Bentone BG 300-2 Installation And Maintenance Instruction

Providing sustainable energy solutions worldwide
178 001 72-4 2018-03-23
Installation- and maintenance instruction
BG 300-2
2
Bentone
3 Bentone
General
Table of contents
1. General Information _____________________________________________ 4
2. Technical data __________________________________________________ 7
2.1 Burners are intended for use at: ________________________________ 7
2.2 Dimensions _________________________________________________ 7
2.3 Description BG 300 _________________________________________ 10
3. General instruktions ____________________________________________ 11
3.1 General instructions _________________________________________ 11
3.2 Installation and maintenance instructions _______________________ 11
3.3 Instructions ________________________________________________ 11
3.4 Inspection and maintenance __________________________________ 11
3.5 Start up ___________________________________________________ 11
3.6 Commissioning of installation _________________________________ 11
4. Installation ____________________________________________________ 12
4.1 Delivery check ______________________________________________ 12
4.2 Preparations for installation ___________________________________ 12
4.3 Gas supply _________________________________________________ 12
4.4 Electric connection __________________________________________ 12
4.5 Skeleton diagrams __________________________________________ 13
4.6 Mounting on the boiler _______________________________________ 14
4.7 Inspection of gas nozzle before commissioning __________________ 15
4.8 Gas nozzle _________________________________________________ 16
4.9 Setting Air damper __________________________________________ 17
4.10 Air adjustment ______________________________________________ 17
4.11 Low load: __________________________________________________ 17
4.12 Full load ___________________________________________________ 17
5. Setting the burner ______________________________________________ 18
5.1 Adjustment of brake plate ____________________________________ 18
5.2 Control of burner head _______________________________________ 18
5.3 Setting the air pressure switch ________________________________ 20
5.4 Setting the min. gas pressure switch ___________________________ 21
5.5 Multiblock MB-ZRDLE 405-412 _______________________________ 22
5.6 Recommended excess air when using default setting _____________ 25
5.7 Determining the gas quantity for the system _____________________ 25
5.8 Calculating the quantity of gas supplied ________________________ 27
6. Service ________________________________________________________ 28
6.1 Servicing the combustion assembly ____________________________ 28
6.2 Replacement of damper motor, air _____________________________ 29
6.3 Flame monitoring and ionisation current check ___________________ 30
6.4 UV-Detector ________________________________________________ 31
7. Handing over of the installation __________________________________ 32
8. Fault location, functional troubles ________________________________ 32
9. Electric equipment _____________________________________________ 33
9.1 Safety system ______________________________________________ 33
9.2 Wiring diagram LME _________________________________________ 34
9.3 List of components __________________________________________ 35
9.4 Control program at faults; fault mode indicator LME .... ___________ 36
10. Troubleshooting _____________________________________________ 38
11. EU Declaration of conformity _________________________________ 41
13. General instructions for gasburners ____________________________ 42
4
Bentone
1. General Information
This Installation and Maintenance manual:
• is to be regarded as part of the burner and must always be kept near the installation site
• is intended for use by authorised personnel
• must be read prior to installation
• must be observed by all who work with the burner and associated system components
• work with the burner may only be carried out by certifi ed installers/ personnel
Enertech AB is not liable for any typographical errors and reserves the right to make design changes without prior notice.
Safety instructions
• The burner may only be used for its intended purpose in accordance with the product’s technical data.
• The burner may only be installed and operated by authorised personnel.
• The product is packaged to prevent damage from occurring during handling. Handle the product with care. Lifting equipment must be used to lift larger packages.
• The products must be transported/stored on a level surface in a dry environment, max. 80% relative humidity, no condensation. Temperature -20 to +60 °C.
• Check that the burner is compatible with the boiler’s output range.
• All components must be installed without being bent, twisted or subjected to mechanical or thermal forces which can affect the components.
• The burner must be installed so that it complies with local regulations for fi re safety, electrical safety, and fuel distribution.
• The gas outlet from the pressure regulator shall be confi gured in accordance with applicable regulations and lead to a safe area.
• Make sure when installing the equipment that there is enough space to service the burner.
• Permitted temperature during operation -10 to +60 °C. Max 80% relative humidity, no condensation.
• The installer must ensure that the room has adequate air supply.
• The room must comply with local regulations pertaining to its intended use.
• The installation site must be free of chemicals.
• Burner pipes, fan wheels and air dampers may contain sharp edges.
• The surface temperature of the burner’s components can exceed 60 °C.
• Caution: The burner has moving parts, and there is risk of crushing injuries.
172 515 01 2018-01-02
5 Bentone
• The electrical installation must be professionally carried out in accordance with applicable high voltage regulations, as per Enertech’s recommendations.
• Before servicing, shut off the fuel supply and turn off the power to the burner.
• Seal inspections must be performed during installation and servicing to prevent gas leakage.
• Care should be taken by the installer to ensure that no electrical cables or fuel lines are crushed or otherwise damaged during installation or servicing.
• If the boiler is equipped with an access hatch, this must be equipped with a hatch opening switch connected to the burner's safety system.
• When in operation, the burner’s noise level can exceed 85 dBA. Use hearing protection.
• The burner must not be put into operation without proper safety and protection devices.
• A Class BE fi re extinguisher is recommended.
• It is forbidden to alter thedesign or use accessories which have not been approved by Enertech in writing.
• Prior to operation, the following points must be checked:
- fi tting and installation work has been completed and approved
- electrical installation has been correctly performed
- fl ue gas ducts and combustion air ducts are not blocked
- all actuators and control and safety devices are in working order and correctly set
Actions to take if you smell gas
Turn off the equipment and the boiler. Open windows and doors. Prevent open fl ames or sparking, e.g. do not turn lights on or off, do not use any electrical appliances, do not use mobile phones. Open windows and doors. Close the gas ball valve. Warn residents; do not use doorbells. Evacuate the building. Notify the installer or gas supplier once the building has been evacuated.
6
Bentone
Control system 10 years 250,000 starts
Valve control system 10 years 250,000 starts
Pressure switch 10 years 250,000 starts
Ignition system with flame guard 10 years 250,000 starts
UV flame sensor 10000 hrs N/A
Gas pressure regulators 15 years N/A
Gas valve without seal testing 10 years 250,000 starts
Gas valve with seal testing Replacement upon fault detection N/A
Gas pressure switch 10 years 250,000 starts
Safety blow-off system 10 years N/A
Damper motor N/A 500,000 starts
Contactor 10 years 500,000 starts
Burner 1 year 3000 hrs
Inspection of electrical installation 1 year 3000 hrs
Leakage check 1 year 3000 hrs
Filter 1 year replacement at ∆p>10 mbar 3000 hrs replacement at ∆p>10
mbar
Electrodes Replacement/Cleaning 1 year Replacement/Cleaning 3000 hrs
Brake disc Replacement/Cleaning 1 year Replacement/Cleaning 3000 hrs
Motor 1 year 3000 hrs
Fan wheel 1 Year
Replacement when cleaning needed/ imbalance
3000 h Replacement when cleaning needed/ imbalance
The burner and its components must be recycled according to applicable regulations.
Burner servicing schedule
Servicing must be carried out once a year or after 3000 hours of operation
Component replacement intervals
Delivery check
• Make sure everything is delivered and the goods have not been damaged during transit.
• If something is wrong with a delivery, report it to the supplier.
• Transport damage must be reported to the shipping company.
7 Bentone
172 515 62 2018-02-02
1.2.1 Heat generator connection dimensions
Type
Length of burner
tube
Flange
measure A
Burner tube
measure B
Burner tube
measure C
BG 300
Standard 1 145 125 ø120 ø110
Standard 2 245 225 ø120 ø110
K L M
BG 300
M10 Ø 175-240 ø125 (***115)
D E F G H I J
BG 300
372 220 100 *380 *460 170 **200
2. Technical data
2.1 Burners are intended for use at:
• Hot water boilers in intermittent operation
2.2 Dimensions
• Gas connection ¾-2”
* The above dimensions are max. measurements. Depending on the
components used, the measurements may vary.
** Min. recommended distance to floor.
***Dimensions when installing blast tubes from the inside of the boiler
A
F
B
C
D
E
G
H
I
**J
K
L
M
Dimensions stated in mm
8
Bentone
2.2.1 Gas categories, approved gases
Only dry gas is permitted for use
2.2.2 Capacity range
Gerätekategorien
Appliance categories
Versorgungsdrücke
Supply pressures
Besimmungsländer
Countries of desinaion
II
2R/3R
20-360mBar BG, CZ, DE, EE, ES, FR, GR, HU, IS,
IT, LU, LV, NO, PT, SI, All countries
II
2H3B/P
20-360mBar AT, CH, CY, DK, FI, LT, RO, SE,
II
2H3P
20-360mBar GB, IE,
II
2L3B/P
20-360mBar NL, RO
II
2E3B/P
20-360mBar PL
I
2E(R)B
20-360mBar BE
I
3P
20-360mBar BE
Capacity kW Gas quantity
at min. power
Nm3/h 1)
Gas quantity
at max. power
Nm3/h 1)
Max.
connection
pressure
mbar
Min connection
pressure mbar
See data plate
Lower heat value Hu at normal state 15°C and 1013.25 mbar EN676
Grade of gas
Natural gas
Natural gas
Butane
Propane
BG 300
G20 50-200 5.2 21 360
G25 50-180 6,1 21.9 360
G30 65-200 2.6 8.1 360
G31 50-200 1.5 6,1 360
kWh/Nm
3
MJ/Nm
3
kcal/Nm
3
G20 9.5 34.02 8126
G25 8.2 29.25 6986
G30 32.5 116.09 27728
G31 24.6 88.00 21019
9 Bentone
2.2.3 Electric Specification EN 60335-2-102
Burner correspond to IP20
Type BG 300
Motor
180W 230V 1,3A 50Hz
The recommended main fuse
motor
C10A
Control power
230V 2,1A 50Hz
Sound
82 dBA ± 0,5 dBA
2.2.4 Working field
BG 300
G20,G31 50-200 kW
BG 300
G30 65-200 kW G25 50-180 kW
-1
0
1
2
3
4
40 60 80 100 120 140 160 180 200 220
kW
G20, G31
mbar
-1
0
1
2
3
4
40 60 80 100 120 140 160 180 200 220
kW
G30, G25
mbar
!
Do not exceed working field
Measurements according to EN 3746: 2010
Alt.1 The sound level of the burner can be reduced by equipping the burner
with silencer. Installation must be done so it does not prevent air supply to the burner.
Alt.2 The burner’s noise level can be reduced by connecting the burner’s air
intake to the air duct that opens into an appropriate location. Installation must be done so it does not prevent air supply to the burner.
10
Bentone
2.3 Description BG 300
Components
1. Switch 0-1
2. Switch I-II
3. Cover, inspection glass
4. Reset button
5. Air pressure switch
6. Damper motor
7. Inner assembly adjustment (not town gas)
8. Flame cone
9. Connection gas fittings
10. Air damper
11. Air intake
12. Ignition electrode
13. Electric panel
14. Indicating lamp Stage 2
15. Indicating lamp Stage 1
16. Fan wheel
17. Motor
18. Ionization electrode
19. Transformer
20. Inner assembly
21. Nozzle
22. Brake plate
11 Bentone
172 515 03 2018-01-02
3. General instruktions
3.1 General instructions
The installation of the gas burner must be carried out in accordance with current regulations and standards. The installers of gas burners should therefore be acquainted with all regulations and ensure that the installation complies with the requirements. The installation, mounting and adjustment should be made with the greatest care and only the correct gas should be used.
3.2 Installation and maintenance
instructions
The maintenance instructions supplied with the burner must be kept at an easily accessible location in the boiler room.
3.3 Instructions
The user should be thoroughly in-structed in the function of the gas burner and the whole installation. The supplier must instruct the user.
3.4 Inspection and maintenance
See service schedule.
3.5 Start up
After the burner has been fitted to the boiler and the electric connection, the leakage control, the venting and the electric function test have been carried out, the burner will be ready for start-up.
Howerer, study the sections dealing with adjustments of multi-bloc, combustion air and combustion head. Open the ball valve and switch on the main switch. If the burner starts the actual adjustment can be made.
3.6 Commissioning of installation
Control of the combustion. The combustion quality is checked by means of a flue gas analysis device. Adjust the burner to appr. 20%
excess air in accordance with the table. Check the flue gas temperature. Calculate the efficiency. Check also the actual gas volume on the gas meter so that the correct input is achieved.
12
Bentone
172 515 03 2018-01-02
4. Installation
4.1 Delivery check
Check that all has been delivered and that the goods have not been damaged during transport. If that is not the case, please notify the delivery company. Transport damages should be reported to the forwarding agency.
4.2 Preparations for installation
Check that the measurements and capacity range of the burner are compatible with the boiler. The power ratings on the type plate refer to the min. and max. power of the burner.
4.3 Gas supply
For good operating safety, it is important that the gas supply system is installed correctly. Consider the following:
1. Check that the burner is approved for the gas quality of the installation. If not, please contact the supplier.
2. Check that the gas components of the burner are approved for indicated gas pressure.
3. The gas supply system should be installed in accordance with current standards.
4. Pipe lines should be run so that service on boiler and burner is facilitated.
5. Pipe lines should be run so that eventual contaminants cannot come into contact with the gas components.
6. Gas discharge system must be installed prior to local regulations.
4.4 Electric connection
Before starting the electric installation, the main switch must be turned off. If the boiler has a 7-pole and a 4-pole Eurostecker connector, these usually fit directly to the burner. If not, use the connectors included. (Refer to connection under Electric equipment)
!
If an electric connection other than the one recommended by Enertech is used, a risk of damage and injury can arise.
13 Bentone
172 515 05 2018-01-02
4.5 Skeleton diagrams
1. Ball valve
2. Filter
3. Governor
4. Pressure gauge with shut-off cock
5a. Gas pressure switch, mini
5b. Gas pressure switch, maxi
6a. Main valve, 2 -stage. When modulaing operation is required this
valve is equipped with controls for variable opening.
6b. Safety valve
1)7. Valve proving system
9. Air pressure switch
10. Gas burner control
Pos. 5b, 7: Components not required according to EN 676.
1) Required over 1200 kW according to EN 676.hhh
14
Bentone
4.6 Mounting on the boiler
Remove the combustion unit from the burner. Fit the enclosed flange and gasket to the boiler. If new fixing holes must be drilled, use the fixing flange as a pattern.
Removal of valve unit from burner
Remove the plug-in contact from the multi-bloc. Loosen the union nut.
Removal of fan house unit from burner.
Remove the screws (A). Swing out the fan housing. Remove the ionisation and ignition wires from the electrodes. Remove the bolt (B) on the spectacle flange. Lift away the fan housing.
Installation example
Connect the gas to the burner by means of the ball valve. Ensure that the union nut, ball valve and tubing make it easy to remove the burner for inspection and service.
B
A
!
Check the gas tightness.
172 515 06 2018-01-02
15 Bentone
172 515 08 2018-01-02
4.7 Inspection of gas nozzle before
commissioning
General rules
Care should be taken by the installer to ensure that no electrical cables or fuel/gas pipes are trapped or damaged during installation or service/ maintenance.
Gas nozzle
Check that the ignition and ionisation electrodes are correctly set. In the figure (see the gas nozzle chapter), the dimensions are specified for adjustment of the ignition and ionisation electrodes.
Gas quality
Ensure that the burner head is meant for the gas quality to be used (see capter gas nozzle).
De-aerating
De-aerating of the gas line is conducted, for example, by unscrewing the screw on the measuring nipple for the connection pressure. Connect a plastic hose and release the gas in a safe place. Once de-aerating is completed, be sure to refit the screw on the measuring nipple.
Leakage control
When making a leakage control of the gas supply system the solenoid valve should be closed. Connect a pressure gauge to the test nipple Pa, see fig. The test pressure in the system should be 1,5x max. inlet pressure or min. 150 mbar. If any leakage, locate the source by means of soapy water or a leak location spray. After tightening repeat the test.
Electric function test:
Ensure that phase and neutral are not reversed. The gas shut-off cock should be closed.To prevent the gas pressure switch from locking out it should be linked temporarily.
After the main switch has been switched on and the thermostats have been adjusted the pre-purging period begins (30-35sec.). At the end of this period the pre-ignition period starts (0,5-2,5 sec. dependent on the design of the gas control). The gas valve is energized and opens and flame is established. At the end of the safety time (2-3 sec.) the gas control locks out. The solenoid valve and the motor will be "dead". Remove the link from the gas pressure switch after the test is finished.
Note on 2-stage and modulating burners that during the pre-purging period the damper opens to the set value for air on stage 2 and just before the end of the pre-purging period it goes down to the air setting for stage 1. On some burners under 350kW the pre-purging mainly takes place with the air damper set for stage 1.
!
If the burner is directly connected, ensure that all components on the burner are without power.
16
Bentone
172 515 08 2018-01-02
4.8 Gas nozzle
Natural gas
Propan
Biogas (UV detector)
2,5
8,0
17 Bentone
172 515 14 2018-01-02
4.9 Setting Air damper
4.10 Air adjustment
The damper motor turns the damper between three pre-set positions: fully closed, low load, full load. These positons are controlled in the motor by cams of different colours. The black cam controls the gas valve for full load. If the air volume needs changing: Remove the cover of the damper motor and change the position of the cams by turning them with the tools accompanying the burner.
4.11 Low load:
Adjust the operating switch to full load (ll).
- * Reduce the air volume: Turn orange cam towards 0°
- * Increase the air volume: Turn orange cam towards 90°
Adjust the operating switch back to low load and check the air volume.
4.12 Full load
Adjust the operating switch to low load.
- Reduce the air volume: Turn red cam towards 0°
- Inrease the air volume: Turn red cam towards 90°
If the red cam is moved, change the black cam as much. Adjust the operating switch to low load and check that the correct air volume has been obtained.
Note! The blue cam is the limit position for fully closed damper and it is normally not necessary to change it.
Releasing button
By pressing the button and snapping it down, the motor will be released and the damper can easily be turned. This function facilitates an exchange of damper motor.
Releasing button
N.B! The upper position is the standard positiont
High capacity (red)
Low capacity (orange)
Closed damper (blue)
Solenoid valve High capacity (black)
18
Bentone
172 515 10 2018-01-02
5. Setting the burner
5.1 Adjustment of brake plate
-Loosen the screw on the adjustment device.
-To reduce the opening: turn the knob to the left.
-To increase the opening: turn the knob to the right.
The adjustment of the position of the brake plate affects the air flow. It is therefore always necessary to make a fine adjustment of the air by means of the adjustment device of the burner.
5.2 Control of burner
head
To check the burner head, brake plate and electrodes proceed as follows:
Loosen the nuts a. Swing out the burner. Remove the screw b and the knob for adjustment of burner head. Loosen the screw c so much so that the inner assembly can be pulled out.
Control of burner head
Adjustment of inner assembly
19 Bentone
General instructions
The installation of the gas burner must be carried out in accordance with current regulations and standards. The installers of gas burners should therefore be acquainted with all regulations and ensure that the installation complies with the requirements. The installation, mounting and adjustment should be made with the greatest care and only the correct gas should be used.
Operating instructions
The installation and maintenance instructions supplied with the burner must be kept at an easily accessible location in the boiler room.
Instructions
The user should be thoroughly in-structed in the function of the gas burner and the whole installation. The supplier must instruct the user.
Inspection and maintenance
Inspection as needed, preferably daily. Maintenance per service schedule.
Start up
After the burner has been fitted to the boiler and the electric connection, the leakage control, the venting and the electric function test have been carried out, the burner will be ready for start-up.
Howerer, study the sections dealing with adjustments of multi-bloc, combustion air and combustion head.
Open the ball valve and switch on the main switch. If the burner starts the actual adjustment can be made.
Adjustment of burner head
The burner is equipped with an adjustment device changing the po si tion of the brake plate in the burner head. This is used to adjust the cor rect pressure drop over the com bus tion device in order to obtain a good pulsation free combustion.
Which position to use depends on input and overpressure in the boiler.
A general rule is that the lower capacity the smaller the opening between brake plate and combustion device.
Commissioning of installation
Control of the combustion. The combustion quality is checked by means of a flue gas analysis device. Adjust the burner to appr. 20% excess air in accordance with the table. Check the flue gas temperature. Calculate the efficiency. Check also the actual gas volume on the gas meter so that the correct input is achieved
Service
Service should only be carried out by qualified personnel. Replacement parts should be of the same make and approved by the same authorities as the original. If the burner is converted to fire another gas quality it must be re-commissioned. If town gas is to be fired the combustion head must be converted and the gas train adjusted to suit (e.g.a larger gas armature or a different spring in the governor may be required).
Gas quality CO2%
lambda 1,2
02% max. CO2%
Natural gas 10,0 3,5 11,9
LPG 11,5 3,5 13,9
20
Bentone
!
Be careful when adjusting the air pressure switch; it contains a live component.
Inställningsområde ca: LGW 10 1-10 mbar LGW 50 2,5-50 mbar
5.3 Setting the air pressure switch
The air pressure switch should block the burner if the air quantity supplied for combustion is insufficient. The air pressure switch must be set so that, if there is a defective air supply at the burner’s max. or min. capacity, it reacts before the monitored pressure falls so much that it results in poor combustion.
Setting for air pressure switch
1. Remove the protective cover, screw (Y).
2. Start the burner.
3. Carefully turn the scale on the air pressure switch clockwise until the air pressure switch stops the burner. Is the tolerance on the scale for
the min. air pressure switch approx. ±15%?
4. Try to find the pressure at which the burner stops for both the minimum and maximum input power by turning the scale. Make a note of the values and then set the air pressure switch on the basis of the highest pressure noted at which the burner stopped.
5. The air pressure switch should be set to a pressure approx. 10–15% lower than the highest noted pressure at which the burner stopped.
6. After setting the air pressure switch, perform repeated starts and run through the burner’s set output range several times. This is to ensure the reliable function of the burner. If breakdowns or interruptions occur, the air pressure switch is probably set to a too narrow position.
7. Fit the protective cover, screw (Y).
Y
Y
21 Bentone
5.4 Setting the min. gas pressure
switch
The min. gas pressure switch should react to a burner connection pressure that is too low and in such cases prevent the burner from starting. If the connection pressure to the burner is too low during operation, the min. gas pressure switch should stop the burner. The burner can start again once the connection pressure has risen above the pressure set for the min. gas pressure switch.
Setting for min. gas pressure switch
1. Remove the protective cover, screw (Y).
2. Open the pressure outlet (X) and connect a manometer to measure the connection pressure.
3. Start the burner.
4. Measure and make a note of the connection pressure to the burner during normal operation at the highest input power.
5. Based on the desired connection pressure set, determine the connection pressure at which the gas pressure switch should stop the burner. Set the connection pressure at which the burner is stopped at a level where the burner is stopped before poor combustion occurs.
6. Set the min. gas pressure switch to this value by turning the scale.
7. Check the setting by carefully closing the ball valve while measuring the connection pressure.
8. When the min. gas pressure switch stops the burner, the value measured should then approximately correspond to the setting on the min. gas pressure switch. The tolerance on the scale for the min. gas pressure switch is approx. ±15%.
9. Open the ball valve.
10. Remove the pressure gauge and close the pressure outlet (X).
11. Fit the protective cover, screw (Y).
!
Check the gas tightness.
X
Y
22
Bentone
!
All gasline components shall be assembled and mounted without bending, torque and outher mechanical or thermal stress.
1. Gas pressure switch
2. Inlet pressure
3. Governor with pressure adjustment
4. Hydraulic device, adjustment of stage 2
5. Protective cover, start gas adjustment
6. Lock screw for fl ow adjustment
7. Main valve
8. Knob for adjustment of stage 1
9. Test nipple, pressure after governor
10. Test nipple for nozzle pressure
11. Filter
12. Fixing fl ange
13. Ball valve
5.5 Multiblock MB-ZRDLE 405-412
1
2
3
4
5
6
7
9
11
12
10
8
13
Max. inlet pressure: 360 mbar. Adjustable governor pressure: 405 - 412 S50 = 4 - 50 mbar 415 - 420 S20 = 4 - 20 mbar 415 - 420 S50 = 20 - 50 mbar
Solenoid valve: Slow opening valves with adjustable start load, stage 1 and stage 2.
Turn to the left = the start gas fl ow is increased.
172 515 11 2018-01-03
23 Bentone
Flow adjustment 2-stage design
For stage 1, loosen the lock screw a. Turn the hydraulic device e:
to the right = the gas flow is reduced
to the left = the gas flow is increased
For stage 2, turn the hydraulic device b:
to the right = the gas flow is reduced
to the left = the gas flow is increased
Do not forget to tighten the lock screw again.
Adjustment of governor
Adjust outlet pressure from governor by means of a screw driver. Min. and max. outlet pressures correspond to appr. 60 turns of the spring. It is not possible to change pressure springs in order to change the outlet pressure.
Turn to the right = the outlet pressure is increased
Turn to the left = the outlet pressure is reduced
Adjustment of start gas flow
Remove the protective cover c.
Turn the adjustment knob d (use the protective cover as a tool) to the desired start gas flow.
Turn to the right = the start gas flow is reduced
Turn to the left = the start gas flow is increased
Adjustment of governor
Adjustment of start gas flow
Multi-bloc MB-ZRDLE 405-420
Flow adjustment
172 515 11 2018-01-03
24
Bentone
5.5.1 Pressure taps
1,2,3,4,5 1/8 screwed sealing plug
5.5.2 Electrical connection
S 20/S 50
172 515 11 2018-01-03
25 Bentone
Lower heat value Hu at normal state 15°C and 1013.25 mbar EN676
Grade of gas kWh/Nm
3
MJ/Nm
3
kcal/Nm
3
Natural gas G20 9.5 34.02 8126
Natural gas G25 8.2 29.25 6986
Propane G31 24.6 88.00 21019
Butane G30 32.5 116.09 27728
5.6 Recommended excess air when
using default setting
Grade of gas Excess air flue gases Max. % CO
2
% O
2
% CO2 Lambda 1.2
Natural gas 3–5 ≈10 11.9
Propane 3–5 ≈11.5 13.9
Butane 3–5 ≈11,5 14,1
Liquefied petroleum gas (LPG)
3–5 ≈11 13,8
5.7 Determining the gas quantity for
the system
The heat values indicated are normal values; the heat value varies according to the origin of the gas. For more exact information on values, contact the gas distributor.
172 515 13 2018-01-02
26
Bentone
T = Temperature of gas at the gas meter [°C]
B = Barometer reading [mbar]
P = Pressure of gas at the gas meter [mbar]
f = Factor calculated for multiplication with flow in Nm
3
/h to
arrive at actual flow in Nm
3
/h.
V = Actual flow [m
3
/h]
f =
273
·
B+P
273+T 1013.25
Example A V
0A
= Q . 3600
=
160 · 3600
≈ 18.8 Nm
3
/h
H
u
· η
34020 · 0.90
Example B V
0B
= Q
160
≈ 19 Nm
3
/h
H
u
· η
9.5 · 0.90
Example C V
0C
=
Q
=
160
≈ 19 Nm3/h
H
u
· 0,00116 · η
8126 · 0.00116 · 0.90
If the barometer reading (altitude), pressure and temperature of the gas deviate significantly from normal values, this must be taken into account as follows:
Calculation example:
Q = 160 kW
H
U
= Example A: 34020 MJ/Nm
3
Example B: 9.5 kWh/Nm3
Example C: 8126 kcal/Nm
3
η = 90%
V0 = Desired quantity of gas [Nm3/h]
Q = Boiler output [kW]
H
U
= Gas heat value [kWh/Nm3] or [MJ/Nm3] or [kcal/
Nm3]
η=
Boiler efficiency [%]
5.7.1 Example of how to calculate the gas quantity
(natural gas G20):
27 Bentone
M = 330 = 0.33 m
3
1000
t = 1 + 10 = 0.0194 h
60 3600
V = M = 0,33 17 m
3
/h
t 0.0194
Calculation example:
t = 1 min 10 s
M = 330 dm
3
(litre)
V = M
[m
3
/h]
t
5.8 Calculating the quantity of gas
supplied
The quantity of gas supplied can be calculated if the system is equipped with a gas flow meter of some type. The procedure here is usually to measure how long it takes for the burner to consume a certain quantity of gas.
To measure:
t = Time for a certain quantity of gas consumed by the burner. [h]
M = Quantity of gas consumed. [m
3
]
V = Actual gas flow [m
3
/h]
V = V
0
. f
V
A
= V
0A
. f = 18.8 . 0.90 ≈ 17 m3/h
V
B
=
V
0B
. f = 19 . 0.90 ≈ 17 m3/h
V
C
=
V
0C
. f = 19 . 0.90 ≈ 17 m3/h
This means that the quantity of gas read from the gas meter should actually be read off as 1.11 . the calculated flow in a normal state.
f = 273
.
945+15
≈ 0.90 Nm
3
/h
273+15 1013.25
Calculation example:
T = 15°C
B = 945 mbar
P = 15 mbar
28
Bentone
172 615 08 2018-01-03
6. Service
Whoever carries out service and maintenance on the burner must be authorised to do so. If components need to be replaced, the replacements must be of the same make and type and be approved by the authorities. If the burner is to be used for a different grade of gas, a new adjustment must be carried out. If town gas is to be used, it is also necessary to convert the combustion assembly; in some cases the multi-block or valves and gas train may also need to be changed to a larger type.
6.1 Servicing the combustion assembly
Removal and installation
1. Switch off the main power supply and disconnect the Euro plugs from the burner.
2. Remove the screws (A), turn off the burner Remove the ignition and ionisation cables
3. Check the combustion device’s position. Remove the screw (B) to remove the adjustment device.
4. Remove the screw (C), remove the combustion device.
5. Check and clean the brake plate and gas inlet. If necessary, replace the worn parts.
6. Check the ignition electrode (see chapter Gas nozzle). Replace if necessary.
7. Check the ionisation electrode (see chapter Gas nozzle). Replace if necessary.
8. Fit the combustion assembly in reverse order.
9. Press the burner together and lock using the nuts (B).
10. Fit the Euro plugs and turn on the main power supply.
11. Check/adjust the combustion.
!
If the burner is directly connected, ensure that all components on the burner are without power.
29 Bentone
G
G
G
H
I
I
I
6.2 Replacement of damper motor, air
Removal and installation
1. Break the main current and disconnect the Euro plugs from the burner.
2. Note the connection position of the cables on the damper motor.
3. Disconnect the damper motor cable from the damper motor.
4. Loosen the screws (G) to the damper motor mounting plate.
5. Decouple the damper motor and rotate to approx. 70°.
6. Lift up the damper motor.
7. Loosen the screw (H) and remove the damper from the motor shaft
8. Remove the screws (I) securing the damper motor to the mounting plate.
9. Remove the damper motor from the mounting plate (I).
10. Install the new damper motor on the mounting plate.
11. Mount the damper to the damper motor’s shaft. Ensure that the screw is perpendicular to the plane of the shaft.
12. Re-install the damper motor and mounting plate on the air intake. Ensure that the damper shaft and control arm are connected correctly.
13. Connect the damper motor cable.
14. Fit the Euro plugs and turn on the mains power.
15. Check/adjust the combustion.
!
If the burner is directly connected, ensure that all components on the burner are without power.
- Releasing button
By pressing the button and snapping it down, the motor will be released and the damper can easily be turned. This function facilitates an exchange of damper motor.
30
Bentone
7.5 Flame monitoring and ionisation
current check
The standard version of the burner is monitored according to the ionisation principle. The ionisation current should be checked on initial start-up and at each service visit. The reason for low ionisation current can be leakage current, poor connection to earth, fouling or incorrectly positioned ionisation electrode in the combustion head. Occasionally, an incorrect gas/air mix may result in poor ionisation current. Ionisation current is measured using a micro ammeter (µA) connected in series with the ionisation electrode and gas burner control. Connect the µ ammeter according to the diagram. The minimum required ionisation current is shown in the table. In practice, this current must be significantly higher, preferably more than 10µA. Connection of the µA instrument is made easier by the fact that all gas burners are equipped with a divisible ionisation cable.
Technical data
For continuous operation!
Idle voltage at ION-terminals AC 115-230 V
!
Protect the ionisation electrode from electric shock!
Short-circuit current Max. AC 100-300 mA
Min. current for flame detection Min. DC 1.5 µA
Required current to ensure detection
Min. DC 3 µA
Possible detection current Max. DC 20 µA
Operational indicator lamp flashes green
<5 µA DC
Operational indicator lamp shines green
>5 µA DC
172 615 02 2018-01-02
31 Bentone
DC current detector signals with flame detector QRQ...
Min. required Max. possible
Measurement at the flame detector QRA… 200 A 500 A
In connection with burner controls LMExx.xxxx2, use of UV ancillary unit AGQ3...A27 is mandatory. Correct functioning of aged UV cells can be checked as UV test with a higher supply voltage across the UV cell after controlled shutdown until terminal 3 ON.
Ancillary unit AGQ3...A27
7.6 UV-Detector
Connection diagram Measuring circuit for measuring the
UV flame current
Measurement made at the flame detector QRA…
32
Bentone
172 615 04 2018-01-02
7. Handing over of the
installation
• Make repeated start attempts to ensure that the adjustments function.
• Close the ball valve during operation to check that the gas switch switches off at the set value.
• Remove the hose for the air pressure switch to check that the burner locks out.
• Check that all protective covers and measurement nipples are mounted and fastened.
• Fill out necessary test reports.
• Instruct the persons in charge of the operation on the service and maintenance of the installation and what to do should any troubles occur.
• Inspection and service must be carried out by authorized personnel.
8. Fault location, functional troubles
Trouble free operation is dependent on three factors: electricity, gas and air supply. Should there be any changes in the ratio between these three factors there is a risk of break downs. It has been proved that most break downs are caused by simple faults. Before calling the service engineer, the following should therefore be checked:
• Is the gas cock open?
• Are all fuses in order and the current switched on?
• Are the thermostats correctly set?
• Are pressostats, overheating protection etc. in operating position and not locked-out?
• Is the gas pressure sufficient?
• Is the gas burner control in start position?
• Has the gas control or the motor protector locked out? - Reset.
• Is the circulation pump in operation?
• Is there a supply of fresh air to the installation?
• If integral components are of a different make from what is stated in this manual, see the enclosed loose-leaf.
!
Review and service should be performed by authorised personnel only
33 Bentone
9. Electric equipment
9.1 Safety system
Safety systems must be installed in accordance with regulations that are applicable for the appliance. This may differ according to the process burner are installed in to. Se local regulations for information.
Safety system cables must be run in separate cables outgoing signal must not come in same cable as incoming signal. Signals must be in different harnesses for safety reasons.
Safety system as door switches, water level, pressure, temperature and other safety limiters must be installed in safety loop according to process.
172 615 13 2018-01-12
34
Bentone
9.2 Wiring diagram LME
If there is no Plug-in contact (X4,X6) on the boiler, connect to the contact enclosed.
If S6 is missing connect T6 and T8.
1N~50/60Hz 230V
35 Bentone
9.3 List of components
A1 Gas burner control
B1 Ionization electrode
F1 Operating fuse
H1 Lamp, low capacity
H2 Lamp, high capacity
H3 Alarm signal 230 V
M1 Burner motor
M2 Damper motor, L&S
SQN75.254.A21B
P1 Time meter, total operating
time
P2 Time meter, high capacity,
total operating time
S1 Operating switch
S2 Operating switch, stage 2
S3 Control thermostat
S4 Temperature limiter
S5 Micro switch for hinged door
S6 Control thermostat, stage 2
S7 Main switch
S8 Air pressure switch
S9 Gas pressure switch
T1 Ignition transformer
X1 Connection terminal board
X2 Earth terminal
X3 Plug-in contact, burner
X4 Plug-in contact, boiler
X5 Plug-in contact, stage 2,
burner
X6 Plug-in contact, stage 2,
boiler
Y1 Gas solenoid valve 1
Y2 Gas solenoid valve 2
9.3.1 Function LME...
1. Operating switch ON-Thermostat ON-Gas pressure switch ON
A check that the air pressure switch does not indicate fan pressure is carried out
2. Burner motor starts
A check that the air pressure switch indicates sufficient fan pressure is carried out
3. The ignition spark is created
4. The gas solenoid valve is open
The gas is ignited. The ionisation electrode now indicates a flame
5. The safety time expires
The ignition spark ceases. The safety period ceases. If the spark is missing or it disappears after this time limit, the gas burner control is blocked
6. Operating position
7. Stop
The operation of the burner can now be stopped with the control switch or thermostat
If the gas burner control is blocked
Red light in the gas burner control is lit. The burner is restarted by pushing the reset button
36
Bentone
Light period (waiting period ≥ 10 s)
Blinking code
Pause
Blinking code
Press the reset button > 3 s
9.4 Control program at faults; fault
mode indicator LME ....
9.4.1 Colour codes
Table colour codes for multi-coloured signal light (LED)
Status Colour codes Colours
Waiting period «tw», other waiting periods
○…………………
Off
Ignition phase, ignition controlled
•○ •○ •○ •○ •○ •
Blinking yellow
Normal operation
□…………………
Green
Operation, poor flame signal
□○□○□○□○□○
Blinking green
Illegal flame signal during start-up
□▲□▲□▲□▲□▲
Green-Red
Undervoltage
●▲●▲●▲●▲●▲
Yellow-Red
Fault, alarm
▲…………………
Red
Blinking code for fault codes
▲○ ▲○ ▲○ ▲○
Blinking red
Interface diagnostics
▲▲▲▲▲▲▲▲
Red flicking
9.4.1.1 Diagnosing alarm causes
After alarm disconnection, the red alarm signal light is lit continuously. The diagnosing of the alarm cause can be read according to the following sequence:
……
Continuous
Off
Red
Yellow
Green
9.4.1.2 Limiting of starting repetitions
LME 11... has a function with start repetition if the flame is not created at start or disappears during operation.. LME 11... allows max. three repetitions during continuous starting cycle.
37 Bentone
9.4.1.3 Alarm code table
Red blinking code on signal lamp (LED)
Possible causes
Blinking 2 x
..
No flame creation at End of “TSA”
- defective or fouled flame monitoring
- defective or fouled fuel valves
- poor burner setting
- defective firing device
Blinking 3 x
...
“LP” defective
- No air pressure switch signal after “t10”
- “LP” is welded in open position
Blinking 4 x
....
Illegal flame signal during start-up
Blinking 5 x
.....
Time out “LP”
- “LP” is welded in open position
Blinking 6 x
......
Free
Blinking 7 x
.......
Too many flame disappearances during operation
- poor burner setting
- defective or fouled fuel valves
- defective or fouled flame monitoring
Blinking 8 x
........
Free
Blinking 9 x
.........
Free
Blinking 10 x
..........
Connection fault or internal fault, outgoing contacts or other faults
Blinking 14 x
..........
....
CPI contact not closed
During the diagnosing of the alarm cause, the control outputs are voltage­free.
• The burner is disconnected
• Exception, alarm signal «AL» at board 10
• Reconnection of the burner happens after resetting only.
• Press the reset button 0.5...3 s
9.4.1.4 Interface diagnostics
To change to interface mode, press and hold the reset button longer than 3 s. To go back to the normal position, press and hold the reset button longer than 3 s. If the gas burner control is in the alarm position, it is reset by pressing the reset button 0.5...3 s.
38
Bentone
172 615 06 2018-01-10
10. Troubleshooting
Gas Burner
Conditions favourable to disruption-free operation of the system can only be guaranteed through the interaction between three factors – electricity, gas flow and combustion air. A change in any of these factors may cause disruptions.
It has been shown that a large proportion of disruptions can be attributed to relatively small things. Therefore, before requesting servicing, you should ascertain the following:
1. Are the system’s gas taps open?
2. Are the fuses intact and is the power on?
3. Are control devices (room thermostat, boiler thermostat, etc.) correctly set?
4. Is gas pressure to the burner sufficient?
5. Are the burner controls on standby and not locked?
6. Is air supply to the burner adequate?
To facilitate troubleshooting, we have created a table of the most common faults that may arise in a gas burner system and how they should be rectified.
Cause of fault Action
Burner does not start
No gas Make sure all gas taps are open
No power Check the fuse, thermostat and electrical
connections
Burner motor does not start Motor protection has tripped. Motor faulty.
Burner control faulty Replace
Burner motor running, no ignition spark at the end of pre­aeration
No power in the terminals Check the connector. Replace faulty burner
controls
Ignition electrodes in contact with each other or earth Adjust
Ignition electrode porcelain damaged Replace the electrodes
Poor connection to cable connectors Adjust connection
Ignition cables damaged Replace
Transformer damaged, no power to secondary winding Replace the transformer
Ignition cable and ionisation cable swapped around Reconnect
No flame propagation
Gas solenoid valve faulty Replace
Gas solenoid valve does not open despite having power Replace solenoid valve terminals, or entire
valve
No power to solenoid valve Check the connection
No electrical connection through air pressure gauge Check the air pressure gauge’s settings and
functions
Ignition load incorrectly set Increase/decrease gas supply Reduce
airflow
39 Bentone
Cause of fault Action
Burner control faulty Replace
Air pressure gauge incorrectly set or faulty Check the settings and reset, or replace
No acknowledgement signal due to incorrect adjustment or misalignment of the control motor cams.
Check the settings and realign.
Burner trips after safety time limit despite flame propagation
No ionisation current or UV cell incorrectly positioned Adjust ionisation electrode and UV cell
Check cables and connectors
Burner control monitor faulty Replace burner control
Voltage lower than 185 V Contact an electrician
Ignition electrodes disrupting ionisation current Adjust ignition electrodes. Re-polarise the
transformer
Poor earth connection Ensure adequate earth connection
Phase and neutral swapped around Check wiring diagram and change
accordingly
Burner trips during pre-aeration.
Air sensor faulty or incorrectly set Increase/decrease air setting. Reduce air
volume
Ignition load incorrectly set Increase/decrease gas supply Reduce
airflow
Gas pressure too low Increase pressure. If necessary, contact gas
supplier
Pulsations at start-up
Ignition electrodes incorrectly set Adjust
Gas pressure too high Check and adjust using pressure gauge and
pressure control valve
Flue gas side blocked Check the chimney flue
Burner pulsates during operation
Burner incorrectly set Adjust
Burner dirty Clean the burner
Incorrect chimney Check and modify dimensions if necessary
Burner functioning properly but with occasional blockage
Ionisation current too low Check. Must be at least 6 µA, but should
ideally lie between 8 and 20 µA
UV cell incorrectly positioned Adjust
Voltage drop at certain times Must not drop below 15% of rated voltage.
Contact an electrician if necessary
Incorrectly set or faulty air sensor Check the settings and reset, or replace
Ignition electrode overload Replace
Burner control ambient temperature too high Insulate for heat, Max. 60 °
Ignition spark too weak Check the transformer
Poor combustion
Poor draught conditions Check the chimney
40
Bentone
Cause of fault Action
Flue gas temperature too high Boiler overloaded Decrease the gas volume,
sweep the chimney if necessary
CO
2
content too low Choke the air supply. Check the boiler for
any leakages. Choke the draught if too high
CO content too high
Surplus air when using natural gas and liquefied petroleum (propane, butane)
Choke the air supply
Poor air supply Open the air supply. Check flue gas damper
Holes in gas nozzle clogged. Clean
Poor fresh air intake Check and increase
Flame at incorrect angle due to combustion head out of position Check the combustion head and readjust
Condensation build up in boiler and chimney
Flue gas temperature too low or gas volume too low Raise the flue gas temperature by increasing
gas volume Insulate the chimney
172 905 04 2018-02-15
11. EU Declaration of conformity
Bentone Gasburners
172 615 07 2018-01-04
13. General instructions for gasburners
13.3.1 Installation
1. Press the reset button of the relay
2. Check that the max. thermostat has not cut out
3. Check other thermostats for example room ther mostat, if any
4. Check that the gas pressure to the burner is sufficient
5. Check that the electric fuses have not blown
6. Make a new attempt to start the burner and check the counter of the gas meter to find out whether the solenoid valve opens
7. If the burner does not start in spite of repeated starting attempts call the installer
1. Follow standards and instructions applicable to the installation of gas burners
2. Ensure that the electric installation is made in accordance with existing regulations
3. Check that the fresh air intake of the boiler room is sufficiently dimensioned
4. Check by studying the data plate that the efficiency of the burner is adapted to the boiler output
5. Check that the burner is adapted to the gas quality in question
6. Check that the input pressure of the gas is correct
7. Check that the dampers of the boiler are open
8. Check that there is water in the system
9. Check that thermostats etc. are correctly adjusted
10. Read the instructions and follow the directions given for the burner as to starting-up and service
13.3.2 Maintenance
1. Switch off the current with the main switch
2. Shut-off the gas supply with the shut-off cock on the burner
Normal operation
1. Ensure that the air supply to the burner is not obstructed by dust and dirt
2. Have the installer make a yearly overhaul of the installation so that safety is not jeopardized
3. Have the installer at the yearly overhaul also adjust the burner to ensure optimal combustion economy
4. Check periodically that there is water in the system ( fill up if necessary ) and that thermostats etc. are normally adjusted
5. Ensure that there is no water or dampness in contact with the burner
General instructions
1. Keep the boiler room clean
2. Ensure that the fresh air intake of the boiler room is not restricted
3. Switch off the current and shut off the gas supply if the burner must be withdrawn from the boiler
4. Do not use the boiler for burning paper and waste if there is no special arrangement ( fire room ) for this
1(2)
13.3.3 If the burner has stopped 13.3.4 Shut-Off
13.3.5 Warning
1. Never keep your face in front of the fire room door when starting up the burner
2. Do not use naked flame when inspecting the fire room
Authorized installer::
Address:
Telephone:
172 615 07 2018-01-04
Service- and inspection card
Installation Boiler
Name: Type: Efficiency kW:
Address: Burner
Type: Efficiency kW:
Installed by: Date:
Date
Nm3 gas/h Governor CO
2
CO Fluegas
temp
Ionisation current
Pressure Efficiency
Fire
room
Chimney
%
Measu­rement % % °C µ ABefore After mbar mbar
Small
Flame Large
Flame
Measures
Date
Nm3 gas/h Governor CO
2
CO Fluegas
temp
Ionisation current
Pressure Efficiency
Fire
room
Chimney
%
Measu­rement % % °C µ ABefore After mbar mbar
Small
Flame Large
Flame
Measures
Date
Nm3 gas/h Governor CO
2
CO Fluegas
temp
Ionisation current
Pressure Efficiency
Fire
room
Chimney
%
Measu­rement % % °C µ ABefore After mbar mbar
Small
Flame Large
Flame
Measures
Enertech AB. P.O Box 309, SE-341 26 Ljungby.
www.bentone.se, www.bentone.com
Loading...