Bender MK2000CBM Installation Bulletin / Reference Manual

T M
Document NAE2028450 11.2012 © Bender Inc. Page 1/1 Side 1/2Bender Inc. USA: 800.356.4266 / 610.383.9200 / medical@bender.org Canada: 800.243.2438 / 905.602.9990 / info@bender-ca.com www.bender.org
MK2000CBM
Installation Bulletin / Reference Guide
This document is intended as a reference guide to installing and setting an MK2000CBM series remote indicator. This document includes installation instructions and typical front plate display indications of the device. For complete details, including installation, setup, settings, and troubleshooting, refer to the LIM2010 user manual, document NAE2025010.
Only qualied maintenance personnel shall operate or service this equipment. These instructions should not be viewed as sucient for those who are not otherwise qualied to operate or service this equipment. This document is intended to provide accurate information only. No responsibility is assumed by BENDER for any consequences arising from use of this document. This device series is intended for use only with the BENDER LIM2010 Line Isolation Monitor.
Installation
Mounting
Two-gang plates provide four holes (Two at the top, two at the bottom) for screw mounting. Use the provided screws for mounting. Refer to gure 1 for dimensions.
Figure 1 - Two-gang wall plate dimensions in inches (mm)
Front Panel Display
1. Green “SAFE” LED. Illuminates when the connected LIM2010 is in the normal condition.
2. Yellow “HAZARD” LED. Illuminates when the connected LIM2010 is in the alarm condition.
3. Yellow “OVERLOAD” LED. Illuminates when the connected LIM2010’s trans­former overload alarm is active.
4. TEST button. Initiates a self-test of the connected LIM2010.
5. MUTE button with amber LED. Mutes the audible alarm when in the alarm condition. The amber LED indicates that the audible alarm has been muted.
6. THC Digital Display. Shows the Total Hazard Current in real-time.
7. Overload Digital Display. Shows the transformer overload percentage in re­al-time.
1
4 5
2
3
6
7
Figure 3 - MK2000CBM diagram
Figure 2: Wiring Diagram, MK2000CBM
STW3 / STW4
CP-LIM2010
Connector Plate
L1 from
transformer
secondary
L1 to
load center
To load center
RS-485 cable: twisted, shielded pair
MK2000CBM
120
Termination
Resistor
SAFE
HAZARD
MUTE
ESC
TEST
RESET
MENU
LIM2010
To panel
ground bus
L1 L2 12VDC CM A B RI1 K1/NC K1/COM K1/NO SAFE
HAZARD
RI2
LIMGND TEST 1S1 Z1/M+ 1S2 Z2/M­K2/COM K2/NC K2/NO
GND2
4.6“ (116.8)
4.55“ (115.6)
Wiring
MK2000CBM series remotes connect to a connector plate assembly utilizing a two-wire RS-485 connection. Ensure that the LIM2010 and corresponding connector plate have already been installed.
Refer to gure 2 below for wiring diagram. The
MK2000CBM may only be used with type LIM2010 line isolation monitor.
!
DANGER
• Disconnect all power before servicing.
• Reference NFPA 99 / CSA Z32 for Installation Standard.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Applicable Devices
This document applies to MK2000CBM remote indicators only.
T M
Document NAE2028450 11.2012 © Bender Inc. Page 1/1 Side 2/2Bender Inc. USA: 800.356.4266 / 610.383.9200 / medical@bender.org Canada: 800.243.2438 / 905.602.9990 / info@bender-ca.com www.bender.org
MK2000CBM
Installation Bulletin / Reference Guide
Connecting Multiple Remotes to a Single LIM2010
Up to two (2) MK2000CBM remotes may be connected to a single LIM2010. MK2000CBM series remotes utilize a special RS-485 protocol for communication. Each remote must be assigned a unique bus address for proper operation. Follow the procedure below to change the ad­dress for each remote indicator.
NOTE: The connected LIM2010 will be assigned address 1. A single connected MK2000CBM will be assigned address 2. This is the factory default and will not require the below procedure. An additionally connected remote must be assigned address 3 and will require the following procedure.
Step 2: Changing the Address of the MK2000CBM
Follow the below procedure for changing the communication address of the MK2000CBM.
Step 1: Wiring Modifications
All remotes and LIM2010 are wired in series with each other via each device’s “A” and “B” termi­nals. ONLY devices at the beginning and the end of the chain require the termination resistor. For the LIM2010, this resistor is activated via a switch on the device. For MK2000CBM remotes, a 120 Ω resistor must be wired across the remote’s “A” and “B” terminals. Refer to Figure 4 for a sample layout.
1) Hold the TEST and MUTE buttons simultaneously for at least four (4) seconds. “SP” will display on both screens.
2) Push the TEST button until “Ad” is displayed in the top screen, and two numbers (factory default “02”) is displayed in the bottom screen. This number is the communication address of the MK2000CBM remote.
3) Press the MUTE button. Press the TEST button until the desired address is displayed on the screen. Press the MUTE button to conrm this value.
4) Press the TEST button. “Ar” will display on the top screen, and two numbers (factory default “01”) will display on the bottom screen. This is the address of the connected LIM2010 device. In most applications, this value will not need to be changed. If so, skip to step 5. Otherwise, press the MUTE button. Press the TEST button until the desired LIM2010 address appears, and press MUTE again to con­rm this value.
5) Cycle power to the MK2000CBM to nish.
Technical Data
Operating voltage 12V DC or 12V AC Max. current 100 mA Operation class continuous operation Ambient temperature when operating 0º C to +50ºC when stored -25º C to +70º C Connection screw terminal block Conductor size AWG 30…12 Tightening torque 5…7 lb-in. Mounting by screws Weight 150 g
Figure 4 - Example communication bus layout
Loading...