TECHNICAL DATA _______________________________________________________ 8
Dimension ________________________________________________________________________________________ 8
Output range ______________________________________________________________________________________ 9
Working field _____________________________________________________________________________________ 10
SKELETON DIAGRAMS _________________________________________________ 11
MOUNTING OF THE BURNER ___________________________________________ 12
Inspection of gas assembly ________________________________________________________________________ 12
Adjustment of the positiion of the shrouded disc in the blast tube _____________________________________ 12
ELECTRIC EQUIPMENT ________________________________________________ 13
Wiring diagram LME22 (BG550/BG650) 2-Stage _____________________________________________________ 13
List of components _______________________________________________________________________________ 14
Function LME22 __________________________________________________________________________________ 14
Wiring diagram LME22 (BG550/BG550LN/BG650) Modulating _________________________________________ 15
List of components _______________________________________________________________________________ 16
Function LME22 __________________________________________________________________________________ 16
Control diagnosis under fault conditions and lockout indicatio ________________________________________ 17
Gas burner control: LMG ... _______________________________________________________________________ 17
MEASURES AND CHECKS BEFORE START UP ___________________________ 18
DETERMINATION OF GAS VOLUME FOR THE INSTALLATION ______________ 21
GAS SOLENOID VALVE DUNGS MVD ____________________________________ 22
OPERATION AND ASSEMBLY INSTRUCTIONS ____________________________ 23
Double solenoid valve Type DMV-D.../11 Type DMV-DLE.../11 _________________________________________ 23
DMV 525/11 ______________________________________________________________________________________ 24
Gas pressure regulator Type FRS ___________________________________________________________________ 26
Technical data ____________________________________________________________________________________ 33
Mounting of impulse lines _________________________________________________________________________ 33
2
Page 3
DAMPER MOTOR 2- STAGE _____________________________________________
Air adjustment____________________________________________________________________________________ 34
Releasing button _________________________________________________________________________________ 34
34
DAMPER MOTOR MODULATING ________________________________________ 35
Air adjustment____________________________________________________________________________________ 35
Releasing button _________________________________________________________________________________ 35
GENERAL INSTUCTION_________________________________________________ 36
Adjustment of burner _____________________________________________________________________________ 36
Service __________________________________________________________________________________________ 36
Flame monitoring and measurement of ionisation current _____________________________________________ 37
UV- detektor _____________________________________________________________________________________ 38
Adjustment of air pressure switch __________________________________________________________________ 39
Adjustment of min. gas pressure switch ____________________________________________________________ 39
Adjustment of max. gas pressure switch ____________________________________________________________ 39
LEAKAGE CONTROL, DUNGS VPS 504 SERIE 2___________________________ 40
Technical data ____________________________________________________________________________________ 40
Programme sequence _____________________________________________________________________________ 40
Program sequende schedule ______________________________________________________________________ 41
Electrical connection VPS 504 Series 2 _____________________________________________________________ 41
HANDING OVER OF THE INSTALLATION _________________________________ 42
G20: Natural gas H9,45
G25: Natural gas L8,06
G30: Butane32,2412,68
G31: LPG24,4412,87
1)
Calorifi c value: kWh/m3 15°C 1013.25 mbar (according to EN676)
2)
Dimension and capacity depending on gas quality and available pressure
Connection
BG550/BG550LN
Natural gas LPG 1
1/2”-2”
2)
MotorIgnition transformer
0,75 kW
230/400V 50 Hz
3,1/1,8A
Primary 230 V,
0,25A 50-60Hz 60VA
Sec. 11kV Ampl
50 mA rms
33% ED in 3 min
BG650
Natural gas LPG 1
1/2”-2”
1,5 kW
230/400V 50 Hz
5,7/3,3A
Primary 230 V,
0,25A 50-60Hz 60VA
Sec. 11kV Ampl
50 mA rms
33% ED in 3 min
9
Page 10
TECHNICAL DATA
Working field
Working fi eld
BG550
140-640 kW
BG550
BG550 (G25)
Measured (test)
14
12
10
8
6
4
2
0
Pressure in fi re place
-2
100200300400500600700
Capacity kW
BG550LN
140-620 kW
BG550LN
Measured (test)
BG550 LPG 60Hz
150-820 kW
14
12
10
8
6
4
2
0
Pressure in fi re place
-2
100200300400500600700
Capacity kW
Pressure in fi re place
Capacity kW
BG650
200-1125 kW
BG650
Measured (test)
Unbroken line is the approved wor-
king fi eld as per EN 676.
16
14
12
10
8
6
4
2
0
-2
Pressure in fi re place
200300400500600700 800
10
900 1000 1100 1200
Capacity kW
Page 11
SKELETON DIAGRAMS
SKELETON DIAGRAMS
2-stage or modulating burners
Incorporated in the MultiBloc
1. Ball valve
2. Filter
3. Governor
4. Pressure gauge with shut-off cock
5a. Gas pressure switch, mini
5b. Gas pressure switch, maxi
6a. Main valve, 2 -stage
6b. Safety valve
8. Air damper motor
9. Air pressure switch
10. Gas burner control
1)
7. Valve proving system
Pos. 5b, 7: Components not required according to EN 676.
1)
Required over 1200 kW according to EN 676.
When Bio gas is used, Bentone shall always be contacted.
!
11
Page 12
MOUNTING OF THE BURNER
MOUNTING OF THE BURNER
Inspection of gas assembly
Fit the burner to the boiler by means of 4 bolts M12. For fl ange and bolt
Adjustment of the positiion of the shrouded disc in the blast tube
If for some reason you want to separate the burner from the gas fl ange
Do like this:- Remove the cover of the fan housing.
- Loosen the nut D of the gas assembly package.
- Loosen the electric cables to the valve package.
- Loosen the screws B on both sides.
- Loosen the stop bolt C on the pull rods.
- Loosen the ignition cable and the ionisation cable from the gas
- Pull out the burner on the pull rods and put it in a suitable place.
When the burner head and the gas fl ange have been fi tted to the boiler
Inspection of gas assembly
If the gas assembly needs to be inspected the pull rods are very useful.
Do like this:- Remove the cover of the fan housing.
- Loosen the nut D of the gas assembly package.
- Loosen ignition cable and ionisation cable of gas assembly.
- Loosen the screw A on both sides.
- Pull out the burner on the pull rods.
- Loosen the screws B on the gas fl ange.
- Withdraw the gas assembly.
Ensure that the O-ring between the gas assembly and the gas fl ange will
dimensions see technical data.
with burner head and valve package you can do so.
assembly.
it is easy to lift up the burner to where it belongs.
be in the correct position when the gas assembly is fi tted again.
Adjustment of the position of the shrouded disc in the blast tube
Sometimes it is necessary to adjust the position of the shrouded disc in
the blast tube. This can be done with the screw E (can be adjusted when
the burner is in operation). If you turn the screw to the left the shrouded
disc will move forward (+), to the right it will move backward.
NOTE!
For maintenance of the brake plate, nozzles, electrodes etc, when using a
long design of the burner tube, you have to remove the nozzle assembly from the connecting pipe and move the assembly backwards in the
fan housing (from the boiler).
A1 Gas burner control
A2 Power control
B1 Ionization electrode
F1 Operation fuse
F2 Operation fuse
F3 Operation fuse
H1 Lamp, low capacity
H2 Lamp, high capacity (optional)
K1 Motor contactor with thermal overload protector
M1 Burner motor
M2 Damper motor
S1 Operating switch
S2 Operating switch, stage 2
S3 Control thermostat
S4 Temperature limiter
S5 Micro switch for hinged door
S6 Control thermostat, stage 2
S7 Main switch 3-phase
S8 Air pressure switch
If S6 is missing, connection between T6 and T8.
Mains connection and fuse in accordance with local regulations.
Max loading K1
Connection A1,A2 / 95, 96 / 97, 98 Max 0,2A/15W
S9 Gas pressure switch
S11 Change-over switch, Aut.-man.
S12 Change-over switch, Increase Reduce
S15 Control thermostat, 3-pole (only for 2-stage
A control is made that the air pressure switch does not indicate fan
pressure. Then the burner motor starts.
2. Air damper motor opens.
The air damper motor opens the damper to full load. A control is made
that the air pressure switch indicates suffi cient fan pressure.
3. Air damper motor closes. The air damper motor closes to low load . Then the ignition spark is
formed.
4. Main and safety valves open
The gas is ignited. The ionization electrode indicates a fl ame.
5. The safety time expires.
The ignition spark goes out. The safety time expires. If there is no fl ame
or if for some reason the fl ame disappears after this time limit, the burner
control locks out.
6. Operating position. The burner is in operating position and can now change over to full load
if the operating switch and the thermostat for full load are in positon ON.
The burner can alternate between full and low load depending on set
temperature.
7. Stop. The operation of the burner can now be interrupted by means of the
operating switch or the thermostat.
The control locks out. The red lamp in the control is lit. Restart the burner by pressing the reset
Control program when disruption; disruption display
Gas burner control: LME....
Colour codes
Status Colour codes Colours
Waiting time «tw», other waiting times Off
Ignition phase, ignition checked Flashing yellow
Normal operation Green
Operation, poor fl ame signal Flashing green
Prohibited fl ame signal during start up Green-Red
Undervoltage Yellow-Red
Disruption, alarm Red
Flashing code for fault codes Flashing red
Interface diagnostics Red fl ickering
Diagnostics alarm trigger
lights red
FS
AL
Colour code table for multi-coloured signal lamps (Light diodes)
Continuous
Off
The red alarm signal lamp lights continuously after the alarm is disconnected.
Diagnostics for alarm triggers can be read as specifi ed by the following sequence:
Light period (waiting time 10 s)
Press the reset
button > 3 s
Red
Yellow
Green
Flash code PauseFlash code
Approx. 3 s
Limit on start attempts
LME 11 … limits the number of start attempts if the fl ame does not ignite on start-up
or goes out during operation. LME 11 … permits a maximum of three start attempts
if the start cycle is uninterrupted.
16
4(5)
172 445 12 16-01
Page 17
ELECTRICAL EQUIPMENT
Control diagnosis under fault conditions and lockout indicatioGas burner control: LMG ...
Control program when disruption; disruption display
Gas burner control: LME....
Alarm control table
Red fl ashing code on Possible causes
signal lamp (LED)
Flashing 2 x No fl ame at End of «TSA»
•• - Defective or obscured fl ame monitor
- Defective or obscured fuel valves
- Poor burner installation
- Defective ignition unit
Flashing 3 x «LP» defective
••• - No air monitor signal after «t10»
- «LP» is welded in the open position
Flashing 4 x Prohibited fl ame signal during start up
••••
Flashing 5 x Time out «LP»
••••• - «LP» is welded in the closed position
Flashing 6 x Free
••••••
Flashing 7 x Too many loss of fl ame during operation
••••••• - Poor burner installation
- Defective or obscured fuel valves
- Defective or obscured fl ame monitor
Flashing 8 x Free
••••••••
Flashing 9 x Free
•••••••••
Flashing 10 x Connection fault or internal fault,
•••••••••• outgoing contacts or other fault
Flashing 14 x CPI contact not closed
••••••••••
••••
During alarm trigger diagnostics, control outputs are to be disconnected from all power.
- The burner is disconnected
- Exception, the «AL» alarm signal at connection block 10
The burner is only to be reconnected after it is reset
- Press the reset button 0.5...3 s.
Interface diagnostics
To switch to interface mode, hold the reset button depressed for more than 3 s. To return
to normal mode, hold the reset button depressed for more than 3 s. If the fi ring unit is
in the alarm mode, it is reset by pressing the reset button 0.5...3 s.
Connecting signal amplifi er
GP
R/W
LN
A1 = LME
17
111122
brblrtsw
swrtQ1 = AGQ 3...
QRA
5(5)
172 445 12 16-01
Page 18
MEASURES AND CHECKS BEFORE START-UP
MEASURES AND CHECKS BEFORE START UP
2-Stage or modulating burners
2-Stage or modulating burners
General rules Care should be taken by the installer to ensure that no electrical cables
or fuel/gas pipes are trapped or damaged during installation or service/
maintenance.
Inner assembly Ensure that the ignition and ionisation electrodes are correctly adjusted.
The sketch (see separate page) shows the correct measurements.
Gas qualityEnsure that the burner head is meant for the gas quality to be used
(see fi g.).
Venting The gas line is vented by loosening the screw on the test nipple for the
inlet pressure. Connect a plastic hose and conduct the gas into the open
air.
After having vented the gas line tighten the screw again.
Electric function test: Ensure that phase and neutral are not reversed. The gas shut-off cock
should be closed.To prevent the gas pressure switch from locking out,
it should be linked temporarily.
After the main switch has been switched on and the thermostats have
been adjusted, the pre-purging period begins (30-35sec.). At the end of
this period the pre-ignition period starts (0,5-2,5 sec. depending on the
design of the gas control). The gas valve is energized and opens and fl ame
is established. At the end of the safety time (2-3 sec.) the gas control
locks out. The solenoid valve and the motor will be ”dead”. Remove the
link from the gas pressure switch after the test is fi nished.
Note on 2-stage and modulating burners that during the pre-purging period
the damper opens to the set value for air on stage 2 and just before the
end of the pre-purging period it goes down to the air setting for stage 1.
On some burners under 350kW the pre-purging mainly takes place with
the air damper set for stage 1.
NOTE! Applies only to gas burner control LFL1.
When using LPG (Propane) the burner should be connected for post-
purging. Move the connection on terminal 6 to terminal 7 in the base of
LFL1.
Leakage control When making a leakage control of the gas supply system, the solenoid
valve should be closed. Connect a pressure gauge to the test nipple Pa,
see fi g. The test pressure in the system should be 1,5x max. inlet pressure
or min. 150 mbar. If any leakage, locate the source by means of soapy
water or a leak location spray. After tightening repeat the test.
Gas trainMultibloc
18
Page 19
MEASURES AND CHECKS BEFORE START-UP
Inner assembly
Inner assembly
Town gas
Inner assembly
Natural gas, LPG
Inner assembly
Biogas ((UV-detector)
19
Page 20
MEASURES AND CHECKS BEFORE START-UP
Inner assembly BG 550LN
Inner assembly BG 550LN
A = 10 mm Front edge Brake plate
B = 3 mm
A
B
A = Position Ionisation detector
B = Position Ignition electrode
AB
20
Page 21
DETERMINATION OF GAS VOLUME FOR THE INSTALLATION
DETERMINATION OF GAS VOLUME FOR THE INSTALLATION
Specifi cations on natural gas, town gas and biogas vary. For more exact
For stage 1, loosen the lock screw a. Turn the hydraulic device e:to the right = the gas fl ow is reduced
to the left = the gas fl ow is increased
For stage 2, turn the hydraulic device b:to the right = the gas fl ow is reduced
Åt vänster = the gas fl ow is increased
Do not forget to tighten the lock screw again.
Adjustment of governor
Adjust outlet pressure from governor by means of a screw driver. Min.
and max. outlet pressures correspond to appr. 60 turns of the spring. It
is not possible to change pressure springs in order to change the outlet
pressure.
Turn to the right = the outlet pressure is increased
Turn to the left = the outlet pressure is reduced
Adjustment of start gas fl ow
Remove the protective cover c.
Turn the adjustment knob d (use the protective cover as a tool) to the
desired start gas fl ow.
Turn to the right = the start gas fl ow is reduced
Turn to the left = the start gas fl ow is increased
Adjustment of governor
Adjustment of start gas fl ow
Flow adjustment
Multi-bloc MB-ZRDLE 405-420
29
Page 30
MULTI-BLOC, MB-VEF 412 - 425 B01
201379
19
8
6
5
4
3
1
17 2
161011 18
14
15
12
:P0,75:1-3:1
- ZeropointadjustmentN±2mbar
canflowback intothemultibloc.This is especially important
V = 3:1
V = 1:1
V = 0,75:1
V = 3:1
V = 1:1
V = 0,75:1
MULTI-BLOC, MB-VEF 412-425 B01
view
View
1. Electrical connection gas pressure switch mini
2. Electrical connection gas valve
3. Pressure switch mini
4. Flange connection inlet
5. Test point connection 1/8” before V
6. Filter (on Multi-Bloc 425 external fi lter)
7. Data plate
8. Connection 1/8” P
9. Adjustment screw V for ratio PBr: PL (max. load)
10. Test point connection 1/8” before V1 (before governor)
11. Connection M4 for measurement of burner pressure after V
12. Adjustment screw for zero point adjustment N (min. load)
13. Test point connection 1/8” P
(after V2 burner)
15. Flange connection, outlet
16. Test point connection 1/8” Pa before V2 (after governor)
17. Indication of V1 and V2 in operation (not standard)
19. Impulse line PL (air pressure)
20. Impulse line (fi re room)
14. Test point connection 1/8” P
18. Impulse fl ange PBr (gas pressure)
L
F
Br
1
2
It is possible to connect a leakage control VPS 504 and a gas pressure
switch maxi.
30
Page 31
MULTI-BLOC, MB-VEF 412 - 425 B01
MULTI-BLOC, MB VEF 412-425 B01
Technical dataMounting instruction-impulse lines
Technical data
Adjustment possibilities
- Max inlet pressure 360 mbar
- Valves V1+V2 class A group 2 in accordance with EN 161
- Governor class A group 2 in accordance with EN88
- Ratio V PBr:PL 0,75:1-3:1
- Filter according to DIN 3386
- Ambient temperature -15°C- +70°C
- Protection standard type IP54 (according to IEC 529, DIN 40050)
- Gas family 1 +2 +3
- Outlet pressure 0,5 - 100 mbar
- Zero point adjustment N ±2 mbar
- Pressure switch DIN3398 TI
- Fan pressure PL0,4-100 mbar
- Fire room pressure PF -2 -+5mbar
- Burner pressure PBr 0,5 - 100 mbar
Mounting instruction - impulse lines PL, PF and P
- Impulse lines should preferably be made of steel. Inside diametre
>ø 4 mm (steel tube ø 6/4)
- For PL other material can be used.
- Impulse lines PL and PBR are ready from factory
- Impulse lines shall be mounted in such a way that no conden sate
can fl ow back into the multibloc.This is especially important
when PF is concerned.
- Impulse lines shall be mounted in such a way that they are
protected against rupture and damage.
- Impulse lines shall be as short as possible
Adjustment possibilities
Adjustment range
pL, min =0,4 mbar
V = 3:1
Br
V = 1:1
V = 0,75:1
pBr, min =0,5 mbar
P
, max. = 100
Br
!
Effective burner pressure
P
= PBr - P
Br
!
Effective fan pressure
PL = PL-P
F
F
V = 3:1
V
31
V = 1:1
PL, max. = 100 mbar
+ N
- N
V = 0,75:1
Page 32
MULTI-BLOC VDG20… SKP75/15
MULTI-BLOCK VDG20...SKP75/15
View
26122
7
9
8
21
20
3
10
11
25
14
19
18
24
1617
1
5
6
13
22
154
1. Protective cover, adjustment of V och N
2. Adjustment screw V for ratio pG : pA (max. load)
3. Adjustment screw for zero point adjustment N (min. load)
4. Stroke indication
5. Connection ¼” pA
6. Impuls tube pA
7. Connection ¼” pG
8. Impuls tube pG
9. Test nippel pG (measurement of nozzle pressure after V2)
10. Connection ¼” pC
11. Impuls tube pC
12. Test nippel pC (measurement of combustion chamber pressure)
13. Electrical connection gas valve V1
14. Electrical connection gas valve V2
15. Indication of V1 and V2 in operation
16. Electrical connection gas pressure switch min
17. Pressure switch min
18. Electrical connection gas pressure switch max (option)
19. Pressure switch max (option)
20. Flange connection inlet
21. Test point connection 1/4" before V1
22. Data plate
23. VPS 504 leakage control (option under 1200kW)
24. Flange connection, outlet
25. Display for N
26. Display for V
It is possible to connect a leakage control VPS 504 and a gas pressure
switch max.
32
Page 33
MULTI-BLOC VDG20… SKP75/15
Technical dataMounting of impulse lines
Technical data
Mounting of impulse lines pA, pC OCH pG
- 220 V-15%...240 V+10%, 50-60 Hz,13,5 VA
- Adjustment range Gas/Air, 0,4-9
- Max. permissible inlet pressure 600 mbar
- Differansce pressure pG-pA 0,8…120 mbar
- Min. air pressure 0,5 mbar
- Min. period of time required when load changes from min. load to
max. load 5 s.
- Permissible test pressure 1 bar.
- Permissible vacuum 200 mbar.
- Closing time in the event of voltage failure < 1 sek.
- Mounting position. Avoid mounting the valves upside down.
- Protection class IP54
- Ambient temperature -10 - +60°C, with heater AGA63.5 -20 - +60°C.
- Impulse lines are mounted from factory
- Should any of the impulse lines be changed should it be made of steel.
Inner diameter > ø 8 mm (steel tube ø 10/8)
- Impulse lines must be mounted so that condensate cannot enter into
the multi-bloc. This especially applies to pC.
- Impulse lines must be mounted so that they are protected against rupture
and damage.
- Impulse lines shall be as short as possible.
Adjustment possibilities
Adjustment range
p
p
G
(max.)
953
10
9
8
7
6
5
4
3
2
1
0
2345678910
1
0
45°
G
p
A
1.5
2
bzw.
1.25
p -p
GC
p -p
AC
1
0.8
0.6
0.4
(min.)
-
p -p
GA
bzw.
AC
p -p
p
GA
ASIR
/p
0.4
2
p
A
9
+
+
-
p
G
+
^
-
0
0
+
0
0
0=
-
p
A
33
23
2(2)
172 505 35-1 12-01
Page 34
DAMPER MOTOR 2-STAGE
DAMPER MOTOR 2- STAGE
Air adjustment
Air adjustment
Releasing button
The damper motor turns the damper between three pre-set positions: fully
closed, low load, full load. These positons are controlled in the motor by
cams of different colours. The black cam controls the gas valve for full
load.
If the air volume needs changing: Remove the cover of the damper motor
and change the position of the cams by turning them with the tools accompanying the burner.
Low load:
Adjust the operating switch to full load (ll).
* Reduce the air volume:
Turn orange cam towards 0°
* Increase the air volume:
Turn orange cam towards 90°
Adjust the operating switch back to low load and check the air volume.
Full load
Adjust the operating switch to low load (l).
* Reduce the air volume:
Turn red cam towards 0°
* Inrease the air volume:
Turn red cam towards 90°
If the red cam is moved, change the black cam as much.
Adjust the operating switch to low load and check that the correct air
volume has been obtained.
Note! The blue cam is the limit position for fully closed damper and it is normally
not necessary to change it.
Releasing button
By pressing the button and snapping it down, the motor will be released
and the damper can easily be turned. This function facilitates an exchange
of damper motor.
Solenoid valve
High capacity (black)
High capacity (red)
Low capacity (orange)
Closed damper (blue))
Releasing button
N.B. The upper position is the standard position
34
Page 35
DAMPER MOTOR MODULATING
DAMPER MOTOR MODULATING
- Before the burner starts vent the lines to make sure that there is gas
Air adjustment
vailable at the multibloc
Releasing button
- Use an allen key size 2,5 mm for adjusting N and V
- Connect a pressure gauge for measur-ing PBr, (advisable to fi nd out if
the valves are open)
- Set the switch in position MAN.
- Set the gas pressure switch min. and air pressure switch on min.
adjustment. Set the gas pressure switch max, if any, on max. adjust-
ment.
- Start the burner, observe the pressure gauge, if no fl ame is established and the pressure gauge needle does not fl icker, increase N.
When the fl ame is established adjust the gas fl ow by means of the
screw N. Use a fl ue gas instrument.
- Change over to max. load, press the switch “increase”
- Adjust the gas fl ow with V and check at the same time the combus-
tion values.
- Go back to min. load and check the combustion value. Adjust if ne-
cessary.
- If necessary repeat the controls of the adjustment made on min. (N)
and max.load(V)
- The desired gas fl ow on min. and max. has now been adjusted by
changing the orange and the red cams. Check the gas fl ow on the
gas meter available on the installation.
Note! Do not forget to set the air and gas pressure switches after the
adjustment, see special instructions
Air adjustment
Adjust the orange cam for min. load (about 5-10 on scale)
Adjust the red cam for max. load (90° )
The blue cam is factory set for closed position during standstill
The black cam has no function at modulating operation
Releasing button
By pressing the button and snapping it down, the motor will be relea-
sed and the damper can easily be turned. This function facilitates an
exchange of damper motor..
Gas valve (black)
Max. load (red)
Min. load (orange)
Closed damper (blue)
35
Releasing button
N.B. The upper position is the standard position
Page 36
GENERAL INSTRUCTIONS
GENERAL INSTUCTION
Adjustment of burner
Adjustment of burner
Service
The burner is from the factory pre-set to an average value that must then
be adjusted to the boiler in question. All burner adjustments must be made
in accordance with boiler manu-facturers instructions.These must include
the checking of fl ue gas temperatures, average water temperature and
CO2 or O2 concentration.
General instructions The installation of the gas burner must be carried out in accordance with
current regulations and standards. The installers of gas burners should
therefore be acquainted with all regulations and ensure that the installation complies with the requirements. The installation, mounting and
adjustment should be made with the greatest care and only the correct
gas should be used.
Operating instructions The operating instructions accompanying the burner should be left in a
prominent position in the boiler room.
Instructions The user should be thoroughly in-structed in the function of the gas burner
and the whole installation. The supplier must instruct the user.
Inspection and maintenance Daily inspection is advisable.
Start up After the burner has been fi tted to the boiler and the electric connection,
the leakage control, the venting and the electric function test have been
carried out, the burner will be ready for start-up.
Howerer, study the sections dealing with adjustments of multi-bloc,
combustion air and combustion head. Open the ball valve and switch on
the main switch. If the burner starts the actual adjustment can be made.
Adjustment of burner head The burner is equipped with an adjustment device changing the po si tion
of the brake plate in the burner head. This is used to adjust the cor rect
pressure drop over the com bus tion device in order to obtain a good
pulsation free combustion.
Which position to use depends on input and overpressure in the boiler. A
general rule is that the lower capacity the smaller the opening between
brake plate and combustion device.
Commissioning of installation
Control of the combustion. The combustion quality is checked by means
of a fl ue gas analysis device. Adjust the burner to appr. 20% excess air
in accordance with the table. Check the fl ue gas temperature. Calculate
the effi ciency. Check also the actual gas volume on the gas meter so
that the correct input is achieved.
Service
Service should only be carried out by qualifi ed personnel. Replacement
parts should be of the same make and approved by the same authori-
ties as the original. If the burner is converted to fi re another gas quality
it must be re-commissioned. If town gas is to be fi red the combustion
head must be converted and the gas train adjusted to suit (e.g.a larger
gas armature or a different spring in the governor may be required).
Gas quality CO2% 02% max. CO2%
lambda 1,2
Natural gas 10,0 3,5 11,9
LPG 11,5 3,5 13,9
36
Page 37
GENERAL INSTRUCTION
Flame monitoring and measurement of ionisation current
Flame monitoring and measurement of ionisation current
The burner is monitored according to the ionisation principle. Check the
ionisation current on start-up and on each service call.
The reason for a low ionisation current may be leaking currents, bad
connection to earth, dirt or a faulty position of the fl ame electrode in the
burner head. Sometimes also a faulty gas/air mixture may cause too weak
a ionisation current.
The ionisation current is measured by means of a microampere meter (µA)
connected in series with the fl ame electrode and the gas burner control.
Connect the µA-meter, see fi gure. Min. required ionisation current accor-
ding to table. In practice this current must be considerably higher, preferably more than 10 µA. All the gas burners are equipped with a ionisation
cable that can be slit which facilitates the connection of the µA-device.
Gas controlConnection to terminal
in gas control
LME15 µ A
LGB110 µ A
LFL2410 µ A
MMI 81025 µ A
TMG 740-315 µ A
Flame monitoring
Min. ionisation
current required
37
Page 38
GENERAL INSTRUCTION
UV- detektor
UV-detector
This should not be exposed to temperatures exceeding 60°C. The current
passing through the UV-detector, when it is being illuminated, should be
at least 70 µ A for LFL1.. This current can be measured by means of a
moving coil instrument. Checks should only be made if a fault is suspected.
The capacitor, which sould be placed between the terminals on the moving
coil instrument, must be of 100 µ F 10-25 V.
Flame monitoring
Control box LFL1
UV-detector
38
Page 39
GENERAL INSTRUCTION
Adjustment of air pressure switch
Adjustment of air pressure switchAdjustment of min. gas pressure switchAdjustment of max. gas pressure switch
Adjustment of min. gas pressure switch
Adjustment of max. gas pressure switch
The air pressure switch should stop the burner, if the air volume is reduced.
The air proving device shall be adjusted in such a way that if there is
insuffi cien air supply at the highest or lowest burner operating stage, the
device operates before the supervised pressure is less than 80% of the
pressure at the controlled stage and the CO content of the combustion
products exceeds 1% by volume. On adjustment, turn the scale on the
air pressure switch in clockwise direction. When the switch-off point has
been reached and the burner stops read off the value on the scale. Then
turn the scale in anti-clockweise direstion to desired value. Make repeated
start attempts to ensure that the air pressure switch is not too closely set.
Adjustment range ca:
1-10 mbar LGW 10
2,5-50 mbar LGW 50
The min. pressure switch should react if the gas pressure is too low and
prevent the burner from starting. Too low a gas pressure during operation should stop the burner. The burner may start again when the rated
gas pressure has been reached. Remove the protective cover. Connect
a pressure gauge for measuring the rated pressure. Decide on pressure
at which the gas switch should switch off. Set this pressure by means of
the valve. Carefully turn the knob (see fi gure until the gas pressure switch
switches off. The value shown on the scale should then approximately
correspond with the value shown on the pressure gauge. Tolerance on
scale appr. ± 15 %. Open the ball valve.
The burner is equipped with a max. gas pressure switch only on request.
It should stop the burner if the gas pressure exceeds the set value. The
burner can then only be re-started manually (gas burner control or overpressure switch). Remove the protective cover. Connect a pressure gauge
for measuring the rated gas pressure. Decide on pressure at which the
gas pressure switch should switch off. Turn the adjustment knob to this
value. Tolerance on the scale ±15%.
Adjustment range:
2,5-50 mbar GW 50
5-150 mbar GW 150
Gas pressure switch, air pressure switch
39
Page 40
LEAKAGE CONTROL, DUNGS VPS 504 SERIE 2
LEAKAGE CONTROL, DUNGS VPS 504 SERIE 2
Technical data
Technical data
Programme sequence
Programme sequence
Test volume≤ 4,0 l
Pressurre increase using motor pumps≈ 20 mbar
Backup (customer supply)10A fast or 6.3A slow
Fuse integrated in
Sensitivity limit50 l/h
Max. number of test cycles20/h
Idle state: Valves 1 and 2 are closed. Pressure build-up: The internal
motorpump increases the gas pressure Pe in the section by approx.
20 mbarcompared with the input pressure at valve V1. During the test
time, theintegrated differential pressure sensor monitors the test section
for leaks.When the test pressure is attained, the motor pump switches
off (end oftest period). The release time (10-30 s) is depending on the
test volume(max. 4.0 l). If the test section has no leaks, the contact is
released to thecontrol box after approx. 30 s and the yellow LED lights
up.If the test section is leaky or if the pressure increase by + 20 mbar is
notattained during the test period (max. 26 s), the VPS 504 generates a
fault.The red LED is lit as long as the contact is released by the regulator
(heatrequirement).
After a short voltage drop during testing or during burner operation, anautomatic restart is performed.
T6,3L 250V (IEC 127-2/111) (DIN41662)
Faul output SO4 1, 2, 3, T7: 1A
Dependent on test volume and input pressure.
output T7: 1A
Programmer Idle statePressure buildupOperation
40
Page 41
LEAKAGE CONTROL
Program sequende scheduleElectrical connection VPS 504 Series 2
Program sequende schedule
VPS 504 ”TIGHT” TEST =00,31,31
Controller
Pump motor
Solenoid valve
Differential pressure sensor
Release signal
Controller
Pump motor
Solenoid valve
Differential pressure sensor
Release signal
Controller
Pump motor
Solenoid valve
Differential pressure sensor
Release signal
Fault signal
VPS 504 ”TIGHT” TEST =41
VPS 504 ”NOT TIGHT”
Electrical connection VPS 504 Series 02
The VPS 504 is connected in series between the temperature regulatorand the control box via a 7-pole plug connector.See the Bentone
wiring diagram.
(S)
tight
untight
Lock-outOperation
Plug
Outlet
Operating voltage
~(AC) 230V 50Hz
41
Page 42
FINAL TEST OF THE INSTALLATION
HANDING OVER OF THE INSTALLATION
Fault location, functional troubles
Fault location, functional troubles
Trouble free operation is depending on three factors: electricity, gas and
- Make repeated start attempts to ensure that the adjustments function.
- Close the ball valve during operation to check that the gas switch
switches off at the set value.
- Remove the hose for the air pressure switch to check that the burner
locks out.
- Check that all protective covers and measurement nipples are mounted
and fastened.
- Fill out necessary test reports.
- Instruct the persons in charge of the operation on the service and maintenance of the installation and what to do should any troubles occur.
- Inspection and service must be carried out by authorized
personnel.
air supply. Should there be any changes in the ratio between these three
factors, there is a risk of break downs. It has been proved that most break
downs are caused by simple faults. Before calling the service engineer,
the following should therefore be checked:
- Is the gas cock open?
- Are all fuses in order and the current switched on?
- Are the thermostats correctly set?
- Are pressostats, overheating protection etc. in operating position and
not locked-out?
- Is the gas pressure suffi cient?
- Is the gas burner control in start position?
- Has the gas control or the motor protector locked out? - Reset.
- Is the circulation pump in operation?
- Is there a supply of fresh air to the installation?
If integral components are of a different make from what is stated in this
manual, see the enclosed sheet.
42
Page 43
DECLARATION OF CONFORMITY
Declaration of conformity
Gas burner
Zertifi kat TÜV Süddeutschland
Certifi cate NoBurnerCertifi cate NoBurner
CE-0085 BT 0064BFG1CE-0085 BP 0352BG550
CE-0085 AO 0230BG100CE-0085 BP 0353BG550LN
CE-0085 AP 0623BG150CE-0085 AO 0084BG600LN
CE-0085 AP 0624BG200CE-0085 BP 0354BG650
CE-0085 AT 0192STG120, STG146CE-0085 AT 0313BG700
CE-0085 AP 0625BG300CE-0085 AT 0314BG800
CE-0085 AP 0626BG400CE-0085 BR 5754BG950
CE-0085 AU 0156BG450
Enertech AB declares that the above-mentioned products
comply with the following standards or other normative
documents and meet applicable sections of the EU directive.
Enertech AB försäkrar under eget ansvar att ovannämnda
produkter är i överensstämmelse med följande standarder eller
andra regelgivande dokument och uppfyller tillämpliga delar i EU
direktiv.
By conforming to the above-mentioned standards and
directives, the burner will receive the CE marking.
Genom att brännaren uppfyller ovannämnda standarder och
direktiv erhåller brännaren CE - märkningen.
Enertech AB Bentone Division is quality certifi ed according
to SS-EN ISO 9001
Enertech AB Bentone Division är kvalitetscertifi erat enligt
SS-EN ISO 9001
Enertech AB erklärt hiemit, dass oben genannten Produkte mit
den folgenden Normen oder anderen normativen Dokumenten
übereinstimmen und die anwendbaren Teile der EU-Richtlinie
erfüllen.
Enertech AB déclare que les produits ci-dessus mentionnés sont
conformes aux normes ou autres documents normatifs suivants,
et répondent aux sections applicables de la directive EU.
Durch Übereinstimmung mit den oben genannten Normen und
Richtlinien erhalt der Brenner die CE-Kennzeichnung.
De par sa conformité aux normes et directives mentionnées cidessus, le brûleur recevra le marquage CE de conformité.
Ljungby, Sweden, 141127 (27/11/14)
ENERTECH AB Bentone Division
Box 309
SE-341 26 Ljungby Sweden
Enertech AB Bentone Division ist nach SS-EN ISO
9001qualitätszertifi ziert.
Enertech AB Bentone Division a reçu la certifi cation
d’assurance qualité SS-EN ISO 9001qualitätszertifi ziert.
Håkan Lennartsson
43
Page 44
FAULT LOCATION GUIDE
Gas burner
1. Fault location guide
Gas burner
The basis for a trouble free operation can only be ensured by the correct
combined effect of the three factors:
electricity, gas fl ow and combustion air. Should any of these factors change,
troubles may arise.
t has been proved that many troubles have rather simple causes. Before
calling the serviceman, the following checks should be made:
o facilitate fault location we have drawn up a scheme showing the most
frequent faults in a gas burner installation and the remedies.
1. Are the gas cocks of the installation open?
2. Are the fuses in order and the current switched on?
3. Are the controls (room thermostat, boiler thermostat etc.) correctly
adjusted?
4. Is the gas pressure to the burner suffi cient?
5. Is the gas relay of the burner ready for start and not locked out?
6. Is the air supply to the burner suffi cient?
CauseRemedy
The burner does not start
No gasCheck that all gas cocks are open.
No voltageCheck fuses, thermostats and electrical
connections.
The burner motor fails to startThe thermal protection has locked out.
Motor defective.
The gas relay is defectiveReplace
Burner motor is running but no
ignition after the pre-purge time has elapsed
No voltage on the terminalsCheck the contact. Replace faulty relay
The ignition electrodes in contact with each other or with earthAdjust
The porcelain of the electrodes is brokenReplace the electrodes
The cable shoes have bad contactImprove the contact
The ignition cables are damagedReplace
The ignition transformer is damaged, no voltage on the secondary
side
The ignition cable and the ionisation cable have been transposed.Change
No fl ame establishment despite a trouble free start
The gas solenoid valve defectiveReplace
The gas solenoid valve does not open despite its obtaining voltageReplace coil or the whole valve if necessary.
No voltage to the solenoid valveCheck the contact
Replace the transformer
44
1(3)
170 091 16 15-01
Page 45
CauseRemedy
No electrical connection through the air pressure switchTest the adjustment and the function of the
air pres-sure switch.
The starting load is not correctly adjustedReduce or increase the gas supply, reduce
the quanti ty of air.
Gas relay defectiveReplace
Air pressure switch incorrectly adjusted or defectiveCheck the adjustment and readjust.
No reponse as the cams of the servomotor are not correctly
adjusted or out of position.
The burner locks out after the safety time has el-apsed in
spite of fl ame establishment
No ionisation current or the UV-cell in wrong positionAdjust the ionisation electrode and the UV-
cell, examine cables and connections.
The supervision part of the gas relay is defectiveReplace the relay
Voltage lower than 185 VContact the electricity authorities.
The ignition electrodes are disturbing the ionisation currentAdjust the ignition electrodes, repole the
ignition transformer if necessary.
Bad earthingArrange for proper earthing.
Phase and neutral transposedSee wiring diagram and change.
The burner locks out during pre-purge
Air pressure switch defective or incorrectly adjustedReduce or increase the gas supply. Reduce
the quantity of air.
The starting load is not correctly adjustedReduce or increase the gas supply. Reduce
the quantity of air.
The gas pressure is too lowIncrease the pressure. Contact the gas
supply company if necessary.
Pulsations at start
The ignition electrodes are wrongly adjustedReadjust
The gas pressure is too highCheck and adjust by means of a pressure
gauge and a pressure adjustment valve.
The fl ue gas side is blockedCheck the chimney fl ue.
Pulsations during operation
The burner is not correctly adjustedReadjust
The burner is dirtyClean the burner.
Defective chimneyCheck and change the dimensions if
necessary.
45
2(3)
170 091 16 15-01
Page 46
CauseRemedy
The burner is operating correctly but locking out now and
then
The ionisation current is too lowCheck. Must be at least 4 µ A according to
the relay manufacturer but should be 8-20 µ A.
The UV-cell is in a wrong positionAdjust
Voltage drop at certain timesMust not drop more than 15% of the rated
current. Contact the electricity authorities if
necessary.
Air pressure switch defective or incorrectly adjusted
Spark-over in ignition electrodesReplace the electrodes
The ambient temperature of the gas relay is too highHeat insulate, max. 60° C.
The ignition spark is too weakCheck the transformern
Bad combustion
Bad draught conditionsCheck the chimney
The fl ue gas temperature is too highThe boiler is overloaded. Reduce the
quantity of gas.
The CO2-content is too lowCheck the boiler with regard to leaks. Choke
the draught if it is too high.
The CO-content is too high
Excess air when using natural gas and gasoil (propane, butane)Choke the air.
Air shortageOpen the air supply. Check the fl ue gas
damper.
The holes in the gas nozzle are cloggedClean
The fresh air intake is too smallCheck and enlarge.
The fl ame is not burning straight because the burner head is out of
position
Condensation in boiler and chimney
The fl ow gas temperature is too low or the quantity of gas is not
suffi cient
Check the burner head and readjust.
Increase the fl ue gas temperature by
increasing the gas supply. Insulate the
chimney
46
3(3)
170 091 16 15-01
Page 47
CauseRemedy
The burner is operating correctly but locking out now and
then
The ionisation current is too lowCheck. Must be at least 4 µ A according to
the relay manufacturer but should be 8-20 µ A.
The UV-cell is in a wrong positionAdjust
Voltage drop at certain timesMust not drop more than 15% of the rated
current. Contact the electricity authorities if
necessary.
Air pressure switch defective or incorrectly adjusted
Spark-over in ignition electrodesReplace the electrodes
The ambient temperature of the gas relay is too highHeat insulate, max. 60° C.
The ignition spark is too weakCheck the transformern
Bad combustion
Bad draught conditionsCheck the chimney
The fl ue gas temperature is too highThe boiler is overloaded. Reduce the
quantity of gas.
The CO2-content is too lowCheck the boiler with regard to leaks. Choke
the draught if it is too high.
The CO-content is too high
Excess air when using natural gas and gasoil (propane, butane)Choke the air.
Air shortageOpen the air supply. Check the fl ue gas
damper.
The holes in the gas nozzle are cloggedClean
The fresh air intake is too smallCheck and enlarge.
The fl ame is not burning straight because the burner head is out of
position
Condensation in boiler and chimney
The fl ow gas temperature is too low or the quantity of gas is not
suffi cient
Check the burner head and readjust.
Increase the fl ue gas temperature by
increasing the gas supply. Insulate the
chimney
47
3(3)
170 091 16 15-01
Page 48
48
Page 49
GENERAL INSTRUCTIONS FOR
GASBURNERS
Installation
1. Follow standards and instructions applicable to the
installation of gas burners
2. Ensure that the electric installation is made in
accordance with existing regulations
3. Check that the fresh air intake of the boiler room is
suffi ciently dimensioned
4. Check by studying the data plate that the effi ciency
of the burner is adapted to the boiler output
5. Check that the burner is adapted to the gas quality
in question
Maintenance
General instructions
6. Check that the input pressure of the gas is correct
7. Check that the dampers of the boiler are open
8. Check that there is water in the system
9. Check that thermostats etc. are correctly adjusted
10. Read the instructions and follow the directions
given for the burner as to starting-up and service
Normal operation
1. Keep the boiler room clean
2. Ensure that the fresh air intake of the boiler room is
not restricted
3. Switch off the current and shut off the gas supply if
the burner must be withdrawn from the boiler
4. Do not use the boiler for burning paper and waste
if there is no special arrangement ( fi re room ) for
this
If the burner has stopped
1. Press the reset button of the relay
2. Check that the max. thermostat has not cut out
3. Check other thermostats for example room ther
mostat, if any
4. Check that the gas pressure to the burner is
suffi cient
5. Check that the electric fuses have not blown
6. Make a new attempt to start the burner and check
the counter of the gas meter to fi nd out whether
the solenoid valve opens
7. If the burner does not start in spite of repeated
starting attempts call the installer
1. Ensure that the air supply to the burner is not
obstructed by dust and dirt
2. Have the installer make a yearly overhaul of the
installation so that safety is not jeopardized
3. Have the installer at the yearly overhaul also adjust
the burner to ensure optimal combustion economy
4. Check periodically that there is water in the system
( fi ll up if necessary ) and that thermostats etc. are
normally adjusted
5. Ensure that there is no water or dampness in
contact with the burner
Shut-Off
1. Switch off the current with the main switch
2. Shut-off the gas supply with the shut-off cock on
the burner
Warning
1. Never keep your face in front of the fi re room door
when starting up the burner
2. Do not use naked fl ame when inspecting the fi re
room