Bender LifeGuard Reference Manual

LifeGuard® Series (Digital)
T M
This document is intended as a reference guide for installing and using a BENDER LifeGuard series Ground Fault Circuit Interrupter (GFCI) with digital display option. This document includes installa­tion, setup, and usage instructions. For complete instructions, including setup, use, and troubleshoot­ing, refer to LifeGuard user manual, document NAE1085011.
Only qualied maintenance personnel shall operate or service this equipment. These instructions should not be viewed as sucient for those who are not otherwise qualied to operate or service this equipment. This document is intended to provide accurate information only. No responsibility is as­sumed by BENDER for any consequences arising from use of this document.
Installation Bulletin / Reference Guide
Use of This Document
This installation guide applies to the special digital display version (option “D”) of the LifeGuard GFCI which meets the following requirements:
Uses door mounted MK1500-D remote (backplate only models have connections)
Uses “6” or “20” option (6 mA xed or 20 mA xed trip level) For compact LifeGuard GFCI models, consult document NAE1088320. For standard LifeGuard GFCIs with pushbutton front, consult document NAE1088011. For all models, consult the full LifeGuard GFCI user manual, document NAE1085011.
Installation
Mounting - NEMA 4X Polycarbonate Enclosure
The standard enclosure for LifeGuard series GFCIs is a NEMA 4X polycarbonate enclosure. The enclosure includes mounting feet and separate instructions on wall-mounting the enclosure. Refer to these instructions for more infromation. Refer to gure 1 below for dimensions.
Figure W1 - Single-Phase, Two-Wire Configurations (L1, N)
Figure W2 - Three-Phase, Three-Wire Configurations (L1, L2, L3)
Figure 1 - Dimensions of NEMA 4X polycarbonate enclosure
Table 1: Enclosure Dimensions in Inches (mm)
Type Enclosure A x B C D E F G
< 100 A 12x10x6
100 A 14x12x6
For other enclosure types, refer to LifeGuard user manual, document NAE1085011. If the LifeGuard GFCI was purchased without an enclosure (backplate only), consult the follow­ing section “Wiring,” as well as the section “Backplate Only Models” on the reverse side of this document for additional mounting and wiring requirements.
10.25“ x 8.25“
(260.5 x 209.5)
12.25“ x 10.25“ (311 x 260.5)
12.75“ (324)
14.75“ (375)
10.75“ (273)
12.75“ (324)
13.4“ (340)
15.4“ (391)
7.7“
(195.5)
7.7“
(195.5)
12.3“
(312.5)
14.3“ (363)
Wiring
The GFCI is installed in series with the main circuit. Connection of the main circuit conductors varies based on quantity of conductors and system voltage. In general, the following steps must be taken:
All active conductors, including the neutral, must be brought into the device, through the current trans­former, and landed on the line side of the contactor.
All active conductors are then brought out from the load side of the contactor to the load / remaining branch of the circuit.
The ground wire is landed on the ground lug on the backplate. The ground wire is NOT routed through the current transformer.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Disconnect all power before servicing.
• Observe all local, state, and national codes, standards, and regulations.
DANGER
!
Figure W3 - Three-Phase, Four-Wire Configurations (L1, L2, L3, N)
Figure W4 - 240Y/120 VAC Configurations (L1, L2, N)
Table 2: Legend of Wiring Diagrams
Voltage
120 VAC 1ph / 2w (L1, N) Figure W1
208 VAC 3ph / 3w (L1, L2, L3) FIgure W2
208/120 VAC 3ph / 4w (L1, L2, L3, N) Figure W3
240/120 VAC 3ph / 3w (L1, L2, N) Figure W4
277 VAC 1ph / 2w (L1, N) Figure W1
480 VAC 3ph / 3w (L1, L2, L3) Figure W2
480/277 VAC 3ph / 4w (L1, L2, L3, N) Figure W3
600 VAC 3ph / 3w (L1, L2, L3) Figure W2
600/346 VAC 3ph / 4w (L1, L2, L3, N) Figure W3
Conductors (NOT including
ground)
Referenced Wiring Diagram
Document NAE1088440 02.2013 © Bender Inc. Page 1/1 Side 1/2Bender Inc. USA: 800.356.4266 / 610.383.9200 / info@bender.org Canada: 800.243.2438 / 905.602.9990 / info@bender-ca.com www.bender.org
T M
This section only applies to LifeGuard models purchased without an enclosure and on the backplate only. Refer to instructions below for additional requirements for installation and
wiring. Backplate-only models are typically integrated into existing cabinets or machinery.
Mounting - Backplate Only
Refer to Figure 3 below for dimensions. The GFCI must be mounted in a location sucient to protect live electrical equipment. Use four (4) #10 screws for mounting. The vertical clearance of the backplate is 6” for models less than 100 A, and 8” for 100 A models.
A
C
Backplate Dimensions in Inches (mm)
Type A x B C x D
LifeGuard® Series (Digital)
Installation Bulletin / Reference Guide
Use - Enclosure FrontAdditional Requirements - Backplate Only Models
1
2
3
MK1500
POWER
ON
5
5
0
.
.
I mAI mA
25 50 75 100
TEST RESET
GFCI-SERIES
CIRCUIT TRIPPED
%
4
5
6
Figure 3 - DImensions of LifeGuard, backplate only
D
B
100 A
< 100 A
8.75“ x 10.5“ (222 x 267)
10.75“ x 12.75“ (273 x 324)
8.25“ x 10.25“ (210 x 260)
Wiring - Control and Remote Indicator Wiring
LifeGuard part numbers ending in “-N-D” apply to this section. Follow the standard wiring in­structions on the reverse side of this document. Additionally, backplate only models may con­nect to additional devices for remote capabilities.
Test and reset functions are carried out in one of the following ways:
Using the test and reset pushbuttons located directly on the ground fault module
Connecting an MK1500-D remote indicator and using the built-in test and reset buttons
Connecting an MK1500-D remote indicator and using the TEST, RESET, and T/R terminals to connect external test and reset pushbuttons
The MK1500-D duplicates indication and test/reset pushbutton functionality. Additionally, ter­minals are provided for external test and reset. Both are normally open (N/O) contacts.
Observe the following additional requirements:
Use shielded RS-485 cable, AWG 18 for connections “A” and “B.”
The red switch labeled “R” on the underside of the ground fault module must be switched to ON to ensure proper RS-485 termination. Standard RS-485 cable length limitations ap­ply.
External test and reset control connections are optional and not necessary for the built-in test and reset functionality of the MK1500-D and ground fault module.
The MK1500-D requires an external supply voltage not supplied from the backplate, con­nected to terminals A1 and A2. The supply voltage range is 100-240 VAC, 50/60 Hz.
Figure 3 - Front of LifeGuard enclosure with digital indicator
1. Digital display: Shows measured ground fault current in real-time.
2. POWER LED: Illuminates when the GFCI has received power and has not tripped.
3. TEST button: Performs a functional test of the GFCI (instructions for use below).
4. TRIPPED LED: Illuminates when the GFCI has tripped.
5. LED bar graph: Indicates how close the GFCI is to tripping.
6. RESET button: Resets the GFCI if faults have been cleared (instructions for use below).
Field Adjustments
LifeGuard GFCIs with digital display utilize ground fault modules which are not eld-adjustable. Models are either xed at a 6 mA or 20 mA trip level, depending on option.
Operation
Apply power to the GFCI
To apply power, close the circuit breaker / disconnect on the line side of the GFCI. If there are no ground faults present on the system, the green ON LED will illuminate.
Refer to the wiring diagram below for additional wiring required for the MK1500-D. For addi­tional information on installation and use of the remote indicator, refer to MK1500-D installa­tion manual. Do not modify any other wiring on the backplate when installing the remote
indicator.
RCMA421H-DCB-2 RCMA426H-DCB-2
A1 A2T1
21 22 24
A B
T2
MK1500
POWER
ON
MK1500-D
I mAI mA
25 50 75 100
TEST RESET
GFCI-SERIES
CIRCUIT TRIPPED
%
A B RESET T/R TEST
A2 A1
To supply voltage
100-240 VAC
RS-485 cable: twisted, shielded pair
(Optional External Test/Reset Connections)
Test procedure
Press and hold the TEST button until display reads “tES.” An internal self-test will initiate. Unit must trip within 15 seconds. Power to any connected loads will be interrupted.
Press and hold the RESET button until display reads “rES.” Power will be restored to the load side of the GFCI.
Error Codes
For error codes and troubleshooting, refer to LifeGuard user manual, document NAE1085011. For digital display models, error codes will appear both on the internal ground fault module as well as the display of the door-mounted remote indicator.
Figure 4 - Wiring MK1500-D remote indicator to LifeGuard GFCI on backplate only (no enclosure)
Document NAE1088440 02.2013 © Bender Inc. Page 1/1 Side 2/2Bender Inc. USA: 800.356.4266 / 610.383.9200 / info@bender.org Canada: 800.243.2438 / 905.602.9990 / info@bender-ca.com www.bender.org
Loading...