Bentone BG 300LN, BG 400LN Installation And Maintenance Instruction

Page 1
Installation- and maintenance instruction
BG300LN
1
172 115 07 05-01
Page 2
178 026 72
Page 3
DESCRIPTION BG300/400LN
178910
2
3
45
6
11
12
13
14
15
16
17
18
19
20
1. Switch man-aut
2. Switch 0-1
4. Indicating lamp Stage 1
5. Reset button
6. Air pressure switch
7. Damper motor
8. Connection flange
9. Blast tube
10. Gas nozzle
11. Connection gas fittings
12. Multibloc
13. Air intake
14. Shut-off cock
15. Cover, inspection glass
1
16. Transformer
17. Gas burner control
18. Electric panel
19. Electrical connection
20. Motor
172 205 99 03-01
Page 4
TECHNICAL DATA
Type designation BG 300LN
ø108
485
ø100
245185
A
Length of Measure A
345
M10
330
220
ø175-240
ø110
Standard 230 217
The above dimensions are max. measurements. Depending on the com ponents used, the measurements may vary.
1/2
1
172 215 53 03-01
Page 5
TECHNICAL DATA
Type designation BG 300LN
Output range
Capacity Gas volume at a min.Gas volume at a max Max. inlet Rated inlet pressure
kW output Nm3/h 1) output Nm3/h 1) pressure mbar mbar
G20 51-120 kW
1)
G20 5,1 G20 12 360 20
G25 45-120 kW G25 5,5 G25 14,6
Connection 3) Motor Ignition transformer
Natural gas
1-fas, 0,18 kW Primary 230 V, 1 A
1" 2 800 r/m, 230 V Secondary 8 000 V
1,3 A
1
) G20 = Natural gas Calorific value 10 kWh/Nm
G25 = Natural gas Calorific value 8,2 kWh/Nm
2
) Dimension and capacity depending on gas quality and
available pressure
Capacity chart according to EN 676
3
3
2/2
2
172 215 53 03-01
Page 6
SKELETON DIAGRAM
2-stage or modulating burners
1. Ball valve
2. Filter
3. Governor
4. Pressure gauge with shut-off cock 5a. Gas pressure switch, mini 5b. Gas pressure switch, maxi 6a. Main valve, 2 -stage. When modulating operation is required,
this valve is equipped with controls for variable opening.
6b. Safety valve
1)
7. Valve proving system
8. Air damper motor
9. Air pressure switch
10. Gas burner control
Pos. 5b, 7: Components not required according to EN 676.
1)
Required over 1200 kW according to EN 676.
9
8
10
4
5a
5b
6b
6a
3
2
1
Incorporated in the MultiBloc
7
When biogas is used, Bentone shall always be contacted.
6
172 415 05 03-01
Page 7
MOUNTING ON THE BOILER
Fit the burner to the boiler by means of 4 bolts M10 (do not forget the flange gasket). For flange and bolt dimensions see Technical Data or use the fixing flange as a pattern. If for some reason you want to separate the combustion part from the fan housing part to mount the burner on the boiler, see General Instructions.
Mounting of the multi-bloc on the burner
Connect the multi-bloc to the burner head. Connect PL to the fan housing. Connect the two cables by means of the plug-in contact to the multi-bloc. Do not mix up the cables to the valves and to the gas switch. IMPORTANT! The burner cannot start, if these cables have been mixed up. Do not forget to connect the plug-in contact to the leakage control, if any.
Installation example
Connect the gas to the burner by means of the ball valve. Ensure that the union nut, ball valve and tubing make it easy to remove the burner for inspection and service.
a
P
L
7
172 155 01 03-01
Page 8
ELECTRIC EQUIPMENT
Gas burner control: LMG22/LME22
Wiring diagram
connect to the contact enclosed.
* If there is no Plug-in contact (X4,X16) on the boiler,
*
1(2)
8
172 425 51 08-01
Page 9
ELECTRIC EQUIPMENT
List of components
A1 Gas burner control S12 Change-over switch, Increase­A2 Power control Reduce B1 Ionization electrode S15 Control thermostat, 3-pole F1 Operating fuse (only for 2-stage sliding) H1 Operating lamp T1 Ignition transformer H3 Alarm signal 230 V X1 Connection terminal board M1 Burner motor X2 Earth terminal M2 Damper motor, X3 Plug-in contact, burner
L&S SQN75.624A21B X4 Plug-in contact, boiler
P1 Time meter, X15 Plug-in contact, power
total operating time controller, burner S1 Operating switch X16 Plug-in contact, power S3 Control thermostat controller S4 Temperature limiter S9 Gas pressure switch S5 Micro switch for hinged door Y1 Gas solenoid valve 1 S7 Main switch Y3 Safety solenoid valve S8 Air pressure switch S11 Change-over switch, Aut.-Man.
Mains connection in fuse in accordance with local regulations.
Gas burner control: LMG22/LME22 Function
1.Operating switch ON-Thermostat ON-Gas pressure switch ON-Air damper closed.
A control is made that the air pressure switch does not indicate fan pressure. Then the burner motor starts.
2.Air damper motor opens.
The air damper motor opens the damper to max. position. A control is made that the air pressure switch indicates sufficient fan pressure.
3.Air damper motor closes.
The air damper motor closes to min. load position. Then the ignition spark is formed.
4.Main and safety valves open.
The gas is ignited. The ionization electrode indicates a flame.
5.The safety time expires.
The ignition spark goes out. The safety time expires. If there is no flame or if for some reason the flame disappears after this time limit, the burner control locks out.
6.Operating position.
The burner is in operating position and can now change over to the capa­city controlled by the regulator.
7.Stop. The operation of the burner can now be interrupted by means of
the operating switch or the thermostat.
The control locks out. The red lamp in the control is lit. Restart the burner by pressing the reset
button.
2(2)
9
172 425 51 08-01
Page 10
ELECTRIC EQUIPMENT
Control diagnosis under fault conditions and lockout indication Gas burner control: LMG ...
Diagnosis of cause of fault After lockout, the red fault LED is steady on. For reading the cause of fault,
Red LED on
FS
AL
Error code table
During the time the cause of the fault is diagnosed, the control outputs are deactivated.
- The burner remains shut down
- Exception: fault status signal «AL» at terminal 10
The burner is switched on only after a reset is made.
- Press lockout reset button for
0.5...3 seconds
refer to the blink code given in the following table:
Press lockout reset button
LED on (waiting time 10 s)
Fault
for > 3 s
Blink code
Off
Approx. 3 s
Blink code
Blink code Possible cause 2 x • No establishment of flame at the end of «TSA»
•• - Faulty or soiled detector electrode
- Faulty or soiled fuel valves
- Poor adjustment of burner
3 x • Air pressure monitor does not close
••• - «LP» faulty
- «LP» incorrectly adjusted
- Fan motor does not run
4 x • Air pressure monitor does not open or extraneous
light on burner startup
•••• - «LP» faulty
- «LP» incorrectly adjusted
5 x • Extraneous light during pre-purging
••••• - Or internal device fault 7 x • Loss of flame during operation
••••••• - Poor adjustment of burner
- Faulty or soiled fuel valves
- Short-circuit between detector electrode and ground
8...17 x • Free
••••••••
..................
••••••••••
••••••• 18 x • Air pressure monitor opens during pre-purging or
operation
•••••••••• - «LP» incorrectly adjusted
•••••••• -Four times loss of flame during operation (LMG25) 19 x • Faulty output contact
•••••••••• - Wiring error
••••••••• - External power supply on output terminal 20 x • Internal device fault
••••••••••
••••••••••
Connecting signal amplifier
A1 = LMG
GP R/W
LN
21
11112 2
br bl rt sw
sw r tQ1 = AGQ 2...
QRA
172 425 57 08-01
Page 11
ELECTRICAL EQUIPMENT
Control program when disruption; disruption display
Gas burner control: LME....
Colour codes
Colour code table for multi-coloured signal lamps (Light diodes)
Status Colour codes Colours Waiting time «tw», other waiting times Off Ignition phase, ignition checked Flashing yellow Normal operation Green Operation, poor flame signal Flashing green Prohibited flame signal during start up Green-Red Undervoltage Yellow-Red Disruption, alarm Red Flashing code for fault codes Flashing red Interface diagnostics Red flickering
Diagnostics alarm trigger
lights red
FS
AL
Limit on start attempts
Continuous
Off
Yellow Green
The red alarm signal lamp lights continuously after the alarm is disconnected. Diagnostics for alarm triggers can be read as specified by the following sequence:
Red
Light period (waiting time 10 s)
Press the reset button > 3 s
Flash code Pause Flash code
Approx. 3 s
LME 11 … limits the number of start attempts if the flame does not ignite on start-up or goes out during operation. LME 11 … permits a maximum of three start attempts if the start cycle is uninterrupted.
22
1(2)
172 445 02 08-01
Page 12
ELECTRICAL EQUIPMENT
Control program when disruption; disruption display
Gas burner control: LME....
Alarm control table
Red flashing code on Possible causes signal lamp (LED)
Flashing 2 x No flame at End of «TSA»
•• - Defective or obscured flame monitor
- Defective or obscured fuel valves
- Poor burner installation
- Defective ignition unit
Flashing 3 x «LP» defective
••• - No air monitor signal after «t10»
- «LP» is welded in the open position
Flashing 4 x Prohibited flame signal during start up
•••• Flashing 5 x Time out «LP»
••••• - «LP» is welded in the closed position Flashing 6 x Free
•••••• Flashing 7 x Too many loss of flame during operation
••••••• - Poor burner installation
- Defective or obscured fuel valves
- Defective or obscured flame monitor
Flashing 8 x Free
•••••••• Flashing 9 x Free
••••••••• Flashing 10 x Connection fault or internal fault,
•••••••••• outgoing contacts or other fault Flashing 14 x CPI contact not closed
••••••••••
••••
During alarm trigger diagnostics, control outputs are to be disconnected from all power.
- The burner is disconnected
- Exception, the «AL» alarm signal at connection block 10 The burner is only to be reconnected after it is reset
- Press the reset button 0.5...3 s.
Interface diagnostics
To switch to interface mode, hold the reset button depressed for more than 3 s. To return to normal mode, hold the reset button depressed for more than 3 s. If the firing unit is in the alarm mode, it is reset by pressing the reset button 0.5...3 s.
Connecting signal amplifier
A1 = LME
GP R/W
LN
23
11112 2
br bl rt sw
sw r tQ1 = AGQ 3...
QRA
2(2)
172 445 02 08-01
Page 13
MEASURES AND CHECKS BEFORE START-UP
2-Stage or modulating burners
General rules Care should be taken by the installer to ensure that no electrical cables or
fuel/gas pipes are trapped or damaged during installation or service/ maintenance.
Inner assembly Ensure that the ignition and ionisation electrodes are correctly adjusted.
The sketch (see separate page) shows the correct measurements.
Gas quality Ensure that the burner head is meant for the gas quality to be used
(see fig.).
Venting The gas line is vented by loosening the screw on the test nipple for the inlet
pressure. Connect a plastic hose and conduct the gas into the open air.
After having vented the gas line tighten the screw again.
Electric function test: Ensure that phase and neutral are not reversed. The gas shut-off cock
should be closed.To prevent the gas pressure switch from locking out, it should be linked temporarily. After the main switch has been switched on and the thermostats have been adjusted, the pre-purging period begins (30-35sec.). At the end of this period the pre-ignition period starts (0,5-2,5 sec. depending on the design of the gas control). The gas valve is energized and opens and flame is established. At the end of the safety time (2-3 sec.) the gas control locks out. The solenoid valve and the motor will be "dead". Remove the link from the gas pressure switch after the test is finished. Note on 2-stage and modulating burners that during the pre-purging period the damper opens to the set value for air on stage 2 and just before the end of the pre-purging period it goes down to the air setting for stage 1. On some burners under 350kW the pre-purging mainly takes place with the air damper set for stage 1.
NOTE! Applies only to gas burner control LFL1.
When using LPG (Propane) the burner should be connected for post-purging. Move the connection on terminal 6 to terminal 7 in the base of LFL1.
Leakage control When making a leakage control of the gas supply system, the solenoid
valve should be closed. Connect a pressure gauge to the test nipple Pa, see fig. The test pressure in the system should be 1,5x max. inlet pressure or min. 150 mbar. If any leakage, locate the source by means of soapy water or a leak location spray. After tightening repeat the test.
Gas train Multibloc
33
172 205 34 07-01
Page 14
EASURES AND CHECKS BEFORE START-UP
BG300 / 400LN Gas nozzle assembly
Natural gas
4-5
12-14
14
2
172 155 05 01- 01
Page 15
DETERMINATION OF GAS VOLUME FOR THE INSTALLATION
Specifications on natural gas, town gas and biogas vary. For more exact information please contact the gas distributor.
Net calorific value
Gas quality kWh/Nm
Natural gas 10.3 37 144 8 865 Propane 26.0 93 647 22 350 Butane 34.3 123 571 29 492 Town gas 4.9 17 653 4 213 Biogas 7.0 25 219 6 019
Example how to calculate the gas volume (natural gas)
V = Gas volume Nm3/h
Q = Boiler output 120 kW
Hu= Calorific value of the gas A. 37 144 kJ/Nm3, B. 10.3 kWh/ Nm
η = Expected efficiency 90%
Ex. A
Ex. B
Q .3 600
=
V
Hu · η
120
=
V
10,3 · 0,90
120 . 3 600
=
37 144 . 0,90
12,9 Nm3/h
3
12,9 Nm3/h
kJ/Nm
3
kcal/Nm
3
3
If the barometer height, pressure and temperature of the gas deviate con­siderably from the normal values this must be taken into account as follows:
f=
273+t
273
1013,25
.
B+P
u
t = Temperature of the gas at the gas meter (15°C)
B = Barometer height (945 mbar)
Pu= Pressure of the gas at the gas meter (15,0 mbar)
f=
273+15
273
1013,25
.
945+15
f 1.11
The gas volume read on the gas meter actually reads 1,11 . 12,9 = 14,4 m3/h.
36
172 205 16 03-01
Page 16
DUNGS COMBI BLOC WITH RATIO ADJUSTMENT
MB-VEF BO1, 407 View
1. Electrical connection gas pressure switch mini
2. Electrical connection gas valve
3. Pressure switch mini
4. Flange connection inlet
5. Test point connection 1/8" before V
1
6. Filter
7. Data plate
8. Connection 1/8" P
L
9. Adjustment screw V for ratio PBr: PL (max. load)
10. Test point connection 1/8" before V1 (before governor)
11. Connection M4 for measurement of burner presssure after V
2
12. Adjustment screw for zero point adjustment N (min. load)
13. Test point connection 1/8" P
14. Test point connection 1/8" P
F
Br
15. Flange connection, outlet
16. Test point connection 1/8" Pa before V2 (after governor)
17. Indication of V1 and V2 in operation (not standard)
1)
18. Impulse line PBr (gas pressure)
19. Impulse line PL (air pressure)
20. Impulse line (fire room)
It is possible to connect a leakage control VPS 504 and a gas pressure switch maxi.
1)
NOTE!
The impulse line PBr can be replaced by an impulse flange on the multiblock.If so, the impulse line PBr is placed included in the flange.
16
172 205 43 03-01
Page 17
MULTI-BLOC, MB-VEF 412 - 425 B01
Technical data
- Max inlet pressure 360 mbar
- Valves V1+V2 class A group 2 in accordance with EN 161
- Governor class A group 2 in accordance with EN88
- Ratio V PBr:PL 0,75:1-3:1
- Filter according to DIN 3386
- Ambient temperature -15°C- +70°C
- Protection standard type IP54 (according to IEC 529, DIN 40050)
- Gas family 1 +2 +3
- Outlet pressure 0,5 - 100 mbar
- Zero point adjustment N ±2 mbar
- Pressure switch DIN3398 TI
- Fan pressure PL0,4-100 mbar
- Fire room pressure PF -2 -+5mbar
- Burner pressure PBr 0,5 - 100 mbar
Mounting instruction - impulse lines PL, PF and P
- Impulse lines should preferably be made of steel. Inside diametre >ø 4 mm (steel tube ø 6/4)
- For PL other material can be used.
- Impulse lines PL and PBR are ready from factory
- Impulse lines shall be mounted in such a way that no conden sate can flow back into the multibloc.This is especially important when PF is concerned.
- Impulse lines shall be mounted in such a way that they are protected against rupture and damage.
- Impulse lines shall be as short as possible
Adjustment possibilities
Adjustment range
pL, min =0,4 mbar
V = 1:1
V = 3:1
Br
V = 0,75:1
pBr, min =0,5 mbar
P
, max. = 100
Br
!
Effective burner pressure
P
= PBr - P
Br
!
Effective fan pressure
PL = PL-P
F
F
V = 3:1
V = 1:1
V
46
PL, max. = 100 mbar
+ N
- N
V = 0,75:1
172 215 16 03-01
Page 18
ADJUSTMENT OF GAS FLOW
- Before the burner starts vent the lines to make sure that there is gas
available at the multibloc
- Use an allen key size 2,5 mm for adjusting N and V.
- Connect a pressure gauge for measur-ing PBr, (advisable to find out if
the valves are open)
- Set the switch in position MAN.
- Set the gas pressure switch min. and air pressure switch on min.
adjustment. Set the gas pressure switch max, if any, on max. adjustment.
- Start the burner, observe the pressure gauge, if no flame is established
and the pressure gauge needle does not flicker, increase N. When the flame is established adjust the gas flow by means of the screw N. Use a flue gas instrument.
- Change over to max. load, press the switch “increase”
- Adjust the gas flow with V and check at the same time the
combustion values.
- Go back to min. load and check the combustion value. Adjust if
necessary.
- If necessary repeat the controls of the adjustment made on min. (N)
and max .load(V)
- The desired gas flow on min. and max. has now been adjusted by
changing the orange and the red cams. Check the gas flow on the gas meter available on the installation.
Damper motor, air volume
Releasing button
Note! Do not forget to set the air and gas pressure switches after the
adjustment, see special instructions.
Adjust the orange cam for min. load (about 5-10 on scale) Adjust the red cam for max. load (90° ) The blue cam is factory set for closed position during standstill The black cam has no function at modulating operation
By pressing the button and snapping it down, the motor will be released and the damper can easily be turned. This function facilitates an exchange of damper motor..
Gas valve (black) Max. load (red)
Min. load (orange) Closed damper (blue)
 
1
o
Releasing button N.B. The upper position is
172 305 68 03-01
Page 19
GENERAL INSTRUCTIONS
General instructions
The installation of the gas burner must be carried out in accordance with current regulations and standards. The installers of gas burners should therefore be acquainted with all regulations and ensure that the installation complies with the requirements. The installation, mounting and adjustment should be made with the greatest care and only the correct gas should be used
Operating instructions
The operating instructions accompanying the burner should be left in a prominent position in the boiler room.
Instructions
The user should be thoroughly instructed in the function of the gas burner and the whole installation. The supplier must instruct the user.
Inspection and maintenance
Daily inspection is advisable.
Start up
Commissioning of installation
Service
Important
After the burner has been fitted to the boiler and the electric connection, the leakage control, the venting and the electric function test have been carried out, the burner will be ready for start-up. Howerer, study the sections dealing with adjustments of multi-bloc, combustion air and combustion head. Open the ball valve and switch on the main switch. If the burner starts the actual adjustment can be made.
Control of the combustion. The combustion quality is checked by means of a flue gas analysis device. Adjust the burner to appr. 20% excess air in accordance with the table. Check the flue gas temperature. Calculate the efficiency. Check also the actual gas volume on the gas meter so that the correct input is achieved.
Service should be carried out by qualified personnel. Replacement parts should be of the same make and approved by the same authorities as the original. If the burner is converted to fire, another gas quality it must be re-commissioned. If town gas is to be fired, the combustion head must be converted and the gas train adjusted to suit (i.e. larger gas armature or a different spring in the governor may be required).
To get as low emissions as possible, the burner, the boiler and the chimney must be adapted to each other.
Gas quality CO2%0
lambda 1,2
Natural gas 10,0 3,5 11,9
18
% max CO2%
2
172 305 61 03-01
Page 20
GENERAL INSTRUCTIONS
Adjustment of shrouded disc and burner head
The burner head is firm adjusted and there are no possibilities of settings besides the adjustment and the inspection of the ignition electrode and the ionisation electrode.
Inspection of burner head when multi-bloc MB...407
The burner head, the shrouded disc and the electrodes can be inspected by following the instructions below: Loosen the nut a, the nut b to the impulse line PL , the plug-in contacts c and the screws d. Pull out the fan housing part. Loosen carefully the ionisation and ignition cables. When the fan housing part is separated from the fixing flange, the combustion unit can be checked as follows: Loosen the screws e and pull out the combustion unit.
Note! Greatest caution at this working moment.
When making service to the burner,
switch off the electric current and the gas supply. Do not forget the gaskets and O-rings and to check the density after the service.
abce
d
This screw should be loosen when pulling out the blast tube. When re­mounting the blast tube, push the blast tube so far into the flange that the ring in the blast tube fits tight to the combustion head.
20
172 305 62 03-01
Page 21
GENERAL INSTRUCTION
Flame monitoring and measurement of ionisation current
The burner is monitored according to the ionisation principle. Check the ionisation current on start-up and on each service call.
The reason for a low ionisation current may be leaking currents, bad connection to earth, dirt or a faulty position of the flame electrode in the burner head. Sometimes also a faulty gas/air mixture may cause too weak a ionisation current.
The ionisation current is measured by means of a microampere meter (μA) connected in series with the flame electrode and the gas burner control.
Connect the μA-meter, see figure. Min. required ionisation current according to table. In practice this current must be considerably higher, preferably more than 10 μA. All the gas burners are equipped with a ionisation cable that can be slit which facilitates the connection of the μA-device.
Gas control Connection to terminal Min. ionisation
in gas control current required
LMG Serie A 1 2 μ A LMG Serie B 2 10 μA LGB 1 10 μ A LFL 24 10 μ A MMI 810 2 5 μ A TMG 740-3 1 5 μ A
Flame monitoring
50
1(3)
172 305 25 05-01
Page 22
GENERAL INSTRUCTION
UV-detector
This should not be exposed to temperatures exceeding 60°C. The current passing through the UV-detector, when it is being illuminated, should be at least 70 μ A for LFL1.. This current can be measured by means of a moving coil instrument. Checks should only be made if a fault is suspected.
The capacitor, which sould be placed between the terminals on the moving coil instrument, must be of 100 μ F 10-25 V.
Flame monitoring
Control box LFL1
UV-detector
μ A
22
1
2
23
51
2(3)
172 305 25 05-01
Page 23
GENERAL INSTRUCTION
Adjustment of air pressure switch
The air pressure switch should stop the burner, if the air volume is reduced. The air proving device shall be adjusted in such a way that if there is insufficient air supply at the highest or lowest burner operating stage, the device operates before the supervised pressure is less than 80% of the pressure at the controlled stage and the CO content of the combustion products exceeds 1% by volume. On adjustment, turn the scale on the air pressure switch in clockwise direction. When the switch-off point has been reached and the burner stops read off the value on the scale. Then turn the scale in anti-clockweise direstion to desired value. Make repeated start attempts to ensure that the air pressure switch is not too closely set.
Adjustment range ca: 1-10 mbar LGW 10 2,5-50 mbar LGW 50
Adjustment of min. gas pressure switch
The min. pressure switch should react if the gas pressure is too low and prevent the burner from starting. Too low a gas pressure during operation should stop the burner. The burner may start again when the rated gas pressure has been reached. Remove the protective cover. Connect a pressure gauge for measuring the rated pressure. Decide on pressure at which the gas switch should switch off. Set this pressure by means of the valve. Carefully turn the knob (see figure) until the gas pressure switch switches off. The value shown on the scale should then approximately correspond with the value shown on the pressure gauge. Tolerance on scale appr. ± 15 %. Open the ball valve.
Adjustment of max. gas pressure switch
The burner is equipped with a max. gas pressure switch only on request. It should stop the burner if the gas pressure exceeds the set value. The burner can then only be re-started manually (gas burner control or overpressure switch). Remove the protective cover. Connect a pressure gauge for measuring the rated gas pressure. Decide on pressure at which the gas pressure switch should switch off. Turn the adjustment knob to this value. Tolerance on the scale ±15%.
Adjustment range: 2,5-50 mbar GW 50 5-150 mbar GW 150
Gas pressure switch, air pressure switch
52
3(3)
172 305 25 05-01
Page 24
HANDING OVER OF THE INSTALLATION
- Make repeated start attempts to ensure that the adjustments function.
- Close the ball valve during operation to check that the gas switch switches off at the set value.
- Remove the hose for the air pressure switch to check that the burner locks out.
- Check that all protective covers and measurement nipples are mounted and fastened.
- Fill out necessary test reports.
- Instruct the persons in charge of the operation on the service and main­tenance of the installation and what to do should any troubles occur.
- Inspection and service must be carried out by authorized
personnel.
Fault location, functional troubles
Trouble free operation is depending on three factors: electricity, gas and air supply. Should there be any changes in the ratio between these three factors, there is a risk of break downs. It has been proved that most break downs are caused by simple faults. Before calling the service engineer, the following should therefore be checked:
- Is the gas cock open?
- Are all fuses in order and the current switched on?
- Are the thermostats correctly set?
- Are pressostats, overheating protection etc. in operating position and not locked-out?
- Is the gas pressure sufficient?
- Is the gas burner control in start position?
- Has the gas control or the motor protector locked out? - Reset.
- Is the circulation pump in operation?
- Is there a supply of fresh air to the installation?
If integral components are of a different make from what is stated in this manual, see the enclosed sheet.
57
172 305 17 03-01
Page 25
FAULT LOCATION GUIDE
Gas burner
The basis for a trouble free operation can only be ensured by the correct combined effect of the three factors: electricity, gas flow and combustion air. Should any of these factors change, troubles may arise.
It has been proved that many troubles have rather simple causes. Before calling the serviceman, the following checks should be made:
1. Are the gas cocks of the installation open?
2. Are the fuses in order and the current switched on?
3. Are the controls (room thermostat, boiler thermostat etc.) correctly adjusted?
4. Is the gas pressure to the burner sufficient?
5. Is the gas relay of the burner ready for start and not locked out?
6. Is the air supply to the burner sufficient?
To facilitate fault location we have drawn up a scheme showing the most frequent faults in a gas burner installation and the remedies.
Cause Remedy
The burner does not start
No gas Check that all gas cocks are open.
No voltage Check fuses, thermostats and
electrical connections.
The burner motor fails to start The thermal protection has locked out.
Motor defective.
The gas relay is defective Replace
Burner motor is running but no ignition after the pre-purge time has elapsed
No voltage on the terminals Check the contact. Replace faulty relay
The ignition electrodes in contact Adjust with each other or with earth
The porcelain of the electrodes is broken Replace the electrodes
The cable shoes have bad contact Improve the contact
The ignition cables are damaged Replace
The ignition transformer is damaged, no voltage Replace the transformer on the secondary side
The ignition cable and the ionisation cable Change have been transposed.
59
1(3)
170 091 16 03-01
Page 26
Cause Remedy
No flame establishment despite a trouble free start
The gas solenoid valve defective Replace
The gas solenoid valve does not open despite Replace coil or the whole valve if necessary. its obtaining voltage
No voltage to the solenoid valve Check the contact
No electrical connection through Test the adjustment and the function of the air pres­the air pressure switch sure switch.
The starting load is not correctly adjusted Reduce or increase the gas supply, reduce the quanti
ty of air.
Gas relay defective Replace
Air pressure switch incorrectly adjusted or defective Check the adjustment and readjust.
No reponse as the cams of the servomotor are not correctly adjusted or out of position.
The burner locks out after the safety time has el­apsed in spite of flame establishment
No ionisation current or the UV-cell in wrong Adjust the ionisation electrode and the UV-cell, position examine cables and connections.
The supervision part of the gas relay is defective Replace the relay
Voltage lower than 185 V Contact the electricity authorities.
The ignition electrodes are disturbing the ionisation Adjust the ignition electrodes, repole the ignition current transformer if necessary.
Bad earthing Arrange for proper earthing.
Phase and neutral transposed See wiring diagram and change.
The burner locks out during pre-purge
Air pressure switch defective or incorrectly adjusted
The starting load is not correctly adjusted Reduce or increase the gas supply. Reduce
. the quantity of air.
The gas pressure is too low Increase the pressure. Contact the gas supply
company if necessary.
Condensation in boiler and chimney
The flow gas temperature is too low or the Increase the flue gas temperature by increasing quantity of gas is not sufficient the gas supply. Insulate the chimney.
60
170 091 16 03-01
2(3)
Page 27
Cause Remedy
Pulsations at start
The ignition electrodes are wrongly adjusted Re-adjust.
The gas pressure is too high Check and adjust by means of a pressure gauge
and a pressure adjustment valve.
The flue gas side is blocked Check the chimney flue.
Pulsations during operation
The burner is not correctly adjusted Re-adjust
The burner is dirty Clean the burner.
Defective chimney Check and change the dimensions if necessary.
The burner is operating correctly but locking out now and then
The ionisation current is too low Check. Must be at least 4 μ A according to the
relay manufacturer but should be 8-20 μ A.
The UV-cell is in a wrong position Adjust.
Voltage drop at certain times Must not drop more than 15% of the rated current.
Air pressure switch defective or incorrectly adjusted Contact the electricity authorities if necessary.
Spark-over in ignition electrodes Replace the electrodes
The ambient temperature of the gas relay is too high Heat insulate, max. 60° C.
The ignition spark is too weak Check the transformer
Bad combustion
Bad draught conditions Check the chimney
The flue gas temperature is too high The boiler is overloaded. Reduce the quantity of gas.
The CO
-content is too low Check the boiler with regard to leaks. Choke
2
the draught if it is too high.
The CO-content is too high
Excess air when using natural gas and Choke the air. gasoil (propane, butane) Air shortage Open the air supply. Check the flue gas damper.
The holes in the gas nozzle are clogged Clean.
The fresh air intake is too small Check and enlarge
The flame is not burning straight because Check the burner head and readjust. the burner head is out of position
61
170 091 16 03-01
3(3)
Page 28
DECLARATION OF CONFORMITY
We (supplier´s name)
BENTONE
.................................................................
(address)
P.O. Box 309, S-341 26 Ljungby, Sverige
.................................................................
declare under our sole responsibility that the product (name, type or model, batch or serial number, possible sources and number of items)
BG 100, BG 150, BG 200, STG 120, STG 146, BG 300,BG 300LN, BG 400, BG 400LN BG 450,BG 450LN,
..........................................................................................................................................................................................
BG 500,BG 500LN, BG550, BG550LN, BG 600,BG 600LN, BG650, BG 700,BG 700LN, BG 800,BG 800LN
....................................................................................................................................................................................................
and BG950 all fan gas burners
.............................................................................................................................................................................................................
to which this declaration relates is in conformity with the following standard(s) or the normative socument(s) (title and/or number and date of issue of the standard(s) or other normative document(s)
EN 676, DIN 4788
...................................................................................................................................................................................................
following the provisions of Directive (if applicable)
Gas directive 90 / 396 / EEC, EMC directive 89 / 336 / EEC och Low voltage directive 73 / 23 / EEC
..........................................................................................................................................................................................
............................................................................................................................................................................................
Ljungby, 031201
...........................................................
(Place and date of issue)
BENTONE
Sven-Olov Lövgren
..........................................................................................................................
(name and signature of equivalent marking of authorized person)
58
172 905 95 09-01
Loading...