BENSON HEATING RS/UHA2 50, RS/UHA2 80, RS/UHA2 105, RS/UHA2 140, RS/UHA2 200 Technical Information, Assembling Instructions, Use And Maintenance

...
Gas room sealed unit heaters 2 stage
TECHNICAL INFORMATION ASSEMBLY
INSTRUCTIONS, USE AND MAINTENANCE
RS/UHA-2
BENSON HEATING
LUDLOW ROAD
KNIGHTON
POWYS
LD7 1LP
MAY 2003
Benson Heating is a divison of
Benson Climate Systems Ltd
COMPLIANCE NOTICES
The Benson RS/UHA2 range of warm air heaters detailed herewith are manufactured for Benson Heating within the parameters of ISO 9002.
The Benson RS/UHA2 Range has been independentl y tested and assessed, and h as been found to meet the Essential Requirement of the following European Directives:
Gas appliance Directive (90/396/EEC) Machinery Directive (89/392/EEC) 91368/EEC 93/44/EEC 93/65/EEC Low Voltage Directive (73/23/EEC Electromagnetic Compatibility Directive (98/336/EEC and 91/31/EEC) Product Liability Directive (65/374/EEC)
The manufacturer has taken reasonable and practical steps to ensure th at Benson RS/UHA2 Ra nge of Heaters are safe and without risk when properly used. These heaters should therefore only be used i n the manner and pu rpose for which they were intended, and in accordance with the recommendations detailed herewith. The heaters have been designed, manufactured, assembled, inspected, and tested, with safety and quality in mind, there are certain basic precautions which the installer and user should be a ware of, and they are strongly advised to read the appropriate sections of the information pack accompanying the heater, prior to installation or use.
Benson Heating supports all new products being supplied to their customers with a comprehensive infor m ation pack; this clearly defines mandatory instructions for the safe installation, use, and maintenance, of the appliance(s).
Where proprietary items are incorporated into Benson Heating products, detailed information and instructions are also provided as part of the information pack.
It is the responsibility of the installer, owner, user, or hirer, of such products supplied by Benson Heating, to ensure that they are familiar with the appropriate information/manuals, supplied by the manufacturer, and that they are suitably aware of the purpose of the manuals and the safety instructions. In addition, operators must be suitably trained i n the use of the appliance so as to ensure its continued safe and efficient use.
Benson Heating has a commitment to continuous improvement, and therefore reserves the right to amend or chan ge the specification of the RS/UHA2Heater range subject to agreement from The Notified Body.
Contained within the text of the manual, the words 'Caution' and 'Warning' are used to highlight certain points. Caution is used when failure to follow or implement the instruction(s) can lead to premature failure or damage to the
heater or its component parts. Warning is used when failure to heed or implement the instruction(s) can lead to not only component damage, but also
to a hazardous situation being created where there is a risk of personal injury.
Notified Body PIN Reference is
RANGE
Type Model Code
1 RS/UHA2 50
3TAIT2C016
2 RS/UHA2 80
3TAIT2C026
3 RS/UHA2 105
3TAIT2C036
4 RS/UHA2 140
3TAIT2C046
5 RS/UHA2 200
3TAIT2C066
6 RS/UHA2 260
3TAIT2C086
7 RS/UHA2 325
3TAIT2C106
INDEX
GENERAL
Description of equipment page. Identification Description “ Identification “ Description “ Technical data “ Wiring diagram “ Remote control connections Regulating air flow
FOR THE USER
Operation “ Servicing Heater indication lights “ Receipt of product “ Transport “ Dimension “
FOR THE INSTALLER
Location “ Wall bracket dimensions “ Gas connection “ Flue and combustion options Electrical control panel “ Electrical connections
TECHNICAL ASSISTANCE SERVICE
Pre commissioning checks Initial start up “ Gas conversion “ Thermostat operation “ Control Maintenance “ Fault finding
Heaters type 1-2-3-4-5
C
FAN 1
C
FAN 2
IMT
J6
NL
F2
F1
N
J5
II°
SF
230V 50Hz
EF
SE
J4
J8
IGN1
PA
COMCOM
NA NC
ION
EA1
J11
J17
J2
J14
VM
TA
J16 J13
J7
RSTR
MS
EVG1-I°
EVG1-II°
RST
LB
LL
LF
J10
J9 J12
SND
LM
TR
J15J18
J1
KEY: SND Temperature probe
TR Regulatory control thermostat (auto reset) LM LIMIT thermostat (manual reset) EVG1-I° Gas solenoid valve1 EVG1-II° Second stage gas valve 2 C Fan capacitor FAN 1 Axial fan 1 FAN 2 Axial fan 2 (t ype 5) F1-F2 Line fuse (6,3 A) LF Green working light LL High temperature indication light LB Lockout indication RST Lockout reset EF Flue venter
PA Differential pressure switch IGN1 Ignition transformer EA1 Spark electrode ION Ionisation probe SE Electrical control board IMT (*) Fused isolator MS (*) Fire damper connection (accessory) RSTR (*) Remote reset connection TA (*) Room thermostat connection VM (*) Fan switch connection SF (*) Second stage gas valve connection
(*) External to the heater customer supply.
Heater type 6-7
IGN2
EA2
EF
SE
J4
J8
IGN1
PA
COMCOM
NA NC
ION
EA1
J11
J17
J2
J14
VM
TA
J16 J13
J7
RSTR
MS
EVG2-I°
EVG1-I°
EVG2-II°
EVG1-II°
RST
LL
LB
LF
J10
J9 J12
SND
LM
TR
J15J18
J1
IMT
J6
230V ~ 50Hz
NL
F2
F1
N
J5
II°
SF
C
FAN 1
C
FAN 2
FAN 3
C
KEY: SND Temperature probe TR Regulatory control thermostat (auto reset) LM LIMIT thermostat (manual reset) EVG1-I° Gas solenoid valve 1 EVG2-I° Gas solenoid valve 2 EVG1-II° Second stage gas valve 1 EVG2-II° Second stage gas valve 2 C Fan capacitor FAN 1 Axial fan 1 FAN 2 Axial fan 2 FAN 3 Axial fan 3(Type 7) F1-F2 Line fuse LF Green working light LL High temperature indication light LB Lockout indication
RST Lockout reset button EF Flue venter PA Differential pressure switch IGN1 Ignition transformer 1 IGN2 Ignition transformer 2 EA1 Spark electrode 1 EA2 Spark electrode 2 ION Ionisation probe SE Electrical control board IMT (*) Fused isolator MS (*) Fire damper connection (accessory) RSTR (*) Remote reset connection TA (*) Room thermostat connections VM (*) Fan switch connections SF (*) Second stage gas valve connection
(*) External to the heater customer supply.
GAS CONVERSION
The heaters are supplied ready for use with (G20) Natural Gas as p er the table belo w Conversion kits are availab le from the manufacturer:
Natural Gas (G20)
TYPE 1 23456 7
Number of injectors 1 1 1 1 2 2 4 N° Diameter of injectors 3,10 410 480 555 500 540 450 mm/100 Gas supply pressure 20 mBar Head pressure high fire 11,0 13,0 13,0 13,0 10,0 13,0 10,5 mBar Head pressure low fire 6,0 7,0 6,5 6,5 7,0 6,5 5,0 mBar
BEFORE CHANGING INJECTORS ENSURE GAS SUPPLY IS ISOLATED
INSTRUCTIONS FOR CONVERSION TO PROPANE GAS G(31)
1. Change the injectors
2. Adjust the gas inlet pressure
3. Adjust the head pressure
4. Fit primary air diaphragm (if required )
5. Fit adhesive label supplied with kit indicating gas type
6. Ensure settings are correct as per the manual and data plate
CHANGE INJECTORS:
To change injectors: Unscrew the natural gas injectors and replace them with the correct size injectors for propane as shown in table below:
Propane gas (G31)
TYPE 1 23456 7
Number of injectors 1 1 1 1 2 2 4 N° Diameter of injectors 190 250 280 335 285 320 255 mm/100
Replacing injectors single manifold (type 1-2-3-4-6)
Replacing injectors 2 per manifold (type 5-7)
Check the size stamped on the side of the injector is correct to the data in the manual.
Ensure that the new injectors are correctly fitted in the manifold and are gas tight, When the conversion is complete fix the transfer supplied
with the kit showing the correct gas pressure on to the manifold Test for gas soundness on completion Ensure that the aluminium washers supplied for (types 5–7) are fitted when changing the injectors.
If the gas line has not been correctly purged ignition
may not take place at the first attempt resulting in
the heater going to lockout
Reset the lockout before re starting ignition sequence
Before each attempt at ignition it is necessary to wait at least 10 seconds
Connect the manometer on to the pressure test point PM and check inlet gas pressure if correct connect manometer to test point PV and start heater with heater running ensure the gas pressure corresponds to that shown on the data plate adjust by altering the screws RP1 and RP2 on the gas valve
Check that the gas consumption reading corresponds with that indicated in the TECHNICAL DATA section Set on/standby switch to standby when heater is sufficiently cool isolate gas supply
Remove manometer ensure the screw at the test point is tightened test for gas leaks
Open the gas isolating cock switch on the electrical supply set the room thermostat to the desired temperature.
T he heater is now ready for operation
GAS VALVE Model SIT 843 (two stage)
The heater must only be operated with the burner compartment door(s) closed
STOPPING
To stop the heater use only the room thermostat Set it to the minimum temperature The fan will stop after 3 minutes or when the heat exchanger is sufficiently cool If required switch off the electricity supply at the isolator
!
The main electrical supply must not be switched off or used as a method of stopping the heater except in an emergency until the heater has cooled down sufficiently preventing damage to the heat exchanger Interruption of electrical supply whilst heater is in operation will cause it to go to overheat and may damage the heat exchanger the LIMIT thermostat will operate and this will have to be manually re set.
PM Inlet pressure test point. PV Head pressure test point RP1 Cross cut screw low fire adjuster RP2 Hexagonal screw high fire adjuster
Assembly of primary air diaphragm: Diagram showing the fitting of a primary air
diaphragm to single burner manifold (1-2-3-4-6)
Diagram showing the fitting of a primary air diaphragm for a two burner manifold type (7)
Warning the diaphragm plates should only be used when using propane gas G31.
Gas conversion adhesive label:
Once the heater has been converted to propane ensure that the correct label is fitted to the burner overtop of the factory fitted one covering it completely. It is recommended that the diameter of the nozzles be checked also that the pressure corresponds to that shown on the data plate provided Ensure that all of the additional gas components are correct for the installation (including storage tank, pipes and pressure valves etc Ensure that the pressure regulators are sealed after carrying out the conversion.
GAS PRESSURE REGULATION
To regulate the gas inlet pressure :
Connect a manometer onto the gas valve test point (PM)
Adjust the inlet gas supply regul ator (customer installation) to pressure indicated on data plate:
To regulate the gas head pressure to the burner:
Connect a manometer onto the gas v alve test point (PV)
Adjust the pressure regulating adjusters RP1/ RP2 as detailed on next page to obtain correct pressures indicated in table below:
Propane gas (G31)
TYPE 1 23456 7
Gas supply pressure 37 mBar Head pressure max 35,5 35,0 35,5 35,5 34,5 35,5 34,5 mBar Head pressure min 20,0 18,0 18,5 18,0 18,0 18,0 18,5 mBar
Gas inlet pressure must not exceed 60 mbar at the gas valve inlet.
Gas valve head pressure setting high fire Propane G31:
When setting the gas pressure for propane high fire (second stage ) contact SF should be closed the high fire pressure adjusting screw on the gas valve must be excluded. Connect a manometer on test point PV
Remove the plastic cover from the adjuster RP1 RP2 With a screw driver hold the adjuster RP1 stationary and using a spanner, screw adjuster RP2 clockwise to the bottom of the thread until the correct pressure according to the data plate is achieved .
Gas valve head pressure setting low fire Propane G31 :
When setting the gas pressure for propane low fire (first stage) contact SF should be open. The low fire pressure should be adjusted to the settings shown on the data plate and the data in the manual provided by adjusting screw RP1 Clockwise increases the pressure
Anti clockwise to decrease the pressure On completion replace the plastic cover and seal with paint Remove manometer ensuring that the test point screw is gas tight
Gas valve gas SIT 843
On heaters with 2 gas valves the pressure regulation must be carried out on both gas valves
FAULT FINDING
If the heater is not working firstly check the following :
Check electric al supply
Check voltage is as stated +15%, -15%
Check gas supply is on
Check that the pressure is as stated in the TECHNICAL DATA
FAULT CAUSE SOLUTION
No operation
No electrical supply
Check main isolator. Check supply cables Check line fuses. Check electrical connections
No spark ignition.
Flue venter working No indication lights on
Differential pressure switch not working
Check flue pipe and combustion air pipe are clear.
Faulty differential pressure switch
Replace differential pressure switch
Poor connection at pressure switch
Check air pipe to switch is connected and not damaged Check electrical connections Check that pipes are condensate free .
Faulty flue venter
Replace flue venter
Faulty control panel
Replace control panel
Faulty ignition electrode
Check ignition probe is not cracked or damaged
Replace the ignition probe
No ignition
Flue venter working No indication lights on
Room thermostat open
Check room thermostat.
Faulty flue venter
Replace flue venter
Faulty control panel
Replace control panel
Burner lights but locks out after 5 seconds
Live and neutral inverted Poor earth
Check electrical connections
Faulty ionisation probe
Check electrical connection on probe.
Check probe for cracks or damage.
Replace ionisation probe .
Faulty ignition
Check the gas type is suitable for the heater.
Check the inlet gas pressure. Check the head pressure. Check the gas supply pipes
have been properly purged of air .
Explosive start up.
Faulty ignition electrode
Replace ignition electrode
Incorrect electrode position
Reposition electrode correctly over the burner bar.
Faulty burner tube
Replace the burner tube
Faulty ignition transformer
Replace ignition transformer
Faulty ignition
Check the gas type is suitable for the heater.
Check the inlet gas pressure. Check the head pressure. Check the gas supply pipes
have been properly purged of air .
heat exchanger dirty
Check / clean heat exchanger
Burner shuts down then re lights automatically .
No indication lights on.
Pressure differential switch not operating correctly
Check that air pipe to switch not damaged or blocked. Check that the flue and combustion air pipes are clear.
Check that the thermal overload on the flue venter has not operated
Faulty pressure differential switch
Replace differential switch
Room thermostat in warm air flow
Check position of thermostat
Burner goes out due to the intervention of the SND thermostat and is restarted automatically when the heater has cooled down .
Yellow indication light on.
Excessive heat exchanger temperature
Check inlet gas pressure Check burner head pressure Check that gas type is suitable
for heater Check injector size is correct for
the heater.
Excessive air temperature due to insufficient air flow over heat exchanger.
Check the fan blades are clean Check that the horizontal and
(vertical if fitted) louvers are sufficiently open. (see in installation section of manual)
Check that the fan speed is correct and the air flow over the chamber is sufficient.
Faulty SND thermostat or control panel
Replace SND thermostat or control panel
Burner goes out due to the intervention of the TR thermostat and is restarted automatically when the heater has cooled down .
Yellow indication light on.
Excessive heat exchanger temperature
Check inlet gas pressure Check burner head pressure Check that gas type is suitable
for heater Check injector size is correct for
the heater.
Excessive air temperature due to poor air flow
Check the fan blades are clean Check that the horizontal and
(vertical if fitted) louvers are sufficiently open. (see in installation section of manual)
Check that the fan speed is correct and the air flow over the chamber is sufficient.
Faulty thermostat
Replace thermostat
Burner goes out due to the intervention of the LIMIT thermostat (LM).
Yellow light flashing
Excessive heat exchanger temperature.
Check inlet gas pressure Check burner head pressure Check that gas type is suitable
for heater Check injector size is correct for
the heater.
Excessive air temperature due to poor air flow over heat exchanger
Check the fan blades are clean Check that the horizontal and
(vertical if fitted) louvers are sufficiently open. (see in installation section of manual)
Check that the fan speed is correct and the air flow over the chamber is sufficient..
Faulty thermostat
Replace thermostat
Faulty fan
Check fan capacitor Check fan motor.
Intervention of thermal overload on fan
Check electrical absorption Replace fan motor
Faulty fan operation
Change fan control or SND thermostat
Heater at lockout
Red lamp illuminated
Faulty ignition
Check inlet gas pressure Check burner head pressure Check that gas type is suitable
for heater Check that gas line has been
purged correctly.
Faulty ionisation probe
Check electrical connection to the probe.
Check probe is not cracked or damaged Change probe or probe lead
Faulty ignition electrode
Replace ignition electrode.
Faulty solenoid
Replace solenoid
Dirty gas filter
Clean filter
The control panel will not reset .
Red light on
Faulty flame control module
Replace the flame control module after first checking the electrical connections
Fan works intermittently
Defective fan control
Change fan control or SND thermostat
Insufficient gas pressure
Check that the gas type is suitable for the heater .
Check the gas pressure Check burner head pressure.
The fan does not work.
Defective fan control
Change fan control or SND thermostat
Faulty fan
Check fan capacitor. Check the fan motor .
The heater works continuously with out reaching the required temperature
Heater to small for application
Insufficient gas pressure
Re check heat output required for the application
Check that the gas type is suitable for the heater .
Check gas pressure. Check burner head pressure.
Dirty heat exchanger
Clean heat exchanger
B22: Single flue option with condensate tee and roof terminal combustion air from inside the room
Type 1 – 2 – 3 – 4
MIN 300
MAX 10000
140
132
U
970
410
*
Ø100
A
T
V
157 mm type 1 – 2 – 3 165 mm type 4
ITEM DESCRIPTION
A
Pipe M/F 100 L=1000 with seal
T
Terminal with guard
100
U Condensate Tee with drain point
V
Pipe M/M 100 L=200 without seal
NOTE IMPORTANT:
MODEL
1-2-3-4
FLUE SPIGOT
100 female
COMBUSTION AIR SPIGOT
100 female
INSTALLATION
Flue should be adequately supported
each bend corresponds to approx 0,8-1 meter of horizontal pipe work
B22: Single flue option with condensate tee and roof terminal combustion air from inside the room
Type 5 – 6 – 7
A
T
410
970
Ø100
Z
U
MIN 340
MAX 10000
132
165
ITEM DESCRIPTION
A
Pipe M/F 100 L=1000 with seal
T
Terminal with guard
100
U Condensate tee with drain point
Z
Pipe M/F 100 L=250 with seal
NOTE IMPORTANT:
MODEL
5-6-7
FLUE SPIGOT SIZE
100 male
COMBUSTION AIR SPIGOT SIZE
150 male
INSTALLATION
Flue should be adequately supported
Each bend corresponds to approx 0,8-1 meters of horizontal pipe work
MAX 10000
Ø100
Ø100
H
H
U
175
132
970
235
140
*
MIN 300
A
Ø150
L
A
V
C32 Installation showing Vertical co axial flue terminal with condensate drain
Type 1 – 2 – 3 – 4
157 mm type 1 – 2 – 3 165 mm type 4
ITEM DESCRIPTION
A
Flue pipe M/F 100 L=1000 with seal
H
Bend 90° M/F 100 with seal
L
Vertical co axial roof terminal kit
100-100
U Condensate tee with drain point
V
pipe M/M 100 L=200 without seal
NOTE IMPORTANT:
MODEL
1-2-3-4
FLUE SPIGOT SIZE
100 female
COMBUSTION AIR SPIGOT SIZE
100 female
INSTALLATION
Flue should be adequately supported
each bend corresponds to about 0,8-1 meters of horizontal pipework
MIN 10000
115
970
410
MIN 340
185
U
Ø100
Ø150
165
Z
A
N
Ø160
C32 Installation showing Vertical co axial roof terminal with condensate drain
Type 5 – 6 – 7
ITEM DESCRIPTION
A
Pipe M/F 100 L=1000 with seal
F
Pipe M/F 150 L=1000 with seal
I
Bend 90° M/F 150 with seal
N
Vertical co axial roof terminal kit
100-150
P
Adaptor F/F 150 L=200 with seal
Q
Bend 45° M/F 150 with seal
R
Pipe M/F 150 L=140 with seal
S
Bend 90° F/F 100 with seal
U Condensate tee with drain point
Z
Pipe M/F 100 L=250 with seal
NOTE IMPORTANT:
MODEL
5-6-7
FLUE SPIGOT SIZE
100 male
COMBUSTION AIR SPIGOT SIZE
150 male
INSTALLATION
Flue should be adequately supported
each bend corresponds to about 0,8-1 meters of horizontal pipework
Loading...