Beretta EXCLUSIVE 30C, EXCLUSIVE 25C, EXCLUSIVE 35C Installation And User Manual

Please remember to service this appliance annually
RO
MANUAL DE INSTALARE SI UTILIZARE
EXCLUSIVE C
NZ
Gas adaptive condensing boiler
Installation and user manual
INSTALLER AND USER MANUAL
RANGE RATING
This boiler can be adapted to the heat requirements of the system, it is possible to set the range rated parameter as shown in the specific paragraph. If applied the engineer must note the set value on the adhesive label supplied for successive maintenance, engineers to refer to this adjusted value.
EN
0051 51C S4793
Thank you for purchasing this Beretta Exclusive condensing boiler
EXCLUSIVE C complies with basic requirements of the following Directives:
- Gas directive 2009/142/EC
- Efficiency directive: Article 7(2) and Annex III of directive 92/42/ EEC
- Electromagnetic compatibility directive 2014/30/EU
- Low-voltage directive 2014/35/EU
- Directive 2009/125/EC Eco design for energy-using appliances
- Directive 2010/30/EU Indication by labelling of the consumption of energy by energy-related products
- Delegated Regulation (EU) No. 811/2013
- Delegated Regulation (EU) No. 813/2013
Delegated Regulation (EU) No. 814/2013
Within this manual there are sections in red text these should be noted especially where they refer to safety and the prohibition of actions other than by a qualified engineer The manufacturer is not Liable for any failure to observe the requirements set out in this manual or relevant New Zealand code.
Some prohibited actions are also noted by the symbol P
Note : User relevant sections are presented with green text
The user must not perform operations on the safety devices, replacing parts of the product, tamper with or attempt to repair the appliance. These operations must be entrusted exclusively to qualified persons.
Important note regarding service requirements
Servicing of this appliance must be carried out at 12 month intervals
The servicing engineer
Minimum service must include the specific actions listed Pay specific attention to the requirement to replace the burner chamber seal at each service,
-
This instruction manual contains data and information for both the user and the installer. The user of the use of the appliance, must also refer to chapters:
Warnings and safety (Next page)
Maintenance
must pay particular attention to
Installer’s-user’s manual 3-28 Boiler operating elements 40 Electric diagrams 41 Hydraulic circuit 42 Circulator residual head 43
Pages 28 / 40 Service requirements
ENGLISH
3
a
EN
ENGLISH NZ
INSTALLATION MANUAL
1 WARNINGS AND SAFETY
The boilers manufactured are inspected in the smallest detail in
order to protect users and installers against possible injury. After installation check the electrical wiring, in particular stripped parts of leads, which must not protrude from the terminal boards
This installer and user manual constitutes an integral part of this
product.. Make sure it is always kept with the appliance, even if it is transferred to another owner or user, or moved to another heating system. In case of loss or damage, please contact Heat IQ Technical Assistance for a new copy.
This boiler may only be installed and serviced by personnel qualified
in accordance with current regulations.
The installer must instruct the user in the operation of the
appliance and about essential safety regulations.
This boiler must only be used for the application it was designed for.
The manufacturer accepts no liability within or without the contract for any damage caused to people, animals and property due to installation, adjustment and maintenance errors or to improper use.
After removing the packaging, make sure the content is in good
condition and complete. If not, contact the supplier immediately.
The safety valve outlet must be connected to a suitable collection
and drain system. The manufacturer declines all liability for damage caused due to any intervention carried out to the safety valve.
The seal of the condensate drainage connection line must be fully protected against the risk of freezing
Check that the rain water drainage channel of the flue and the
relative connection pipe are free of obstructions.
Dispose of waste by being careful not to harm human health and
without employing procedures or methods which may damage the environment.
At the end of its life, the product should be not be disposed of as solid
urban waste, but rather it should be recycled.
During installation, inform the user that:
- In the event of water leaks, the water supply must be shut off and the Installer contacted immediately
- Periodically check that the operating pressure of the hydraulic system is between 1 and 1.5 bar. If it is not, contact the installer
If the boiler is unused for a long period we recommended
- Turn the main appliance switch and the main system switch to “off”
- Close the fuel and water valves for the heating and domestic hot
water system Drain if there is a risk of freezing
Boiler maintenance must be carried out at least once a year;
s e rv i c in g mu s t b e ca r ri ed o ut by a suitably qualified
competent engineer
The appliance is not to be used by children
It is forbidden to touch the appliance while barefoot or if parts of your body are wet.
Do no activate electric devices or appliances such as switches, household appliances and so on if you notice a smell of Gas. In this case:
- Ventilate the room by opening the doors and windows;
- Close the fuel shut-off device;
- Request the prompt intervention of a Gas fitter or service engineer
Any technical or cleaning operation is forbidden before isolating the appliance from the power supply by turning the power point switch to “OFF” and the main switch of the boiler to “OFF”.
Do not modify the safety or adjustment devices without the
manufacturer’s precise instructions.
.
Do not leave inflammable containers and substances in the room where the appliance is installed.
Do not leave flammable containers and substances in the room where the device is installed.
Do not leave packaging material in reach of children as it may be a potential source of suffocation.
The condensate drain outlet must be run avoiding double trapping
Never carry out any Adjustment of the gas valve.
2 Boiler Description
EXCLUSIVE are equipped with a new ACC (Activate Combustion
Control) system.
This new control system, developed by Beretta, ensures functionality, efficiency and low emissions under any conditions . The ACC system uses an ionisation sensor immersed in the
burner flame, whose information allows the control board to operate the gas valve which regulates the fuel.
This sophisticated control system provides the auto-regulation of the combustion, so there is no need for an initial calibration. The ACC system is able to adapt the boiler to operate with different gas compositions, different outlet pipes lengths and different altitudes (within the specified design limits).
The ACC system can also perform an auto-diagnostic operation that locks out the burner before the permitted upper emissions limit is exceeded.
EXCLUSIVE is a type C condensing wall-hung boiler to be used for
heating and the production of domestic hot water: depending on the fume discharge accessory used, it is classified in categories C13,C13x; C33,C33x; C43,C43x; C53,C53x; C63,C63x; C83, C83x; C93, C93x. In configurations prefix C, this appliance can be installed in any type of room (There are no limitations due to ventilation conditions or room volume).
EXCLUSIVE
4
PARAMETERS
UM
HEATING CIRCUIT
WATER
FILLING WATER
pH value 7-8
-
Hardness
°F - 15-20
Appearance -
clear
3 INSTALLATION
3.1 Installation regulations
Installation must be carried out by qualified persons, in compliance with the following reference standards:
- UNI 7129-7131
- CEI 64-8.
- NZ building and plumbing codes with reference to NZ standards
POSITION
EXCLUSIVE - a wall-hung boiler for heating and for the production of DHW.
with f lue gas discharge pipe and pick-up of combustion air from outside. It does not require an air intake point in the installation area. It must be installed using concentric pipes, or other types of discharge designed for condensing boilers with an airtight chamber.
MINIMUM CLEARANCES
To ensure access to the boiler for normal maintenance operations, respect the minimum installation clearances envisaged.
For correct appliance positioning, bear in mind that:
- It must not be placed above a cooker or other cooking device
- Heat-sensitive walls (e.g. wooden walls) must be protected by use of a
cement fiber board
It is ESSENTIAL to provide the necessary space for the introduction of an
analyser for the combustion analysis check. In fig. 6a P44 a
sample drawing where distances between boiler and cabinet/niche were obtained using a 300mm length analyser probe.
3.2 Removing the casing
To access the components inside, remove the casing as indicated below:
-
Locate and unscrew the 2 screws (A - f casing.
-
The noise absorbing panels inside the front and side walls ensure the airtight seal for the air supply duct in the installation
environment. It is therefore ESSENTIAL after dismantling operations to correctly reposition the components so as not to compromise the boiler’s operation.
WARNING If damaged the front panel must be replaced.
Prior to ignition, make sure that the boiler is designed to operate
It is important to highlight that in some cases the flue is under
By leveraging the fixing clips (C - fig. 13), unhook the lower part of the casing now (B - fig. 13 P44), then
Under the safety valve, install a tundish with the corresponding discharge in the event of leaks due to the overpressure of the heating system. The domestic cold input must not exceed 6 Bar
with the gas available; this can be checked by the wording on the packaging and by the adhesive label indicating the gas type.
pressure, so the joints of the various elements must be airtight.
lift the casing upwards to release it from the top tabs
remove the face panel.
3.3 Positioning and hydraulic
The boiler comes as standard with a boiler hanger jig. The position and dimensions of hydraulic fittings are shown in Fig 8/9 on page 44 , proceed as follows:
- Fasten the boiler Bkt (F) to the wall and use a spirit level to make sure it is perfectly horizontal
- Use the jig to identify the required pipe centers
-
The pipe template and hanger can then be removed
Install pipework
Using the valve kit supplied . include a magnetic filter (not supplied) in the return line . A magnetic filter is a requirement of warranty Note The 1st 1m (minimum) of pipe used for the flow and return line should be run in copper.
The condensate and relief drain outlet must be run avoiding double trapping
The system attached must include a low point drain for flushing the system
3.4 Gas connection
Connection of the gas supply must be carried out in compliance with current NZ installation standards. By a certifying Gas fitter
Ensure the supply pipework supports the delivery of the relevant Gas being used and is correctly sized.
If the appliance is to use LPG attach the Gas type label supplied
( Ref fig. 6-6a Page 44)
ig.
13) that f
ix
the front
connections
form the jig .
3.5 Electrical connections
(
Figure 10/11 Page 45)
Low voltage connections
Carry out the low voltage connections as follows:
- Use the external cable box supplied as standard
- Unscrew the fixing screws of the cover (V)
- Carry out the connections as shown in fig. 11
It is recommended to use wires with section not exceeding
0,5mm2. In case of TA or TBT connection, remove the respective shunts
(fig. 12).
- Close the box with the screws that were previously removed
- Press the two tabs on the sides of the box to place it correctly in its housing in the boiler sliding upward within the guide rails and tighten the safety screw (V1)
If the low voltage electrical connection box is not connected the boiler
will not ignite.
High voltage connections
The connection to the mains supply must be made via a standard power point. The appliance works with alternating current at 230 Volt/50 Hz, and is in compliance with Standard EN 60335-1. (NZ Compliant) It is obligatory to make the connection with a safe ground/earth,
The manufacturer will not be liable for any damage resulting incorrect or
absent earth connection.
.
3.6 Flue gas exhaust and combustion air suction
To evacuate combustion products, refer to UNI 7129-7131. Always comply with local standards of the Fire Department, and with possible local municipal dispositions.
The release of combustion products is assured by a centrifugal fan. The control board constantly checks that it is operating correctly. It is essential for evacuating fumes and induction of boiler combustion air that only original flue pipes are used and that the connection is made correctly as shown in the instructions provided with the flue gas accessories.
A single flue can be connected to several appliances provided that every appliance is the condensing type.
The boiler is a C-type appliance (with airtight chamber), and must therefore have a safe connection to the flue gas discharge pipe and to the combustion air suction pipe; these carry their contents too and from outside, and are essential for the operation of the appliance. Both concentric and twin terminals are available.
3.7 Filling the heating system (fig. 16)
Note:
Even though the boiler is fitted with a semi-automatic filling device, the first filling operation must be carried out by using the filler tap (B) with the boiler in the off position.
Filling
- Open the caps of the lower (A) automatic air vent valve by two or
- Open the filling tap (B) until the pressure indicated by the water pressure
-
On going venting of the boiler takes place automatically via the two
3.8 Flush and Protect
In the case of a new installation or replacement of the boiler, it is necessary to pre flush the heating system
To ensure the device operates well and is protected from scale and corrosion add inhibitors, antifreeze etc as required and check the parameters in the table are within the values indicated.
Failures as result of not flushing the system will not be covered.
. must be carried out when the system is cold, as follows.
Three turns; to allow a continuous venting of the air, leave valve
A open.
gauge is between 1 and 1.5 bar Re-close the filling tap.
automatic vent valves positioned on the circulator & top point
ENGLISH
5
Maximum straight length
Pressure drop
25C
30C
35C
bend
45°
bend
90°
Concentric pipe Ø 60-100 mm (horizontal)
10 m 10 m 8 m 1,3 m
1,6 m
Concentric pipe Ø 60-100 mm (vertical)
11 m 11 m 9 m 1,3 m
1,6 m
Concentric pipe Ø 80-125 mm
25 m
25 m
20 m
1 m
1,5 m
Twin pipe Ø 80 mm
70+70 m
50+50 m
35+35 m
1 m
1,5 m
Flue Suction/discharge pipes length table
“Straight length” means with terminals and joints but without bends.
The boiler is supplied without the flue, Allowing you to use the accessories for condensing appliances that most suit the installation characteristics (see catalogue).
. It is compulsory to use the Beretta flue components.
Flue gas outlets are potential sources of danger. Ensure they remain clear
The use of longer flue causes a minor loss of output of the boiler
Make sure the flue gas discharge pipe is tilted 3° towards the boiler.
The boiler is designed to take in and dispose of flue gas condensate and/or meteoric water condensate deriving from the flue gas discharge system using its own siphon.
Flue installation
Concentric pipes (ø 60-100 mm)
- Position the bend so that the Ø 60 pipe goes fully into the flue gas turret of the boiler.
- Once positioned, make sure that the 4 notches (A) on the flange connect to the groove (B) on the Ø100 of the bend.
- Fully tighten the two locking terminals of the flange (C) so the bend itself is restrained.
-
Twin pipes (ø 80 mm)
The combustion air suction pipe should be selected from the two inputs, remove the closing plug fixed with the screws and deflector.
- Position the adaptor on the flue gases pipe so that the Ø 60 pipe goes fully into the flue gases turret of the boiler
- Once positioned, make sure that the 4 notches (A) on the flange connect to the groove (B) on the Ø100 of the adaptor.
- Fully tighten the two locking terminals of the flange (C) so the adaptor itself is restrained.
- For Twin pipes in NZ seek advice from heat IQ
SPIECIAL ITEM
- see graphs fig. 18
ix
Concentric pipes (ø 80-125 mm)
- Position the adaptor so that the Ø60 pipe goes fully into the f lue turret of the boiler.
- Once positioned, make sure that the 4 notches (A) on the flange connect to the groove (B) on the Ø100 of the adaptor.
- Fully tighten the two locking terminals of the flange (C) so the adaptor itself is restrained.
-
Then f
it
the Ø 80-125 adaptor kit on the vertical fitting.
the specific air
6
EXCLUSIVE
a
LED status
CIRCULATOR status
Consumption in % of MAX P1 (*)
Green LED on + 1 yellow LED on
Operating at minimum
0~25
Green LED on + 2
yellow LEDs on
Operating at
minimum-medium
25~50
Green LED on +
3 yellow LEDs on
Operating at medium-
maximum
50~75
Green LED on +
4 yellow LEDs on
Operating at maximum
100
LED status
ALARM
description
Status
CIRCULATOR
Possible
SOLUTION
Red LED on +
1 yellow LED
on (LED 5)
The drive shaft is
jammed
Start attempt
every 1.5
seconds
Wait or unjam
the drive shaft
Red LED on +
1 yellow LED
on (LED 4)
Low input
voltage
Warning only. The circulator
continues to
operate
Check the
input voltage
Red LED on +
1 yellow LED
on (LED 3)
Electrical power
supply fault or
faulty circulator
The circulator is
stopped
Check the electrical
power supply or
replace the
circulator
3.9 Elimination of air from the heating circuit
and
from the boiler
(fig. 7)
During initial installation, or in the event of extraordinary maintenance, you are advised to perform the following sequence of operations:
1. Open by two or three turns the automatic relief valve cap (A) and leave
it open.
2. Open the system filling tap located under the appliance.
3. Switch on the electricity supply to the boiler, leaving the gas tap turned
off.
4. Activate a heat request via the room thermostat or the remote control
panel, so that the 3-way valve goes into heating mode.
5. Activate a request for DHW as follows: open a tap for 30 seconds so
that the three-way valve cycles from heating to DHW and vice versa for about ten times (in this situation, the boiler will go into alarm due to lack of gas, simply reset it whenever this is proposed).
6. Continue the sequence until no more air is coming from the air vent
valve.
7. Check the system pressure level is correct (the ideal level is 1 bar).
8. Turn off the system filling tap.
Turn on the gas tap and ignite the boiler
3.10
Draining the heating system
Before draining, switch off the electricity supply by turning off the main switch of the system.
- Close the heating system’s flow and return valves.
- Connect a hose to the system drain valve (C).
- Manually loosen the system drain valve (C).
-
(fig. 16)
3.11 Emptying the domestic hot water system
If there is risk of frost, the domestic hot water system must be emptied in the following way:
- turn off the main water inlet supply tap on the boiler
- turn on all the hot taps to drain.
3.12 Circulation pump settings
Modify only in specific circumstances
Circulator residual discharge head
The boiler is equipped with an already hydraulically and electrically connected circulating pump, its useful available performance is indicated in the graphs at page 43. The circulator comes set from the factory with a 6 meter discharge head curve. The boiler is equipped with an anti-seize system which starts up an operation cycle every 24 hours in standby mode
The “anti seize” function is active only if the boiler is electrically powered.
Operating the circulation pump without water is strictly forbidden.
If you need to use a different curve you can select the desired level on the circulator. The main characteristics and the way to set up their desired operation are listed. Below
3.12.1 Pump on board User interface
The user interface is made up of a button (A), a two-colored red / green LED (B) and four yellow LEDs (C) arranged in a row.
The user interface allows the operating performance to be viewed (operating status & alarm status) , it also allows the circulator operating modes to be set. The performance, indicated by the LEDs (B) and (C) is always visible during normal operation of the circulator whereas settings can be carried out by pressing the button (A).
3.12.2 Operating status indication
When the circulator is in operation the LED (B) is green. The four yellow LEDs (C) indicate the electrical energy consumption (P1) as shown in the following table.
(*) For the power (P1) absorbed by the circulator see the indications in the “Technical Data” table.
3.12.3 Alarm status indication
If the circulator has detected one or more alarms the two-colour LED (B) will be red. The four yellow LEDs (C) indicate the type of alarm as shown in the following table.
If there are several alarms the circulator will display only the alarm with
the highest priority.
3.12.4 Display of active settings
With the circulator powered, press briefly on the button (A) to view the active configuration of the circulator. The LEDs indicate the active settings. In this phase no variations can be made to the circulator configuration. Two seconds after the button (A) has been pressed the user interface returns to the normal operating status display.
3.12.5 Key lock function
The purpose of the key lock function is to prevent accidental modifications to the settings or the improper use of the circulator. When the key lock function is activated, long-pressing the button (A) is
prevented. This prevents the user from entering the circulator’s operating
modes setting section. Enabling/disabling the key lock function is achieved by pressing the button (A) for more than 10 seconds. During this step all of the LEDs (C) will lash for 1 second.
7
ENGLISH
A. Operating status display B. Settings display C. Settings
Configuration
B
C
A
D
E
25-30 kW
F
35 kW
D
F
E
3.12.6 Changing the pump operating mode
In normal operating conditions the circulator works with the factory settings or the last settings carried out.
To change the configuration:
Ensure that the key lock function is deactivated. Press the button (A) for more than 2 seconds until the LEDs begin to flash. Short-press the button (A) within 10 seconds and the user interface will move on to display the next settings. The various available settings will appear in a cyclic sequence. If the button (A) is not pressed, the last setting will be stored.
IMPORTANT
If the 3 = (5 metres) or 4 = (4 metres) curves are set the bypass must be replaced with the one supplied,
Follow the procedure indicated below:
Remove boiler electrical power by setting the system’s main switch to off. Close the system taps and empty the boiler heating circuit. Extract the bypass body cover fixing spring (D). Extract the bypass body cover (E). Replace the bypass valve (F) with the one included with the boiler. Refit the bypass body cover and its spring.
If the button (A) is pressed you can move back to the “active settings display” again and check that the LEDs (B) and (C) indicate (for 2 seconds) the last setting carried out. If the button (A) is not pressed for more than 2 seconds the user interfaces
switches to the “Operating status display”.
The available settings are shown in figure along with related representation of LED (B) and (C).
8
EXCLUSIVE
LED
Light signal indicating the operating status of the boiler. Can be red or green (see specific paragraph)
REC10
Boiler control panel
Key area
ok= confirm
back= return to the previous screen
cancel selection
return to the main screen (press > 2 sec.)
up= allows you to choose between the options PLANT-STATE-SET-INFO-MENU and to surf through the
submenus scrolling upwards
down= allows you to choose between the options PLANT-STATE-SET-INFO-MENU and to surf through the
submenus scrolling down
This icon indicates that the OFF operating status mode has been set. Each ignition request is ignored except for the anti-freeze function. The pump anti-lock, 3-way valve and anti-freeze function remain active.
This icon indicates that WINTER mode has been selected (HEATING function enabled). If a heating request from the main zone is in progress, the icon will be flashing.
This icon indicates that the circuit for domestic hot water production is enabled. When a domestic hot water request is in progress, the icon flashes. The P at the top of the domestic hot water icon indicates that the boiler preheating function is enabled; the P when flashing indicates that a preheating request is in progress.
When the “central heating programming timing” is enabled this icon indicates that the system heating (main zone) is in AUTOMATIC mode (the management of the heating requests follows what has been set with the timer). If the heating function is not enabled during the current time frame, the icon will be crossed out.
When the “central heating programming timing” is enabled this icon indicates that the system heating (main zone) is in MANUAL mode (the management of the heating requests does not follow what has been set with the programming timing, but it is always active).
OFF
This icon indicates that the system (main zone) has been set to off (not active).
This icon indicates that the system is detecting the presence of a flame.
This icon indicates the presence of an anomaly, and is always flashing.
4 CONTROL PANEL (REC10)
The REC10 remote control has the function of machine interface, Displaying the system and providing access to the parameters. The middle of the main screen displays the temperature of the domestic hot water probe, unless there is a heat request is in progress, in this case the delivery temperature of the boiler at that particular time is displayed.
The value expressed in bar refers to the system’s water pressure.
The top of the screen shows the information regarding the current date and time, as well as the outdoor temperature, if available.
On the left and right sides are displayed the icons indicating the status of the system; their meaning is as follows.
Pressing the keys “up” and “down” it is possible to choose from among the following options:
PLANT: a scrolling message on the display can indicate the temperature of the domestic hot water probe rather than the flow sensor of the boiler
STATE (when the SYSTEM SCREEN is selected): to set the status of the boiler (OFF, SUMMER or WINTER) and, when managed by the room thermostat, the operating mode of the main area in heating mode (ON or OFF if the time schedule is disabled, AUTO according to hourly programming, MANUAL or OFF if programming timing is enabled)
SET: to establish the heating or hot water set point value or for activating preheating
INFO: to display the value of the system variables
MENU: to access the system’s configuration menus
The configuration MENU is organized with a multi-level tree structure. With the “ok” key you can access the selected submenu, with the “up” and
“down” keys it is possible to navigate through the submenus, while the “back” key takes you back to the previous level.
An access level has been fixed for each submenu: USER level, always available; TECHNICAL level, password protected. Below is a summary of the MENU tree structure of the REC10.
Some of the information might not be available on the REC10
depending on the access level, the status of the machine or the system configuration.
LED
9
ENGLISH
DEFAULT VALUE
FACTORY SE T
MINIMUM
VALUE
MAXIMUM
VALUE
ACCESS LEVEL
NOTES
SET
VALUE
USER
USER
ITALIANO / EN GLISH
USER
5 min 1 min 15 min USER
USER
USER
Only if POR = 1
USER
Only if POR = 1
USER
Only if POR = 1
USER
USER
INSTALLER
INSTALLER
INSTALLER
MAIN MAIN / ZONE1 / ZON E2
INSTALLER
ITRF05/AKM
ITRF05/AKM
BE16
INSTALLER
Only M AIN zone
THERMOSTAT
THERMOSTAT / TEMPERATURE PROBE /
REC10 MASTER / REC10 SLAVE
INSTALLER
- - 1 6
INSTALLER
Only zones wit h ACTU ATION = BE16
DIRECT ZONE
DIRECT ZONE
MIXING ZONE
INSTALLER
Only zones wit h ACTUATION = BE16
HIGH TEMP.
HIGH TEMP.
LOW TEMP. INSTALLER
40°C (AT) 20°C (BT)
20°C
MAX C H SET INSTALLER
80,5°C ( AT)
45°C (BT)
MIN CH SET
80,5°C ( AT)
45°C (BT)
INSTALLER INSTALLER
5 0 99
SERVICE
Only mixing z ones with AC TUATION=BE16
10 0 99
SERVICE
Only mixing z ones with AC TUATION=BE16
120 sec
0 sec 240 sec
SERVICE
Only mixing z ones with AC TUATION=BE16
140 sec
0 sec 240 sec
SERVICE
Only mixing z ones with AC TUATION=BE16
55°C
0°C
100°C
SERVICE
Only BT zones with ACTUATION =BE16
0min 0min 240min
SERVICE
Only BT zones with ACTUATION =BE16
2min
VALVE RUN
240min
SERVICE
Only BT zones with ACTUATION =BE16
2min 0min 240min
SERVICE
Only BT zones with ACTUATION =BE16
6°C -20°C 50°C
SERVICE
Only zones wit h ACTU ATION = BE16
5°C 1°C 20°C
SERVICE
Only zones wit h ACTU ATION = BE16
10°C
0°C
100°C
SERVICE
Only zones wit h ACTU ATION = BE16
0 (1 if REC10
in the AMBIENT)
0
1
INSTALLER
INSTALLER
INSTALLER
0,0°C
- 6,0°C 6,0°C
INSTALLER
INSTALLER
MENU
SETTINGS
TIME SCHEDULE
TIME & DATE
LANGUAGE
BACKLIG HT
MAIN
ZONE1
ZONE2
DHW
DHW H EAT PUMP
TECHNI CAL
INSTALLATION
ZONES MANAGER
MODIFY ZONE
ACTUATION TYPE
REQUEST TYPE
BE16 ADDR ESS
HYDRAULIC CONF
ZONE TYPE
MIN CH SET
MAX C H SET
CHANGE NAME
PI - PROPORTIONAL
PI - INTEGRAL
VALVE RUN
CLOSING AT POWER ON
OUTLET OVER
OUTLET OVER TEST TIME
OUTLET OVER WAIT TIME
OUTLET OVER REST TIME
FREEZE PROT TEMP
FREEZE PROT OFFSET ZONE
FREEZE PROT T EXT
POR
ADD ZONE
DELETE ZONE
SENSOR CALIBRATION
SYSTEM RESET
10
EXCLUSIVE
DEFAULT VALUE
FACTORY SE T
MINIMUM
VALUE
MAXIMUM
VALUE
ACCESS LEVEL
NOTES
SET
VALUE
INSTALLER
3 min 0 min 20 min INSTALLER
5°C
2°C
10°C
SERVICE
5°C
2°C
10°C
SERVICE
3°C
2°C
10°C
SERVICE
3°C
2°C
10°C
SERVICE
5°C
0°C
10°C
SERVICE
0°C
0°C
6°C
SERVICE
0°C
0°C
10°C
SERVICE
85 41 100 SERVICE
FUNC. NOT ACTIVE
FUNC. NOT ACTIVE
FUNCTI ON ACTIVE
INSTALLER
RELATED
RELATED
ABSOLUTE
INSTALLER
Only in instantaneous confi guration
DEACTIVATE F UNC.
DEACT IVATE FUNC .
ACTIVA TE FUNCTI ON
INSTALLER
0 0 1 SERVICE
6sec 1sec 255sec
SERVICE
If CH DELAY POST- DHW = 1
1 0 1 SERVICE
1 0 1
SERVICE
Only if PRESS TRANSDUCE R = 1
0,6 0,4 1
SERVICE
Only if LOAD ENABLE = 1
0 0 1
INSTALLER
Only if managed by th e contr ol boar d
INSTALLER
MAIN MAIN / ZONE1 / ZON E2
INSTALLER
80,5 °C (AT)
45 °C ( BT)
MIN CH SET
MAX C H SET
INSTALLER
If EXTERNAL PROBE NOT connected
FUNC. NOT ACTIVE
FUNC. NOT ACTIVE
FUNCTI ON ACTIVE
INSTALLER
If EXTERNAL PROBE connected
2,0
1,0
3,0
INSTALLER
If EXTERNAL PROBE connected,
request type TA and z one type AT
0,4
0,2
0,8
INSTALLER
If EXTERNAL PROBE connected,
request type TA and z one type BT
2,0
0,1
5,0
INSTALLER
If request type AMBIENT P ROBE
or REC10
10
0
20
INSTALLER
If request type AMBIENT P ROBE
or REC10
20°C 20°C 40°C
INSTALLER
If request type AMBIENT P ROBE
or REC10
18°C
4°C
20°C
INSTALLER
5min 5min 20min
INSTALLER
Only if EXTERNA L PROBE connected
20 0 255
INSTALLER
Only if EXTERNA L PROBE connected
MAX C H
MIN MAX C H INSTALLER
INSTALLER
see MULTIGAS TABLE
1500 R PM
3000 RPM
INSTALLER
see MULTIGAS TABLE
5500 R PM
9999 R PM
INSTALLER
see MULTIGAS TABLE
MIN MAX INSTALLER
see MULTIGAS TABLE
MIN MAX INSTALLER
PARAMETERS
TIMER OFF CH
HYST ON HIGH T EMP
HYST OF F HIGH TEMP
HYST O N LOW TEMP
HYST OF F LOW TEMP
SP INCR HIGH TEMP
SP INCR LOW TEMP
INCR C OOLING SP
PUMP DUTY CYCLE
RESET TIMER S CH
DHW THERMO STAT
SLIDIN G OUTLET
CH DELAY POST-DHW
CH DELAY TIME
PRESS TRANSDUCER
LOAD ENABLE
START LOADING VALUE
PREHEATING
THERMOREGULATION
CLIMATIC CURVES
FIXED SET POINT
NIGHT COMP
CURVE SLOPE
AMBIENT INFLUENCE
OFFSET
COOLING
RANGE RATED
CALIBRATION
BUILDI NG TYP E
OUTDOOR R EACTIVITY
MIN
MAX
RLA
MAX CH
11
ENGLISH
DEFAULT VALUE
FACTORY SE T
MINIMUM
VALUE
MAXIM UM
VALUE
ACCESS LEVEL
NOTES
SET
VALUE
INSTALLER
INSTALLER
INSTALLER
MAX
INSTALLER
RANGE RATED
INSTALLER
MIN
INSTALLER
Current speed
MIN MAX INSTALLER
WEEKLY FUNCTION
F. NOT ACTIVE / DAILY FUNCTION /
WEEKLY FUNCTION
INSTALLER
ENABLE FUN.
ENABLE FUN.
DISABLE FUN. SERVICE
SERVICE
SERVICE
INSTALLER
Only if VENT C YLCE in progress
INSTALLER
INSTALLER
Only in instantaneous confi guration
INSTALLER
INSTALLER
50°C
37,5°C
60°C
INSTALLER
Only if HE AT PUM P enabled to DHW
7°C 0°C 100°C
SERVICE
Only if HE AT PUM P enabled to DHW
5°C 1°C 20°C
SERVICE
Only if HE AT PUM P enabled to DHW
INSTALLER
Only if solar system is not configured
INSTALLER
INSTALLER
60°C 10°C 130°C INSTALLER
8°C
DELTA T OFF
30°C INSTALLER
4°C
4°C
DELTA T ON INSTALLER
0 min 0 min 199 min INSTALLER
(- -)
(- -) / -3 0°C 0°C
INSTALLER
110°C
COLL. T PROT
180°C INSTALLER
110°C 80°C.
T MAX COLL. INSTALLER
40°C
T LOCK 95°C INSTALLER
35°C -20°C
COLL. T AUTH
INSTALLER
0 min 0 min 30 min INSTALLER
FUNC. NOT ACTIVE
FUNC. NOT ACTIVE
FUNCTIO N ACTIVE
INSTALLER
OFF OFF / ON / AU TO
INSTALLER
SWEEP ER
ANTI-LEGIONELLA
VENT C YCLE
ACTIVATE FUN CTIO N
DEACTIVATE FUNCTION
MAX SPEED
RANGE RATED SPEED
MIN SPEED
CHANG E FAN SPEE D
DISABLE FUNCTION
ENABLE FUNCTION
STOP FUNCTION
EXHAUST PROBE RESET
ADD WATER TANK
WATER TANK
ADD SOLAR PLANT
SOLAR
REMOVE WATER TANK
WATER TAN K SETPOINT
TANK FROST PROTECT
TANK FR PROT OFFSET
REMOVE SOLAR PLANT
T MAX TANK
DELTA T ON PUMP
DELTA T OFF PUMP
INTEGRATION DELAY
COLLECTOR T MIN
COLLECTOR T M AX
COLLECTOR T PROT
COLLECTOR T AUTH
COLLECTOR T LOCK
PWM COLL PUMP
TANK C OOLING
SOLAR PUM P STATE
12
EXCLUSIVE
DEFAULT VALUE
FACTOR Y SET
MINIMUM
VALUE
MAXIMUM
VALUE
ACCESS LEVEL
NOTES
SET
VALUE
INSTALLER
Only if heat pump not configured
INSTALLER
INSTALLER
Only if heat pump configured
USE BUS
USE BUS
USE FR EE CO NTACTS
SERVICE
DEACTIVATE FUNCTION
FUNCTIO N ACTIVE
DEACTIV ATE FUNCTION
INSTALLER
DHW FUNCTION
NOT ACTIVE
DHW FUNCTION
ACTIVE
DHW FUNCTION
NOT ACTIVE
INSTALLER
1°C
0°C
6°C
SERVICE
DEACTIVATE FUNCTION
FUNCTION ACTIVE
DEACTIV ATE FUNCTION
INSTALLER
100% 50% 100% SERVICE
5°C
-5°C
20°C
INSTALLER
5°C
-5°C
20°C
INSTALLER
-10°C
-20°C
10°C
INSTALLER
30min
1min 240min SERVICE
30min
1min 240min SERVICE
2min 1min 60min SERVICE
2min 1min 60min SERVICE
5°C
0°C
10°C
SERVICE
0h 0h 24h SERVICE
60sec
1sec 300sec SERVICE
AUTO ON AUTO INSTALLER
60°C
20°C
60°C
SERVICE
10°C
0°C
25°C
SERVICE
SERVICE
INSTALLER
DEACTI VATE F.
DEACTI VATE F.
ACTIVATE F.
INSTALLER
INSTALLER
INSTALLER
SERVICE
20°C
15°C
30°C
SERVICE
35°C
30°C
55°C
SERVICE
SERVICE
NG
NG/LPG
SERVICE
A
A/B/C
SERVICE
RESTORE
RESTORE
RESET SERVICE
SERVICE
ADD HEAT PUMP
HEAT PUMP
REMOVE HEAT PUM P
USE FRE E CONTACTS / USE BUS
ENABLE / DISABLE COOLING
USE FO R DHW / DON'T USE FOR DHW
ANTI FR EEZE DELTA SET
ENABLE / DISABLE NIGHT REDUCT
REDUCED FREQUENCY
MIN OUTDOOR TEMP
MIN DHW OUT TE MP
MIN EMERG OUT T
BOILER INTEGR DELAY
HP INTEGR DELAY
BOILER WAITING
HEAT PUMP WAITING
INTEGRATION OFFSET
WINTER SUMMER DELAY
WARNING VALIDATION
ENABLE CIRC STATE ON/ AUTO
DHW H P SETPOINT
DHW O FFSET
ENABLE ALARM HISTORY
ALARM HISTO RY
SCREED HEA TING
COMBUSTION CHECK
SYSTEM INFO
DEACTI VATE FUNCTION
ACTIVATE FUNCTION
FUNCTION S ETTINGS
GAS TYPE
BOILER TYPE
COMBUSTION OFFSET
TFMIN
TFMAX
13
ENGLISH
FRI
PLANT
18/05/2013 12:17
MENU
1.3
bar
STATE
30
°C .3
INFO SET
HOT WATER TEMPERATURE
FRI
MENU
18/11/2013 12:17
SETTINGS
SELECT OPTION
MENU
SETTINGS
TECHNICAL
SELECT OPTION
the level of the tree menu, then press the key
INSERT PASSWORD
00
4.1 Access to the technical parameters
Through the REC10 (controller) it is possible to access, using the TECHNICAL menu, a series of parameters that can be programmed to allow you to personalise the operation of the boiler:
- Keep the keys and pressed at the same time to enter the
password menu (about 5 sec)
- Using the keys and select the value of the password to
access the INSTALLER or SERVICE authorisation level, depending on
5
-
-
-
-
- select TECHNICAL with the keys and , confirming the
selection with the key
- Access the desired menu and change/view the parameter concerned
(see the menu tree on page 8).
It is possible to return to the start page at any time by keeping the key “back” pressed for at least 2 seconds.
5.1
14
EXCLUSIVE
5.2 Initial Programming
At start up the control displays an initial screen showing the firmware version.
Pressing “ok” a guided procedure is started for configuring the system; select the desired options with the “up” and
When this screen is presented select FROM AKM and confirm OK
Set the TIME and DATE confirming each parameter by pressing ok to confirm
b 1 a
5 COMMISSIONING
5.1 Preliminary checks
First ignition must be performed by a qualified competent engineer.
Before starting the boiler, check:
- That supply networks (electricity, water, gas) correspond to the data
- That the flue pipes and air suction pipes are installed correctly
- that spacing conditions for regular maintenance are guaranteed if the boiler is placed inside or between items of furniture
- The Gas system is sound
- That the fuel flow rate corresponds to values required by the boiler
- That the fuel supply system is sized to provide the correct low rate to the boiler, and that it has all the safety and control devices required
- That the circulator rotates freely because, occasionally
from new or after a long period of dormancy the impeller can stick. See below
Releasing of the circulating pump shaft
- Insert a screwdriver in hole (1) of the circulator.
- Press (a) and turn with Phillips screwdriver (b) to release the pump shaft
Perform this operation with caution to avoid damaging components.
SLAVE
MASTER
Select MASTER from the next screen and ok to confirm
15
ENGLISH
TIMER OFF CH
3
MIN
TIMER OFF CH
RESET TIMERS CH
DHW THERMOSTAT
PREHEATING
FRI
PLANT
18/05/2013 12:17
MENU
1.3
bar
STATE
42
°C
INFO SET
HOT WATER TEMPERATURE
INSTALLER
RESET TIMERS CH
FUNCTION NOT ACTIVE
FUNCTION ACTIVE
INSTALLER
DHW THERMOSTAT
RELATED
ABSOLUTE
INSTALLER
Each time that the boiler is powered an automatic venting
cycle is carried out lasting 2 min. To interrupt the vent cycle, carry out the procedure explained in the section “5.3 First commissioning”.
- Set the boiler to OFF from REC10 selecting the STATE
menu and then BOILER.
Through the control it is possible to access using the TECHNICAL menu a series of parameters that can be programmed allowing you to personalize the operation of this appliance based on the type of system to which it is attached.
set parameters according to the desired operating mode
CUSTOMISATION
Configuring the boiler to suit the system
- TIMER OFF CH
This parameter allows you to change the TIMER OFF CH, regarding the delay time introduced for re-igniting the burner in the face of an off due to the heating temperature being reached. The factory setting for this parameter is 3 minutes and can be set to a value between 0 min and 20 min selecting as desired with the “up” and “down”, keys confirming the selection.
In all cases at least step 5.2.1 must be followed
5.2.1
Typical Boiler configuration
- Access the technical parameters as explained in the section “4.1 Access to the technical parameters”.
- With the “up” and “down” keys select PARAMETERS, confirming the selection.
- Select from among the following options with the “up” and “down”, keys, confirming the selection.
- RESET TIMERS CH
This parameter allows you to reset the REDUCED HEATING MAXIMUM OUTPUT TIMING, during which the speed of the fan is limited to 75% of the maximum heating output that has been set, and the TIMER OFF CH. The factory setting for this parameter is FUNCTION NON ACTIVE, select FUNCTION ACTIVE using the keys “up” and “down”, confirming the selection for resetting the timings.
- DOMESTIC HOT WATER THERMOSTAT
This parameter allows you to set the type of DOMESTIC HOT WATER THERMOSTAT. The factory setting for this parameter is RELATED, i.e. for domestic hot water the boiler switches off at set point +5°C and restarts at set point +4°C. To select the ABSOLUTE values, where the boiler for domestic hot water will still switch off at 65°C and restart at 63°C, use the keys “up” and “down”.
Loading...
+ 35 hidden pages