These short instructions do not replace the operating manual. You will find the operating manual onwww.bender-de.com
Make sure that the personnel has read this manual and understood all instructions relating to safety.
Intended use
The digital universal measuring device PEM330/PEM333 is suitable
for measuring and displaying electrical parameters of electricity
networks. The device measures current, voltage, energy consumption and power as well as the total harmonic distortion for assessment of the voltage and current quality.
The accuracy of the active energy metering corresponds to class
0.5 S in compliance with the DIN EN 62053-22 (VDE 0418 Part 3-
22):2003-11.
Scope of deliverySafety instruction
●one PEM330 or PEM333
●important safety instructions for Bender Products
●these short instructions
●one sealing frame "IP54"
Danger of electric shock!
Follow the basic safety rules when working with electricity.
Consider the data on the rated voltage and supply voltage as
specified in the technical data!
Installing the device
Front panel mounting (front view, side view, panel cut-out)
80
62
96
91
96
A front panel cutout of 92 mm x 92 mm is required for the device.
1.Fit the device through the cut-out in the front panel.
2.Put the 4 transparent mounting brackets from behind on the edges of the device.
3.Push the clips tightly against the panel to secure the device.
4.Check the device to ensure that it is firmly installed in the front panel.
181862
9691
92
92
PEM330-333_D00004_00_Q_XXEN/03.2013
1
Page 2
Quick start PEM330/PEM333
TerminalDescription
A1, A2,
Supply voltage. Power protection by a 6 A fuse, quick response. If being supplied from an IT system, both lines
have to be protected by a fuse.
DI1, DI2, DICDigital inputs (PEM333 only)
DO13, DO14,
DO23, DO24
Digital outputs (N/O contacts) (PEM333 only)
I11, I12,
I21, I22,
I31, I32
Connection to the system to be monitored
D+, D-, SHConnection RS-485 bus (PEM333 only)
L1, L2, L3, N
Measuring voltage inputs: The measuring leads should
be protected with appropriate fuses.
V
Connection of the device
Wiring diagram
D-SH
DO
13
DO14DO
23
24 DI1 DI2
DIC
P1(RS-485)DO
D+
• l11 l12 l22 l32 L1 L2N• l21• l31
A1/
A2/
+
-
U
S
DI
L3
DI1DI2DIC
I12
I11
L1
I22
I21
L2L2L3L3N
I32
I31
L1
N
DO
DO13DO14
DO23DO24
Connection
1.The connecting terminals are located on the rear. Connect
the PEM330/PEM333 to the supply voltage (terminals A1 and
A2 resp. +/-). Connect terminal " " to the protective conductor.
Connection diagram voltage inputs
Three-phase 4-wire system (TN, TT, IT systems)
The PEM can be used in three-phase 4-wire systems, independent of
the type of distribution system (TN, TT, IT system).
2.Power protection by a 6 A fuse, quick response. If being supplied from an IT system, both lines have to be protected by a
fuse.
3.Connection to the RS-485-Bus is made via the terminals D+,
D- and SH. Up to 32 devices can be connected to the bus. The
maximum cable length for the bus connection of all devices
is 1200 m.
AC 400 V / 230 V
PEM
L1L2L3
R
i
N
Three-phase 3-wire system
The PEM can be used in three-phase 3-wire systems.
The line-to-line voltage must not exceed AC 400 V.
Connection via voltage transformers
The coupling via measuring voltage transformers allows the use of
a measuring device in medium and high voltage systems. The transformation ratio in PEM330/PEM333 can be adjusted (1…2200).
2
AC 400 V
L1L2L3
R
i
PEM
LV / MV / H
PEM
L1L2L3
R
i
N
PEM330-333_D00004_00_Q_XXEN/03.2013
Page 3
Commissioning
Check proper connection
During installation and connection, abide by the relevant standards
and regulations and follow the operating manuals for the device.
Before switching on
1.Before switching on think carefully about these questions:
2.Does the connected supply voltage US correspond to the
nameplates information?
3.Is the nominal system voltage of the measuring current
transformer not exceeded?
4.Does the measuring current transformer's maximum current
correspond to the nameplate information of the connected
device?
Getting to know the operating elements
Quick start PEM330/PEM333
Switching on
After switching on, proceed as follows:
1.Connect the supply voltage.
2.Set the bus address/IP address.
3.Set the CT transformer ratio (for each channel).
4.Change the measuring current transformer's counting direction, if required.
5.Set the nominal voltage.
6.Select wye connection or delta connection.
Legend
LED "kWh" and LED "kvarh": Pulse output
"SYSTEM" button: Display mean value and total value (current, vol-
tage); in the menu: in case of numerical values: move the cursor
one position to the left
"PHASE" button: Display line-conductor related measured quanti-
ties; in the menu: go up one entry;in case of numerical values: increasing the value
"ENERGY" button: Display measured values: Active and reactive
energy import/active and reactive energy export (line 4); inthe menu: move down one entry; in case of numerical values: reduce the value
"SETUP" button: Press > 3 s: switching between setup menu and
standard display; in the menu: selection of the parameter to
be edited; confirm entry
Data display
"SYSTEM" button
Column
left
LLV
LnV
I
4
U
I
D
M
D
D
M
D
Column
right
First
line
A
WPFØ I
Ø U
kvar
Hz
kW
kvar
kVA
A
kW
AI4
%
%
A
A
A
kW
kvar
kVA
LL
P
ges
Wye connection:
Ø U
LN
Delta connection:
Ø U
LL
Unbalance UUnbalance
Demand I
Demand P Demand Q Demand S
Second
line
P
ges
Q
ges
Q
ges
Ø I
I
Demand I2Demand I
1
Power
factor λ
F
S
ges
P
ges
Third
line
Button "ENERGY"
Parameters in the fourth line:
Column leftColumn rightValue
kWhActive energy import
--kWhActive energy export
kvarhReactive energy import
--kvarhReactive energy export
SApparent energy
3
PEM330-333_D00004_00_Q_XXEN/03.2013
3
Page 4
Quick start PEM330/PEM333
"PHASE" button
Column
left
Ln
Ln
Ln
LL
LL
LL
D
U
U
P
F
K
F
Column
First lineSecond lineThird line
right
A
AAI1I2I3
V
V
V
*
U
L1
V
U
V
L1L2
V
kW
kW
kW
var
var
var
kVA
kVA
kVA
PF
PF
PF
PF
PF
PF
*
P
L1
*
Q
L1
*
S
L1
*
λ
L1
Displacement
factor
*
cos (φ)
L1
%
THD U
%
%
t
%
I
%
%
t
L1
THD I
1
k-factor I
1
Phase angle
U
L1
I
Phase angle I
*
U
L2
U
L2L3
*
P
L2
*
Q
L2
*
S
L2
*
λ
L2
Displacement
factor
*
cos (φ)
L2
THD U
L2
THD I
2
k-factor I
2
Phase angle
U
L2
Phase angle I2Phase angle I
1
*
U
L3
U
L3L1
*
P
L3
*
Q
L3
*
S
L3
*
λ
L3
Displacement
factor
cos (φ)
THD U
THD I
3
k-factor I
Phase angle
U
L3
Note:
* In "delta connection" mode the display shows "– ".
"SETUP" button
Press the "SETUP" button for more than 3 s to access the setup
mode.
Press the "SETUP" button again to return to the default display
screen.
To be able to change parameters, you must first enter
the password. (factory setting: 0)
The following diagram will help you to familiarise yourself with
the menu:
Serial number of device
info INFO
set backlight time out BLTO SET
choose CT direction CT REV
* set DO triggered mode DO CTRL
clear SOE CLR SOE
*
L3
L3
3
3
clear peak demand CLR DMD
clear energy CLR ENGY
set energy pulse constant EN CONST
enable energy pulse EN PULSE
set demand DMD SET
set energy values SET ENGY
set clock CLK
set date DATE
* set conguration parity bit CONFIG
* set baud rate BAUD
* set address for measuring device ID
choose kVA calcuation method KVA SET
choose power factor convention PF SET
select current transformer ratio CT
select transformer ratio for the voltage transformer PT
set wiring mode TYPE
change password SET PASS
enter password PASSWORD
OK
OK
OK
OK
OK
OK
Date of software update UPDATE
Protocol version PRO VER
Software Version SW-VER
CT polarity I3 REV
set I
3
CT polarity I2 REV
set I
2
CT polarity I1 REV
set I
1
set DO2 control mode DO2
set DO1 control mode DO1
set no. of sliding windows NUM
set demand period PERIOD
set apparent energykVAh
set reactive energy export -kvarh
set reactive energy import kvarh
set active energy export -kWh
set active energy import kWh
enter new password NEW PASS
OK
PROGRAMMING
Setup menu
OK
* PEM333 only
Button
All rights reserved.
Reprinting only with permission
of the publisher.
Subject to change!