BENSON VRBD 250, VRBD 330, VRBD 490, VRBD 410 User Instructions

Headin
g
Place your message here. For m a xi m u m im pa ct, use two or three sentences.
BENSON
VARIANTE 2 RANGE
BI DIRECTIONAL
NATURAL GAS (G20 I2H)
PROPANE GAS (G31 I3P)
TUBULAR HEATER
I N S T A L L A T I O N C O M M I S S I O N I N G
S E R V I C I N G
U S E R I N S T R U C T I O N S
Issue 3 October 2007
THIS MANUAL SHOULD BE LEFT WITH THE END USER . TO ENSURE SERVICE AND MAINTENANCE INFORMATION IS AVAILABLE ON SITE
BENSON
Section Contents Page No
1.0 Compliance Notices
4
1.1 Certificates of Conformity 5
1.2 General product Information 5
1.3 General Requirements 6
1.4 Delivery & Pre-installation Checks 6
1.5 Warranty 7 Special risk areas 7
2.0 Installation
8
2.1 Installation Clearances and Mounting Heights 8
2.2 Heater Mounting 8
2.3 Warm Air Circulation 9
2.4 Air Supply 9
2.5 Flue Installation 13
2.6 Electrical Installation 17
2.7 Gas Installation 18
3.0 Commissioning
19
3.1 Electrical Pre tests 19
3.2 Gas pre tests 19
3.3 Ignition Sequence 20
3.4 Hand Over 21
4.0 Servicing
21
4.1 Servicing Procedure 21
5.0 Fault Diagnosis
23
6.0 Wiring Diagrams
25
7.0 Technical Data
30
7.1 Technical Data Common Information 30 Pre Purge information 32
7.2 Technical Data Heater Specifications 33
8.0 Parts Listing
34
9.0 Dimensions
35
IMPORTANT NOTICE TO INSTALLERS
Installers should satisfy themselves that the gas pipework installation is carried out in accordance with all current legislation, Codes of Practice and recommendations . Additionally it may be necessary to protect the gas valves which form part of the heater or burner assembly from potential pipe contamination particularly, but not exclusively , where copper gas pipework is used.
In instances where copper pipework is to be used for all or part of a gas pipework installation, including short length final connections then we advise that installers consult with gas supplier or provider and satisfy themselves what additional precautions may be necessary
Any reference made to Laws, Standards, Directives , Codes of Practice or other recommendations governing the application and installation of heating appliances and which may be referred to in Brochures, Specifications, Quotations, and Installation, Operation and Maintenance manuals is done so for information and guida nce purposes only and should only be considered valid at the time of the publication. Benson Heating cannot be held responsible from any matters arising from the revision to or introduction of new Laws, Standards, Directives, Codes of Practice or other recommendations.
1.0 Compliance notices
The Benson Variante range of warm air heaters detailed herewith are manufactured by Benson Heating within a strictly controlled environment within the parameters of ISO9001: 2000 These instructions are only valid if the following country code is on the appliance GB. IE. If this code is not present on the appliance, it is necessary to refer to the technical instructions which will provide the necessary information concerning the modification of then appliance to the conditions of use for the country.
The Benson Variante Range has been independently tested and assessed, and has been found to meet the Essential Requirements of the following European Directives.
Gas Appliance Directive (90 / 396 / EEC) Machinery Directive (89 / 392 EEC) Low Voltage Directive (73 / 23 / EEC & 93 / 68 / EEC) Electromagnetic Compatibility Directive (98 / 336 / EEC & 91 / 31 / EEC) Product Liability Directive 65 / 374 / EEC)
The manufacturer has taken reasonable and practical steps to ensure that Benson Variante Range of Heaters are safe and without risk when properly used. These heaters should therefore only be used in the manner and purpose for which they were intended, and in accordance with the recommendations detailed herewith.
The heaters have been designed, manufactured, assembled, inspected, and tested, with safety and quality in mind, there are certain basic precautions which the installer and user should be aware of, and they are strongly advised to read the appropriate sections of the information pack accompanying the heater, prior to installation or use.
Benson Heating supports all new products being supplied to their customers with a comprehensive information pack; this clearly defines mandatory instructions for the safe installation, use, and maintenance, of the Appliance (s).
Where proprietary items are incorporated into Benson Heating products, detailed information and instructions are also provided as part of the information pack.
It is the responsibility of the installer, owner, user, or hirer, of such products supplied by Benson Heating, to ensure that they are familiar with the appropriate information manuals, supplied by the manufacturer, and that they are suitably aware of the purpose of the manuals and the safety instructions. In addition, operators must be suitably trained in the use of the appliance so as to ensure its continued safe and efficient use.
Benson Heating has a commitment to continuous improvement, and therefore reserves the right to amend or change the specification of the Variante Heater range subject to agreement from The Notified Body.
Contained within the text of the manual, the words 'Caution' and 'Warning' are used to highlight certain points.
Caution is used when failure to follow or implement the instruction (s) can lead to premature failure or damage to the heater or its component parts.
Warning is used when failure to heed or implement the instruction (s) can lead to not only component damage, but also to a hazardous situation being created where there is a risk of personal injury.
The Benson Variante range of heaters conform to the following European Harmonised Standards.
BS EN 1020 Requirements for non domestic gas fired forced convection air heaters for space heating incorporating a fan to assist transportation of combustion air and/ or combustion products.
BS EN - ISO 12100-1:2003 & BS EN - ISO 12100-2:2003 Safety of Machinery - Basic Concepts, General Principles for Design Part 1 & Part 2
BS EN 60204 - Part 1 : 1993 Safety of Machinery - Electrical Equipment for Machines Specification for General Requirements
BS EN 60335 - Part 1 : 1988 Safety of Household and Similar Electrical Appliances General Requirements
BS EN 55014 - 1993 Limits and methods of measurement of radio disturbance characteristics of electrical motor-operated and thermal appliances for household and similar purposes, electrical tools and similar electric apparatus
BS EN 50165 - 1997 Electrical Equipment of non-electric heating appliances for household and similar purposes, safety requirements
The Benson Variante range of gas unit heaters meet with the governments criteria in respect of the Enhanced Capital Allowance Scheme
1.1 Certificates of conformity
Declarations and Certificates are available upon request from the Quality Control Department at Benson Heating .
Notified Body PIN Reference is
063BQ5461
1.2 General product information
The Benson Bi Directional Variante range
includes for 4 model sizes with outputs from
72.0 kW to 144.0 kW, Variante heaters are suitable for operation on natural gas (G20) or LPG (Propane G31)
The Model Range is made up as follows
Variante heaters have been approved for alternative flue discharge arrangements These are detailed in following page’s
Cabinet
Manufactured
from electro-
zinc coated
steel,
finished in a
durable stove
enamelled
polyester
powder paint.
Heat Exchanger
Manufactured
from aluminised
dimpled steel
tube formed into
a W shape to
give enhanced
efficiency .
Model No 250 330 410 490
Output kW
72.0 96.0 120.0 144.0
Flue / Combustion Air Spigot
Each heater is fitted with two spigots both of which are located to the rear of the appliance One of the pair is for connection for the flue whilst the other is a screened combustion air intake WARNING (SEE FLUE INSTALLATION 2.5 PAGE 14)
Burner
The induced draught multi in-shot burner assembly is manufactured from aluzinc coated steel and mounted to a common steel manifold which can be easily withdrawn through the burner access compartment.
Burner Control
The heaters are fitted with automatic ignition for all models within the range.
Exhaust Fan
Combustion gases are evacuated to atmosphere via an in built power flue venter fan which is safety interlocked to the gas valve via an air pressure proving device
Air Movement Fan
VRABD are supplied with an Axial fan for free blowing applications .
Note
Neither asbestos nor soft soldered joints are used in the construction or manufacture of the Benson VRA range of Heaters. The materials selected for use can withstand the mechanical, chemical, and thermal stresses which they will be subject to during foreseen normal use when installed in accordance with the manufacturers recommendations.
1.3 General Requirements
Caution
Before installation, check that the local distribution conditions, nature of gas and pressure, and the current state adjustment of the appliance are compatible.
Warning Unauthorised modifications to the appliance, or departure from the manufacturers guidance on intended use, or, installation
contrary to the manufacturers recommendations may constitute a hazard.
Note To ignore the warning and caution notices, and to ignore the advice from the manufacturer on installation, commissioning, servicing, or use, will jeopardise any applicable warranty, moreover, such a situation could also compromise the safe and efficient running of the appliance itself, and thereby constitute a hazard.
This appliance must be installed by a competent person and in accordance with European, National, and Local criteria, including any relevant standards, codes of practice the requirements of the current building Regulations (and in particular parts J & L), Health and safety regulations IEE regulations and any requirements of the local Authority, Fire Officer or insurers Relevant standards may include BS6230, BS6891 and BS5588 parts 2 and 3
Prior to installation the following points should be considered;
a) The position of the heater for the optimum efficient distribution and circulation of warm air
b) The position of the heater relative to the route of the flue
c) The position of the heater relative to the supply of gas
d) The position of the heater relative to the electrical services, wiring routes, and if appropriate, any additional controls.
e) The position of the heater relative to the supply of fresh air
f) The position of the heater relative to potential stratification / circulation problems, which generally occur at higher levels and which may be overcome through the provision of a suitable de-stratification unit.
g) The position of the heater relative to service and maintenance requirements
Caution The heater must not be installed within an area where the conditions are unsuitable, e.g. where the atmosphere is highly corrosive, has a high degree of salinity, or where high wind velocities may affect burner operation. Suitable protection should be provided for the appliance when it is located in a position where it may be susceptible to external mechanical damage from; for example, fork lift trucks, overhead cranes etc.
1.4 Delivery and pre-installation checks
The heater is supplied wrapped in heavy duty protective polythene, mounted on a pallet. On receipt of the heater, the following checks should be carried out;
a) The model is as per order b) That it is undamaged c) That it is suitable for the gas supply and
pressure d) That it is suitable for the electrical supply If any of these points are not satisfied then
contact should be made with the Sales Office at Benson Heating as soon as possible by telephoning 01547-528534. In the case of claims for damage, this must be reported in writing within 24 hours of delivery, in order to comply with insurance criteria
1.5 Warranty
The heater is supplied with a 1 year parts and labour warranty and a further year on all parts excluding consumable’ s. In addition to this there is also a 10 year time related warranty on the combustion chamber. The warranty commences from the date of dispatch from the manufacturer, and is subject to the terms detailed within the Benson Heating 'conditions of business'.
Note (i)
The warranty may be invalidated if ­a) The warranty registration/commissioning card has not been completed and returned to Benson Heating
b) The installation is not in accordance with the general requirements of this manual
c) The flue arrangement and air supply for the heater are not in accordance with the manufacturers recommendations, codes of practice, or similar standards
d) Air flow through the heater is not in accordance with the manufacturers technical specifications
e) Internal wiring on the heater has been tampered with or unauthorised service repairs undertaken
f) The main electrical supply input to the heater has been interrupted during the heating mode
g) The heater has been subject to and affected by the ingress of water in any form
h) The heater is not operated at the rating(s) laid down in the manufacturers technical specifications
i) The heater has not been operated or used within the normal scope of its intended application
j) The manufacturer's recommended minimum service requirements have not been complied with
Note (ii)
All warranty claims must contain the following information to enable processing to take place; (1) Heater model (2) Heater serial number (3) Order reference/date of order, together with full installation details (name and address) (4) Details or symptoms of fault (5) Installers name and address.
Faulty parts must be returned to the Benson Heating Spares Department, the address of which is provided on the cover of this
manual. Any such parts will undergo inspection to verify the claim. Replacement parts supplied prior to this may be charged, and a credit supplied upon subsequent validation of the warranty claim. Consumable items are specifically not included within the scope of the warranty.
Note (iii)
Notification is required immediately a fault is suspected. The manufacturer will not accept responsibility for any additional damage that has been caused, expense incurred, or consequential loss resulting from any failure of the heater(s).
SPECIAL RISK AREAS
Where it is proposed to install a heater within a special risk area (e.g. an area containing flammable vapours where petrol engined vehicles are stored parked or serviced where paint spraying occurs, or where woodworking machinery or other flammable dust creating process’s are employed then restrictions, additional regulations concerning the heater flue wiring or controls may apply. It is strongly recommended that you contact Benson Technical before installation
Caution
When used in room sealed mode it may be possible to install Variante heaters in areas containing flammable vapours, high levels of airborne dust combustible dust chlorinated or halogenated hydrocarbons degreasing solvents styrenes other laminating materials or airborne silicones. Benson Technical should be contacted before installation . Failure to do so may invalidate or reduce guarantee cover.
2.0 Installation
The location chosen for the heater must allow for the fitting of an effective flue system. The location must also allow for adequate clearance for the air supply, return air circulation, gas supply, electrical supply, whilst also providing good and safe working access.
The heater must be installed so that it is level, supports for the heater must be sufficiently robust to withstand the weight of
the heater and any ancillary equipment Any combustible material adjacent to the heater or flue system must be so placed or shielded so that its surface temperature does not exceed 65
0
C. Generally a free blowing heater should be located at a height (measured from floor level to the base of unit) as detailed within section 2.1
VRABD free blowing heaters are at their most effective when located as close to the working area as possible. However care should be exercised to avoid directing the discharged air directly onto the occupants of the area to be heated.
Where the passage of cold air causes problems (e.g. by entrances, loading bays etc) it is considered favourable if the heater is positioned so as the discharge towards or across the cold air source from a distance from 1.5m - 6m dependent upon the size of the entrance and the air throw characteristics of the heater. On exposed walls heaters should be positioned so as to discharge towards, or along the length of the exposed wall. In areas where it is proposed that more than one heater is to be installed, a general scheme of circulation should be drawn up and maintained, thereby offering the best heat distribution. Air pressure within the area heated and the outside air pressure must remain the same, factors influencing this would be the presence of extraction systems,
Model VRA/C
250 330 410 490
Min 2.4 2.4 2.4 2.4 Max 5.0 5.0 5.0 5.0
Model 250 330 410 490
Above
300 300 300 300
Below
300 300 300 300
Right side
250 250 250 250
Left side
950 950 950 950
Clearances VRABD in mm
Left hand side = burner compartment side
ventilation systems, and various types of process plant. Applications should be suspended centrally over the area into which the warm air is to be discharged .
2.1 Installation Mounting Heights and Clearances
The Heater must be installed within the mounting heights indicated below The following heights in metres On a level non-combustible surface capable of adequately supporting the weight of the unit and ancillary equipment .
2.2 Heater Mounting
The heater and flue must be adequately supported by one of the following methods ;
a) Suspension by steel drop rods or straps from the M10 fixing points located on top of the heater These must be of sufficient strength to safely carry the weight of the unit and ancillary equipment. The straps may only drop vertically to eyebolts, if used; I.E. They must not be joined to the eyebolt at an angle to the vertical, and eyebolts if used should be of an approved type.
2.3 Warm Air Circulation
The air heater should be positioned to enable maximum circulation of discharged warm air within the area to be heated, whilst taking account of personnel within the area, sources of cold air ingress , and obstructions.
Ensure louvres are adjusted outwards and ensure blades are not resonating
The air temperature rise on passing the heat exchanger is typically around 34
0
C
A full and
unobstructed
return air path to
the air heater
must be
provided
(see 2.4 Air
Supply).
Where the heater is positioned to deliver blown air through an opening in a wall, return air intakes should be located so that they cannot become blocked. Similarly these intakes must be positioned so as not to draw in odours, fumes, hazardous vapours or particles.
2.4 Air Supply for Combustion and Ventilation
Consideration
must be given to
the provision of
air for the
purposes of
combustion and
ventilation of the
heated space,
plant room or
enclosure where
the heaters are to be installed .
It is strongly
recommended
that BS 6230 :
2005 is referred
to for further
information
concerning
ventilation
requirements
2.4.1 Heaters installed within the heated space
Where heaters are installed within the heated space (i.e. not a plant room , or enclosure ) then
Combustion air or heater related ventilation air will not be required if -
 The heaters are installed in room
sealed mode (ie with a positive connection to atmosphere of both flue and combustion air)
OR
 If the design air change rate of the
heated space is 0.5 air changes per
hour or greater The design air change rate may be satisfied by natural infiltration or by mechanical ventilation.
Combustion air ventilation will be required if
 The heater(s) are installed with flue
only (ie without the positive connection
to atmosphere of a combustion air
duct)
And
 The design air change rate of the
heated space is less than 0.5 air
changes per hour Where heater(s) are installed without the
positive connection of combustion ductwork within a heated space where air change rate of that heated space is less than 0.5 air changes per hour then it will be necessary to provide either natural ventilation openings to the heated space (Section 2.4.1.1 refers) or the mechanical ventilation of the heated space (Section 2.4.1.2 refers)
2.4.1.1 Natural Ventilation Openings to the Heated Space
If the heater(s) are to be installed without the positive connection of combustion air ductwork within a heated space, and where
MODEL
Minimum Free Area Of
Ventilation Opening
High Level Low Level
cm2 cm2
250 None 158 330 None 211 410 None 263 490 None 315
the design air change rate of that heated space is less than 0.5 air changes per hour, then provision for low level natural ventilation openings only will be necessary. The minimum free area of the low level natural ventilation opening shall be
 2 cm
2
for each kW of rated heat input
The low level natural ventilation opening should be situated on an external wall and be within 1000 mm of floor level for natural gas and ideally at floor level for lpg gas installations but in any event no higher than 250 mm.
The table below provides specific data for each heater model as -
2.4.1.2 Mechanical Ventilation to the Heated Space
In the event that the heater(s) are to be installed without the positive connection of combustion ductwork within a heated space and where that heated space has a design air change of less than 0.5 air changes per hour and that the installer prefers to mechanically ventilate the heated space rather than provide ventilation openings then
-
 The heated space needs to be
mechanically ventilated so that the
design air change is 0.5 air changes
per hour or greater.
 It is a requirement that the mechanical
ventilation shall be of the !input! Type
with either natural or mechanical
extraction
 Systems of mechanical extraction with
a natural inlet shall not be used
 It is necessary to provide an automatic
means to safely inhibit heater(s)
operation should mechanical air supply
fail for any reason
2.4.2 Heaters Installed within a Plant Room or Enclosure
A plant room means a room housing the heater plant and probably other items of building service plant and would generally have generous space for maintenance
An enclosure is where the heater is installed within a compartment or confined area where space is limited Where heaters are installed within a plant room or enclosure then provision for both combustion air and / or air for general ventilation will be required by means of high
MODEL
Minimum Free Area Of
Ventilation Opening
High Level Low Level
cm2 cm2
250 394 394
330 527 527
410 656 656
490 787 787
MODEL
Minimum Free Area Of
Ventilation Opening
High Level Low Level
cm2 cm2
250 158 316 330 211 422 410 263 525 490 315 630
and low level ventilation openings (sections
2.4.2.1 and 2.4.2.2 refer to plant room applications and sections 2.4.2.3 and 2.4.2.4 refer to enclosure applications).
Alternatively the plant room or enclosure may be mechanically ventilated (section 2.4.2.5 refers)
2.4.2.1 Natural Ventilation Openings to Plant Rooms for Room Sealed Heaters
For plant room applications the minimum free area of ventilation opening will depend upon whether the heater(s) is installed in room sealed mode (ie with a positive connection to atmosphere of both flue and combustion air) Or with flue only (ie without the positive connection to atmosphere of a combustion air duct)
Where the heater(s) is installed in a plant room and in room sealed mode (ie with a positive connection to atmosphere of both flue and combustion air ) the minimum free area of ventilation opening needs to be
 At high level 5 cm
2
for each kW of
rated heat input
 At low level 5 cm
2
for each kW of rated
heat input
The high level ventilation opening should be sited on an external wall and positioned as high as is practical and always within the top 15% of the wall height
The low level natural ventilation opening should be situated on an external wall and be
within 1000 mm of floor level for natural gas and ideally at floor level for l.p.g gas installations but in any event no higher than 250 mm.
The table below provides specific data for each heater model as -
2.4.2.2 Natural Ventilation Openings to Plant Rooms for Flued Heaters
Where the heater(s) is installed in a plant room and in flue mode (ie without a positive connection to atmosphere of combustion air ductwork ) the minimum free area of ventilation opening needs to be
 At high level 2 cm
2
for each kW of
rated heat input
 At low level 4 cm
2
for each kW of rated
heat input The high level ventilation opening should be
sited on an external wall and positioned as high as is practical and always within the top 15% of the wall height
The low level natural ventilation opening should be situated on an external wall and be within 1000 mm of floor level for natural gas and ideally at floor level for l.p.g gas installations but in any event no higher than
MODEL
Minimum Free Area Of
Ventilation Opening
High Level Low Level
cm2 cm2
250 394 394
330 527 527
410 656 656
490 787 787
MODEL
Minimum Free Area Of
Ventilation Opening
High Level Low Level
cm2 cm2
250 394 788
330 527 1053
410 656 1312
490 787 1574
250 mm. The table below provides specific data for each heater model as -
2.4.2.3 Natural Ventilation Openings to
Enclosures for Room Sealed Heaters
For enclosure applications the minimum free area of ventilation opening will also depend upon whether the heater(s) is installed in room sealed mode (ie with a positive connection to atmosphere of both flue and combustion air) Or with flue only (ie without the positive connection to atmosphere of a combustion air duct)
Where the heater(s) is installed in a plant room and in room sealed mode (ie with a positive connection to atmosphere of both flue and combustion air ) the minimum free area of ventilation opening needs to be
 At high level 5 cm
2
for each kW of
rated heat input
 At low level 5 cm
2
for each kW of rated
heat input
The high level ventilation opening should be sited on an external wall and positioned as high as is practical and always within the top 15% of the wall height The low level natural ventilation opening should be situated on an external wall and be within 1000 mm of floor level for natural gas and ideally at floor level for l.p.g gas installations but in any event no higher than 250 mm.
The table below provides specific data for each heater model as -
2.4.2.4 Natural Ventilation Openings to Enclosures for Flued Heaters
Where the heater(s) is in an enclosure and in flue only mode (ie without a positive connection to atmosphere of combustion air ductwork ) the minimum free area of ventilation opening needs to be
 At high level 5 cm
2
for each kW of
rated heat input
 At low level 10 cm
2
for each kW of
rated heat input The high level ventilation opening should be
sited on an external wall and positioned as high as is practical and always within the top 15% of the wall height The low level natural ventilation opening should be situated on an external wall and be within 1000 mm of floor level for natural gas and ideally at floor level for l.p.g gas installations but in any event no higher than 250 mm.
The table below provides specific data for each heater model as -
2.4.2.5 Mechanical Ventilation to a Plant Room or Enclosure
In the event that the installer prefers to mechanically ventilate the plant room or enclosure rather than provide ventilation openings then -
 The plant room or enclosure needs to
be mechanically ventilated at the rate
of 4.14 m
3
/h of fresh air per kW or
rated heat input.
 It is a requirement that the mechanical
Mechanical Ventilation Rate for Plant Room or
Enclosure
M3/h
250
327
330
436
410
543
490
652
MODEL
Provision for the disconnection of the flue for servicing and inspection purposes must also be made. The position of the flue and its terminal should be such that it does not impair the combustion process. It should terminate in an exposed position so as to allow the free escape of flue gases without risk of their re­entering the building through windows, ventilation ports etc.
The following distances in mm’s should be observed
200
below guttering or eaves
300
from corners or openings (windows
doors etc) and from other horizontal terminals on same wall
1200
from a facing surface
1500
from another terminal vertically on the
same wall
2000
from ground level
The heaters must be connected to the flue system supplied by Benson Heating and be capable of withstanding the stresses and loadings associated with normal use. When designing the flue system the prevention of the formation and entrapment of condensation must be a key consideration. Horizontal flue should be fitted ensuring a slight gradient approx 2
0
towards the terminal
Where condensation is unavoidable traps should be included to encourage the condensates to flow freely to a point from which they may be released, preferably into a gully.
The condensate pipe from the flue to the disposal point must be made from corrosion resistant pipe of not less than 25mm internal diameter. If the flue passes through a wall, ceiling, or roof made from combustible material then it has to be sleeved so as to provide a minimum of a 25mm void between the exterior of the flue and the internal wall of the sleeve.
C32 Vertical Co axial flue Kit options
L1 maximum combined flue length 10 metres
Coaxial Terminal Extra pipes to extend the flue are available as an option Pipe Ø 130 x 1000 mm
Pipe Ø 130 x 500 mm Pipe Ø 130 x 250 mm Bend
Ø 130 x 45
0
Bend Ø 130 x 900
Part No 33-55-207
33-54-201 33-54-202 33-54-203 33-54-204 33-54-205
Option C
12
Not Illustrated Contact Benson Technical Dept
In this configuration the heater is connected to a horizontal flue system discharging the products of combustion and bringing in the combustion air from outside the building in which the heater is located. The outlet / inlet must be through the wall and may be made with two separate pipes or with a horizontal coaxial concentric terminal. Not always practical in the Bi Directional configuration.
Option B22
In this configuration the heater is connected to a single flue pipe to discharge the products of combustion outside the building either through the roof or through a wall. The air for combustion is taken from inside the building.
L1 maximum flue length 10 metres
Universal Terminal Extra pipes to extend the flue are available as an option Pipe Ø 130 x 1000 mm Pipe Ø 130 x 500 mm Pipe Ø 130 x 250 mm Bend
Ø 130 x 45
0
Bend Ø 130 x 900
Part No 33-54-207
33-54-201 33-54-202 33-54-203 33-54-204 33-54-205
Heater Unit Flue Exit HORIZONTAL Flue Exit VERTICAL
MIN. MAX. MIN. MAX.
250 m 1,00 8,00 1,00 10,00
330 m 1,00 8,00 1,00 10,00
410 m 1,00 8,00 1,00 10,00
490 m 1,00 8,00 1,00 10,00
Caution
It is imperative that the flue should be properly sealed where it passes through the roof, this can best be achieved by using the approved method of roof flashing plate and cravat. The flue spigot outlet on all Variante heaters is in horizontal configuration.
Note
It should be noted that claims made under warranty and attributed to the ingress of water may not be considered especially if an approved method of sealing has not been used, or if the design of the flue has not made provision for possible condensation problems. It is also recommended that BS5854: 1980 and BS5440: parts 1 and 2 are used as a consultative document when considering flue requirements. If terminating through a wall only use Benson approved horizontal terminals
2.6 Electrical Installation
All electrical
wiring and
connections
must be in
accordance with
the relevant
European,
National, and
Local
regulations as
well as to IEE
Standards.
Ensure that the Electric and Gas supplies are turned off before any electrical work is carried out on the heater.
Also ensure that
wiring cannot
make contact with any metal surfaces liable
to be subject to
high
temperatures,
and where
insulation of the
wiring could be
impaired as a result of such
contact.
All Variante models must be earthed.
Warning
Ensure that the
electrical supply is
compatible to
the heater.
ALL HEATERS
ARE
NEUTRALLY
RESET
Caution
The main electrical supply must not be switched off or disconnected as a method for stopping the heater, the exception to this is in the event of an emergency, or when the heater has been allowed to cool sufficiently to prevent any damage from being sustained to the heater or its controls (ie: during servicing). Claims for damage will not be considered if they have resulted from incorrect wiring or the incorrect use of the heater Each heater requires a permanent 230V 50Hz 1ph electrical supply, which must be wired through a fused isolator fitted with a fuse of the correct rating (see section 7.1). The correct supply connection points for the live, neutral, and earth. Wiring diagrams are also detailed within this manual, (section 6.0 ) The electrical supply isolator should be mounted adjacent to the air heater in an easily accessible position to allow for servicing isolation, or emergency shut off.
Electrical panel
Warning
Ensure that the mains isolator is turned OFF before undertaking any electrical work on the heater. Access to the electrical panel is gained by opening the right hand heater side panel.
Warning
Ensure that all connections are secure and that there are no loose strands which could bridge across the terminals. A minimum conductor size of 1.0 mm (diameter) is required.
Caution
When using
CP4 Optimised
Controller
Consideration
should be made
when routing
the cable
between the
control and
heater . Avoiding
where possible
any existing
cables and
switch gear as
any induced voltage may
affect the
operation of the
sequential
control box
within the
heater.
It is recommended that screened
cable is used
when the
control is to be
sited more
than 10 metres
away from the
heater
One electrical
panel per heater
is required,
unless heaters
are specified for
multiple heater
control
applications. On
no account
should more
than one heater
be connected to
a single time
switch or
thermostat.
The only
exception to this
is when a
control panel
suitable for
multiple heater
applications is
supplied by the
manufacturer.
Any ancillary electrical items e.g. room thermostats , time switches, remote panels etc, must be wired into the heater electrical circuit in accordance with the diagrams provided
Note When external controls operate to switch the
heater OFF, power to the heater should remain to allow the fan to continue to operate to sufficiently cool the heater thereby preventing damage to the heat exchanger.
Fan limit control
( Situated inside the right hand side panel)
FAN ON 50
c
FAN OFF 30c
These settings may require slight adjustment on commissioning Fan control (white button) The fan control switch features normally open 230V contacts, and is wired to control the live supply to the fan motor . When the circuit is made, the fan will switch on when the heat anticipator has closed the fan switch contacts. When the thermostat or time switch shuts down the burner, the fan will continue to run until the thermal switch has cooled sufficiently to prevent the residual heat from damaging the heater or its controls. On start up the fan delay prevents air being circulated until the desired temperature is achieved
Limit control (red button) SET at 100
c
An adjustable high temperature manual reset limit control. If this control needs resetting the cause should be determined and rectified immediately. On models with two fans a second limit control is situated inside the right side panel and is wired in series. Operation of either switch will shut down the heater. On larger models there will be additional limit stats fitted Caution The power supply to the fan must not be interrupted, the only time when power supply can be disconnected or interrupted is during servicing or in emergencies If there is a requirement for the heater to be switched off over night then the gas valve circuit should be opened via a time switch, etc, as per the wiring instructions and diagrams supplied within section 6.0 of this manual.
2.7 Gas installation
Warning Please read notice on page 3 of this manual
As there have been recorded instances of the deposition of copper sulphide dust within the valves and orifices of gas appliances as a direct result of a reaction between the hydrogen sulphide contained in some natural gasses and copper pipe we recommend that the heater(s) should not be connected to any natural gas pipe distribution system which utilizes copper pipework, including final connections. Instead steel pipework should be used throughout. In the event that it is impractical to use steel pipework or where installers are obliged or insist on using elements of copper pipework within the installation then we strongly recommend that the gas supplier be consulted as specific conditions and requirements may be necessary.
The Variante range of heaters are all manufactured and pre set for use with Natural Gas,or Lpg and all feature a 3/4” BSP connection point. Prior to installation the supply characteristics (gas type and pressure) must be checked to ensure that they are in accordance with the data plate on the heater.
The gas
supplier should
check that the
meter and
service
connection to
the heater are
capable of
delivering the
required volume
of gas, thereby
ensuring that the minimum
burner pressure
can be
achieved.
Consideration
should be given
to the
pressure drop
on single and
multi heater
installations and
the effect they
may have on
other plant
sharing the
supply.
If it is necessary to fit a gas pressure booster, the controls must include a low pressure cut off switch which must be fitted on the supply / inlet side of the booster. It is also a requirement that the gas supplier is advised prior to the installation or fitting of the booster. Each heater supply must be fitted with a separate isolating cock positioned adjacent to and upstream of the union which must be sited outside the heater.
The isolating cock should be of the 90
0
turn type and should be clearly marked OPEN / CLOSED it should also be installed so as to fall to the closed position An approved gas jointing compound must be used on all joints and unions and the system purged and tested for soundness prior to final connection The connection to the heater can be made by way of either an approved flexible coupling or rigid connection . Threaded connections must comply to ISO 288/1 or ISO 7/1 further information concerning accepted European practice is detailed in BS EN1020 1998. The diameter of the pipework from the isolating cock to the burner must not be less
than the diameter of the connection into the multiblock.
Note
Reference to The Institute of Gas Engineers publications Utilisation Procedures IGE/UP1 and IGE/UP2 together with reference to BS6891 is strongly advised.
3.0 Commissioning
Note It is a requirement that only suitably qualified and competent personnel are allowed to undertake the commissioning of the heater. It is also strongly recommended that prior to commissioning the engineers familiarises themselves with the heater. the specific requirements of the installation / application, and the information contained within the manual.
Warning
All heaters are subject to a rigorous test programme prior to despatch, whilst such a programme does involve pre-commissioning and the setting of the heater to operate efficiently and within its designed operational limits this does not mean that the function of thorough on site commissioning is less important It is strongly recommended that the equipment used for the sampling and analysis of the flue gases is accurate to within +/- 0.1% and maintained so that it is regularly calibrated.
The following
pre-
commissioning
checks should
be undertaken,
having first
ensured that the
gas and
electrical
supplies are
turned off.
(a) Check that all panels and fasteners are secure and in place.
(b) Check that the heater is mounted safely. (c) Check that the flue is sealed, secured,
and adequately supported. (d) Check that the fan is free to rotate, that
the fan is secured to its shaft, and that the guards and fan assembly are all in place and properly secured.
(e) Check that the heater is installed so that it is not tilted and remains square.
(f) Check that the outlet louvres (Axial heaters) are set to offer minimum resistance to air flow.
3.1 Electrical pre-tests
The electrical safety checks must include the following a) Test for earth continuity
b) Test for resistance to earth c) Check live and neutral connections are
correct. d) Check to ensure that when the external
controls operate to switch the heater off, power remains to the fan
3.2 Gas supply pre-test
Ensure that the service pipework has been installed purged and tested in accordance
Fault Finding
Gas Supply ON
Burner fails to li
g
ht
Turn on Gas Supply
Electric Supply ON
Turn on Electric Supply
Air in Gas Supply
Purge Gas Line
Thermostat calling for heat
Limit thermostat operated
No
Yes
Rese t Li mi t thermostat
Air pressure switch made
Check flue fan connections
Flue fan running
Yes
Replace flue fan
Check flue is clear
Change air pressure switch
Yes
Spark ignition on
Check HT leads and connections
No flame
Faulty control box
No
Change gas valve
Faulty G a s valve
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
YesYes
Yes
Check fuse Replace if required
Fault finding cont’d
Fan will not run heater goes off on limit
No
Bad electrical connection
Yes
Check wiring connection
Reset fan control settin
g
s
Fan runs in manual mode
Fan control settings incorrect
Yes
Yes
Yes
Yes
Yes
No
No
Faulty fan control
Faulty fan motor or ca
p
acitor
Change fan control
Change fan motor or ca
p
acitor
Wiring Diagrams VR 250-330 Auto Ignition
WARNING NEUTRAL RESET
Wiring Diagram VRBD 410- Auto Ignition
WARNING NEUTRAL RESET
TBA
Wiring Diagram VRBD 490- Auto Ignition
Wiring Connection CP2 On/Off 33-64-350T
Wiring Connection CP2 Hi/Lo 33-64-488T
WARNING NEUTRAL RESET
WARNING NEUTRAL RESET
CP4 Controller Connections 33-64-351T
Less Controls Connections 33-64-349T
WARNING NEUTRAL RESET
WARNING NEUTRAL RESET
7.1 Technical Data Common Information
Appliance Type B
22 C 32 C12
PIN / report no 0063BQ5461 Electrical Supply 230V 50Hz 1ph Fuse Rating 6 AMP IP Rating IP20 Fan Limit Settings Fan On 50ºC Fan Off 30ºC Limit 100ºC
Country Approved Gas Category
AT,CH,CZ,DK,EE,ES,FI,GB,GR,HU,IE,IT IS,LT,LV,NO,PT,RO,SE,SI,SK,TR
I2H
BE,CZ,NL,FR,DE,IE,IT,ES,CH,PT,GB,SE,
SK,SL,PT,PL,TR
I3P
PL,LU,DE,RO
I2E
PL
I
2LS
PL
I
2LW
Natural Gas (G20 I2H) Tubular Heater
The minimum allowable pre-purge time requires calculating [BS EN1020:1998 clause 6.38]. To do this only the Carbon Dioxide CO
2
figure needs to be measured.
E.G. on a model 250 the calculated minimum time is = 286.2/ ((100 / CO2) + 1) If the measured CO
2
is 6.7%
Then 100 / 6.7 = 14.9
14.9 + 1 = 15.9 Therefore minimum pre-purge time is = 286.2 / 15.9 = 18.0 seconds The calculation to be conducted is given below for all models:
Model 250 Minimum pre-purge time = 286.2 / ((100 / CO2) + 1) Model 330 Minimum pre-purge time = 269.7 / ((100 / CO2) + 1) Model 410 Minimum pre-purge time = 261.4 / ((100 / CO2) + 1) Model 490 Minimum pre-purge time = 269.2 / ((100 / CO2) + 1)
The pre-purge time must then be measured. If the measured pre-purge time is lower than the calculated time STOP and contact Benson Heating.
Propane (G31 I3P) Tubular Heater
The minimum allowable pre-purge time requires calculating [BS EN1020:1998 clause 6.38]. To do this only the Carbon Dioxide CO
2
figure needs to be measured.
E.G. on a model 250 the calculated minimum time is = 724.7 / ((300 / CO2) + 2.01) If the measured CO
2
is 8.0%
Then 300 / 8.0 = 37.5
37.5 + 2.01 = 39.51 Therefore minimum pre-purge time is = 724.7 / 39.51 = 18.3 seconds The calculation to be conducted is given below for all models:
Model 250 Minimum pre-purge time = 724.7 / ((300 / CO2) + 2.01) Model 330 Minimum pre-purge time = 682.8 / ((300 / CO2) + 2.01) Model 410 Minimum pre-purge time = 661.7 / ((300 / CO2) + 2.01) Model 490 Minimum pre-purge time = 681.6 / ((300 / CO2) + 2.01)
The pre-purge time must then be measured. If the measured pre-purge time is lower than the calculated time STOP and contact Benson Heating.
NAT GAS / LPG MODEL 250 330 410 490
HEAT
OUTPUT
kW Btu
72.0
246,000
96.0
328.000
120.0
409,000
144.0
491,000
HEAT INPUT
(Nett)
kW Btu
78.8
268,900
105.2
359,000
130.4
445,000
156.5
534,000
EFFICIENCY % Nett 91.4 91.2 91.5 91.5
EFFICIENCY % Gross 82.3 82.1 82.4 82.4
HEAT
OUTPUT Low Fire
kW Btu
46.6
159,000
62.2
212.250
77.5
264,430
93.0
317,300
HEAT INPUT
(Nett) Low Fire
kW Btu
50.7
173,000
67.6
230,720
83.8
286,000
100.6
343,200
GAS CONNECTION BSP/Rc
3/4”
3/4” 3/4” 3/4”
MIN INLET
PRESS NAT GAS
mbar
Ins WG
17.5 7
17.5 7
17.5 7
17.5 7
BURNER
PRESSURE NAT GAS
mbar
Ins WG
8.7
3.5
8.7
3.5
9.2
3.7
9.2
3.7
BURNER PRESSURE
NAT GAS Hi Lo
Hi mbar
Lo mbar
8.7
3..5
8.7
3.5
9.2
3.8
9.2
3.8
MAIN INJECTOR
NATURAL GAS
mm
No Off
3.4 6
3.4 8
3.4 10
3.4 12
NAT GAS
CONSUMPTION
ft3/hr
m
3
/hr
294
8.33
393
11.12
490
13.87
587
16.63
MIN INLET
PRESS LPG
Mbar
Ins WG
37.0
14.8
37.0
14.8
37.0
14.8
37.0
14.8
BURNER
PRESSURE LPG
Mbar
Ins WG
25.5
10.2
25.5
10.2
25.5
10.2
25.5
10.2
LPG PROPANE
CONSUMPTION
m3/hr
Kg/h
3.21
5.94
4.28
7.92
5.34
9.88
6.41
11.86
MAIN INJECTOR
PROPANE GAS
Mm
No Off
2.0 6
2.0 8
2.0 10
2.0 12
TEMPERATURE
RISE
ºC
ºF
32 58
34 61
32 58
32 58
AIR
FLOW
ft3/min m
3
/sec
4026
1.90
4789
2.26
6527
3.08
8010
3.78
VRABD THROW
ft
mtrs
203
62
210
64
249
76
256
78
FAN STATIC
PRESSURE
Pa
Ins WG
150
0.60
180
0.72
200
0.80
200
0.80
SOUND LEVEL @ 3m Dba 61 63 66 66
FLUE DIAMETER * mm 130 130 130 130
COMBUSTION AIR DIA mm 130 130 130 130
SUPPLY VOLTAGE Axial 230/1/50 230/1/50 230/1/50 230/1/50
ELECTRICAL POWER(AMPERES) Axial 2.8 4.2 4.8 5.8
INTERNAL FUSE
RATING AMPERES
VRA 6 6 6 6
POWER ABSORPTION Kw Axial 0.56 0.88 0.95 1.2
MOUNTING HEIGHT
(MTRS)
Min
Max
2.4
3.5
2.4
3.5
2.4
3.5
2.4
3.5
GROSS FLUE TEMP ºC 150 150 160 160
WEIGHT Kgs Axial 181 203 242 279
AIR PRESS SWITCH mbar 1.65 1.65 1.65 1.65
FLUE
RESISTANCE
min mbar max mbar
-0.2
+0.4
-0.2 +0.4
-0.2
+0.4
-0.2
+0.4
7.2 Technical Data
MODEL 250 330 410 490
Fan Plenum Axial 33-64-585 33-64-586 33-64-587 33-64-588
Fan Axial VRA Standard 28-09-062 28-09-092 28-09-056 28-09-098
Fan Limit Stat 28-60-021 28-60-021 28-60-021 28-60-021
Gas Valve 28-30-181 28-30-181 28-30-184 28-30-184
Control Box 29-01-183 29-01-183 29-01-183 29-01-183
Injector Natural Gas 33-64-145 33-64-145 33-64-145 33-64-145
Injector LPG Propane 33-64-147 33-64-147 33-64-147 33-64-147
Inshot 33-64-160 33-64-160 33-64-160 33-64-160
Gas Manifold 33-64-017 33-64-018 33-64-153 33-64-154
Air Pressure Switch 28-40-139 28-40-139 28-40-139 28-40-139
Flue Fan 28-09-089 28-09-089 28-09-090 28-09-090
Run Neon Green 28-50-038 28-50-038 28-50-038 28-50-038
Lockout Neon Red 28-50-030 28-50-030 28-50-030 28-50-030
Overheat Thermostat 28-60-039 28-60-039 28-60-039 28-60-039
Electrode 33-64-193 33-64-193 33-64-193 33-64-193
Ionisation Probe 33-64-194 33-64-194 33-64-194 33-64-194
Fuse Holder 28-07-050 28-07-050 28-07-050 28-07-050
Fuse 28-07-048 28-07-048 28-07-048 28-07-048
Reset Switch 28-40-141 28-40-141 28-40-141 28-40-141
Reset Relay 230 Volt 28-25-039 28-25-039 28-25-039 28-25-039
Optimised Control B-CP4 B-CP4 B-CP4 B-CP4
8.0 Parts list
V2RABD
Heater A B C D E F G H J K
250- 490
225 85 330 900 1630 1860 210 200 130 130
Vertical Co/Axial Terminal Dimensions
Dimensions in mm’s
AIR FLUE
Heater A B C D E F G B+C
250-490
180 420 340 225 200 130 130 750
Horizontal Co/Axial Terminal Dimensions
Ensure Terminal is located on the wall in this configuration
TOP
BOTTOM
Dimensions in mm’s
AIR
FLUE
BENSON HEATING LUDLOW ROAD KNIGHTON POWYS LD7 1LP
Telephone +44 (0) 1547 528534 Facsimile +44 (0) 1547 520399 email information@bensonheating.co.uk Web www.bensonheating.com
Loading...