Bender PEM330, PEM333 Quick Start Manual

Page 1
Quick start PEM330/PEM333
These short instructions do not replace the operating manu­al. You will find the operating manual on www.bender-de.com
Make sure that the personnel has read this manual and under­stood all instructions relating to safety.
Intended use
The digital universal measuring device PEM330/PEM333 is suitable for measuring and displaying electrical parameters of electricity networks. The device measures current, voltage, energy consumpti­on and power as well as the total harmonic distortion for assess­ment of the voltage and current quality.
The accuracy of the active energy metering corresponds to class
0.5 S in compliance with the DIN EN 62053-22 (VDE 0418 Part 3-
22):2003-11.
Scope of delivery Safety instruction
one PEM330 or PEM333
important safety instructions for Bender Products
these short instructions
one sealing frame "IP54"

Danger of electric shock!

Follow the basic safety rules when working with electricity. Consider the data on the rated voltage and supply voltage as specified in the technical data!
Installing the device
Front panel mounting (front view, side view, panel cut-out)
80
62
96
91
96
A front panel cutout of 92 mm x 92 mm is required for the device.
1. Fit the device through the cut-out in the front panel.
2. Put the 4 transparent mounting brackets from behind on the edges of the device.
3. Push the clips tightly against the panel to secure the device.
4. Check the device to ensure that it is firmly installed in the front panel.
18 1862
9691
92
92
PEM330-333_D00004_00_Q_XXEN/03.2013
1
Page 2
Quick start PEM330/PEM333
Terminal Description
A1, A2,
Supply voltage. Power protection by a 6 A fuse, quick re­sponse. If being supplied from an IT system, both lines have to be protected by a fuse.
DI1, DI2, DIC Digital inputs (PEM333 only)
DO13, DO14,
DO23, DO24
Digital outputs (N/O contacts) (PEM333 only)
I11, I12, I21, I22,
I31, I32
Connection to the system to be monitored
D+, D-, SH Connection RS-485 bus (PEM333 only)
L1, L2, L3, N
Measuring voltage inputs: The measuring leads should be protected with appropriate fuses.
V
Connection of the device

Wiring diagram

D-SH
DO 13
DO14DO
23
24 DI1 DI2
DIC
P1(RS-485) DO D+
• l11 l12 l22 l32 L1 L2 N• l21 • l31
A1/
A2/
+
-
U
S
DI
L3
DI1 DI2 DIC
I12
I11
L1
I22
I21
L2L2L3L3N
I32
I31
L1
N
DO
DO13 DO14
DO23 DO24

Connection

1. The connecting terminals are located on the rear. Connect the PEM330/PEM333 to the supply voltage (terminals A1 and A2 resp. +/-). Connect terminal " " to the protective con­ductor.
Connection diagram voltage inputs
Three-phase 4-wire system (TN, TT, IT systems)
The PEM can be used in three-phase 4-wire systems, independent of the type of distribution system (TN, TT, IT system).
2. Power protection by a 6 A fuse, quick response. If being sup­plied from an IT system, both lines have to be protected by a fuse.
3. Connection to the RS-485-Bus is made via the terminals D+, D- and SH. Up to 32 devices can be connected to the bus. The maximum cable length for the bus connection of all devices is 1200 m.
AC 400 V / 230 V
PEM
L1L2L3
R
i
N
Three-phase 3-wire system
The PEM can be used in three-phase 3-wire systems. The line-to-line voltage must not exceed AC 400 V.
Connection via voltage transformers
The coupling via measuring voltage transformers allows the use of a measuring device in medium and high voltage systems. The trans­formation ratio in PEM330/PEM333 can be adjusted (1…2200).
2
AC 400 V
L1L2L3
R
i
PEM
LV / MV / H
PEM
L1L2L3
R
i
N
PEM330-333_D00004_00_Q_XXEN/03.2013
Page 3
Commissioning
Check proper connection
During installation and connection, abide by the relevant standards and regulations and follow the operating manuals for the device.
Before switching on
1. Before switching on think carefully about these questions:
2. Does the connected supply voltage US correspond to the nameplates information?
3. Is the nominal system voltage of the measuring current transformer not exceeded?
4. Does the measuring current transformer's maximum current correspond to the nameplate information of the connected device?
Getting to know the operating elements
Quick start PEM330/PEM333
Switching on
After switching on, proceed as follows:
1. Connect the supply voltage.
2. Set the bus address/IP address.
3. Set the CT transformer ratio (for each channel).
4. Change the measuring current transformer's counting direc­tion, if required.
5. Set the nominal voltage.
6. Select wye connection or delta connection.

Legend

LED "kWh" and LED "kvarh": Pulse output "SYSTEM" button: Display mean value and total value (current, vol-
tage); in the menu: in case of numerical values: move the cursor one position to the left "PHASE" button: Display line-conductor related measured quanti-
ties; in the menu: go up one entry;in case of numerical valu­es: increasing the value
"ENERGY" button: Display measured values: Active and reactive
energy import/active and reactive energy export (line 4); in the menu: move down one entry; in case of numerical valu­es: reduce the value
"SETUP" button: Press > 3 s: switching between setup menu and
standard display; in the menu: selection of the parameter to be edited; confirm entry
Data display

"SYSTEM" button

Column
left
LL V
Ln V
I
4
U
I
D
M
D
D
M
D
Column
right
First
line
A
WPFØ I
Ø U
kvar
Hz
kW
kvar
kVA
A
kW
A I4
% %
A A A
kW
kvar
kVA
LL
P
ges
Wye con­nection: Ø U
LN
Delta con­nection: Ø U
LL
Unbalance UUnbalance
Demand I
Demand P Demand Q Demand S
Second
line
P
ges
Q
ges
Q
ges
Ø I
I
Demand I2Demand I
1
Power factor λ
F
S
ges
P
ges
Third
line

Button "ENERGY"

Parameters in the fourth line:
Column left Column right Value
kWh Active energy import
-- kWh Active energy export
kvarh Reactive energy import
-- kvarh Reactive energy export
S Apparent energy
3
PEM330-333_D00004_00_Q_XXEN/03.2013
3
Page 4
Quick start PEM330/PEM333

"PHASE" button

Column
left
Ln Ln Ln
LL LL LL
D
U
U
P F
K F
Column
First line Second line Third line
right
A AAI1 I2 I3
V V V
*
U
L1
V
U
V
L1L2
V
kW kW kW
var var var
kVA kVA kVA
PF PF PF
PF PF PF
*
P
L1
*
Q
L1
*
S
L1
*
λ
L1
Displacement factor
*
cos (φ)
L1
%
THD U
% %
t
%
I
% %
t
L1
THD I
1
k-factor I
1
Phase angle
U
L1
I
Phase angle I
*
U
L2
U
L2L3
*
P
L2
*
Q
L2
*
S
L2
*
λ
L2
Displacement factor
*
cos (φ)
L2
THD U
L2
THD I
2
k-factor I
2
Phase angle
U
L2
Phase angle I2Phase angle I
1
*
U
L3
U
L3L1
*
P
L3
*
Q
L3
*
S
L3
*
λ
L3
Displacement factor
cos (φ)
THD U
THD I
3
k-factor I
Phase angle
U
L3
Note: * In "delta connection" mode the display shows "– ".

"SETUP" button

Press the "SETUP" button for more than 3 s to access the setup mode. Press the "SETUP" button again to return to the default display screen.
To be able to change parameters, you must first enter
the password. (factory setting: 0)
The following diagram will help you to familiarise yourself with the menu:
Serial number of device
info INFO
set backlight time out BLTO SET
choose CT direction CT REV
* set DO triggered mode DO CTRL
clear SOE CLR SOE
*
L3
L3
3
3
clear peak demand CLR DMD
clear energy CLR ENGY
set energy pulse constant EN CONST
enable energy pulse EN PULSE
set demand DMD SET
set energy values SET ENGY
set clock CLK
set date DATE
* set conguration parity bit CONFIG
* set baud rate BAUD
* set address for measuring device ID
choose kVA calcuation method KVA SET
choose power factor convention PF SET
select current transformer ratio CT
select transformer ratio for the voltage transformer PT
set wiring mode TYPE
change password SET PASS
enter password PASSWORD
OK
OK
OK
OK
OK
OK
Date of software update UPDATE
Protocol version PRO VER
Software Version SW-VER
CT polarity I3 REV
set I
3
CT polarity I2 REV
set I
2
CT polarity I1 REV
set I
1
set DO2 control mode DO2
set DO1 control mode DO1
set no. of sliding windows NUM
set demand period PERIOD
set apparent energy kVAh
set reactive energy export -kvarh
set reactive energy import kvarh
set active energy export -kWh
set active energy import kWh
enter new password NEW PASS
OK
PROGRAMMING
Setup menu
OK
* PEM333 only
Button
All rights reserved. Reprinting only with permission of the publisher. Subject to change!
D0000400QXXEN
© Bender GmbH & Co. KG
Bender GmbH & Co. KG Tel.: +49 6401 807-0 E-Mail: info@bender-de.com Londorfer Str. 65 Postfach 1161
4
35305 Gruenberg Germany Fax: +49 6401 807-259 Web: http://www.bender-de.com
35301 Gruenberg Germany
PEM330-333_D00004_00_Q_XXEN/03.2013
Loading...