9. TROUBLESHOOTING
If the
warm
air heater malfunctions check that:
- the power supply has not been interrupted.
- power fluctuations do not exceed +10%, - 15%
- the fuel has not run out.
PROBLEM
PROBABLE CAUSE
RECOMMENDED SOLUTION
WARM AIR HEATER WITH LIGHT OIL BURNER
The burner fails to start - No power - Check main switch position
- Check mains power supply
- Check connections
- Room thermostat setting too low - Change setting
The burner is shut down
by the LIMIT switch
Overheating of air caused by:
- Excessive fuel delivery rate - Calibrate as per data ID plate data
- Fan not working - Check connections or repair
- Air filter dirty - Clean
- LIMIT thermostat faulty - Replace
- FAN thermostat faulty - Replace
The burner fails to start:
The red warning light on
the burner shows that
the electronic control
unit lock-out has tripped.
Button is pressed but unit stays in
lock-out
- Power supply in excess of 230 V
+10%
- Voltage must not exceed 242 V
- Control unit faulty - Replace
Button is pressed and unit locks out
after safety time expires without the
burner igniting
- Ignition electrodes positioned
incorrectly or earthed
- Adjust position or replace
- Feed tubes broken or inverted - Repair or correct position
- Pump filter dirty - Clean
- Pump faulty - Replace
- Pump-motor coupling broken - Replace
- No fuel - Fill tank
Button is pressed and unit locks out
even where burner is already ignited
- Photocell dirty - Clean
- Control unit faulty - Replace
- Smoky combustion - Adjust combustion air gate
Burner goes out during
routine operation even
where room temperature
is below thermostat
setting.
- Room thermostat faulty - Replace
The heater runs
continuously without
reaching required
temperature.
- Rated output insufficient to heat
that room/zone
- Replace unit or back it up with
another of suitable power
- Light oil consumption below normal - Adjust it to the power rating in the
table
- The heat exchanger is dirty - Clean
The heater produces
condensation and gets
dirty
- Insufficient light oil consumption - Adjust it to the power rating in the
table.
The fan does not - Motor and/or condensator faulty - Repair or replace
- FAN-LIMIT bi-thermostat faulty - Replace