BENSON JETSTREME 4+ Instruction Manual

,
f
S
BENSON
-
!
j
• Installation
• Commissioning
• Service
and
Maintenance
• User Manual
(to
be
retained
by
the user)
\J
_~_J
I
Introduction
The Benson Jetstreme 4+ series of
highly
efficient oil fired boilers
combine
the
benefits of
advanced design with well proven construction techniques
and
modern
manufacturing processes.
They operate at high efficiency with clean combustion
and a low
operating noise level.
The heat exchanger is enclosed within
an
insulated jacket
with
secondary insulation attached
on
the
inside ofthe
case. The case is finished
in
white
powder
coat enamel
and
is styled to blend into
any
kitchen. The controls are enclosed behind
an
hinged panel
on
the
front of
the
appliance
thus
reducing possible accidental
damage
to them.
A flame viewing port facility is located
at
the
front of the boiler directly behind
the
front panel.
A combustion test point is located
on
the flue spigot
of
the
boiler to enable the commissioning
engineer to carry
out
his setting checks at a convenient point.
The Jetstreme 4+
range
is available for
both
Conventional
and
Balanced Flue systems.
The Balanced Flue range is extremely versatile offering several configurations for the installation of the terminal.
The Jetstreme 4+ range
of
both Conventional
and
Balanced Flue Appliances are designed to
operate
on
Kerosene fuel oil
(28
sec). The Conventional Flue appliance can also
be
operated
on
gas
oil
(35
sec), however
it
is not recommended that
the
Balanced Flue appliances are operated
on
this
fuel as combustion problems could occur. All boilers are supplied
with
the
burners
adjusted for
use
with Kerosene (class C2)
28
sec fuel oil. Should the
use
of
gas oil (class D) 35 sec
be
required to
be
used with a Conventional Flued appliance
then
the modification
must
be
carried
out
at
the time
of
installing
and
commissioning.
Although the Jetstreme range of boilers will operate successfully
on
a gravity
hot
water system
it is recommended that a fully
pumped
system is used for both hot water
and
central heating
if
installing a
new
system. The boiler is suitable for
open
vent
and
pressurised systems, however if a
pressurised
system
is
used,
the
manufacturers
recommendations
for
the
use
of
the
auxiliary
components
must
be
adhered
to,
and
pressure
must
not exceed
45
psi
(3
bar).
The Jetstreme
4+
boiler is
approved
by
BSRIA
(the Building Services Research & Information
Association) for OFTEC.
1
Regulations
This appliance
must
be
installed
by
a competent person working
to
the following:-
The
Latest OFTEC Technical Information Book 3.1992 (Installation Requirements for Oil Fired Boilers & Storage Tanks). The current Building Regulations
and
Local By-laws. Local Water By-laws. The current
IEE
regulations.
BS
799.
part
5:
1987 Specifications for Oil Tanks.
BS
5410.
part
1:
1977 Code
of
practice for oil firing.
BS
5449.
part
1:
1990 Code of practice for Central Heating for Domestic Premises.
BS
6798.
1987 Specification for the installation of Gas Fired
Hot
Water Boilers of Rated
input
not
exceeding
60
kW.
BS
7593.
1992 Code of practice for
the
treatment of water
in
domestic hot
water
central heating
systems.
Jetstreme
4+
Installation Instructions.
On
completion
of
installation
the
appliance
must
be
commissioned
by
a competent engineer
with
an
understanding
of the technology
and
with
the
equipment to enable
him
to carry
out
tests
to set the appliance at its
optimum
efficiency
and
clean combustion.
The Health and Safety at Work Act
The installer should be aware
of
his responsibilities
under
the Health and Safety at Work Act
whereby
it
is necessary for him to afford protection to persons carrying
out
the installation
and
others within the location.
2
Technical Data
Model
40/52
50/70 70/90
951120
1251140
Heat
Output
15.2kW 52,000 Btu
20.5kW 70,000 Btu
26.4 kW 90,000 Btu
35.2kW 120,000 Btu
41.2kW 140,000 Btu
Fuel Conventional Flue
Class C2 or
Class D
Class C2 or
Class D
Class C2 or
Class D
Class C2 or
Class D
Class C2 or
Class D
Fuel Balanced Flue
Class C2 only
Class C2 only
Class C2 only
Class C2 only
Class C2 only
Weight (Empty) Kg
Ib
85.0
187.0
85.0
187.0
118.0
260.0
159.0
350.4
159.0
350.4
Water
Content
It
imp
gal
13.3
2.9
13.3
2.9
25.0
5.5
31.0
6.8
31.0
6.8
Flow
& Return
connections
4 x 11/4
BSP
4
X
}1/4
BSP
4 x 1 BSp1/
2
4
X
}1/2
BSP 4 X
}1/2
BSP
Flue Socket Dia.
c.F.
Only
102mm 4 in.
102mm 4 in.
127mm 5 in.
152mm 6 in.
152mm 6 in.
Fuel Connection
3/8
BSP
Compression
3/8
BSP
Compression
3/8
BSP
Compression
3/8
BSP
Compression
3/8
BSP
Compression
Water Resistance
@ 11°C Diff.
300mm 12 in.
300mm 12 in.
300mm 12 in.
300mm 12
in.
300mm 12 in.
Minimum
Flue
Draught
8.7
N/m2
0.035 in.
wg
8.7
N/m2
0.035 in.
wg
8.7N/m2
0.035 in.
wg
8.7N/m2
0.035 in.
wg
8.7
N/m2
0.035 in.
wg
Maximum
Flue
Daught
37.4
N/m2
0.15"
wg
37.4
N/m2
0.15"
wg
37.4
N/m2
0.15"
wg
37.4
N/m2
0.15"
wg
37.4
N/m2
0.15"
wg
Rec.
Minimum
Return
Temp.
50°C 120°F
50°C 120°F
50°C 120°F
50°C 120°F
50°C 120°F
Maximum Working
Head
27.5 metres 90
Feet
27.5 metres 90
Feet
27.5 metres 90 Feet
27.5 metres 90 Feet
27.5 metres 90
Feet
Maximum Working Press.
45
psi
3
bar
45
psi
3
bar
45 psi 3
bar
45
psi
3
bar
45
psi
3
bar
Electrical
Supply
240 vac 50Hz
240 vac 50Hz
240 vac 50Hz
240 vac 50Hz
240 vac 50Hz
Operating
Temp.
Range
48°C to 85°C
48°C 85°C
48°C 85°C
48°C 85°C
48°C 85°C
Table 1
3
!.
Int.
Diameter
Height
Volume
40/52
292mm
300mm
0.02M
3
50/70
292mm
300mm
0.02M
3
70/90
375mm
387mm
0.04M
3
95/120
457mm
390mm
0.06M
3
125/140
457mm
390mm
0.06M
3
Table
2
Combustion
Chamber
Size
Location
The
Jetstreme 4+
must
be
located
on
a level
non-inflammable
surface
that
can
withstand
the
weight
of
the
boiler
and
associated
equipment.
The
boiler
location
must
permit
adequate
ease
of
access for
maintenance
and
servicing.
It
is
recommended
that
the
following clearances
should
be
provided:-
Above
the
boiler
600mm
(24 inches)
To
either
side
25mm
(1
inch)
In
front
900mm
(36 inches)
When
choosing
a site for
the
boiler,
the
major
consideration
is
the
provision
of a suitable
flue
system
and
whether a Conventional
type
flue
or
a Balanced Flue
type
should
be
used.
Consideration
must
be
given
to
the
required
position
of
the
flue, access of
the
oil
supply
from
the
storage
tank,
and
the
location
of
the
air
vents
that
may
be
required.
If
the
boiler
is
to
be
located
within a compartment
or
cupboard
then
the
compartment
or
cupboard
must
be
constructed
or
modified
for
the
purpose
intended.
Details
of
these
requirements
are
given
in
BS
6798: 1987 Specification for
the
installation of
Gas
Fired
Hot
Water Boilers
of
Rated
Input
not
exceeding 60 kW.
Conventional Flue
If
the
flue is
on
the
outside
of
the
building
then
the
flue
must
be
of
the
insulated
twin
wall
type
to
eliminate
the
possible
formation
of condensate.
The
flue
should
rise
as
near
vertically
as
possible
to
its
maximum
possible
length
before
any
bends
are
included.
The
number
of
bends
should
be
kept
to
an
absolute
maximum
of
two.
No
bend
should
have
an
angle
less
than
135°.
No
part
of
the
flue
internal
diameter
should
be
less
than
that
of
the
flue
outlet
spigot
diameter
on
the
boiler.
A
brick
chimney
should
be
lined
with a suitable
stainless steel flue
pipe,
or
other
suitable
non-
combustible
lining,
with
the
void
between
the
lining
and
the
masonry
filled
with a suitable
insulating
material
e.g. vermiculite.
The
chimney
must
always
be
swept
before
the
fitting
of
a liner.
A
draught
stabiliser
must
not
be
used
unless
the
flue
pull
is
found
to
be
excessive.
The
flue
outlet
should
terminate
at
least
600mm
(24 inches)
above
the
apex
of
the
roof, if this is
not
practical,
or
it
is
found
that
the
appliance
is
being
subjected
to a down
draught,
then
an
approved
cowl
should
be
fitted to
eliminate
this condition.
The
fitting
of a suitable
cowl is
always
recommended.
4
Balanced Flue
Jetstreme 4+ boilers
are
designed
to
also
use
a Balanced Flue
system,
whereby
the
appliance
is
completely
sealed
from
the
room
where
it is installed.
Air
is
taken
directly from
the
outside
of
the
building
to
the
burner
for
combustion,
and
then
discharged
again
to
the
outside
of
the
building.
It
is
sometimes
found
that
the
burner
noise level is increased
when
passing
through
a
normal
inlet/exhaust
pipe,
but
the
Jetstreme
4+
inlet/exhaust
also
incorporates a silencer
to
reduce
this effect.
The flue kit
may
be
positioned so as to
pass
through
the
wall to
the
rear,
or
through
a side wall
to
the
left
or
right,
taking
due
account of
the
building
regulations
and
the
recommendations
shown
in
fig
5.
The
standard
flue kit is suitable for walls
up
to
11
inches thick. For walls
up
to 22 inches thick a
supplementary
kit is available
and
can
be
ordered
directly from Benson Heating,
quoting
Flue
Kit
No.1.
Flue
Kit
No.2.
This kit enables
the
balanced flue to
be
discharged
through
the
wall
at a high
level
(2
metres) above
the
floor.
Flue
Kit
No.3.
This kit,
although
still a
balanced
flue system, is suitable for situations
where
the
only
route for
the
discharge is
through
a flat
or
shallow pitched roof.
The
terminal
guard
basket
supplied
with
the
balanced
flue kit
must
always
be
fitted
even
at
high
level.
If
the
balanced
flue
terminal
discharges
within
900mm
(3
feet)
below a plastic
gutter
or
overhang,
the
gutter
must
be
protected
with
a non-combustible material.
Burner
Various
burners
are available for
use
on
the
Jetstreme 4+ boiler
and
all are rigorously tested for
their
suitability. Because
burners
may
be
added
to
the
range
from
time
to
time,
details
of
the
burners
are given
within a separate
document.
It
should
be
noted
that
the
EOGB
burner
is referred
to here; this is because
the
initial external BSRIA
approvals
for
the
Jetstreme 4+
were
carried
out
with
the
EOBG 'Burner fitted.
Oil
Supply
Any
fuel oil leak,
however
small must
be
rectified immediately.
Careful consideration
must
be
given to
the
siting of
the
oil storage tank,
taking
account of:-
Access for delivery
of
oil.
Proximity
and
relationship
of
tank
to boiler.
Visual acceptability
by
the
customer
and
neighbours.
Conformity
to local bylaws. Building Regulations. Protection for
the
retention
of
oil
in
the
event
of a leak.
Plastic oil storage
tanks
should
comply
with
OFS
TlOO
and
should
be
OFTEC
Approved
under
the
OFCERT Scheme.
5
Gravity One Pipe System
It
is recommended that the oil tank is situated so that the oil outlet from the tank is not less
than
lOOmrn
(4
inches) above the oil
burner
pump.
This will
permit
the
use
of a gravity feed system
from
the
tank to
the
burner. The oil tank outlet
must
not
exceed 4 metres (13 feet approx.) above
the
burner
pump.
All Jetstreme
4+
appliances are supplied ready to
be
used
on
a gravity system.
If
it is
not
possible to
use
a gravity feed system then conversion to a two pipe system
must
be
carried
out, this is explained
on
page
7.
A filter of the metal bowl type
with
a micronic filter element
must
be fitted
in
the
oil
supply
line.
A valve
must
not
be
fitted
on
the
oil return pipe, if this
pipe
should
become blocked it
may
cause the
pump
to
faiL
The installer MUST
supply
and
fit a fire check valve in
the
oil
supply
line,
and
this valve
must
comply
with
BS
799:
part
5: 1977 Specification for Oil Storage Tanks.
The following table shows the relationship between the head
of
oil,
the
diameter of the
supply
pipe
and
the flow.
GRAVITY ONE PIPE OIL
SYSTEM
- TANK OUTLET ABOVE BURNER
SLUDGE
COCK
FILL
20 mm PER METRE FALL
VENT
t
4 METRES MAXIMUM
FIRE CHECK
VALVE-
FLOW
-
....
L MAX PIPE LENGTH
FIRE CHECK VALVE SENSOR
FILTER
\
JETSTREME 4 +
Fig. 1
TABLE
GIVING MAXIMUM PIPE LENGTH 'L'
I
I
r,
"ETRES
05
LO
1.5
2.0
MAXIMU
L
METRES
M
PIPE lOmrnOD
PIPE 12mmOD
10
20
20 40
40 80
60
100
Table 3
6
Two Pipe System
Where
it
is
not
possible to install a gravity oil
supply
system
then a two
pipe
pumped
system
must
be
installed. The oil
in
this
arrangement
is
drawn
from the
tank
by
the
pump
on
the burner,
and any
excess is
returned
via
the
second
pipe
to
the
tank
If a
two
pipe
system
is to
be
fitted,
the
pump
on
the
burner
will require to
be
modified from
that
supplied
(See Burner Manual).
The
diagrammatic
layout
of
the
pipe
work
for a
two
pipe
system is
shown
below. Where
the
tank is
below
the level of
the
oil
pump
the
two
pipes
should
each
be
the
same
length
into
the
oil. If
the
return
pipe
is shorter
than
the
flow,
then
it will
be
necessary to fit a
spring
loaded
non-return
valve to this pipe.
On a two
pipe
system
the
pump
vacuum
should
not
exceed 0.4
bar
(30cm Hg). If this is
not
observed
then
dissolved gas will
be
released from
the
oil resulting
in
oil starvation
to
the
burner
and
repeated boiler 'lockouts'.
A filter
of
the
metal
bowl
type
with
a micronic filter
should
be
installed
in
the oil
return
pipe. If
this
pipe
should
become blocked it
may
cause
the
pump
to fail.
The installer MUST
supply
and
fit a fire check valve
in
the
oil
supply
line,
and
this valve
must
comply
with
BS
799:
part
5:
1977 Specification for Oil Storage Tanks.
The
pipe
size requirement is given
in
the
table below.
TWO PIPE OIL SYSTEM - TANK OUTLET BELOW BURNER
JETSTREME
4 +
FIRE
CHECK
VALVE
SENSOR
VENT
.-------------;;::::~~F=F::r::F1
'.::t:J[j.Lf-jf-----
RETURN
PORT
A
NON
RETURN
RETURN
PIPE
FILL
SLUDGE
COC~K~~~~~~~~~~~~L-~
FL
OW ----Il1o-
FILTER
VALVE
Fig. 2
20
mm
PER
METRE
FALL
--
RE1\.lRN
TABLE GIVING MAXIMUM SUCTION PIPE LENGTH
'L'
HMETRES 0
0.5 1.0 1.5 2.0
3.0 3.5
MAXIMUM
L
PIPEI0mmOD
35
30
25
20 15 8 6
METRES
PIPE
12mmOD
100 100 100
90
70
30 20
Table 4
7
TWO PIPE OIL
SYSTEM
- TANK OUTLET ABOVE BURNER
RETURN PIPE
VENT
FILL
SLUDGE
COC~KxH~~~~~~~~~~~
____________
FLOW
--
20 mm PER METRE FALL
--
RETURN
r-
JETSTREME 4 +
H
FIRE CHECK VALVE SENSOR
LJ
'lJ~I---
RETURN PORT
1-t;4.~*=;;;;;;;;;;~~
NON RETURN
LMAX
FILTER
VALVE
Fig. 3
FIRE CHECK VALVE
TABLE
GIVING MAXIMUM SUCTION PIPE LENGTH 'L'
HMETRES
0
0.5
1.0
15
2.0
3.0
35
MAXIMUM
L
PIPE10mmOD
35 30 25 20
15
8 6
METRES
PIPE 12mmOD 100 100
100
90
70
30 20
Table 5
Note:-
In all cases the tank should be positioned so that it slopes
away
from the outlet
by
20mm
per
metre
of
length
of
tank
(1/4
inch
per
foot length). This is to
ensure
that
any
impurities
do
not
contaminate the oil
supply
feed. The customer should be
shown
how
to remove these impurities
from time to time,
or
this should
be
carried
out
at
its service
or
maintenance check.
Connections
on
the oil
supply
pipe
should
be
made
using compression fittings where possible.
Galvanised
pipe
or
fittings MUST
NOT
be
used.
Always
check
sealing
compounds
for
their
suitability for
use
in conjunction
with
oil.
8
Air Supply
Conventional Flue
For a conventional flue boiler, air is required, not only for combustion,
but
also for ventilation,
and where the boiler is located in a compartment
or
cupboard additional ventilation is required.
The
volume
of
air required is 550mm
2
jkW
of
boiler output. The requirements for the Jetstreme
4+
range
of
boilers are given below.
information
supplied
by:
A
OPEN FLUE OPEN FLUE
BOILER IN ROOM
BOILER COMPARTMENT
VENTILATED FROM OUTSIDE
OPEN FLUE
BOILER COMPARTMENT
VENTILATED FROM ROOM
Fig. 4
Model
40/52
~
70/90 95/120
125/140
Boiler
in
a ventilation
In
83.6cm
2
112.8cm
2
I 45.2cm
2
I 93.6cm
2
226.6cm
2
room
Out
Nil Nil Nil Nil Nil
Boiler in a
compartment
ventilation In
Out
16.72cm
2
83.6cm
2
225.6cm2
112.8cm
2
290
Acm
2
I 45.2cm
2
387.2cm
2
I 93.6cm
2
453.2cm
2
226.6cm
2
Boiler in a vent to In
83.6cm
2
112.8cm
2
I 45.2cm
2
I 93.6cm
2
226.6cm
2
compartment room
Out
Nil Nil Nil Nil
Nil
in a room vent to In 250.8cm
2
338Acm
2
435.6cm2
580.8cm2
679.8cm2
compo
Out
I
67.2cm2
225.6cm
2
290Acm
2
387.2cm
2
453.2cm
2
Table 6
Extraction Fan- Conventional Flued Boiler only.
If
an
extraction fan is fitted either into the room
or
an
adjacent room, to where the boiler is fitted,
it
MUST NOT have
any
effect
on
the flue pull of
the boiler.
If
the extractor fan DOES have a detrimental effect
on
the boiler,
then
extra ventilation
must
be
introduced into the boiler room
or
to the room adjacent to where the boiler is installed.
9
INSTALLATION INSTRUCTIONS
Electrical Supply
Warnings:- This appliance must
be
earthed.
All wiring
and
electrical
work
must
be carried
out
by
a competent electrician working to
the
current
lEE Regulations.
The electric
supply
must
be
made
via a fused
double
pole isolation switch
with
at least
3mm
between
the
contacts. The fuse rating is 6 amp.
All conductors
must
have
a cross sectional area of
O.75mm2
or
greater.
Electrical circuit
diagrams
are
provided
later
in
this
manual
(see pages 15-17).
Conventional Flue
Carefully remove
the
packing from
around
the boiler.
Fit
the
water
flow
and
return
fittings into
the
required positions
on
the
boiler.
If
only
one
flow
and
one
return
connection is required
then
they should preferably be positioned
on
opposite sides
of
the
boiler. Place
the
boiler
in
the
required installation position
and
remove
the
top
panel,
by
lifting it
upward,
and
the
lower front panel,
by
pulling it forward. Place the top
and
front panels
safely
to
one
side so
that
they will
not
be
damaged.
Locate
the
first section of the flue into
the
flue spigot
and
seal the area between
the
flue
and
the
boiler spigot
with
ceramic rope
and
fire cement. Brackets
should
be
fitted
to
help
support
the flue
as it is being built.
It
is recommended
that
the
boiler
be
covered to prevent
masonry
falling into the
boiler
when
making
a hole
in
the
wall
or
ceiling.
If
the flue is to pass
through
an
existing brick chimney, a stainless steel flue liner
should
be
used
and
the cavity
between
the liner
and
the brickwork
should
be insulated
with
vermiculite
or
similar.
The first section(s) from the boiler
to
within the brick chimney
should
be
of twin wall flue pipe.
On
completion
of
the
flue installation
make
good
any
area
where
the
flue passes
through
the
wall
or
ceiling.
Replace
the
cover
and
refit the screw
and
serrated washer.
Complete
the
pipework
to
the
boiler.
Connect
the
oil
supply
line
and
terminate
within
450mm
(18
inches) of
the
oil
pump
on
the
burner. From this point fit the flexible hose supplied to
the
burner
connection (in the case of a
two
pipe
system
the
installer will
have
to
supply
the second hose).
The installer
should
fit a fire check valve
with
a fusible link located above the burner.
Insert
the
electrical four
pin
plug
on
the
end
of
the
fly lead from
the
burner
into
the
socket
located
on
the
underside
of
the control panel.
Refit
the
top
and
front panels,
by
placing
the
panels
in
position
and
then
pressing to lock
them
into the clips.
10
Balanced flue
Before starting the installation, check
that
the
proposed
position of the balanced flue terminal
on
the
outer
wall conforms
with
the requirements of fig
5.
A Below a
gutter
or
sanitary
pipework
B Horizontal from opening, airbrick,
window
etc.
C Above
ground
or
balcony level
D Below eaves
or
balcony
E From
an
internal
or
external corner
F From a terminal facing a terminal
Fig. 5
G From a surface facing the terminal
H Vertical from terminals
on
the same wall
I Horizontal from terminals
on
the
same
wall
J Below
an
opening, airbrick,
window
etc.
K From vertical sanitary
pipework
A B
C
D E F
'G
H I
J
K
Building Regulations
England
and
Wales 1990
-
600
- -
600 -
- -
- 600
-
Scotland 1990 Balanced * 600
-
600 600 600 600 600
600 600 600
600
Low Level*
1000
-
600
1000
600
600 600 1500
600 600
1000
Northern
Ireland 1990
-
600
- -
600
-
- -
- 600
-
British
Standard
BS
5410 Part 1 1977 600 600
600
600 600 - -
- -
600 700
Table 7
*Where the terminal is
within
1 metre of
any
plastic material, such material
should
be
protected from the
effects of combustion products of the fuel.
There are additional general requirements
in
most
Regulations
and
Standards
that
the flue
must
be
~
positioned so
that
it
does
not
cause a nuisance
and
permits the dispersal of combustion products. ®
CCl!F1T"Ili<C
11
Balanced Flue
Carefully remove the packing from
around
the boiler.
Fit the water flow
and
return fittings into the required positions
on
the boiler.
If
only one flow
and
one return connection is required, then they should preferably
be
positioned on opposite sides of the boiler.
Place
the
boiler
in
the
required installation position
and
remove
the
top
panel,
by
lifting
it
upward,
and
the
lower front panel
by
pulling it forward. Place the
top
and
front panels safely to
one
side so
that
they will not
be
damaged.
Mark the position of
the
flue duct
and
then remove
the
boiler. Check the position for
the
duct
(see fig 6),
and
cut a hole
through
the walL Check
on
completion that the
duct
passes through the
hole
in
the wall, ensuring
that
there is
at
least a 70mm projection.
Fig. 6
Replace the boiler into position
and
remove
the
4 screws located
in
the balanced flue outlet
on
the boiler.
Remove
the
access plate from
the
end
of the balanced flue duct,
and
locate the duct over the
four fixing holes
on
the outlet
of
the boiler. Ensure
that
the gasket is correctly fitted between the
two
faces.
The
spigot should
then
be placed in position, face
down
again
with
a gasket in place.
The four fasteners should
be
tightened,
and
the exhaust tube slid into the duct
and
inserted into
the spigot. Joints should then
be
sealed
with
fire cement prior to fitting the access cover.
The
wind
cowl should
then
be
fitted over the
end
of the duct, ensuring the
gap
between
the
dish
and
the extension tube
on
the exhaust is not more
than
40 mm.
Locate
the
terminal
guard
basket over the
wind
cowl
and
mark
the four fixing points. Drill
and
plug, and fix into position.
Unscrew
the
cover to the electrical control panel
and
then connect the mains
input
(and
any
additional wiring) passing the wires through the cable clamp (see figs 7-13).
On
completion replace
the
cover
and
refit
the
screw
and
serrated washer.
FIT
THE
BALANCED
FLUE
AIR
SUPPLY
PIPE
TO
THE
SPIGOT
ON
THE
BALANCED
FLUE
TERMINAL
DUCT
AND ro
THE
INLET
OF
THE
BURNER.
SECURE
WITH
THE
JUBILEE
CLIPS
PROVIDED. Complete the pipework to the boiler. Connect
the
oil
supply
line
and
terminate within 450mm (18 inches) of
the
oil
pump
on
the
12
burner. From this point fit the flexible hose supplied to
the
burner
connection (in the case of a two
pipe
system the installer will have to
supply
the second hose).
The installer should fit a fire check valve
with
a fusible link located above the burner.
Insert
the
electrical four
pin
plug
on
the
end
of
the fly lead from
the
burner
into the socket
on
the
underside
of
the
control panel.
Refit
the
top
and
front panels,
by
placing
them
in
position
and
then
pressing to lock
them
into
the clips.
Programmer
This is
an
optional extra which can be fitted either
when
the
boiler is purchased,
or
at a later
stage. See
page
26 for further information.
COMMISSIONING
Combustion - The responsibilities of
the
commissioning engineer are clearly stated
in
British
Standard 5410
part
1:
1971
and
these responsibilities
must
be
adhered
to.
It
is important that the boiler is commissioned
by
a competent engineer
with
an
understanding
of
the technology
and
with
the
equipment suitable to enable
him
to carry
out
the tests to set the
appliance
at
its
optimum
efficiency
and
with
clean combustion.
It
is strongly recommended
that
an
OFTEC (Oil Firing Technical Association for the Petroleum
Industry) registered engineer is
used
for this purpose. If difficulty is found locating
an
engineer
then
contact can
be
made
through OFTEC
on
telephone
number
01737-373311.
Electrical - Checks for electrical safety should be carried
out
by a competent electrician
with
a
working knowledge of
the
current
IEE
Regulations.
Fuel - Bleed all the air from
the
oil
supply
line to ensure
an
uninterrupted
supply
of
oil to the
burner. This can
be
achieved
on
gravity systems
by
loosening the suction line connection.
It
is
essential
that
any
oil spillage is contained
and
the area
be
cleane~
on
completion.
On a two
pipe
system purging can
be
carried
out
by
running
the oil
burner
and
resetting after lockout.
Water - Ensure that the system is full of water
and
that all air is bled from the radiators
and
boiler. After firing
and
checking that the system is free of water leaks
and
is working satisfactorily
it
is
recommended
that a suitable
anti-corrosion
additive
is
introduced
into
the
system
(e.g.
Fernox). This is
done
by partly draining
down
the system,
putting
in
the additive
and
then
topping
up
with fresh water.
13
First Firing
1.
Ensure
that
the Boiler thermostat
and
the limit thermostat phials are located in their respective
phial pockets
and
are fully home.
2.
Turn
ON
any
isolating taps in the oil
supply
line.
3.
Switch
ON
the
mains electricity isolating switch.
4.
Set
the
programmer
I time clock,
if
fitted, to
an
'ON'
position for
both
CH
and
HW.
5.
Set the
room
thermostat to its
maximum
position.
6.
Set the cylinder thermostat to its
maximum
position.
7.
Turn boiler thermostat to its
maximum
position. -
At
this point
the
burner
will start to
run
and
a
series of clicks will
be
heard as the ignitor attempts to fire the oil.
If
the oil fires satisfactorily the
burner
noise will be heard.
If
the oil fails to ignite, the
burner
will
go
to lockout mode. A red
light will
show
on
the
control panel
to
indicate lockout.
Turn
the
boiler thermostat
on
the control
panel
to the OFF position
and
wait 30 seconds.
Press the
manual
reset
button
on
the burner,
if
the lockout is reset then this
button
will remain
in,
and
the
lockout light will extinguish.
Again
turn
the
thermostat
to
its
maximum
position
to
repeat
the
ignition
sequence.
This
sometimes has to
be
repeated
several times before getting ignition, particularly
with
two
pipe
systems.
Once
the
flame has been established allow
the
burner
to continue to
run
for approximately
10
minutes
before
turning
off the boiler thermostat,
and
inspecting for water
or
oil leaks.
It
may
also
be
necessary to again bleed the system. Once satisfied that the system is again sealed, remove
the
combustion test point screw from
the
flue spigot
and
insert the sample probe of the test equipment. Turn
on
the
boiler thermostat,
and
carry
out
the combustion tests, referring to
the
information given
in
the
appropriate
tables (see
tables 8-10). All
burners
used
on
the Jetstreme 4+ are factory set
at
a pressure of approximately
20
p.s.i. below
that
required for
maximum
rated output. The oil pressure
and
the
combustion level
must
be
verified
by
on
site testing,
and
adjustments
made
where necessary. Information regarding
the
methods
of
burner
adjustments are explained in the
burner
technical booklet
supplied
with
these instructions.
IMPORTANT
To
ensure that the appliance is covered
by
the 2 year guarantee
the
installation
details
section
of
these
instructions
and
the
warranty card should
be
completed. The warranty card must
be
returned to
Benson
Heating
within
the registration period
of
28 days.
This
does
not affect the statutory rights
of
the purchaser.
14
-
--
-
--
-
--
STANDARD WIRING DIAGRAMS
Internal Wiring Diagram:
THERMOSTAT
THERMOSTAT
CONTROL
PANEL
i
I
I
I
BURNER
ON
I
BLACK
I
LOCKOUT
I
I
I
I
I
I
0------
----~
~J;~;--
-,
I
;'ov
At SlA'I. Y
,I
I I
I
1~ll.rf/~fH
'I'-l-=i-
I I
I PlMR
'ON'
INDICATIIR
L<t...9--U
1
i i
~
I
_____
L_~~
BURNER
Fig. 7
~;s;-
:--
-
--
-
--
-----,
EARTH
BIlILER
LIMn
I
External Wiring Diagram:
ROOM
T/STAT
0000
000
Ll
N2
[3
4 5 6 7 a 9
10
JETSTREHE
CONTROL
PANEL
PUMP
ON/orF
FROM
ROOM
THERMOSTAT
Fig. 8
15
PROGRAMMER WIRING DIAGRAMS
Internal Wiring Diagram:
,
---------------------l
RAM
CHASSIS~'
PROG
I£R
EARTH
BmLER
LIMIT
CONTROL
PANEL
PIIVtR
'ON'
INDICIITlR
!.2..£...JJ
'
l
~
i
BURNER
____
L
:~
L
l
zzz
~~~
""X
'"
"'
.....
THERMOSTAT
H£RKlSTAT
~---+-H~----4--.
r-:
----
fXlIBMN
ylRHa
fUS£
SA
241111
K;
SU'PI.
Y
I I
I
I~&r~tt
!"'j...:l
I I
LOCKOUT
Fig.
10
External Wiring Diagrams:
RO!lH
THERH!lSTAT
000
0
LI
N2
E3 4 :)
6 7 8 9
]0
JETSTREME
CONTROL
PANEL
Fig.
11
GRA
VIlY
HOT
WATER
AND
PUMPED
CENTRAL
HEATING
16
External Wiring Continued:
FULLY
PUMPED
SYSTEM
WITH
ZONE
VAL
YES
ZIK
WLVE
ZIJNE
VALVE
H.I.',
CYlINDER
Cll.
ROOM
C.H.
Ill.',
THERMOSTAT
THERMOSTAT
pii;;71
'---I
~t--llJ'
£~r--lli'
it«:,I"""'lE
i[
.~
~.~,'l"-++-I-+'
L::.
--\,4
L'
-
--
.
~.
I I
6 C 6 6
6834523
3
10
1 5 2 3
10
1 8 2
JUNCTION
BOX
1 2 3
10
...
6
3]
5
~
r
.---..-
--,
!~
- !
: [
••••
J :
;.......
:
I :
:
IPTlrtlAL
;
-------H--
--
~
- _
__
~=:.__==
___
!!~J"."'!;
000
UN2E345678910
JETSTREME
CONTROL
PANEL
Fig. 12
FULLY
PUMPED
SYSTEM
WITH
MID
POSmON
DIVERTER
VAL
YES
MID
POSITION
KII.
CYLINOCR
C.H.
ROIJ4
DlVERTER
VALVE
THERMOSTAT
THERMOSTAT
r------l
r;i.---~
'---I
A;j-'I---
-J
310852
~~
~
~~
L
___
~.
I
6
]0
6 5 3 4 8 2 3
JUNCTION
BOX
1 2 3
9
PUMP
~
10
4 6 5 3 I 8
~
o 0 (
u
~O
4 5 6 7 8 9 W
JETSTREME
CONTROL
PAI£L
EXTERNAl
IIIRING
Fig.
13
17
I
TECHNICAL SPECIFICATION - KEROSENE (CONVENTIONAL FLUE)
.....
(lQ
Table
8
MODEL
40/52 50/70 70/90
951120
1251140.
OUTPUT
KW
14.3
20.37
26.4 36.0 39.7
Btu/hr
48,800 69,500 90,000 122,700
135,300
BURNER
E.O.G.B. 40
40
50 50 50
Sterling
(Eng 108)
(Eng 108) (Eng 120)
(Eng 120)
(Eng 120)
HEAD
Distance
from
SETTING
front
of
Blast
Tube
to
Nozzle
43mm
43mm
43mm
43mm
43mm
BLAST TUBE PL 10-5-16-8 10-5-16-8 6-7-19-10
1 0-8-6-19-10 1 0-8-1 0-6-19-1 0
_
.....
NOZZLE
Danfoss
0.4580'S
0.6080'H 0.8580'H
1.0 60'S 1.10 60'S
OIL
Bar
7.6 7.6
7.6
9.3
9.3
PRESSURE P.S.!. 110 110 110 135 135
.....
\
,
,
._.
;
AIR
SETTING
2.5 16
11
14 16.5
SMOKE
No.
0
0 0 0
0
NET
FLUE
GAS
TEMP
°C 149
197 234
189
196
CO2
% 12.5
12.4
12.5 12.5
12.5
c
....
FUEL
Llhr
1.73 2.45
3.41
4.31
4.68
CONS
Kg/hr
1.35
1.92
2.65 3.36
3.65
g/hr
0.38
0.54
0.75
0.95
1.03
------- -------
WATERFLOW RATE
glhr
300 350
345
500
520
TECHNICAL SPECIFICATION - KEROSENE (BALANCED FLUE)
......
1.0
MODEL
40/52
50/70 70/90 95/120 125/140
OUTPUT
KW Btuthr
14.7 50,200
19.93 68,000
26.0 88,700
34.6 118,100
41.0 130,000
BURNER
E.O.G.B. Sterling
40 (Eng 108)
40 (Eng 108)
50
(Eng 120)
50
(Eng 120)
50 (Eng 120)
HEAD SETTING
Distance
from
front
of
Blast
Tube
to
Nozzle
43mm
43mm
43mm
43mm
43mm
BLAST
TUBE PL 10-5-16-8 10-5-16-8 6-7-19-10 10-8-6-19-10
10-8-10-6-19-10
NOZZLE
OIL PRESSURE
Danfoss
Bar P.S.I.
0.4580"5
7.6 110
0.6080
o
H
7.6 110
0.85800 H
7.6 110
1.060°5
9.3 135
1.1060"5
9.3 135
AIR
SETTING
5 18 15
17
26
SMOKE
No.
0 0 0 0 0
NET
FLUE
GAS
TEMP
CO2
°C
%
167 222
212
201
217
12.6 12.6
12.4 12.5 12.6
FUEL CONS
Lthr Kglhr glhr
..
1.73
1.35
0.38
2.45
1.93
0.54
3.54
2.76
0.78
4.31
3.36
0.95
4.77
3.71
1.05
WATERFLOW RATE
g/hr
300 320
340 500 520
Table 9
TECHNICAL SPECIFICATION -
GAS
OIL (CONVENTIONAL
FLUE
ONLY)
t:5
MODEL
40/52
50/70 70/90 95/120 125/140
OUTPUT
KW Btuihr
15.1
51,600
19.05
65,000
25.5 87,000
34.9 119,000
39.3 134,000
BURNER
E.O.G.B.
Sterling
40
(Eng 108)
40
(Eng 108)
50
(Eng 120)
50
(Eng 120)
50
(Eng 120)
HEAD SETTING
Distance
from
front
of
Blast
Tube
to
Nozzle
43mm
43mm
43mm 43mm 43mm
BLAST
TUBE PL
10-5-16-8 10-5-16-8 6-7-19-10 10-8-6-19-10 10-8-10-6-19-10
NOZZLE
OIL PRESSURE
Danfoss
Bar P.S.I.
0.40800 H
10.4 150
0.5080
0
H
10.4 150
0.6060°5
11.0 160
0.7560°5
11.7 170
0.8560°5
11.7 170
AIR
SETTING
3.5
10.5
11.5 13.5 19.5
SMOKE
No.
0 1
0
0/1
1
NET FLUE GAS
TEMP
°C 219 243 208 192
208
CO2
%
12.5 12.5 12.5 12.4 12.5
FUEL CONS
Llhr Kg/hr g/hr
1.73
1.45
0.38
2.18
1.83
0.48
3.00
2.50
0.66
3.90
3.23
0.86
4.50
3.75
0.99
WATERFLOW RATE
g/hr
270 320
420 500 540
Table 10
.A'-T--l'--"
ALL FLANGES TO THE TOP
BAFFLE CUTAWAY
SERVICING
AND
MAINTENANCE
INSTRUCTIONS
Notes
on
Servicing
The boiler
should
be serviced annually
by
a competent engineer. Failure to observe
the
correct
procedures could result
in a danger
to
the
user.
The cleaning
should
be
such that all residue is removed from both
the
interior
and
exterior of
the
boiler.
On
completion
of
the
interior
cleaning
the
baffles MUST
be
fitted as
per
fig
14.
If
they
are
assembled in
an
incorrect
manner
damage
may
occur
and
the
warranty
may
be
invalidated.
UPPER BAFFLE
MID BAFFLE
---/
LOWER BAFFLE
BAFFLE CONFIGURATION Fig. 14
FRONT
OF
BOILER
All
damaged
components
should
be replaced
or
made
good.
The
burner
should
be checked
and
cleaned.
The room sealing
of
the
Balanced Flue appliance MUST be maintained.
The
Burner
settings
should
be
checked
against
those
in
the
Technical Specifications in this
manual
(see figs. 8-10)
and
be
adjusted,
if
necessary,
so
that it is operating
at
its
optimum
efficiency
and
with clean combustion.
It
is recommended that the flexible oil
pipes
to the
burner
are replaced every
two
years.
21
FAULT
FINDING
Burner Fails to Start
If
the
burner
has failed to operate check the following:-
1.
Ensure that the mains
supply
switch is ON.
2.
The thermostats are
turned
to the required setting. For test purposes only,
turn
the thermostats
to their
maximum
setting. But remember to reset them later.
3.
Is the
Timer/Programmer
set to
an
On
period?
4.
Check
that
the Reset Button
on
the
burner
control box is not illuminated.
5.
Check
that
the Limit Thermostat
on
the
underside
of
the facia is fully in.
6.
Again start the ignition procedure.
Burner
goes
to Lockout
1.
Remove the lower front panel.
2.
On
the
burner
control box a
glowing
red
button
will
be
noticed. This is
the
Lockout Reset
Button.
3.
Turn the boiler thermostat to the OFF position.
4.
Press
the
Lockout Reset Button fully home.
5.
Release the Lockout Reset Button. The light will
go
out
and
should remain so.
6.
Turn the boiler thermostat to the required setting. The ignition cycle should then automatically commence.
If
the appliance is still failing, check the following:-
a. Oil
supply
- Ensure that there is
an
adequate
supply
of
oil in the Tank.
That the
supply
valves have not been
turned
off.
That the fire check valve has
not
operated.
Was
the
storage
tank
allowed
to
run
dry
before
being
refilled
thereby
creating air in the
supply
pipe.
Check fuel
grade
to match
burner
is correct.
Check for correct oil pressure (See Technical Specification).
b. Air lock
If
a one
pipe
system, Bleed
supply
pipe
at
the boiler.
If
a
two
pipe system continue to rectify lockout until air lock is cleared.
c.
Blocked Nozzle Clean
or
replace
with
new
nozzle as
per
the
manufacturer's
instructions.
(See Burner Manual).
d.
No
Spark Check
spark
gap. (See Burner Manual). Check Burner Control Box Spark output. (See Burner Manual). Replace as necessary.
22
USER INSTRUCTIONS Warning
Before carrying
out
any
work
on
the
appliance it MUST
be
isolated from
the
mains electrical
supply.
DO
NOT
adjust in
any
way
the
setting of
the
oil
burner
or
its controls. This type
of
work
must
only
be
carried
out
by
a competent engineer.
Should
an
oil spillage
or
leak occur it MUST
be
rectified immediately. Oil
must
not
be
allowed
to
soak into
the
ground
where
it can pollute
ground
water
and
water
courses. Contact
your
oil
supply
company
or
engineer.
Located
on
the
front of
the
boiler
and
directly
behind
the
front
panel
is a flame viewing point.
To
view
the
flame
the
blanking cap
must
be
removed
but
in doing
so
exercise caution
as
it
may
be
very
hot ifthe
boiler has been operating.
Only
view
the
flame from a safe distance.
This appliance as
with
all similar appliances
should
be
serviced
at
least annually
to
maintain
the
efficiency
and
clean combustion
of
the
boiler. Failure to
do
so
could severely reduce
the
life of
the
boiler.
It
is
recommended
that
servicing
should
take
place
prior
to
the
summer
shut
down
to
minimise corrosion
during
the
summer
months.
Lighting Instructions
Ensure that:-
1. All oil
taps
and
valves are open.
2.
An
adequate
supply
is
in
the oil storage tank.
3.
Mains isolation switch is ON.
4.
Room thermostat is set
at
the
required setting.
5.
Cylinder thermostat is set
at
the
required setting.
6.
TimerI Programmer is set at
an
ON
period for Central Heating
and
Hot
Water.
7.
Turn
the
boiler thermostat to its
maximum
setting.
The boiler
should
now
commence its ignition cycle.
a. Fan
motor
runs.
b. After approximately 5 seconds
the
oil solenoid valve
opens
and
oil is
sprayed
from
the
burner
nozzle into
the
combustion chamber.
c.
Immediately oil is
sprayed
from
the
nozzle, ignition takes place.
If
ignition
is
satisfactory
allow
the
boiler
to
continue
with
its
operating
sequence
being
controlled
by
the
thermostats
and
the
time
controller.
The
GREEN
NEON
will
illuminate
to
indicate
that
the
boiler is
operating
and
that
the
burner
is being fired.
During
the
burner
OFF
periods
within
the
operating
cycle
the
GREEN
NEON
will
be
extinguished.
If
igniti()n fails
the
burner
will go
to
lockout. This is indicated
by
the illumination of
the
RED
NEON
on
the
control
panel. Follow
the
instructions for 'Lockout Reset',
shown
on
page
25.
Under
normal
running
conditions the boiler will automatically operate daily
to
the
programme
set
and
without
further adjustments.
For adjustment of
the
programmer, iffitted, (see pages 24,
26
and
27).
23
The Control Panel and its Components
CONTROL PANEL (COVER OMITTED FOR CLARITY)
I I
OF~
10FF
g~~~~~~~
ON,-,
__
--''ON
ii.
1iI,-
AnI/
SET'
.....
I I
.aD.
SElECT
YES
GREEN NEON
RED NEON
PROGRAMMER LIMIT THERMOSTAT /
BOILER THERMOSTAT
Fig. 15
Programmer
- This is
an
optional extra - The
programmer
is of a compact
advanced
design
that
can be
programmed
to
vary
the
ON/OFF
periods
for the
Hot
Water
and
Central
Heating
independently
of
each
other
on
fully
pumped
systems,
but
on
gravity
hot
water
with
pumped
central heating, the central heating times
work
in
conjunction
with
the
hot
water
times. The operating times for
Saturday
and
Sunday
can be set to different times to those
of
the
weekdays.
To
set
the
programmer
refer
to
the
programmer
section
of
these
instructions (pages 26-29).
Boiler
Thermostat
- This
controls
the
temperature
of
the
water
leaving
the
boiler
to
be
circu.lated
around
the system. The boiler
must
not
be
run
for-
long
periods
with
the boiler
thermostat
set
at
the
low
end
of
the
range.
This
creates
condensation
within
the
combustion
chamber
which
over
time
will
damage
the
interior
surface.
For
the
most
efficient
use
of
the
system
the
boiler
thermostat
should
be
set
at
the
higher
end
of
the
range. Radiators are designed for flows of approximately 80°C
with
an 11°C differential to
the return.
Limit
Thermostat
- This is a safety device
that
switches off the boiler
in
the case of a failure
in
the boiler thermostat. This
can
be reset
by
pressing
in
the
button
located
on
the
underside
of
the
control
panel
upwards
where
it
should
be
retained.
Should
this limit
thermostat
repeatedly operate
then
you
should
consult
your
engineer.
Green
Neon
- This only illuminates
when
the Burner is
in
its
operating
mode.
Red
Neon
- This is only illuminated
when a burner
fault develops
and
the
lockout procedure
occurs. (Also the lockout
button
on
the
burner
control box will illuminate)
both
lights will
remain
on
until
the
burner
is reset
or
mains electricity to the appliance is disconnected.
24
Lockout
The Lockout condition is a built
in
safety device which comes into operation
when
the
burner
controls suspect
or
register
that
a fault
has
developed
that
could cause
damage
to the burner. Several things can create this situation such as:­Oil tank allowed to
run
out
of fuel.
The valves
in
the oil line have been turned off. The fire check valve has operated. Air
in
the
supply
pipe;
usually
caused
by
allowing the
tank
to
run
dry,
then
on
refilling
not
bleeding the air from the
supply
pipe. Wrong grade of fuel supplied. Water contamination of the oil tank, this
is
quite common where the inspection doors
or
vent caps etc. have been left open. Faulty
or
contaminated filter causing blockage to the
burner
nozzle.
No
ignition at the
burner
nozzle
due
to
burner
fault.
In
most cases it is recommended that a qualified service engineer is employed
to
correct the
fault.
Lockout Reset
If
the boiler goes to lockout condition, this is indicated
by
the illumination of the
RED
NEON
on
the control panel.
To
reset the
burner
the following procedure should be followed:-
1.
Remove the lower front panel.
2.
On
the
burner
control box a glowing
red
button
will
be
noticed. This is the Lockout Reset
Button.
3.
Turn the boiler thermostat to the OFF position.
4.
Press the Lockout Reset Button fully horne.
5.
Release the Lockout Reset Button. The light will go
out
and
should remain so.
6.
Turn the boiler thermostat to the required setting. The ignition .cycle should then automatically
commence.
7.
If
Lockout continues to re-occur
then
a competent engineer should be consulted. Do
not
attempt
to adjust the
burner
or
its controls.
Note:
If
the oil storage tank has been allowed
to
become
empty
then air
may
be present
in
the
supply
pipe. The oil
supply
pipe
will require either 'bleeding' ifit is a
one
pipe system
or
the
continued resetting of the lockout to clear the air
on a two
pipe system.
It
is always useful to
consult
your
installer as to which system is fitted.
25
••
Failure
of
Burner
to
Operate
If
the
burner
has failed to operate, check
the
following:-
1.
Ensure
that
the
mains
supply
switch is ON.
2.
The thermostats are
turned
to
the
required setting. For test
purposes
only
turn
the
thermostats
to
their
maximum
setting. But
remember
to reset
them
later.
3. Is
the
Timer
/Programmer
set to
an
On
period?
4.
Check
the
Reset Button
on
the
Burner control
box
is
not
illuminated.
5. Check
that
the
Limit Thermostat
on
the
underside
of
the
facia is fully in.
6.
Again
start
the
ignition sequence.
If
the
appliance
continues
to
fail to ignite consult
your
service engineer.
Cleaning
the
Case
The
case
may
be
cleaned
by
using a mild
soap
solution
or a propriety
cream
cleanser
on
a
damp
soft
cloth.
DO
NOT
USE
an
abrasive
cleaner
or
scouring
pads.
Servicing
Servicing
should
be
carried
out
by a competent
Engineer
who
is
OFTEC
registered
or
is
registered
under
one
of
the
oil
companies
maintenance
schemes.
Programmer
OFF I OFF
TIMED TIMED
ONCE
ONCE
ON
ON
'-----------'
-H.W.
C.W.-
ADV SET?
ADV
Fig. 16
The
programmer
is located
behind
the
hinged
cover
on
the
facia panel, adjacent to
the
boiler
thermostat
contol knob.
On
fully
pumped
systems
the
programmer
will allow
the
hot
water
and
central
heating
to
work
independently
of
each other, ifrequired. However,
on
systems
with
gravity
hot
water
and
pumped
central heating,
the
hot
water
shares
the
central heating
programme.
The
programmer
can
be
set
to
allow
for
different
times
on
week
days
and
weekends,
pre-set
programmes
are protected
in
the
event
of a
power
failure
by
a rechargeable
battery
back-up.
On
a
fuHy
pumped
system
it is possible to
have
four
'On'
settings
(2
for centra] heating
and
2 for
hot
water)
and
four
'Off'
settings
per
day.
Programmes
can
be
advanced
using
the
'On'
facility
to
override
what
would
otherwise
be
an
'Off' period.
26
During installation,
and
before commissioning, the presence of the blue tag connector
on
the
back of the
programmer
must
be
checked
and
matched to the requirements of the system, i.e. left
in place for a
pumped
central heating
with
gravity hot water, or, in the case of a fully
pumped
system, removed (See fig. 17).
VIEW OF REAR OF PROGRAMMER TO SHOW
TAG
_
........
MPS2211)4
.-
by
APPI.IANCE
COMPONENTS
~ED
VOLTAGE 220 250 v-50
Hz
MAlOMUIIII.OAD 2 (1) A TOTAL
0
REART55
_T54
~
"51
Z
!ii1l
llI:
..
"0
..
z
"'z
:E
:E
'"
rn
'"
£:
z
m
"'z
/I)
!;j
"'"'
i
.,
~
i
.,
i!
.,
Ii
~
~!l
rn
r
rni!!
0
0
:E
~
lll.,
!
i i
~
r
I~
I
~pl
~
~-
~
........
~-~
~
IJ
~
IJ_
c~
Fig. 17
Set the Clock
a. Switch
on
the mains
supply
to the boiler.
b. Press
& release the
button
marked
SET.
The question
SET
CLOCK? will
appear
in
the display.
Press
& release the button marked
YES.
c.
The
day
section of the display will flash.
Using the
+
or
- buttons set the correct day.
Press
& release
SET.
d. The
hour
section will flash.
Using the
+
or
- buttons set the correct hour. Note the
am
or pm.
Press
& release
SET.
e.
The minute section will flash. Using the
+ or - set the correct minute.
Press
& release
SET.
f.
The question
SET
PROG? will
be
displayed. Either Press
& release
SET
to display the time of
day
that
has been set. or Press & release
YES
if
a change to the standard programme is required.
27
Standard Programmer Times.
The
programmer
is supplied
ready
set to a
standard
programme
of times
as
listed
in
the table
below.
IT
different times to the
standard
settings are required then these can be changed. This is
done
by
following
the
question
and
answer instructions
in
the
paragraph
'Setting the Programme times'.
Programme
Monday-Friday
Saturday & Sunday
HW
iCH
HW
CH
ONt
Start
of
first
ON
period
6.30
am
6.30
am
7.00
am
7.00
am
OFFt
End
of first
ON
period
8.30
am
8.30
am
9.00
am
9.00
am
ON2
Start of Second
ON
period
4.30
pm
4.30
pm
4.00
pm
4.00
pm
OFF 2 End of Second
ON
period
10.30
pm
10.30
pm
11.00
pm
i 11.00
pm
Table
11
Setting the Programme Times
a. Press & release the
button
marked
SET.
The question SET CLOCK? will
appear
in
the
display.
As
this
has
already
been
done
press
& release the
button
marked
SET.
b. The
question
SET PROG? will
appear
in
the display.
Press
& release
YES
button.
c.
The display will
now
show
the question SET
CH
MON-FR1?
Press
& release
YES
if a
change
to
the
Central
Heating
times are required. Or Press & release SET ifno
change is required.
cm
If
YES
was
pressed
the display will
show
the
first Central
Heating
ONI
time.
By pressing
the +or -buttons
the time will
be
altered
in
10
minute
stages.
When
the
correct time is
shown
in
the
display
Press & release
SET.
The
OFFl
time will
now
show
in
the
display
repeat
as
ONI
setting.
Repeat for
ON2
and
OFF2.
d. After setting
CH
OFF2 the
display
will
show
SET
HW
MON-FRI?
Press
& release
YES
if
a change is required
to
the
Hot
Water times. Or Press & release SET ifno
change
is
required.
IT
YES
was
pressed follow the
same
procesure
as
c(i).
e. After pressing
HW
OFF2
the
display will
show
SET
CH
SATSUN?
Follow
the
same
procedure as c & c(i).
f.
After setting
CH
SATSUN
the
display will
show
SET
HW
SATSUN?
Follow the
same
procedure
as d & cm.
g. After pressing
SET
for
HW
SATSUN the clock will revert to the time of
day
and
its operating mode.
28
Options
At the left
and
right
hand
sides of
the
display is a rectangular line corresponding to one
of
the
four timing statement options. These are;-
OFF
-OFF at all times.
TWICE
-
ON
for two periods each day.
ONCE
-
ON
for one period each
day
(On 1 to OFF
2).
ON
-
ON
at
all times.
To
choose one of the four options press & release
the
SELECT button.
As the programming for
HW
and
CH
are
independent
of
each other the left
hand
side
of
the
display can
vary
from that
on
the right hand side.
The normal switching times can
be
overridden
by
pressing the advance button. This will switch
the
programme
between
ON
& OFF.
There
is
no
need
to
press
the
advance
to
return
to
the
programme
as it will be automatically returned at the next switching time.
Helpful hints for setting the programmer and its use.
When using the +
or
- buttons to set the time.
If
they are pressed & released the display will
change at the rate of
10
minutes
per
press,
but
if
the buttons are held in the clock will 'run'.
OFF2 cannot be set more
than
23
hours
50
minutes after the
ONI
time.
The switching time periods have to be set in sequence of
ONl,
OFFl, ON2
and
OFF2.
If
at
any
point it is wished to start again press
SET
and
+ buttons
at
the same time. Ifthis is
done
the
display will return to 12.00
am
and
the standard time programme. The clock will be required to
be
reset
at
the
correct time.
If
when
setting
no
button
is pressed after one minute the programmer will revert to its normal
opperating mode.
If
in
summer
only the
Hot
Water service is required then repeatedly press the
CH
Select
button
until the display indicates
CH
OFF mode.
29
(}t,"l.l
s~
,~),
Jetstreme 4+ MODEL
70/90
CONVENTIONAL FLUE ILLUSTRATED BALANCED FLUE
SHOWN
INSETS 1
and
2
1----.1
I
c:::J
I
I
1:Cd
I
I I
I I
I
I
L
_______
J
Fig. 18
30
Jetstreme 4+ - Spare Parts List
40/52 50/70 70/90 95/120 125/140
Top
PanelCF
3912201
-+
3952059
3912209
-+
Top
Panel
BF
3912202
-+
3962061
3912210
-+
LH
Side
Panel
Assembly
3913137
-+
3913144 3913140
-+
RH
Side
Panel
Assembly
3913138
-+
3913145
3913141
-+
Front
Lower
Panel
Assembly
3913143
-+
3913146
3913142
-+
Electrical
Assembly
3912195
-+
-+ -+
-+
Front
Upper
Panel
3912169
-+
3912170
3912171
-+
affle Plate Weld
Assembly
3913
096
-+
3912215
3913102
-+
Insulation
Kit
3915022
-+
3955019
3955020
-+
Top
Front
Boiler
Insulation
3932110
-+
3952113
3972116
-+
Top
Rear
Boiler
Insulation
3942112
-+
3962115
3972118
-+
Limit
Thermostat
2860022
-+
-+
-+ -+
Boiler
Thermostat
2816041
-+
-+
-+
-+
Bezel
and
Knob
2816042
-+
-+
-+
-+
Green
Indicator
2850014
-+
-+
-+
-+
Red
Indicator
2850015
-+
-+
-+ -+
Magnetic
Fastener
3915019
-+
-+
-+
-+
Snap
in
Connector
2802181
-+
-+
-+ -+
'0'
Top
Gasket
3913118
-+
3912193 3912194
-+
Flue
Spigot
Gasket
3913119
-+
3913116
3913117
-+
BumerEOGB
2999424
2999423
2999421
2999428 2999422
CF
Air
Silencer
3955021
-+
-+
-+
-+
BF
Air
Duct
3955018
-+
-+
-+
-+
BFHose
3913147
-+
-+
-+
-+
BF
Hose
Clip
3915024
-+
-+
-+
-+
Programmer
MP522
2815025
-+
-+ -+ -+
Nozzle
- Kerosene
2701047
2700001
2701048 2700418 2700398
Nozzle -
Diesel
Oil
2701045
2701046 2700406
2700412
2700415
31
Installation Details
Date installed
Name, Address and
Telephone Number
of
Installer
Name, Address and Telephone Number
of
Commissioning Engineer
Fuel Type
28
second / 35 second
Nozzle size
At commissioning
C02
Smoke
Number
Efficiency
Service Details
It is recommended
that
this appliance should be serviced
at
least annually.
Date
of
Remarks inc C02, Smoke No. &
Service Company and Telephone
Service
Efficiency
Number
i
32
Warranty
Jetstreme
4+
Oil Fired Boilers are guaranteed against manufacturing or material defects for a
period of
2 years* from the date of original purchase. The guarantee is valid provided that
the Jetstreme
4+
Boiler
and
Burner
has
been
properly
installed, commissioned
and
used
in
accordance with the manufacturers instructions
and
has
not
been fitted with parts other than
those approved
by
Benson Heating. The guarantee does not cover defects caused from normal
wear
and
tear, alteration, misuse, neglect
or
improper maintenance.
Under
these terms, Benson Heating will
bear
the cost of replacement parts,
provided
the
faulty component is returned to
our
Knighton Factory, carriage paid.
In
addition, provided the
attached
commissioning
card
has
been
completed
in
full
and
returned
to
the
Service
Department of Benson Heating within
28
days of the
date
of commissioning,
any
labour charges
incurred within two years from the
date
of sale will
be
borne
by
Benson Heating,
provided
authorization has been given prior to the
work
being carried
out
by
an
approved
Jetstreme
Service Agent.
*The 2 year guarantee of the Boiler
and
Burner refers to the Jetstreme 4+ Boiler
with
the
EOGB Burner supplied with the boiler,
it
does
not
cover
any
other Boiler/Burner combination
supplied unless specifically stated
by
Benson Heating.
The above is
in
addition to
your
statutory rights, which remain unaffected.
Benson Heating
Ludlow
Road Knighton Powys LD71LP
I
Telephone 01547528534
...
\
Facsimile
01547520399
Telex
35323
Customer Services Hotline
For Sales, Service
and
Spares:
Telephone 01547529245
© Benson Environmental Limited
Printed
by Leominster Print. Telephone 01568 615305
J
Loading...