Bentone B10E Installation And Maintenance Instructions Manual

Page 1
Installation- and maintenance instruction
B10E
1
171 615 02 05-01
Page 2
178 072 03
Page 3
DESCRIPTION
COMPONENTS
2. Nozzle assembly adjustment
3. Photocell
4. Preheater
5. Nozzle
6. Schrouded disc
7. Blast tube
8. Ignition electrodes
9. Ignition cables
10. Ignition transformer
11. Electrical connection
12. Control box
13. Solenoid valve
14. Reset button
15. Pump
16. Motor
17. Indicating lamp, preheater
18. Fan wheel
19. Air regulation
20. Scale, air regulation
21. Cover, nozzle assembly (fixed burner head)
171 205 07 95-01
Page 4
TECHNICAL DATA
-0,2
0,0
0,2
0,4
0,6
0,8
1,0
1,2
2,0 2,5 3,0 3,5 4,0 4,5
DIMENSIONS
B
94
ø89
155
148
202
Burner tube Length of Flange A Flange B Flange C
burner tube Measure B Measure B Measure B
E 77 524761 E 124 99 94 108 E 154 129 124 138 E 215 190 185 199
7
296
Flange A
Flange B
Flange C
10,5
12
12
ø89,5
130-150
ø89,5
130-150
ø89,5
130-150
21
26
12
OUTPUT RANGE AND NOZZLES RECOMMENDED
Recommended Recommended
Burner tube Oil capacity Nozzle Pump pressure
kg/h kW Mcal/h Angle Size Type Bar
E 2,35-4,1 28-49 24-42 60°, 80° 0,50-1,00 S or R 10
The net calorific value of 11,86 kWh/kg for light oil has been used.
RECOMMENDED NOZZLE
Because of different boiler types existing on the market, with varying combustion chamber designs, it is not possible to
BURNER HEAD
E
6,0-8,0
state a definite spray angle or spray pattern.
Note that the spray angle and the spray pattern change with the pump pressure.
2,4-3,2
(-1,0)-0,0
10,0-11,0
171 215 21 04-01
Page 5
GENERAL INSTRUCTIONS
GENERAL RULES
The installation of an oil burner should be carried out in accordance with local regulations. The installer of the burner must therefore be aware of all regulations relating to oil and combu­stion. Only oil suitable for the burner should be used and then in combination with a suitable oil filter before the oil pump of the burner. If the burner is replacing an existing burner make sure that the oil filter is replaced or cleaned. The installation must only be undertaken by experien­ced personnel. Care should be taken by the installer to ensure that no electrical cables or fuel/gas pipes are trapped or damaged during installation or service/maintenance.
INSTALLATION INSTRUCTIONS
General installation instructions ac­company the burner and should be left in a prominent place adjacent to the burner.
ADJUSTMENT OF BURNER
The burner is from the factory pre-set to an average value that must then be adjusted to the boiler in question. All burner adjustments must be made in accordance with boiler manufacturers instructions.These must include the checking of flue gas temperatures, average water temperature and CO2 or O2 concentration. To adjust the combustion device, start by increasing the air volume somewhat. When the burner starts it is burning with excess air and smoke number 0. Reduce the air volume until soot occurs and increase again to reach a combustion free of soot. By this procedure an optimum adjust­ment is obtained. If larger nozzles are used the preadjustment of the air volume must be increased.
Install a tube in the chimney Install a draught regulator (dilutes the flue gases during operation and dries them up during standstill) Increase the oil quantity Raise the flue gas temperature by removing turbulators, if any, in the boiler.
INSTRUCTIONS FOR USE
The end user of the burner should be instructed about the operation and safety features of the burner. He should also be made aware of the importance of the area around the boiler/burner being kept free of combu­stible material.
PUMP ADJUSTMENT
See separate description.
ADJUSTMENT OF BURNER
To obtain a correct adjustment a flue gas analysis and a temperature measurement must be carried out. Otherwise there is a risk that a bad adjustment may cause a formation of soot, bad efficiency or condensate in the chimney.
AIR ADJUSTMENT
On all burners the air adjustment can be made with or without the cover fitted. Final fine adjustment must be made with the cover on.
MAINTENANCE
The boiler/burner should be exami­ned regularly for any signs of mal­function or oil leakage.
FASTENING OF THE BURNER TO THE BOILER (FLANGE)
CONDENSATION IN CHIMNEY
A modern burner works with less ex­cess air and often also with smaller nozzles than older models. This increases the efficiency but also the risk of condensation in the chimney. The risk increases if the area of the chimney flue is too large. The tempera­ture of the flue gases should exceed 60°C measured 0,5 metres from the chimney top. Measures to raise the temperature: Insulate the chimney in cold attics
AIR ADJUSTMENT
171 305 17 06-01
Page 6
MAINTENANCE OF OIL BURNER
Warning: Before doing any service switch off power at the main switch and cut off the oil supply.
SERVICE OF BURNER HEAD (alt. A)
1. Remove the cover.
2. Withdraw the photo resistor.
3. Loosen the connecting pipe.
4. Loosen two fixing screws of the nozzle assembly cover.
5. Retract the nozzle assembly so far that the ignition cables can be removed from the ignition electrodes.
6. Remove the nozzle assembly.
SERVICE OF BURNER HEAD (alt. B)
1. Slacken retaining screws.
2. Remove the burner.
3. Loosen the two blast tube retaining screws.
4. Turn the tube to the right and remove.
SUSPENSION OF BURNER
A. Pin for suspension of burner.
A
B. Hole for suspension (also avail-
able on the right side).
CLEANING OF FAN WHEEL
Loosen five fixing screws. Remove the fan housing half.
171 305 14 95-01
Page 7
ELECTRIC EQUIPMENT
OIL BURNER CONTROL: LOA21... / LOA24...
FUNCTION
1. Switch on operating switch and twin thermostat The burner motor starts, an ignition spark is formed, the prepurge goes on till the prepurge period expires and the solenoid valve opens (2).
2. Solenoid valve opens Oil mist is formed and ignited. The photocell indicates a flame.
(1) The ignition spark goes out 15 s. after flame indication (LOA24.171...).
(2) The ignition spark goes out 2 s. after flame indication when the ignition
transformer is connected to terminal 7 (LOA24.173...).
3. The safety time expires a. If no flame is established before this time limit the control cuts out. b. If for some reasons the flame disappears after this time limit, the
burner will make an attempt to re-start.
3-4. Operating position
If the burner operation is interrupted by means of the main switch or the thermostat, a new start takes place when the conditions in accordance with point 1 are fulfilled.
The oil burner control cuts out A red lamp in the control is lit. Press the reset button and the burner re-starts.
WIRING DIAGRAM
(1)(2)
Post-ignition
(2) If a post-igniton of 15 s. is wanted, move the ignition transformer from
terminal 7 to terminal 6 (LOA24.173...).
LIST OF COMPONENTS
A1 Oil burner control R1 Photoresistor A2 Twin thermostat S3 Main switch F1 Fuse, max. 10A T1 Ignition transformer H1 Alarm lamp Y1 Solenoid valve H2 Signal lamp (optional) X1 Plug-in contact, burner M1 Burner motor X2 Plug-in contact, boiler P1 Time meter (optional)
Mains connection and fuses in accordance with local regulations.
TECHNICAL DATA
Pre-ignition time: 13 s Pre-purge time: 13 s
(1) Post-ignition time: 15 s (2) Post-ignition time: 2 s
Safety lock-out time: 10 s
Reset time after lockout: » 50 s
Reaction time on flame failure: max. 1 s Ambient temperature: from - 20 to +60°C Min. current with flame established: 65 A Max. photo current at start: 5 A Enclosure: IP 40 (Under voltage proof only LOA24...)
*
* If there is no plug-in contact (X2) on the boiler,
connect to the contact enclosed. In case the twin thermostat is in series on incoming phase L1, a loop between the terminals T1 and T2 is necessary.
OUTER ELECTRICAL CONNECTION
X1
X2
CONTROL OF PHOTO CURRENT
Current through photo unit is measured with a d.c. ammeter (a moving coil instrument connected in series with the photo unit).
171 415 20 04-01
Page 8
INSTRUCTIONS PUMP TYPE DANFOSS BFP41
TECHNICAL DATA
Viscosity range: 1,3-12,0 mm2/s Pressure range: 7-15 bar Oil temperature: -10 to +70°C
COMPONENTS
1.Nozzle port G 1/8"
2.Pressure gauge port
3.Pressure adjustment, 4mm allen key
4. Cartridge filter
5.Vacuum gauge port G 1/8"
6.Return line G 1/4"
7.Suction line G 1/4"
8.Return plug
SUCTION LINE TABLES
The suction line tables consist of theoretically calculated values where the pipe dimensions and oil velocity have been matched so that turbulences will not occur. Such turbulences will result in increased pressure losses and in acoustic noise in the pipe system. In addition to drawn copper piping a pipe system usually comprises 4 elbows, a non-return valve, a cut-off valve and an external oil filter. The sum of these individual resistances is so insignificant that they can be disregarded. The tables do not include any lengths exceeding 100 m as experience shows that longer lengths are not needed. The tables apply to a standard fuel oil of normal commercial quality according to current standards. On commissioning with an empty tube system the oil pump should not be run without oil for more than 5 min. (a condition is that the pump is being lubricated during operation). The tables state the total suction line length in metres at a nozzle capacity of 2,5 kg/h. Max. permissible pressure at the suction and pressure side is 2,0 bar.
PURGING
On 1-pipe systems it is necessary to purge the pump. On 2-pipe systems purging is automatic through the return line.
H
H
1-pipe system 1-pipe system
Height Pipe diameter
H ø4 mm ø5 mm ø6 mm
mmmm 4,0 51 100 100 3,5 45 100 100 3,0 38 94 100 2,5 32 78 100 2,0 26 62 100 1,5 19 47 97 1,0 13 31 65 0,5 6 16 32
Two-pipe system
Height Pipe diameter
H ø6 mm ø8 mm ø10 mm
mmmm
4,0 33 100 100 3,5 31 98 100 3,0 29 91 100 2,5 27 85 100 2,0 25 79 100 1,5 23 72 100 1,0 21 66 100 0,5 19 60 92
Height Pipe diameter
H ø4 mm ø5 mm ø6 mm
mmmm
With an underlying tank a 1-pipe­system is not recommended
Two-pipe system Height Pipe diameter
H ø6 mm ø8 mm ø10 mm
mmmm
0 17 53 100
-0,5 15 47 100
-1,0 13 41 99
-1,5 11 34 84
-2,0 9 28 68
-2,5 7 22 53
-3,0 5 15 37
-3,5 3 9 22 4,0 1 3 6
171 505 07 96-01
Page 9
FUNCTION DANFOSS BFP41
When the oil pump is started, oil is drawn from the suction connection (S) through the filter (H) to the suction side of the gear wheel (C).
The gear wheel then pumps oil to the pressure side and the oil is put under pressure. The pressure is controlled and kept constant at the set value by the regulating valve (P1) with the diaphragm (D). The regulating valve (P1) distributes the oil quantity supplied by the gear set (C) between the nozzle port (E) and the return side of the pump (R). The oil quantity utilized is determined by the set pressure on the regulating valve (P1) and the size of the oil nozzle in the nozzle line. The valve (P1) functions in the following way:
- When the opening pressure has been reached, the passage to the return side opens.
- The diaphragm and the spring keep the pump pressure constant at set value.
- If the pump is overloaded, i.e. if you try to get out more oil than the gear
V
P
H
C
S
G
A
R
set can supply under existing circum­stances, the oil pressure falls below the set value and the valve closes against the return side (R) by means of the diaphragm (D) and goes into starting position.
This can be remedied by:
- Reducing the pump pressure.
- Reducing the oil quantity supplied by using a smaller nozzle.
- Using a pump with a larger capacity.
NC
E
D
P
1
BURNER WITH PREHEATING
Consider that the oil quantity is reduced at preheating by 5-20% depending on.
- Rise in temperature at the nozzle
- Nozzle design
- Capacity (high capacity - small difference)
HOW TO REMOVE CARTRIDGE FILTER FROM PLUG
Unscrew the cartridge filter plug in the cover by means of a 4 mm allen key and withdraw the cartridge filter. If necessary, put a screwdriver between the cartridge filter and the plug and turn the cartridge filter carefully until it comes off. Reject the cartridge filter and replace it by a new one. Press it on to the plug. Ensure that the O-ring is not damaged. Then fit the new cartridge filter to the pump.
REPLACEMENT OF CARTRIDGE FILTER
MOUNTING/DISMOUNTING RETURN PLUG
One pipe system
Two pipe system
171 505 08 00-01
Page 10
NOZZLE TABLE
Gph 8 9 10 11 12 13 14 15
kg/h kW Mcal/h kg/h kW Mcal/h kg/h kW Mcal/h kg/h kW Mcal/h kg/h k W Mcal/h kg/h kW Mcal/h kg/h kW Mcal/h kg/h k W Mcal/h
0,40 1,33 16 13 1,41 17 14 1,49 18 15 1,56 18 16 1,63 19 17 1,70 20 17 1,76 21 18 1,82 21 18
0,50 1,66 20 17 1,76 21 18 1,86 22 19 1,95 23 20 2,04 24 21 2,12 25 22 2,20 26 22 2,28 27 23 0,60 2,00 24 20 2,12 25 22 2,23 26 23 2,34 28 24 2,45 29 25 2,55 30 26 2,64 31 27 2,73 32 28 0,65 2,16 26 22 2,29 27 23 2,42 29 25 2,54 30 26 2,65 31 27 2,75 33 28 2,86 34 29 2,96 35 30 0,75 2,49 29 25 2,65 31 27 2,79 33 28 2,93 35 30 3,08 36 31 3,18 38 32 3,30 39 34 3,42 40 35 0,85 2,83 33 29 3,00 36 31 3,16 37 32 3,32 39 34 3,47 41 35 3,61 43 37 3,74 44 38 3,87 46 39 1,00 3,33 39 34 3,53 42 36 3,72 44 38 3,90 46 40 4,08 48 42 4,24 50 43 4,40 52 45 4,56 54 46 1,10 3,66 43 37 3,88 46 39 4,09 48 42 4,29 51 44 4,48 53 46 4,67 55 48 4,84 57 49 5,01 59 51 1,20 3,99 47 41 4,24 50 43 4,47 53 46 4,68 55 48 4,89 58 50 5,09 60 52 5,29 63 54 5,47 65 56 1,25 4,16 49 42 4,40 52 45 4,65 55 47 4,88 58 50 5,10 60 52 5,30 63 54 5,51 65 56 5,70 68 58 1,35 4,49 53 46 4,76 56 48 5,02 59 51 5,27 62 54 5,50 65 56 5,73 68 58 5,95 70 61 6,15 73 63 1,50 4,98 59 51 5,29 63 54 5,58 66 57 5,85 69 60 6,11 72 62 6,36 75 65 6,60 78 67 6,83 81 70 1,65 5,49 65 56 5,82 69 59 6,14 73 63 6,44 76 66 6,73 80 69 7,00 83 71 7,27 86 74 7,52 89 77 1,75 5,82 69 59 6,18 73 63 6,51 77 66 6,83 81 70 7,14 85 73 7,42 88 76 7,71 91 79 7,97 94 81 2,00 6,65 79 68 7,06 84 72 7,45 88 76 7,81 93 80 8,18 97 83 8,49 101 86 8,81 104 90 9,12 108 93 2,25 7,49 89 76 7,94 94 81 8,38 99 85 8,78 104 89 9,18 109 94 9,55 113 97 9,91 117 101 10,26 122 105 2,50 8,32 99 85 8,82 105 90 9,31 110 95 9,76 116 99 10,19 121 104 10,61 126 108 11,01 130 112 11,39 135 116 2,75 9,15 108 93 9,71 115 99 10,24 121 104 10,73 127 109 11,21 133 114 11,67 138 119 12,11 144 123 12,53 148 128 3,00 9,98 118 102 10,59 126 108 11,16 132 114 11,71 139 119 12,23 145 125 12,73 151 130 13,21 157 135 13,67 162 139 3,50 11,65 138 119 12,35 146 126 13,03 154 133 13,66 162 139 14,27 169 145 14,85 176 151 15,42 183 157 15,95 189 163 4,00 13,31 158 136 14,12 167 144 14,89 176 152 15,62 185 159 16,31 193 166 16,97 201 173 17,62 209 180 18,23 216 186 4,50 14,97 177 153 15,88 188 162 16,75 198 171 17,57 208 179 18,35 217 187 19,10 226 195 19,82 235 202 20,51 243 209 5,00 16,64 197 170 17,65 209 180 18,62 221 190 19,52 231 199 20,39 242 208 21,22 251 216 22,03 261 225 22,79 270 232 5,50 18,30 217 187 19,42 230 198 20,48 243 209 21,47 255 219 22,43 266 229 23,34 277 238 24,23 287 247 25,07 297 256 6,00 19,97 237 204 21,18 251 216 22,34 265 228 23,42 278 239 24,47 290 249 25,46 302 260 26,43 313 269 27,49 326 280 6,50 21,63 256 220 22,94 272 234 24,20 287 247 25,37 301 259 26,51 314 270 27,58 327 281 28,63 339 292 29,63 351 302 7,00 23,29 276 237 24,71 293 252 26,06 309 266 27,33 324 279 28,55 338 291 29,70 352 303 30,84 366 314 31,91 378 325 7,50 24,96 296 254 26,47 314 270 27,92 331 285 29,28 347 298 30,59 363 312 31,83 377 324 33,04 392 337 34,19 405 349 8,00 26,62 316 271 28,24 335 288 29,79 353 304 31,23 370 318 32,63 387 333 33,95 403 346 35,25 418 359 36,47 432 372 8,50 28,28 335 288 30,00 356 306 31,65 375 323 33,18 393 338 34,66 411 353 36,07 428 368 37,45 444 382 38,74 459 395 9,00 29,95 355 305 31,77 377 324 33,59 398 342 35,14 417 358 36,71 435 374 38,19 453 389 39,65 470 404 41,02 486 418
The table applies to oil with a viscosity of 4,4 mm2/s (cSt) with density 830 kg/m3.
Pump pressure bar
BURNER WITH PREHEATER
Consider that on preheating the oil quantity is reduced by 5-20% depending on.
- Rise in temperature at the nozzle
- Design of nozzle
- Capacity (high capacity - small difference)
171 505 44 00-01
Page 11
FAULT LOCATION
BURNER FAILS TO START
Situation
Motor runs Flame instabillity
Burner pre-purges
Flame occurs
Burner locks out
Motor runs
Burner pre-purges
No flame occurs
Burner locks out
Possible causes
Incorrect head settings
Low oil pressure
Excess air
Photocell not seeing light
Photocell failed
Control faulty
False light
No spark
No oil
BURNER FAILS TO START AFTER NORMAL OPERATION
Burner fails to start
Fuse has blown
Remedies
Check nozzle to burner head dimension and
electrode position
Check oil pressure
Adjust air damper
Check that photocell is clean and unobstructed
Confirm with new photocell
Confirm with new control. (NB. it is advisable to
change the photocell if also changing control)
Check that photocell is not seeing ambient light
Check that H.T. leads are sound and are not
arcing other than at electrode gap
Check oil supply to burner - check that pump
is not airlocked
Check operation of magnetic valve
Check or replace fuse if necessary. Check
reason for failure
Lamp not lit
Motor runs
Burner runs to lockout
Burner pulsates on start-up
only with hot flue
Burner pulsates on start-up
Appliance thermostat has not reset
Appliance overheat device has operated
Control relay or photocell defective
No oil being delivered
Excessive flue draught is preventing
flame establishment
No spark
Reset overheat device. Find reason for its
Check that tank, oil lines, fire valve, pump and
Check ignition transformer. Check electrode
Adjust thermostat
operation and rectify
Check by replacement
nozzle are all in good order
Rectify condition
gap and porecelains
DELAYED IGNITION, BURNERS STARTS VIOLENTLY
Excessive draught
Nozzle partly blocked
Oil pressure too low
Flue blocked or damaged
Fan slipping on shaft
Recommission burner
Replace nozzle
Check and recommission
Check and rectify
Check and retighten
Burner starts violently
171 915 01 01-01
Pump coupling loose or worn
Delayed ignition
Check and replace
Check the electrode adjustment, see diagram
Check electrodes for damage
Check H.T. leads for damage and disconnection
Page 12
DECLARATION OF CONFORMITY
We (supplier´s name)
BENTONE
...........................................................
(address)
P.O. Box 309, S-341 26 Ljungby, Sverige
................................................................
declare under our sole responsibility that the product (name, type or model, batch or serial number, possibly sources and number of items)
ST 97, ST 108, ST 120, ST 133, ST 146, B 9, B 10, B 11, B 20, B 30, B 40, B 45, B 50, B 60, B 70, B 80,
..........................................................................................................................................................................................
fan burners for gasoil
....................................................................................................................................................................................................
to which this declaration relates is in conformity with the following standard(s) or the normative document(s) (title and/or number and date of issue of the standard(s) or other normative document(s)
EN 267
...................................................................................................................................................................................................
following the provisions of Directive (if applicable)
EMC directive 89 / 336 / EEC, Low voltage directive 73 / 23 / EEC and Machinery directive 89/392/EEC.
..........................................................................................................................................................................................
Re. the Efficiency directive 92/42/EEC, please see the next page.
............................................................................................................................................................................................
Ljungby 28 - 1 2003
......................................................
(Place and date of issue)
BENTONE
Ulf Bondeson
..........................................................................................................................
(name and signature of equivalent marking of authorized person)
1(3)
171 905 07 03-01
Page 13
To fulfil the demands according to the Efficiency directive 92/42/EEC, Article 2, we herewith state the following parameters.
Burner Capacity Test report No. Pressure in combustion Product ID-No. as per type kg/h (kW) TÜV chamber mbar EC-Type Examination
Certificate
ST 97 1,2-2,6 3728 -0,2 to+1,4 CE 0036 0128/98
(14,2-30,8) (15.03.96) to + 0,1
ST 108 1,2-3,8 3729 -0,2 to + 1,4 CE 0036 0129/98
(14,2-45) (15.03.96) to + 0,2
ST 120 2,1-4,5 3581 -0,2 to + 1,9 CE 0036 0130/98
(24,9-53,3) (10.11.94) to + 0,2
ST 133 2,0-10,0 3795 -0,2 to + 2,2 CE 0036 0131/98
(23,7-118,5) (12.11.96) to + 0,1
ST 146 4,0-10,0 3796 -0,2 to + 3,9 CE 0036 0132/98
(47,4-118,5) (12.11.96) to + 0,1
B 9 1,2-2,5 3341 -0,2 to + 0,8 CE 0036 0133/98
(14,2-29,6) (21.08.92) to + 0,1
B 10 1,4-3,0 3465 -0,2 to + 1,1 CE 0036 0134/98
(16,6-35,6) (03.09.93) to + 0,25
B 10KA 2,0-4,6 3778 -0,2 to + 0,95 CE 0036 0135/98
(23,7-54,5) (18.10.96) to + 0,1
B 10ZHV 1,2-2,5 3525 -0,2 to + 1,0 CE 0036 0136/98
(14,2-29,5) (21.01.94) to + 0,3
B 11
B 20K 4,3-9,8 3779 -0,2 to + 1,15 CE 0036 0137/98
(51,0-116,1) (18.10.96) to + 0,1
B 20KA 2,0-8,0 3333 -0,2 to 0,78 CE 0036 0138/98
(23,7-94,8) (04.08.92) to + 0,1
B 20ZHV 2,1-4,3 3397 -0,2 to 1,25 CE 0036 0139/98
(24,9-51,0) (14-06.93) to + 0,1
B 30 6,0-17,5 3524 -0,2 to + 2,8 CE 0036 0140/98
(71,1-207,4) (24.01.94) to + 0,2
B 30A 6,0-17,0 3797 -0,2 to + 3,0 CE 0036 0141/98
(71,1-207,4) (12.11.96) to + 0,1
B 30A2 4,5-15,0 3798 -0,2 to 3,8 CE 0036 0142/98
(53,3-177,8) (12.11.96) to + 0,1
B 30ZHV-2 3,3-10,0 3563 -0,2 to + 1,3 CE 0036 0143/98
(39,1-118,5) (10.11.94) to + 0,1
B 40 9,0-29,5 3503 -0,3 to + 4,1 CE 0036 0144/98
(106,7-349,6) (21.09.93) to + 0,2
B 40A 9,0-29,5 3799 -0,2 to + 5,3 CE 0036 0145/98
(106,7-349,6) (12.11.96) to + 0,1
2(3)
Page 14
To fulfil the demands according to the Efficiency directive 92/42/EEC, Article 2, we herewith state the following parameters.
Burner Capacity Test report No. Pressure in combustion Product ID-No. as per type kg/h (kW) TÜV chamber mbar EC-Type Examination
Certificate
B 50-2F 12,0-59,0 3390 -0,2 to +9,4 CE 0036 0147/98
(142,2-699,2) (09.06.93) to + 0,2
B 50-3F 12,0-59,0 3592 -0,2 to + 9,25 CE 0036 0148/98
(142,2-699,2) (10.11.94) to + 0,1
B 60-2F 20,0-90,0 3466 -0,3 to + 11,4 CE 0036 0149/98
(237,0-1066,5) (03.09.93) to + 0,8
B 60-3F 20,0-90,0 3591 -0,3 to + 11,4 CE 0036 0150/98
(237,0-1066,5) (10.11.94) to + 0,8
B 70
B 80
SF 141-3 50,0-140,0 3502 -0,7 to 8,7 CE 0036 0151/98
(592,5-1659,0) (16.09.93) to + 12,0
to + 0,1
TF 205-3 70,0-205,0 3501 -0,7 to + 14,0 CE 0036 0152/98
(16.09.93) to + 16,0
to + 0,1
B45A 8,5-47,0 3977 -0,1 to + 0,4 CE 0036 0250/99
(100,8-557,5) (16.04.99) to + 7,0
B45A2 8,5-45,5 3978 -0,1 to + 0,4 CE 0036 0251/99
(100,8-539,7) (16.04.99) to + 7,5
3(3)
Loading...