Bender iso685W-D-B, iso685-D, iso685W-D, iso685-S, iso685W-S User Manual

...
EN
Manual
ISOMETER®
iso685-D-B
iso685W-D-B iso685-S-B

iso685W-S-B

iso685-D-B_D00177_05_M_XXEN/07.2017
PLEASE READ THIS MANUAL AND ANY ACCOMPANYING DOCUMENTS CAREFULLY AND KEEP THEM IN A SECURE PLACE FOR FUTURE REFERENCE.
Bender GmbH & Co. KG
Postfach 1161 • 35301 Gruenberg • Germany Londorfer Straße 65 • 35305 Gruenberg • Germany
Tel.: +49 6401 807-0 Fax: +49 6401 807-259
E-Mail: info@bender.de Web: www.bender.de
Customer service Service-Hotline: 0700-BenderHelp (Telephone and Fax) Carl-Benz-Straße 8 • 35305 Gruenberg • Germany
Tel.:+49 6401 807-760 Fax:+49 6401 807-629
E-Mail:info@bender-service.com
© Bender GmbH & Co. KG
All rights reserved.
Reproduction only with permission
of the publisher.
Subject to change.
Table of contents
1. Important information .................................................................... 6
1.1 How to use this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.2 Technical support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.2.1 First level support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.2.2 Repair service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.2.3 Field service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.3 Training courses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.4 Delivery conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.5 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.6 Disposal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2. Safety instructions ............................................................................ 8
2.1 General safety instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.2 Work activities on electrical installations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.3 Device-specific safety information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.4 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3. Function ........................................................................................... 10
3.1 Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.2 Product description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.2.1 General product description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.2.2 Special characteristics of ISOMETER® iso685-S-B with front panel 10
3.3 Functional description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.4 Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.5 Self test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.1 General instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
5.2 Screw mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.3 DIN rail mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
6. Connection ....................................................................................... 17
6.1 Connection requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
6.2 Connection to a 3(N)AC system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
6.3 Connection to an AC system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
6.4 Connection to a DC system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
6.5 Connection to the X1 interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
6.6 Connection to the supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
6.7 Connection to the Ethernet interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
6.8 Connection to the relay 1 interface (11 12 14) . . . . . . . . . . . . . . . . . . . . . . 22
6.9 Connection to the relay 2 interface (21 22 24) . . . . . . . . . . . . . . . . . . . . . . 22
7. Commissioning ............................................................................... 23
7.1 General initial commissioning process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
7.2 Initial commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
7.2.1 Set language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
7.2.2 Set time and date . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
7.2.3 Set system type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
7.2.4 Set profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
7.2.5 Set response value Ran1 for Alarm 1 . . . . . . . . . . . . . . . . . . . . . . . . . . .25
7.2.6 Set response value Ran2 for Alarm 2 . . . . . . . . . . . . . . . . . . . . . . . . . . .25
7.3 Recommissioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
4. Device overview .............................................................................. 12
4.1 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.2 Device variants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.3 Connections and panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.4 Display elements and device buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5. Mounting .......................................................................................... 16
3
8. Display ..............................................................................................26
8.1 Standard display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
8.2 Fault display (active) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
8.3 Fault display (inactive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
8.4 Acknowledge fault memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
8.5 Data-isoGraph . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
8.6 History memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
iso685-D-B_D00177_05_M_XXEN/07.2017
Table of contentsTable of contents
8.7 Initial measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
8.8 ISOnet mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
9. Menu ................................................................................................. 31
9.1 Menu structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
9.2 Operating and navigating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
9.2.1 Easy operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
10. Settings .......................................................................................... 33
10.1 Settings in the device menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
10.1 (1.0) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Alarm settings 33
10.1 (1.1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Insulation alarm 33
10.1 (1.1.1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Alarm 1 33
10.1 (1.1.2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Alarm 2 33
10.1 (1.1.3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Fault memory 33
10.1 (1.2) DC alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
10.1 (1.2.1) Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
10.1 (1.2.2) U(DC-E) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
10.1 (1.3) Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
10.1 (1.4) System type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
10.1 (1.5) ISOnet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
10.1 (1.5.1) ISOnet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
10.1 (1.5.2) Number of devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
10.1 (1.6) Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
10.1 (1.7) T(Start). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
10.1 (1.8) Coupling monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
10.1 (1.9) Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
10.1 (1.9.1) Digital 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
10.1 (1.9.1.1) Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
10.1 (1.9.1.2) t(on) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
10.1 (1.9.1.3) t(off) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
10.1 (1.9.1.4) Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
10.1 (1.9.2) Digital 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
10.1 (1.9.3) Digital 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
10.1 (1.10) Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
10.1 (1.10.1) Relay 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
10.1 (1.10.1.1) TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
10.1 (1.10.1.2) Relay mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
10.1 (1.10.1.3) Function 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
10.1 (1.10.1.4) Function 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
10.1 (1.10.1.5) Function 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
10.1 (1.10.2) Relay 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
10.1 (1.10.3) Digital 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
10.1 (1.10.3.1) TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
10.1 (1.10.3.2) Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
10.1 (1.10.3.3) Function 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
10.1 (1.10.3.4) Function 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
10.1 (1.10.3.5) Function 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
10.1 (1.10.4) Digital 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
10.1 (1.10.5) Buzzer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
10.1 (1.10.5.1) TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
10.1 (1.10.5.2) Function 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
10.1 (1.10.5.3) Function 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
10.1 (1.10.5.4) Function 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
10.1 (1.10.6) Analogue . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
10.1 (1.10.6.1) Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
10.1 (1.10.6.2) Midscale . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
10.1 (1.10.6.3) TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
10.1 (1.10.6.4) Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
10.1 (2.0) Data measured values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
10.1 (3.0) Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
10.1 (4.0) History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
10.1 (5.0) Device settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
10.1 (5.1) Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
10.1 (5.2) Clock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
10.1 (5.2.1) Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
10.1 (5.2.2) Format (time). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
10.1 (5.2.3) Summer time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
10.1 (5.2.4) Date . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
10.1 (5.2.5) Format (date). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
10.1 (5.2.6) NTP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
10.1 (5.2.7) NTP server. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
10.1 (5.2.8) UTC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
10.1 (5.3) Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
10.1 (5.3.1) Write access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
10.1 (5.3.2) Ethernet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
10.1 (5.3.2.1) DHCP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
10.1 (5.3.2.2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP 42
4
iso685-D-B_D00177_05_M_XXEN/07.2017
Table of contentsTable of contents
10.1 (5.3.2.3) SN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
10.1 (5.3.2.4) Std. GW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
10.1 (5.3.2.5) DNS server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
10.1 (5.3.2.6) Domain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
10.1 (5.3.3) BCOM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
10.1 (5.3.3.1) System name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
10.1 (5.3.3.2) Subsystem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
10.1 (5.3.3.3) Device address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
10.1 (5.3.3.4) Timeout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
10.1 (5.3.3.5) TTL for subscription . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
10.1 (5.3.4) Modbus TCP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
10.1 (5.3.4.1) Port 502 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
10.1 (5.3.5) BS bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
10.1 (5.3.5.1) Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
10.1 (5.4) Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
10.1 (5.4.1) Brightness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
10.1 (5.5) Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
10.1 (5.5.1) Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
10.1 (5.5.2) Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
10.1 (5.6) Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
10.1 (5.7) Data backup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
10.1 (5.8) Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
10.1 (6.0) Info . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
11. Device communication ............................................................... 44
11.1 Ethernet interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
11.2 BCOM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
11.3 Modbus TCP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
11.4 Web server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
11.5 BS bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
14. Diagrams ........................................................................................53
14.1 Response time profile power circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
14.2 Response time profile control circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
14.3 Response time profile generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
14.4 Response time profile high capacitance . . . . . . . . . . . . . . . . . . . . . . . . . . .54
14.5 Response time profile inverter > 10 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
14.6 Response time profile inverter < 10 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
14.7 Response time DC alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
14.8 Relative uncertainty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
15. Alarm messages ............................................................................57
16. Factory settings .............................................................................59
17. Technical data ...............................................................................60
17.1 Tabular data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
17.2 Option "W" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63
17.3 Standards and certifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63
17.4 Ordering details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63
18. Glossary ..........................................................................................64
Index ...................................................................................................... 65
12. Special functions for coupled IT systems ................................. 49
12.1 Particularities when monitoring coupled IT systems . . . . . . . . . . . . . . . 49
12.2 System isolation via digital input with two coupled systems . . . . . . . 49
12.3 System isolation via ISOnet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
13. Device profiles .............................................................................. 52
5
iso685-D-B_D00177_05_M_XXEN/07.2017

1. Important information

DANGER

WARNING

CAUTION

Important information

1.1 How to use this manual

This manual is intended for qualified personnel working in electrical en­gineering and electronics!
Always keep this manual within easy reach for future reference.
To make it easier for you to understand and revisit certain sections in this manual, we have used symbols to identify important instructions and information. The meaning of these symbols is explained below:
This signal word indicates that there is a high risk of danger that will re­sult in electrocution or serious injury if not avoided.
This signal word indicates a medium risk of danger that can lead to death or serious injury if not avoided.
This signal word indicates a low level risk that can result in minor or mo- derate injury or damage to property if not avoided.
This symbol denotes information intended to assist the user in making optimum use of the product.

1.2 Technical support

For commissioning and troubleshooting Bender offers you:
1.2.1 First level support
Technical support by phone or e-mail for all Bender products
• Questions concerning specific customer applications
• Commissioning
• Troubleshooting
Telephone: +49 6401 807-760* Fax: +49 6401 807-259
In Germany only: 0700BenderHelp (Tel. and Fax) E-mail: support@bender-service.de
1.2.2 Repair service
Repair, calibration, update and replacement service for Bender products
• Repairing, calibrating, testing and analysing Bender products
• Hardware and software update for Bender devices
• Delivery of replacement devices in the event of faulty or incorrectly delivered Ben­der devices
• Extended guarantee for Bender devices, which includes an in-house repair service or replacement devices at no extra cost
Telephone: +49 6401 807-780** (technical issues)
+49 6401 807-784**, -785** (sales)
Fax: +49 6401 807-789 E-mail: repair@bender-service.de
Please send the devices for repair to the following address:
Bender GmbH, Repair-Service, Londorfer Strasse 65, 35305 Grünberg
6
iso685-D-B_D00177_05_M_XXEN/07.2017
Important informationImportant information
1.2.3 Field service
On-site service for all Bender products
• Commissioning, parameter setting, maintenance, troubleshooting for Bender pro­ducts
• Analysis of the electrical installation in the building (power quality test, EMC test, thermography)
• Training courses for customers
Telephone: +49 6401 807-752**, -762 **(technical issues)
+49 6401 807-753** (sales)
Fax: +49 6401 807-759 E-mail: fieldservice@bender-service.de Internet: www.bender-de.com
*Available from 7.00 a.m. to 8.00 p.m. 365 days a year (CET/UTC+1) **Mo-Thu 7.00 a.m. - 8.00 p.m., Fr 7.00 a.m. - 13.00 p.m.

1.3 Training courses

Bender is happy to provide training regarding the use of test equipment. The dates of training courses and workshops can be found on the Internet at www.bender-de.com -> Know-how -> Seminars.

1.4 Delivery conditions

Bender sale and delivery conditions apply. For software products the "Softwareklausel zur Überlassung von Standard-Software als Teil von Lieferungen, Ergänzung und Änderung der Allgemeinen Lieferbedingungen für Erzeugnisse und Leistungen der Elektroindustrie" (software clause in respect of the licen­sing of standard software as part of deliveries, modifications and changes to general deli­very conditions for products and services in the electrical industry) set out by the ZVEI (Zentralverband Elektrotechnik- und Elektronikindustrie e. V.) (German Electrical and Electronic Manufacturer's Association) also applies. Sale and delivery conditions can be obtained from Bender in printed or electronic format.

1.6 Disposal

Abide by the national regulations and laws governing the disposal of this device. Ask your supplier if you are not sure how to dispose of the old equipment. The directive on waste electrical and electronic equipment (WEEE directive) and the di­rective on the restriction of certain hazardous substances in electrical and electronic equipment (RoHS directive) apply in the European Community. In Germany, these po­licies are implemented through the "Electrical and Electronic Equipment Act" (ElektroG). According to this, the following applies:
• Electrical and electronic equipment are not part of household waste.
• Batteries and accumulators are not part of household waste and must be disposed of in accordance with the regulations.
• Old electrical and electronic equipment from users other than private households which was introduced to the market after 13 August 2005 must be taken back by the manufacturer and disposed of properly.
For more information on the disposal of Bender devices, refer to our homepage at www.bender-de.com -> Service & support.

1.5 Storage

The devices must only be stored in areas where they are protected from dust, damp, and spray and dripping water, and in which the specified storage temperatures can be ensu­red.
7
iso685-D-B_D00177_05_M_XXEN/07.2017

2. Safety instructions

DANGER

WARNING

CAUTION

Safety instructions

2.1 General safety instructions

Part of the device documentation in addition to this manual is the enclosed "Safety in­structions for Bender products".

2.2 Work activities on electrical installations

Only qualified personnel are permitted to carry out the work necessary to install, commission and run a device or system.
Risk of electrocution due to electric shock!
Touching live parts of the system carries the risk of:
• An electric shock
• Damage to the electrical installation
• Destruction of the device
Before installing and connecting the device, make sure that the in­stallation has been de-energised. Observe the rules for working on elec-
trical installations.
If the device is used outside the Federal Republic of Germany, the applicable local stand­ards and regulations must be complied with. The European standard EN 50110 can be used as a guide.

2.3 Device-specific safety information

Make sure that the basic settings meet the requirements of the IT system. Children and unauthorised persons must not have access to or contact with the ISOMETER®.
Make sure that the operating voltage is correct!
Prior to insulation and voltage tests, the ISOMETER® must be disconnected from the IT system for the duration of the test. In order to check the correct connection of the device, a functional test has to be carried out before start­ing the system.
In the event of an alarm message of the ISOMETER®, the insulation fault should be eliminated as quickly as possible.
If the ISOMETER® is installed inside a control cabinet, the insulation fault message must be audible and/or visible to attract attention.
When using ISOMETER®s in IT systems, make sure that only one active ISOMETER® is connected in each interconnected system. If IT systems are interconnected via coupling switches, make sure that ISOMETER®s not currently used are disconnected from the IT system and deactivated. IT systems coupled via diodes or capacitances may also influence the insu­lation monitoring process so that a central control of the different ISOMETER®s is required.
8
iso685-D-B_D00177_05_M_XXEN/07.2017
Prevent measurement errors!
When a monitored IT system contains galvanically coupled DC circuits, an insulation fault can only be detected correctly if the rectifier valves (e.g. rectifier diode, thyristors, IGBTs, frequency inverters, …) carry a minimum current of > 10 mA.
Safety instructionsSafety instructions

2.4 Intended use

Only qualified personnel are permitted to carry out the work necessary to install, commission and run a device or system.
Unspecified frequency range
When connecting to an IT system with frequency components below the specified frequency range, the response times and response values may differ from the indicated technical data. However, depending on the ap­plication and the selected measurement method, continuous insulation monitoring is also possible in this frequency range. There is no influence on the insulation monitoring for IT systems with fre­quency components above the specified frequency range, e.g. within the range of typical switching frequencies of frequency inverters (2…20 kHz).
The ISOMETER® monitors the insulation resistance of unearthed AC/DC main circuits (IT systems) with mains voltages of AC 0…690 V or DC 0…1000 V.
DC components existing in AC/DC systems do not influence the operating characteristics. Due to the separate supply voltage, de-energised systems can also be monitored. The maximum permissible system leakage capacitance is 0…1000 µF, depending on the pro­file.
Intended use also implies:
• The observation of all information in the operating manual
• Compliance with test intervals
In order to meet the requirements of applicable standards, customised parameter set­tings must be made on the equipment in order to adapt it to local equipment and oper­ating conditions. Please heed the limits of the area of application indicated in the technical specifications.
Any other use than that described in this manual is regarded as improper.
9
iso685-D-B_D00177_05_M_XXEN/07.2017

3. Function

*
Function

3.1 Features

• ISOMETER® for IT AC systems with galvanically connected rectifiers or inverters and for IT DC systems (IT = unearthed systems)
• Automatic adaptation to the existing system leakage capacitance
• Combination of and other profile-specific measurement methods
• Two separately adjustable response value ranges of 1 kΩ…10 MΩ for alarm 1 and alarm 2
• High-resolution graphic LC display for excellent readability and recording of the device status
• Connection monitoring (monitoring of the measuring lines)
• Automatic device self test
• Graphical representation of the insulation resistance over time (isoGraph)
• History memory with real-time clock (buffer for three days) for storing 1023 alarm messages with date and time
• Current or voltage output 0(4)…20 mA, 0…400 µA, 0…10 V, 2…10 V (galvanically separated), which is analogous to the measured insulation value of the system
• Freely programmable digital inputs and outputs
• Remote setting of certain parameters via the Internet (Option; COMTRAXX® gateway)
• Worldwide remote diagnosis via the Internet (made available by Bender Service only)
• RS-485/BS (Bender sensor bus) for communication with other Bender devices
• ISOnet: Internal separation of the ISOMETER® from the IT system to be monitored (e.g. if several IT systems are interconnected)
• BCOM, Modbus TCP and web server

3.2.2 Special characteristics of ISOMETER® iso685-S-B with front panel

The ISOMETER® iso685-D-B and iso685W-D-B are devices of the iso685 device family with integrated display. This manual applies in full to these ISOMETER®s. The ISOMETER® iso685-S-B and iso685W-S-B are sensor variants of the iso685 device fam­ily without display. The only difference between these variants and the ISOMETER®s iso685-D and iso685W-D-B is that they do not feature a display. The ISOMETER®s iso685-S-B and iso685W-S-B must be used in combination with a front panel because the devices are operated via the front panel. The operation of the front panel is equal to the operation of the ISOMETER®s with integrated display, which is described in this manual.
Only the sensor variant (ISOMETER® iso685-S-B or iso685W-S-B) can be connected to the front panel. Connection to the display variant (ISOMETER® iso685-D-B or iso685W-D-B) is not possible.
Hereafter, the ISOMETER®s with integrated display are described. This description is sim­ilar to the combination of ISOMETER® sensor variants and the front panel FP200. The de­vices to which this manual applies will be referred to as ISOMETER®s hereafter.

3.3 Functional description

The insulation monitoring device continuously monitors the entire insulation resistance of an IT system during operation and triggers an alarm when the value falls below a pre­set response value. To obtain a measurement the device has to be connected between the IT system (unearthed system) and the protective earth conductor (PE). A measuring current in the µA range is superimposed onto the system which is recorded and evalu­ated by a micro-controlled measuring circuit. The measuring time is dependent on the selected measurement profiles, the system leakage capacitance, the insulation resistance and possible system-related disturbances.

3.2 Product description

3.2.1 General product description

The ISOMETER® is an insulation monitoring devices in accordance with IEC 61557-8 for IT systems. The devices are universally applicable in AC, 3(N)AC, AC/DC and DC systems. AC systems may include extensive DC-supplied loads (such as rectifiers, inverters, variable­speed drives).
10
The response values and other parameters are set using a commissioning wizard or via different setup menus using the device buttons and a high-resolution graphical LC dis­play. The selected settings are stored in a permanent fail-safe memory. Different languages can be selected for the setup menus as well as the messages indicated on the display. The device utilises a clock for storing fault messages and events in a history memory with time and date stamp. The settings can be protected against unauthorised modifications by entering a password. To ensure proper functioning of connection mo­nitoring, the device requires the setting of the system type 3AC, AC or DC and the red use of the appropriate terminals
L1/+, L2, L3/-.
iso685-D-B_D00177_05_M_XXEN/07.2017
requi-
FunctionFunction
TEST
√ Measurement
Coupling Earth connection Outputs
33 %
The insulation monitoring device is able to measure the insulation resistance reliably and precisely in all common IT systems (unearthed systems). Due to various applications, sys­tem types, operating conditions, application of variable-speed drives, high system leaka­ge capacitances etc., the measurement technique must be able to meet varying requirements in order to ensure an optimised response time and relative uncertainty. Different measurement profiles which can be selected from a setup menu allow optimum adaptation of the measurement technique to the specific application.
If the preset response value falls below the value of Alarm 1 and/or Alarm 2, the associa­ted alarm relays switch, the LEDs Alarm 1 resp. Alarm 2 light and the measured value is shown on the LC display (in case of insulation faults in DC systems, a trend graph for the faulty conductor L+/L- is displayed). If the fault memory is activated, the fault message will be stored. Pressing the reset button, resets the insulation fault message, provided that the insulation resistance is at least 25 % above the preset response value. As additional Information, the quality of the measuring signal and the time required to up­date the measured value are shown on the display. A poor signal quality (1-2 bars) may be an indication that the wrong measurement profile has been selected.
The insulation monitoring device has an internal system isolating switch, which makes it possible to operate several ISOMETER®s in coupled IT systems. For this purpose, the ISOMETER®s are connected via an Ethernet bus. The integrated Isonet function ensures that only one ISOMETER® is actively measuring at a time, while the other devices are com­pletely isolated from the system and waiting in standby mode for measuring permission.

3.5 Self test

After switching on the supply voltage, the ISOMETER® automatically and continuously checks all internal measuring functions, the components of the process control such as the data and parameter memory, as well as the connections to the IT system and earth.
The self test can also be activated manually by means of the test button to check the func­tions of the relays (depending on the configuration) or it can be selected via the "Control" menu (refer to “Control” on page 40).
The progress of the manual self test is shown on the LC display by a bar graph. Depending on the conditions in the IT system being monitored, the self test is completed after 15…20 seconds. The device then returns to the standard mode (measurement mode) and the actual measured value will be displayed after the measuring time has expired. The display shows the message ured (refer to “Initial measurement” on page 29).
If a fault is detected during the self test, the respective LEDs of the device light (refer to
“Alarm messages” on page 57). In addition, the respective message will be indicated on
the display and a previously programmed output will provide the respective signal.
Initial measurement
until the first valid value is meas-

3.4 Interfaces

• Communication protocol Modbus TCP
• BCOM for Bender device communication via Ethernet
• BS bus for communication of Bender devices (RS-485)
• Integrated web server for reading out measured values and for parameter setting
11
The test has been run and the result was positive.
The test has been run and the result was negative.
The test is not available and is not carried out (e.g. due to specific device settings).
The test is running.
iso685-D-B_D00177_05_M_XXEN/07.2017

4. Device overview

4.1 Dimensions

108 mm
110 mm
mm 39
12
iso685-D-B_D00177_05_M_XXEN/07.2017
Device overview
ISOMETER® iso685-D-B
ISOMETER® iso685-S-B with front panel FP200 connected via an RJ45 cable

4.2 Device variants

iso685-D-B:
iso685-S-B:
Option "W":
This device variant features a high-resolution graphic LC display and operating controls for direct operation of the device functions. It cannot be combined with an FP200.
This device variant features neither a display nor operating controls. It can only be used in combination with the FP200 and it is operated via this front panel.
The ISOMETER®s with and without integrated display are available with option "W" for extreme climatic and mechanical conditions (ISOMETER® iso685W-D-B and iso685W-S-B).
13
iso685-D-B_D00177_05_M_XXEN/07.2017
Device overview
A1/+, A2/- Connection to the power supply voltage U
s
L1/+ Connection to the IT system to be monitored L2 Connection to the IT system to be monitored L3/- Connection to the IT system to be monitored KE, E Connection to PE
To p
ON Display
RESET
DATA
LEDs: SERVICE, ALARM 1, ALARM 2
MENU ESC
TEST
INFO OK
X3
iso685-D-B
REMOTE
X4
X3 Optional expansion module for Bender devices (e. g. BB-Bus) X4 REMOTE interface to connect to the FP200
iso685-S-B
Back
Front
ETH
X1 Digital interface ETH Ethernet interface R Selectable resistance R 11 12 14 Connector for alarm relay 1 21 22 24 Connector for alarm relay 2
Bottom

4.3 Connections and panel

14
iso685-D-B_D00177_05_M_XXEN/07.2017
Device overviewDevice overview
1
7
8
9
10
11
2
3
4
5
6

4.4 Display elements and device buttons

Display elements
1 ON The LED "ON" lights when the device is turned on.
The device display shows information regarding the device and the meas-
2
3
SERVICE
4
ALARM 1
5
ALARM 2
urements. Other information is available in the chapter “Display” from page 26.
The LED "SERVICE" lights when there is either a device fault or a connection fault, or when the device is in maintenance mode.
The LED "ALARM 1" lights when the insulation resistance of the IT system falls below the set response value R
The LED "ALARM 2" lights when the insulation resistance of the IT system falls below the set response value R
an1
an2
.
.
Device buttons
You can adjust the device settings in the respective menu using the menu buttons. Depending on the menu entry, one of the options displayed below is assigned to the buttons.
MENU Opens the device menu.
6
ESC
7
TEST
8
RESET
9
Info
10
OK
DATA
11
Cancels the current process or navigates one step back in the device menu.
Navigates up in a list or increases a value.
Starts the device self test.
Navigates forwards (e.g. to the next setting step) or selects a parameter.
Resets alarms.
Navigates backwards (e.g. to the previous setting step) or selects a parameter.
Shows information.
Confirms an action or a selection.
Indicates data and values.
Navigates down in a list or reduces a value.
15
iso685-D-B_D00177_05_M_XXEN/07.2017

5. Mounting

DANGER

72 mm
108 mm
54 mm
100 mm
107,3 mm
Mounting

5.1 General instructions

Only qualified personnel are permitted to carry out the work necessary to install, commission and run a device or system.
Risk of electrocution due to electric shock!
Touching live parts of the system carries the risk of:
• An electric shock
• Damage to the electrical installation
• Destruction of the device
Before installing and connecting the device, make sure that the in­stallation has been de-energised. Observe the rules for working on elec-
trical installations.

5.2 Screw mounting

19. Fix the three mounting clips delivered with the device (two of them packed separa­tely) manually or using a tool, as illustrated below.
20. Drill the mounting holes for the M4 thread according to the dimensioned drilling template.
21. Fix the ISOMETER® using three M4 screws.
16
iso685-D-B_D00177_05_M_XXEN/07.2017
Connection

DANGER

DANGER

DANGER

WARNING

6. Connection

5.3 DIN rail mounting

1. Fix the three mounting clips delivered with the device (two of them packed separa­tely) manually or using a tool, as illustrated below.
2. Fix the ISOMETER® onto the DIN rail until it snaps into place.

6.1 Connection requirements

Consider the minimum distance to adjacent devices: lateral 0 mm, top 20 mm, bottom 20 mm.
Only qualified personnel are permitted to carry out the work necessary to install, commission and run a device or system.
Risk of electrocution due to electric shock!
Touching live parts of the system carries the risk of:
• An electric shock
• Damage to the electrical installation
• Destruction of the device
Before installing and connecting the device, make sure that the in­stallation has been de-energised. Observe the rules for working on elec-
trical installations.
Risk of electric shock!
Nominal voltages up to 1000 V may be present on the terminals L1/+ to L3/- which can be lethal. Make sure the terminal covers are properly mounted and clicked in before putting the device into operation.
17
Risk of electric shock!
High voltage is applied at the terminals, which in case of direct contact can be life-threatening. If the terminals L1/+, L2, L3/- of the device are con­nected to a live IT system, the terminals E and KE must not be disconnected from the protective conductor (PE).
Warning of insulation monitoring devices that do not work correctly!
Connect the terminals KE and E individually to the protective earth con­ductor PE.
iso685-D-B_D00177_05_M_XXEN/07.2017
ConnectionConnection

CAUTION

CAUTION

CAUTION

CAUTION

CAUTION

Provide line protection!
According to DIN VDE 0100-430, a line protection shall be provided for the supply voltage.
Risk of injury from sharp-edged terminals!
Risk of lacerations. Touch the enclosure and the terminals with due care.
Ensure disconnection from the IT system!
When insulation or voltage tests are to be carried out, the device must be isolated from the system for the test period. Otherwise the device may be damaged.
Risk of property damage due to unprofessional installation!
If more than one insulation monitoring device is connected to a conduc­tively connected system, the system can be damaged. If several devices are connected, the device does not function and does not signal insula­tion faults. Make sure that only one insulation monitoring device is con­nected in each conductively connected system. The ISOMETER® iso685-D-B is suitable for use in coupled systems. For the necessary parameter setting, refer to “Special functions for coupled IT sys-
tems” from page 49
Prevent measurement errors!
When an AC system being monitored contains galvanically coupled DC circuits, take into consideration that: an insulation fault can only be de­tected correctly when the rectifier valves carry a minimum current of >10 mA.
For UL applications:
Use 60/70 °C copper lines only! For UL and CSA applications, the supply voltage must be protected via 5 A fuses.
18
Risk of property damage due to unprofessional installation!
The connecting lines L1/+, L2, L3/- to the system to be monitored must be carried out as spur lines. Inadmissible load current can result in damage to property and personal injury. Do not apply any load current to the ter­minals.
Check proper connection!
Prior to commissioning of the installation, check that the device has been properly connected and check the device functions. Perform a functional test using an earth fault via a suitable resistance.
iso685-D-B_D00177_05_M_XXEN/07.2017
ConnectionConnection

WARNING

L1
L2
L3
N
PE
U
S
U
n

WARNING

L1
L2
PE
U
n
U
S

6.2 Connection to a 3(N)AC system

Risk of injury, fire and damage to property due to a short circuit!
According to DIN VDE 0100-430, devices used to protect against a short circuit when terminals L1/+, L2 und L3/- are coupled to the IT system to be monitored can be omitted if the wiring is carried out in such a manner as to reduce the risk of a short circuit to a minimum. Ensure short-circuit­proof and earth-fault-proof wiring.

6.3 Connection to an AC system

Risk of injury, fire and damage to property due to a short circuit!
According to DIN VDE 0100-430, devices used to protect against a short circuit when terminals L1/+, L2 und L3/- are coupled to the IT system to be monitored can be omitted if the wiring is carried out in such a manner as to reduce the risk of a short circuit to a minimum. Ensure short-circuit­proof and earth-fault-proof wiring.
19
Position the terminal cover and click it into place
Position the terminal cover and click it into place
iso685-D-B_D00177_05_M_XXEN/07.2017
ConnectionConnection

WARNING

L+
L-
PE
U
S
U
n
Electrical overload protection. Auto shut-off in the event of a short circuit and transients (resettable)
Input 1 Input 2 Input 3 RS-485 A RS-485 B
Ground Analogue output Output 2 Output 1 +24 V

6.4 Connection to a DC system

Risk of injury, fire and damage to property due to a short circuit!
According to DIN VDE 0100-430, devices used to protect against a short circuit when terminals L1/+, L2 und L3/- are coupled to the IT system to be monitored can be omitted if the wiring is carried out in such a manner as to reduce the risk of a short circuit to a minimum. Ensure short-circuit­proof and earth-fault-proof wiring.
Position the terminal cover and click it into place

6.5 Connection to the X1 interface

I1 I2 I3
A B
M+
Q2 Q1
+
20
For systems > 690 V and with overvoltage category III a fuse for the connection to the system to be monitored must be provided. Recommendation: 2 A fuses.
Position the terminal cover and click it into place
iso685-D-B_D00177_05_M_XXEN/07.2017
ConnectionConnection

CAUTION

U
S

6.6 Connection to the supply voltage

External Power supply for powering the ISOMETER® via terminal X1 must fulfil immunity and emission standards of the required application. For wiring longer than 1 m the use of a shielded cable is prescribed.
Danger of damage to property due to faulty connections!
The device can be damaged if the unit is simultaneously connected to the supply voltage via the X1 interface, and A1/+ and A2/- terminals. Do not connect the device simultaneously via X1, and A1/+ and A2/- to different supply voltages.

6.7 Connection to the Ethernet interface

Position the terminal cover and click it into place
21
iso685-D-B_D00177_05_M_XXEN/07.2017
Loading...