Benshaw RSM10, RSM10B, RSM11, RSM11B User Manual

BENSHAW
REDISTART MICRO II
INSTRUCTION MANUAL
RSM10/10B/11/11B SERIES
The Leader In
Solid State Motor Control
Technology
Publication #: 890015-03-08
TABLE OF CONTENTS
1. INTRODUCTION .......................................1
1.1 INTRODUCTION .......................................2
Using This manual ..........................................2
Benshaw Services ...........................................3
Features ................................................5
2. TECHNICAL SPECIFICATIONS ..............................7
2.1 TECHNICAL SPECIFICATIONS...............................8
CT (Current Transformer) Inputs ..................................8
Voltage Inputs.............................................8
Metering ................................................8
Real Time Clock............................................8
Output Relays .............................................8
Control Power.............................................9
Storage and Operating Conditions .................................9
DeviceNet (Embedded) .......................................9
Modbus (Optional) ..........................................9
EU Declaration of Conformity ...................................10
Overload Curves ...........................................11
Overload Curve Chart ........................................12
Low Voltage UL/CUL Fault Ratings ................................13
Low Voltage UL/CUL Fault Ratings ................................14
RediStart Micro II CPU Jumpers ..................................15
Computer Card JC11 Header Assignments ............................15
RediStart Micro II Power Card Jumpers ..............................15
3.INSTALLATION........................................17
3.1 INSTALLATION ........................................18
Site Preparation ............................................18
EMC Installation guidelines .....................................18
Installation Procedures........................................19
Preventative Maintenance ......................................23
Ventilation Requirements ......................................23
Remote RTD Module .........................................23
CT Mounting .............................................24
CT Ratio Scaling ...........................................24
RediStart Micro II Computer Card Jumpers ............................25
i
TABLE OF CONTENTS
4.OPERATION..........................................27
4.1 OPERATION ..........................................28
Main Display Messages .......................................28
Meter Display Pages .........................................29
Parameters...............................................33
Starter Modes .............................................33
Current Ramp Adjustment .....................................34
Programming A Kick Current....................................35
Jog at Set Speed ............................................35
Tachometer Feedback ........................................36
Programming The Motor Deceleration...............................37
PORT (Power Outage Ride Through) ...............................38
TruTorque Acceleration Ramp ...................................38
TruTorque Deceleration Ramp ...................................39
How Fault Classes Work.......................................40
Use of Overcurrent and Undercurrent ...............................41
Overload................................................41
Performing an Emergency Restart .................................43
5. PROGRAMMING .......................................45
5.1 PROGRAMMING: How To Program ............................46
Menu Buttons .............................................46
Menu Structure ............................................47
Viewing a Parameter .........................................48
Changing a Parameter ........................................48
5.2 PROGRAMMING: Quick Start ................................49
Motor FLA...............................................49
Serv. Fact (service factor) ......................................49
Start Mode ...............................................49
Stop Mode ...............................................49
Int. Curr. (initial current) ......................................50
Max. Curr. (maximum current) ...................................50
Ramp Time ..............................................50
Overload................................................51
Phase Orde (Phase Order) ......................................51
5.3 PROGRAMMING: Motor Nameplate ............................52
Motor FLA...............................................52
Serv. Fact (service factor) ......................................52
Motor RPMs ..............................................52
Energy Sav (energy saver) ......................................52
Source Volt (source voltage).....................................53
5.4 PROGRAMMING: Starter Setup - Starter Modes .....................54
Start Mode ...............................................54
Stop Mode ...............................................54
5.5 PROGRAMMING: Starter Setup - Forward1 Profile ....................55
Int. Curr. (initial current) ......................................55
Max. Curr. (maximum current) ...................................55
Ramp Time ..............................................55
Kick Curr. (kick current) .......................................56
Kick Time ...............................................56
ii
TABLE OF CONTENTS
5.6 PROGRAMMING: Starter Setup - Forward2 Profile ....................57
Forward #2 Ramp Profile ......................................57
Int. Curr. (initial current) ......................................57
Max. Curr. (maximum current) ...................................57
Ramp Time ..............................................57
Kick Curr. (kick current) .......................................58
Kick Time ...............................................58
5.7 PROGRAMMING: Starter Setup - Reverse1 Profile ....................59
Reverse #1 Ramp Profile.......................................59
Int. Curr. (initial current) ......................................59
Max. Curr. (maximum current) ...................................59
Ramp Time ..............................................59
Coast Time...............................................60
Kick Curr. (kick current) .......................................60
Kick Time ...............................................60
5.8 PROGRAMMING: Starter Setup - Reverse2 Profile ....................61
Reverse #2 Ramp Profile.......................................61
Int. Curr. (initial current) ......................................61
Max. Curr. (maximum current) ...................................61
Ramp Time ..............................................61
Coast Time...............................................62
Kick Curr. (kick current) .......................................62
Kick Time ...............................................62
5.9 PROGRAMMING: Starter Setup - Jog Cntrl Setup .....................63
Jog Curr. (jog current) ........................................63
Max. Time (maximum time).....................................63
Kick Curr (kick current) .......................................64
Kick Time ...............................................64
FWD Speed ..............................................64
REV Speed...............................................64
5.10 PROGRAMMING: Starter Setup - Tachometer Setup ..................65
FS Volts (Full Speed Volts) .....................................65
Stab Cnst (Stability Constant) ....................................65
Ramp#1 Tim..............................................65
Ramp#2 Tim..............................................65
TLoss Dela (Tachometer Signal Loss Delay)............................66
TLoss Mode (Tachometer Signal Loss Mode) ...........................66
5.11 PROGRAMMING: Starter Setup - Brake Ctl Setup ....................67
D.C. Injection Braking ........................................67
Current #1 ...............................................67
Time #1 ................................................67
Current #2 ...............................................67
Time #2 ................................................68
5.12 PROGRAMMING: Starter Setup - Decel Setup ......................69
V Level #1 ...............................................69
V Level #2 ...............................................69
V DCL Time (decel time).......................................69
TT DCL Tim (TruTorque deceleration time)............................70
TT DCL Tor (ending deceleration torque) .............................70
iii
TABLE OF CONTENTS
5.13 PROGRAMMING: Starter Setup - PORT CTL Setup ...................71
Fault Dly (Fault Delay)........................................71
Bypass Dly (Bypass Delay) .....................................71
Sense Time...............................................71
5.14 PROGRAMMING: Starter Setup - TruTorque Ramp ...................72
Int Torque (initial torque) ......................................72
Max Torque (maximum torque)...................................72
Ramp Time ..............................................72
TT Over Cu (TruTorque overcurrent trip) .............................73
Ovr Cur Dl (TruTorque overcurrent trip delay)..........................73
5.15 PROGRAMMING: Starter Setup - Heat/Anti-wind ...................74
Heat Curr. (heater current) .....................................74
5.16 PROGRAMMING: Motor Protection - Overload .....................75
Overload................................................75
5.17 PROGRAMMING: Motor Protection - Line Current ...................76
% Imbalanc (percent imbalance) ..................................76
Imbal Dela (imbalance delay) ....................................76
@ Stop Dly (current at stop delay) .................................76
% No C@Run (percent no current at run) .............................77
No C@R Dly (no current at run delay) ...............................77
5.18 PROGRAMMING: Motor Protection - Line Voltage ...................78
H/L Volts (high/low voltage) ...................................78
Delay Time ..............................................78
PH Dect Dl (Phase detect delay) ..................................78
5.19 PROGRAMMING: Motor Protection - Line Frequency..................79
High Freq. (high frequency) .....................................79
Low Freq. (low frequency)......................................79
Freq Delay (frequency delay) ....................................79
5.20 PROGRAMMING: Motor Protection - Ground Fault...................80
GND Fault (ground fault) ......................................80
GND Delay (ground delay) .....................................80
5.21 PROGRAMMING: Motor Protection - Shorted SCR ...................81
@ Ramp DLY (shorted SCR at ramp delay) ............................81
@ Stop DLY (shorted SCR at stop delay) ..............................81
5.22 PROGRAMMING: Motor Protection - Over Current ...................82
Current.................................................82
Detect Dly (detect delay).......................................82
Release Dl (release delay) ......................................82
5.23 PROGRAMMING: Motor Protection - Under Current ..................83
Current.................................................83
Detect Dly (detect delay).......................................83
Release Dl (release delay) ......................................83
5.24 PROGRAMMING: Motor Protection - Start Lockouts ..................84
Starts/Hou (starts per hour).....................................84
Time Start (time between starts) ..................................84
BKS Timer (backspin timer) .....................................84
iv
TABLE OF CONTENTS
5.25 PROGRAMMING: Motor Protection - Starting Timers..................85
UTS Timer (up-to-speed timer) ...................................85
Zero Speed...............................................85
5.26 PROGRAMMING: Motor Protection - Permissive Input.................86
Therm. In ...............................................86
5.27 PROGRAMMING: Motor Protection - Misc.........................87
Phase Orde (phase order) ......................................87
# Auto RST (number of auto resets) ................................87
No Main PW (no main power) ...................................87
5.28 PROGRAMMING: Motor Protection - Fault Classes ...................88
Fault Classes..............................................88
5.29 PROGRAMMING: Meters & Relays - Meter Setup ....................89
Meter #1 , Meter #2..........................................89
AutoRange...............................................90
Meter Rsts (meter resets).......................................90
Scroll Tim (scroll time) ........................................90
5.30 PROGRAMMING: Meters & Relays - Standard Relays .................91
Relay#1, K5 and Relay#2, K6 ....................................91
5.31 PROGRAMMING: Meters & Relays - Extended Relays .................92
Opt. #?, K?...............................................92
5.32 PROGRAMMING: Event Recorder .............................93
Event Recorder ............................................93
5.33 PROGRAMMING: Control Config - System Clock ....................95
System Clock .............................................95
5.34 PROGRAMMING: Control Config - System Password .................96
Password ...............................................96
5.35 PROGRAMMING: Control Config - Comm. Settings ..................97
COMM. Mode (communications mode) ..............................97
COM Addres (communications address) .............................97
COM Delay (communications delay)................................97
MB:Baud (MODBUS baud rate)...................................98
MB:Com T/O (MODBUS communications timeout) .......................98
DN:MAC ID (DeviceNet MAC ID) .................................98
DN:Baud (DeviceNet baud rate) ..................................98
DN:InAssy (DeviceNet input assembly) ..............................99
DN:OutAssy (DeviceNet output assembly) ............................99
DN:T/O Act (DeviceNet timeout action) .............................99
DN:Rev (DeviceNet interface revision) ..............................99
5.36 PROGRAMMING: Control Config - Options List.....................100
Options List ..............................................100
5.37 PROGRAMMING: Control Config - Software Part# ...................101
Software Part# ............................................101
5.38 PROGRAMMING: Factory Setup - Hardware Setup ...................102
C.T. Ratio ...............................................102
Relay Card...............................................102
v
TABLE OF CONTENTS
5.39 PROGRAMMING: Factory Setup - Factory Control ...................103
FACT Pass. (factory password) ...................................103
Reset Def (reset to default parameters)...............................103
CLR Events (clear event log) ....................................103
CLR Pass. (clear password) .....................................103
Cal Volt L1, L2, L3 (calibrate voltage meter)............................103
Cal Curr L1, L2, L3 (calibrate current meter) ...........................104
5.40 PROGRAMMING: RTD Setup - RTD Module Setup ...................105
Mod#1 Addr (module #1 address) .................................105
Mod#2 Addr (module #2 address) .................................105
#RTDs Mod1 (number of RTDs on module #1) ..........................105
#RTDs Mod2 (number of RTDs on module #2) ..........................105
Temp Scale (temperature scale) ...................................105
5.41 PROGRAMMING: RTD Setup - RTD SetPnts 1-8 .....................106
RTD#? Grp (RTD #? Group).....................................106
RTD#? Warn (RTD #? warning level) ...............................106
RTD#? Alm (RTD #? alarm level)..................................106
5.42 PROGRAMMING: RTD Setup - RTD SetPnts 9-16 ....................107
RTD#? Grp (RTD #? Group).....................................107
RTD#? Warn (RTD #? warning level) ...............................107
RTD#? Alm (RTD #? alarm level)..................................107
6. TROUBLESHOOTING ....................................109
6.1 TROUBLESHOOTING ....................................110
LED Diagnostics ...........................................110
Meter Tests ..............................................111
Event Recorder ............................................111
Fault/Log Codes ...........................................112
General Troubleshooting Charts ..................................116
Spare Parts...............................................118
SCR Replacement ...........................................119
7. DRAWINGS ..........................................121
7.1 DRAWINGS ..........................................122
RediStart Micro II Computer Card Diagram ...........................122
RediStart Micro II Power Card Layout ...............................123
Old RediStart Micro Power Card Layout .............................124
RediStart Micro II Four (4) Relay Card Layout ..........................125
RediStart Micro II Seven (7) Relay Card Layout .........................125
RediStart Micro II RS-232 Communications Card Layout ....................126
RediStart Micro II RS-485 Communications Card Layout ....................126
RediStart Micro II RS-232/485 Communications Card Layout .................127
RediStart Micro II Reversing/Braking Card Layout .......................127
Modbus Master Card (for Remote RTD Module) .........................128
RediStart Micro II Display Cut-out .................................129
vi
TABLE OF CONTENTS
8. PARAMETER LIST ......................................131
8.1 Parameter List .........................................132
RediStart Micro II Parameter List ..................................132
Quick Start...............................................132
Motor Nameplate ...........................................132
Starter Setup..............................................132
Motor Protection ...........................................134
Meters & Relays............................................137
Event Recorder ............................................137
Control Config ............................................137
Factory Setup .............................................138
RTD Setup ...............................................138
vii
TABLE OF CONTENTS
viii
1. INTRODUCTION
1.1 INTRODUCTION
Using This manual
Layout This manual is divided into eight sections. Each section contains topics related to the
Parameter List The last chapter of the manual is a parameter list. This list gives the user a place to
Symbols There are two symbols used in this manual to highlight important information. The
section. The sections are as follows;
Introduction - Basic RediStart Micro II information.
Technical Specifications - RediStart Micro II specifications.
Installation - Information on installing the RediStart Micro II.
Operation - Information on how the starter operates.
Programming - Programming the RediStart Micro II.
Troubleshooting - Diagnosing RediStart Micro II problems.
Drawings - RediStart Micro II layout drawings.
Parameter List - List allowing user to record programmed values.
enter the programmed value for each parameter and also gives the page number where the description of the parameter can be found. This list can be used as a quick reference to find the information on a parameter.
symbols appear as the following;
Electrical hazard that could result in injury or death.
Caution that could result in damage to the starter or motor. Highlight marking an important point in the documentation.
2
1.1 INTRODUCTION
Benshaw Services
General Information Benshaw offers its customers the following services:
Start-Up Services Benshaw technical field support personnel are available to assist customers with the
On-Site Training Services Benshaw technical field support personnel are available to conduct on-site training on
Technical Support Benshaw technical support personnel are available (at no charge) to answer customer
Documentation Benshaw provides all customers with:
Start-up services.
On-site training services.
Technical support.
Detailed documentation.
Replacement parts.
NOTE: Information about products and services is available by contacting Benshaw.
initial start-up of the RediStart Micro II. Information about start-up services and fees are available by contacting Benshaw.
RediStart Micro II operations and troubleshooting.
questions and provide technical support over the telephone. For information about contacting technical support personnel, refer to Contacting Benshaw on page 4.
Operations manual.
Wiring diagram.
All drawings are produced in AutoCAD© format. The drawings are available on standard 3.5” diskettes or via e-mail by contacting Benshaw.
On-Line Documentation All RediStart MicroII documentation is available on-line at www.benshaw.com.
Replacement Parts Spare and replacement parts can be purchased from Benshaw.
3
1.1 - INTRODUCTION
Contacting Benshaw
Contacting Benshaw Information about Benshaw products and services is available by contacting Benshaw at
one of the following offices:
Benshaw Inc. Corporate Headquarters
1659 E. Sutter Road
Glenshaw, PA 15116
United States of America
Phone: (412) 487-8235
Fax: (412) 487-4201
Benshaw Canada Controls Inc.
550 Bright Street. E.
Listowel, Ontario N4W 3W3
Canada
Phone: (519) 291-5112
Fax: (519) 291-2595
Benshaw West
14715 North 78th Way, Suite 600
Scottsdale, AZ 85260
United States of America
Phone: (480) 905-0601
Fax: (480) 905-0757
E-mail: usatechsupport@benshaw.com
cantechsupport@benshaw.com
Technical support for the BC4/BC6 Series is available at no charge by contacting Benshaw’s
customer service department at one of the above telephone numbers. A service technician is
available Monday through Friday from 8:00 a.m. to 5:00 p.m. EST.
z NOTE: An on-call technician is available after normal business hours and on weekends
by calling Benshaw and following the recorded instructions.
To help assure prompt and accurate service, please have the following information
available when contacting Benshaw:
Name of Company
Telephone number where the caller can be contacted
Fax number of caller
Benshaw product name
Benshaw model number
Benshaw serial number
Name of product distributor
Approximate date of purchase
System Voltage
FLA of motor attached to Benshaw product
A brief description of the application
4
1.1 INTRODUCTION
General
Chassis or NEMA 1, 4, 12, or 3R enclosure
Protection (ANSI standard numbers given)
51 - Electronic motor overload (Off, class 1 to 40, or bypass during start)
86 - Overload lockout
48 - Adjustable up-to-speed timer (off; 0 to 300 seconds)
59/27 - Adjustable over/under voltage protection
46 - Adjustable line to average current imbalance
81 - Adjustable high and low frequency protection
Single phase protection
66 - Adjustable starts per hour (off or 1 to 20 starts)
Adjustable time between starts (off or 1 to 600 minutes)
Backspin timer (off or 1 to 200 minutes)
51 - Over current detection (Off or 50 to 800%) and time (0.1 to 90.0 sec. in 0.1 sec. intervals)
37 - Undercurrent detection (Off or 10 to 100% and time (0.1 to 90.0 sec. in 0.1 sec. intervals)
51G - Ground fault detection (Off or 1 to 100 amps) and time (0.1 to 90.0 sec. in 0.1 sec. intervals)
Over-current, undercurrent, and ground fault can each be set to trip or activate a relay
50 - Instantaneous electronic over-current trip
Shorted SCR detection
47 - Phase rotation selectable ABC, CBA, or Ins (insensitive)
38/49 - Remote Mountable RTD protection package, 8 or 16 RTD inputs (optional)
PORT (power outage ride through) available with external 120VAC.
Features
Control
Two programmable current ramp profiles selectable at any time via 120 volt input
Initial current, maximum current, and ramp time adjustments for each ramp
Kick Current and time adjustments for each ramp
TruTorque acceleration and deceleration profiles
Adjustable deceleration profiles (to eliminate water hammer)
Adjustable brake profile
Energy saver (on or off)
Local start/stop controls
Emergency reset capability
Tachometer ramp control (requires 0-5VDC tachometer feedback signal)
Input/Output and Display
Plain English operation via back lit LCD display interface
LCD and LED status and diagnostics (full fault annunciation)
Programmable metering (amps, volts, frequency, overload, power factor, elapsed time, watts, VARs, watt-hours, VA, Current Imbalance, Ground Fault Current, RTD temperatures)
Programmable relay outputs
Latched fault relay output
Real time clock
Time stamped event recorder
Password protection
Battery backed-up starter parameters and lockout times
5
2. TECHNICAL SPECIFICATIONS
2.1 TECHNICAL SPECIFICATIONS
CT (Current Transformer) Inputs
Conversion Calibrated RMS, 12 samples per cycle
Range 0.01 to 1.5 × phase CT primary amps set point
Accuracy ±3.5% of phase CT primary amps set point
Frequency 23 to 72 Hz
Current Withstand - 2.0 × CT primary amps set point (CT ratio parameter) - continuous
- 10 × CT primary amps set point (CT ratio parameter) - 30 seconds
- 55 × CT primary amps set point (CT ratio parameter) - 1 seconds
Voltage Inputs
Conversion Calibrated RMS, 12 samples per cycle
Range 1000VAC to 9999VAC
Accuracy ±3.5% of full range
Current ±5%, 0 to 9999Amps
Voltage ±5%, 0 to 9999Volts
Watts ±5%, 0 to 6553kW
Volt-Amps Reactive ±5%, 0 to 6553kVAR
Volt-Amps ±5%, 0 to 6553kVA
WH ±5%, 0 to 6553MWH
PF ±3%, -0.01 to +0.01
Metering
Accuracy ±1 minute per month
Range 1/1/1970 to 1/1/2069
Fault Relay - SPDT - Form C
- 2A, 125VAC, resistive
- 1A, 125VAC, 0.4 PF
- 2A, 30VDC resistive
- 100VA inrush
Output Relay #1 & #2 - SPDT - Form C
- 16A, 250VAC resistive
- 8A, 250VAC 0.4 PF
- 16A, 30VDC resistive
- 2000VA inrush
8
Real Time Clock
Output Relays
2.1 TECHNICAL SPECIFICATIONS
Four Relay Card - DPDT - Dual Form C
- 5A, 250VAC, resistive
- 2A, 250VAC, 0.4 PF
- 5A, 30VDC, resistive
- 500VA inrush
Seven Relay Card - SPDT - Form C
- 8A, 250VAC resistive
- 4A, 250VAC 0.4 PF
- 8A, 30VDC resistive
- 800VA inrush
Voltage 120VAC, ±15%
240VAC, ±15% (Optional)
Frequency 50 to 60hz
Power Consumption Varies for required control.
Fuse Time delay control circuit protection fuses.
Storage -20ºC (-4°F) to +60°C (+140°F)
0% to 95% relative humidity, non-condensing
Control Power
Storage and Operating Conditions
Operating 0°C (+32°F) to +50°C (+122°F)
0% to 95% relative humidity, non-condensing
DeviceNet (Embedded)
Manual Available at www.benshaw.com or from your Benshaw sales office.
EDS File Available at www.benshaw.com or from your Benshaw sales office.
Device Type Softstart Starter
I/O Slave Messaging Polling
Baud Rates - 125K
Conformance Self tested with ODVA (open DeviceNet Vendor Association) software.
- 250K
- 500K
Modbus (Optional)
Manual Available at www.benshaw.com or from your Benshaw sales office.
Type Modbus RTU
Connections - RS-232
- RS-485
Baud Rates - 2400
- 4800
- 9600
9
2.1 TECHNICAL SPECIFICATIONS
EU Declaration of Conformity
According to the EMC – Directive 89/336/EEC as Amended by 92/31/EEC and 93/68/EEC
Product Category: Motor Controller
Product Type: Reduced Voltage Solid State Motor Controller
Model Numbers: RSM6, RSM7, RSM10, RSM11, RMB6, MVRSM12/18
Manufactures Name: Benshaw, Inc.
Manufacture’s Address: 1659 East Sutter Road
The before mentioned products comply with the following EU directives and Standards:
Safety: UL 508 Standard for Industrial Control Equipment covering devices for starting,
EMC: EN 50081-2 Emissions Radiated/Conducted
The technical files and other documentation are on file at Benshaw, Inc. and controlled by the Product Engineering Group. Benshaw, Inc. has internal production control systems that ensures compliance between the manufactured products and the technical documentation.
Neil Abrams Harry Hagerty Charles E. Cook Quality Control Manager Advanced Controls and Drives Manager Product Development Manager
Glenshaw, PA USA 15116
stopping, regulating, controlling, or protecting electric motors with ratings of 1500 volts or less.
EN 55011/05.98+A1:1999
EN 50082-2 Immunity/Susceptibility which includes:
EN 61000-4-2 Electrostatic Discharge EN 61000-4-3 Radiated RF EN 61000-4-4 Electrical Fast Transient/Burst EN 61000-4-6 Injected Currents
10
2.1 TECHNICAL SPECIFICATIONS
Overload Curves
General The RediStart Micro II comes with forty (40) standard overload curves. The 100% (no
Curves The overload can be set to;
Trip Time Accuracy ±2 seconds up to 30 seconds
trip) point is the motor FLA setting multiplied by the service factor. These curves are shown on the next page.
NOTE: The user can display the overload by setting the overload to Off. The overload can also be set to BYP (Bypass), which limits the charging current during ramping to 90%. One the unit has reached UTS (up-to-speed), the overload can charge the remaining 10%. This is useful on extremely large centrifugal loads such as centrifuges.
NOTE: When the overload counter is at a number other than 0%, the time to trip will be lowered by this percentage.
NOTE: In heavy duty DC braking application, the overload settings may be limited to protect the starter and motor from potential damage.
Caution must be taken when using the Bypass mode. The starter does not overload protect the unit during the start.
OFF - no thermal overload
1-40 - class 1 through 40 overload in steps of 1.
BYP - overload bypassed during starting, class 10 once up-to-speed
11
2.1 TECHNICAL SPECIFICATIONS
RediStart Micro II Overload Curves
10000
Overload Curve Chart
Class 40
Class 35
Class 30
1000
100
10
Class 40
Class 25
Class 20
Class 15
Class 10
Class 7
Class 5
Class 3
Class 2
Class 1
Class 1
12
1
0 100 200 300 400 500 600 700 800
Current as Percent of FLA
Rating
Short Circuit
Catalog Number Trip Plug
HPD63F160 1200-1600A 85kA
HPD63F160 1200-1600A 85kA
85kA
CND63B 1200A
CND63B 800A
85kA
CND63B 1200A
CND63B 800A
85kA
CND63B 1200A
CND63B 800A
65kA
CLD63B 600A
CJD63B 400A
65kA
CLD63B 600A
CJD63B 400A
2.1 TECHNICAL SPECIFICATIONS
Low Voltage UL/CUL Fault Ratings
CED63B 100A 42KA
CED63B 60A 42KA
CED63B 60A 42KA
Short Circuit
Max. Fuse
Fuse Protected Rating Current Limiting Circuit Breaker Protected Rating
Fuse Class
Unit
Withstand
125%
Rating
Current
Rating
1600A 100kA
Current Rating
Rating
(amps)
2000A 50kA
1600A 100kA
2000A 50kA
800A 100kA
RK-1
J, 600VAC T,
800A 100kA
RK-1
J, 600VAC T,
800A 100kA CFD63B 400A 65kA
J, 600VAC T,
RK-1
600A 100kA CFD63B 400A 65kA
J, 600VAC T,
RK-1
400A 100kA CFD63B 250A 65kA
J, 600VAC T,
RK-1
400A 100kA CFD63B 225A 65kA
J, 600VAC T,
RK-1
350A 100kA CFD63B 225A 42KA
RK-1
J, 600VAC T,
225A 100kA CFD63B 225A 42KA
RK-1
J, 600VAC T,
225A 100kA CED63B 125A 42KA
RK-1
J, 600VAC T,
225A 100kA CED63B 100A 42KA
RK-1
J, 600VAC T,
60A 100kA
100A 50KA
60A 100kA
100A 50KA
40A 100KA
60A 50KA
RK-1, G, CD
J, 600VAC T,
TABLE CONTINUED NEXT PAGE
FLA (amps)
96 120 42kA
77 96 42kA
65 81 42kA
52 65 42kA RK-1
40 50 42kA RK-1
960 1200 85kA L
840 1050 85kA L 1600A 100kA
720 900 42kA L 1600A 100kA
590 737 42kA L 1400A 100kA
477 596 42kA
361 421 42kA
302 377 42kA
240 300 42kA
180 225 42kA
156 195 42kA
1200 1440 85kA L
124 155 42kA
27 33.75 42KA
13
2.1 TECHNICAL SPECIFICATIONS
Rating
Short Circuit
CED63B 15A 65KA
CED63B 30A 65KA
CED63B 20A 65KA
Catalog Number Trip Plug
CED63B 80A 65KA
CED63B 50A 65KA
CED63B 40A 65KA
Low Voltage UL/CUL Fault Ratings
TABLE CONTINUED PREVIOUS PAGE
Short Circuit
Max. Fuse
Fuse Protected Rating Current Limiting Circuit Breaker Protected Rating
Fuse Class
Unit
Withstand
125%
Rating
Current
Rating
35A 100KA
Current Rating
Rating
(amps)
J, 600VAC T,
45A 50KA
RK-1
20A 100KA
30A 50KA
RK-1
J, 600VAC T,
15A 100KA
20A 50KA
RK-1
J, 600VAC T,
12A 100KA
15A 50KA
RK-1
J, 600VAC T,
8A 100KA
10A 50KA
RK-1
J, 600VAC T,
5A 100KA
7A 50KA
RK-1
J, 600VAC T,
14
FLA (amps)
21 26.25 42
14 17.5 42
11 13.75 42
7.6 9.5 42
3.4 4.25 42
4.8 6 42
2.1 TECHNICAL SPECIFICATIONS
RediStart Micro II CPU Jumpers
Jumper Description Position 1-2 Position 2-3 Standard
JPC5 LCD Start Button Enable Disable 1-2 JPC7 O/L Reset Auto/Manual Automatic Manual 2-3 JPC8 Display Format Standard Local Bus 1-2 JPC12 SCR Firing Pulse Block In JPC13 LCD Stop Button Enable Disable 1-2 JPC14 RAM Size 8K RAM 2K RAM 1-2 JPC15 PWM/ADDR16 ADDR16 PWM 1-2,3-4 JPC16 RS-232 Communications Enable Disable Out JPC17 Equip Forward Bypass Yes No 2-3 JPC18 Equip Reverse Bypass Yes No 2-3 JPC19 Fault Reset Automatic Manual 2-3 JPC25 Synchronous Application Yes No Out JPC27 Micro Enable/ADDR17 ADDR17 Enable 1-2,3-4
(In - 2-pos. jumper) (Out - 2-pos. jumper)
Computer Card JC11 Header Assignments
Position Assignment
1-16 Enables Reversing. 2-15 Enables D.C. Braking. 3-14 Starter Equipped with MODBUS master card (for RTD module). 4-13 Enables Motor Winding Heater/Anti-windmilling Brake. 5-12 Not used. 6-11 Enables emergency reset. 7-10 Enables light duty braking (2-15 must also be installed for this option). 8-9 Not used.
RediStart Micro II Power Card Jumpers
Jumper Description Position 1-2 Position 2-3 Standard
JPP2 Line Synching Line to Line Line to Neutral 1-2 JPP3 Line Synching Line to Line Line to Neutral 1-2 JPP4 Line Synching Line to Line Line to Neutral 1-2
NOTE: Jumpers JPP2, JPP3, and JPP4 do not apply to the BIPC-300030-xx Power Card.
15
2.1 TECHNICAL SPECIFICATIONS
16
3. INSTALLATION
3.1 INSTALLATION
Site Preparation
General Before the installation of the RediStart Micro II, the site should be prepared. The
Connection Cables The connection cables for the starter must have the correct NEC/C.S.A. current rating
Site Requirements The installation site must adhere to the applicable starter NEMA rating. For optimal
Mounting The starter must be mounted so the heat sink fins are vertically oriented in an area
customer is responsible for:
Providing the correct power source.
Selecting the control mechanism.
Providing the connection cables and associated hardware.
Ensuring the installation site meets all environmental specifications for the
enclosure NEMA rating.
for the unit being installed. Depending upon the model, the connection cables can range from a single #14 AWG conductor to four 750 MCM cables.
performance, the installation site must meet the following specifications, unless equipment (such as a heater or air conditioner) was added to the unit for operation outside of these ranges:
Temperature: 0°C (+32F) to 40°C (+104°F).
Humidity: 20% to 95% non-condensing.
Airways: Clearances are provided around all heat sinks.
Altitude: Less than 3300 feet (1000 meters) above sea level.
NOTE: The starter rating must be derated 1% for every 330 feet (100 meters) above 3300 feet (1000 meters).
that does not experience excessive shock or vibration. All models require airway passages around the heat sink. During normal operation the heat sink may reach 194 degrees Fahrenheit (90 degrees Centigrade). Do not install the starter in direct contact with any materials that cannot withstand these temperatures.
EMC Installation guidelines
General In order to help our customers comply with European electromagnetic compatability
Enclosure Install the product in a grounded metal enclosure.
Grounding Connect a grounding conductor to the screw or terminal provided as standard on each
Wiring Wire in an industrial application can be divided into three groups: power control and
Filtering To comply with Conducted Voltage Limits a 0.33 uF capacitor should be connected
standards, Benshaw Inc. has developed the following guidelines.
Attention: This product has been designed for Class A equipment. Use of the product in domestic environments may cause radio interference, in which case the installer may need to use additional mitigation methods.
controller. Refer to layout/power wiring schematic for grounding provision location.
signal. The following recommendations for physical separation between these groups are provided to reduce the coupling effect;
Different wire groups should cross at 90 degrees inside an enclosure.
Minimum spacing between different wiring groups in the same tray should be six inches.
Wire runs outside an enclosure should be run in conduit or have shielding/armor with equivalent attenuation.
Different wire groups should be run in separate conduits.
Minimum spacing between conduits containing different wire groups should be three inches (8cm).
between each incoming power line and ground at a point nearest to where the incoming power enters the enclosure.
18
3.1 INSTALLATION
Installation Procedures
General Information Installation of some models may require halting production during installation. If
Safety Precautions To ensure the safety of the individuals installing the starter, and the safe operation of
applicable, ensure that the starter is installed when production can be halted long enough to accommodate the installation.
Before installing the starter, ensure:
The wiring diagram (supplied separately with the starter) is correct for the
required application. The starter is the correct current rating for the motor being started.
All of the installation safety precautions are followed.
The correct power source is available.
The starter control method has been selected.
The necessary installation tools and supplies are obtained.
The installation site meets all environmental specifications for the starter
NEMA/CEMA rating. The motor being started has been installed and is ready to be started.
Any power factor correction capacitors (PFCC) are installed on the power source
side of the starter and not on the motor side.
NOTE: Failure to remove power factor correction or surge capacitors from the load side of the starter will result in serious damage to the starter which will not be covered by the starter’s warranty. The capacitors must be powered from the line side of the starter. The up-to-speed contact can be used to energize the capacitors after the motor has reached full speed.
the starter, observe the following guidelines:
Ensure that the installation site meets all of the required environmental
conditions (Refer to Site Preparation, page 18). LOCK OUT ALL SOURCES OF POWER.
Install circuit disconnecting devices (i.e., circuit breaker, fused disconnect or
non-fused disconnect) if they were not previously installed by the factory as part of the package.
Install short circuit protection (i.e., circuit breaker or fuses) if not previously installed by the factory as part of the package. See page 14 for the fault rating table.
Follow all NEC (National Electrical Code) and/or C.S.A. (Canadian Standards Association) standards.
Remove any foreign objects from the interior of the enclosure.
Ensure that wiring is installed by an experienced electrician.
Ensure that the individuals installing the starter have protective eye wear and clothing.
The opening of the branch circuit protective device may be an indication that a fault current has been interrupted. To reduce the risk of electrical shock, current carrying parts and other components of the starter should be inspected and replaced if damaged.
19
3.1 INSTALLATION
Installation To begin installation:
Control Wiring The control wiring should be connected to suit the customers needs. The control
Read and follow all of the installation safety precautions.
Procure the necessary installation tools and any supplies.
Ensure the site has sufficient lighting for safe installation.
Move the starter to the installation site.
Ensure that the starter is positioned so that the cabinet door has ample
clearance, and all of the controls are accessible. DO NOT install the starter in direct contact with any materials that cannot
withstand the maximum heat sink temperature of 194 degrees Fahrenheit (90 degrees Centigrade). All models require airway passages around the heat sink for proper cooling.
If the starter is to be wall mounted:
Mount the starter on the applicable surface using the appropriate hardware.
NOTE: Moving some models may require more than one individual or lifting equipment (e.g., forklift, crane).
terminals on the control cards are as follows:
RediStart Micro II Power Card (refer to card layout on page 123):
TBP1-1 24VDC common for relay and reversing card
TBP1-2 24VDC power for relay and reversing card
TBP2-1 Run relay neutral
TBP2-2 Run relay live
TBP2-5 Run relay holding contact
TBP3-1 General fault contact N.C. (not faulted)
TBP3-2 General fault contact common
TBP3-3 General fault contact N.O. (not faulted)
TBP3-4 Programmable relay #1 N.O.
TBP3-5 Programmable relay #1 common
TBP3-6 Programmable relay #1 N.C.
TBP3-7 Programmable relay #2 N.O.
TBP3-8 Programmable relay #2 common
TBP3-9 Programmable relay #2 N.C.
RediStart Micro II computer card inputs (refer to card layout on page 122):
JC13-1 Heat sink thermal switch or external starter trip input.
JC13-2 AC neutral.
JC13-3 Run confirm.
JC13-4 Jog operation select.
JC13-5 Not Used.
JC13-6 Reverse operation select (for Jog and Reversing).
JC13-7 Brake disable.
JC13-8 Zero Speed input or motor winding heater/anti-windmilling brake select.
JC13-9 Ramp #2 operation select.
JC13-10 External motor thermal overload reset.
JC13-11 External computer reset.
JC13-12 AC neutral.
20
3.1 INSTALLATION
RediStart Micro II Four (4) Relay Card (refer to card layout on page 125):
TB2-1 Optional programmable relay #1 N.O.
TB2-2 Optional programmable relay #1 N.C.
TB2-3 Optional programmable relay #1 common
TB2-4 Optional programmable relay #1 N.O.
TB2-5 Optional programmable relay #1 N.C.
TB2-6 Optional programmable relay #1 common
TB2-7 Optional programmable relay #2 N.O.
TB2-8 Optional programmable relay #2 N.C.
TB2-9 Optional programmable relay #2 common
TB2-10 Optional programmable relay #2 N.O.
TB2-11 Optional programmable relay #2 N.C.
TB2-12 Optional programmable relay #2 common
TB2-13 Optional programmable relay #3 N.O.
TB2-14 Optional programmable relay #3 N.C.
TB2-15 Optional programmable relay #3 common
TB2-16 Optional programmable relay #3 N.O.
TB2-17 Optional programmable relay #3 N.C.
TB2-18 Optional programmable relay #3 common
TB2-19 Optional programmable relay #4 N.O.
TB2-20 Optional programmable relay #4 N.C.
TB2-21 Optional programmable relay #4 common
TB2-22 Optional programmable relay #4 N.O.
TB2-23 Optional programmable relay #4 N.C.
TB2-24 Optional programmable relay #4 common
RediStart Micro II seven (7) Relay Card (refer to card layout on page 125):
TB2-1 Optional programmable relay #1 N.O.
TB2-2 Optional programmable relay #1 common
TB2-3 Optional programmable relay #1 N.C.
TB2-4 Optional programmable relay #2 N.O.
TB2-5 Optional programmable relay #2 common
TB2-6 Optional programmable relay #2 N.C.
TB2-7 Optional programmable relay #3 N.O.
TB2-8 Optional programmable relay #3 common
TB2-9 Optional programmable relay #3 N.C.
TB2-10 Optional programmable relay #4 N.O.
TB2-11 Optional programmable relay #4 common
TB2-12 Optional programmable relay #4 N.C.
TB2-13 Optional programmable relay #5 N.O.
TB2-14 Optional programmable relay #5 common
TB2-15 Optional programmable relay #5 N.C.
TB2-16 Optional programmable relay #6 N.O.
TB2-17 Optional programmable relay #6 common
TB2-18 Optional programmable relay #6 N.C.
TB2-19 Optional programmable relay #7 N.O.
TB2-20 Optional programmable relay #7 common
TB2-21 Optional programmable relay #7 N.C.
21
3.1 INSTALLATION
Power Wiring Thread the power and motor cables through a connector into the enclosure. Strip
away the motor cable insulation and apply anti-oxidation paste to the conductors.
Attach the motor cables:
Use the T1, T2 and T3 lugs or terminals.
Attach the power source cables:
Use the L1, L2 and L3 lugs or terminals.
NOTE: For larger starters, thread each incoming power cable through its applicable current transformer (CT). The cables must be threaded through the CTs in the same direction to insure proper operation (Refer to the wiring diagram supplied with the starter).
The following is a list of the recommended crimp-on wire connectors manufactured by Penn-union Corp.
Wire Size Part # Wire Size Part #
1/0 BLU-1/0S20 500 MCM BLU-050S2
2/0 BLU-2/0S4 600 MCM BLU-060S1
3/0 BLU-3/0S1 650 MCM BLU-065S5
4/0 BLU-4/0S1 750 MCM BLU-075S
250 MCM BLU-025S 800 MCM BLU-080S
300 MCM BLU-030S 1000 MCM BLU-100S
350 MCM BLU-035S 1500 MCM BLU-150S
400 MCM BLU-040S4 2000 MCM BLU-200s
450 MCM BLU-045S1
Power Factor Capacitors Power factor correction capacitors and surge capacitors MUST NOT be connected
Electro-Mechanical Brakes If an electro-mechanical brake is used with the RediStart Micro II, it must be powered
Finishing After all of the safety precautions and installation procedures have been completed,
between the RediStart Micro II and the motor. These devices can damage the SCR’s in the package during ramping. These devices appear like a short circuit to the SCR when it turns on, which causes a di/dt level greater than the SCR can handle. If used, power factor correction capacitors or surge capacitors must be connected ahead of the RediStart Micro II. Programmable relay #2 (K6) can be set to an up-to-speed (UTS) contact (up-to-speed is the default setting) and then used to pull-in a contactor to connect the capacitors after the motor has reached full speed.
NOTE: The motor manufacturer should be contacted before surge capacitors are removed from the motor terminal box.
from the line side of the starter to ensure full voltage is applied to the brake during a start so it will properly release. Programmable relay #1 (K5) can be set to a run contact (run is the default setting) and then used to pull-in a contactor to power the brake whenever the starter is providing power to the motor.
verify that the following settings are correct for the application:
Current transformer scaling switches.
Hardware deceleration/braking control (JPC3).
RediStart Micro II computer card jumpers.
22
3.1 INSTALLATION
Preventative Maintenance
General Information Preventive maintenance performed on a regular basis will help ensure that the starter
Preventive Maintenance During Commissioning;
continues to operate reliably and safely. The frequency of preventive maintenance depends upon the type of maintenance and the installation site’s environment.
NOTE: Preventive maintenance should always be performed by a trained technician.
Torque all power connections during commissioning. This includes pre-wired
equipment. Check all of the control wiring in the package for loose connections.
For the first month after the starter has been put in operation;
Re-torque all power connections every two weeks. This includes pre-wired
equipment. Inspect the cooling fans after two weeks to ensure proper operation.
After the first month of operation;
Re-torque all power connections every year.
Clean any accumulated dust from the starter using a clean source of compressed
air. Inspect the cooling fans every three months to ensure proper operation.
Clean or replace any air vent filters on the starter every three months.
NOTE: If mechanical vibrations are present at the installation site, inspect the
connections more frequently.
Ventilation Requirements
General Provisions should be provided with the starter installation to ensure that the
temperature inside the enclosure never rises above 50°C. If the temperature inside the enclosure is too high, the starter can be damaged or it’s life can be reduced. As a general rule of thumb, the following ventilation guidelines can be followed.
Current Range Bottom of Enclosure Top of Enclosure
< 200 amps Fans or grills depending on enclosure size 200 to 300 amps 2 x 4” grills (12 sq.in.) 2 x 4” grills (12 sq.in.) 301 to 400 amps 1 x 4” fan (115 cfm) 2 x 4” grills (12 sq.in.) 401 to 600 amps 2 x 4” fan (230 cfm) 2 x 6” grills (28 sq.in.) 601 to 700 amps 2 x 6” fan (470 cfm) 2 x 6” grills (28 sq.in.) > 700 amps Consult factory Consult Factory
Benshaw installs starters under 124 amps with the heat sink protruding from the back of the enclosure. This allows a small enclosure size while still maintaining the cooling capability of the starter. The starter produces 4 watts of heat per amp of current and 14 square inches of enclosure wall are required per watt of heat generation. Contact Benshaw and ask for the enclosure sizing technical note for more information concerning starters in sealed enclosures.
Remote RTD Module
General The RediStart Micro II can have up to 2 RTD modules installed. The RTD modules
MODBUS Master Card The MODBUS master card is installed on the RediStart Micro II CPU card to allow
can be installed in the cabinet with the RediStart Micro II or they can be installed remotely at the motor. Refer to the Remote RTD Module manual for details on this module.
the starter to communicate with the RTD Module.
23
3.1 INSTALLATION
CT Mounting
General On larger horsepower starters, the current transformers have to be installed on the
power wire. To ensure that the CT is not damaged by rubbing on the power lug, the CT should be tie wrapped to the power wire 3 inches from power lug using 2 tie wraps in a cross pattern. Refer to the following diagram. The CTs must be installed so that the white dot is facing the LINE side of the starter with the proper CT installed for each phase. The metering functions will not work correctly if the CTs are not installed correctly.
CUSTOMER MUST FASTEN CT
TO POWER WIRE WITH TWO 1/4"
NYLON WRAPS TO PREVENT
MOVEMENT DURING RUNNING
MUST BE A 3" (MIN.) SPACE BETWEEN CT
AND TOP OF LUG
TOP VIEW DETAIL SIDE VIEW DETAIL
CT Ratio Scaling
General Information The motor current signal scaling is set according to the motor current specified when
the starter is ordered. To ensure accurate operation, the motor current signal must be correctly scaled for the motor current being controlled by the starter.Motor current signal scaling may have to be changed if the motor size has been changed from the original specification.Motor current signal scaling is accomplished by verifying the current transformer ratio as supplied with the starter and then selecting the correct DIP switch setting from the chart on the following page for the current transformer ratio.
The DIP switches are:
ON in the right position
OFF in the left position
NOTE: Adjust the DIP switches only when the motor is stopped, or the switches could be damaged.
Confirm Switch Settings To verify or change the motor current signal scaling:
Compare the CT ratio stamped on each CT to the CT ratio listed on the wiring diagram supplied with the starter to ensure the correct CTs are installed.
Inspect the RediStart Micro II power card to ensure that the DIP switches are in the correct positions for the applicable CT ratio and the motor full-load current (FLA) rating.
24
3.1 INSTALLATION
Switch Settings CT Ratio Motor FLA Switch 1 Switch 2
Changing FLA If the actual motor FLA has been changed from the motor FLA documented on the
288:1 3A to 9A Off Off 288:1 9A to 24A On Off 288:1 25A to 60A On On 864:1 20A to 24A Off Off 864:1 25A to 70A On Off 864:1 71A to 180A On On 2640:1 40A to 80A Off Off 2640:1 81A to 200A On Off 2640:1 201A to 500A On On 5760:1 70A to 160A Off Off 5760:1 161A to 400A On Off 5760:1 401A to 1200A On On
purchase order:
The DIP switch positions may need to be changed.
Different CTs may have to be installed in the starter and the current
transformer ratio parameter may need to be changed (Refer to current transformer ratio parameter, page 102).
RediStart Micro II Computer Card Jumpers
General Information The RediStart Micro II computer card has a number of jumpers that affect the
JPC5 - LCD Start button The LCD Start button can be enabled or disabled by this jumper. The LCD Start
operation of the starter. In some cases, these jumpers will over-ride the programmed values.
button is factory enabled unless the purchase order requests that the LCD Start button is disabled. The LCD Start button is controlled by jumper JPC5 on the RediStart Micro II computer card (Refer to RediStart Micro II computer card layout on page 122).
Mode Position
Enable 1-2 Disable 2-3
JPC7 - Overload Auto/Man. The motor thermal overload can be set to require a manual reset or to automatically
JPC13 - LCD Stop Button The LCD Stop button can be enabled or disabled by this jumper. The LCD Stop button
reset after a thermal trip. The motor thermal overload is set to the manual reset position unless the purchase order requests that the motor thermal overload is set to the automatic reset position. The motor thermal overload reset is controlled by jumper JPC7 on the RediStart Micro II computer card (Refer to RediStart Micro II computer card layout on page 122).
Mode Position
Automatic Reset 1-2 Manual Reset 2-3
is factory enabled unless the purchase order requests that the LCD Stop button is disabled. The LCD Stop button is controlled by jumper JPC13 on the RediStart Micro II computer card (Refer to RediStart Micro II computer card layout on page 122).
Mode Position
Enable 1-2 Disable 2-3
25
3.1 INSTALLATION
JPC17 - Forward Bypass The RediStart Micro II can be set to monitor a forward bypass contactor. This jumper
JPC18 - Reverse Bypass The RediStart Micro II can be set to monitor a reverse bypass contactor. This jumper
will allow the RediStart Micro II to monitor a bypass contactor that operates when the starter is running in the forward direction. The RediStart Micro II takes the contactor feedback from an auxiliary contact connected between terminals 3 and 4 of JPC3 on the computer card or from the wiring connection to the integral bypass circuit card. The forward bypass monitoring jumper is set to the disabled position unless the starter is equipped with a factory installed bypass contactor. The forward bypass monitoring is controlled by jumper JPC17 on the RediStart Micro II computer card (Refer to RediStart Micro II computer card layout on page 122).
Mode Position
Forward Bypass monitoring 1-2 No Forward Bypass monitoring 2-3
will allow the RediStart Micro II to monitor a bypass contactor that operates when the starter is running in the reverse direction. The RediStart Micro II either takes the contactor feedback from an auxiliary contact connected between terminals 3 and 4 of JPC3 on the computer card or from the wiring connection to the integral bypass circuit card. The reverse bypass monitoring jumper is set to the disabled position unless the starter is equipped with a factory installed bypass contactor. The reverse bypass monitoring is controlled by jumper JPC18 on the RediStart Micro II computer Card (Refer to RediStart Micro II computer card layout on page 122).
Mode Position
Reverse Bypass monitoring 1-2 No Reverse Bypass monitoring 2-3
JPC19 - Fault Reset The RediStart Micro II can be set to either require a manual reset or automatically
reset after a fault occurs. The RediStart Micro II is set for manual fault reset unless the purchase order requests that the fault reset jumper is set to automatic. The fault reset is controlled by jumper JPC19 on the RediStart Micro II computer card (Refer to RediStart Micro II computer card layout on page 122).
Mode Position
Automatic Fault Reset 1-2 Manual Fault Reset 2-3
The automatic fault reset works in conjunction with the # auto resets parameter (see page 87) and the Fault Classes sub-menu (see page 88).
The # auto resets parameter sets how many non-critical faults will be reset in one hour. Once this number has been reached, the starter will not automatically reset the next fault. When this occurs, the user should check the event recorder for the cause of the faults and correct the problem.
The fault classes sub-menu allows the user to set faults as critical, non-critical, disabled, warning relay A, warning relay B or warning relay C. When JPC19 is set to automatic fault reset and a fault is set to non-critical, the RediStart Micro II will automatically reset the fault.
26
4. OPERATION
4.1 OPERATION
Main Display Messages
General During normal operation, the RediStart Micro II can show a number of different
operating messages on the display. These messages give information on the present operating state of the starter and motor. There are three locations where messages are displayed as shown in the following diagram.
Location 1 Location 2
Run UTS I= 0A Running . V= 0V
Location 3
Messages The messages, display locations and descriptions are as follows:
Message Location Description
Stop 1 Starter is in a stopped state. Coast 1 Starter coasting between direction changes. BKS hld 1 Backspin timer is active. TBS hld 1 Time between starts is active. SPH hld 1 Starts per hour is active. BKS LOC 1 Backspin timer is locked. TBS LOC 1 Time between starts counter has locked. SPH LOC 1 Starts per hour counter has locked. JOG 1 Starter is operating in the jog at set speed mode. RUN 1 Starter is applying power to motor. Stopping 1 Stop command was applied, motor is being stopped. RUN UTS 1 Starter is running and motor is at full speed. RUN SYN 1 Starter is running and motor is synchronized. XXX.Xmin 2 Next start cannot be performed for xxx.x min. PH Err 2 The phase order is incorrect. Freq Err 2 The line frequency is outside of the trip settings. Volt Err 2 The line voltage is outside of the trip settings. OCT Trip 2 Motor current went above the over current trip setting. UCT Trip 2 Motor current went below the under current trip setting. GDF Trip 2 A ground fault was detected. Door In 2 The Disconnect switch is open. No Line 2 Line voltage is not present. OL Warn 2 Motor thermal overload is over 90% content. OL Trip 2 Motor thermal overload is tripped and reset is allowed. OL Lock 2 Motor thermal overload tripped and reset is not allowed. Ready 2 All conditions OK to run. Accel 2 Starter is ramping. Accel 2 2 Starter is ramping using 2nd ramp profile. Running 2 Starter ramp profile is complete. FWD Acc 2 The motor is being accelerated in the forward direction. REV Acc 2 The motor is being accelerated in the reverse direction. Forward 2 The motor is running in the forward direction. Reverse 2 The motor is running in the reverse direction. LS Acc 2 The motor is being accelerated in low speed. HS Acc 2 The motor is being accelerating in high speed. Low Sp 2 The motor is running in low speed. High Sp 2 The motor is running in high speed. Kicking 2 Starter is applying kick start current. Kicking 2 2 Starter is kicking using 2nd ramp profile. Decel 2 Motor is decelerating. Braking 2 The motor is being braked. FWD Jog 2 Motor is jogging in the forward direction. REV Jog 2 Motor is jogging in the reverse direction. ComLoss 2 Modbus communications lockout. EN Save 2 Energy saver is active. Heater 2 The motor heater is operating. RTD Alar 2 A RTD went over its alarm setting. RTD ComF 2 Communications with an RTD module was lost. RTD Open 2 A RTD is detected as being open. RTD Shor 2 A RTD is detected as being shorted. RTD Warn 2 A RTD went over its warning setting.
28
4.1 OPERATION
If Lock 2 Starter is providing set maximum field current. If CTRL 2 Starter is in field current control mode. PF CTRL 2 Starter is in power factor control mode. TachLoss 2 The tachometer feedback signal was lost. PORT 2 The starter is in Power Outage Ride-Through mode. . (dot) 3 Password protection is enabled.
Meter Display Pages
General Besides the main display, the RediStart Micro II has a number of other display pages
that show various operational values. By pressing the Up or Down arrow buttons, it is possible for the user to view all operational information without having to enter the menu system. The display pages are described below in the order they appear when pressing the Up button.
NOTE: Not every display page shown here may be present depending on the options provided with the starter.
Current Page The current meter page displays the currents for all three phases.
Phase 1 Current
Current I2= 0A I1= 0 I3= 0A
Phase 2 Current Phase 3 Current
Voltage Page The voltage page displays the voltages for all three phases.
Phase 1 Voltage
Voltage V2= 0V V1= 0 V3= 0V
Phase 2 Voltage Phase 3 Voltage
Kilo-Watt Hour Page The Kilo-Watt Hour power page displays the true power measurements for the motor.
KWatt Hour= 0.0H MWatt Hour= 0.0H
Kilo-Watt Hours Mega-Watt Hours
Power Page The power page displays the KW and kVA power measurements for the motor.
KWatts = 0.0W KVA Usage = 0.0
Kilo-Watts KVA
Tru Torque Page The tru torque page displays the Tru Torque % and Power Factor measurements for
the motor.
Tru Torq% = 0.0% Motor pf = 1.0
True Torque Power Factor
29
4.1 OPERATION
e
Runtime Page The runtime page displays the runtime on the motor.
RunTime Hr= 123h HoursX100 = 1.2
Operating Hours Hundreds of Hours
User Counts Page The user counts page displays the user resettable runtime and number of starts.
User RT Hr= 123h User Start= 45#
User Resettable Run tim User Resettable Starts
Motor #1 Page The motor #1 page displays the motor current imbalance as a percentage and the
number of motor starts.
Curr. Imba= 3% # Starts = 45
Current Imbalance Number of Starts
Motor #2 Page The motor #2 page displays overload content and ground fault current information.
% Overload= 3% Ground Fau= 0A
Overload Content Ground Fault Current
Motor #3 Page The motor #3 page displays operating frequency and motor power factor information.
Frequency= 60.0 Motor PF = 1.00
Line Frequency Power Factor
Sync Page The sync page gives the synchronous motor field current and slip.
Field Amps= 0.0A % Rotor Sl=99.9%
Field Current Slip Percentage
Communications Page The communications page displays the communications statistics.
Communication Rate
Com’s Tx= 0# Cr= 0 Rx= 0#
# of Transmits # of Receives
RTD #1 & #2 Temp. The RTD #1 & #2 temperature page displays the temperatures those RTDs are
measuring.
RTD#1 = 90C RTD#2 = 80C
RTD #1 Temperature RTD #2 Temperature
30
4.1 OPERATION
RTD #3 & #4 Temp. The RTD #3 & #4 temperature page displays the temperatures those RTDs are
measuring.
RTD#3 = 90C RTD#4 = 80C
RTD #3 Temperature RTD #4 Temperature
RTD #5 & #6 Temp. The RTD #5 & #6 temperature page displays the temperatures those RTDs are
measuring.
RTD#5 = 90C RTD#6 = 80C
RTD #5 Temperature RTD #6 Temperature
RTD #7 & #8 Temp. The RTD #7 & #8 temperature page displays the temperatures those RTDs are
measuring.
RTD#7 = 90C RTD#8 = 80C
RTD #7 Temperature RTD #8 Temperature
RTD #9 & #10 Temp. The RTD #9 & #10 temperature page displays the temperatures those RTDs are
measuring.
RTD#9 = 90C RTD#10 = 80C
RTD #9 Temperature RTD #10 Temperature
RTD #11 & #12 Temp. The RTD #11 & #12 temperature page displays the temperatures those RTDs are
measuring.
RTD#11 = 90C RTD#12 = 80C
RTD #11 Temperature RTD #12 Temperature
RTD #13 & #14 Temp. The RTD #13 & #14 temperature page displays the temperatures those RTDs are
measuring.
RTD#13 = 90C RTD#14 = 80C
RTD #13 Temperature RTD #14 Temperature
RTD #15 & #16 Temp. The RTD #15 & #16 temperature page displays the temperatures those RTDs are
measuring.
RTD#15 = 90C RTD#16 = 80C
RTD #15 Temperature RTD #16 Temperature
31
4.1 OPERATION
e
Max. RTD Temp. The maximum RTD temperature page displays the temperature and RTD number
from the highest measuring RTD.
Max of All= 90C M All RTD#= 5#
Max. RTD Temperatur RTD Number
Max. Bearing RTD Temp. The maximum bearing RTD temperature page displays the temperature and RTD
number from the highest measuring RTD in the bearing group.
Max Bearin= 90C M Bea RTD#= 5#
Max. Bearing Temp. Bearing RTD Number
Max. Stator RTD Temp. The maximum stator RTD temperature page displays the temperature and RTD
number from the highest measuring RTD in the stator group.
Max Stator= 90C M Sta RTD#= 5#
Max. Stator Temp. Stator RTD Number
Peak RTD Temp. The peak RTD temperature page displays the highest peak temperature reached and
the number of the RTD that read the temperature.
Peak of Al= 90C P All RTD#= 5#
Peak RTD Temp. RTD Number
Peak Bearing RTD Temp. The peak bearing RTD temperature page displays the highest bearing temperature
reached and the number of the RTD that read the temperature.
Peak Beari= 90C P Bea RTD#= 5#
Peak Bearing Temp. Bearing RTD Number
Peak Stator RTD Temp. The peak stator RTD temperature page displays the highest stator temperature
reached and the number of the RTD that read the temperature.
Peak Stato= 90C P Sta RTD#= 5#
Peak Stator Temp. Stator RTD Number
32
4.1 OPERATION
Parameters
Parameter Usage The description and use of each parameter is described in the programming section of
the manual. Most parameters are fairly straightforward and don’t require any further explanation. The rest of this chapter gives a more detailed description of the use of the parameters that are more complicated to use.
Starter Modes
Description The Starter Mode sub menu (see page 54) contains parameters for selecting the type
Start Modes Curr (Current Ramp): The current ramp is ideal for most general-purpose motor
of start and stop to perform. By allowing the user to select the start and stop mode the system can be operated in the optimal start and stop fashion for the load. Below are the available modes along with some examples for typical applications.
control applications; Examples: crushers, ball mills, compressors, saws, and centrifuges).
The Current Ramp applies to the following in the Starter Setup Main Menu: Forward1 Profile, Forward2 Profile, Reverse1 Profile, and Reverse2 Profile.
TT (Tru Torque): The true torque ramp is suitable for applications that require a minimum of torque transients during starting or for consistenly loaded applications that require a reduction of torque surges during starting; Examples: pumps, fans, and belt driven equipment).
The Tru Torque ramp applies to the following in the Starter Setup Main Menu: True Torque Ramp
Tach (Tachometer Feedback): The tachometer feedback ramp is for applications where torque transients must be held to a minimum, and the starting load is unknown, vary, or change during the start cycle; Examples: Belts, and conveyors.
The Tachometer ramp applies to the following in the Starter Setup Main Menu: Tachometer Setup
Stop Modes Coas (Coast): A coast stop should be used when no special stopping requirements are
necessary; Example: crushers, balls mills, centrifuges, belts, conveyor.
There is no menu that applies in the Starter Setup Main Menu.
VDCL (S Curve Voltage Deceleration): A standard open loop S-Curve voltage deceleration is best suited for applications such as pumps and compressors.
The S Curve Voltage Deceleration applies to the following in the Starter Setup Main Menu: Decel Setup
TT (Tru Torque): The true torque deceleration is best suited to pumping and compressor applications where pressure surges during a stop must be eliminated. This setup is easier than the S-Curve Voltage Deceleration and is less source voltage dependent.
The Tru Torque deceleration applies to the following in the Starter Setup Main Menu: True Torque Ramp
Brak (Brake): The Brake stop mode allows a static DC field to be injected into the stator of the motor, which makes the rotor stop in a fashion similar to the way the 3 phase rotating magnetic field brings the motor up to operating speed; Examples: saws, E-Stop applications, machine tools, and large centrifugal loads.
The Brake deceleration applies to the following in the Starter Setup Main Menu: Brake Ctl Setup
33
4.1 OPERATION
)
Current Ramp Adjustment
Current Ramp The current ramp sets how the motor accelerates. The current ramp is a linear
increase in current from the initial setting to the maximum setting. The ramp time sets the speed of this linear current increase. The following figure shows the relationships of these different ramp settings.
Current
(% of FLA)
Maximum
Current
Kick
Current
Initial
Current
Motor
Stall
Time
0
Kick
0
Time
Ramp Time
Up To Speed
Running
Time (Seconds
Initial Current Setting The initial current should be set to the level that allows the motor to begin rotating
within a couple of seconds of receiving a start command.
To adjust the initial current setting give the starter a run command. Observe the motor to see how long it takes before it begins rotating and then stop the unit. For every second that the motor doesn’t rotate, increase the initial current by 20%. Typical loads will require an initial current in the 50% to 175% range.
Maximum Current Setting For most applications, the maximum current can be left at 600%. This will ensure
that enough current is applied to the motor to accelerate it to full speed.
The maximum current can also be set to a lower current limit. This is usually done to limit the voltage drop on the power system or to limit the torque the motor produces to help prevent damage to the driven load.
NOTE: The motor may achieve full speed at any time during the current ramp. This means that the maximum current setting may not be reached. Therefore, the maximum current setting is the most current that could ever reach the motor, and not necessarily the maximum current that will reach the motor.
NOTE: When setting a current limit, the motor must be monitored to ensure that the current is high enough to allow the motor to reach full speed under worst case load conditions.
34
4.1 OPERATION
Ramp Time Setting The ramp time is the time it takes for the current to go from the initial current to the
maximum current. To make the motor accelerate faster, decrease the ramp time. To make the motor accelerate slower, increase the ramp time.
If the ramp time expires before the motor reaches full speed, the starter will maintain the set maximum current level until either the motor reaches full speed, the stall time expires, or the motor thermal overload trips.
NOTE: Setting the ramp time to a specific value does not necessarily mean that the motor will take this time to accelerate to full speed. The motor and load may achieve full speed before the ramp time expires if the application does not require the set ramp time and maximum current to reach full speed. Alternatively, the motor and load may take longer than the set ramp time to achieve full speed.
Programming A Kick Current
General The kick current sets a current level that overrides the current ramp when a start is
Kick Current The kick current parameter is usually set to a low value and then the kick time is
first commanded. The kick current is only useful on motor loads that are hard to get rotating but then are much easier to move once they are rotating. An example of a load which is hard to get rotating is a ball mill. The ball mill requires a high torque to get it to rotate the first quarter turn (90 the material inside will begin tumbling and it is easier to turn.
adjusted to get the motor rotating. If the kick time is set to more than 2.0 seconds without the motor rotating, increase the kick current by 100% and re-adjust the kick time.
o
). Once the ball mill is past 90oof rotation,
Kick Time The kick time adjustment should begin at 0.5 seconds and be adjusted by 0.1 or 0.2
second intervals until the motor begins rotating. If the kick time is adjusted above 2.0 seconds without the motor rotating, start over with a higher kick current setting.
Jog at Set Speed
Description The jog at set speed allows the motor to be operated at fixed low speeds. It is possible
Forward Jog The motor can be jogged in the forward direction at fixed speeds of 7% or 14% of full
Reverse Jog There are two options for jogging the motor in reverse. On a non-reversing starter, the
to operate the motor at fixed speeds of 7%, 14% and 20% of full speed.
speed. To make the motor jog in the forward direction, the starter must be told to jog the motor by energizing the jog input. Then, the starter must be given a run command to actually operate. Energize the jog input by applying 120VAC to terminal 4 of the JC13 terminal block on the RediStart Micro II computer card(see computer card layout on page 122)
The jog speed is set by the forward speed parameter (see page 64)
motor can be jogged at a fixed 20% reverse speed. On a reversing starter, the motor can be jogged at 7% or 14% reverse speed. The 7% or 14% speed is selected by the reverse speed parameter (see page 64).
To make the motor jog in the reverse direction, the starter must be told to operate in the jog mode by energizing the jog input and the reverse input. Then the starter must be given a run command to actually operate. Energize the jog and reverse inputs by applying 120VAC to terminal 4 (jog) and terminal 6 (reverse) of the JC13 terminal block on the RediStart Micro II computer card.
35
4.1 OPERATION
Jog Current The jog current sets the level of current reaching the motor when it is being jogged. A
Kick Current The jog at set speed produces lower starting torque than running torque. Often, with
Kick Time The kick time setting in the jog sub-menu sets the time that the kick current is
motor will heat up more when it is being jogged since the speed is too low for the cooling fan to move any air over the motor. Therefore, the jog current should be set to the lowest possible level that will still rotate the motor. This will prevent excessive heating of the motor.
low jog currents, the motor will produce enough torque to keep the motor turning but it won’t produce enough torque to start it. The kick current can be used to start the load rotating to overcome this. Start with the kick current at a middle level and increase it in 50% increments if the current is not enough.
applied. If a kick current is required, start with a 0.5 second time and continue to increase the time until the load will rotate.
Tachometer Feedback
Description The Tachometer control ramp profile (see page 65)provides a method to linearly ramp
the speed of the system. When this control mode is selected, the starter uses a tachometer to provide speed feedback to the starter. This mode is commonly used on conveyor belt applications where a smooth controlled start is necessary under various load conditions to prevent belt breakage, lifting, or excessive stretching. The Tachometer controller consists of an inner PID current loop and an outer PI speed control loop.
NOTE: The maximum current limit will override the speed control loop if necessary. If the Maximum Current level is not set high enough or the load is too great, the RediStart Micro II starter will limit the motor current to this maximum level. When current limiting occurs, the speed profile will no longer be linear and the motor(s) will take longer to accelerate to full speed. Therefore, if current limiting is undesirable, this parameter must be set higher than the peak starting current during a linear speed ramp start.
Tachometer Requirements In addition to the basic motor and starter setup variables, the following needs to done
to use the tachometer feedback control ramp:
1. Connect a tachometer with appropriate DC output voltage and correct polarity to the Redistart Micro II power card input (terminal TBP13).
2. The tachometer feedback Start Mode is selectable as “Tach” from the Starter Modes menu.
3. Program the appropriate variables in the Tachometer Setup menu.
4. Set the Initial Current level in either the Quick Start menu or the Forward1 Profile menu to the desired current limit.
5. Set the Maximum Current level in either the Quick Start menu or the Forward1 Profile menu to the desired maximum current limit.
36
4.1 OPERATION
Programming The Motor Deceleration
Deceleration Control The standard deceleration control on the RediStart Micro II uses an open loop voltage
ramp. The RediStart Micro II will ramp the voltage down to decelerate the motor. The curve shows the motor voltage vs the decel setting.
RediStart Micro Decel Curve
100
90
80
70
60
50
40
30
Motor Voltage (% of Line Voltage)
20
10
0
Programmed Decel Level (%)
Decel Level 1 This sets the starting voltage of the deceleration ramp. Most motors require the
voltage to drop to around 60% or lower before any significant deceleration is observed. Therefore, a good first setting for this parameter is 35%.
0102030405060708090100
To adjust this parameter, it is necessary to observe the motor operation as soon as a stop is commanded. If the motor hunts (speed oscillations) at the beginning of the deceleration, then lower the parameter by 5%. If the motor has a big drop in speed as soon as a stop is commanded, then raise the parameter by 5%.
Some motors are very sensitive to the adjustment of this parameter. If a 5% adjustment changes the motor from hunting to dropping in speed, then a smaller change of 1% or 2% may be necessary.
Decel Level 2 This sets the final voltage for the deceleration ramp. In most cases, this parameter
can be set to 10% and the decel time can be used to adjust the deceleration rate. If the motor is coming to a stop too quickly or if the starter continues to apply current to the motor after the motor has stopped, this parameter can be increased in 5% increments to fix this.
Decel Time The decel time sets how quicky the motor decelerates. Usually a time of 30 seconds is
a good starting point. To make the motor take longer to decelerate, increase this parameter or to make the motor decelerate quicker, decrease this parameter.
37
4.1 OPERATION
PORT (Power Outage Ride Through)
Description The Power Outage Ride Through capability (see page 71)allows the starter to ride
Bypass Delay PORT can also hold a bypass contactor in for a programmed BYP Dly when the power
through short duration brown outs, single phase, and power loss conditions.
When the system senses a voltage disturbance in a time frame greater than the Sense Time parameter, the power will be removed from the motor for a coast to stop, and the Fault Dly timer will begin to time; if it is not set to OFF.
If the power disturbance ends before the programmed Fault Dly time, the motor will restart -- if a start command is still present -- from initial to maximum current in the specified ramp time.
If the outage lasts longer than the programmed Fault Dly time, the starter will issue a Fault 98; “No Mains PWR.”
If Fault Dly is set to OFF, the starter will use the standard motor protection fault delay timers to sense power disturbances.
NOTE: Starts/Hou (starters per hour), Time Start (time between starts), and BKS Timer (backspin timer) are not incremented for PORT.
NOTE: If the system Start Mode parameter is programmed with a tachometer ramp, the system will restart using a tachometer ramp.
disturbance is Sensed.
NOTE: The BYP Dly is fixed at 0.0 seconds to protect systems that contain an integral bypass card.
NOTE: Caution must be taken when the BYP Dly is set above 0.0 seconds. If the bypass contactor is energized when the power disturbance ends, the motor will start across the line. The resulting torque may damage the system.
PORT Detection The starter can be detected in PORT operation by monitor of the PORT relay output;
Selectable on any of the programmable relays. Once programmed, this relay can be used to feed 120VAC to input 9 of the JC13 terminal block on the computer card. This causes the system to use the Forward/Reverse2 Profile for starting the motor.
TruTorque Acceleration Ramp
TruTorque Ramp The TruTorque ramp sub-menu (see page 72) contains the parameters that that are
used to activate and tune TruTorque Acceleration and Deceleration Control.
The primary purpose of TruTorque Control is to reduce the torque surge that occurs as an AC induction motor comes up to full speed. This torque surge can be a problem in applications especially in pumps and belt driven applications. In pumping applications this torque surge results in a pressure peak as the motor comes up to speed. In most situations this small pressure peak is not a problem. However in selected cases, even a small pressure peak can be highly undesirable. In belt drive applications, TruTorque prevents the slipping of belts as the motor reaches full speed.
Note: When TruTorque acceleration control is enabled the second ramp (Ramp #2) and Kick Current functions are disabled.
TruTorque control can be very useful for a variety of applications. However it is best used for pump and other variable torque applications. TruTorque generally should not be used in applications where the starting load varies greatly from one start to another.
38
4.1 OPERATION
Initial Torque This value sets the initial torque value for the motor. The initial torque level should
Maximum Torque This value sets the final torque reference value at the end of the ramp time. Typical
be set to a level that allows the motor to begin rotating within a couple of seconds of receiving a start command. Typical loads will require values between 10% to 30%
If the value is set too high a current surge may result. If the value is set too low a “No current at Run” fault may occur.
loads require a value around 100-110%. If the load is less than motor rating then the maximum torque value can be decreased. If the load is hard to start or the motor is a NEMA C or D type motor then this value may need to be increased.
If the motor reaches full speed too quickly then decrease the Maximum Torque value by 5% and retest. If the motor does not achieve full speed, increase the Maximum Torque value by 10% and retest.
If the motor can be started either by using default TruTorque values or current ramp control, the Maximum Torque value can be more precisely determined so that the motor comes up to speed in approximately the preset Ramp Time. In this case, while the motor is running at full load, display the TT% meter on the display (see Meter Setup for information on how to display the TT% meter). Record the value displayed when the motor is running with full load. The Maximum Torque value should then be set to the recorded running value of TT% plus an additional 10%. Retest with this value to verify correct operation.
Note: When setting the Maximum Torque value the motor must be monitored to ensure that the torque is high enough to allow the motor to reach full speed under worst case load conditions.
Ramp Time The Ramp Time setting is the time it takes for the torque to go from the Initial Torque
Setting to the Maximum Torque Setting. To make the motor accelerate faster, decrease the ramp time. To make the motor accelerate slower, increase the ramp time.
If the ramp time expires before the motor reaches full speed the starter will maintain the set Maximum Torque level until either the motor reaches full speed, the stall (UTS) timer expires, or the motor thermal overload trips.
Note: Setting the ramp time to a specific value does not necessarily mean that the motor will take this time to accelerate to full speed. The motor and load may achieve full speed before the ramp time expires if the application does not require the set ramp time and maximum torque to reach full speed. Alternatively, the motor and load may take longer than the set ramp time to achieve full speed.
TruTorque Deceleration Ramp
General The TruTorque ramp sub-menu (see page 72) contains the parameters that activate
TruTorque Decel Mode As a default deceleration control will be an open-loop voltage ramp. TruTorque Decel
TruTorque Acceleration and Deceleration Control.
TruTorque deceleration is a closed-loop deceleration control. The RediStart MicroII will ramp down the torque to smoothly decelerate the motor. TruTorque deceleration is very simple to setup.
Mode needs to be turned on to utilize TruTorque deceleration control. When TruTorque deceleration is enabled the TruTorque deceleration settings listed below will be used for deceleration control.
39
4.1 OPERATION
TT End Decel Torque The value sets the final torque level for the TruTorque deceleration ramp. In most
TT Decel Ramp Time The TruTorque deceleration time sets how quickly the motor decelerates. Usually a
cases, this parameter can be set to 10%.
To adjust this parameter, it is necessary to observe the motor. If the motor is coming to a stop too quickly or if the starter continues to apply current to the motor after the motor has stopped this parameter can be increased in 5% increments.
If the motor is still rotating when the desired deceleration time has expired, decrease this parameter by 5% and retest.
time of 30 seconds is a good starting point. To make the motor decelerate at a slower rate increase this time or to make the motor stop quicker decrease this time.
How Fault Classes Work
General The Fault classes sub-menu (see page 88) allows the starter behavior for different
NonC Non-critical fault. If this fault occurs, the starter will shut down and display the fault
faults to be altered. There are six different options that a fault can be set to. These options are described in the following paragraphs. See page 112 for a complete fault code and description listing.
number and description on the display. A non-critical fault can be set to either require a manual reset or to automatically reset.
The automatic resetting of a non-critical fault is dependant on the automatic computer reset jumper JPC19 (see page 26). WhenJPC19 is set to auto reset (position 1-2), the starter will automatically reset the fault. The number of automatic resets parameter (# Auto RST) on page 87 sets how many times the starter will perform this automatic reset sequence in one hour.
Crit Critical fault. If this fault occurs, the starter will shut down and display the fault
Dis Fault is Disabled. If this fault occurs, the starter will ignore the fault and continue to
WrnA Fault warning relay A. If this fault occurs, the starter will continue to operate. If a
WrnB Fault warning relay B. If this fault occurs, the starter will continue to operate. If a
WrnC Fault warning relay C. If this fault occurs, the starter will continue to operate. If a
number and description on the display. To clear the fault, the computer reset button must be pressed or the control power to the starter cycled.
operate.
programmable relay is programmed to WrnA, that relay will be energized when the fault occurs. The WrnA relay can be assigned to as many different faults as the user requires.
programmable relay is programmed to WrnB, that relay will be energized when the fault occurs. The WrnB relay can be assigned to as many different faults as the user requires.
programmable relay is programmed to WrnC, that relay will be energized when the fault occurs. The WrnC relay can be assigned to as many different faults as the user requires.
40
4.1 OPERATION
Use of Overcurrent and Undercurrent
General For the over current and undercurrent trips, there are settings for the current level
Overcurrent The overcurrent parameters are for the user to set a user defined high current trip.
Undercurrent The undercurrent parameters are used to set a user defined low current trip. The
Activating a Relay To make the starter activate a relay when an overcorrect or undercurrent is detected,
Tripping vs Running As the default, the starter will trip when an over-current or undercurrent is detected.
and the detect time. The motor current must go above or below the current level settings for the detect time before the overcurrent or undercurrent condition is detected. The overcurrent and undercurrent trips do not become active until the starter is up-to-speed (UTS is shown in top line of display).
The overcurrent parameters are not used for the thermal overload. If the driven load can be damaged by the full motor torque being applied during a stall or jam of the driven load, the over-current should be used to prevent this.
undercurrent parameters are used to protect a driven load from running empty. A good example of the undercurrent trip usage is a water pump. If the pump can run dry, the undercurrent parameters can be set to detect the low current and shut the pump down. To use this, the current could be set to 50% and the detect delay to 5 seconds to shut the pump down 5 seconds after the current falls below 50% of the motor FLA parameter.
a programmable relay must be programmed to OCT or UCT respectively.
To keep the starter operating, the over-current fault (fault #78) or undercurrent fault (fault #79) must be set to dis (disabled) in the fault classes sub-menu (see page 88) to turn off the fault trip.
Once the over-current or undercurrent fault is disabled, the starter will not trip when the over-current or undercurrent condition is detected, The relay programmed to OCT or UCT will still operate when the condition is detected. Once the condition clears, the relay will remain active for the programmed release delay time. The user must monitor the relay output and take appropriate action when the relay is energized.
Overload
General The RediStart Micro II comes with a programmable overload that allows classes 1-40
Overload Classes The overload class sets the time it takes for the overload to trip when the motor
to be programmed plus an overload disable and overload bypass during starting. The thermal overload is displayed as a percentage of overload used, with 0% representing a “cold” overload and 100% representing a “tripped” overload. The overload always operates on the highest phase current.
current is six (6) times the motor FLA. The overload follows an exponential curve that gives a long trip time for slight overloads and a short trip time for large overloads. This models the heating of a typical squirrel cage induction motor. See page 11 for the motor thermal overload curves.
41
4.1 OPERATION
Overload Operation There are two ways that the overload can operate. The operation is changed in the
fault classes sub-menu by changing the overload lock fault (fault #90) from Crit to Dis.
When fault #90 is set to Crit;
The overload warning relay will energize when the O/L content goes above 90%
and de-energize when the O/L content goes back below 80%. The starter will shut down if the overload content reaches 100%.
The overload lock relay will energize when the O/L content reaches 100% and
de-energize when the O/L content goes back below 60%. The starter will not allow an overload reset once the overload trips until the
overload content goes back below 60%. The overload relay will energize when the overload trips and will de-energize
when the overload condition is cleared by an automatic or manual reset.
When fault #90 is set to Dis;
The overload warning relay will energize if the overload content goes above 90%
and will de-energize when the overload content goes back below 80%. The starter will not shut if the overload content reaches 100%.
The overload lock relay will never energize.
The overload relay will energize when the overload content goes above 100% and
will de-energize when the overload content goes back below 100%.
Overload OK Overload Warning
Starter Prohibited: No OLW Relay: Off OLL Relay: Off OL Relay: Off
OL Reset (Manual or Automatic)
OL > 90%
OL < 80%
Starter Prohibited: No OLW Relay: On OLW Relay: On OLL Relay: Off OL Relay: Off
OL > 100% & F90 = Crit
OL > 100% & F90 = Dis
OL < 100%
Overload > 100%
Starter Prohibited: No
OLL Relay: Off OL Relay: On
Overload Tripped
Starter Prohibited: Yes OLW Relay: Off OLW Relay: On OLL Relay: Off OL Relay: On
OL < 60%
Overload Lock
Starter Prohibited: Yes OLW Relay: Off OLL Relay: On OL Relay: On
Overload Warning & Lock
Starter Prohibited: Yes
OLL Relay: On OL Relay: On
OL < 80%
Running Overload When the RediStart Micro II is running the overload content will never discharge
below 30%. The overload content will always hold at any value below 30% during the running period. As soon as the unit is stopped the overload will begin to discharge back to 0%.
42
4.1 OPERATION
Resolving Overload Trips The National Electrical Code, article 430 Part C, allows for different overload
multiplier factors depending on the motor and operating conditions.
NEC section 430-32 outlines the allowable service factor (Serv. Fact) for different motors as follows:
Motor Overload Multiplier
Service factor 1.15 or more 1.25 Motor temp. rise 40°C or less 1.25 All others 1.15
NEC section 430-34 permits further modifications if the service factor (Serv. Fact) is not sufficient to start the motor:
Motor Overload Multiplier
Service factor 1.15 or more 1.40 Motor temp. rise 40°C or less 1.40 All others 1.30
Although the NEC doesn’t address the effect of the ambient temperature of the motor location, guidance can be derived by examining NEC limits. If the motor is operating in an ambient temperature that is less than 40°C, then the overload multiplier can be increased while still protecting the motor from exceeding it maximum designed temperature. The following curve gives the ambient temperature vs the correction factor.
Temperature vs Correction Factor
100
80
e
60
peratur
40
Tem
20
0
Correction Factor
1.00 1.500.50
Example: If a motor operates at 0°C then a 1.36 correction factor could be applied to the overload multiplier. This could give a theoretical overload multiplier of 1.36 x 1.25 or 1.70. The highest legal value of overload multiplier is 1.40 so this could be used.
Performing an Emergency Restart
General The RediStart Micro II has an emergency restart feature which allows the user to
Performing a Reset Place a jumper between pins 6 and 11 of JC11 on the computer card. Hold the Enter
override any lock-outs that are present. This feature should only be used in an emergency. Before an emergency reset is performed, the reason for the lock-out and the condition of the motor should be examined to ensure that the motor is capable of being re-started without causing any damage.
button on the display and press the thermal overload reset pushbutton until a microprocessor reset occurs.
43
4.1 OPERATION
44
5. PROGRAMMING
5.1 PROGRAMMING: How To Program
Menu Buttons
General The RediStart Micro II has a display/keypad that allows the user to set the starter
Press to enter the menu system.
Press to abandon changes made to a parameter (before pressing the Enter key).
Press to exit a sub-menu.
MENU
ENTER
Press to exit the menu system.
Press to enter a menu.
Press to enter a sub-menu.
Press to change the parameter displayed.
Press to store the new value entered.
Select the menu to enter.
Select the sub-menu to enter.
Scroll between parameters when in a specific menu or sub-menu.
Increase a parameter value.
Press to view the meter pages when the main display is shown.
Select the menu to enter.
Select the sub-menu to enter.
Scroll between parameters when in a specific menu or sub-menu.
Decrease a parameter value.
Press to view the meters when the main display is shown.
parameters using a plain English interface. The functions of the display buttons are as follows.
START
STOP
Press to start the motor when the starter is connected for local display control.
Press to activate the BIST (Built-In Self Test).
If 2-wire control is used or the Start button is disabled, this button is inoperative.
Press to stop the motor when the starter is connected for local display control.
If 2-wire control is used or the Stop button is disabled, this button is inoperative.
46
5.1 PROGRAMMING: How To Program
Menu Structure
Menu Structure The RediStart Micro II has a 2 level menu structure. There are eight main menus that
contain parameters related to the different functions of the starter and five of the main menus contain additional sub-menus that divide the parameters into functional groups. The following shows the structure of the menu structure.
Main Menu
Quick Start Motor Nameplate Starter Setup Motor Protection Meters & Relays
Starter Modes Forward1 Profile
Forward2 Profile
Reverse1 Profile
Reverse2 Profile
Jog Cntrl Setup Tachometer Setup
Brake Ctl Setup
Decel Setup
PORT Ctl Setup True Torque ramp Heat/Anti-wind
Overload Class
Line Current
Line Voltage
Line Frequency
Ground Fault
Shorted SCR
Over Curr. Trip
Under Curr. Trip
Start Lockouts
Starting Timers
Permissive Input
Misc.
Fault Classes
Meters Setup
Standard Relays
Extended Relays
Event Recorder
Control Config
System Clock
System Password
Comm. Settings
Options List
Software Part#
Factory Setup
Hardware Setup RTD Module Setup Factory Control
RTD Setup
RTD Setpnts 1-8
RTD Setpnts 9-16
47
5.1 PROGRAMMING: How To Program
Viewing a Parameter
Viewing a Parameter To access a specific parameter in the RediStart Micro II menu structure, follow these
steps. Refer to the previous page for a graphical representation of the menu structure.
Press the Menu button to enter the menu system.
Press the Up or Down buttons to get the desired menu on the display.
Press the Enter button to go into the menu.
Press the Up or Down button to get to the desired sub-menu, if necessary.
Press the Enter button to go into the sub-menu, if necessary.
Press the Up or Down arrow buttons until the parameter is displayed.
Changing a Parameter
Changing a Parameter To change a parameter, follow these steps;
An Example The ramp time is set to 30 seconds and it is to be changed to 20 seconds.
View the desired parameter by following the Viewing a Parameter instructions.
Press the Enter button to switch to the change parameter screen.
Press the Up or Down buttons to get the desired value on the screen.
Press the Enter button to store the new value.
The following steps must be taken to change the ramp time.
Press the Menu button to enter the menu system.
Press the Down button twice to get to the Starter Setup screen.
Press the Enter button to access the Starter Setup menu.
Press the Down button once to display the Forward1 Profile.
Press the Enter button to access the Forward1 Profile sub-menu.
Press the Down button twice to display the Ramp Time parameter.
Press the Enter button to allow a change to the ramp time.
Press the Down button repeatedly to change the Ramp Time to the desired
value.
Press the Enter button to store the value.
Press the Menu button repeatedly to return to the main display.
48
5.2 PROGRAMMING: Quick Start
Motor FLA
Parameter Description The motor FLA parameter must be set to the full load amps of the motor connected to
Parameter Values The motor FLA parameter is adjustable from 1 to 1200 amps in 1 amp increments.
Parameter Default The default value for the motor FLA is 1 amp.
the starter for the starter to function correctly. If there is more than one motor connected, the motor FLA should be set to the sum of the connected motor full load amps.
NOTE: The starter uses the entered motor FLA for every current based calculation. If the motor FLA is not entered correctly, the current ramp profile and many of the starter’s advanced protection features will not function properly.
Serv. Fact (service factor)
Description The service factor parameter should be set to the service factor of the motor. The
Values The service factor can be set from 1.00 to 1.99, in 0.01 increments.
service factor is used for the overload calculations. If the service factor of the motor is not known then the service factor should be set to 1.00. See the motor overload parameter on page 11 for a detailed description on how to set the service factor for different applications to avoid overload trips.
NOTE: The NEC (National Electrical Code) does not allow the service factor to be set above 1.40. Check with other local electrical codes for their requirements.
Default The default value for the service factor is 1.15.
Start Mode
Description The Start Mode parameter allows for an optimal start of the motor based on the
Values The Start Mode Parameter can be set to Curr, TT, or Tach.
Default The default value for the Start Mode is Curr.
application. For a description of the possible Start Mode parameters, refer to page 33 in the Operations chapter.
Stop Mode
Description The Stop Mode parameter allows for the most suitable stop of the motor based on the
Values The Stop Mode can be set to Coas, VDCL, TT, or Brak.
Default The default value for the Stop Mode is Coas.
application. For a description of the possible Stop Mode parameters, refer to page 33 in the Operations chapter.
49
5.2 PROGRAMMING: Quick Start
Int. Curr. (initial current)
Description The initial current parameter is set as a percentage of the motor FLA parameter
Values The initial current is adjustable from 50% to 400% in 1% intervals.
Default The default value for the initial current is 100%.
setting. The initial current parameter sets the current that will initially reach the motor when a start is commanded.
If the motor does not rotate within a few seconds after a start command, the initial current should be increased. If the motor takes off too quickly after a start command, the initial current should be decreased.
The initial current must be set to a value that is lower than the maximum current parameter setting.
A typical setting for the initial current parameter is from 50% to 175%.
Max. Curr. (maximum current)
Description The maximum current parameter is set as a percentage of the motor FLA parameter
setting. The maximum current parameter performs two functions. It sets the current for the end of the ramp profile. It also sets the maximum current that is allowed to reach the motor while the motor is being started.
If the ramp time expires before the motor has reached full speed, the starter will hold the current at the maximum current level until the stall time expires, the motor reaches full speed, or the overload trips.
Typically, the maximum current is set to 600% unless the power system or load dictates the setting of a lower maximum current.
Values The maximum current is adjustable from 100% to 600% in 1% intervals.
Default The default value for the maximum current is 600%.
Ramp Time
Description The ramp time sets the amount of time that it takes for the starter to linearly
Settings The ramp time is adjustable from 0 to 120 seconds in 1 second intervals.
Default The default value for the ramp time is 15 seconds.
increase the current from the initial current level to the maximum current level.
A typical ramp time setting is from 15 to 30 seconds.
50
5.2 PROGRAMMING: Quick Start
Overload
Description The overload parameter sets the class of the electronic overload. The starter stores the
Values The overload can be set to;
Default The default value for the overload parameter is 10.
thermal overload value as a percentage value between 0 and 100%, with 0% representing a “cold” overload and 100% representing a tripped overload. See page 11 for the overload trip time vs current curves.
When the overload is set to not available (OFF), the electronic overload is disabled and another motor overload protection device must be supplied.
When the overload is set to bypass (BYP), the electronic overload is disabled during starting and then the thermal content is charged to 90% once the starter gets up-to-speed. When the motor is up-to-speed, the RediStart Micro II will use a class 10 overload for the motor protection.
OFF - no thermal overload
1-40 - class 1 through 40 overload in steps of 1.
BYP - overload bypassed during starting, class 10 once up-to-speed
Phase Orde (Phase Order)
Description The line phasing parameter sets the phase sensitivity of the starter. This can be used
to protect the motor from a possible change in the incoming phase sequence. If the incoming phase sequence does not match the set phase rotation, the starter will display phs err while stopped and will fault if a start is attempted.
Values The line phasing can be set to;
Default The default value for the phase sensitivity parameter is Ins.
Ins - will run with either phase sequence
ABC - will only run with ABC phase sequence
CBA - will only run with CBA phase sequence
51
5.3 PROGRAMMING: Motor Nameplate
Motor FLA
Description The motor FLA parameter must be set to the full load amps of the motor connected to
Values The motor FLA parameter is adjustable from 1 to 1200 amps in 1 amp increments.
Default The default value for the motor FLA is 1 amp.
the starter for the starter to function correctly. If there is more than one motor connected, the motor FLA should be set to the sum of the connected motor full load amps.
NOTE: The starter uses the entered motor FLA for every current based calculation. If the motor FLA is not entered correctly, the current ramp profile and many of the starter’s advanced protection features will not function properly.
Serv. Fact (service factor)
Description The service factor parameter should be set to the service factor of the motor. The
Values The service factor can be set from 1.00 to 1.99, in 0.01 increments.
service factor is used for the overload calculations. If the service factor of the motor is not known then the service factor should be set to 1.00. See the motor overload parameter on page 11 for a detailed description on how to set the service factor for different applications to avoid overload trips.
NOTE: The NEC (National Electrical Code) does not allow the service factor to be set above 1.40. Check with other local electrical codes for their requirements.
Default The default value for the service factor is 1.15.
Motor RPMs
Description The Motor RPMs can be set to match the RPM rating of the motor.
Values The Motor RPMs can be set from 1 to 3600RPM’s in increments of 1.
Default The default value for the Motor RPMs is 1760.
Energy Sav (energy saver)
Description The energy saver will lower the voltage applied to a lightly loaded motor. It will
Values The energy saver can be set to Off or On. If the starter is equipped with a bypass
Default The default value for the energy saver is Off.
continue to lower the voltage until it finds the point where the current reaches its lowest level and then regulate the voltage around this point. If the load on the motor increases, the starter will immediately return the output of the starter to full voltage. Potential true saving are in the order of 1 kilowatt per 100 horsepower.
contactor then the energy saver will be fixed as Off.
52
5.3 PROGRAMMING: Motor Nameplate
Source Volt (source voltage)
Description The source voltage parameter sets the line voltage that is used when the starter
Values The source voltage can be set to Auto or from 100 volts to 1000 volts, in 1 volt
Default The default value for the source voltage is Auto.
performs high/low line voltage calculations. See the high/low voltage parameter on page 78 for a description of the over/under voltage parameter.
When the source voltage is set to Auto, the starter will pick a standard line voltage value, based on the average incoming line voltage, when a start is commanded. The operating voltage is selected as;
208VAC if average line voltage is between 180VAC and 224VAC. 240VAC if average line voltage is between 225VAC and 269VAC. 315VAC if average line voltage is between 270VAC and 334VAC. 380VAC if average line voltage is between 345VAC and 409VAC. 460VAC if average line voltage is between 410VAC and 489VAC. 480VAC if average line voltage is between 490VAC and 524VAC. 575VAC if average line voltage is between 525VAC and 650VAC. 1000VAC if average line voltage is between 651VAC and 1000VAC.
When the source voltage is set to a numerical value, the starter will use the entered value as the line voltage.
increments.
53
5.4 PROGRAMMING: Starter Setup - Starter Modes
Start Mode
Description The Start Mode parameter allows for an optimal start of the motor based on the
Values The Start Mode Parameter can be set to Curr, TT, or Tach.
Default The default value for the Start Mode is Curr.
application. For a description of the possible Start Mode parameters, refer to page 33 in the Operations chapter.
Stop Mode
Description The Stop Mode parameter allows for the most suitable stop of the motor based on the
Values The Stop Mode can be set to Coas, VDCL, TT, or Brak.
Default The default value for the Stop Mode is Coas.
application. For a description of the possible Stop Mode parameters, refer to page 33 in the Operations chapter.
54
5.5 PROGRAMMING: Starter Setup - Forward1 Profile
Int. Curr. (initial current)
Description The initial current parameter is set as a percentage of the motor FLA parameter
Values The initial current is adjustable from 50% to 400% in 1% intervals.
Default The default value for the initial current is 100%.
setting. The initial current parameter sets the current that will initially reach the motor when a start is commanded.
If the motor does not rotate within a few seconds after a start command, the initial current should be increased. If the motor takes off too quickly after a start command, the initial current should be decreased.
The initial current must be set to a value that is lower than the maximum current parameter setting.
A typical setting for the initial current parameter is from 50% to 175%.
Max. Curr. (maximum current)
Description The maximum current parameter is set as a percentage of the motor FLA parameter
setting. The maximum current parameter performs two functions. It sets the current for the end of the ramp profile. It also sets the maximum current that is allowed to reach the motor while the motor is being started.
If the ramp time expires before the motor has reached full speed, the starter will hold the current at the maximum current level until the stall time expires, the motor reaches full speed, or the overload trips.
Typically, the maximum current is set to 600% unless the power system or load dictates the setting of a lower maximum current.
Values The maximum current is adjustable from 100% to 600% in 1% intervals.
Default The default value for the maximum current is 600%.
Ramp Time
Description The ramp time sets the amount of time that it takes for the starter to linearly
Settings The ramp time is adjustable from 0 to 120 seconds in 1 second intervals.
Default The default value for the ramp time is 15 seconds.
increase the current from the initial current level to the maximum current level.
A typical ramp time setting is from 15 to 30 seconds.
55
5.5 PROGRAMMING: Starter Setup - Forward1 Profile
Kick Curr. (kick current)
Description The kick current parameter is set as a percentage of the motor FLA parameter
Values The kick current is adjustable from 100% to 600% in 1% increments.
Default The default value for the kick current is 300%.
setting. The kick current sets a current level that overrides the current ramp profile, for the set kick time, when a start is commanded. If a kick time is programmed, the starter will provide the current level specified by the kick current setting for this set time. This current can be used to overcome the break over torque of some loads, while still allowing the starter to smoothly accelerate the load to full speed.
Kick Time
Description The kick time parameter sets the amount of time that the kick current level is
Values The kick time is adjustable from 0.1 to 10.0 seconds in 0.1 second intervals. If a kick
Default The default value for the kick time is Off.
provided to the motor when a start is commanded.
If the kick time is set to any time other than Off, the starter will provide the kick current level for the set time. The kick time should be increased or decreased to reach the time required to begin rotating the load.
current is not required, the kick time should be set to Off.
56
5.6 PROGRAMMING: Starter Setup - Forward2 Profile
Forward #2 Ramp Profile
General The forward #2 ramp profile sub-menu contains the parameters that set the starting
ramp profile when the second ramp is selected. The second ramp is selected by applying 120VAC to input 9 of the JC13 terminal block on the RediStart Micro II CPU card.
Int. Curr. (initial current)
Description The initial current parameter is set as a percentage of the motor FLA parameter
Values The initial current is adjustable from 50% to 400% in 1% intervals.
Default The default value for the initial current is 100%.
setting. The initial current parameter sets the current that will initially reach the motor when a start is commanded.
If the motor does not rotate within a few seconds after a start command, the initial current should be increased. If the motor takes off too quickly after a start command, the initial current should be decreased.
The initial current must be set to a value that is lower than the maximum current parameter setting.
A typical setting for the initial current parameter is from 50% to 175%.
Max. Curr. (maximum current)
Description The maximum current parameter is set as a percentage of the motor FLA parameter
Values The maximum current is adjustable from 100% to 600% in 1% intervals.
Default The default value for the maximum current is 600%.
setting. The maximum current parameter performs two functions. It sets the current for the end of the ramp profile. It also sets the maximum current that is allowed to reach the motor while the motor is being started.
If the ramp time expires before the motor has reached full speed, the starter will hold the current at the maximum current level until the stall time expires, the motor reaches full speed, or the overload trips.
Typically, the maximum current is set to 600% unless the power system or load dictates the setting of a lower maximum current.
Ramp Time
Description The ramp time sets the amount of time that it takes for the starter to linearly
Settings The ramp time is adjustable from 0 to 120 seconds in 1 second intervals.
Default The default value for the ramp time is 15 seconds.
increase the current from the initial current level to the maximum current level.
A typical ramp time setting is from 15 to 30 seconds.
57
5.6 PROGRAMMING: Starter Setup - Forward2 Profile
Kick Curr. (kick current)
Description The kick current parameter is set as a percentage of the motor FLA parameter
Values The kick current is adjustable from 100% to 600% in 1% increments.
Default The default value for the kick current is 300%.
setting. The kick current sets a current level that overrides the current ramp profile, for the set kick time, when a start is commanded. If a kick time is programmed, the starter will provide the current level specified by the kick current setting for this set time. This current can be used to overcome the break over torque of some loads, while still allowing the starter to smoothly accelerate the load to full speed.
Kick Time
Description The kick time parameter sets the amount of time that the kick current level is
Values The kick time is adjustable from 0.1 to 10.0 seconds in 0.1 second intervals. If a kick
Default The default value for the kick time is Off.
provided to the motor when a start is commanded.
If the kick time is set to any time other than Off, the starter will provide the kick current level for the set time. The kick time should be increased or decreased to reach the time required to begin rotating the load.
current is not required, the kick time should be set to Off.
58
5.7 PROGRAMMING: Starter Setup - Reverse1 Profile
Reverse #1 Ramp Profile
General The reverse #1 ramp profile sub-menu contains the parameters that set the starting
ramp profile when the second ramp is selected. Reverse operation is selected by applying 120VAC to input 6 of the JC13 terminal block on the RediStart Micro II CPU card.
Int. Curr. (initial current)
Description The initial current parameter is set as a percentage of the motor FLA parameter
Values The initial current is adjustable from 50% to 400% in 1% intervals.
Default The default value for the initial current is 100%.
setting. The initial current parameter sets the current that will initially reach the motor when a start is commanded.
If the motor does not rotate within a few seconds after a start command, the initial current should be increased. If the motor takes off too quickly after a start command, the initial current should be decreased.
The initial current must be set to a value that is lower than the maximum current parameter setting.
A typical setting for the initial current parameter is from 50% to 175%.
Max. Curr. (maximum current)
Description The maximum current parameter is set as a percentage of the motor FLA parameter
Values The maximum current is adjustable from 100% to 600% in 1% intervals.
Default The default value for the maximum current is 600%.
setting. The maximum current parameter performs two functions. It sets the current for the end of the ramp profile. It also sets the maximum current that is allowed to reach the motor while the motor is being started.
If the ramp time expires before the motor has reached full speed, the starter will hold the current at the maximum current level until the stall time expires, the motor reaches full speed, or the overload trips.
Typically, the maximum current is set to 600% unless the power system or load dictates the setting of a lower maximum current.
Ramp Time
Description The ramp time sets the amount of time that it takes for the starter to linearly
Settings The ramp time is adjustable from 0 to 120 seconds in 1 second intervals.
Default The default value for the ramp time is 15 seconds.
increase the current from the initial current level to the maximum current level.
A typical ramp time setting is from 15 to 30 seconds.
59
5.7 PROGRAMMING: Starter Setup - Reverse1 Profile
Coast Time
Description The Coast Time parameter sets the time the starter will “coast” with no power applied
Values The coast time is adjustable from 0 to 90 seconds in 1 second increments.
Default The default value for the coast time is 1 second.
to the motor if a change of direction is made while the starter is running. Caution must be taken when setting a short coast time and a high initial current. The starter will begin to apply power in the opposite direction once the coast time has expired and the high initial current setting will cause a high torque on the motor shaft.
Kick Curr. (kick current)
Description The kick current parameter is set as a percentage of the motor FLA parameter
Values The kick current is adjustable from 100% to 600% in 1% increments.
Default The default value for the kick current is 300%.
setting. The kick current sets a current level that overrides the current ramp profile, for the set kick time, when a start is commanded. If a kick time is programmed, the starter will provide the current level specified by the kick current setting for this set time. This current can be used to overcome the break over torque of some loads, while still allowing the starter to smoothly accelerate the load to full speed.
Kick Time
Description The kick time parameter sets the amount of time that the kick current level is
Values The kick time is adjustable from 0.1 to 10.0 seconds in 0.1 second intervals. If a kick
Default The default value for the kick time is Off.
provided to the motor when a start is commanded.
If the kick time is set to any time other than Off, the starter will provide the kick current level for the set time. The kick time should be increased or decreased to reach the time required to begin rotating the load.
current is not required, the kick time should be set to Off.
60
5.8 PROGRAMMING: Starter Setup - Reverse2 Profile
Reverse #2 Ramp Profile
General The reverse #2 ramp profile sub-menu contains the parameters that set the starting
ramp profile when reverse operation and the second ramp are both selected. Reverse operation is selected by applying 120VAC to input 6 of the JC13 terminal block on the RediStart Micro II CPU card. The second ramp is selected by applying 120VAC to input 9 of the JC13 terminal block on the RediStart Micro II CPU card.
Int. Curr. (initial current)
Description The initial current parameter is set as a percentage of the motor FLA parameter
Values The initial current is adjustable from 50% to 400% in 1% intervals.
Default The default value for the initial current is 100%.
setting. The initial current parameter sets the current that will initially reach the motor when a start is commanded.
If the motor does not rotate within a few seconds after a start command, the initial current should be increased. If the motor takes off too quickly after a start command, the initial current should be decreased.
The initial current must be set to a value that is lower than the maximum current parameter setting.
A typical setting for the initial current parameter is from 50% to 175%.
Max. Curr. (maximum current)
Description The maximum current parameter is set as a percentage of the motor FLA parameter
Values The maximum current is adjustable from 100% to 600% in 1% intervals.
Default The default value for the maximum current is 600%.
setting. The maximum current parameter performs two functions. It sets the current for the end of the ramp profile. It also sets the maximum current that is allowed to reach the motor while the motor is being started.
If the ramp time expires before the motor has reached full speed, the starter will hold the current at the maximum current level until the stall time expires, the motor reaches full speed, or the overload trips.
Typically, the maximum current is set to 600% unless the power system or load dictates the setting of a lower maximum current.
Ramp Time
Description The ramp time sets the amount of time that it takes for the starter to linearly
Settings The ramp time is adjustable from 0 to 120 seconds in 1 second intervals.
Default The default value for the ramp time is 15 seconds.
increase the current from the initial current level to the maximum current level.
A typical ramp time setting is from 15 to 30 seconds.
61
5.8 PROGRAMMING: Starter Setup - Reverse2 Profile
Coast Time
Description The Coast Time parameter sets the time the starter will “coast” with no power applied
Values The coast time is adjustable from 0 to 90 seconds in 1 second increments.
Default The default value for the coast time is 1 second.
to the motor if a change of direction is made while the starter is running. Caution must be taken when setting a short coast time and a high initial current. The starter will begin to apply power in the opposite direction once the coast time has expired and the high initial current setting will cause a high torque on the motor shaft.
Kick Curr. (kick current)
Description The kick current parameter is set as a percentage of the motor FLA parameter
Values The kick current is adjustable from 100% to 600% in 1% increments.
Default The default value for the kick current is 300%.
setting. The kick current sets a current level that overrides the current ramp profile, for the set kick time, when a start is commanded. If a kick time is programmed, the starter will provide the current level specified by the kick current setting for this set time. This current can be used to overcome the break over torque of some loads, while still allowing the starter to smoothly accelerate the load to full speed.
Kick Time
Description The kick time parameter sets the amount of time that the kick current level is
Values The kick time is adjustable from 0.1 to 10.0 seconds in 0.1 second intervals. If a kick
Default The default value for the kick time is Off.
provided to the motor when a start is commanded.
If the kick time is set to any time other than Off, the starter will provide the kick current level for the set time. The kick time should be increased or decreased to reach the time required to begin rotating the load.
current is not required, the kick time should be set to Off.
62
5.9 PROGRAMMING: Starter Setup - Jog Cntrl Setup
Jog Curr. (jog current)
Description The jog current parameter is set as a percentage of the motor FLA parameter setting.
Values The jog current is adjustable from 25% to 250% in 1% increments.
Default The default value for the jog current is 50%.
The jog current parameter is used to set the maximum current that will reach the motor while the motor is being operated in the jog at set speed mode. It should be set to the lowest possible current level that will still operate the motor.
When a motor is operating in the jog at set speed mode, its cooling capability is greatly reduced. Therefore, the running time of the motor is dependant on the motor current. If the jog at set speed will be used on a regular basis, the motor temperature should be monitored using a thermostat. The thermostat can be connected between the power and input terminal 1 of the JC13 terminal block on the RediStart Micro II computer card so that the starter will trip when a fault occurs. Alternatively, temperature monitoring devices, such as thermistors or RTDs can be used. This will prevent the motor from being overheated and inadvertently damaged.
Due to the way the jog at set speed operates, the starter may require the installation of a 5% line reactor to eliminate harmonic problems being introduced into the power system. This is dependent on the size of the motor in relation to the capacity of the power system. The jog at set speed has more of an effect on a weak power system.
Max. Time (maximum time)
Description The maximum time parameter sets the time limit for continuous operation in the jog
at set speed mode. This parameter should be set to a value that doesn’t allow the motor to be operated in the jog at set speed mode for such a length of time that damage to the motor can occur.
During initial set-up, monitor the motor temperature to determine it’s maximum safe jogging time and then enter this time. This can help avoid damage to the motor by stopping the starter before the motor overheats. This parameter does not stop the operator from stopping and re-starting the motor during jog operation which could still lead to the operation time of the motor being exceeded. Use the timers in the Starts Lockouts submenu to protect against this.
Values The maximum time is adjustable from 1 to 9000 seconds in 1 second intervals.
Default The default value for the maximum time parameter is 200 seconds.
63
5.9 PROGRAMMING: Starter Setup - Jog Cntrl Setup
Kick Curr (kick current)
Description The kick current parameter sets the level of the kick current that is applied to the
Values The kick current parameter is adjustable from 50% to 400% in 1% increments.
Default The default value for the kick current parameter is 300%.
motor when a start command is given and the starter is set for operation in the forward jog at set speed mode.
This parameter should be set to a midrange value and then the kick time should be increased in 0.1 second intervals until the kick is applied long enough to start the motor rotating when a start is given. If the motor does not start rotating with the set kick current value then increase the kick current and begin adjusting the kick time from 0.1 seconds again.
If the motor accelerates to a speed which is greater than the jog speed, then either the kick current or kick time should be decreased.
Kick Time
Description The kick time parameter sets the length of time that the current level, as specified by
Values The kick time parameter is adjustable from 0.1 to 10.0 seconds in 0.1 second intervals.
Default The default value for the kick time is Off.
the kick current, is applied to the motor.
The kick time parameter can also be set to Off.
FWD Speed
Description The forward speed parameter sets the frequency of the cyclically converted signal that
Values The forward speed can be set to 7% or 14%.
Default The default value for the forward speed is 14%.
reaches the motor while the starter is operating in the forward direction and the forward jog at set speed mode is selected. This is done by applying 120VAC to input terminal 4 of the JC13 terminal block on the RediStart Micro II computer card.
REV Speed
Description The reverse speed parameter sets the frequency of the cyclically converted signal that
Values The reverse speed can be set to 7% or 14%.
Default The default value for the reverse speed is 14%.
reaches the motor while the starter is jogging in the reverse direction. This is done by applying 120VAC to input terminals 4 and 6 of the JC13 terminal block on the RediStart Micro II computer card.
64
5.10 PROGRAMMING: Starter Setup - Tachometer Setup
FS Volts (Full Speed Volts)
Description The FS Volts parameter sets the tachometer input voltage at full speed. This value
Values The tachometer FS Volts value can be set between 1.00 and 7.00 volts in 0.01 volt
Default The default value for the tachometer FS Volts value is 5.00 volts.
should be set at full (unloaded) motor speed.
For example: A tachometer rated at 0.0033 volts-per-rpm is mounted on a 4-pole 1800 rpm motor. Therefore, the FS Volts should be set to: 0.0033 x 1800 = 5.94 volts.
increments.
Stab Cnst (Stability Constant)
Description The Stab Cnst parameter is used to control the speed and bandwidth of the of the
Values The Stab Cnst parameter is adjustable from 10% to 150% in 1% increments.
Default The default value for the Stab Cnst parameter is 100%.
speed controller.
NOTE: Lower values slow down the controller’s response,which is useful if the system has a large inertia and/or low stiffness. Higher values will speed up the controler’s response, which can be useful if the more precise speed control is necessary. If the stability constant is set too low, the starter will not track the speed reference properly and the motor speed profile will not be linear.
Ramp#1 Tim
Description The Ramp#1 Tim parameter sets the length of time that the D.C. brake current is
Values The Ramp#1 Tim is adjustable from 0 to 120 seconds in 1 second intervals.
Default The default value for the Ramp#1 Tim is 15 seconds.
applied to the motor.
Ramp#2 Tim
Description The Ramp#2 Tim parameter sets the length of time that the D.C. brake current is
Values The Ramp#2 Tim is adjustable from 0 to 120 seconds in 1 second intervals.
Default The default value for the Ramp#2 Tim is 15 seconds.
applied to the motor.
65
5.10 PROGRAMMING: Starter Setup - Tachometer Setup
TLoss Dela (Tachometer Signal Loss Delay)
Description The TLoss Delay time is the allowable time the starter will operate when a
Values The TLoss Delay time parameter is adjustable from 0.1 seconds to 90.0 seconds in 0.1
Default The default value for the TLoss Delay time is 1.5 seconds.
tachometer signal is lost. If the signal is lost, the starter will perform the action set by the TLoss Mode parameter.
NOTE: Nuisance tachometer loss faults at start can be prevented by setting the initial current parameter to a value that allows the motor to begin rotating soon after a start is commanded.
second intervals.
TLoss Mode (Tachometer Signal Loss Mode)
Description The TLoss Mode determines the starter’s action if it has been detected the tachometer
Values The TLoss Mode parameter can be set to Shut (shutdown), Curr (Current Ramp), or
Default The default value for the TLoss Mode is Shut.
signal is lost.
NOTE: If Current ramp or TruTorque ramp is selected, all values within these ramp profiles must be set for proper operation.
NOTE: If Current ramp or TruTorque ramp is selected, and the tachometer signal is lost, the starter will shut down and automatically restart with the new starting mode. The new start mode will apply until a manual reset to Tach is performed.
TT (TruTorque Ramp).
66
5.11 PROGRAMMING: Starter Setup - Brake Ctl Setup
D.C. Injection Braking
Description The D.C. injection braking parameter is used to quickly bring a motor to a stop. The
Braking Options There are three (3) levels of D.C. braking current rated as a percentage of the motor
D.C. braking applies a static D.C. field to the stator of the motor which applies a braking torque to the rotor which makes it stop much in the same way the 3 phase rotating magnetic field brings the motor up to operating speed.
FLA value that are available depending on the type of starter. They are:
Light duty - 100% D.C. Current for 30 seconds.
Standard Duty - 300% D.C. current for 30 seconds (RSM7 or RSM11).
Heavy Duty - 300% D.C. current for 90 seconds (RSM7 or RSM11).
NOTE: When DC injection braking is used on a motor, discretion must be used when setting up the DC braking parameters. Excessive motor heating may result if the load inertia is large or the brake current or brake time is set too high. In Heavy-Duty brake applications, caution must be used to assure the motor has the thermal capacity to brake the desired load, in the desired period of time,without excessive heating.
Current #1
Description The brake #1 current parameter sets the level of D.C. current applied to the motor. If
Values The brake #1 current is adjustable from 10% to 100% of available brake current in 1%
the motor braking is too fast, the current should be reduced. If the motor is not braking fast enough, the current level should be increased. To minimize motor heating, only the necessary level of current should be used.
increments.
Default The default value for the brake #1 current is 25%.
Time #1
Description The brake #1 time parameter sets the length of time that the D.C. brake current is
Values The brake #1 time parameter is adjustable from 0 to 30 seconds (0 to 90 seconds for
Default The default value for the brake #1 time is 0 seconds.
applied to the motor. If the motor is still rotating faster than desired at the end of the brake time, increase the brake time if possible. If the motor stops before the desired brake time has expired, decrease the brake time to minimize motor heating.
heavy duty) in 1 second intervals.
Current #2
Description The brake #2 current parameter sets the level of the D.C. current applied to the motor
Values The brake #2 current is adjustable from 10% to 100% of available brake current in 1%
when the second ramp profile is selected. If the motor braking is too fast, the current should be reduced. If the motor is not braking fast enough, the current level should be increased. To minimize motor heating, only the necessary level of current should be used.
increments.
Default The default value for the brake #2 current is 25%.
67
5.11 PROGRAMMING: Starter Setup - Brake Ctl Setup
Time #2
Description The brake #2 time parameter sets the length of time that the D.C. brake current is
Values The brake #2 time parameter is adjustable from 0 to 30 seconds (0 to 90 seconds for
Default The default value for the brake #2 time parameter is 0 seconds.
applied to the motor when the second ramp is selected. If the motor is still rotating faster than desired at the end of the brake time, increase the brake time if possible. If the motor stops before the desired brake time has expired, decrease the brake time to minimize motor heating.
heavy duty) in 1 second intervals.
68
5.12 PROGRAMMING: Starter Setup - Decel Setup
V Level #1
Description The decel level #1 parameter sets the starting voltage for the voltage ramp
Values The decel level #1 is adjustable from 10% to 100% in 1% increments. The decel level
Default The default value for the decel level #1 parameter is 40%.
deceleration ramp profile.
The deceleration profile uses an open loop voltage ramp profile. The decel level #1 parameter sets the starting point on the S curve. This means that decel level #1 is not set as a percentage of actual line voltage.
If the motor initially surges when a stop is commanded, decrease this parameter value. If there is a sudden drop in motor speed when a stop is commanded, increase this parameter value.
A typical decel level #1 setting is between 30% and 40%.
#1 setting must be greater than the decel level #2 setting.
V Level #2
Description The decel level #2 parameter sets the ending voltage for the voltage ramp profile.
Decel level #2 can not be set greater than decel level #1.
The deceleration profile uses an open loop voltage ramp profile. The decel level #2 parameter sets the ending point on the S curve. This means that decel level #2 is not set as a percentage of actual line voltage.
If the motor stops rotating before the deceleration time has expired, increase this parameter value. If the motor is still rotating when the deceleration time has expired, decrease this parameter value. A typical decel level #2 setting is between 10% and 20%.
Values The decel level #2 parameter is adjustable from 1% to 99% in 1% increments. The
Default The default value for the decel level #2 parameter is 20%.
decel level #2 must be less than the decel level 1 setting.
V DCL Time (decel time)
Description The decel time parameter sets the amount of time taken to go from the decel level #1
Values The decel time parameter is adjustable from 0 to 60 seconds in 1 second intervals.
Default The default value for the decel time parameter is 0 seconds.
setting to the decel level #2 setting.
If the motor stops rotating before the decel time has expired, decrease the decel time. If the motor is still rotating when the decel time expires, increase the decel time.
A typical decel time setting is 20 to 40 seconds.
69
5.12 PROGRAMMING: Starter Setup - Decel Setup
TT DCL Tim (TruTorque deceleration time)
Description The TruTorque deceleration time sets how quickly the motor decelerates. Usually a
Values The TruTorque deceleration time parameter is adjustable from 0 to 100 seconds in 1
Default The default TruTorque deceleration time is 0 seconds.
time of 30 seconds is a good starting point. To make the motor decelerate at a slower rate increase this time or to make the motor stop quicker decrease this time.
second intervals.
TT DCL Tor (ending deceleration torque)
Description The value sets the final torque level for the Trutorque deceleration ramp. In most
Values The TruTorque deceleration ending torque value can be set from 1% to 100% torque in
Default The default TruTorque deceleration ending torque setting is 10%
cases, this parameter can be set to 10%.
To adjust this parameter, it is necessary to observe the motor. If the motor is coming to a stop too quickly or if the starter continues to apply current to the motor after the motor has stopped this parameter can be increased in 5% increments.
If the motor is still rotating when the desired deceleration time has expired, decrease this parameter by 5% and retest.
1% steps.
70
5.13 PROGRAMMING: Starter Setup - PORT CTL Setup
Fault Dly (Fault Delay)
Description The Fault Dly parameter determines how long a power disturbance can exist before
Values The Fault Dly parameter is adjustable from OFF, 0.1 through 90.0 seconds, in 0.1
Default The default value for the Fault Dly parameter is OFF.
the micro system will fualt out on a power loss; and no longer restart. If the Fault Dly parameter is set to OFF, the PORT detection wil be disabled and the standard motor protection features will be enabled.
second increments.
Bypass Dly (Bypass Delay)
Description The Bypass Dly parameter determines when the bypass contactor will drop after a
Values The Bypass Dly parameter is adjustable from 0.0 through 3.0 seconds, in 0.1 second
Default The default value for the Bypass Dly time is 0.0 seconds.
power disturbance is sensed.
increments.
Sense Time
Description The Sense Time parameter determines how long a power outage must exist before the
micro will drop to a coast to stop, and wait for a valid line voltage before restarting.
Values The Sense Time parameter is adjustable from 0.01 through 0.50 seconds, in 0.01
Default The default value for the Sense Time parameter is 0.05 seconds.
increments.
71
5.14 PROGRAMMING: Starter Setup - TruTorque Ramp
Int Torque (initial torque)
Description The initial torque parameter sets the initial torque level that the motor will produce
Values The initial torque is adjustable from 1% to 100% in 1% increments.
Default The default value for initial torque is 20%.
during starting. This parameter should be set to a level that allows the motor to begin acceleration with a few seconds of a start command being received.
Max Torque (maximum torque)
Description The maximum torque parameter sets the final level of torque that is supplied to the
Values The maximum torque is adjustable from 10% to 325% in 1% increments.
Default The default value for the maximum torque parameter is 105%.
motor during starting. For a loaded motor, the maximum torque parameter initially should be set to 100% or greater. If the maximum torque value is set too low, the motor may not produce enough torque to reach full speed (UTS). On a lightly loaded motor this parameter may be reduced below 100% to provide for smoother starts.
Ramp Time
Description The ramp time parameter sets the time it takes for the commanded torque to go from
the Initial Torque Setting to the Maximum Torque Setting. To make the motor accelerate faster, decrease the ramp time. To make the motor accelerate slower, increase the ramp time.
If the ramp time expires before the motor reaches full speed the starter will maintain the set Maximum Torque level until either the motor reaches full speed, the stall (UTS) timer expires, or the motor thermal overload trips.
Note: This ramp time setting is only used for TruTorque starts. It is not the same ramp time parameter that is used for current ramp profile starts.
Note: Setting the ramp time to a specific value does not necessarily mean that the motor will take this time to accelerate to full speed. The motor and load may achieve full speed before the ramp time expires if the application does not require the set ramp time and maximum torque to reach full speed. Alternatively, the motor and load may take longer than the set ramp time to achieve full speed.
Values The TruTorque ramp time is adjustable from 0 to 120 seconds in 1 second intervals.
Default The default value for the TruTorque ramp time is 15 seconds.
72
5.14 PROGRAMMING: Starter Setup - TruTorque Ramp
TT Over Cu (TruTorque overcurrent trip)
Description The TruTorque overcurrent trip parameter is set as a percentage of FLA. If the motor
Values The TruTorque overcurrent can be set to Off or from 100% to 800% of FLA in 1%
Default The default value for the TruTorque Overcurrent parameter is Off
current remains above this level for longer than the delay time the starter will trip. In order to protect applications such as pumps from water hammer when a fault does occur a normal deceleration profile will occur to "gracefully" shut down the system before the TruTorque Overcurrent Fault is displayed and the starter is disabled.
Note: The TruTorque Overcurrent Trip only operates during TruTorque ramping before the starter has indicated an up-to-speed condition. If overcurrent protection is desired after the motor has come up to speed the Over Current parameter under the Motor Protection menu must be used.
increments.
Ovr Cur Dl (TruTorque overcurrent trip delay)
Description The TruTorque overcurrent trip delay parameter sets the time that the motor current
Values The TruTorque overcurrent delay parameter can be set from 0.1 to 90.0 seconds in 0.1
Default The default value for the TruTorque overcurrent delay parameter is 0.1 seconds.
must exceed the TruTorque Overcurrent Trip setting, while the starter is ramping, before a trip will occur.
second intervals.
73
5.15 PROGRAMMING: Starter Setup - Heat/Anti-wind
Heat Curr. (heater current)
Description The heater current parameter sets the level of D.C. current that reaches the motor
Values The heater current can be set from 5% to 25% in 1% increments.
Default The default value for the heater current is 10%.
when the motor winding heater/anti-windmilling brake is enabled.
The motor winding heater/anti-windmilling brake can be used to heat a motor to prevent internal condensation or it can be used to prevent a motor from rotating.
NOTE: The motor can still slowly creep when the anti-windmilling brake is being used. If the motor has to be held without rotating, a mechanical means of holding the motor has to be used.
The motor winding heater/anti-windmilling brake operation has to be enabled by placing a jumper between terminals 4 and 13 of JC11.
To use the motor winding heater/anti-windmilling brake, apply 120VAC to input terminal 8 of the JC13 terminal block on the RediStart Micro II computer card and then give the unit a start command. Instead of starting the motor, the unit will provide a continuous, low level D.C. current to the motor.
The level of DC current applied to the motor during this operation needs to be monitored to ensure that the motor isn’t overheated. The current level should be set as low as possible and then slowly increased over a long period of time. While this is being done, the temperature of the motor should be monitored to ensure it is not overheating.
74
5.16 PROGRAMMING: Motor Protection - Overload
Overload
Description The overload parameter sets the class of the electronic overload. The starter stores the
Values The overload can be set to;
Default The default value for the overload parameter is 10.
thermal overload value as a percentage value between 0 and 100%, with 0% representing a “cold” overload and 100% representing a tripped overload. See page 11 for the overload trip time vs current curves.
When the overload is set to not available (OFF), the electronic overload is disabled and another motor overload protection device must be supplied.
When the overload is set to bypass (BYP), the electronic overload is disabled during starting and then the thermal content is charged to 90% once the starter gets up-to-speed. When the motor is up-to-speed, the RediStart Micro II will use a class 10 overload for the motor protection.
OFF - no thermal overload
1-40 - class 1 through 40 overload
BYP - overload bypassed during starting, class 10 once up-to-speed
75
5.17 PROGRAMMING: Motor Protection - Line Current
% Imbalanc (percent imbalance)
Description The percent imbalance parameter sets the allowable phase to average current
Values The percent imbalance is adjustable from 10 to 40% in 1% increments.
Default The default value for the percent imbalance is 15%.
difference that is allowed before the starter will shut down. The current imbalance must exist for the amount of time set by the imbalance delay time before this will occur.
The current imbalance for each phase is calculated as the percentage difference between the phase current and the average current. The equation for the current imbalance is;
II
% imbalance
If the highest calculated current imbalance is greater than the current imbalance level, the starter will shut down the motor and display a fault 23 to fault 28 depending on the phase that has the out of range current.
ave phase
=
100%
×
ave
I
Imbal Dela (imbalance delay)
Description The imbalance delay parameter sets the time that the current imbalance must be
Values The imbalance delay parameter can be set from 0.1 to 90.0 seconds in 0.1 second
greater than the percent imbalance parameter before a trip will occur.
intervals.
Default The default value for the imbalance delay parameter is 0.5 seconds.
@ Stop Dly (current at stop delay)
Description The current at stop delay parameter sets the time that a phase current must be
Values The current at stop delay parameter can be set from 0.1 to 10.0 seconds in 0.1 second
Default The default value for the current at stop delay parameter is 1.5 seconds.
greater than 5% of the motor FLA parameter, while the starter is in a stopped state, before a trip will occur.
intervals
76
5.17 PROGRAMMING: Motor Protection - Line Current
% No C@Run (percent no current at run)
Description The percent no current at run parameter sets a low current operating level. If the
Values The percent no current at run parameter can be set from 2 to 40% in 1% increments.
Default The default value for the percent no current at run parameter is 5%.
current falls below this level, the RediStart Micro II will shut down the starter and give a no current at run fault. This level is set as a percentage of the motor full load amps. The current must remain below this parameter setting for the no current at run delay time before a fault will occur.
No C@R Dly (no current at run delay)
Description The no current at run delay parameter sets the time that the motor current must be
Values The no current at run parameter can be set from 0.1 to 90.0 seconds in 0.1 second
Default The default value for the no current at run parameter is 1.0 seconds.
less than the percent no current at run parameter setting, while the starter is in a run state, before a trip will occur.
intervals.
77
5.18 PROGRAMMING: Motor Protection - Line Voltage
H/L Volts (high/low voltage)
Description The high/low voltage trip sets the allowable operating voltage range. If the voltage on
Values The high/low voltage is adjustable from 10 to 30% in 1% increments.
any line goes outside of the allowable operating range, the starter will shut down and give a high or low line fault.
The low and high voltage trip points are calculated as follows;
The base voltage (V voltage parameter (see page 53) or automatically selected according to the following list;
The base voltage (V and JPC18 on the RediStart Micro computer card. Refer to the jumper settings on page for information on setting these parameters.
The line voltage must be out of the specified range for the time specified by the delay time parameter before the starter will trip.
low base base=−× ÷
V V V (Parameter 100)
high base base=+× ÷
V V V (Parameter 100)
) that is used for the calculations is either set by the source
base
208VAC if average line voltage is between 180VAC and 224VAC. 240VAC if average line voltage is between 225VAC and 269VAC. 315VAC if average line voltage is between 270VAC and 334VAC. 380VAC if average line voltage is between 345VAC and 409VAC. 460VAC if average line voltage is between 410VAC and 489VAC. 480VAC if average line voltage is between 490VAC and 524VAC. 575VAC if average line voltage is between 525VAC and 650VAC. 1000VAC if average line voltage is between 651VAC and 1000VAC.
) used for the calculations is selected by setting jumpers JPC17
base
Default The default value for the high/low voltage parameter is 20%.
Delay Time
Description The delay time parameter sets the time that the line voltage must go outside of the
Values The voltage delay parameter is adjustable from 0.1 to 90.0 seconds in 0.1 second
Default The default value for the voltage delay parameter is 0.5 seconds.
voltage range set by the high/low voltage parameter before a high or low voltage trip will occur.
This parameter may be lengthened to allow for temporary voltage fluctuations outside of the allowable voltage range. If the time is extended, the control voltage must be monitored to ensure it remains within acceptable limits. If the control voltage is fluctuating, an un-interruptible power supply should be used.
intervals.
PH Dect Dl (Phase detect delay)
Description The phase detect delay parameter sets the delay time on Fault #56: “Phase Detection.”
This fault detects a loss of proper phase timing even when the phase code remains valid; example: loss of line when the motor back generates a voltage. This allows a much faster detection than low line or no current at run faults.
Values The PH Dect Dl parameter is adjustable from 0.3 to 5.0 seconds in 0.1 second
Default The default value for the PH Dect Dl parameter is 0.8 seconds.
78
intervals.
5.19 PROGRAMMING: Motor Protection - Line Frequency
High Freq. (high frequency)
Description The high frequency parameter sets the highest line frequency that the starter will
Values The high frequency trip is adjustable from 72 to 24hz in 1hz increments.
Default The default value for the high frequency trip parameter is 72hz.
operate on.
When operating on line power, the default setting will usually suffice. If the application is speed sensitive, or the line power is suspect, the high frequency parameter can be set to the highest acceptable frequency. When operating on generator power, the high frequency parameter should be set to the highest acceptable frequency. This will ensure that a generator problem will not cause unnecessarily large fluctuations in the speed of the motor.
The frequency must be above the high frequency setting for the frequency delay parameter before the starter will recognize a high frequency condition. Once a high frequency condition exists, the starter will shut down and display a fault 4, High Freq. Trip.
Low Freq. (low frequency)
Description The low frequency parameter sets the lowest line frequency that the starter will
operate on.
When operating on line power, the default setting will usually suffice. If the application is speed sensitive, or the line power is suspect, the low frequency parameter can be set to the lowest acceptable frequency. When operating on generator power, the low frequency parameter should be set to the lowest acceptable frequency. This will ensure that a generator problem will not cause unnecessarily large fluctuations in the speed of the motor.
The frequency must be below the low frequency setting for the frequency delay parameter before the starter will recognize a low frequency condition. Once a low frequency condition exists, the starter will shut down and display a fault 5, frequency < Low Freq. Trip.
Values The low frequency trip is adjustable from 23 to 71hz in 1 Hz intervals.
Default The default value for the low frequency trip parameter is 23hz.
Freq Delay (frequency delay)
Description The frequency delay parameter sets the time that the line frequency must go above
Values The frequency delay parameter can be set from 0.1 to 90.0 seconds in 0.1 second
Default The default value for the frequency delay parameter is 0.1 seconds.
the high frequency trip point or below the low frequency trip parameter before a high or low frequency fault will occur.
intervals.
79
5.20 PROGRAMMING: Motor Protection - Ground Fault
GND Fault (ground fault)
Description The ground fault parameter sets a ground fault current trip or indicate level that can
Values The ground fault is adjustable from 1 to 100 amps in 1 amp increments. The ground
Default The default value for the ground fault parameter is Off.
be used to protect the system from a ground fault condition.
The starter monitors the instantaneous sum of the three line currents to detect the ground fault current. This is often referred to as residual ground fault
protection. This type of protection is meant to provide machine ground fault protection only. It is not meant to provide human ground fault protection.
The ground fault current has to remain above the ground fault level for the ground delay parameter time before the starter will recognize a ground fault condition. Once the starter recognizes a ground fault condition, it will shut down the motor and display a fault 71-Ground Fault. If a programmable relay is set to ground fault (GND), the starter will energize the relay when the condition exists.
If it is desired to have the starter continue to operate after a ground fault is detected, enter the fault classes menu (see page 88) and change the classification of fault 71 to either Dis, WrnA, WrnB, or WrnC.
A typical value for the ground fault current setting is 10% to 20% of the full load amps of the motor.
fault current can also be set to Off by setting it below 1 amp.
GND Delay (ground delay)
Description The ground delay parameter sets the period of time that the ground fault current
Values The ground delay parameter can be set from 0.1 to 90.0 seconds in 0.1 second
Default The default value for the ground delay parameter is 1.0 seconds.
must be above the ground fault current setting before a ground fault trip will occur.
intervals.
80
5.21 PROGRAMMING: Motor Protection - Shorted SCR
@ Ramp DLY (shorted SCR at ramp delay)
Description The shorted SCR at ramp parameter sets the period of time that there must be a
Values The shorted SCR at ramp parameter can be set from 0.1 to 90.0 seconds in 0.1 second
Default The default value for the shorted SCR at ramp parameter is 0.2 seconds.
current imbalance of more than 50%, while the starter is accelerating, before a shorted SCR fault occurs.
intervals.
@ Stop DLY (shorted SCR at stop delay)
Description The shorted SCR at stop parameter sets the period of time that there must be a
Values The shorted SCR at stop parameter can be set from 0.1 to 90.0 seconds in 0.1 second
Default The default value for the shorted SCR at stop parameter is 1.0 seconds.
current flow of more than 50% of the motor FLA value, while the motor is stopped, before a shorted SCR fault will occur.
intervals.
81
5.22 PROGRAMMING: Motor Protection - Over Current
Current
Description The current parameter is set as a percentage of the motor FLA parameter. It sets a
Values The current is adjustable from 50 to 800%, in 1% increments. The current can also be
Default The default value for the current parameter is Off.
high current trip or indicate level that can be used to protect the system from an overloaded condition.
The motor current has to remain above the current setting for the delay time parameter before the starter will recognize an over current condition.
NOTE: The overcurrent parameter does not become active until after the starter has reached full speed.
set to Off by going above 800%.
Detect Dly (detect delay)
Description The detect delay time parameter sets the period of time that the motor current must
Values The detect delay time can be set from 0.1 to 90.0 seconds in 0.1 second intervals.
Default The default value for the detect delay time parameter is 0.1 second.
be greater than the over current level before a shear pin trip will occur.
Release Dl (release delay)
General The release delay time sets how long the relay is energized after the over current
Values The release delay time parameter can be set from 1.0 to 90.0 seconds in 0.1 second
Default The default value for the release delay time parameter is 10.0 seconds.
condition is cleared. This parameter is only functional if a relay has been programmed to OCT (over current trip) in the relay sub-menu (see page 91) and the fault has been disabled in the fault classes sub-menu (see page 88).
intervals
82
5.23 PROGRAMMING: Motor Protection - Under Current
Current
Description The current parameter is set as a percentage of the motor FLA parameter. It sets a
Values The current is adjustable from 10 to 100% in 1% increments. The current can also be
Default The default value for the current parameter is Off.
low current trip or indicate level and can be used to protect the system from an unloaded condition. The under current protection is especially useful to protect a pump. The motor current will fall when the pump becomes unloaded and the under current protection can be used to shut down the motor or warn of this unloaded condition.
The motor current has to remain below the under current setting for the under current delay time parameter before the starter will recognize an under current condition.
set to Off by going below 10%
Detect Dly (detect delay)
Description The detect delay time parameter sets the period of time that the motor current must
Values The detect delay time parameter can be set from 0.1 to 90.0 seconds in 0.1 second
Default The default value for the detect delay time parameter is 0.1 seconds.
be less than the current level before an under current trip will occur.
intervals.
Release Dl (release delay)
General The release delay time sets how long the relay is energized after the under current
Values The release delay time parameter can be set from 1.0 to 90.0 seconds in 0.1 second
Default The default value for the release delay time parameter is 10.0 seconds.
condition is cleared. This parameter is only functional if a relay has been programmed to UCT (under current trip) in the relay sub-menu (see page 91) and the fault has been disabled in the fault classes sub-menu (see page 88).
intervals
83
5.24 PROGRAMMING: Motor Protection - Start Lockouts
Starts/Hou (starts per hour)
Description The starts per hour parameter will set the number of allowed starts in one hour. If the
Values The starts per hour is adjustable from 1 to 20 starts, in 1 start intervals. The starts
Default The default value for the starts per hour parameter is Off.
starter has been stopped and the number of starts given in the last hour has exceeded this setting, the starter will display SPH in the top left of the display and the time, in minutes, until the next start is allowed in the bottom left of the display.
NOTE: Starts/Hou does not increment on a PORT restart.
per hour can also be set to Off by going below 1.
Time Start (time between starts)
Description The time between starts parameter sets the minimum allowed time between starts.
Values The time between starts is adjustable from 1 to 600 minutes, in 1 minute intervals.
Default The default value for the time between starts parameter is Off.
Once a start command has been given, the next start cannot be performed until this time has expired. If the starter is stopped and the time between starts has yet to expire, the starter will display TBS in the top left of the display and the time, in minutes, until the next start is allowed in the bottom left of the display.
NOTE: Time Start does not increment on a PORT restart.
The time between starts can also be set to Off by going below 1 minute.
BKS Timer (backspin timer)
Description The backspin timer parameter sets the minimum time between a stop and the next
Values The backspin timer is adjustable from 1 to 200 minutes, in 1 minute intervals. The
Default The default value for the backspin timer parameter is Off.
allowed start. If the starter is stopped and a time has been set, the starter will display BKS in the top left of the display and the time, in minutes, until the next allowed start in the bottom left.
NOTE: The BKS Timer does not increment on a PORT restart.
backspin timer can also be set to Off by going below 1 minute.
84
5.25 PROGRAMMING: Motor Protection - Starting Timers
UTS Timer (up-to-speed timer)
Description The up-to-speed timer parameter sets the maximum acceleration time to full speed
Values The up-to-speed timer parameter can be set from 1 to 300 seconds. The up-to-speed
Default The default value for the up-to-speed timer parameter is 30 seconds.
that the motor can take. A stalled motor condition will be detected if the motor does not get up-to-speed before the up-to-speed timer expires. This allows the programming of a maximum acceleration time for the motor. The motor is considered up-to-speed once the current stabilizes below 175 percent of the FLA value and the ramp time expires.
NOTE: The up-to-speed timer has to be set to a time that is greater than the highest ramp time in use. The up-to-speed timer will not automatically change to be greater than the ramp time. If a ramp time greater than the up-to-speed timer is set, the starter will display a up-to-speed fault every time a start is attempted.
Fault Code 74 - Up to Speed Fault will be displayed when a stalled motor condition is detected.
timer can be set to Off by setting it below 1 second.
Zero Speed
Description When using the zero speed stall protection, the starter will start monitoring the zero
speed input (at JC13-8) as soon as a run command is given and will recognize a stalled motor if the zero speed time has elapsed before the zero speed signal is removed. The zero speed input requires a 120VAC signal to indicate the zero speed condition.
Fault Code 69 - Zero Speed Timer will be displayed when a stalled motor condition is detected.
NOTE: The zero speed timer is not available on synchronous starters.
Values The zero speed parameter can be set from 1 to 30 seconds, The zero speed timer can be
Default The default value for the zero speed parameter is Off.
set to Off by setting it below 1 second.
85
5.26 PROGRAMMING: Motor Protection - Permissive Input
Therm. In
Description The trip input parameter sets the time that power must be removed from the 120VAC
Values The trip input parameter can be set from 0.1 to 90.0 seconds in 0.1 second intervals.
Default The default value for the trip input parameter is 0.5 seconds.
input at JC13 terminal #1 on the RediStart Micro II CPU card before a fault occurs. When an external fault occurs, the starter will shut down and display a Fault 75 ­External Fault.
86
5.27 PROGRAMMING: Motor Protection - Misc.
Phase Orde (phase order)
Description The line phasing parameter sets the phase sensitivity of the starter. This can be used
Values The line phasing can be set to;
Default The default value for the phase sensitivity parameter is Ins.
to protect the motor from a possible change in the incoming phase sequence. If the incoming phase sequence does not match the set phase rotation, the starter will display phs err while stopped and will fault if a start is attempted.
Ins - will run with either phase sequence
ABC - will only run with ABC phase sequence
CBA - will only run with CBA phase sequence
# Auto RST (number of auto resets)
Description The number of auto resets parameter sets how many times in one hour the RediStart
Values The number of auto resets parameter can be set from 1 to 5.
Default The default value for the number of auto resets parameter is 4.
Micro II will reset a non-critical fault.
This parameter is used in conjunction with the automatic fault reset jumper JPC19 (see page 26) and with the fault classes sub-menu (see page 88). When JPC19 is placed in the automatic fault reset position (1-2), this parameter sets how many times in one hour any non-critical faults are reset. Non-critical faults are set in the fault classes sub-menu (see page 88).
No Main PW (no main power)
Description The no mains power delay parameter sets the period of time that the starter must
Values The no mains power delay parameter is adjustable from 1 to 5 seconds in 1 second
Default The default value for the no mains power parameter is 1 second.
have a run command without mains power before a no mains fault will occur.
intervals
87
5.28 PROGRAMMING: Motor Protection - Fault Classes
Fault Classes
Description The fault classes menu allows the user to change the action taken when a fault occurs.
Values Each fault can be classified as;
Default The default value for each fault depends on the fault.
The menu will allow every fault to be given a different classification depending on the user requirements. This allows the user to set the starter to;
Trip the starter and display the fault code and description if it occurs.
Ignore the fault if it occurs and continue to run.
Activate a relay if the fault occurs and continue to run.
Note: Not all faults can be assigned every classification. Faults critical to starter operation may only be programmed to non-critical (NonC) and/or critical (Crit).
NonC - Non-critical fault. Starter will trip. Resets if JPC19 set to 1-2.
Crit - Critical fault. Starter will trip and require a manual reset.
Dis - Fault is disabled. No action will be taken when fault occurs.
WrnA - Fault will not trip starter. Energizes relay programmed to WrnA.
WrnB - Fault will not trip starter. Energizes relay programmed to WrnB.
WrnC - Fault will not trip starter. Energizes relay programmed to WrnC.
Note: Each relay output can be assigned to as many different faults as required.
88
5.29 PROGRAMMING: Meters & Relays - Meter Setup
2
Meter #1 , Meter #2
Description The RediStart Micro II displays two meter functions on the right side of the display.
Values The meter#1 display and meter#2 display parameters can each be set to one of the
These parameters set what each meter will display. The meter locations are as shown.
Stop Ready
following;
Asc - Each phase current in a scrolling manner.
Aav - Average current.
A1 - Phase 1 current.
A2 - Phase 2 current.
A3 - Phase 3 current.
Vsc - Each phase voltage in a scrolling manner.
Vav - Average voltage.
V1 - Phase 1 voltage.
V2 - Phase 2 voltage.
V3 - Phase 3 voltage.
Hz - Frequency.
O/L - Thermal overload in percentage from 0% to 100% (100% = Trip).
pf - Motor power factor.
etm - The elapsed running time in tenths of an hour.
Hetm - The elapsed running time in hours.
Uetm - The user resettable elapsed running time.
Ustr - The user resettable motor starts counter.
I1= 0A
V1= 0V
Meter #1 Meter #
KW - Motor real power consumption.
KWH - Kilo-watt-hours used by the motor.
MWH - Mega-watt-hours used by the motor.
KVar - Motor reactive power consumption.
KVA - Motor apparent power consumption.
Tv - Tachometer voltage.
%s - Maximum speed in percentage.
Ms - Motor speed.
GDF - Ground fault current in amps.
Srts - Motor starts counter.
Ibal - Motor current imbalance in percentage.
ComR - The number of communication requests received.
ComT - The number of communication transmits sent.
CRat - The communications rate.
RTD#? - The temperature being read by RTD with the number ?.
TAmx - The maximum temperature being read by a RTD.
TSmx - The maximum temperature being read by a stator RTD.
TBmx - The maximum temperature being read by a bearing RTD.
TApk - The peak temperature being read by a RTD.
TSpk - The peak temperature being read by a stator RTD.
TBpk - The peak temperature being read by a bearing RTD.
IAmx - The number of the RTD reading the highest temperature.
ISmx - The number of the RTD reading the stator highest temperature.
IBmx - The number of the RTD reading the highest bearing temperature.
IApk - The number of the RTD reading the peak temperature.
ISpk - The number of the RTD reading the peak stator temperature.
IBpk - The number of the RTD reading the peak bearing temperature.
TT% - Calculated TruTorque torque value in % of Micro II torque units.
Default The default value for the meter #1 display parameter is Asc.
The default value for the meter #2 display parameter is Vsc.
89
5.29 PROGRAMMING: Meters & Relays - Meter Setup
NOTE: The following meters will show a single decimal place when below the AutoRange setpoint: etm, Hetm, Uetm, KW, KWH, MWH, KVar, KVA. The value will show MAX and stop incrementing when they reach (6553). All other meters will show MAX when they reach (9999).
AutoRange
Description The autorange parameter sets the value where the display meter will change ranges.
Values The autorange can be set from 50.0 to 99.9 in 0.1 intervals.
Default The default value for the autorange parameter is 99.9.
Meter Rsts (meter resets)
Description The meter resets parameter allows the user to reset the different RediStart Micro II
Values The meter resets can be set to the following;
Default The default value for the meter resets parameter is None.
meters.
None - No meter resets.
KWH - Reset the kilo-watt hour meter.
RunT - Reset the user run time hours meter.
Strt - Reset the user number of starts counter.
SCtr - Reset the serial communication counters.
RTDP - Reset the peak RTD meters.
When set to any of these values, the parameter will automatically return to None but the meter will be reset.
Scroll Tim (scroll time)
Description The scroll time parameter sets the delay time between display pages. If this is set to a
Values The scroll time is adjustable from 1 second to 120 seconds in 1 second intervals. The
Default The default value for the scroll time is Off.
time, the display will switch between different pages which will show all the different metering values. See page 29 for a description of the display pages. If this is set to Off, the display pages can be viewed by pressing the Up or Down buttons.
meter scroll time can also be turned Off.
90
Loading...