OK” to store in the memory
5
the new value.
After 3 seconds it will turn back to the Display mode with
6
the new set value.
If after having pressed
“Set/Esc” no operation is done for 10
seconds, (because the desired value corresponds to the set one) the PCB will go back to the functioning in Display mode. If af­ter having pressed “+” or “-” no button is pressed for the next minute, the PCB will go back to Display mode. Should this happen no value will be stored in memory.
3.2 CENTRAL HEATING PARAMETERS SETTING
The following functions can be set for the CH functioning.
3.2.1 Setpoint_T_CH_High
Set-point in the high temperature circuit (parameter 1)
If the operating mode is set to “fixed set point” (par. 14=CH_type_high=0), this is the objective temperature. If in­stead the outdoor temperature probe is used, i.e. the operating mode is set to “climate control” (par. 14= CH_type_high =1), this is the maximum objective temperature correspondent to the minimum outside temperature (T_out_min=par. 37, pre­set to 0°C). (Picture 3.1) Parameter 18 (T_CH_high_foot, pre­set to 50°C) defines the minimum set point correspondent to the maximum outside temperature (T_out_max, pre-set to 18°C). Pre-set to 70°C with upper limit set by par. 17
(T_CH_high_limit, pre-set to 80°C).
Procedure Display
Read value on the display for the high
1
temperature circuit 80°C.
Press to access the Readout mode, press again until “6” appears on the
2
first digit to visualise the set value of 50°C.
16
Fig. 3.1
Page 23
BOILER FUNCTIONING
3.2.2 Setpoint_T_CH_Low
Set point in the low temperature circuit (parameter 3)
If the operating mode is set to “fixed set point” (par. 22=CH_type_low=0), this is the objective temperature. If in­stead the outdoor temperature probe is used, i.e. the operating mode is set to “climate control” (par. 22=CH_type_low =1), this is the maximum objective temperature correspondent to the minimum outside temperature (T_out_min=par. 37, pre­set to 0°C). Parameter 24 (T_CH_low_foot, pre-set to 25°C) defines the minimum set point for the maximum outside tem­perature (T_out_max, pre-set to 18°C). Pre-set to 40°C with
upper limit set by par. 23 (T_CH_Low_limit, pre-set to 50°C).
CLIMATIC CURVE
100
90
80
70
T_CH_Low_foot
60
50
40
30
Flow temperature (°C)
20
10
0
25 20 15 10 5 0 -5 -10 -15 -20
LOW TEMPERATURE Circuit
maximum
T_out_min
T_out_max
Outdoor Temperature (°C)
heat need
T_CH_Low
Fig. 3.2
3.2.3 CH_Priority
Central heating priority (parameter 16)
If this is set to 0 the system works without central heating pri­ority, that is, with the high temperature and low temperature circuit served in parallel. If set to 1, the demand from the low temperature circuit is ignored and the corresponding pump re­mains off. The demand from the low temperature circuit is only accepted when the high temperature circuit demand is ab­sent. Vice-versa, if set to 2 the low temperature circuit has pri­ority. Pre-set to 0.
REMARK: If a priority is selected, it will be necessary to use the system with thermostatic setting.
The Master can be in different operative conditions, represent­ed by the flow diagram in F
IG. 3.3.
The diagram has been drawn with absolute DHW priority (Dhw_Priority Par.9 = 2) and without any CH priority (Ch_Priority Par. 16 = 0) and works with High temperature and Low Temperature circuits working in parallel.
With CH Priority on the High Temperature circuit (Ch_Priority Par.16 = 1), the High Temperature circuit is ac­tive whenever TA_H = 1 and DHW = 0. Under this condition the Low Temperature circuit is not active.
With CH Priority on the Low Temperature circuit (Ch_Priority Par.16 = 2), the Low Temperature circuit is ac­tive whenever TA_L = 1 and DHW = 0. Under this condition the High Temperature circuit is not active.
3.3 DOMESTIC HOT WATER
PARAMETERS SETTING
The following functions can be set for the domestic hot water circuit.
3.3.1 Setpoint_DHW
Domestic hot water set point (parameter 2)
This is the temperature value for the production of domestic hot water. The maximum limit is set by par. 8 (T_DHW_limit, pre-set to 60°C). Pre-set to 50°C.
3.3.2 DHW_Type
Type of storage tank (parameter 6)
- 0 = No DHW service
- 1 = Rapid heat exchanger with probe
- 2 = Storage tank with probe
- 6 = Storage tank with thermostat
For the storage tank with thermostat, if the input is a closed contact, the domestic hot water demand is activated, if it is an open contact the demand is not active. Pre-set to 0.
3.3.3 DHW_Priority
Domestic hot water priority (parameter 9)
- 0 = Sliding priority A
The purpose of the sliding priority A function is to allow the system to also serve the central heating function when the heating demand is low. The system reacts to the heating de­mand if:
(Setpoint_Ch - 50°C) < Manifold temp. < (Setpoint_Ch + 1°C)
Setpoint_Ch = Set point in the high or low temperature cir­cuit, according to the request.
- 1 = Sliding priority B
The purpose of the sliding priority B function is to ensure that the system does not stop the central heating service for a too long time.
The system reacts to the heating request if:
(Setpoint_Dhw+T_Tank_extra) - 50°C < Manifold temp. < (Setpoint_Dhw+T_Tank_extra) + 1°C
T_tank_extra = Par. 10 = pre-set to 30°C.
- 2 = Absolute priority (DHW service only) Pre-set to 0.
3.4 MAIN FUNCTIONS
3.4.1 Domestic Hot Water Priority function
The domestic hot water priority function allows that when there is demand for domestic hot water, the master board can also serve the high or low temperature circuit.
3.4.2 Anti-frost function
The frost protection function, also active in standby, starts the pump in the high temperature circuit and the loop pump if the temperature in the manifold falls below 5°C. If the outdoor probe is fitted, the pumps start if the outside temperature falls below 3°C. If after 10 minutes the temperature in the manifold is less than 5°C, one burner starts at maximum output, until the
17
Page 24
BOILER FUNCTIONING
TA_H = 1 & TA_L = 0 & DHW = 0
HIGH TEMPERATURE
CIRCUIT
TA_H = 0 or TA_L = 1 or DHW = 1 ERROR = 255
STAND BY
TA_H = 0 & TA_L = 1 & DHW = 0
LOW TEMPERATURE
CIRCUIT
TA_H = 1 or TA_L = 0 or DHW = 1 ERROR = 255
ERROR = 255
LOW AND HIGH TEMPERATURE
CIRCUIT
NO
TA_H = 1 & TA_L = 1 & DHW = 0
TA_H = 0 or TA_L = 0 or DHW = 1 ERROR = 255
YES
ANTI-FROST
DHW = 1
DHW
DHW = 0 ERROR = 255
ALARM
ERROR = 255 MEANS ABSENCE OF ERRORS
Fig. 3.3
temperature in the manifold reaches 20°C. If after 10 minutes the temperature in the manifold exceeds 5°C but the outside temperature is less than 3°C, the pumps stay on until the out­side temperature exceeds this value.
3.4.3 Dispersion function
Thanks to the dispersion function the pumps in the high and low temperature circuits remain on for 5 minutes after the last burner has shut down. There is a 6-minutes delay from the mo­ment when the burner shuts down to the moment when the two-way valve is closed or the injection pump is switched off. When the last burner has shut down, the valve closes only when there is no demand from the room thermostat.
3.4.4 Cascade management function
With the cascade management function is possible to select between minimum and maximum number of burners to be switched on to provide the power requested by the system.
ERROR
CHECK
ERROR = 255
3.4.5 Switch ON/OFF management function
In both cascading modes there is a function that limits the ig­nition and shutdown of the burners in the event of low heating requirement.
3.4.6 Emergency function
In the event of faults on the Master board, there are two was of manually controlling the Slave boards:
- By eBUS and manifold probe
Disconnect the power supply from the system, unplug the BUS. Set the address 000000 on all the Slave boards (J10 and J17 OFF). Connect a power supply between 21 and 28 Vac to the BUS. If the Manifold Temperature < Emergency Temp. (Par.40; pre-set to 70°C; settable between 10 and 80°C) all the burners operate at maximum output. If the Manifold Temperature > Emergency Temp. + 5°C all the burners are stopped.
18
Page 25
BOILER FUNCTIONING
-By PC
Disconnect the power supply from the system, unplug the BUS and connect the PC interface. The output of the burners can be sent directly to the Slave boards using the PC.
In the event of faults, contact BERETTA Technical
Assistance Service or a suitably qualified person.
3.5 PARAMETERS SETTING
3.5.1 Password setting
The installer parameters can be changed by entering the pass­word (22) from the readout mode. The password for the in­staller level allows access to display and change the user and installer parameters. Procedure to enter programming mode:
Procedure Display
E.g.: the outlet temperature T1 is
1
80°C.
Press “Set/Esc” and “OK”. After 5
2
seconds the second and third digit will flash.
Use “+” and “-” to enter on the right-hand side digit the second ci-
3
pher of the password. E.g.: pass­word = X2.
Procedure Display
Use “+” and “-” to enter on the cen-
5
tral digit the first cipher of the pass­word. E.g.: password = 22.
Press “OK” to confirm the password, if the password is
6
wrong the board returns to Display mode.
Press “+” and “-” to scroll the parameters enabled by the password. Press “Set/Esc” to start setting the parame-
7
ters. The code P-XX and the corresponding value will al­ternate on the display.
Use “+” and “-” to change the value of the parameter. Whenever a button is pressed, the alternating display of
8
the parameter and the corresponding value is stopped for 5 seconds and only the value is shown.
9 Press “OK” to save the new value of the parameter.
To exit installer programming mode press “Set/Esc”.
3.5.2 Parameters list
This boiler is equipped with a Master PCB that allows, via the functional parameters setting, a superior customisation to sat­isfy all the system or user needs. The programmable parame­ters are the ones reported in the following table.
Press “OK” to save the second ci-
4
pher of the password.
N. Name
USER Parameters
1 SetPoint_ch_high 10 Par. 17 70 °C
2 SetPoint_DHW 10 Par. 8 50 °C
3 SetPoint_ch_low 10 Par. 23 40 °C
INSTALLER parameters accessible by password 22
6 DHW_type 0 6 0
limit
Lower
limit
Upper
settings
Factory
U.M. Description
If Par. 14=0 this is the high temperature circuit set point.
If Par. 14=1 this is the maximum temperature in the high temperature circuit.
If Par. 22=0 this is the low temperature circuit set point. If Par. 22=1 this is the maximum temperature in the low temperature circuit.
0 = No DHW service 1 = Instant with NTC probe 2 = Storage tank with NTC probe 5 = Instant with flow switch 6 = Storage tank with thermostat
19
Page 26
BOILER FUNCTIONING
N. Name
7 P_DHW_max 1 255 230
8 T_DHW_limit 10 80 60 Limit for user DHW setting
9 DHW_priority 0 2 0
10 T_tank_extra 0 50 30 °C Thermal unit temperature in DHW = Par. 2 + Par. 10
11 T_tank_hyst_up 0 20 1 °C Upper DHW differential
12 T_tank_hyst_down 0 20 5 °C Lower DHW differential
13 N°_bruc_DHW 1 60 60 Maximum no. of burners in DHW
14 CH_type_high 0 3 1
15 P_ch_max 1 255
limit
Lower
limit
Upper
155
(DEP)
230
U.M. Description
settings
Factory
Maximum speed/output in DHW. The power changes proportionally from 15 kW = 1 to 45 kW = 255. Every point from 1 t o255 is equal to 0,12 kW. If for instance we want to set a power of 30 kW for each thermal en­gine, we will insert 127.
0 = Sliding A 1 = Sliding B 2 = Absolute priority
0 = Fixed temperature 1 = Climate with outside probe 2 = 0-10 Vdc for heat output 3 = 0-10 Vdc for temperature
Maximum speed/output in CH
0 = No priority between circuits
16 CH_priority 0 2 0
17 T_CH_high_limit 10 80 80 °C Limit for user high temperature circuit setting
18 T_CH_high_foot 10 Par. 1 50 °C
19 CH_high_mod_hyst_on 0 20 7 °C Hysteresis ON for high temperature pump
20 CH_high_mod_hyst_off 0 20 3 °C Hysteresis OFF for high temperature pump
21 Attenuation_high 0 70 0 °C Set point attenuation with room thermostat open
22 CH_type_low 0 3 1
23 T_CH_low_limit 10 70 50 °C Limit for user low temperature circuit setting
24 T_CH_low_foot 10 Par. 13 25 °C
25 Attenuation_low 0 70 0 °C Set point attenuation with room thermostat open
26 CH_low_hyst_on 0 20 5 °C
27 CH_low_hyst_off 0 20 3 °C
28 Mix_valve_step_ open_time 0 255 5 s For each step the valve opens 1/2 of the set value
1 = Priority to the high temperature circuit 2 = Priority to the low temperature circuit
Min. high circuit set point at the maximum outdoor temperature (Par. 38)
0 = Fixed temperature 1 = Thermoregulation with outdoor probe 2 = 0-10 Vdc for heat output 3 = 0-10 Vdc for temperature
Min. low temp. circuit set point - at the maximum out­side temperature (Par. 38)
Hysteresis ON for low temperature circuit calculated on the T flow Mix
Hysteresis OFF for low temperature circuit calculated on the T flow Mix
29 Mix_valve_step_close_time 0 255 7 s For each step the valve closes 1/2 of the set value
30 Mix_valve_interval_time 0 255 5 s Mixing valve delay
31 Mixing_p_hyst 0 255 2 °C Hysteresis for maximum valve opening
32 Mixing_still_hyst 0 255 2 °C
20
Page 27
BOILER FUNCTIONING
N. Name
limit
Lower
limit
Upper
33 Power control mode 0 1 1
rd
34 3
pump 0 1 0
U.M. Description
settings
Factory
0 = Minimum number of burners 1 = Maximum number of burners
0 = System/loop 1 = Low temperature circuit
35 Frost protection -30 15 3 °C System
1 = NG with flue < 15m
36 Gas_type 1 7 1
2 = NG with flue > 15m 3 = LPG with flue < 15m 4 = LPG with flue > 15m
37 T_out_min -20 30 0 °C Minimum outdoor temperature
38 T_out_max 0 30 18 °C Maximum outdoor temperature
39 T_out_correct -30 30 0 °C Outdoor temperature correction
40 T_emergency 10 80 70 °C
41 Parameter_reset 0 1 0
42 Flow switch_si/no 0 1 1 0 = The slave does not control the pressure switch
43 Protocol 0 1 1
0 = Eco protocol 1 = Argus link (new)
MANUFACTURER Parameters (OEM) accessible by password 82
REMARK - These parameters should not be modified
44 T_ch_high_max 10 117 90 °C Upper limit for Par.17
45 P_factor_CH_high 0 255 30
46 I_factor_CH_high 0 255 70
47 D_factor_CH_high 0 255 128
48 Ch_H_block_time 0 255 0 min
Proportional Constant for the high temperature circuit power modulation
Integral Constant for the high temperature circuit pow­er modulation
Derivative Constant for the high temperature circuit power modulation
When the TA_H opens the system accepts a new heat request only after the set time
49 Postcirc_high 0 255 5 min Postcirculation of P1 (+P3)
50 T_H_correct_20° -30 30 0 °C
51 T_H_correct_85° -30 30 1 °C
52 Blocking_time_ DHW-CH 0 255 0 min
Correction of the value read by the collector probe at 20°C
Correction of the value read by the collector probe at 85°C
The burner stays OFF for the set time in the passage from DHW to CH
53 T_ch_low_max 10 90 80 °C Upper limit of the Par. 23
54 P_factor_CH_low 0 255 30
55 I_factor_CH_low 0 255 70
56 D_factor_CH_low 0 255 128
Proportional Constant for the low temperature circuit power modulation
Integral Constant for the low temperature circuit pow­er modulation
Derivative Constant for the low temperature circuit power modulation
57 Ch_L_block_time 0 255 0 min
58 T_dhw_max 10 117 80 °C
59 P_factor_DHW_istantaneous 0 255 30
21
Page 28
BOILER FUNCTIONING
N. Name
limit
Lower
limit
Upper
U.M. Description
settings
Factory
60 I_factor_DHW_istantaneous 0 255 70
61 D_factor_DHW_istantaneous 0 255 128
62 P_factor_DHW_storage 0 255 30
63 I_factor_DHW_storage 0 255 70
64 D_factor_DHW_storage 0 255 128
65 Dhw_&_ch_hysterese_up 1 80 1
66 Dhw_&_ch_hysterese_down 1 80 50
67 T_tank_hyst_down_2 0 20 5
68 T_tank_hyst_up_2 20 3
69 Postcirc sanitary 0 255 3 m
70 Hyst_up_reduce_burner 0 20 2 °C
71 Hyst_down_add_burner 0 20 5 °C
72 Hyst_up_quick_stop 0 80 4
73 Hyst_down_quick_start 0 80 70
74 Quick stop time 0 255 2 s
75 Quick start time 0 255 2 s
Wai time after
76
burner_switched
025530 s
77 Cycle_limitation 0 1 0
78 Cycle_limit_stop 0 255 60
79 Cycle_limit_inc 0 50 10
80 Cascade Rotation 0 255 24 h
81 Flow Switch 0 1 0
82 Return probe 0 1 1
83 Maximum_fan_speed_slave 20 70 57 rpm
84 Minimum_fan_speed 20 Par.83 25 rpm
85 Ignition_fan_speed Par.84 Par.83 45 rpm
86 Prepurge_fan_speed Par.84 Par.83 45 rpm
87 Max flow temperature 10 117 90 °C
88 Max return temperature 10 117 80 °C
89 Max flue temperature 10 117 80 °C
90 Flue Temperature Safety 0 1 0
91 T.max flow/return Safety 0 1 0
Pump postcirculation/slave
92
valve
02556 m 255 = Continuous functioning
93 D_max_flow_return 10 99 35 °C
94 Postcirculation 3
rd
pump 0 255 5 m 255 = Continuous functioning
0 = NO flow switch 1 = YES flow switch
0 = NO return probe 1 = return probe present with control on ∆T
0 = Volatile lockout 1 = Permanent lockout
0 = Volatile lockout 1 = Permanent lockout
> Par.93: OFF ∆ > Par.93 - 5°C: Minimum ∆ > Par.93 -10°C: Power reduction of 60°C.
22
Page 29
BOILER FUNCTIONING
N. Name
limit
Lower
limit
Upper
U.M. Description
settings
Factory
95 Password 00 99 22-44 DO NOT MODIFY
96 Hyst_up_PID_I_reduce 0 10 1
If T.flow setpoint + Par. 96, the Par. 97 is deducted
97 I_reduce_value 0 30 1 s
from the high bit of the sums of the differences from the set. Reduction of the fastest integral factor
98 Low_load waiting 0 255 60 s
Waiting time of the Master to recognise the low load condition
Waiting time to enable the low load condition. The low
99 Low_load period 0 255 60 °C
load condition is active if the T.flow is above the set temperature with PAR. 9B and remains high after the time set with Par. 99.
9A Neg_delta2_T 0 20 8 °C
9B Calc_neg_delta 0 1 1
9C Neg_delta2_T 0 30 0 °C
9D Low_load_ 0205 °C
9E Hyst__mand/rit. 0 5 2 °C
This is used to reset the burners power when T.flow < setpoint - Par. 9A
0 = Calculation low load from 85°C 1 = Calculation low load from set-point
It is used to reduce the burners power when T.mand Setpoint - Par. 9C. the power reduction is 60/1°C
The low load condition is active with T.flow > Setpoint + Par. 9D
Hysteresis of Par. 93: the burner is switched off with > Par. 93 and is switched on when < Par. 93- Par. 9E
3.6 SETTINGS
The POWER PLUS Boiler is supplied for operation on G20 (natural gas), as indicated on the rating plate, and has already been adjusted in the factory by the manufacturer. If, however, the adjustments need to be performed again, for example after special servicing operations, the replacement of the gas valve, or alternatively following the conversion from G20 to G30­G31 or vice-versa, proceed as follows.
The adjustments at maximum and minimum output
must be carried out in the sequence described, and only by BERETTA Technical Assistance or qualified personnel authorised by BERETTA.
TEST mode
In Test mode, a high temperature heating demand can be gen­erated corresponding to maximum and minimum power. All the system fans must be activated. If the installer switches off some of the Slaves, the others, connected to the Master, must continue operating.
To enter Test mode from Display mode, proceed as follows:
Procedure Display
Press “Set/Esc” and “+” at the same time per 5 seconds. After 5 seconds the maximum or minimum speed can be se­lected using the “+” and “-” buttons. All the system fans will operate at the selected speed. The first digit will show
1
the selected speed: H = maximum speed L = minimum speed The other two digits will show the out-
let temperature. E.g.: T1 = 80°C.
Press “OK” to exit Test mode and re-
2
turn to Display mode.
3.6.1 Maximum power CO
2 setting
- Press the “Set/Esc” and “+” buttons together for 5s.
- Start the boiler by the room thermostat (close). The boiler
will operate at maximum output showing “H” on the dis­play, followed by the flow temperature (chimney sweep function).
- Unscrew the protective cap (1 - F
IG. 3.4) with a socket
wrench of 10mm and insert the combustion analyser probe.
- Adjust the CO
(2 - F
IG. 3.4) located on the fan assembly (turning clock-
wise decreases the CO
2 using a screwdriver on the adjustment screw
2 value), so as to achieve a value of
9.4% for G20 and 10.7% for G30-G31.
23
Page 30
BOILER FUNCTIONING
2
The conversion must only be carried out by BER-
ETTA Technical Assistance or qualified personnel authorised by BERETTA, even when the boiler is already installed.
Once the conversion has been completed, set the
boiler again as described in S
ECT.3.6, PAGE 23.
Before performing the conversion:
- Disconnect the power supply
from the appliance by moving
ON
the main switch to “OFF”.
1
Fig. 3.4
3.6.2 Minimum power CO2 setting
- Press the “Set/Esc” and “-” buttons together for 5s. The boiler will operate at minimum output showing “L” on the display, followed by the flow temperature.
- Remove the protective cap on the gas valve by using an Allen key (5 mm). Adjust the CO on the adjustment screw (3 - F sembly (turning anticlockwise decreases the CO
2 using the same Allen key
IG. 3.5) located on the fan as-
2 value),
so as to achieve a value of 8.4% for G20 and 8.7% for G30­G31.
3
- Close the fuel general valve.
To fit the kit:
- Unscrew the fastening screws (1
- F
IG. 3.6) on the front panel (2 -
F
IG. 3.6).
2
OFF
1
Fig. 3.5
3.6.3 Adjustments verification
Press the “Set/Esc” and “+” buttons together for 5s and check the max CO
2 value (9.4% for G20 and 10.7% for G30-G31).
Then press the “Set/Esc” and “-” buttons for 5s and check the min CO
2 value (8.4% for G20 and 8.7% for G30-G31).
After having completed the checks:
- Stop the chimney sweep function by pressing “OK”.
- Adjust the thermostat (open) so as to stop the boiler.
- Remove the analyser probe and carefully retighten the flue test point cap (1 - F
IG. 3.5) with a socket wrench of 10 mm.
3.7 GAS CONVERSIONS
The POWER PLUS Boiler is supplied for operation on G20 (natural gas). However, it can be converted for operation on G30-G31 (LPG), using the special kit supplied.
1
Fig. 3.6
- Pull the base of the panel (2 - F
IG. 3.6) outwards and then
upwards to release it from the frame and then remove it.
- Set parameter 36 to 3 or 4, according to the length (L) of the flue:
• 3 = L < 15 m
• 4 = L > 15 m.
The fan speed is adapted automatically.
- Disassemble the gas valve from the fan assembly by loosen­ing the three screws (3 - F
IG. 3.7).
3
Fig. 3.7
24
Page 31
- Locate the gas passage hole and seal. If the system is Natural
6.5
Gas fuelled, there is no diaphragm.
- Insert the calibrated diaphragm (4 - F
IG. 3.8) supplied inside
the kit, marked with “6.5” without removing the seal. Only if the boiler is supplied by a mixture of gases that causes ig­nition problems, use the other supplier diaphragm (5 - F
IG.
3.8) marked with “6.75”.
6.75
4 5
Fig. 3.8
- Reassemble the gas valve.
- Apply the sticker (6 - F
IG. 3.9) for G30-G31, supplied inside
the kit, on the inside of the panelling, and remove the sticker for G20.
- Remove the sticker for G20 placed on the side of the frame.
BOILER FUNCTIONING
2
1
Fig. 3.10
6
Boiler regulated for:
G31 37 mbar
Destination Country:
TXXXXXXXX
IT
Fig. 3.9
After having installed the kit make sure that:
- All the joints made are tight.
- All the calibration operations described in S
PAGE 23 have been completed
ECT.3.6,
3.8 BURNER PRESSURES SETTINGS
3.8.1 Gas supply pressure check
- Move the main system switch to “OFF”.
- Unscrew the fastening screws (1
- F
IG. 3.10) on the front panel (2
- F
IG. 3.10).
- Pull the base of the panel (2 -
F
IG. 3.10) outwards and then up-
wards to release it from the frame and then remove it.
- Unscrew the screw on the pressure test point (3 - F located upstream of the gas valve by around two turns, and connect a pressure gauge.
ON
OFF
IG. 3.11),
3
Fig. 3.11
- Power-up the boiler by moving the main system
ON
switch and the main switch/switches on the ap­pliance to “ON”.
OFF
In TEST mode, a high tem­perature heating request at maximum output can be generated.
To do this:
- Press the “Set/Esc” and “+” buttons together for 5 seconds.
- Start the boiler by adjusting (close) the room thermostat. The boiler will operate at maximum output showing “H” on the display, followed by the flow temperature (chimney sweep function).
Fig. 3.12
25
Page 32
BOILER FUNCTIONING
- Check that with the burner on at maximum output the gas pressure is the rated supply pressure, as shown in the table.
Description G20 G30 G31
Wobbe index 45,7 80,6 70,7 MJ/m
Rated supply pressure 20 28-30 37 mbar
- Adjust the thermostat (open) so as to stop the boiler.
- Press “OK” to exit TEST mode.
- Disconnect the pressure gauge and tighten the screw on the pressure test point (3 - F
IG. 3.11) upstream of the gas valve.
3.9 COMBUSTION CHECK
- Power-up the boiler by moving the main system switch and the main switch/switches on the ap­pliance to “ON”.
In TEST mode, a high tem­perature heating request at maximum output can be generated. To do this:
- Press the “Set/Esc” and “+” buttons together for 5 seconds.
- Start the boiler by adjusting the room thermostat (close). The boiler will operate at maximum output showing “H” on the display, followed by the flow temperature (chimney sweep function).
Fig. 3.13
- Combustion can be checked by unscrewing the protective cap (4 - F ing the analyser probe in the available position.
REMARK: Once the set-point has been reached, the boiler
- Once having completed the check, stop the chimney sweep function by pressing “OK”.
- Adjust the thermostat (open) so as to stop the boiler.
- Remove the analyser probe and carefully retighten the pro­tective cap (4 - F mm.
REMARK: Perform the check on each thermal engine.
Fig. 3.14
IG. 3.14) with a socket wrench of 10mm and insert-
will modulate its power.
IG. 3.14) by means of a socket wrench of 10
ON
OFF
4
3.10 FAN SPEEDS
The fan speed is adjusted automatically based on the type of gas and the length of the flue (L). This information is managed by parameter 36. To modify it:
3
- Enter “INSTALLER PROGRAMMING MODE” following the procedure described in S rameter 36 to: 1 = natural gas and L<15 m
2 = natural gas and L>15 m
3 = GPL e L<15 m
4 = GPL e L>15 m.
The POWER PLUS boilers are supplied for operation with G20 (natural gas), with a flue L<15m (parameter 36=1).
Once the checks are complete, replace the front panel and se­cure it using the same screws removed before.
All the check must only be carried out by BERETTA
Technical Assistance or qualified personnel autho­rised by BERETTA.
ECT. 3.5, PAGE 19 and set pa-
3.11 THERMOREGULATION SETTINGS
3.11.1 Central heating high temperature circuit
functioning
The burner delay time of the circuit of high temperature (Ch_high_blocking_time; Par.48 OEM pre-set 0; adjustable between 0 and 255min) is the time between two successive burner ignitions during an heat request of the High Tempera­ture circuit. The delay time is active only when the OFF of the burner is caused by the hysteresis and not for the room thermo­stat TA_H opening. The delay time is not active in case of heat request of the DHW circuit.
In this state the power requested by the Master to the Slaves changes linearly between 1 and the parameter of the Maxi­mum Power in CH (P_ch_max; Par.15 pre-set 230 for the models 50 M - 100 M - 100 S, pre-set 170 for the models 100 M DEP - 100 S DEP; adjustable between 1 minimum power and 255 maximum power).
3.11.2 Attenuation_High
Attenuation function for the HIGH TEMPERATURE cir­cuit (parameter 21)
Two cases are possible:
- Operation with fixed set point, Par. 14=0.
- Operation with climate control Par. 14=1.
Operation with fixed set point, PAR. 14=0
- With attenuation in the high temperature circuit disabled, Par. 21=0, when the thermostat in the high temperature cir­cuit closes, the heating demand is enabled. When opening, the system stops.
- The Master controller activates the pump in the high temper­ature circuit PZ1 and the loop pump PZ2 (configuration with loop circuit pump), if the parameter for the third pump is set to 0 (Par. 34=0), otherwise the third pump remains off.
- The set point for the high temperature circuit can be set on the Master controller, Setpoint_T_CH_High = Par. 1, pre­set to 70°C, settable in the range from 10°C to T_CH_high_limit=Par 17, in turn pre-set to 80°C. The set point used will be the value set for parameter 1.
26
Page 33
BOILER FUNCTIONING
- The burner is on when: Manifold Temperature Set point ­Start hysteresis.
- The hysteresis ON can be set, CH_High_mod_hyst_on = Par. 19, pre-set to 7°C, settable between 0 and 20°C. The Master controller converts the heating request into a power requirement for each slave controller.
- The burners are off when: Manifold Temperature Set point + Hysteresis OFF.
- The hysteresis OFF can be set (CH_High_mod_Hyst_off = Par. 20, pre-set to 3, settable between 0 and 20°C).
- When the attenuation in the high temperature circuit param­eter is enabled, Par. 21 0, the contact on the high temper­ature circuit thermostat is ignored, and a request for heat in the high temperature circuit is present when: Manifold Tem­perature Set point - Start hysteresis.
- The demand for heat is interrupted when: Manifold Temper­ature Set point + Stop hysteresis.
- The set point in this case coincides with the value set for pa­rameter 1 (Setpoint_T_CH_High), if the contact of the high temperature circuit thermostat is closed, while it is calculat­ed as the value set for parameter 1 minus the attenuation (Setpoint_ T_CH_High-Attenuation_high) if the contact is open.
- If no heat request is present form the Low Temperature cir­cuit, the mixing valve is closed and the power requested to the Slave controllers is calculated through the PID control of the high temperature circuit (PID_CH_high: P_factor_CH_high; Par.45 OEM pre-set to 30; settable from 0 to 255; I_factor_CH_high Par.46 OEMpre-set to 70; ad­justable from 0 to 255; D_CH_high Par.47 OEM pre-set at 128, programmable from 0 to 255) applied to the selected set-point (Setpoint_ch_high; Par.1) and to the collector tem­perature.
- The power requested to each Slave controller is also depen­dent from the cascading strategy selected.
- When the room thermostat TA_H opens, the heat request ceases, the burner is switched off and the High Temperature pump P1 continues to run for the post-circulation time (Postpump_ch_high; Par.49 OEM pre-set 5 min; settable between 0 and 255 min). if the parameter 3rd_pump Par.34 is set to 0 (system pump) the third pump, as well, continues to function along the post-circulation time. If present the in­jection pump, or the 2-ways valve, they are supplied for the post-circulation time only.
Operation with climate control, Par. 14=1
If the attenuation in the High Temperature circuit parameter is equal to 0, Attenuation_high=Par. 21=0, the behaviour is the same as in the previous paragraph, except for the set point be­ing calculated according to the outside temperature.
- If the outside temperature = T out_min=Par. 37, pre-set to 0°C, then set point =setpoint_T_Ch_high.
- If the outside temperature = T out_max=Par. 38, pre-set to 18°C, then set point = T_CH_high_ foot=Par. 18, preset to 50°C.
Between the two outside temperature values, the set point is calculated linearly.
The outside temperature is measured between -30°c and 98°C and can be amended with the parameter T_out_correct (Par. 39 pre-set to 0°; adjustable between -30°C and 30°C).
If the parameter High Temperature circuit Attenuation is dif-
90
80
70
60
50
Setpoint
40
30
20
-30 -20 -10 0 10 20 30
Climatic curves
Par. 1
Par. 3
Par. 39 Par. 38
Outdoor Temperature
CH_high CH_low CH high attenuated
Par. 18
Fig. 3.15
ferent from 0 (Attenuation_high; Par. 21 pre-set to 0; adjust­able from 0 to 70), the TA_H doesn’t affect the heat request at all.
The heat request is active when:
- Outdoor Temperature < T_out_max (par.38 pre-set to 18°C) AND
- Flow Temperature SetPoint_ch_high (Par. 1 pre-set to 70°C) - ch_high_mod_hyst_on (Par. 19 pre-set to 7°C).
The heat request ceases when:
- Flow Temperature > SetPoint_ch_high (Par.1 pre-set to 70°C) + ch_high_mod_hyst_off (Par.20 pre-set to 3°C) OR
- Outdoor Temperature > T_out_max (Par.38 pre-set to 18°C)
The set-point is calculated as above, but the value of High Temperature circuit Attenuation (Attenuation_high; Par. 21 pre-set to 0, programmable between 0 and 70) is deducted from the calculation when the TA_H contact is opened.
3.11.3 Central heating low temperature circuit
functioning
The burner delay time of the circuit of low temperature (Ch_low_blocking_time; Par. 57 OEM pre-set 0; adjustable between 0 and 255min) is the time between two successive burner ignitions during an heat request of the Low Tempera­ture circuit. The delay time is active only when the OFF of the burner is caused by the hysteresis and not for the room thermo­stat TA_L opening. The delay time is not active in case of heat request of the DHW circuit.
In this state the power requested by the Master to the Slaves changes linearly between 1 and the parameter of the Maxi­mum Power in CH (P_ch_max; Par. 15 pre-set 230; adjustable between 1 minimum power and 255 maximum power).
3.11.4 Attenuation_Low
Attenuation function for the HIGH TEMPERATURE cir­cuit (parameter 25)
This paragraph is similar to the previous one, but for the Low Temperature circuit. Two cases are possible:
- Operation with fixed set point, Par. 14=0.
- Operation with climate control Par. 14=1.
Operation with fixed set point, Par. 22=0
- With attenuation in the low temperature circuit disabled, Par25=0, when the thermostat in the low temperature circuit closes, the heating demand is enabled. When opening, the
27
Page 34
BOILER FUNCTIONING
system stops.
- The Master controller activates the pump in the low temper­ature circuit PZ2 (except configuration with loop circuit pump). The set point for the low temperature circuit can be set on the Master controller, Setpoint_T_CH_Low = Par. 3, pre-set to 40°C, settable in the range from 10°C to T_CH_low_limit = Par. 23, in turn pre-set to 50°C. The set point used will be the value set for parameter 3.
- The burner is on when: Manifold Temperature Set point ­Start hysteresis. The hysteresis ON can be set, CH_Low_mod_hyst_on = Par. 26, pre-set to 5°C, settable between 0 and 20°C. The Master controller converts the heating request into a power requirement for each slave controller.
- The burners are off when: Manifold Temperature Set point + Hysteresis OFF. The hysteresis OFF can be set (CH_Low_mod_Hyst_off = Par. 27, pre-set to 3, settable between 0 and 20°C).
- hen the attenuation in the low temperature circuit parameter is enabled, Par. 25 0, the contact on the low temperature circuit thermostat is ignored, and a request for heat in the low temperature circuit is present when: Manifold Temper­ature Set point - Hysteresis ON.
- The demand for heat is interrupted when: Manifold Temper­ature Set point + Hysteresis ON. The set point in this case coincides with the value set for pa­rameter 3 (Setpoint_T_CH_Low), if the contact of the low temperature circuit thermostat is closed, while it is calculat­ed as the value set for parameter 3 minus the attenuation (Setpoint_ T_CH_Low-Attenuation_low) if the contact is open.
- If no heat request is present from the High Temperature cir­cuit, the mixing valve is completely open and the power re­quested to the Slave controllers is calculated through the PID control of the low temperature circuit (PID_CH_low: P_factor_CH_low; Par.54 OEM pre-set to 30; settable from 0 to 255; I_factor_CH_low Par.55 OEMpre-set to 70; ad­justable from 0 to 255; D_CH_low Par.56 OEM pre-set to 128, programmable from 0 to 255) applied to the selected set-point (Setpoint_ch_low). The algorithms for the quick start and quick stop are calculated according to the Low Temperature circuit set-point (Setpoint_ch_low) and to the Collector Temperature (T_flow_high).
- The power requested to each Slave controller is also depen­dent from the cascading strategy selected.
- If an heat request form the High Temperature circuit is also present, the mixing valve is controlled in order for the Low Temperature Circuit Flow Temperature to be equal to the setpoint_ch_low. For this a specific algorithm, described in the section “Mix valve Management” exist.
- When the room thermostat TA_L opens, the heat request ceases, the burner is switched off and the Low Temperature pump or the System pump continue to run for the post-cir­culation time (Postpump_ch_low; Par. 49 OEM pre-set 5 min; settable between 0 and 255 min).
Operation with climate control, Par. 22=1
If the attenuation in the Low Temperature circuit parameter is equal to 0, Attenuation_low = Par. 25=0, the behaviour is the same as in the previous paragraph, except for the set point be­ing calculated according to the outside temperature.
- If the outside temperature = T out_min = Par. 37, pre-set to 0°C, then set point = setpoint_T_Ch_low.
- If the outside temperature = T out_max = Par. 38, pre-set to 18°C, then set point = T_CH_low_ foot = Par. 24, preset to 50°C.
Between the two outside temperature values, the set point is calculated linearly.
The outside temperature is measured between -30°c and 98°C and can be amended with the parameter T_out_correct (Par. 39 pre-set to 0°, adjustable between -30°C and 30°C).
If, instead, the parameter Low Temperature circuit Attenua­tion is different from 0 (Attenuation_low; Par. 25 pre-set to 0; adjustable from 0 to 70), the TA_L (Low Temperature Circuit Room thermostat) doesn’t affect the heat request at all.
The heat request is active when:
- Outdoor Temperature < T_out_max (Par. 38 pre-set to 18°C) AND
- Flow Temperature SetPoint_ch_low (Par. 3 pre-set to 40°C) - ch_low_mod_hyst_on (Par. 25 pre-set to 7°C).
The heat request ceases when:
- Flow Temperature > SetPoint_ch_low (Par. 3 pre-set to 40°C) + ch_low_mod_hyst_off (Par. 27 pre-set to 3°C) OR
- Outdoor Temperature > T_out_max (Par. 38 pre-set to 18°C)
The set-point is calculated as above, but the value of Low Temperature circuit Attenuation (Attenuation_low; Par. 25 pre-set to 0, programmable between 0 and 70) is deducted from the calculation when the TA_H contact is opened.
3.11.5 T_out_correct
Outside temperature correction (parameter 39)
The value normally displayed is the value read by the micro­controller, plus or minus a correction value (T displayed = T read by the probe +/- correction).
The outside temperature value read can be corrected by chang­ing the value of parameter 39, (the limit allowed for the cor­rection is +/-30 °C). In this phase, the use of a reference ther­mometer is suggested.
Pre-set to 0.
3.11.6 T4_frost_protection
Frost protection (parameter 35)
- The electronic controller provides a built-in frost protection function that is also active in standby. The frost protection function has two levels, the first that starts the pump only , and the second that starts the pump and the burner.
- If the Manifold Temperature 5°C, the pump in the high temperature circuit and the loop pump are activated, or, with CH_type=1 and the outside probe connected, if the Outside Temperature 3°C (Par. 35), the pump in the high temper­ature circuit and the loop pump are started.
- If after 10 minutes the Manifold Temperature 5°C a burner is started at maximum power, until the Manifold Tempera­ture 20°C.
- If after 10 minutes the Manifold Temperature 5°C but, with CH_type=1 (Par. 14 or 22) and the outside probe con-
28
Page 35
BOILER FUNCTIONING
nected, the Outside Temperature 3°C (Par. 35), the pump continues operating until the Outside Temperature 3°C. The Parameter 35 can be set between -30°C and 15°C.
Pre-set to 3.
3.11.7 Power_control_mode
Cascading management (parameter 33)
To manage the power delivered by the system, two cascading strategies are available. In both cases, the Master controller can only start a new burner when another is already on. If the Master controller needs to increase the number of burners on, it first verifies that the subsequent burner can be started: no er­ror is present and temperature of the boiler is less than the maximum. Otherwise, it checks another burner. If no burner is available, the master decreases the number of burners to be started.
Mode: minimum number of burners ON (Par. 33 = 0)
The output of the system is modulated by a PID control algo­rithm, where the value controlled is the temperature in the manifold, and the set point refers to the active circuit (set point in the high or low temperature circuit, or DHW set point). The PID control directly manages the last 2 burners started, while the previous burners operate at maximum output.
- If the Manifold Temperature < set point - 5°C, the next burn­er is switched on, and both are managed by the PID control algorithm. The Master controller waits 30 seconds, and then if the Manifold Temperature < set point - 5°C, another burn­er is started. The first burner works at maximum power, while the other two are managed by the PID control algo­rithm.
- If the Manifold Temperature > set point + 2°C, the last burn­er switched on is stopped, the other two most recently start­ed burners are managed by the PID control algorithm, while the others work at maximum output. The Master controller waits 30 seconds before checking the situation again.
Mode: maximum number of burners ON (Par. 33 = 1)
All the burners are controlled by the same PID control algo­rithm, where the value controlled is the temperature in the manifold, and the set point refers to the active circuit (set point in the high or low temperature circuit, or DHW set point).
- If the Manifold Temperature < set point - 5°C, the next burn­er is started. The Master controller waits 30 seconds, and then if the Manifold Temperature < set point - 5°C, another burner is started.
- If the Manifold Temperature > set point + 2°C the last burn­er is stopped. The Master controller waits 30 seconds before checking the situation again.
ADDITIONAL CASCADING MANAGEMENT FUNCTIONS
Rotation of burner ignition sequence
When the Master controller is switched on, the burner with ad­dress 1 is the first in the sequence. After 24 hours, the burner with address 2 becomes the first burner, while the burner with address 1 becomes the last in the sequence.
Limitation of starts/stops
In both cascading strategies, after each start or stop, a mini­mum time must expire before the Master can start or stop any of the remaining burners.
Rapid start/stop
In both modes a function is available for rapidly reaching sta­ble operating conditions and shutting down.
- If the Manifold Temperature < set point - 70°C the burners are started at 2 second intervals.
- If the Manifold Temperature > set point + 4°C the burners are stopped at 2 second intervals.
Low load
The low load function prevents the burners from stating and stopping when there is a low heating demand. The conditions for the activation of the Low Load function are checked on ev­ery Slave board, which sends the request to enable the function to the Master. During normal operation, the set point in the ac­tive circuit (set point in the high or low temperature circuit, or DHW set point) is sent to the Slave boards, and the tempera­ture of the heating unit is checked by each Slave board:
- if the heating unit temperature > Set point - 8°C OR
- if the heating unit temperature > 85°C - 8°C, the signal to start the burner is disabled.
When the Slave board reads a boiler temperature greater than 85°C three times when the burner is on, the heating unit is stopped and the start-up procedure is started again.
Being that every heating unit has its own limit thermostat set to 85°C, the single burner power is limited by the boiler tem­perature:
- if the Boiler temperature > set point - Neg_2_slave, the burner modulates;
- if the Boiler temperature > set point - Neg_2_slave +
4.5°C, the burner works at the minimum.
When the Boiler temperature > 85°C for the time Low_load_period_slave (Par. 99; pre-set to 60”) or the Boiler temperature > setpoint + Lox_load_ (Par. 9D; pre-set to 5°C) a request is sent to the master board for the Low Load function to be activated and the Master board reduces the number of working burners. The Master board waits then for the time Low_load_waiting (Par. 99; pre-set to 60”) and verifies again the presence of the Low Load request, diminishing the number of working burners until a single working burner is reached.
Managing the heating demand in the high temperature cir­cuit by analogue input (Par. 14 = 2 or 3)
The room thermostat in the high temperature circuit is ignored for the heating demand, and the input signal is used to calcu­late the output or the system set point. There is just one ana­logue input (see terminals 13-14 on the wiring diagram on AP-
PENDIX G -
PAG.76) on the Master board and this can also be
used for the low temperature circuit (Par. 22). The analogue input cannot be used for both the circuits.
Analogue input for heat power, Par. 14 = 2 (Par. 22 = 2 for low temperature circuits)
The heat request for the high temperature (low temperature) circuit is made according to the following rules (F
IG. 3.16):
29
Page 36
BOILER FUNCTIONING
-0-2Vdc
No demand from the high temperature (low temperature) circuit
-2-9Vdc
The request for heat is converted into a power demand for each Slave. An input of 2 V corresponds to minimum power, 9 V to maximum power (Par. 15). Between 2 V and 9 V the power is calculated linearly. The hysteresis for the end of the request is 0.2 V and therefore the demand is active above 2 V and ceases below 1.8 V. The burner starts when:
Flow Temp. = Setpoint_Ch_high (Par. 1) ­Ch_high_mod_hist_on (Par. 19)
(Flow Temp. = Setpoint_Ch_low (Par. 3) ­Ch_low_mod_hist_on (Par. 26))
The burner stops when:
Flow Temp. > Setpoint_Ch_high (Par. 1) + Ch_high_hist_off (Par. 20)
(Flow Temp. > Setpoint_Ch_low (Par. 3) + Ch_low_hist_off (Par. 27))
250
200
150
100
Power (kW)
50
0
0
12345678910
Voltage (Volt)
Fig. 3.16
Analogue input for temperature, Par. 14 = 3 (Par. 22 = 3 for low temperature circuits)
The request for the high temperature (low temperature) circuit is made according to the following rules (F
IG. 3.17):
-0-2Vdc
No request from the high temperature (low temperature) cir­cuit
-2-9Vdc
The demand for heat is converted into a power requirement for each Slave, by the PID_CH_high (PID_CH_low) algo­rithm. 2 V corresponds to a set-point of T_Ch_high_foot, Par. 18 (T_Ch_low_foot, Par. 24), 9 V to a set point of Setpoint_Ch_high, Par. 1 (Setpoint_Ch_low, Par. 3). Be­tween 2 V and 9 V the set point is calculated linearly. The hysteresis for the end of the request is 0.2 V and therefore the request is active above 2 V and ends below 1.8 V. The burner starts when:
Flow Temp. Setpoint_ch_high (Par. 1) - Ch_high_hist_on (Par. 19)
(Flow Temp. Setpoint_ch_low (Par. 3) ­Ch_low_mod_hist_on (Par. 26))
The burner stops when:
Flow Temp. > Setpoint_ch_high (Par. 1) + Ch_high_hist_off (Par. 20)
(Flow Temp. > Setpoint_ch_low (Par. 3) + Ch_low_hist_off
90
80
70
60
50
40
Set-point
30
20
10
0
012345678910
Voltage (Volt)
Fig. 3.17
3.11.8 Slave PCBs safety functions
When the Flow Temperature > 90°C for 5s, the Slave board locks out (E46).
When the Return Temperature > 80°C for 5s, the Slave board locks out (E 47).
When the Flue Gas Temperature > 80°C for 5s, the Slave board locks out (E48) and the fan operates for 10 minutes at maximum speed.
The Slave board can protect the main exchanger against the dangers of low water circulation, in three ways:
- 1 = by flow switch (water differential pressure switch)
- 2 = by controlling the difference between the flow and return temperature ∆T
- 3 = by flow switch and ∆T
The control on the T uses a parameter T_max (pre-set to 35°C) and limits the output of the burner as follows:
if T_max -5°C>∆T>T_max-10°C burner modulates
if T_max>∆T>T_max-5°C burner at minimum
if ∆_T>_T_max burner off
3.11.9 Mix valve management
The mixing valve is controlled by the following parameters:
- mix_valve_step_open_time (Par. 28): pre-set to 5s
- mix_valve_step_close_time (Par. 29): pre-set to 7s
- mix_valve_interval_time (Par. 30): pre-set to 5s
- mix_valve_p_hyst (Par. 31): pre-set to 2°C
- mix_valve_still_hyst (Par. 32) pre-set to 2°C
Before opening or closing, the valve waits the time set for Par. 30:
- it opens if T_flow_low < Setpoint_low - Par. 32
- it closes if T_flow_low > Setpoint_low + Par. 32
Within the interval (the valve remains in the current position):
- if T_ flow_low < Setpoint_low - Par. 31 it opens for a time equal to half of the value set for Par. 28.
- if T_ flow_low > Setpoint_low + Par. 31 it closes for a time equal to half of the value set for Par. 29
3.11.10 Gas type (fan speeds)
With the Parameter 36 (Gas_type; pre-set to 1; adjustable from 1 to 4) is possible to select the kind of gas used and the kind of installation. The Gas type selection automatically alters the
30
Page 37
BOILER FUNCTIONING
55
45
35
25
15
Manifold temperature
5
-5 05 10
Time [s]
Fig. 3.18
15 20
3
2
Opening
1
0
Closing
-1
-2
-3
-4
Closing – Opening [s]
20 25 30
Fig. 3.19
the Master board to all the linked Slave boards.
- 1 = NG with flues length < 15 m
Setpoint 40˚C
35
40 45 50 55 60
Mix Flow Temperature
Default
Par. 31 = 10
- 2 = NG with flues length > 15 m parameters referring to the fan speeds in the different burner management phases. The modified parameters are sent from
- 3 = LPG with flues length < 15 m
- 4 = LPG with flues length > 15 m
3.11.11Burner ignition procedure
Status OFF
Pump
ON
Relay
Safety
OFF
Safety
Relay
Flow
switch
Closed
Pre-purge
Ignition
Phase 0
Ignition
Pre-spark
Spark
Phase 2
Burner
Time 0TC>80°C 10 s 10 s 5 s 24h max
Requested Power
0-------> 0
ON
5
4
Fan 00000
Pump 01101
6
Par. 86
Pre-purge
1111
Par. 85
Ignition
Par. 85
Ignition
Second request
Gas Valve 000000011
Spark 00000011
Ionisation 0000000
If the ignition procedure is started, it will be completed even if
mum of 7,5 Hz / 300 ms (25 rps
1
3
2
1
2
).
0
1
the heat request ceases meanwhile.
1. If the flame is detected at the end of the phase of pre-spark
the Slave boards generates a permanent lockout
2. If at the end of he safety time (5 s) no flame is detected, the
Slave board performs a post-ventilation to drain out all the unburnts. After that a new ignition attempt is started. After 3 ignition attempts failed the Salve board generates a per­manent lockout.
3. The spark is present for all the safety time diminished by 1
second.
4. The request power has to be updated by the Master board,
otherwise the Slave board turns off the burner.
5. The burner can work continuously for a maximum of 24
hours. After 24 h of constant working the burner is turned off and then switched on again.
6. If a flow switch is present (water differential pressure
switch) the board verifies the status of “closed contact”. In this status the Slave board verifies that the pressure switch is closed and if this doesn’t happen within 10 seconds, a lockout is generated. If the contact opens during the burner functioning, the burner is switched off and a new ignition
3.11.12 Factory settings
With the parameter 41 is possible to restore all the parameters (user and installer) to the factory pre-sets. When this RESET is performed the parameters 36, 42 and 43 remain unchanged.
This parameter is factory pre-set to 0.
3.12 ADDRESSES SETTINGS FOR
CASCADE CONNECTIONS
3.12.1 Master PCB data
The Master board is designed to be the control unit of 60 Slave boards.
Power supply 230Vac (-15% +10%), 50Hz
Functioning Temperature
Storing temperature -25 + 75°C
Relative humidity 93% a 25°C
Fuses 2×3,15A-T, 230V
0-60°C (peak temperature, not continuous)
attempt is started.
7. During the phases of pre-purge and functioning the fan ac-
celeration is checked. The acceleration is adjustable from the minimum of 0,5 Hz / 300 ms (1,67 rps
2
) to the maxi-
31
Page 38
BOILER FUNCTIONING
3.12.2 Slave PCBs data
The Slave board is designed to be an independent unit.
Power supply 230Vac (-15% +10%), 50Hz
Functioning Temperature
0-60°C (peak temperature, not continuous)
Storing temperature -25 + 75°C
Relative humidity 93% a 25°C
Fuses 1x3,15A T, 230V
Safety time 5,0s
Ignition attempts 3
Detection electrode
Separate or combined with ignition
Minimum ionisation current 1,2 µA
Detection beginning ionisa­tion current
1,3 µA
Maximum ionisation current 4,9 µA
ATTENTION - The boards are sensitive to the Live and Neu­tral inversion. The inversion between Live and Neutral causes a lockout.
All the Slave boards are complete with lockout functions and are designed with all the safety functions necessary for one burner direct control.
3.12.3 Slave PCB user interface
- The green LED flashes with a frequency of 1 Hz if no heat request is present.
- The green LED flashes with a frequency of 2 Hz during the ignition cycle.
- The green LED is lit solid if the flame is present.
- The red LED is not lit if no lockouts are present.
- The red LED flashes with a frequency of 2 Hz if a volatile lockout is present.
- The red LED is lit solid if a permanent lockout is present.
3.12.4 Slave PCBs access
The micro-switches on the slave boards are factory-set so as to interface a master boiler (50 M - 100 M - 100 M DEP) to a slave boiler (100 S or 100 S DEP). If further slave boilers need to be connected, only the micro-switches on these boilers will need to be reset.
- Move the main system switch to “OFF”.
- Access the slave boards inside the boiler control panel (see the steps described with P
ROCEDURE 5.6.2, PAGE 38).
- Follow the address setting procedure described below, and then connect the boilers using the special bus cable (see AP-
PENDIX H -
PAG.82).
3.12.5 Addresses settings
Each slave board (one for each heat generator) must be config­ured so as to be recognised in the right sequence by the master board. The slave generators should first of all be divided into blocks; the system can manage up to 15 blocks of four slave generators each. For example, if 5 slave generators are con­nected to a master, there are two blocks: the first made up of four slave generators and the second of one slave generator. Consequently, the addresses should be set as follows:
- Identify the block of four that the slave generator being con­figured belongs to (for example block 1, 2, ... , up to block
15).
- Identify the position of the slave generator inside each block (e.g. position 1, 2, 3 or 4).
SLAVE address
BLOCK address
SLAVE addresses table
Micro-switches SLAVE
OFF OFF 1 OFF ON 2
ON OFF 3 ON ON 4
12
OFF
1
234
OFF
address
21
ON
ON
J17
J10
BLOCKS addresses table
Micro-switches
1234
OFF OFF OFF OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF ON ON OFF ON OFF OFF OFF ON OFF ON OFF ON ON OFF OFF ON ON ON
ON OFF OFF OFF ON OFF OFF ON ON OFF ON OFF
OFF OFF ON ON
ON ON OFF OFF ON ON OFF ON ON ON ON OFF ON ON ON ON
Slave PCB
Main
BLOCKS
Emergency
st
block
1
nd
2
block
rd
3
block
th
4
block
th
5
block
th
6
block
th
7
block
th
8
block
th
9
block
th
10
block
th
11
block
th
12
block
th
13
block
th
14
block
th
15
block
32
Page 39
BOILER FUNCTIONING
Example configuration of a set of 7 burners in cascade
If installing a set of seven slave generators, there are two blocks: the first made up of four generators, and the second of three. Therefore, two blocks need to be configured, with address 1 and 2 respectively, and the generators belonging to the first block must have address 1, 2, 3 and 4, and those belonging to the second block address 1, 2 and 3.
1st Generator
nd
2
Generator
rd
Generator
3
SLAVE address
ON
BLOCK address
ON
1 2 1234
OFF
ON
OFF
ON
1 2 1234
OFF
ON
OFF
ON
1 2 1234
OFF
ON
OFF
ON
1st Block
th
Generator
4
st
Generator
1
nd
Generator
2
rd
Generator
3
1 2 1234
OFF
ON
OFF
ON
1 2 1234
OFF
ON
OFF
ON
1 2 1234
OFF
ON
OFF
ON
1 2 1234
OFF
OFF
nd
2
Block
33
Page 40
BOILER SHUTDOWN
4 BOILER SHUTDOWN
4.1 TEMPORARY SHUTDOWN
In the event of temporary absence over the weekend, short trips, etc. proceed as follows:
- Set the room thermostats to around 10°C.
- Set parameter 2 to “10” or alternatively set the storage heat­er thermostat to 10°C.
By leaving the power supply on, as signalled by the green LED flashing, and the fuel supply open the boiler is protected.
The electronic controller has a frost protection function that is also active in standby. The frost protection function has two levels:
- the first starts the pump
If the manifold temperature 5°C, or alternatively, when CH_type = 1 and the outdoor probe is connected.
If the outdoor temperature 3°C (Par. 35 = Frost_protection) the system pump and the pump in the high temperature circuit are activated.
- the second starts the pump and the burner
If after 10 minutes the temperature in the manifold 5°C, a burner is started at maximum power until the temperature in the manifold 20°C. If after 10 minutes the temperature in the manifold 5°C, but with CH_Type = 1 and the outdoor probe is connected, and the outdoor temperature 3°C, the pump continues op­erating until the outside temperature 3°C.
4.2 EXTENDED PERIODS SHUTDOWN
If the Power Plus boiler is not used for an extended period, the following operations must be performed:
- Move the main system switch and the main boiler switch (1
- F
IG. 4.1) to “OFF” and check that the green indicator light
(2 - F
IG. 4.1) turns off.
Fig. 4.1
- Close the fuel and water valves on the central heating sys­tem.
Fig. 4.2
In this case, the frost protection system is deacti-
vated. Empty the central heating and DHW system if there is the risk of freezing.
34
Page 41
5 MAINTENANCE
MAINTENANCE
To grant that all the characteristics and features of the product can last in the time and to comply with the law prescriptions, is necessary for the product to have systematic checks per­formed at regular intervals.
The frequency of the checks depends on the peculiar installa­tion and use conditions, however a yearly check performed by Service Centres authorised personnel is necessary
In case of maintenance operations performed on structures in the proximity of the flue ducts or flue drain apparatuses and their accessories, switch off the boiler and, once the operations are finished, make them and the boiler verified by qualified personnel.
IMPORTANT: Before any maintenance or cleaning opera­tion of the boiler, disconnect the mains supply by moving the main system switch and the main boiler switch to “OFF” and close the fuel valve on the boiler.
5.1 ORDINARY MAINTENANCE
The following operations have to be intended as ordinary:
- removal of eventual oxide traces on the burner;
- removal of eventual deposits from the exchanger;
- verification and general cleaning of the flue ducts;
- boiler external appearance check;
- check of ignition and shutdown of the boiler, both in CH and DHW;
- check that all the joints and pipes are sound, both on the wa­ter and gas circuits;
- check of the gas consumption at the maximum and mini­mum power;
- check of the flame ignition-detection electrode position;
- gas absence safety check.
Never clean the boiler or parts belonging to it with flammable substances (i.e. petrol, alcohol, etc.).
Never clean the casing, painted or plastic parts with paint thin­ner or solvent.
The casing should be cleaned with soap water only.
5.2 EXTRAORDINARY MAINTENANCE
These are the interventions necessary to restore the boiler functioning according to what the project and standards pre­scribe, for instance, consequent to an accidental fault.
They have to be intended as:
- substitution
- repairing
- components review.
All this by means of special tools and instruments.
Before performing any action:
- Disconnect the mains supply by moving the main system switch and the main boiler switch to “OFF” (F
ON
OFF
Fig. 5.1
- Close the main fuel valve on the system (F
Fig. 5.2
IG. 5.1).
IG. 5.2).
35
Page 42
MAINTENANCE
5.3 PERIODICAL PROGRAMMED MAINTENANCE TABLE
OPERATION TO BE DONE AT THE END OF THE
COMBUSTION ANALYSIS - SECT. 3.6, PAGE 23
AIR INTAKE AND FLUE DRAIN DUCT AND TERMINALS CHECK -
S
ECT.7.9, PAGE 63
FLAME IGNITION ELECTRODE CHECK AND CLEANING - SECT. 5.6.4,
PAGE 40
VENTURI CHECK AND CLEANING - SECT. 5.6.5, PAGE 41
FAN CHECK AND CLEANING - SECT. 5.6.6, PAGE 42
BURNER CHECK AND CLEANING - SECT. 5.6.7, PAGE 43
CONDENSING EXCHANGER CHECK AND CLEANING - SECT. 5.6.7, PAGE 43
SIPHON CHECK AND CLEANING - SECT. 5.6.8, PAGE 44
VERIFICATION OF SAFETIES: LOCKOUT, MODULATION OPERATORS CLOSING AFTER FLAME SHUTDOWN
ADJUSTMENTS AND SETTINGS CHECK - SECT. 3.6, PAGE 23 - SECT. 3.8,
PAGE 25
st
1
YEAR
nd
2
YEAR
rd
3
YEAR
th
4
YEAR
✘✘ ✘✘✘✘ ✘✘✘✘ ✘✘✘✘
✘✘✘✘ ✘✘✘✘ ✘✘✘✘ ✘✘✘✘
✘✘✘✘ ✘✘✘✘
5.4 NECESSARY TOOLS FOR MAINTENANCE
- Magnetic screwdriver PH1
- Magnetic screwdriver PH2
- Broad tipped screwdriver
- Socket wrench 7mm – 10mm
- Monkey wrench 5mm – 7mm – 10mm – 11mm – 13mm – 14mm – 15mm – 17mm – 23mm – 24mm – 27mm – 29mm – 36mm
-Scissors
5.5 SAFETY RULES
The installation and maintenance of the boiler should be per­formed only by qualified personnel according to the laws and practice rules of the Country where the boiler is sold.
Before every operation:
- turn off the boiler and system main switches;
- close the gas main valve;
- if necessary close the domestic water general valve and the valves on the central heating circuit. For the eventual drain of the central heating and/or domestic hot water circuit, refer to S
PAGE 62.
ECT.7.8,
- Lubricant type Molikote 111
- Cleaning cloth
-Brush
- Thermal conductive paste
- Needlenose pliers
-Pliers
- Drill
5.6 COMPONENTS ACCESSIBILITY
All the operations necessary to access to and remove the main components of the boiler are reported in details in this chapter.
If not explicitly indicated the procedures are valid for all the versions.
36
Page 43
5.6.1 Casing disassembly
OPERATIONS SEQUENCE COMPONENT NECESSARY TOOLS
1 Turn off the thermal unit main power supply and close the gas tap
1.1 Unscrew the screws (1) fastening the casing (2) N. 2 screws Magnetic screwdriver
1.2 Pull the base of the casing outwards and then upwards to release it from the frame and then remove it Casing No tools - by hand
For the re-assembly operations proceed in the reverse way
MAINTENANCE
2
1
37
Page 44
MAINTENANCE
5.6.2 Control panel disassembly
OPERATIONS SEQUENCE COMPONENT NECESSARY TOOLS
2 Turn off the thermal unit main power supply and close the gas tap
2.1 Remove the casing. Refer to
P
ROCEDURE 5.6.1, PAGE 37
2.2 Turn the control panel (1) by 90° and take out the four screws (2) so as to remove the rear cover N. 4 screws Magnetic screwdriver
For the re-assembly operations proceed in the reverse way
38
1
2
Page 45
5.6.3 PCBs disassembly
OPERATIONS SEQUENCE COMPONENT NECESSARY TOOLS
3 Turn off the thermal unit main power supply and close the gas tap
3.1 Remove the casing. Refer to
P
ROCEDURE 5.6.1, PAGE 37
3.2 Disassemble the control panel. Refer to P
ROCEDURE 5.6.2, PAGE 38
3.3 Take out the screws (1) and the cover of the Master PCB N. 2 screws Magnetic screwdriver
3.4 Repeat the same procedure to remove the cover (2) of the first Slave PCB and of the eventual (3) second Slave PCB N. 2 screws + N. 2 screws Screwdriver
3.5 Remove the wiring harnesses connec­tors (4) from the PCBs and remove the fastening screws to take them out Screws Screwdriver
3.6 The PCBs present inside the control panel are:
- Master PCB (5) for the models Pow-
er Plus 50 M – 100 M – 100 M DEP
- First Slave PCB (6)
- Second Slave PCB (7) for the models
Power Plus 100 M DEP – 100 S – 100 S DEP
MAINTENANCE
For the re-assembly operations proceed in the reverse way
2
3
1
5
7
4
6
4
4
39
Page 46
MAINTENANCE
5.6.4 Ignition electrode disassembly
OPERATIONS SEQUENCE COMPONENT NECESSARY TOOLS
4 Turn off the thermal unit main power supply and close the gas tap
4.1 Remove the casing. Refer to
P
ROCEDURE 5.6.1, PAGE 37
4.2 Remove the electrode protective cap (1) Cap No tools - by hand
4.3 Take out the screws (2) fastening the electrode and remove it N. 2 screws Screwdriver
For the re-assembly operations proceed in the reverse way
2
1
40
Page 47
5.6.5 Venturi disassembly
OPERATIONS SEQUENCE COMPONENT NECESSARY TOOLS
5 Turn off the thermal unit main power supply and close the gas tap
5.1 Remove the casing. Refer to
P
ROCEDURE 5.6.1, PAGE 37
5.2 Take out the screws (1) fastening the venturi to the fan N. 2 screws Screwdriver
5.3 Take out the screws (2) fastening the venturi to the gas valve N. 3 screws Screwdriver
For the re-assembly operations proceed in the reverse way
MAINTENANCE
1
2
41
Page 48
MAINTENANCE
5.6.6 Fan disassembly
OPERATIONS SEQUENCE COMPONENT NECESSARY TOOLS
6 Turn off the thermal unit main power supply and close the gas tap
6.1 Remove the casing. Refer to
P
ROCEDURE 5.6.1, PAGE 37
6.2 Disconnect the wiring harness (1) from the fan (2) Wiring harness
6.3 Undo the four bolts (3) fastening the fan group (4) to the exchanger N. 4 bolts Socket wrench 8 mm
6.4 Take out the two screws (5) fastening the fan (2) to the air conveyor (6) N. 2 screws Screwdriver
6.5 Remove the fan (2) Fan
For the re-assembly operations proceed in the reverse way
2
1
6
5
4
3
42
Page 49
MAINTENANCE
5.6.7 Burner disassembly and combustion chamber cleaninge
OPERATIONS SEQUENCE COMPONENT NECESSARY TOOLS
7 Turn off the thermal unit main power supply and close the gas tap
7.1 Remove the casing. Refer to
P
ROCEDURE 5.6.1, PAGE 37
7.2 Remove the fan. Refer to
P
ROCEDURE 5.6.6, PAGE 42
7.3 Remove the gasket (1) and extract the burner (2) Gasket + Burner No tools - by hand
7.4 Once the burner has been removed, is possible to access to the combustion chamber (3): to clean it use a bristle brush, aspire away the deposits and rinse with water.
For the re-assembly operations proceed in the reverse way
1
2
3
43
Page 50
MAINTENANCE
5.6.8 Siphon disassembly
OPERATIONS SEQUENCE COMPONENT NECESSARY TOOLS
8 Turn off the thermal unit main power supply and close the gas tap
8.1 Remove the casing. Refer to
P
ROCEDURE 5.6.1, PAGE 37
8.2 Remove the clamp (1) and detach the condense drain corrugated hose (2) Clamp + Corrugated hose Pliers
8.3 Extract the siphon and take it apart removing the two screw taps (3) Screw taps No tools - by hand
8.4 Remove the float (4) and clean all the components Float No tools - by hand
For the re-assembly operations proceed in the reverse way
3
4
1
2
3
44
Page 51
5.6.9 NTC probes disassembly
OPERATIONS SEQUENCE COMPONENT NECESSARY TOOLS
9 Turn off the thermal unit main power supply and close the gas tap
9.1 Remove the casing. Refer to
P
ROCEDURE 5.6.1, PAGE 37
9.2 Unscrew the flow NTC probe (1) Flow NTC probe Wrench 15 mm
9.3 Unscrew the return NTC probe (2) eturn NTC probe Wrench 15 mm
For the re-assembly operations proceed in the reverse way
MAINTENANCE
Exchanger
seal
1
If slackened
can flood the
combustion
chamber
Exchanger
seal
2
45
Page 52
MAINTENANCE
5.6.10 Safety thermostat disassembly
OPERATIONS SEQUENCE COMPONENT NECESSARY TOOLS
10 Turn off the thermal unit main power supply and close the gas tap
10.1 Remove the casing. Refer to
P
ROCEDURE 5.6.1, PAGE 37
10.2 Remove the fast-on connector (1) Fast-on connector No tools - by hand
10.3 Remove the two screws (1) fastening the safety thermostat Safety thermostat Screwdriver
For the re-assembly operations proceed in the reverse way
46
1
Page 53
5.6.11 Flue probe disassembly
OPERATIONS SEQUENCE COMPONENT NECESSARY TOOLS
11 Turn off the thermal unit main power supply and close the gas tap
11.1 Remove the casing. Refer to
P
ROCEDURE 5.6.1, PAGE 37
11.2 Remove the electrical connections from the flue probe N. 2 flue probe fast-on No tools - by hand
11.3 Remove the flue probe (1) Flue probe Wrench 13 mm
For the re-assembly operations proceed in the reverse way
MAINTENANCE
1
47
Page 54
MAINTENANCE
5.6.12 Gas valve disassembly
OPERATIONS SEQUENCE COMPONENT NECESSARY TOOLS
12 Turn off the thermal unit main power supply and close the gas tap
12.1 Remove the casing. Refer to
P
ROCEDURE 5.6.1, PAGE 37
12.2 Remove the screws (1) fastening the gas valve to the gas pipe N. 4 screws Screwdriver
12.3 Remove the screws (2) fastening the gas valve to the venturi N. 3 screws Screwdriver
For the re-assembly operations proceed in the reverse way
48
2
1
Page 55
5.6.13 Water differential pressure switch disassembly
OPERATIONS SEQUENCE COMPONENT NECESSARY TOOLS
13 Turn off the thermal unit main power supply and close the gas tap
13.1 Remove the casing. Refer to
P
ROCEDURE 5.6.1, PAGE 37
13.2 Undo the nuts (1) of the connection pipe N. 2 nuts Wrench 17 mm
13.3 Remove the water differential pressure switch (2) Water differential pressure switch
For the re-assembly operations proceed in the reverse way
MAINTENANCE
2
1
49
Page 56
FAULT FINDING
6 FAULT FINDING
6.1 ERROR MODE
The display starts flashing when there is a fault on any of the heating units. Proceed as follows to identify the faults.
Procedure
1 The display starts flashing to signal one or more errors.
Press “+”: the display will show the address of the first unit, alternating with the first error code. Press “+” again to visualise the remaining errors of this unit. The following units faults will be displayed in
2
sequence, by pressing “+”. Pressing “-” the errors will be displayed in reverse order (E.g. unit 2 error code E02). If the errors come from the Master board, these are displayed as errors on unit 00 (U 00 + error code).
3 Press “Set/Esc” to exit Error mode and return to Display mode.
Display
6.2 PERMANENT LOCKOUT
In case of burners in permanent lockout, it is necessary to press “RESET” to reset them. If the button “RESET” is pressed while in Readout mode all the Slave units will be reset. If the button “RESET” is pressed while visualising the error that caused the permanent lockout, only the thermal units affected
by the lockout will be reset.
6.3 LOCKOUTS CODES
6.3.1 Master PCB lockouts
The following tables provide a description of the errors that may occur on the Master board. The errors can be divided into two groups:
- Type A errors, which can only be deactivated by pressing “RESET” (see ref. 3, S
- Type E errors, which are deactivated when their causes are no longer present.
Permanent errors, TYPE A
No.
A 16 EEPROM content not correct Replace the Master board
A 18 EEPROM not recognised by the processor Replace the Master board
Errors deactivated automatically, TYPE E
The following errors may occur and can be deactivated automatically. If any one of these errors occurs, the red LED comes on (see ref. 4, S
No.
E 25 EEPROM cannot be read Replace the Master board
E 23 Temperature reading out of range Replace the Master board
E 24 Temperature reading out of range Replace the Master board
E 25 Temperature reading out of range Replace the Master board
E 26 Temperature reading out of range Replace the Master board
E 32 NO SLAVES CONNECTED
Cause Checks and solutions
ECT. 1.6, PAGE 7).
Cause Checks and solutions
Check that the double pole switches on the individual units are in the “ON” position
Check the Slaves electrical connections
ECT. 1.6, PAGE 7).
50
Page 57
FAULT FINDING
No.
Cause Checks and solutions
E 34 50 Hz ERROR The mains frequency is not 50 Hz
E 02
E 04
E 18
E 20
NTC1 open (NTC1 = Flow sensor)
NTC3 open (NTC3: tank sensor)
NTC1 short circuit (NTC1 = Flow sensor)
NTC3 short circuit (NTC3: tank sensor)
Flow sensor in the primary circuit not connected or interrupted
DHW sensor not connected or interrupted
Flow sensor in the primary circuit short-circuited
DHW sensor short-circuited
6.3.2 Slave PCB lockouts
List of slave errors: manual reset
If slave errors with manual reset occur, the Slave reset button can be used (see ref. 13, S
No.
Cause Checks and solutions
Check that the gas valve is open
A 01 5 failed ignition attempts
Make sure that the spark comes between the two ignition electrodes. Check the ignition cable Replace the electronic board (Slave)
ECT. 1.6, PAGE 7).
A 02 Too many failed ignition attempts
A 04 Gas valve realy open / Limit thermostat intervention Replace the Slave board
A 05
Gas valve relay doesn’t open or Live and neutral twisted in the internal harness
Replace the Slave board
A 06 Safety relay doesn’t close Replace the Slave board
A 07 Safety relay doesn’t open Replace the Slave board
A 08 Safety relay opened instead of closed Replace the Slave board
A 09 RAM error Replace the Slave board
A 10 EEPROM error Replace the Slave board
A 11 Register error Press the reset button
A 12 EEPROM write error Replace the Slave board
A 16 Safety relay closed instead of opened Replace the Slave board
A 17 Flow NTC error over limit temperature
A 18 Return NTC error over limit temperature
A 19
Flue NTC error over limit temperature (with this error the fan runs at maximum speed)
A 20 The flame goes out too late after the gas valve closes
Check that on the water circuit of the single unit there is the correct flow rate (2 m
Check that on the water circuit of the single unit there is the correct flow rate (2 m
Check that on the water circuit of the single unit there is the correct flow rate (2 m
Clean the exchanger on the water and flue sides
Check the correct operation of the gas valve Replace the gas valve
The measured fan speed varies too much with the read speed
A 24 Fan error
Check the fan Check the fan electrical connections Replace the fan
3
/h for each unit)
3
/h for each unit)
3
/h for each unit)
51
Page 58
FAULT FINDING
List of slave errors: automatic reset
No.
Cause Checks and solutions
E 33 Live and neutral reversed Restore the correct live-neutral connection
The button has been pressed more than 7 times in 30
E 34 Reset button error
min.; wait for the error to disappear If after a maximum of 40 min. the error is still present,
replace the Slave board
E 35
Water differential pressure switch error (contact opened)
Check that the flow-rate in each unit’s water circuit is correct (2 m
Replace the water pressure switch (set 500 l/h)
3
/h for each unit)
Check that no air is in the boiler
E 36 EEPROM reading error Replace the Slave board
E 37 Flame detection error Clean the electrodes; replace the electrode
E 38 Flue gas sensor short circuited
E 39 Flue gas sensor open circuit
Check the flue gas sensor connector; replace the flue gas sensor
Check the flue gas sensor connector; replace the flue gas sensor
E 40 The frequency is not 50 Hz Check the frequency of the mains power supply
E 41 Communication error Replace the Slave board
E 42 Flow sensor short circuited
E 43 Flow sensor open circuit
Check the flow sensor connector. Replace the flow sen­sor
Check the flow sensor connector. Replace the flow sen­sor
E 44 Return sensor short circuited
E 45 Return sensor open circuit
E 46 Flow sensor exceeded the limit temperature
E 47 Return sensor exceeded the limit temperature
E 48
Flue gas sensor exceeded limit temperature (with this fault the fan runs at maximum speed)
Check the return sensor connector. Replace the return sensor
Check the return sensor connector. Replace the return sensor
Check that the flow-rate in each unit’s water circuit is correct (2 m
Check that the flow-rate in each unit’s water circuit is correct (2 m
Check that the flow-rate in each unit’s water circuit is correct (2 m
3
/h for each unit)
3
/h for each unit)
3
/h for each unit)
Clean the heat exchanger again on the water side and flue gas side
6.4 EVENTUAL ANOMALIES AND REMEDIES
PROBLEM CAUSE SOLUTION
Smell of gas Gas supply circuit
Smell of unburned gases Flue gas circuit
Check the tightness of the joints and that the pressure test points are closed
Check:
- The tightness of the joints
- The absence of obstructions
- The quality of combustion
Condense on the flue drain pipes Low temperature of the flue
52
Check the combustion settings and the fuel flow rate
Page 59
PROBLEM CAUSE SOLUTION
Burner gas pressure Check adjustment
Diaphragm fitted Check diameter
FAULT FINDING
Irregular combustion
Delays in ignition with pulsating opera­tion of the burner
The thermal group becomes dirty in a short time
The burner does not start when receiving the signal from the boiler controller
The boiler doesn’t start
The boiler does not reach the operating temperature
The boiler lockouts for the thermal safety
The heat generator reaches the tempera­ture but the central heating system is cold
Cleanliness of the burner and exchanger Check conditions
Exchanger openings blocked Check the openings are clean
Fan faulty Check operation
Burner gas pressure Check adjustment
Ignition electrode Check positioning and condition
Combustion
Gas valve
No power supply (the display doesn’t show any symbol)
Generator body dirty Clean combustion chamber
Insufficient burner flow-rate Check burner adjustment
Boiler controller
No water
Thermal group setting
Air in the system Vent the system
Pump fault
Check flame colour
Check combustion adjustments
Check that 230 Vac is present at the ter­minals on the gas valve; check wiring and connections
Check:
- electrical connections
-fuse
Check correct operation
Check set temperature
Check correct operation
Check set temperature
Check electrical wiring
Check position of the probe sensors
Check vent valve
Check pressure in central heating circuit
Unblock the pump
Replace the pump
Check the pump electrical connections
Unblock the pump
The pump doesn’t start Pump fault
System expansion vessel Check calibration or efficiency
Frequent intervention of the system safe­ty valve
Pressure in heating system circuit
System safety valve Check efficiency
Replace the pump
Check the pump electrical connections
Check charge pressure
Check pressure reducer
53
Page 60
INSTALLATION
7INSTALLATION
7.1 HANDLING
Once having removed the packaging, the POWER PLUS Boil­er is handled manually by tilting and lifting it, grabbing the points shown in the figure.
Do not grab the casing of the boiler, but rather the
“solid” parts such as the boiler bed and the rear structure.
Adopt suitable safety and protection measures
( The packaging material must not be dispersed in the
environment or left within the reach of children as it is a potential source of hazard. It must be disposed of according to the legislation in force.
Fig. 7.1
7.2 BOILER INSTALLATION ROOM
The POWER PLUS boiler must be installed in a dedicated boiler room, with adequately sized vents, in compliance with applicable Laws and Technical Rules. If comburent air is drawn from outside the boiler room (using accessories code 1102439 and 1102449), the Power Plus boiler functions as a sealed (type C) appliance.
Provide enough clearance to access the safety and
control devices and to carry out the servicing opera­tions.
Check that the degree of electrical protection of the
boiler is suitable for the characteristics of the room where the appliance is installed.
If the boilers operate on gas fuel with a higher spe-
cific weight than air, the electrical parts must be located at least 500 mm from the floor.
( The boilers cannot be installed outside as they are not
designed for outdoor operation.
7.3 INSTALLATION ON OLD SYSTEMS OR SYSTEMS TO BE UPGRADED
When the Power Plus Boilers are to be installed in old systems or systems to be upgraded, check that:
- The flue is suitable for the temperature of the products of combustion with condensing operation, calculated and man­ufactured according to the standards, as straight as possible, airtight, insulated and not blocked or choked. It must also be fitted with suitable condensate collection and drain systems.
- The electrical system has been installed in compliance with the relevant standards by qualified personnel.
- The fuel supply line and any cylinders or tanks (LPG) are made and installed according to the relevant standards.
- The expansion vessel can completely absorb the expansion of the fluid contained in the system.
- The flow-rate and the discharge head of the pump are suit­able for the characteristics of the system.
- The system is flushed, clean from mud and scale, treated, vented and pressure tested. To clean the system see
S
ECT. 7.5, PAGE 55.
- The condense drain system (drain trap) is connected and runs into the sewerage drain or a neutraliser, where required by the legislation in force.
- A treatment system is available for special supply/top-up water requirements (for the reference values, see the table).
SUPPLY WATER VALUES
pH 6-8
Electrical Conductivity less than 200 mV/cm (25°C)
Chloride ions less than 50 ppm
Sulphuric acid ions less than 50 ppm
Total iron less than 0,3 ppm
Alkalinity M less than 50 ppm
Total hardness less than 20°F
Sulphur ions none
Ammonia ions none
Silica ions less than 30 ppm
The manufacturer is not liable for any damage
caused by the incorrect layout or installation of the flue system.
The flues for condensing boilers are made from spe-
cial material and differ from those used for standard boilers.
7.4 FITTING THE BOILER
The Beretta POWER PLUS Boiler must be secured to a solid brick wall using the bracket (1 - F
- Position the bracket (1 - F around 200 cm from the ground, using a spirit level to make sure that the holes are perfectly horizontal.
- Mark the fastening holes on the wall.
- Drill the holes and insert the expansion plugs (2 - F
- Fasten the bracket to the wall using the screws (3 - F
- Hook the boiler to the bracket.
The height of the boiler should chosen so as to sim-
plify the dismantling and servicing operations.
IG. 7.2). For the installation:
IG. 7.2) on the wall at a height of
IG. 7.2).
IG. 7.2).
54
Page 61
INSTALLATION
The POWER PLUS Boiler is not designed for out-
door installation.
1
3
2
Cleaning the system
This preliminary operation is required when installing the heat generator in pre-existing systems, and is also recommended in new systems, so as to remove any scale, impurities, processing residues etc. Power Flushing is recommended for system cleaning.
To clean the system, if the old heat generator is still installed in the system, proceed as follows:
- Add scale-remover into the system water circuit.
- Operate the system with the heat generator on for around 7 days.
- Empty the dirty water from the system and flush with clean water. Repeat the operation until the system is clean.
If the old heat generator is not installed or not available, use a pump to circulate the water with the additive in the system for around 10 days, and carry out flushing as described in the pre­vious point. At the end of the cleaning operations, before in­stalling the boiler, an additive should be introduced into the water circuit that provides protection against corrosion and fouling.
For additional information on the kind and use
instructions of the additives, refer to the Technical Assistance Service.
Fig. 7.2
7.5 HYDRAULIC CONNECTIONS
The POWER PLUS Boilers are designed and built to be in­stalled in central heating and domestic hot water systems. The characteristics of the water fittings are as follows (F
- MI - Central heating flow outlet 1" M
- RI - Central heating return inlet 1" M
- Gas - Gas supply 3/4" M.
1
2
MI RI GASS MI RI GAS
Fig. 7.3
Condense collection
Identify the condense draina (S - F tom of the boiler and then:
- remove the ring nut/nuts (1 - F
- pass the hose (2 - F ring nut on the outside.
Pipe the condense into the sewerage drain or a neutraliser, where required and in-accordance with any legislation in force.
The manufacturer is not liable for any damage
caused by the failure to install the condensate drain pipe.
The condense drain pipe must be watertight.
IG. 7.3) through the hole and replace the
IG. 7.3) located at the bot-
IG. 7.3);
IG. 7.3):
7.5.1 Hydraulic kits
To ease the construction of the water circuit, two accessory kits are available, featuring water and gas headers (support brackets included in the kit for installations above 100kW).
Water connection kit for installations up to 100 kW (F
7.4)
- 1 gas manifold, Ø45 mm
- 1 central heating flow manifold, Ø45 mm, with pocket for the flow probe
- 1 central heating return manifold, Ø45 mm
- 2" female fittings
- Gas (3/4") and water (1") valves
Water connection kit for installations over 100 kW (F
7.5)
- 1 gas manifold, Ø 3"
- 1 insulated central heating flow manifold, Ø 3" with pocket for the flow probes
- 1 insulated central heating return manifold, Ø 3"
- DN 80 - PN 6 flanged pipes
- manifolds brackets
- Gas (3/4") and water (1") valves
Identify the unit that is closest to the central heating
flow outlet as the Master boiler, so as to minimise the length of the cables to the pumps, the outlet probe and any storage heater probe.
The flwo probe should be fitted in the socket nearest
to the central heating flow outlet, in the direction of water flow.
Injection pump kit (F
-N° 1 Pump
- L-Shaped valve
- Non-return valve
IG. 7.6)
IG.
IG.
55
Page 62
INSTALLATION
Water connection kit for installations up to 100 kW +
Injection pumps kit (2 kits)
250250 200
700
300
Ground
Hydraulic kit for installations up to 100 kW
Injection pumps (2 kits)
REMARK: The hydraulic kit DOESN’T include
the injection pump kit
Fig. 7.4
Water connection kit for installations over 100 kW +
Injection pumps kit (4 kits)
250250 300
1485
300
Ground
Water connection kit for installations over 100 kW
Injection pumps (4 kits)
REMARK: The hydraulic kit DOESNT include
the injection pump kit
1
1. Gasket 1" (3 pcs.)
2
2. Return pipe (1 pcs.)
3. Brass joint 1" M-M (1 pcs.)
1
4. Non-return valve (1 pcs.)
3 4
5. Pump joint 1"F-2"F (1 pcs.)
5 6
6. Gasket 2" (2 pcs.)
7. Pump (separate box in the kit) (1
7
6 5
8
9
pcs.)
8. Metallic extension 1" (1 pcs.)
9. Right angle valve 1" M-M (1 pcs.)
1
Fig. 7.6
ISPESL kit for installations up to 100 kW (with gas inter­ception valve) (F
IG. 7.7)
- Gas interception valve Ø 1”
- Tap with crumpled pipe for pressure gauge Ø 3/8”
- Pressure gauge with scale 10 bar
- Horizontal immersion thermometer with scale 120 °C
- Lockout thermostat 1÷5 bar
- Reference thermometer pocket Ø 10 mm
- System flow pipes Ø 45 mm
- System return pipes Ø 45 mm
- Automatic Air Vent valve Ø 3/8”
- System drain tap with pipe fitting Ø 12 mm
Il kit ISPESL comprende il separatore idraulico; è quindi con­sigliabile rivolgersi ad un progettista per valutarne l’effettiva compatibilità con l’impianto.
The ISPESL kit includes the hydraulic separator; it is conse­quently suggested to ask advice to a designer to evaluate its ef­fective compatibility with the system.
The POWER PLUS thermal groups, when fitted together with the hydraulic kit, are validated by ISPESL. In this kind of in­stallation the fitting of a further safety valve by the installer is not necessary (a copy of the ISPESL certification can be re­quested to Beretta Boilers).
The ISPESL kit is provided disassembled, with all the hydrau­lic features and gaskets represented in the picture.
The kit is reversible, i.e. it can be installed on the right or left hand side, the important thing is to comply with the connec­tions proper way (collector always with the red band on the top) in order that the connections on the boiler side are higher than the ones on the system side.
The hydraulic separator is designed with refer to the maximum flow rate suggested at the mouth (11,6 m
3
/h). The chosen val­ue has to be considered as the sum of the flow rates on both the circuits of high and low temperature.
The maximum flow rate is the sum of the flow rates circulating in the connections M and R of the hydraulic separator second­ary. In the case that only one of the two connections M and R (for instance for high temperature) is used, the value cannot be higher than the given maximum flow rate.
Fig. 7.5
56
ISPESL kit for installations up to 100 kW (F
IG. 7.8)
The kit has been designed to be coupled to a cascade of con-
Page 63
Ground
250250 200
300
6
4
400
1
700
ISPESL kit up to 100kW
Hydraulic kit for installations up to 100kW
Injection punps (2 kits)
Back side connection for
the expansion vessel
(vessel not included in the kit)
3
2
Øe 120
5
10
Øi 80
Separator
sect
9
7
110110
190
8
Ground
250
390
1. Gas interception valve Ø 1"
2. Tap with crumpled pipe for pres­sure gauge Ø 3/8"
3. Pressure gauge with scale 10 bar
4. Horizontal immersion thermome­ter with scale 120°C
5. Lockout thermostat 1÷5 bar
6. Reference thermometer pocket Ø
600
10 mm
7. System flow pipes Ø 45 mm
8. System return pipes Ø 4 5mm
9. Automatic Air Vent valve Ø 3/8"
10. System drain tap with pipe fitting Ø 12 mm
INSTALLATION
Fig. 7.7
densing thermal units POWER PLUS up to a power of 200 kW (cod. 1102409). The kit can be indifferently fitted on the right or left hand side of the cascade of POWER PLUS thermal modules. It is composed of:
- Hydraulic separator with flows balance sect, with bracket and fixing hooks;
- Connecting joint of the flow collector complete with all the ISPESL features and with the expansion vessel connection (vessel not provided);
- Connecting joint of the return collector;
- Gas manifold.
The boilers installed in cascade are validated by the ISPESL institute and all the parts contained in the kit are designed and sized according to the rules of the RACCOLTA R and the spe­cific characteristics of the POWER PLUS thermal units.
The hydraulic separator is designed with refer to the maximum flow rate suggested at the mouth (11,6 m
3
/h). The chosen val­ue has to be considered as the sum of the flow rates on both the circuits of high and low temperature.
The maximum flow rate is the sum of the flow rates circulating in the connections M and R of the hydraulic separator second­ary. In the case that only one of the two connections M and R (for instance for high temperature) is used, the value cannot be higher than the given maximum flow rate.
ISPESL kit for installations up to 400 kW (F
IG. 7.9)
The kit has been designed to be coupled to a cascade of con­densing thermal units POWER PLUS up to a power of 400 kW and to the hydraulic connections kit code 1102409. The kit can be indifferently fitted on the right or left hand side of the cas­cade of POWER PLUS thermal modules. It is composed of:
- Hydraulic separator with flows balance sect, with bracket
and fixing hooks;
- Connecting joint of the flow collector complete with all the ISPESL features and with the expansion vessel connection (vessel not provided);
- Connecting joint of the return collector;
- Gas manifold.
The boilers installed in cascade are validated by the ISPESL institute and all the parts contained in the kit are designed and sized according to the rules of the RACCOLTA R and the spe­cific characteristics of the POWER PLUS thermal units.
The hydraulic separator is designed with refer to the maximum flow rate suggested at the mouth (28 m
3
/h). The chosen value has to be the largest between the one of the primary circuit and the one of the secondary circuit.
Installation instructions (F
IG. 7.10)
Once the hydraulic manifold (code 1102409) has been fas­tened, install the hanging brackets using the provided Torx screws with the provided plugs.
Fit all the accessories that come with the separator (2-3-4) and remove the adhesive protections from the flanges.
Connect to the flow and return collectors of the hydraulic man­ifold (code 1102409) the two joints DN80 PN16. Gasket and bolts are provided with the hydraulic kit (code 1102409).
Connect the separator and the flow joint with the gaskets (6) and bolts (5) provided with the kit.
Connect the flow connector (7) to the connector DN80 PN16 using gaskets (6) and bolts (5) provided with the kit.
Connect the return joint (16) to the fitting DN80 PN16 using gaskets (6) and bolts (5) provided with the kit.
Connect the 2” nipple (19) to the fuel interception valve (17). Connect then the group to the cascade gas collector (gasket and bolts provided with the collectors code 1102409).
Connect the accessories on the flow collector and fasten the
57
Page 64
INSTALLATION
HYDRAULIC SEPARATOR
Ground
2
3
6
7 1
5
1000
150
1485
A
Ø129
663,5
Ø139,7
A
25
Flanged connections DN 80 PN6
The hanging brackets are included in the kit
Ø139,7
Hydraulic separator
1. Separator
450300220140
2. Automatic Air Vent valve
3. Interception valve Ø 1"
4. Drain tap
5. Pipe connection
6. Hanging bracket
7. Supporting consoles (2 pcs.)
8. Fixing hooks (6 pcs.)
9. Flow and return connections fastening nuts (8 pcs.)
10. Gaskets 3" (2 pcs.)
Flow connection
11. Flow pipe 3"
12. ISPESL thermometer pocket (1/2")
13. Bend 1/4" M-F
14. ISPESL pressure gauge connection with tap 3/8"
15. Crumpled pipe for pressure gauge
16. Pressure gauge 3/8" (scale 10 bar)
17. Thermometer 1/2" (scale 120°C)
18. Reduced nipple 1/2"-1/4"
19. Pressure switch (connection 1/4", setting 3 bar)
20. Cap 3/8"
21. Cap 1/2"
22. Fuel Interception Valve pocket
4
FLOW CONNECTION AND ACCESSORIES
12
20
21
22
16
15
14
13
17
18
19
FLOW, RETURN AND
GAS CONNECTIONS
1011
10
23
25
Fig. 7.8
gas interception valve bulb in the designed pocket.
On the back side of the flow collector a threaded fitting 1/2” is foreseen for the thermometer connection (for installations on the left). In case the fitting is not used, close it using the thread­ed cap 1/2” (14) provided.
Return Connection
23. Return pipe 3"
Gas Manifold
24. Fuel Interception Valve (connection 2", setting 98°C)
25. Flanged connection
Low temperature kit installation (F
IG. 7.11)
The low temperature kit code 1102869 is made up of a probe and a mixing valve. Regulation characteristics and technical data:
- PN: 10 bar
58
Page 65
9 + 10 + 11
13 + 15
865
INSTALLATION
1095
Hydraulic separator
7
Flange
12
4
DN80 PN16
450
195
axle
Flange DN80 PN16
450250
1000
250 250 300
1
ACCESSORIES IN THE KIT
13
15
6
1485
HYDRAULIC
2
SEPARATOR
AND ACCESSORIES
3
6
6
4
17
12
8
14
The hydraulic separator hanging brackets are included in the kit
Hydraulic separator
1. Separator (DN80)
5
2. Automatic Air Vent valve (3/8")
3. Interception valve (3/8")
4. Drain tap (1-1/2")
5. Flow and Return connections
5
fastening nuts (40 pcs.)
6. Gaskets DN80 PN16 (4 pcs.)
FLOW, RETURN AND
GAS CONNECTIONS
19
13
7
11
10
16
Flange DN80 PN16
Flange DN80 PN16
145
Hydraulic kit axle
Gas V.I.C. connection (2 F)
Flow Manifold
7. Flow pipe (DN80 PN6/PN16)
8. ISPESL thermometer pocket (1/2")
9. ISPESL pressure gauge connection with tap (3/8")
10. Crumpled pipe for pressure gauge
11. Pressure gauge (3/8", scale 10 bar)
12. Thermometer (1/2", scale 120°C)
13. Pressure switch (1/4", setting 3 bar)
14. Cap 1/2"
15. Nipple 1/4" M
Return manifold
16. Return pipe (DN80 PN6/PN16)
Gas Manifold
17. Fuel interception valve (2", setting 98°C)
18. Flanged connection
19. Nipple 2" M
5
9
Fig. 7.9
- Nominal diameter: DN 32 mm, thread 1” 1/4”
- Flow coefficients: Kvs and Kvo [flow rate in m loss pv = 1 bar]: 100 kPa = 10 mCa = 1 bar
Kvs = 18 m
Kvo = 0,18 m
3
/h
3
/h
18
3
/h with head
F1 1/4": 3 points valve (opening live – closing live 230 Vac – neutral); Kvs 18m
3
/h (maximum flow rate with 1 bar pres­sure); Kvo 0.18. The pumps between the separator and the sys­tem are not provided with the kit. It is suggestible not to con­nect those pumps directly in the boiler, but instead using relays on the power circuits between them and the boiler.
59
Page 66
INSTALLATION
1050
665
195
100
105
N. 4 holes
Ø10 mm
Fig. 7.10
Condense drain kit
Relays on the power circuits (suggested)
Fig. 7.11
60
Connections 1-1/2"
Page 67
INSTALLATION
7.6 FUEL CONNECTIONS
The POWER PLUS Boiler must be connected to the natural gas or LPG supply in compliance with the relevant standards in force.
Before making the connections, check that:
- the type of gas is the same that the appliance is set for;
- the pipes are thoroughly clean;
- the gas supply pipes are the same size or larger than the fit­ting on the boiler (3/4"), with a pressure drop that is less than the pressure drop between the gas supply and the appliance.
When installation is completed, check that the joints are all tight, as required by the installation standards. A suitable filter should be installed on the gas line.
7.7 ELECTRICAL CONNECTIONS
The POWER PLUS 50 M - 100 M – 100 M DEP boilers leave the factory completely wired, with the power cable already connected, and only require the connection of the room ther­mostats, the outdoor probe and the pumps used, to the corre­sponding terminals. For the boilers 100 S and 100 S DEP the Bus cable connection is sufficient (see APPENDIX G -
PAG.76). To do this:
- Move the main system switch to “OFF”.
- Pull the base of the panel (2 - F
IG. 7.13) outwards and then
upwards to release it from the frame and then remove it.
- Turn the control panel (3 - F cover, taking out the locking screws (4 - F
IG. 7.14) and remove the rear
IG. 7.14).
3
4
Fig. 7.14
- Identify the terminal block (5 - F
IG. 7.15) and make the con-
nections, as in the diagram shown below.
5
ON
OFF
Fig. 7.12
- Unscrew the fastening screws (1 - F panel (2 - F
IG. 7.13).
2
Fig. 7.15
IG. 7.13) on the front
Fig. 7.13
1
61
Page 68
INSTALLATION
7.7.1 Master control panel internal connection block
28
27
26
25
24
23
22
21
20
19
18
DHW pump
High Temperature system pump
Mixing valve
Contact for alarm signal
Probe in zone 1
high temperature
Storage tank probe
Loop pump or
Low temperature system pump
Remote
control
17 16 15 14 13 12 11 10 9
Low temperature
room thermostat
0-10V
analogue
input
Probe in zone 2
low temperature
Outdoor probe
High temperature room thermostat
1
2
3
4
5
6
7
8
(*) 230V~50Hz
The following measures are compulsory:
1 - the use of an omnipolar thermal overload switch, mains disconnecting switch, compliant with the CEI­EN standards (minimum contact opening 3 mm); 2 - respect the connection L (Line) - N (Neutral). Leave the earth wire around 2 cm longer than the power wires; 3 - use wires with a cross-section greater than or equal to 1.5 mm
2
, complete with pointed end termi­nals; 4 - refer to the wiring diagrams in this booklet for any operations on the electrical system. 5 - connect the appliance to an effective earth system.
The pumps should be connected by installing suitable
contactors with manual emergency operation.
( The gas and/or water pipes must not be used to earth the
appliance.
( The power supply and room thermostat cables must not
run near hot surfaces (flow pipes).
The manufacturer is not liable for any damage due to the failure to earth the appliance and to observe the informa­tion provided on the wiring diagrams.
7.8 SYSTEMS FILLING AND DRAINING
The Beretta POWER PLUS Boiler is not fitted with a filling valve, which must be installed on the system return.
7.8.1 Filling
- Open the valves (1 - F fittings.
ILLUSTRATIVE SCHEME
Fig. 7.16
- Open the cap/caps on the automatic vent valve/valves (2 -
F
IG. 7.17) by two or three turns.
- If present, open the two-ways valve of each thermal engine, setting the lever (3 - F This lever is placed underneath the two-ways valve.
The air is vented from the POWER PLUS boiler
automatically through the automatic vent valve/
IG. 7.16) installed on the boiler water
1
MI
RI
GAS
IG. 7.19) in its position “MANUAL”.
62
Page 69
Fig. 7.17
INSTALLATION
Before opening the drain tap (4 - FIG. 7.20), protect
2
the electrical devices underneath against water spill­age.
Emptying the SYSTEM
- Check that the valves (1 - F circuit, are open.
- Connect a plastic hose to the drain tap (5 - F on the system return line, and open the tap.
IG. 7.21), installed on the water
IG. 7.21), fitted
valves installed on the top of the heating units. Check that the cap on the valve is open.
7.8.2 Draining
Before starting to empty the system, disconnect the power sup­ply by moving the main system switch to “OFF”.
ON
OFF
Fig. 7.18
Emptying the BOILER
- Close the valves (1 - F fittings.
IG. 7.19) installed on the boiler water
1
1
5
MI
RI
GAS
ILLUSTRATIVE SCHEME
Fig. 7.21
- If present, open the two-ways valve of each thermal engine, setting the lever (3 - F This lever is placed underneath the two-ways valve.
- Once the system has been drained bring back the two-ways valve lever of each thermal unit to its position “AUTO- MATIC”.
IG. 7.22) in its position “MANUAL”.
3
ILLUSTRATIVE SCHEME
Fig. 7.19
- Connect a plastic hose to the drain tap (4 - F each heating unit, and open the tap.
4
Fig. 7.20
MI
RI
GAS
IG. 7.20), on
AU
TO
Fig. 7.22
MAN
7.9 FLUE DRAIN AND COMBURENT AIR INTAKE
The flue and the fitting to the flue/chimney must be made in compliance with the standards and the legislation in force, as well as with local regulations. The pipes used must be rigid and resistant to temperature, condensate and mechanical stress, and airtight. This pipes must be bought by the installer.
Non-insulated flues are potential sources of danger.
The chimney connection of the Beretta Power Plus is
female.
7.9.1 Ducts maximum length
The maximum equivalent length of the sum of the 50 mm in­take pipes and flues is 30 metres, with a pressure drop of 2 me­tres for each 90° bend.
63
Page 70
INSTALLATION
Model 100 M Model 100 M DEP
Minimum dimensions of the compartment for the passage of two flues, diameter 50 mm
Circular
compartment
Rectangular
compartment
20 50 20 50 20
20 50 20 50 20
20 50 20
160 mm
Ø 160 mm
90 mm
Ø 71 mm
Model 50 M
Circular
compartment
Rectangular
compartment
Minimum inside dimensions of the compartment for the passage of 1 flue, diameter 50 mm
Ø 50 mm Ø 50 mm
275 37
Fig. 7.23
A
A - Air intake Ø 50 mm (*) S - Flue drain Ø 50mm
(*) The cover panel for
the comburent air intake  is available separately.
A
S
275 212
S
61
Fig. 7.25
-B23
Fan upstream. Combustion air intake directly from the room where the boiler is installed. Flue gas ex­haust through horizontal or vertical pipes, fitted with ventilation openings.
-C63
Fan upstream. Combustion air intake and flue gas ex­haust without terminals.
Refer to the DPR 412 and UNI CIG 7129.
Fig. 7.24
Installation of a single boiler with flue passing inside a com­partment (open flue operation).
For this type of operation, make sure that the size of the com­partment complies with the standards in force.
F
IG. 7.25, FIG. 7.26 and FIG. 7.26 show the minimum dimen-
sions of the compartment when passing one flue (model 50 M) or two flues (models 100 M or 100 S).
Parameter 36 (see SECT. 3.5, PAGE 19) needs to be set
based on the type of gas and the length of the chim­ney.
7.9.2 Condense drain arrangement
The condense produced by the Beretta POWER PLUS boiler during normal operation must be drained at atmospheric pres-
Fig. 7.26
sure, i.e. by dripping into a siphoned drain system. This should be installed as follows:
- Install a condense tundish/collection tank at the condense drain.
- Connect the condense tundish/collection tank to the drains via a siphon.
- Install a neutraliser if required by law.
64
Page 71
Models 50 M + 100 S
Minimum distance 300 mm
Minimum
distance
10 mm
Condense collector (at atmospheric pressure)
i>3%
Mains sewers
i=3
i
Models 50M+100SDEP
Minimum dimensions of the compartment for the passage of three flues, diameter 50 mm
INSTALLATION
Square
compartment
20 50 20 50 20
20 20
160 mm
Rectangular
compartment
230 mm
90 mm
20 50 20 50 20 50 20
20 50 20
Fig. 7.27
The condense collection tank must be made and
installed in compliance with applicable standards.
Specific pipes for condensing boilers must be used.
For installation, follow the instructions provided with the kit.
Drain trap/siphon along the drain pipe
If the vertical or horizontal section of the drain pipe needs to be extended by more than 4 metres, a drain trap must be in­stalled at the foot of the pipe. The useful height of the drain trap must be at least 300 mm. The discharge of the drain trap must then be connected to the sewerage system.
7.9.3 Kit flue collector with clapet valves (F
IG. 7.11)
For the installation of a boiler of 100kW a flue collector with clapet valve kit is available. It is possible to fit shoulder to shoulder up to 4 of these kits and connect up to four 100kW boilers. The table reports the maximum lengths available when in the open chamber configuration. The clapet valves grant the correct operation of the system.
7.10 OUTDOOR PROBE CONNECTION
The correct positioning of the outdoor probe is fundamental for the correct operation of the climate control function. The probe must be installed outside of the building being heated, at a height of around 2/3 of the wall facing NORTH or NORTH­WEST, and away from flues, doors, windows and areas ex­posed to direct sunlight.
Fig. 7.28
Maximum
Description
Thermal
Power
(HS) [kW]
Maxi-
mum
length [m]
Flue drain
pipe Ø
[mm]
1 Power Plus 50 M < 50 30 50
1 Power Plus 100 M < 100 55 125
1 Power Plus 50 M + 1 Power PLUS 100 S
DEP
1 Power Plus 50 M + 1 Power Plus 100 S
1 Power Plus 100 M + 1 Power Plus 100 S
1 Power Plus 50 M + 2 Power Plus 100 S
1 Power Plus 100 M + 2 Power Plus 100 S
1 Power Plus 100 M + 3 Power Plus 100 S
< 127
(< 115 on
55 125
Hi)
< 150 55 125
< 200 50 125
< 250 30 125
< 300 30 125
< 400 25 125
7.10.1 Outdoor probe wall fitting
- Unscrew the cover on the probe protection box, turning it anticlockwise to access the terminal block and the fastening holes.
- Trace the fastening points using the protection box as a tem­plate.
- Remove the box and drill the holes for the 5x25 expansion plugs.
- Fasten the box to the wall using the two plugs supplied.
- Unscrew the nut on the cable gland, pass a two-wire cable (cross-section from 0.5 to 1mm
2
, not supplied) through to
connect the probe to terminals 7 and 8 (see APPENDIX G -
65
Page 72
INSTALLATION
Cap
Sleeve
Collector Ø125
Clapet
Elbow 45˚
Sleeve
Elbow 45˚
Cap
Collector
Ø125
Clapet
Fig. 7.29
Fig. 7.30
PAG.76).
- Connect the two wires on the cable to the terminal block, without need of identifying the polarity.
- Tighten the nut on the cable gland and close the cover on the protection box.
The probe should be placed on a smooth section of
the wall; in the event of exposed brick walls or uneven walls, a smooth contact area should be fore­seen.
The maximum length of the connection between the
outside probe and the control panel is 50 m.
The connection cable between the probe and control
panel must not have junctions; if required, these must be soldered and adequately protected.
Any conduits used for the connection cable must be
separate from the power cables (230Vac).
66
Page 73
INSTALLATION
Correspondence table
Detected temperatures (°C) - Probes resistive values (Ω).
T (°C) R () T (°C) R (Ω) T (°C) R (Ω) T (°C) R (Ω) T (°C) R () T (°C) R (Ω)
-20
-19
-18
-17
-16
-15
-14
-13
-12
-11
-10
-9
-8
-7
-6
-5
-4
-3
-2
-1 0 1
67739 64571 61568 58719 56016 53452 51018 48707 46513 44429 42449 40568 38780 37079 35463 33925 32461 31069 29743 28481 27279 26135
10 11 12 13 14 15 16 17 18 19 20 21 22 23
2 3 4 5 6 7 8 9
25044 24004 23014 22069 21168 20309 19489 18706 17959 17245 16563 15912 15289 14694 14126 13582 13062 12565 12090 11634 11199 10781
24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45
10382
9999 9633 9281 8945 8622 8313 8016 7731 7458 7196 6944 6702 6470 6247 6033 5828 5630 5440 5258 5082 4913
46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67
4751 4595 4444 4300 4161 4026 3897 3773 3653 3538 3426 3319 3216 3116 3021 2928 2839 2753 2669 2589 2512 2437
68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89
2365 2296 2229 2164 2101 2040 1982 1925 1870 1817 1766 1717 1669 1622 1577 1534 1491 1451 1411 1373 1336 1300
90 91 92 93 94 95 96 97 98
99 100 101 102 103 104 105 106 107 108 109 110
1266 1232 1199 1168 1137 1108 1079 1051 1024
998 973 948 925 901 879 857 836 815 796 776 757
67
Page 74
APPENDIX A - Main components
APPENDIX A - Main components
Power Plus 50 M Power Plus 100 M - 100 S
24 23
22
21
20 19
18 17
16
1234
5 6
7
9
10 11
23 22
21
20
19 18
17 16
1234 1234
5
6
7
8
9
10
11
14 13 12 15
KEY
1. FAN
2. COMBUSTION AIR INTAKE FITTING
3. GAS VALVE
4. FLUE GAS DRAIN FITTING
5. FLUE GAS ANALYSIS TEST POINT
6. FLOW PROBE
7. SAFETY THERMOSTAT
8. SECOND COMBUSTION CHAMBER (MODELS 100 ONLY)
9. RETURN PROBE
10. CONDENSE COLLECTION DRAIN TRAP
11. CONTROL PANEL (90° ROTATION)
12. GAS SUPPLY
13. CENTRAL HEATING RETURN
14. CENTRAL HEATING FLOW
14 13 12 1514 13 12 16 17
15. MAIN SWITCH
16. SAFETY VALVE (5,5 BAR)
17. WATER DIFFERENTIAL PRESSURE SWITCH
18. DRAIN COCK
19. FLUE GAS PROBE
20. FIRST COMBUSTION CHAMBER
21. AUTOMATIC VENT VALVE
22. IGNITION / DETECTION ELECTRODE
23. PANELLING
68
Page 75
APPENDIX B - Dimensions and weight
APPENDIX B - Dimensions and weight
H
L
P
DESCRIPTION
L P
H
Net weight
Weight with packaging
50 M DEP
50 M
600 mm 380 mm
1000 mm
~60 kg ~65 kg
100 M
100 S DEP
100 S
600 mm 380 mm
1000 mm
~90 kg ~90 kg
69
Page 76
APPENDIX C - Technical data table
APPENDIX C - Technical data table
Description Unit 50 M 100 M 100 S 100 M DEP 100 S DEP
Fuel
Appliance category II2H3+ II2H3+ II2H3+ II2H3+ II2H3+
Type of appliance
Heat input ref. HHV (min - max) kW 16,3-50 16,3-100 16,3-100 16,3-77,3 16,3-77,3 Heat input ref. NHV (min - max) kW 15-45 15-90 15-90 15-69,6 15-69,6 Useful heat output (80°/60°C) kW 44,2 88,30 88,30 68,5 68,5 Useful heat output (50°/30°C) kW 48,5 96,8 96,8 75,3 75,3 Net efficiency ref. NHV (80°C/60°C) kW 98,2 98,2 98,2 98,4 98,4 Net efficiency ref. NHV (50°C/30°C) % 107,7 107,7 107,7 108,2 108,2 Net efficiency at 30% ref. NHV (50°C/30°C) % 108,7 108,7 108,7 108,7 108,7 Losses through the chimney
with the burner operating Losses through the chimney
with the burner off Losses through the casing (Tm=70°C) % 0,5 0,5 0,5 0,5 0,5 Flue gas temperature °C Return temp. + 5 Return temp. + 5 Return temp. + 5 Return temp. + 5 Return temp. + 5 CO
2 at minimum - maximum % 8,4-9,4 8,4-9,4 8,4-9,4 8,4-9,4 8,4-9,4
Dry Air free CO at minimum - maximum less than p.p.m. 10-120 10-120 10-120 10-120 10-120 Dry Air free NOx at minimum - maximum less than p.p.m. 10-20 10-20 10-20 10-20 10-20 NOx class 55555 Maximum operating pressure, central heatingbar66666 Maximum admissible temperature °C 90 90 90 90 90 Range of boiler water temperature settings (±3°C) °C 20-80 20-80 20-80 20-80 20-80 Water content l5 10101010 Power supply V~Hz 230~50 230~50 230~50 230~50 230~50 Maximum power input W 169 333 333 333 333 Electrical protection degree IP X0D X0D X0D X0D X0D Quantity of condense Kg/h 7,2 14,4 14,4 11,2 11,2
% 1,3 1,3 1,3 1,3 1,3
% 0,1 0,1 0,1 0,1 0,1
G20 G30 G31
B23 C63
G20 G30 G31
B23 C63
G20 G30 G31
B23 C63
G20 G30 G31
B23 C63
G20 G30 G31
B23 C63
70
Page 77
APPENDIX D - Hydraulic circuit
1. FAN
AA
1
3
4
5
2
SF
6
7
2. GAS VALVE
3. AUTOMATIC VENT VALVE
4. BURNER
5. HEAT EXCHANGER
6. CONDENSE DRAIN TRAP
7. DRAIN COCK
8. WATER DIFFERENTIAL PRESSURE SWITCH
9. SAFETY VALVE (5,5 bar)
AA AIR INTAKE
SF FLUE GAS OUTLET
SC CONDENSE DRAIN
MI CENTRAL HEATING FLOW
RI CENTRAL HEATING RETURN
GASGAS SUPPLY
APPENDIX D - Hydraulic circuit
8
9
SC1
MI RI GASSC2
D.1 Water side head losses
The POWER PLUS Boiler does not come with a pump, which must be installed in the system. When sizing the pump, refer to the water-side pressure drop in the boiler, as shown in the figure below.
1600
1400
1200
1000
800
600
400
Pressure drop (mbar)
200
0
0
500 1000 1500 2000
With 2-ways valve
Without 2-ways valve
2500 3000 3500 4000
Flow-rate (l/h)
71
Page 78
APPENDIX E - NTC probes positions
APPENDIX E - NTC probes positions
The following probes/thermostats are installed for each heating unit:
CENTRAL HEATING
OUTLET PROBE
SAFETY
THERMOSTAT
FLUE GAS
PROBE
CENTRAL HEATING
RETURN PROBE
72
Page 79
APPENDIX F - Pumps
APPENDIX F - Pumps
The POWER PLUS Boiler does not come with a pump, which must be installed in the system. When choosing the pump, refer to the following system diagrams.
F.1 Configuration with distribution pumps
REMARK - The pump sizing is fundamental when using this configuration. This configuration is suggested only when using
one generator at a time. For the configurations of more groups in cascade, this configuration should not be used. ATTENTION - If these prescriptions are not complied with, malfunctioning in the systems may occur. Boiler residual head: 7 mWC Boiler flow rate: 2 m Also consider the pressure drops in the individual circuit.
3
/h for each heating unit.
PB - Tank pump
PZ1 - Pump in zone 1 (high temperature)
PZ2 - Pump in zone 2 (low temperature)
V2 - Two-way valve (accessory)
PB
PZ1
PZ2
SZ2
80°C
50°C
60°C
30°C
SE
Install probes SZ1,
SZ2 and SB in a probe socket (outside of the boiler).
V2V2
SZ1
F.2 Configuration with injection pumps (accessory cod. 1102419)
Boiler residual head: 6 mWC Boiler flow rate: 2 m Recommended applications: injection pump kit type A for each thermal unit.
3
/h for each pump.
SZ1 - Probe in zone 1
SZ2 - Probe in zone 2
SB - Tank probe
SE - Outside probe
SB
SE
Install probes SZ1,
SZ2 and SB in a probe socket (outside of the boiler).
SZ1
PP
PB - Tank pump
PZ1 - Pump in zone 1 (high temperature)
PZ2 - Pump in zone 2 (low temperature)
V2 - Two-way valve (accessory)
PB
PZ1
PZ2
SZ2
80°C
50°C
60°C
30°C
SZ1 - Probe in zone 1
SZ2 - Probe in zone 2
SB - Tank probe
SE - Outside probe
SB
73
Page 80
APPENDIX F - Pumps
F.3 Configuration with ring pump and valves on the units
Boiler residual head: 7 mWC
Boiler flow rate: 2 m
3
/h for each heating unit.
With this configuration the circulator of the low temperature circuit is managed externally by a thermostat (see parameter 34, S
ECT. 3.5, PAGE 19). The circulator PZ2 has to be sized
considering the maximum and minimum flow rates and the
consequent head losses of the single thermal groups. Variable speed pumps use is suggested.
Suggested applications: Power Plus 50 M: type A circulator; Power Plus 100 M or 100 S: circulator type B; Power Plus 100 M + 100 S: circulator type C.
SZ1 - Probe in zone 1
SZ2 - Probe in zone 2
SB - Tank probe
SE - Outside probe
SB
SE
Install probes SZ1,
SZ2 and SB in a probe socket (outside of the boiler).
V2V2
SZ1
PZ2
PB - Tank pump
PZ1 - Pump in zone 1 (high temperature)
PZ2 - :System pump
V2 - Two-way valve (accessory)
PB
PZ1
SZ2
80°C
50°C
60°C
30°C
F.4 Configuration with mixed system and solar system with double-coil storage tank
Boiler residual head: 7 mWC
Boiler flow rate: 2 m
3
/h for each heating unit.
With this configuration the circulator of the low temperature circuit is managed externally by a thermostat.
With this configuration the solar control panel SUN2 manages
both the operation of the solar circuit (operating its pump ac­cording to the T between collector and tank) and the integra­tion boiler. To carry out the part of the system related to the so­lar circuit, refer to the components listed on the BERETTA so­lar catalogue.
A2
A1 - Solar pump
A2 - Contact for boiler request (ON/OFF)
F1 - :Collector probe
F1
A1
Relè
F3 - Tank upper probe
F4 - Tank lower probe
SUN 2
F3
F4
74
Page 81
F.5 Pumps performance graphics
Pump TYPE A – Typical curves injection pump available as an accessory
800
700
600
500
APPENDIX F - Pumps
III
400
II
300
I
Residual head (mbar)
200
100
0
0123456789
Flow-rate (m
Pump TYPE B – Typical curves pump NOT available as an accessory
1100
1000
900
800
700 600
500 400 300
Residual head (mbar)Residual head (mbar)
200
100
0
0 2 4 6 810121416 20
I
Flow-rate (m3/h)
3
/h)
II
18
Pump TYPE C – Typical curves pump NOT available as an accessory
1200 1100 1000
900
800
700 600
500 400
300 200
100
0
0 4 8 12162024 3236 44
I
II
Flow-rate (m
28
3
/h)
40
75
Page 82
APPENDIX G - Electrical schemes
APPENDIX G - Electrical schemes
The control panel on POWER PLUS models 50 M and 100 M contains one master board and one or two slave boards, depending on the power of the boiler. If connecting a series of boilers in cascading, the master board on the POWER PLUS 50 M or 100 M manages all the boards on the POWER PLUS 100 S boilers via BUS.
G.1 Power Plus 50 M – 100 M (master board code R105920)
CONDEXA PRO 50 M - 100 M part 1
15
Bus
7
IACR
1314
Analogic
Input
J12
56
J126J125J12
gv
a
m
TA1TA2
10 9
12
11
Circ.2
432 1
4
2
J123J12
1
J12
SZ1
SB
SZ2
SE
IG
NTC
1
2
NTC
3
4
NTC
5
6
Circ. 2
NTC
7
8
Earth
Neutral
Line
a m gv gv
a m
gv gv
J11 1
1
2
J11
2
J11
3
3
J11
4
4 J11
J11
5
5
J11
6
6
J11
7
7
8
8
J11
230V~50Hz
Neutral pump 1
Line Pump 1
Line DHW pump
Neautral DHW pump
Neutral Max. valve
Neutral pump 3
Line Pompa 3
Main earth
pole
Joint with sheath
J10
6
6
J10
5
5
J10
4
4
J10
J10
3
3
J10
2
2
J10
1
1
J9
3
3
J9
J9
2
2
J9
1
1
J
82
2
J8
J
81
Off - Max. valve
On - Max. valve
1
Pump
Pump
Pump 3
Max valve
0
OFF
ON
Alarm
28
27
26
25
24
23
22
21
20
19
18
PB
PZ1
PZ2
VM
16
17
Com.
24V
87
9
J129J128J12
5 0
J106J1
5
6
R6
Fuse
F1
3.15 A
Line 230 Vac.
Neutral 230 Vac.
Earth
Earth
Earth
Earth
m
1
a
2 3 4
gv
gv
gv
gv
Bus line with male connector for connection to another model 100S boiler.
Common
Common
Common
J11 6
6
Outlet NTC circ. 2
J11 5
57
J11
J1
PC
J11 4
4
Common
DHW NTC
J11 3
J11 2
Outlet NTC circ. 1
J11 1
132
BARCODE
Analogic Input
R.T. circ. 1
24V remote cont.
Common
Alarm
Common
4
3
2
1
0
0
0
0
J1
J1
J1
J1
J93J92J91J
1
342
J10
R5
J3
J7
J6
J5
J4
R4
23
J9 J8
R3 R2
MC
9
2
1
8
8 J
1
21
89
R1
J2
Common
Common
Ebus remote cont.
J126J127J128J12
765
J12
BUS J14
2
1
3
R.T. circ. 2
Common
J122J123J124J12 5
243
4
J12 1
1
T1
MASTER
Climate NTC
J11 8
J11 7
8
Bus line with female connector for connection to another model 100S boiler.
76
Page 83
APPENDIX G - Electrical schemes
The pumps should be connected by installing suitable contactors with manual emergency operation.
part 2
to main earth pole
1
PC
T1
WD
SLAVE 1
J5
J10
J17
EA/ER
gv gv gv
m
5
a
m
6
a
m
8
a
m
7
a
m
a
13
m
a
11
m
10
a
m
9
a
Earth Earth Earth
Line
Neutral
Gas valve
Safety thermostat
Diff. pressure switch
Blower (+) Hall sensor imput Hall sensor power
Hall sensor common Blower (-)
Outlet NTC
Return NTC
Flue gas NTC
J6 J14
J7
1
3
J12
T3
Main
Fuse 4A
J8
5 4 3 2
1
n
2
1
J9
J16
J15
F1
321
J2
4
5
J1
J11
J4
6
7
6 5
4
2 13
4 3
12
6 5 4
213
v g b m
IG1
C
VG
TS
PD
m
b
v
g
n
SM SR SF
BUS 1
to main earth pole
EA/ER
gv
J6
1
T1
J2
Earth
Line
m
123
5
a
Neutral
4
5
6
IG2
SLAVE 2
12
J9
BUS 2
PB - DHW pump PZ1 - Pump in zone 1 (high temperature) PZ2 - Pump in zone 2 (low temperature) VM - Mixing valve CR - Remote control (accessory) IA - Analogue input SB - DHW probe SZ1 - Probe in zone 1 SZ2 - Probe in zone 2 SE - Outside probe TA1 - Room thermostat in zone 1 (high temperature) TA2 - Room thermostat in zone 2 (low temperature)
SYSTEM
VG - Gas valve TS - Safety thermostat PD - Water differential pressure switch SM - Outlet probe SR - Return probe SF - Flue gas probe EA/ER - Ignition/detection electrode C - Cable for connection to two-way valve or injection pump (accessories) IG - Main boiler switch IG1 - FIRST heating unit switch IG2 - SECOND heating unit switch J10/J17 - Microswitches for setting the address (see page 54)
HEATING UNIT
77
Page 84
APPENDIX G - Electrical schemes
G.2 Power Plus 50 M - 100 M (master board code R107584)
POWER PLUS 50 M - 100 M part 1
IACR
15
1314
Analogic
Input
Bus
J12
8
J12 2
J111J11
J11
Analogic Input
Common
Common
Ebus remote cont.
J12 2
J12 3
3 4
J12
gv
12
11
Circ.2
56
432 1
9
J112J11
T. circ. 2 R .
Common
1 2
a
m
TA1TA2
10 9
3
10
J11
Common
J11 10
SZ1
SB
SZ2
SE
IG
NTC
1
2
NTC
3
4
NTC
5
6
Circ. 2
NTC
7
8
1
J11
8
T. circ. 1 R .
J11 3
a m gv gv
a m
gv gv
1
2
3
4 J11
5
6
J11
7
8
J11 11
Common
Climate NTC
J11 4
J11 11
Earth
Neutral Line
J11 7
J11 14
J11 6
J11 13
J11 5
J11 12
4
Common
Outlet NTC circ. 2
J11 12
J11 5
Common
DHW NTC
J11 13
J11 6
Common
Outlet NTC circ. 1
J11 14
J11 7
7 14
Neutral Max. valve
Neutral pump 3
Line Pomp 3
Neautral DHW pump
Line Pump 1
Line DHW pump
Neutral pump 1
J10 6
J10 5
J10 4
J10 3
J10 2
J10 1
J9 3
J9 2
J9 1
J8 2
J8 1
Off - Max. valve
On - Max. valve
J10 6
J105J104J103J102J101J85J8
J10
6
5
4
J10
3
2
1
3
J9
2
1
2
J8
1
Main earth
pole
Pump
Pump
Pump 3
0
OFF
ON
Alarm
4
Valv.M ix
J8
28
27
26
25
24
23
22
21
20
Common
3 J8
J82J8
19
18
PB
PZ1
PZ2
VM
Alarm
1
Joint with
17
24V
9
J12 4
sheath
16
87
J12 3
Com.
24V remote cont.
J12 4
230V~50Hz
R5
R6
Fuse
F1
3.15 A
Earth
Earth
Earth
Earth
m
1
a
2
J3
3
gv
gv
gv
gv
J7
J6
J5
J4
Line 230V a.c. Neutral 230V a.c.
Bus line with male connector for connection to another model 100S boiler.
R4
R3 R2
R1
T1
4
3
MASTER
BARCODE
J1
PC
J2
MC
BUS J14
1
2
Bus line with female connector for connection to another model 100S boiler.
78
Page 85
APPENDIX G - Electrical schemes
The pumps should be connected by installing suitable contactors with manual emergency operation
parte 2
to main earth pole
1
WD
PC
J5
J10
J17
T1
SLAVE 1
T3
Main
J7
1
EA/ER
3
J12
IG1
gv gv gv
m
5
a
m
6
a
m
8
a
m
7
a
m
a
13
m
a
11
m
10
a
m
9
a
Earth Earth Earth
Line
Neutral
C
Gas valve
Safety thermostat
Diff. pressure switch
Blower (+) Hall sensor imput Hall sensor power
Hall sensor common Blower (-)
Outlet NTC
Return NTC
Flue gas NTC
VG
TS
PD
m
b
v
g
n
SM SR SF
J6 J14
Fuse 4A
J8
5 4 3 2
1
n
2
1
J9
J16
J15
F1
321
J2
4
5
J1
J11
J4
6
7
6 5
4
2 13
4 3
12
6 5 4
213
v g b m
BUS 1
to main earth pole
EA/ER
Earth
gv
J6
1
T1
J2
Line
m
123
5
a
Neutral
4
5
6
SLAVE 2
12
J9
BUS 2
IG2
PB - DHW pump PZ1 - Pump in zone 1 (high temperature) PZ2 - Pump in zone 2 (low temperature) VM - Mixing valve CR - Remote control (accessory) IA - Analogue input SB - DHW probe SZ1 - Probe in zone 1 SZ2 - Probe in zone 2 (low temperature) SE - Outside probe TA1 - Room thermostat in zone 1 (high temperature) TA2 - Room thermostat in zone 2 (low temperature)
SYSTEM HEATING UNIT
VG - Gas valve TS - Safety thermostat PD - Water differential pressure switch SM - Outlet probe SR - Return probe SF - Flue gas probe EA/ER - Ignition/detection electrode C - Cable for connection to two-way valve or injection pump (accessories) IG - Main boiler switch IG1 - FIRST heating unit switch IG2 - SECOND heating unit switch J10/J17 - Microswitches for setting the address (see page 54)
79
Page 86
APPENDIX G - Electrical schemes
G.3 Power Plus 100 S
CONDEXA PRO 100 S part 1
Main earth pole
gv
Joint with sheath
PC
IG
Earth Neutral Line
a
m gv gv
to main earth pole
gv
a
3
m
a m gv
EA/ER
gv
J6
1
T1
J7
1
J8
3
Fuse 4A
J14 J15
F1
123
Earth
gv
Earth
gv
Earth Line
m
5
a
Neutral
230V~50Hz
IG1
m
6
a
4
66
m
75
5
4
31 2
4 3 2
1
Gas valve
8
a
Safety thermostat
m
7
a
Diff. pressure switch
m
a
13
Blower (+) Hall sensor imput
Hall sensor power Hall sensor common Blower (-)
m
Outlet NTC
a
11109
m
Return NTC
a
m
Flue gas NTC
a
C
VG
TS
PD
m
b
v
g
n
SM
SR
SF
J5
J10
J17
WD
SLAVE 1
T3
Main
J12
J2
v
5
g
4
b
3
m
2
1
J1
n
J11
6
1
J16
2
J9
5 4
J4
3
12
Bus line with male connector for connection to another model 100S boiler.
80
BUS 1
L = 1500 mm
Page 87
APPENDIX G - Electrical schemes
The pumps should be connected by installing suitable contactors with manual emergency operation
VG - Gas valve TS - Safety thermostat PD - Water differential pressure switch SM - Outlet probe SR - Return probe SF - Flue gas probe EA/ER - Ignition/detection electrode C - Cable for connection to two-way valve or injection pump (accessories) IG - Main boiler switch IG1 - FIRST heating unit switch IG2 - SECOND heating unit switch J10/J17 - Microswitches for setting the address (see page 54)
gv
to main earth pole
EA/ER
gv
J6
1
T1
J7
1
J8
3
Fuse 4A
J14 J15
F1
321
J2
4
575
Earth
gv
Earth
gv
Earth
Line
m
5
a
Neutral
m
6
a
C
part 2
IG2
PC
WD
J5
J10
J17
SLAVE 2
T3
Main
L = 1200 mm
J12
5 4 3 2
1
1
2
J9
J16
BUS 1
v g b m
n
J4
J1
4
23 166
4 32
J11
1
6
5 4 3
21
m
Gas Valve
8
a
Safety thermostat
m
7
a
Diff. pressure switch
m
a
13
Blower (+) Hall sensor imput
Hall sensor power Hall sensor common Blower (-)
m
Outlet NTC
a
m
Return NTC
a
m
Flue gas NTC
91011
a
VG
TS
PD
m
b
v g
n
SM
SR
SF
Bus line with female connector for connection to another model 100S boiler.
81
Page 88
APPENDIX H - Electrical connections
APPENDIX H - Electrical connections
Terminal block inside the master control panel
28
27
26
25
24
23
22
21
20
19
18
DHW pump
High Temperature system pump
Mixing valve
Contact for alarm signal
Probe in zone 1
high temperature
Storage tank probe
Loop pump or
Low temperature system pump
Remote
control
Low temperature
room thermostat
0-10V
analogue
input
Probe in zone 2
low temperature
Outdoor probe
High temperature room thermostat
17 16 15 14 13 12 11 10 9
1
2
3
4
5
6
7
8
(*) 230V~50Hz
The following measures are compulsory:
1 - the use of an omnipolar thermal overload switch, mains disconnecting switch, compliant with the CEI­EN standards (minimum contact opening 3 mm); 2 - respect the connection L (Line) - N (Neutral). Leave the earth wire around 2 cm longer than the power wires; 3 - use wires with a cross-section greater than or equal to 1.5 mm
2
, complete with pointed end termi­nals; 4 - refer to the wiring diagrams in this booklet for any operations on the electrical system. 5 - connect the appliance to an effective earth system.
The pumps should be connected by installing suitable
contactors with manual emergency operation.
( The gas and/or water pipes must not be used to earth the
appliance.
( The power supply and room thermostat cables must not
run near hot surfaces (flow pipes).
The manufacturer is not liable for any damage due to the failure to earth the appliance and to observe the informa­tion provided on the wiring diagrams.
82
Page 89
APPENDIX H - Electrical connections
H.1 Outdoor probe connection
The correct positioning of the outdoor probe is fundamental for the correct operation of the climate control function. The probe must be installed outside of the building being heated, at a height of around 2/3 of the wall facing NORTH or NORTH-WEST, and away from flues, doors, windows and areas exposed to direct sunlight.
Outdoor probe wall fitting
- Unscrew the cover on the probe protection box, turning it anticlockwise to access the terminal block and the fastening holes.
- Trace the fastening points using the protection box as a tem­plate.
- Remove the box and drill the holes for the 5x25 expansion plugs.
- Fasten the box to the wall using the two plugs supplied.
- Unscrew the nut on the cable gland, pass a two-wire cable (cross-section from 0.5 to 1 mm connect the probe to terminals 7 and 8 (vedere APPENDIX
G -
PAGE 76).
- Connect the two wires on the cable to the terminal block, without need of identifying the polarity.
- Tighten the nut on the cable gland and close the cover on the protection box.
The probe should be placed on a smooth section of
the wall; in the event of exposed brick walls or uneven walls, a smooth contact area should be fore­seen.
The maximum length of the connection between the
outside probe and the control panel is 50 m.
2
, not supplied) through to
Fig. H.1
The connection cable between the probe and control
panel must not have junctions; if required, these must be soldered and adequately protected.
Any conduits used for the connection cable must be
separate from the power cables (230Vac).
H.2 External 0-10 V thermoregulation
The eventual use of an external thermoregulation using a 0-10V signal can be done connecting the output signal to the connec­tions number 13 and 14
H.3 Connection of an external alarm device
A dedicated output with a voltage free contact is available on the boiler terminal block. It allows to connect externally a visual or acoustic alarm device able to signal eventual anomalies. The alarm device needs to be connected to the connections number 18 and 19.
83
Page 90
APPENDIX H - Electrical connections
H.4 Remote control kit
Installation
The kit must be installed by professionally qualified personnel from the BERETTA Technical Service Assistance personnel or by professionally qualifies individuals.
For correct installation, remember that the Room Control:
- Must be installed on a wall, where possible on the inside, that is not crossed by hot or cold water pipes.
- Must be mounted around 1.5 m from the ground.
- Must not be installed near doors or windows, cooking appli­ances, radiators, fan coils or in general affected by situations that may cause disturbance to the temperature measured.
To fasten the room control to the wall, proceed as follows:
- Separate the control panel (A - F (B - F
IG. H.2) by pressing the plastic taba (C - FIG. H.2).
- Use the base plate (B - F
IG. H.2) to mark the drilling points
IG. H.2) from the base plate
on the wall.
B
AC
Fig. H.2
- Drill the wall (5 mm diameter holes).
- Thread in a three-wire cable (D - F tion between 0.5 and 1 mm room control to the boiler, through the hole (E - F
For correct operation, check that the surface of the
wall is even.
IG. H.3), with a cross sec-
2
(not supplied), to connect the
IG. H.3).
- Connect the cable from terminals “15-16-17” on the Master board to terminals “BUS-Com-24V” on the connector (F -
F
IG. H.3). A label shows the correct position of the wires.
- Fasten the base plate (B - F screws and the screw anchors (G - F
F
IG. H.3) to the wall using the
IG. H.3) supplied.
G
D
E
B
Fig. H.3
- Secure the control panel to the base plate.
The maximum length of the connection between the
control panel and the boiler is 100 m.
The connection cable between the control panel and
the boiler must not have joints; if necessary, however, any joints must be sealed and suitably protected.
Any conduits used to lay the connection cable must
be separate from the power cables (230Vac).
Electrical connections
Before performing any operations, disconnect the power sup­ply to the boiler, moving the main system switch and the main switch on the appliance to “OFF” (H - F
IG. H.4). To make the
electrical connections:
- Unscrew the fastening screws (I - F el (L - F
IG. H.5).
- Pull the base of the panel (L - F
IG. H.5) on the front pan-
IG. H.5) outwards and up-
wards to release it from the frame, and then remove it.
- Turn the control panel (M - F four screws (N - F
IG. H.6) to remove the rear cover.
- Identify the terminal block (O - F
IG. H.6) 90° and take out the
IG. H.7) and make the con-
nections as shown in the diagram on the following page.
Remote control
The remote control, once connected to the Master board, al­lows to program and monitor the main system parameters (timer, operating hours for the three circuits, status of the pumps, installation output, etc.). Main characteristics:
- Backlit 4x20 display.
- Maximum room control Installation distance: 100 m.
- Simple programming and monitoring.
- Built-in room temperature probe.
- Power supply: 24Vdc.
The device can perform a wide range of functions using just four buttons, simplifying all operations.
General information on the screens
The following pages will describe all the possible screens dis­played on the room control. To simplify the understanding of the images shown on the display, the graphic representation features a number of distinctive characteristics that require ex­planation.
In reference to F
IG. H.9, for example, the areas highlighted in
grey indicate the parts of the display that are controlled using the two cursors ( and ). An arrow will be shown on the dis­play that indicates the selected line.
At the same time, however, as shown in F
IG. H.10, the areas
in grey may also indicate a part of the display where data can be entered, such as the installer code, start and end of the time program, the attenuation parameter and so on.
One final point worth noting is that when an option is selected on the display, the message ACTIVE will appear. In this way, for instance, conformation is provided of the selection made on the display: using the example of F
IG. H.11 of the row
marked “ON/OFF”, this means, as will be explained in detail further on (see the paragraph on “CIRCUIT CONTROL”), that the time settings have been selected (indicated as on/off) for the high temperature circuit (CH1).
IMPORTANT:
- to access a screen press (OK).
84
Page 91
TERMINAL BLOCK INSIDE THE MASTER CONTROL PANEL
ON
OFF
APPENDIX H - Electrical connections
28
27
26
25
24
23
22
21
20
19
18
(*)
230V~50Hz
PB (*)
DHW pump
PZ1 (*)
High temperature system pump
Loop pump or
PZ2 (*)
Low temperature
Pbas (*)
system pump
VM (*)
Mixing valve
Alarm signal contact
24V
Com
17
16 15 14
Low temperature
room thermostat
IA
Analogue
input
0-10V
BUS
13 121110 9
TA2
Probe in zone 1
high temperature
DHW probe
Probe in zone 2
low temperature
Outside probe
TA1
High temperature room thermostat
SZ1
SB
SZ2
SE
1
2
3
4
5
6
7
8
17-24V
16-Com
15-BUS
TERMINAL BLOCK INSIDE
THE ROOM CONTROL
H
Fig. H.4
- to exit a screen press (ESC).
Use of the remote control
The enclosure shows all the possible screens displayed on the remote control. For convenience, these screens have been numbered, and will be described individually below.
General information
The first screen on the remote control (F
IG. H.12) provides in-
formation on the system, indicated in the table below.
L
L
Fig. H.5
85
Page 92
APPENDIX H - Electrical connections
M
N
Fig. H.6
O
Fig. H.7
CONFIRM button and ACCESS the Main Menu
This button is used to access the desired screen or setting. From the first screen, it accesses the Menu.
INCREASE button
This button is used to move upwards on the display and increase the value displayed.
DISPLAY
Program schedule £CH1 CH2 San*
(*) Present only if the value of parameter 6 is not "0".
Fig. H.9
START END CH1 £Mon 11:00 Wed 22:00 Add
LEVEL 3.1
Fig. H.10
CH1
On/off Active £Continue
Off
LEVEL 2.1.1
Fig. H.11
22 Feb 2005
CH1 70°C 09 23
LEVEL 3
DECREASE button
This button is used to move downwards on the display and decrease the value displayed.
ESC button RESET button if pressed for 5 seconds
This button is used to return to the previous screen or exit a setting. If pressed for 5 seconds from the main screen, with one or more type A errors (non-volatile, see
S
ECT.6.3, PAGE 50), it acts as the reset button for both the
master and the slaves.
Fig. H.8
CH2 40°C Tamb 21°C San 50°C Tout 21°C
LEVEL S
Fig. H.12
Value Display
Date 22 feb 2005
Time 09 23
Room temperature (measured by the probe on the room control)
Outdoor temperature (if this line is not visible it means that the outdoor probe is not fitted, or is not connected correctly)
Set point temperature in the high temperature circuit (*)
Set point temperature in the low temperature circuit (*)
Domestic hot water set point temperature (this information is only visible if the domes­tic hot water circuit is present) (*)
Tamb 21°C
Test 21°C
CH1 70°C
CH2 40°C
San 50°C
86
Page 93
(*) If the circuits are off, the message OFF will be displayed
Date
£Thursday 14 Apr 05
10:30
LEVEL 1.3
LEVEL 1.4
Room Parameters
Tamb corr. 30°C
instead of the set point.
Error indications
If any types of errors occur in the system, a light on the main screen comes on, in the top-left corner of the display, as shown in the Picture H.13. The light only comes on when there is a malfunctioning in the system, together with the error code and the number of the unit where the error occurred.
In the example shown in F unit no.1 (01 33).
IG. H.13, error no. 33 occurred on
APPENDIX H - Electrical connections
CONFIGURATION
£LanguageDate
Room Parameters
LEVEL 1
Fig. H.15
error
light
unit
error no.
01 33 22 feb 2005 CH1 70°C 09:23 CH2 40°C Tamb 21°C San 50°C Tout 21°C
LEVEL S
Fig. H.13
General menu
From the main display (S) this screen (F cessed by simply pressing the confirm button (OK). At this stage, all four submenus listed below can be accessed:
- Configuration
- Installation
- Program schedule
-nformation by selecting them with the arrows ( and ) and pressing the
confirm button (OK).
IG. H.14) can be ac-
Language
£Italiano English
LEVEL 1.2
Fig. H.16
Setting the day of the week, date and time
To enter this screen simply select the “Date” option from
“CONFIGURATION” mode using the two arrows ( and) and press the confirm button (OK). Then the day of the
week, the date and the time can be set (F
Fig. H.17
IG. H.17).
£ConfigurationInstallation
Program schedule Information
Fig. H.14
“CONFIGURATION” mode
This screen (F
1.2 to 1.4) that allow to configure the settings indicated (lan­guage/date) as desired.
Setting the language
The default language set on the remote control is Italian. To change this setting selecting another language it is sufficient, once having entered this section (F with the desired option using the two arrows ( and ) and press the confirm button (OK).
IG. H.15) is used to access all the levels (from
MENU
Level 1
Level 2
Level 3
Level 4
LEVEL 0
IG. H.16), select the line
Setting the room temperature correction
This level is used to correct the room temperature value (F H.18). By default the remote control is supplied with a correc­tion value set to 0°C. Parameter 39 is used to save the setting (refer to S ters).
Fig. H.18
“INSTALLATION” mode
This mode accesses the functions for controlling the circuits connected to the boiler and the system parameters, after hav­ing entered the installer password (F
ECT. 3.5, PAGE 19 for the complete list of parame-
IG. H.19).
IG.
87
Page 94
APPENDIX H - Electrical connections
MENU
Configuration £Installation
Program schedule Information
LEVEL 0
Fig. H.19
Circuits control
The boiler operated by the remote control can manage three circuits at the same time (F
- high temperature circuit (CH1)
- low temperature circuit (CH2)
- domestic hot water circuit (San). This circuit is only present if the value of the Parameter 6 (San_type) is set to a value different from zero
IG. H.20 - FIG. H.21).
Installation £Control circuit Parameters
CH1 £On/off Continue Off
LEVEL 2.1.1
Fig. H.22
Setting the operating mode for the low temperature circuit (CH2)
1. Selecting “ON/OFF” enables time programming mode (F
IG. H.23). The time bands are programmed in time pro-
gramming mode (see page 89).
CH2 £On/off Active Continue Off
LEVEL 2.1.2
Fig. H.23
LEVEL 2
Fig. H.20
Control circuit £CHI CH2 San*
(*) Present only if the value of parameter 6 is not "0".
Fig. H.21
The parameters relating to the three circuits can be controlled from this level of the remote control (if they are all present in one single system at the same time). By default, for all three circuits, the option is set to “OFF”. If this setting is not changed the boiler would always be off.
Setting the operating mode for the high temperature cir­cuit (CH1)
1. Selecting “ON/OFF” enables time programming mode (F
IG. H.22). The time bands are programmed in time pro-
gramming mode (see page 89).
2. Selecting “CONTINUE” enables the continuous opera­tion of the boiler within the time bands, irrespective of whether the room thermostat is open or closed. When the room thermostat opens the attenuation function is activat­ed.
3. Selecting “OFF” switches the boiler completely off.
LEVEL 2.1
2. Selecting “CONTINUE” enables the continuous opera- tion of the boiler within the time bands, irrespective of whether the room thermostat is open or closed. When the room thermostat opens the attenuation function is activat­ed.
3. Selecting “OFF” switches the boiler completely off.
Setting the operating mode for the domestic hot water cir­cuit (San) – if present
1. Selecting “ON” the choice is to have the boiler on and pro­grammable (F in time programming mode (see page 89).
IG. H.24). The time bands are programmed
San £On Off Antilegionella 70°C
LEVEL 2.1.3
Fig. H.24
2. Selecting “OFF” switches the choice is to have boiler off and disables programming
3. The “LEGIONELLA PREV.” option is used to set the wa­ter temperature in the domestic hot water circuit for the Le­gionnaire disease prevention function.
Parameters
As seen in “INSTALLATION” mode (LEVEL 2.2), the in­staller code is required to access this section (F this case, after having entered the installer password “22”, as well as a complete list of parameters, a series of sections is dis-
IG. H.25). In
88
Page 95
played relating to special parameters (corresponding to the
MENU
Configuration Installation £ Program schedule
Information
LEVEL 0
LEVEL 3
Program schedule £CHI CH2 San
LEVEL 3.1
START STOP CH1 £Mon 20:00 Wed 22:00 Add
LEVEL 3.1
START STOP CH1 £Mon20:00 Mon20:00 Add
power of the thermal group and of the individual slaves con­nected) and, subsequently, the reference to the parameters for all three circuits, if present.
Installation
Control circuit £Parameters cod. _ _ _
LEVEL 2.2
Fig. H.25
Without the installer code, the first three parameters can still be displayed, corresponding to the set points in the high tem­perature (CH1), low temperature (CH2) and domestic hot wa­ter (San) circuits.
Specifically, the following parameters are displayed (F
H.26):
IG.
Parameters
APPENDIX H - Electrical connections
Fig. H.27
tion to this circuit, one or more boiler operating periods can be programmed. Remember that the same procedure is valid for the other two circuits: low temperature circuit (CH2) and do­mestic hot water (San).
£Complete list Power
Slaves CH1 CH2 San
LEVEL 2.2.1
Fig. H.26
- COMPLETE LIST (par. 1 ÷ 43): these are all the parameters that can be accessed by the installer after entering the pass­word
- POWER: power related parameters
- SLAVES: parameters that reside in the individual slaves
- CH1: parameters corresponding to the high temperature cir­cuit
- CH2: parameters corresponding to the low temperature cir­cuit
- San: parameters corresponding to the domestic hot water circuit
For the description of the displayed parameters, refer to
S
ECT. 3.5, PAGE 19.
Fig. H.28
The first screen displayed (F example, that the system will operate from 20:00 on each Monday until 22:00 on each Wednesday. To change the set­ting, simply select the required line, set the “START” and
“END” of the time band, scroll downwards and press confirm (OK). To cancel the setting simply select the required line,
scroll downwards and press cancel (OK).
Fig. H.29
To program continuous operation simply set the same two times on any day (as shown in F
IG. H.29) (LEVEL 3.1) shows, for
IG. H.30).
“Program schedule” mode
(only if ON/OFF MODE has been selected)
This section (F mode (ON/OFF) or continuous mode has been selected. The days and times when the boiler is operated can be pro­grammed.
Setting the operating periods (day-time) Using the two arrows ( and ) and the confirm button (OK)
enter time programming mode, corresponding to the high tem­perature circuit (CH1) (F
IG. H.27) is only available if programming
IG. H.28): from this point on, in rela-
Fig. H.30
Setting the operating periods and water temperature
Once having accessed LEVEL 3.1, the next screen (LEVEL
3.1.1) (F of the considered parameters and confirm the new settings (se­lecting the confirm option on the display). This section is used
IG. H.31) can be used to specify the preferred values
89
Page 96
APPENDIX H - Electrical connections
to set the start and end (both identified with the day and time) of the boiler operating period, the water flow outlet tempera­ture to the selected circuit and, respectively for the central heating (CH1 and CH2) and domestic hot water circuits the at­tenuation and Legionnaire disease prevention function.
£Start Mon20:00
Stop Wed22:00
Temp 70°C Attenuat. 5°C Confirm Cancel
LEVEL 3.1.1
Fig. H.31
Central heating circuit - attenuation function
The attenuation parameter can be set for the central heating circuits (CH1 or CH2) that operate in “CONTINUOUS” mode. It should be noted that if a temperature of over 80°C is set on the display, the message “AUTO” will be displayed on the line referring to the circuit set point temperature: this means that climate control mode has been set.
naire disease prevention function is automatically activated, as previously entered in LEVEL 2.1.3 (as shown in F
IG. H.33).
Start Mon20:00 Stop Wed22:00 £ Antilegionella 70°C Confirm Cancel
LEVEL 3.1.1
Fig. H.33
“INFORMATION” mode
The last section provides information relating to:
- system
- installation (monitor)
- zones (function not enabled)
- errors
inizio Lun 20:00
INFORMATION
£Start Mon20:00
Stop Wed22:00
Temp 70°C Attenuat. 5°C Confirm Cancel
LEVEL 3.1.1
Fig. H.32
As regards the value of the attenuation parameter, it’s worth noting that the system behaves as follows:
1. if operating with a fixed set point, the attenuation value is calculated as the difference between the set point and the value entered in the corresponding field on the display;
2. if operating in climate control mode, the attenuation value is calculated as the difference between the set point calcu­lated in climate control mode and the value entered in the corresponding field on the display.
Irrespective of the system operating mode, when a value is set for the attenuation parameter, an attenuation cycle will start whenever the room thermostat opens (set temperature reached). In general, the asterisk (*) indicates that the attenu­ation function is active. For attenuation with fixed set point, the screens on the room control will show the message fi*. For attenuation in climate control mode, the message cl* will be displayed.
Domestic hot water circuit – Legionnaire disease preven­tion function
If this value is over 80°C, the value set for the D.H.W. Legion-
Fine Mer 22:00
£System Temp 70°C
Monitor conferma
Zone cancella
Error
LEVEL 4
Fig. H.34
Information on the system
The first set of information provided concerns the monitoring of the operation of the device, with special focus on the num­ber of slaves installed and the number of burners operating (F
IG. H.35).
inizio Lun 20:00 Fine Mer 22:00
Number slaves 09 Temp 70°C
Burners on 05 conferma
£Slave n°03
SYSTEM
cancella
LEVEL 4.1
Fig. H.35
This screen can also be used to access, by selecting the last line on the display, a section for each individual slave present (LEVEL 4.1.1). The example shown in F slave no. 3. The display shows the following data:
- Central heating flow temperature
- Central heating return temperature
- Flue gas temperature
- Ionization current
- Percentage of fan operation
IG. H.36 refers to
90
Page 97
APPENDIX H - Electrical connections
- Differential pressure switch with flow switch function: ON – if operating
- Two-way valve or pump on the unit (only after having been enabled by the installer): ON if active
- Maximum ionization current
- Operating hours of the slave.
SLAVE 03 £Tem.flow 70 Tem.ret 60 Tem.flue 62 Cor.ion 55 Pwm ven 99% Flow sw on Pump on Max ion 60 Funct. hours 4000
LEVEL 4.1.1
Fig. H.36
Information on the installation: the 3 circuits (1/5)
This section provides important information on the current temperature and the set point in the desired circuit.
In addition, it displays whether the control mode is climate (cl) or fixed point (fi) and, in the former case, whether the attenu­ation function is active (only if the asterisk is displayed “*”).
In reference to the screen in F that:
IG. H.36 (LEVEL 4.2.1), note
room temperaturee (2/5)
Moving the cursor downwards displays further information on the installation. The screen displayed (F outside temperature (in this case 5°C). This also indicates whether the room thermostats in the first and second circuits (Ta1, Ta2) are open or closed (on, off) and whether, for each circuit, the Program schedule is active.
IG. H.38) shows the
2/5 MONITOR Tout 05° Ta1 on progr. on Ta2 off progr. off
LEVEL 4.2.2
Fig. H.38
Information on the installation: various (3/5)
Moving further the cursor downwards displays other informa­tion on the Legionnaire disease prevention function for the do­mestic hot water circuit, the power related to the voltage of the analogue input control signal, if used, and finally the mixing valve. In the example shown (F
1. the Legionnaire disease prevention function is active and is set to a temperature of 70°C.
2. an analogue input control signal is used, which reads a voltage of 8.8 V (otherwise this line is not shown on the display).
3. the mixing valve is closing.
IG. H.39):
3/5 MONITOR Antileg. on 70°C
1/5 MONITOR CH1 on 60°£70° cl* CH2 off 30°£40° fi San on 35°£45° pg
LEVEL 4.2.1
Fig. H.37
1. the probe installed in the high temperature circuit (CH1) reads a temperature of 60°C but the set point temperature that must be reached is 70°C. The system is working in cli­mate control mode (cl) with attenuation active (*).
2. The low temperature circuit (CH2) is not operating. The probe reads a temperature of 30°C, the set point tempera­ture that would need to be reached, if operating, is 40°C, and the system is in fixed point mode (fi) without attenua­tion.
3. The water in the domestic hot water circuit (San) is circu­lating at 35°C and needs to reach a temperature of 45°C. The circuit is working in Program schedule mode (tm). If, for example, the message “ANTILEGIONELLA” were displayed rather than the 45°C, this means that a Legion­naire disease prevention cycle is in progress.
Information on the installation: outside temperature and
Input Potenz 8.8 V Valv_mix closed
LEVEL 4.2.3
Fig. H.39
Information on the installation: the pumps (4/5)
Starting from this screen, information are shown on the status of the various pumps installed. In the example (F following information are provided:
1. the pump that moves the thermal exchanging fluid to the radiators (P1) is operating without priority or difference between the high and low temperature circuits (CH1 and CH2). This depends on and indicates the fact that installer parameter no. 16 has been set (CH priority).
2. the pump in the domestic hot water circuit (P2) is off. The 80% output value refers to the heat required by the system to satisfy the demand in the active circuits.
3. in this case pump 3 (P3) is the main return pump that is cur­rently operating.
Information on the installation: operating hours (5/5)
The final set of information provided relates to the operating hours of the system (in the example equal to 40000 hours). This function will be available starting from MASTER soft­ware version A05.
IG. H.40) the
91
Page 98
APPENDIX H - Electrical connections
4/5 MONITOR
P1 on Preced CH1e2 P2 off Output 80% P3 on P3
Fig. H.40
General
LEVEL 4.2.4
5/5 MONITOR Funct. hours 40000
LEVEL 4.2.5
Fig. H.41
Information on the errors
If faults occur in the system, the room control provides infor­mation on the number of the unit where the error occurred on and the error code. The display shown in the example in Pic­ture H.43 indicates the following information:
1. the third error in the list is type E36 and occurred on unit 12
2. the fourth error is number 255 and occurred on unit 5
3. the fifth error in the list is type A02 and occurred on unit
13.
UNIT ERROR  3 12 E36 4 05 255 £ 5 13 A02
LEVEL 4.4
Fig. H.42
In most cases, the error code may initially not provide all the information required on the type of fault found: however, pressing the confirm button on the corresponding line displays the details of the error code in question. In reference to the screen shown in Picture H.44, for example, it can be seen that error A02 corresponds to the flame lockout, which as a direct consequence does not allow the unit to start.
blocking flame
no ignition
LEVEL 4.4.1
Fig. H.43
92
Page 99
APPENDIX I - Accessories
The accessories listed below are available for separate orders.
Accessory Code
Flue collector kit 1102389
Hydraulic kit for installations < 100 kW 1102399
Hydraulic kit for installations > 100 kW 1102409
APPENDIX I - Accessories
Remote control kit 1102379
Two-ways valve kit 1102429
Injection pump kit 1102419
Room sealed conversion kit Power Plus 50 1102439
Room sealed conversion kit Power Plus 100 1102449
ROOM SEALED CONVERSION KIT POWER PLUS 50
(cod. 1102439)
POLYPROPYLENE PIPES Ø125
(Length 500 mm - cod. 1102909
Length 1000 mm - cod. 1102919
Length 1500 mm - cod. 1102929)
POLYPROPYLENE 90° ELBOW
(Ø50 cod. 1102639 - Ø125 cod. 1102779)
ROOM SEALED CONVERSION KIT POWER PLUS 100
(cod. 1102449)
POLYPROPYLENE PIPES Ø50
(Length 500 mm - cod. 1102669
Length 1000 mm - cod. 1102679)
POLYPROPYLENE 45° ELBOW
(Ø50 cod. 1102689
Ø125 cod. 1102769)
AIR INTAKE AND FLUE DRAIN KIT FOR FLAT ROOF
IN POLYPROPYLENE Ø50
(cod. 1102739)
93
Page 100
APPENDIX I - Accessories
AIR INTAKE AND FLUE DRAIN KIT FOR PITCHED
ROOF IN POLYPROPYLENE Ø50
(cod. 1102759)
STAINLESS STEEL HORIZONTAL TERMINALS KIT
(cod. 1102699)
AIR INTAKE AND FLUE DRAIN KIT (WALL) IN
POLYPROPYLENE Ø50
(cod. 1102719)
CHIMNEY CONNECTION (FLAT ROOF) Ø50
(cod. 1102859)
POLYPROPYLENE FLUE DRAIN TERMINAL FOR
Ø50 PIPE
(cod. 1102849)
CONDENSE EVACUATION KIT Ø50
(cod. 1102799)
CHIMNEY CONNECTION Ø50 + FLASHING PLATE
(PITCHED ROOF)
(cod. 1102879)
94
KIT FLUE COLLECTOR AND CLAPET 50kW Ø125
(cod. 1102819)
Loading...