BENSON GUHA, GUHC User Instructions

Page 1
Place your message here. For m a xi m u m im pa ct, use two or three sentences.
Headin
g
BENSON GUHA/GUHC
RANGE
I N S T A L L A T I O N C O M M I S S I O N I N G
S E R V I C I N G
U S E R I N S T R U C T I O N S
Issue 5 March 2005
Page 2
~ C O N T E N T S ~
S E C T I O N A
1.0 Compliance Notices
1.1 Certificates of Conformity
1.2 General Product Information
1.3 General Requirements
1.4 Delivery & Pre-installation Checks
1.5 Warranty
2.0 Installation
2.1 Installation Clearances and Mounting Heights
2.2 Heater Mounting
2.3 Warm Air Circulation
2.4 Air Supply
2.5 Flue Installation
2.6 Electrical Installation
2.7 Electrical Panel
2.8 Time Switch
2.9 Room Thermostat
2.10 Fan and Limit Controls
2.11 Summer / Ventilation Switch
2.12 Gas Installation
3.0 Commissioning
3.1 Electrical Pre-Tests
3.2 Gas Supply Pre-Tests
3.3 Ignition Sequence Manual Versions
3.4 Ignition Sequence Automatic Versions
3.5 Hand Over
4.0 Servicing
4.1 Servicing Procedure
5.0 Fault Diagnosis by Flow Charts
6.0 Wiring Diagrams
7.0 Technical Data Formulae
7.1 Technical Data Common Information
7.2 Technical Data Heater Information
8.0 Reference Information
9.0 Parts Listing
Page 3
S E C T I O N B
Warranty Registration Updated Information Timer Information Manual
S E C T I O N C
10.0 Introduction
10.1 Commissioning / Hand over
10.2 Servicing
10.3 Start up Procedure
10.4 Start up Procedure Automatic Versions
10.5 Stop Procedure Manual / Automatic Versions
10.6 Shut Down Procedure
10.7 Fail-safe Situations
10.8 Contact Information
I L L U S T R A T I O N S
Exploded view Flue Systems Gas Train & Pilot Installation Electrical installation Axial & Centrifugal Fans Fault Diagnosis Flow Charts Electrical Drawings
IMPORTANT NOTICE TO INSTALLERS
Installers should satisfy themselves that the gas pipework installation is carried out in accordance with all current legislation, Codes of Practice and recommendations . Additionally it may be necessary to protect the gas valves which form part of the heater or burner assembly from potential pipe contamination particularly, but not exclusively , where copper gas pipework is used.
In instances where copper pipework is to be used for all or part of a gas pipework installation, including short length final connections then we advise that installers consult with gas supplier or provider and satisfy themselves what additional precautions may be necessary
Any reference made to Laws, Standards, Directives , Codes of Practice or other recommendations governing the application and installation of heating appliances and which may be referred to in Brochures, Specifications, Quotations, and Installation, Operation and Maintenance manuals is done so for information and guidance purposes only and should only be considered valid at the time of the publication. Benson Heating cannot be held responsible from any matters arising from the revision to or introduction of new Laws, Standards, Directives, Codes of Practice or other recommendations.
Page 4
1.0 Compliance notices
The Benson GUH range of warm air heaters detailed herewith are manufactured by Benson Heating within a strictly controlled environment within the parameters of ISO9001 These instructions are only valid if the following country code is on the appliance GB. IE. If this code is not present on the appliance, it is necessary to refer to the technical instructions which will provide the necessary information concerning the modification of then appliance to the conditions of use for the country.
The Benson GUH Range has been independently tested and assessed, and has been found to meet the Essential Requirements of the following European Directives.
Gas Appliance Directive (90 / 396 / EEC) Machinery Directive (89 / 392 EEC) Low Voltage Directive(73 / 23 / EEC & 93 / 68 / EEC) Electromagnetic Compatibility Directive (98 / 336 / EEC & 91 / 31 / EEC) Product Liability Directive 65 / 374 / EEC)
The manufacturer has taken reasonable and practical steps to ensure that Benson GUH Range of Heaters are safe and without risk when properly used. These heaters should therefore only be used in the manner and purpose for which they were intended, and in accordance with the recommendations detailed herewith. The heaters have been designed, manufactured, assembled, inspected, and tested, with safety and quality in mind, there are certain basic precautions which the installer and user should be aware of, and they are strongly advised to read the appropriate sections of the information pack accompanying the heater, prior to installation or use.
Benson Heating supports all new products being supplied to their customers with a comprehensive information pack; this clearly defines mandatory instructions for the safe installation, use, and maintenance, of the appliance(s).
Where proprietary items are incorporated into Benson Heating products, detailed information and instructions are also provided as part of the information pack.
It is the responsibility of the installer, owner, user, or hirer, of such products supplied by Benson Heating, to ensure that they are familiar with the appropriate information/ manuals, supplied by the manufacturer, and that they are suitably aware of the purpose of the manuals and the safety instructions. In addition, operators must be suitably trained in the use of the appliance so as to ensure its continued safe and efficient use.
Benson Heating has a commitment to continuous improvement, and therefore reserves the right to amend or change the specification of the GUH Heater range subject to agreement from The Notified Body.
Contained within the text of the manual, the words 'Caution' and 'Warning' are used to highlight certain points.
Caution is used when failure to follow or implement the instruction(s) can lead to premature failure or damage to the heater or its component parts.
Warning is used when failure to heed or implement the instruction(s) can lead to not only component damage, but also to a hazardous situation being created where there is a risk of personal injury.
The Benson GUH range of heaters conform to the following European Harmonised Standards.
BS EN 621 1998 Requirements for non domestic gas fired forced convection air heaters for space heating without a fan to assist transportation of combustion air and/or combustion products.
BS EN 292 - Part 1 : 1991 Safety of Machinery - Basic Concepts, General Principles for Design Basic terminology, methodology
Page 5
BS EN 292 - Part 2 : 1991 Safety of Machinery - Basic Concepts, General Principles for Design Technical Principles and Specifications
BS EN 60204 - Part 1 : 1993 Safety of Machinery - Electrical Equipment for Machines Specification for General Requirements
BS EN 60335 - Part 1 : 1988 Safety of Household and Similar Electrical Appliances General Requirements
BS EN 55014 - 1993
Limits and
methods of
measurement of
radio
disturbance
characteristics
of electrical
motor- operated
and thermal
appliances for
household and
similar
purposes,
electrical tools
and similar
electric
apparatus
BS EN 50165 - 1995
Electrical
Equipment of
non-electric
heating
appliances for
household and
similar
purposes,
safety
requirements
1.1 Certificates of conformity
Declarations and Certificates are available upon request from the Quality Control
M OD EL N O 50 75 100 125 165 OU TP UT kW 15.2 22.0 29.3 37.0 48.4 M OD EL NO 205 250 285 325 400 480 OU TP UT kW 61.6 73.3 85.0 95.3 117.3 140.7
Page 6
Page 7
Department at Benson Heating .
Notified Body PIN Reference is 63AQ0533
1.2 General product information
The Benson GUH Range have an output rated at between 15.2kW to 140.7kW, and are available with either axial or centrifugal fans Each heater must be connected to its own individual open flue in accordance with the manufactures recommendations.
Cabinet
Manufactured
from zintec
coated steel,
finished in a
durable stove
enameled
polyester
powder paint.
Heat Exchanger
Manufactured
from aluzinc
coated steel,
and formed from
pressed and
welded sections
into a multiple
clam assembly.
Flue Outlet
Fabricated from aluzinc coated steel . The part is designed to terminate with a spigot . the assembly incorporates the down draught diverter.
Burner
The atmospheric gas burner is manufactured from aluzinc coated steel and is located beneath the clam. The complete burner rack is easily withdrawn through the front of the heater. Standard heaters are supplied suitable for Natural Gas.
Burner Control
Models 50 - 480 heaters are fitted with a manually operated piezo spark igniter and low consumption pilot, linked via an integral thermocouple to the main multifunctional valve. An automatic facility is also available for all models within the range.
Fan
Models GUH (A) are supplied with an Axial fan for free blowing applications . Models GUH (C) are supplied with Centrifugal fans suitable for ducted applications
Note
Neither asbestos nor soft soldered joints are used in the construction or manufacture of the Benson range of GUH Heaters. The materials selected for use can withstand the mechanical, chemical, and thermal stresses which they will be subject to during foreseen normal use when installed in accordance with the manufacturers recommendations.
Page 8
1.3 General requirements
Caution
Before installation, check that the local distribution conditions, nature of gas and pressure ,and the current state adjustment of the appliance are compatible.
Installation, commissioning, and servicing must only be carried out by appropriately qualified and competent persons.
Warning Unauthorised modifications to the appliance, or departure from the manufacturers guidance on intended use, or, installation contrary to the manufacturers recommendations may constitute a hazard.
Note
To ignore the warning and caution notices, and to ignore the advice from the manufacturer on installation, commissioning, servicing, or use, will jeopardise any applicable warranty, moreover, such a situation could also compromise the safe and efficient running of the appliance itself, and thereby constitute a hazard. The installation of the appliance must meet all the relevant European, national, and local criteria. (See sections 2 and 8).
Prior to installation the following points should be considered;
a) The position of the heater for the optimum efficient distribution and circulation of warm air
b) The position of the heater relative to the route of the flue
c) The position of the heater relative to the supply of gas
d) The position of the heater relative to the electrical services, wiring routes, and if appropriate, any additional controls.
e) The position of the heater relative to the supply of fresh air
f) The position of the heater relative to
potential stratification / circulation problems, which generally occur at higher levels and which may be overcome through the provision of a suitable de-stratification unit.
g) The position of the heater relative to service and maintenance requirements
Caution The heater must not be installed within an area where the conditions are unsuitable, e.g. where the atmosphere is highly corrosive, has a high degree of salinity, or where high wind velocities may affect burner operation. Suitable protection should be provided for the appliance when it is located in a position where it may be susceptible to external mechanical damage from; for example, fork lift trucks, overhead cranes etc.
1.4 Delivery and pre-installation checks
The heater is supplied wrapped in heavy duty protective polythene, mounted on a pallet. On receipt of the heater, the following checks should be carried out;
a) The model is as per order b) That it is undamaged c) That it is suitable for the gas supply and
pressure d) That it is suitable for the electrical supply If any of these points are not satisfied then
contact should be made with the Sales Office at Benson Heating as soon as possible by telephoning 01547-528534. In the case of claims for damage, this must be reported in writing within 24 hours of delivery, in order to comply with insurance criteria
1.5 Warranty
The heater is supplied with a 1 year warranty on all parts except the thermocouple. In addition to this there is also a 5 year time related warranty on the combustion chamber.
Page 9
The warranty commences from the date of dispatch from the manufacturer, and is subject to the terms detailed within the Benson Heating 'conditions of business'.
Note (i)
The warranty may be invalidated if ­a) The warranty registration/commissioning
card has not been completed and returned to Benson Heating
b) The installation is not in accordance with the general requirements of this manual
c) The flue arrangement and air supply for the heater are not in accordance with the manufacturers recommendations, codes of practice, or similar standards
d) Air flow through the heater is not in accordance with the manufacturers technical specifications
e) Internal wiring on the heater has been tampered with or unauthorised service/ repairs undertaken
f) The main electrical supply input to the heater has been interrupted during the heating mode
g) The heater has been subject to and affected by the ingress of water in any form
h) The heater is not operated at the rating(s) laid down in the manufacturers technical specifications
i) The heater has not been operated or used within the normal scope of its intended application
j) The manufacturer's recommended minimum service requirements have not been complied with
Note (ii)
All warranty claims must contain the following information to enable processing to take place; (1) Heater model
(2) Heater serial number (3) Order reference/date of order, together with full installation details (name and address) (4) Details or symptoms of fault (5) Installers name and address.
Faulty parts must be returned to the Benson Heating Spares Department, the address of which is provided on the cover of this manual. Any such parts will undergo inspection to verify the claim. Replacement parts supplied prior to this may be charged, and a credit supplied upon subsequent validation of the warranty claim. Consumable items are specifically not included within the scope of the warranty.
Note (iii)
Notification is required immediately a fault is suspected. The manufacturer will not accept responsibility for any additional damage that has been caused, expense incurred, or consequential loss resulting from any failure of the heater(s).
2.0 Installation
Note
It is a requirement that only qualified and competent personnel may undertake installation commissioning and servicing of GUH Range Heaters.
Warning
All of the basic criteria must be satisfied prior to commencing installation and commissioning, additionally, the Unit Heater must be positioned and installed so as to comply with all the relevant standards and guide lines (see section 8.0), as well as meeting national and local fire regulations and insurance criteria, especially if it is proposed that the heater is to be installed within a special risk area (e.g. proximity to where petrol engined vehicles are stored or parked, where cellulose spraying takes place, where woodworking machinery is operated, etc,).
Indirect fired heaters must not be located in hazardous areas, however, it is permissible for the heater to supply air to such areas.
Page 10
The recommended maximum and minimum mounting heights in metres are as follows
MODEL 50 75 100 125 165
Max 2.73 2.73 3.03 3.33 3.64 Min 1.82 1.82 2.12 2.42 2.73
MODEL 205 250 285 325 400 480
Max 3.94 3.94 4.24 4.24 4.24 4.24 Min
2.73 2.73 2.73 2.73 2.73 2.73
Any combustible material adjacent to the air heater and / or flue system must be so placed or shielded so as to ensure that its temperature does not exceed 65
0
C
2.2 Heater Mounting
The heater and flue must be adequately supported by one of the following methods ;
a) Suspension by steel drop rods or straps from the fixing points located on top of the heater These must be of sufficient strength to safely carry the weight of the unit and ancillary equipment. The straps may only drop vertically to eyebolts, if used; I.E. They must not be joined to the eyebolt at an angle to the vertical, and eyebolts if used should be of an approved type. b) On specifically designed cantilever brackets mounted from a non-combustible wall. c) On a level non-combustible surface capable of adequately supporting the weight of the unit and ancillary equipment . Under these circumstances approved mounting feet must be fitted.
Note
GUH (C) Models cannot be supported on cantilever brackets.
2.3 Warm Air Circulation
The air heater should be positioned to enable maximum circulation of discharged warm air within the area to be heated, whilst taking account of personnel within the area,
Ensure louvres are adjusted outwards and ensure blades are not resonating
sources of cold air ingress , and obstructions. The air temperature rise on passing the heat
exchanger is typically around 34
0
C A full and unobstructed return air path to the air heater must be provided (see 2.4 Air Supply).
Where the heater is positioned to deliver blown air through an opening in a wall, return air intakes should be located so that they cannot become blocked. Similarly these intakes must be positioned so as not to draw in odours, fumes, hazardous vapours or particles. Barrier rails should be provided to eliminate the risk of combustible materials being placed within 1 metre of the warm air outlet.
2.4 Air Supply
Provision must be made for the existence of an air supply in order to satisfy both combustion and ventilation criteria.
It is a requirement that the area where the air heater is located must have a permanent air vent of negligible resistance direct to the outside air. Such air vents must be positioned so as not to become blocked or flooded, nor should they be placed so as to introduce undesirable matter (e.g. flammable, volatile, or aggressive chemicals/compounds or potentially hazardous or harmful substances) either direct from the outside, or through their proximity to an adjacent extraction system.
The criteria necessary for establishing the
minimum size of natural vents is detailed as follows;
Position of vent Area of vent
direct to outside
INLET
Low level (<60kW) 9.0cm
2
per kW Low level (>60kW) 540cm2 + 4,5cm2 per kW of rated input per heater
OUTLET
High level (<60kW) 4.5cm
2
per kW
High level (>60kW) 270cm
2
+ 2,25cm2 per kW
of rated input per heater
Page 11
Where mechanical ventilation is used it is a requirement that the inlet is of the mechanical type, and the outlet is either mechanical or natural.
Caution
Systems of ventilation that employ mechanical extraction and natural inlet must not be used. Furthermore, where the air supply is by way of a mechanical means the inlet must be positioned at low level and be capable of providing a minimum throughput as detailed in section 7.2 of this manual. The natural extraction air vents must have a minimum area as per the above table, and it is strongly recommended that natural extraction vents are situated at high level.
Additionally, an
automatic
control
interlocked to
the burner must
be fitted to
ensure burner
shutdown in the
event of airflow
failure or
restriction.
When the area to be heated already has an extraction system, the size of the air vent must be sized to account for this and to maintain the required number of air changes
If the heater is to be installed within its own separate building or plant room, the above details do still apply, as does the requirement for minimum space, further consideration should be made for free air for recirculation to avoid the possibility of negative pressure in the plant room (see guidance notes below) Additionally the maximum temperature within the plant room should not exceed 32
0
C
Note
It is strongly
recommended
that BS 6230 :
1991 is referred
to for further
information
concerning
ventilation
requirements.
Page 12
should be fitted with access covers, again to allow for cleaning and inspection.
The position of the flue and its terminal should be such that it does not impair the combustion process. It should terminate in an exposed position so as to allow the free escape of flue gases without risk of their re­entering the building through windows, ventilation ports etc. The following illustrations of different flue configurations are included for guidance purposes (see figures 2-12 )
If the flue does not have access to an existing chimney then it should be extended through the roof or wall to a height of at least 1 metre above that of any object within 3.5 metres of the terminal. The materials from which the flue is constructed must be non-combustible, resistant to internal and external corrosion, and be capable of withstanding the stresses and loadings associated with normal use.
When designing the flue system the prevention of the formation and entrapment of condensation must be a key consideration. Twin wall or insulated systems are recommended, as they tend to inhibit the formation of condensates. Where condensation is unavoidable traps should be included to encourage the condensates to flow freely to a point from which they may be released, preferably into a gully. The condensate pipe from the flue to the disposal point must be made from corrosion resistant pipe of not less than 25mm internal diameter. If the flue passes through a wall, ceiling, or roof made from combustible material then it has to be sleeved so as to provide a minimum of a 25mm void between the exterior of the flue and the internal wall of the sleeve. The maximum permitted temperature of any adjacent combustible material is 65
o
C.
Caution
It is imperative that the flue should be properly sealed where it passes through the roof, this can best be achieved by using the approved method of roof flashing plate and cravat.
The flue outlet on all GUH heaters can be in either vertical or horizontal (top or rear) configuration.
Note
It should be noted that claims made under warranty and attributed to the ingress of water may not be considered especially if an approved method of sealing has not been used, or if the design of the flue has not made provision for possible condensation problems. Where a horizontal outlet is used, the manufacturer strongly recommends that a flue venter of an approved type is fitted to aid the evacuation of the combustion products. It is also recommended that BS5854: 1980 and BS5440: parts 1 and 2 are used as a consultative document when considering flue requirements.
Page 13
Not less than 600mm
Not less th a n 600mm
Greater than 1500mm
Parapet
Fig 2 Flat roof with parapet
Not less th a n 600mm
Less than 10 h
Greater than 1500mm
H
1
H
2
2
Less than 10 h
1
Fig 3 Flat roof envelope method
Structure
Not less than 250mm
2
Greater than 10 h
1
H
1
H
2
Structure
Fig 4 Flat roof where the flue height is more than 10 Heights (H) away from all structures
Structure
Not less th a n 600mm
Less than 1500mm
Fig 5 Flat roof with flue close to parapet
Not less than 600mm
Not less th a
n
250mm
Fig 6 Flat roof with no parapet
Page 14
Not less than 600mm
Less than 1500mm
Structure
Fig 7 Flat roof with structure close to flue outlet
Not less th a n 600mm
Not grea t er tha n 45
°
Not less th a
n
600mm
Fig 8 Pitched roof not greater than 45°
Less than 1500mm
Dormer window
Not less tha
n
600mm
Fig 9 Pitched roof chimney within 1.5m from dormer window measured horizontally
Page 15
Greater than 45
°
Not less tha
n
1000mm
Not less than 1000mm
Fig 10 Pitched roof exceeding 45°
Less than 45
°
Not le s s than 600mm
Termination on ridge
Fig 11 Pitched roof internal route not exceeding 45° and ridge termination
Fig 12 Pitched roof chimney within 1.5m from dormer window measured horizontally
Not less than 600mm
Not less than 1000mm
Dormer window
Page 16
2.6 Electrical Installation
All electrical wiring and connections must be in accordance with the relevant European, National, and Local regulations as well as to IEE Standards.
Warning
Ensure that the Electric and gas supplies are turned off before any electrical work is carried out on the heater. Also ensure that wiring cannot make contact with any metal surfaces liable to be subject to high temperatures, and where insulation of the wiring could be impaired as a result of such contact. All GUH models must be earthed.
Caution
The main electrical supply must not be switched off or disconnected as a method for stopping the heater, the exception to this is in the event of an emergency, or when the heater has been allowed to cool sufficiently to prevent any damage from being sustained to the heater or its controls (ie: during servicing). Claims for damage will not be considered if they have resulted from incorrect wiring or the incorrect use of the heater Each heater requires a permanent 230V 50Hz 1ph electrical supply, which must be wired through a fused isolator fitted with a fuse of the correct rating (see section 7.1). The correct supply connection points for the live, neutral, and earth are clearly indicated on the wiring diagram mounted inside the wiring box cover. Wiring diagrams are also detailed within this manual, (section 6.0 ) The electrical supply isolator should be mounted adjacent to the air heater in an easily accessible position to allow for servicing isolation, or emergency shut off.
2.7 Electrical panel
Warning
Ensure that the mains isolator is turned OFF before undertaking any electrical on the heater. Access to the electrical panel is gained by removing the right hand heater side panel, (Lift the panel clear of the lower lip, pull panel outwards and let it slide until it is retained by the two lugs and the lower lip. The panel can be fully removed by tilting one
of the top corners towards the heater thereby disengaging the lugs). The cover to the electrical panel can be removed by undoing the two screws which secure it to the panel.
Warning
Ensure that all connections are secure and that there are no loose strands which could bridge across the terminals. A minimum conductor size of 1.0 mm (diameter) is required.
Caution
One electrical
panel per heater
is required,
unless heaters
are specified for
multiple heater
control
applications. On
no account
should more
than one heater
be connected to
a single time
switch or
thermostat. The
Page 17
only exception
to this is when a
control panel
suitable for
multiple heater
applications is
supplied by the
manufacturer, in
which case the
wiring diagram
supplied with
the control
panel should be
read in
conjunction with
the existing
wiring diagram.
Any ancillary electrical items e.g. room thermostats , time switches, remote panels etc, must be wired into the heater electrical circuit in accordance with the diagrams provided Note When external controls operate to switch the heater OFF, power to the heater should remain to allow the fan to continue to
operate to sufficiently cool the heater thereby preventing damage to the heat exchanger.
2.8 Time switch
Caution
Time switches may only be fitted if they are of an approved type, and must have separate motor connections, the motor must be connected to a suitable live and neutral supplies, and with the switching contacts then wired in series from the neutral side of the room thermostat to terminal 7 Reference should be made to the wiring diagrams contained with the time switch, and within section 6.0 of this manual
2.9 Room thermostat
Any external room thermostat should be fitted with the common terminal (if fitted with changeover contacts) to terminal 5. If the thermostat is fitted with a heat anticipator this should be fitted to terminal 2. The thermostat should be mounted at a height of approximately 1.5mm from the floor in an area where the ambient temperature is representative of the area to be heated. The siting of the room thermostat should be in a draught free area. or in an area where temperatures are free from the influences of direct sunlight or heated discharged air.
2.10 Fan limit control
( Situated inside the right hand side panel) Fan control (white button) The fan control switch features normally open 230V contacts, and is wired to control the live supply to the fan motor . When the circuit is made, the fan will switch on when the heat anticipator has closed the fan switch contacts. When the thermostat or time switch shuts down the burner, the fan will continue to run until the thermal switch has cooled sufficiently to prevent the residual heat from damaging the heater or its controls. On startup the fan delay prevents air being circulated until the desired temperature is achieved
Limit control (red button) An adjustable high temperature manual reset limit control. If this control needs resetting the cause should be determined and rectified immediately. On models with two fans a second limit
Page 18
control is situated inside the left side panel and is wired in series. Operation of either switch will shut down the heater
On the GUH
400 / 480 where
four fans are
fitted there are
separate
sensors again,
however as
these units are
modular they
will react much
the same as a
twin fan unit as
there are two
sensors per
module linked to
the relevant
control.
Caution The power supply to the fan must not be interrupted, the only time when power supply can be disconnected or interrupted is during servicing or in emergencies.
If there is a requirement for the heater to be switched off over night then the gas valve circuit should be opened via a time switch, etc, as per the wiring instructions and diagrams supplied within section 6.0 of this manual.
2.11 Summer switch
A heat / ventilation switch may be fitted remotely and connected between terminals
1. and 4. This switch will allow the fan motor to run continuously. Where the remote control box is used, the burner is automatically inhibited during the summer / ventilation setting.
2.12 Gas installation
Warning As there have been recorded
instances of the deposition of copper sulphide dust within the valves and orifices of gas appliances as a direct result of a reaction between the hydrogen sulphide contained in some natural gasses and copper pipe we recommend that the heater(s) should not be connected to any natural gas pipe distribution system which utilizes copper pipework, including final connections. Instead steel pipework should be used throughout. In the event that it is impractical to use steel pipework or where installers are obliged or insist on using elements of copper pipework within the installation then we strongly recommend that the gas supplier be consulted as specific conditions and requirements may be necessary.
Please read notice on PAGE 3 of this manual
Only qualified and competent personnel are allowed to undertake the installation, commissioning, and servicing of Unit Heaters
The GUH range of heaters are all manufactured and pre set for use with Natural Gas, and all feature 3/4” BSP connection points. Prior to installation the supply characteristics (gas type and pressure) must be checked to ensure that they are in accordance with the data plate on the heater.
The gas
Page 19
supplier should
check that the
meter and
service
connection to
the heater are
capable of
delivering the
required volume
of gas, thereby
ensuring that
the minimum
burner pressure
can be
achieved.
Consideration
should be given
to the pressure
drop on single
and multi heater
installations and
the effect they
may have on
other plant
sharing the
supply.
If it is necessary to fit a gas pressure booster, the controls must include a low pressure cutoff switch which must be fitted on the supply / inlet side of the booster. It is also a requirement that the gas supplier is advised prior to the installation or fitting of the booster. Each heater supply must be fitted with a separate isolating cock positioned adjacent to and upstream of the union which must be sited outside the heater the isolating cock should be of the 90
0
turn type and should be clearly marked OPEN / CLOSED it should also be installed so as to fall to the closed position An approved gas jointing compound must be used on all joints and unions and the system purged and tested for soundness prior to final connection The connection to the heater can be made by way of either an approved flexible coupling or rigid connection . Threaded connections must comply to ISO 288/1 or ISO 7/1 further information concerning accepted European practice is detailed in June 1995 version of prEN1020 Annex 7. The diameter of the pipework from the isolating cock to the burner must not be less than the diameter of the connection into the multiblock.
Note Reference to The Institute of Gas Engineers publications Utilisation Procedures IGE/UP1 and IGE/UP2 together with reference to BS6891 is strongly advised.
3.0 Commissioning
Page 20
Note It is a requirement that only suitably qualified and competent personnel are allowed to undertake the commissioning of the heater. It is also strongly recommended that prior to commissioning the engineers familiarises themselves with the heater. the specific requirements of the installation /application, and the information contained within the manual.
Warning All heaters are subject to a rigorous test programme prior to despatch, whilst such a programme does involve pre-commissioning and the setting of the heater to operate efficiently and within its designed operational limits this does not mean that the function of thorough on site commissioning is less important It is strongly recommended that the equipment used for the sampling and analysis of the flue gases is accurate to within +/- 0.1% and maintained so that it is regularly calibrated.
The following
pre-
commissioning
checks should
be undertaken,
having first
ensured that the
gas and
electrical
supplies are
turned off.
(a) Check that all panels and fasteners are secure and in place.
(b) Check that the heater is mounted safely. (c) Check that the flue is sealed, secured,
and adequately supported. (d) Check that the fan is free to rotate, that
the fan is secured to its shaft, and that the guards and fan assembly are all in place and properly secured.
(e) Check that the heater is installed so that it is not tilted and remains square.
(f) Check that the outlet louvres are set to offer minimum resistance to air flow.
3.1 Electrical pre-tests
The electrical safety checks must include the following a) Test for earth continuity
b) Test for resistance to earth c) Check live and neutral connections are
correct. d) Check to ensure that when the external
controls operate to switch the heater off, power remains to the fan
3.2 Gas supply pre-test
Ensure that the service pipework has been installed purged and tested in accordance with the relevant regulations, and that the installation is served by an adjacent isolating cock. Connection from the supply to the heater must also comply with the relevant regulations (see section 8.0) and must have been purged and soundness tested by an authorised engineer.
3.3 Ignition sequence manual versions
Warning
Page 21
If during the following sequence of operations the heater fails to operate correctly the fault should be traced and rectified before proceeding, if necessary referring to section 5.0 fault diagnosis. If for any reason the pilot light is extinguished no
attempt should be made to re light it within three minutes
a) Switch off the main electrical supply to the heater
b) Turn off gas supply to the heater c) Remove side panel, and connect
manometers to the gas supply test point and to the main burner test point
d) Ensure outlet louver’s are correctly set e) Ensure fan rotation is not impaired or
obstructed f) Set room thermostat to its lowest setting g) If a time switch is fitted ensure it is set to
an on period h) Switch on electrical supply i) Turn on gas supply, and open burner
viewing port j) Depress and hold in control start button
and test for soundness k) Continue to depress start button whilst
operating igniter until pilot light is present l) Hold in start button for at least one minute
to establish pilot - carefully release button confirming presence of pilot
Warning
If the pilot fails to become established do not attempt to re light for at least three minutes , if the pilot is established continue as follows.
m) Close burner viewing port n) Turn thermostat to the highest setting, and
the main burner will light then re-open the viewing port and check that the main burner is providing a good flame i.e. even, stable,
and conical. o) Check pressure readings on the
manometers, and continue to let the heater fire for ten minutes
p) When the fan starts ensure that the direction of rotation is correct , and that the fan start is within two minutes of burner ignition
Caution
If the fan fails to operate within approximately two minutes and the heater goes to overheat it will shut down through breaking the circuit to the gas valve, the cause must be ascertained and rectified before re-ignition. Once the limit thermostat has tripped out it must be manually reset to allow re-ignition to take place.
q) After ten minutes check burner head pressure is as specification - adjust as necessary by removal of the gas pressure adjustment cover, and using a screwdriver turn the adjustment screw on the governor as follows: Anti clockwise to reduce. Clockwise to increase.
r) Check that the gas pressure remains satisfactory for all appliances on the same circuit
s) Undertake combustion tests checking CO CO
2
and efficiency (see section 7.0) check for spillage using a dry, water cooled ,rhodium or chromium plate.
t) Check that the burners are extinguished when the thermostat is set to its lowest setting, and then remove the manometers.
u) Turn the thermostat to its highest setting to re light the burner and replace the adjustment screw cover
v) Check flame failure circuit by loosening the connection between the thermocouple and the overheat limit control on the main gas valve, the ignition and main burners should go out, retighten after testing
w) Turn the thermostat to its lowest setting and shut off the gas supply at the gas control
Page 22
valve, allow the fan to continue to run until the heater is cooled sufficiently for the fan to shut down
x) Turn off the electrical supply y) Set thermostat to desired room
temperature and replace the side cover panel
z) Ensure that the user is familiar with the heater and its controls and that the user is satisfied with the commissioning and testing, and that he is aware of the instructions within the manual It is strongly advised that the commissioning engineer runs through the lighting, shutdown, and general safe and efficient running of the heater before hand over.
3.4 Ignition sequence automatic versions
Automatic control is by way of a Satronic controller (with automatic gas valve replacing the manual standing pilot valve) used in conjunction with a Satronic spark generator (which replaces the piezo igniter as fitted to manual units) , giving a maximum pilot sequence of 15 seconds. Flame supervision is via a flame sensor rod. instead of the thermocouple as fitted to the manual units. The sequence is as follows: as per 3.3 a-i The start signal will ignite the pilot, once the flame proving has taken place the main gas valve will supply the burner and burner ignition will occur. Continue as per 3.3 m-y
3.5 Hand over
Upon satisfactory completion of commissioning and testing, the customer should receive the completed guarantee and commissioning card from the commissioning engineer together with the user instructions (section C). At the same time the user should be made aware of the most efficient and economical methods of operation. The user must be familiar and satisfied with the safety, ignition, shutdown, and general operational procedures.
4.0 Servicing
Warning
It is a requirement that only qualified personnel are allowed to carry out installation commissioning or servicing. In addition only spare parts recommended by the manufacturer may be fitted, and the installer should provide a list of recommended spare parts that are available through the manufacturer or his agent (see section 9)
Before commencing any maintenance or servicing work the heater must be shut down and allowed to cool, and have the gas and electric supplies to it turned off at the supply cock and isolator respectively.
Always test for gas soundness after completing any service work particularly if this has necessitated the removal and / or replacement of gas carrying components
It is advisable that routine inspections are carried out on a frequent basis, servicing must also be carried out regularly, and in accordance with the manufacturers recommendations i.e. at a maximum interval of one year. In certain applications the frequency of servicing will have to be increased, this to a large extent is governed by the working environment, and both the manufacturer and the installer will be able to offer further advice.
A safe working platform giving good access to the heater is required, It should be noted that on suspended units the lower front panel is removable so as to provide access to the burner tray, injectors, and manifold, all of which should serviced in the normal way as detailed.
Clean all
accessible
surfaces
Page 23
Pilo t Burner fails to
light
No Spark
Air in Gas
Supply
Pilot Feed
Restriction
Purge Gas Line
to Re mov e A ir
No Gas
Supply
Check Pilot
Adju s te r is F u lly
Open and that
the Pilot Tubes
are not blocked
Check Gas
Supply is Present
and that Gas
Taps are open
Che c k that th e Pilot
Flame Path is
supplying Heat to
the Thermocouple
Pilot Burner
Lights but
flame does not become established
Pilot Flame not
being sensed by
Thermocouple
Check that the Pilot
Flame Path is
supplying Heat to
the Thermocouple
Pilot Flame is too
small
Check that the
Thermocouple is
Connected to the
Gas Valve Co r rectly
Check that the Pilot
Flame Adjuster is
correctly set and
that the pilot feed is
Unrestricted
Reposition
Thermocouple
and / or Pilot
Flame Shroud
Replace Faulty
Thermocouple
Pilo t B urner
lights and
becomes
established
but th e Main
Burner fails
to light
Check that all
External Controls
are set to Demand
Heat
Check that
there is
Po w e r to th e
Heater
Check
Limit Stat
Reset
Check
Fuse
Check
Thermostat
Check Time
Switch
Check that the
Ga s Valve is
not Open
Circuit
Replace
Gas Valv
e
Page 24
No
Operation
Check that Limit
Stat is not in Fail
Safe Position
Check Stat
Check
Timer
Check External
Controls are
Demanding Heat
Check there is
power to the
Heater
Check
Fuse
Pilot Will
Not Light
No Spark
Air in Gas
Supply
Pilot Line
Restricted
No Gas
Supply
Check Electrode
Gap is Correct
Purge System to Rem o ve Air
Check that Pilot
Adjuster is set
Correc tly
Check Gas taps
are open and
Gas is Present
Check Electrode is not Cracked
Check HT leads and
Check Spark
Generator
Check Control
Box
Replace Faulty
Unit
Pilot lights but fails to
become
Established
Poor Signal
from Probe
Check
Flame Path
Check
Probe Signal
Faulty
Control
Box
Pilot Flame
to Small
Replace
Faulty Probe
Replace
Faulty Unit
Check Pilot
Flame Adjuster
is Fully O p e n and Pilot Feed is Unrestricted
Page 25
Pilot flame is
Established
but Main
Burner will
not Ignite
Faulty Wiring
from Control to
Valve
Replace
Faulty Control
Unit
Faulty Second
Stage Valve
Fan will not Run
Fan
Control is
Open
Circuit
Check that
Fan will run
when Main
Gas is On
Replace
Faulty Fan
Control
Open Circuit to
Fan Motor
Check Wiring and
Connections
Fan runs
but stops
when Main
Burner is
alight
Faulty Motor
Fan Control is
Open Circuit
Low Ambient Temperature
Check that
Fan will run
when Main
Gas is On
Check that Fan cycles
On / Off.
Check Fan
Button,
Check Fan
Stat
Settings
Replace
Faulty Unit
Page 26
GUH 50 to 165 Piezo Ignition
6.0 Wiring Diagrams
GUH 205 – 325 Piezo Ignition
Page 27
GUH 400-408 Piezo Ignition
GUH 50 – 325 Automatic Ignition
Page 28
GUH 400 – 480 Automatic Ignition
T
CP 2 Control GUH 50 – 325 Piezo ignition
Page 29
CP 2 Control GUH 50 – 325 Auto reset
CP 2 Control GUH 400 — 480 Auto reset
Page 30
CP4 Control GUH 400 — 480
CP 4 Control GUH 50 — 325
Page 31
7.0 Technical Data
Formulae for calculating efficiency are detailed as follows
q1 is the heat of the dry products of combustion (% of heat released per unit volume of gas) q2 is the heat of the water vapour contained in the products of combustion
(% of heat released per unit volume of gas)
C1 is the mean specific heat of
the dry products of combustion
(in MJ / (m3K) )
t1 is the average combustion air temperature (in oC) t2 is the average temperature of the products (in
o
C)
H
i
is the net calorific valueof the gas at 1013 mbar and 15oC, dry (in MJ / m3)
H
s
is the gross calorific value of the gas at 1013 mbar and 15oC, dry (in MJ / m3)
Vf is the volume of dry products of combustion per unit volume of gas (in m
3
)
Ref Gas G110 G120 G20 G25 G30 G31
V CO2 0.26 0.32 1 0.86 4 3
The net efficiency , E (
net) (in % ) is given by : E (net) = 100 + (q1 = q2)
Where t
2
– t
1 Hs
- Hi
q1 = C1 x Vf ------------------ x 100 q2 = 0.077 ------------------- (t
2
– t1)
H
i
Hi
7.1 Technical Data Common Information
Gas supply Types
I
2E
+
I
2E ( R ) B
I
2H I2R
Destinations BE FR GB IE NL Appliance Type B
11
PIN / report no 63AQ0533 / 160009 Electrical Supply 230V 50Hz 1ph Fuse Rating 6 / 10 AMP IP Rating IP44 Fan Limit Settings Fan On 60ºC Fan Off 30ºC Limit 100ºC
Page 32
MODEL NATURAL
GAS
GUH50 GUH75 GUH100 GUH125 GUH165 GUH205
HEAT
OUTPUT
kW Btu
15.2
51,900
22.0
75,000
29.3
100,000
37.0
126,250
48.4
165,140
61.6
210,180
HEAT INPUT
(Gross)
kW Btu
20.1
68,600
28.2
96,200
37.5
128,000
47.6
162,500
62.3
212,600
79.2
270,300
MINIMUM INLET
PRESSURE
mbar
Ins WG
17.5 7
17.5 7
17.5 7
17.5 7
17.5 7
17.5 7
BURNER
PRESSURE
mbar
Ins WG
13.2
5.3
13.0
5.2
6.5
2.6
7.1
2.8
7.4
3.0
7.4
3.0
NAT GAS
CONSUMPTION
ft3/hr
m
3
/hr
66.6
1.9
93.4
2.65
124.3
3.5
157.8
4.5
206.3
5.85
262.5
7.45
TEMPERATURE
RISE
ºC ºF
28 82
34 93
33 91
32.6 90
32.5 90
33 91
AIR
FLOW
ft3/min
m
3
/sec
934
0.441
1114
0.526
1528
0.721
1860
0.878
2485
1.173
3060
1.444
AXIAL FAN
THROW
ft
mtrs
35
10.9
40
12.4
50
15.5
55
17.1
65
20.2
65
20.2
CENTRIFUGAL FAN
STATIC PRESSURE
Pa
Ins WG
75
0.3
100
0.4
100
0.4
125
0.5
163
0.65
125
0.5
SOUND LEVEL
Dba 57 63 63 69 72 72
GAS CONNECTION
BSP 3/4 3/4 3/4 3/4 3/4 3/4
MAIN INJECTOR
NATURAL GAS
mm
No Off
1.8 4
1.8 6
2.6 5
2.6 6
2.6 8
2.6 10
FLUE DIAMETER
mm 125 125 150 175 200 200
ELECTRICITY SUPPLY
230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
ELECTRICAL POWER
(AMPERES)
Axial
Cent
0.4 0.8 0.8 1.5 1.7 2.0
FUSE RATING Axial
Amps 6 6 6 6 6 6
POWER ABSORPTION
Kw
Axial
Cent
0.1
0.4
0.15
0.63
0.15
0.63
0.36
0.85
0.36
1.05
0.3
1.26
AIR OUTLET
VENTILATION AREA
cm2
in
2
90 14
127
20
169
26
215
34
275
43
313
49
MOUNTING HEIGHT
(MTRS)
Min
Max
1.82
2.73
1.82
2.73
2.12
3.03
2.42
3.33
2.73
3.94
2.73
3.94
GROSS FLUE TEMP
ºC 170 180 170 180 170 180
WEIGHT
Kgs
Axial
Cent
70 81
88
101
107 120
123 136
155 175
188 216
7.2 Unit Heater Models Technical Data
Page 33
MODEL
NATURAL GAS
GUH250 GUH285 GUH325 GUH400 GUH480
HEAT
OUTPUT
kW Btu
73.3
250,000
85.0
290,000
95.3
325,000
117.3
400,000
140.7
480,000
HEAT INPUT
(Gross)
kW Btu
93.5
319,000
110.7
377,700
124.1
423,400
151.0
515,000
182.7
623,500
MINIMUM INLET
PRESSURE
mbar
Ins WG
17.5 7
17.5 7
17.5 7
17.5 7
17.5 7
BURNER
PRESSURE
mbar
WG
7.1
2.8
8.1
3.2
8.3
3.3
6.7
2.7
7.0
2.8
NAT GAS
CONSUMPTION
ft3/hr
m
3
/hr
300
8.5
341
9.65
396
11.2
494
14
600
17
TEMPERATURE
RISE
ºC
ºF
34.3 94
33 91
33 91
33 91
34.3 94
AIR
FLOW
ft3/min
m
3
/sec
3530
1.666
4284
2.022
4899
2.312
6120
2.888
7060
3.332
AXIAL FAN
THROW
ft
mtrs
70
21.7
80
24.8
90 28
65
20.2
70
21.7
CENTRIFUGAL FAN STATIC PRESSURE
Pa
ins WG
125
0.5
163
0.65
163
0.65
150
0.6
163
0.65
SOUND LEVEL
Dba 72 70 70 72 73
GAS CONNECTION
BSP 3/4 3/4 3/4 2 x 3/4 2 x 3/4
MAIN INJECTOR
NATURAL GAS
mm
No Off
2.6 12
2.6 14
2.6 16
2.6 20
2.6 24
FLUE DIAMETER
mm 250 250 300 300 300
ELECTRICITY SUPPLY
230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
ELECTRICAL POWER
(AMPERES)
Axial Cent
1.9
8.4
3.1
8.4
3.3
9.6
4.0
9.6
3.9
8.4
FUSE RATING Axial
Amps 6 6 6 10 10
POWER ABSORPTION
Kw
Axial Cent
0.3
1.26
0.72
1.26
0.72
2.1
1.1
2.1
0.6
2.5
AIR OUTLET
VENTILATION AREA
cm2
in
2
346
54
384
60
414
64
475
72
546
85
MOUNTING HEIGHT
(MTRS)
Min
Max
2.73
3.94
2.73
4.24
2.73
4.24
2.73
4.24
2.73
3.95
GROSS FLUE TEMP
ºC 170 170 170 140 150
WEIGHT
Kgs
Axial Cent
218 246
266 313
303 351
386 442
436 492
7.2 Unit heater Technical Data Cont’d
Page 34
8.0 Reference Information
Doc/Ref Title/Subject
prEN 621 Non Domestic Gas Fired Forced Convection Air Heaters For Space Heating BS EN 292 Parts 1 and 2; 1992 Safety of Machinery BS EN 60204 Part 1; 1993 Safety of Machinery - Electrical BS EN 60335 Part 1; 1988 Safety of Electrical Appliances BS EN 55014 1993 Electromagnetic Compatibility BS EN 50165 1995 Safety of Electrical Equipment BS 5854 1980 Code of Practice - Flues/Flue Structures BS 6891 1988 Installation of pipework < 28mm BS 715 1993 Metal Flue Pipes and Fittings BS 5440 Part 1 ; 1990 Specification/Installation of Flues BS 5440 Part 2 ; 1989 Ventilation Requirements Gas Appliances ISO 228/1 See also BS 2779 and BS 5380) Pipe Threads Seals and Couplings UP / 1 Replaces IM / 5 and IM / 16 Installation of Gas Appliances UP / 2 Replaces IM / 7 Installation of Gas Appliances
Page 35
Part Description GUH 50 GUH 75 GUH 100 GUH 125 GUH 165 GUH 205
Heat Exchanger Assy 33-10-598 33-10-599 33-10-600 33-10-601 33-10-602 33-10-603
Draught Diverter Assy 33-20-598 33-20-592 33-20-559 33-20-606 33-20-607 33-20-611
Gas Train Assembly 33-20-261 33-20-264 33-20-263 33-20-264 33-20-265 33-20-266 Pilot Installation Rhs 33-30-330 common common common common common
Control Box Assembly 33-20-326 common common common common common
Flue Kit Assembly N/A N/A N/A N/A N/A N/A
Control Box Lid 33-20-865 common common common common common
F & L Stat L4064 8” 28-60-023 common common common common common Limit Thermostat (IMIT) N/A N/A N/A N/A N/A 28-40-059 Choke Plate Weld Assy 33-30-540 common 33-30-240 common common common
Manifold Assy Rhs 33-10-150 33-10-152 33-10-151 33-10-152 33-10-153 33-10-154
Copper Washer 91-00-052 common common common common common
Injector Nat Gas 33-30-538 common 33-30-302 common common common
Gasket 33-30-295 common common common common common
Gas Valve (Honeywell) 28-30-114 common common common common common
Pilot Burner c/w shear olive 28-90-148 common common common common common
Pilot Injector 28-90-153 common common common common common
Thermocouple 33-50-004 common common common common common
Ignition Electrode 28-90-156 common common common common common
Ignition Lead 28-02-172 common common common common common
Burner 33-00-123 common 33-00-124 common common common
Fuse Holder 28-07-050 common common common common common
Fuse 10 x 38 Axial 28-07-048 common common common common 28-07-048
Fuse 10 x 38 Centrifugal 28-07-048 common common common common 28-07-048 Fan/Motor Guard Assy Axial 28-09-041 28-09-039 28-09-039 28-09-040 28-09-036 28-09-042 Fan/Motor Guard Assy Cent 28-09-025 28-09-001 28-09-001 28-09-001 28-09-002 28-09-001
Fan Plenum Axial 33-10-626 33-10-634 33-10-540 33-10-554 33-10-528 33-10-567 Fan Plenum Cent 33-00-169 33-00-168 33-00-167 33-00-166 33-00-165 33-00-161
*Down Flow head 30 Deg 33-20-476 33-20-477 33-10-427 33-10-428 33-10-429 33-10-430
*Down Flow Head 90 Deg 33-20-502 33-20-503 33-20-504 33-20-505 33-20-506 33-20-507
*Vertical Louvre 33-20-943 common 33-20-873 common common common
*CP2 Control Panel 33-10-424 common common common common common
*Flue Ventor Assy 33-20-751 common 33-20-752 33-20-753 33-20-754 common
* Items marked are available as Optional Extras
9.0 Parts list
Page 36
Part Description GUH 250 GUH 285 GUH 325 GUH 400 GUH 480
Heat Exchanger Assy 33-10-664 33-10-604 33-10-605 33-10-603 33-10-664
Draught Diverter Assy 33-20-665 33-10-615 33-10-609 33-20-611 33-20-665
Gas Train Assembly Rhs 33-10-683 33-20-554 33-20-554 30-20-266 30-10-683
Gas Train Assembly Lhs N/A N/A N/A 33-10-712 33-10-717
Pilot Installation 33-30-330 33-30-553 33-30-553 33-30-330 33-30-330
Pilot Installation Lhs N/A N/A N/A 33-10-713 33-10-713
Control Box Assembly 33-20-326 33-20-326 33-20-326 33-10-716 33-10-715
Flue Kit Assembly N/A N/A N/A 33-21-155 33-21-155
Control Box Lid 33-20-865 common common 33-20-865 common
F & L Stat L4064 8” 28-60-023 common common 28-60-023 common Limit Thermostat (IMIT) 28-40-059 common common common common Choke Plate Weld Assy 33-30-240 common common 33-30-240 common
Manifold Assy Rhs 33-10-682 33-10-155 33-10-156 33-10-154 33-10-682
Manifold Assy Lhs N/A N/A N/A 33-10-715 33-10-718
Copper Washer 91-00-052 91-00-052 91-00-052 91-00-052 91-00-052
Injector Nat Gas 33-30-302 common 33-30-302 common 33-30-302
Gasket 33-30-295 common 33-30-295 common 33-30-295
Gas Valve (Honeywell) 28-30-114 28-30-103 28-30-103 28-30-114 28-30-114
Pilot Burner c/w shear olive 28-90-148 common 28-90-148 common 28-90-148
Pilot Injector 28-90-153 28-90-153 common 28-90-153 common
Thermocouple 33-50-004 35-50-004 35-50-004 35-50-004 35-50-004
Ignition Electrode 28-90-156 common 28-90-156 common 28-90-156
Ignition Lead 28-02-172 28-02-172 28-02-172 28-02-172 28-02-172
Burner 33-00-124 common 33-00-124 common 33-00-124
Fuse Holder 28-07-050 28-07-050 28-07-050 28-07-050 28-07-050
Fuse 10 x 38 Axial 28-07-048 28-07-048 28-07-048 28-07-049 28-07-049
Fuse 10 x 38 Centrifugal 28-07-048 common 28-07-051 28-07-051 28-07-051 Fan/Motor Guard Assy Axial 28-09-042 28-09-040 28-09-036 28-09-042 28-09-042 Fan/Motor Guard Assy Cent 28-09-001 28-09-001 28-09-002 28-09-002 28-09-001
Fan Plenum Axial 33-10-670 33-10-578 33-10-592 33-21-154 33-10-670 Fan Plenum Cent 33-10-672 33-00-164 33-00-163 33-10-706 33-10-672
*Down Flow head 30 Deg 33-10-678 33-10-431 33-10-432 33-10-430 33-10-678 *Down Flow Head 90 Deg 33-10-675 33-20-508 33-20-509 33-20-507 33-10-675
*Vertical Louvre 33-20-873 common 33-20-873 common 33-20-873
*CP2 Control Panel 33-10-424 common 33-10-424 common 33-10-424
*Flue Ventor Assy 33-20-754 33-20-755 TBA TBA TBA
* Items marked are available as Optional Extras
Parts list Cont’d
Page 37
SECTION B
WARRANTY
REGISTRATION
INFORMATION
Warranty terms and Conditions
1. In the first instance any warranty claim or query concerning warranty, must be communicated to the Service Department at Benson Heating
2. Any part
manufactured
by Benson
Heating which
fails due to
defective
materials or
poor
workmanship
within twelve
months from the
despatch date
of the heater,
will be repaired
or replaced free
of charge,
inclusive of
parts and
labour.
3. Any part manufactured by Benson Heating which fails due to defective materials or poor workmanship within two years from the despatch date of the heater will be replaced free of charge on a parts only basis.
4. In addition to 2 and 3 above,
the heat
exchanger and
combustion
chamber carries
a ten year time
related warranty
based upon a
Page 38
S E C T I O N C
B A S I C U S E R
I N S T R U C T I O N S
10.0 Introduction
The following information is relevant to the Gas fired GUH Cabinet Heater range manufactured by Benson Heating. These heaters are manufactured within a strictly controlled quality system to ISO 9001.
All Benson Heating Cabinet Heaters are CE marked, having been found to satisfy the essential requirements of the following European Directives. Machinery Directive (89/392/EEC) Low Voltage Directive (73/23/EEC & 93/68/EEC) Electromagnetic Compatibility Directive (89/336/EEC & 91/31/EEC)
Product Liability Directive (65/374/EEC) Benson Heating support all new products
being supplied to their customers with a comprehensive information pack, and it is the responsibility of the owner, user, or hirer, of such products supplied by Benson Heating to ensure that operators are provided with the operator manual, and that they are suitably instructed regarding the purpose of the manual and safety instructions. In addition to this, operators must also be suitably and adequately trained in the use of the product.
Contained within the text of this manual, the words
'Caution' and 'Warning' are used to
highlight certain points.
Caution is used when failure to follow or
implement the instruction(s) can lead to a premature failure or damage being occasioned to the heater or its component parts.
Warning is used when failure to heed or
implement the instruction(s) can lead not only to component damage, but can also
lead to a hazardous situation being created where there is a risk of personal injury or death
10.1 Commissioning and hand over
Warning
As part of the commissioning programme, the commissioning engineer must go through the following with the operator.
(i) Lighting, shutdown, and operational information. (ii) Safety features, data plate, and labelling. (iii) The requirement for regular inspection ­especially if the heater is within a more demanding environment - and the need for regular servicing, carried out by competent and qualified engineers.
Caution
After approximately 100 hours of running, the tension on the fan belts must be checked to ensure that it is correct, and that the belts have not stretched. It is strongly advised that this is undertaken by the commissioning engineer, and not the operator.
10.2 Servicing
Warning
Servicing must be carried out on a regular basis, the maximum interval between services being one year. It is a requirement that only suitably qualified and competent persons are allowed to undertake the servicing.
Benson Heating advise that the planned service schedule as detailed in section 4.1 of the Installation, Commissioning and Servicing Manual is adopted by the user. Further details are available from either Benson Heating or from the commissioning engineer.
10.3 Start up procedure
Warning
If during the following sequence of operations the heater fails to operate correctly the fault should be traced and rectified before proceeding, if necessary referring to section 5.0 fault diagnosis.
Page 39
If for any reason the pilot light is extinguished
no attempt should be made
to re light it within three minutes
a) Switch on electrical supply b) Turn on gas supply, and open burner
viewing port c) Depress and hold in control start button
whilst operating igniter until pilot light is present
dl) Hold in start button for at least one minute to establish pilot - carefully release button confirming presence of pilot
Warning
If the pilot fails to become established do not attempt to re light for at least three minutes , if the pilot is established continue as follows.
e) Close burner viewing port f) Set the thermostat to the highest setting,
and the main burner will light then re-open the viewing port and check that the main burner is providing a good flame i.e. even, stable, and conical.
Caution
If the fan fails to operate within approximately two minutes and the heater goes to overheat it will shut down through breaking the circuit to the gas valve, the cause must be ascertained and rectified before re-ignition. Once the limit thermostat has tripped out it must be manually reset to allow re-ignition to take place.
g) Set controls as required
10.4 Ignition sequence automatic versions
Automatic control is by way of a Satronic controller (with automatic gas valve replacing the manual standing pilot valve) used in conjunction with a Satronic spark generator (which replaces the piezo igniter as fitted to manual units) , giving a maximum pilot sequence of 15 seconds. Flame supervision is via a flame sensor rod.
instead of the thermocouple as fitted to the manual units. The sequence is as follows: as per 10.3 a-i The start signal will ignite the pilot, once the flame proving has taken place the main gas valve will supply the burner and burner ignition will occur.
10.5 Stop procedure
(a) Set controller to off position. (b) The fan motor will continue to run until
heat dissipation allows the fan and limit stat to shut down the fan.
Caution
Do not use the main electrical isolator to turn off the heater, to do so can cause damage to the heat exchanger and combustion chamber, and thereby invalidate the warranty.
10.6 Shut down procedure
(
a) Follow steps 10.5 (a) and (b), when fan stops turn main electrical isolator off, and shut gas supply cock
10.7 Ventilation only
(
a) Set heat/ventilate switch to 'ventilate'.
10.8 Lockout situations
If either the burner or the fan and limit stat go to lockout, the lockout must be cleared manually before the ignition sequence can be re-initiated.
Caution
Repeated or frequent lockouts must be investigated and their cause determined by a qualified and competent engineer.
Page 40
Benson Heating Ludlow Road Knighton Powys LD7 1LP
Telephone 01547 528534 Facsimile 01547 520399 Email [email protected]
Web www.bensonheating.com
Benson Heating is a Division of Benson Climate Systems Ltd
Loading...