Bender IRDH275BW-435, IRDH275B, IRDH275, IRDH275-427, IRDH275W-427 User Manual

...
Page 1
Manual
EN

ISOMETER®IRDH275

IRDH275B

Insulation monitoring device for IT AC systems with galvanically connected rectifiers and converters and for IT DC systems Software version IRDH275: D160 V1.8
IRDH275_D00122_02_M_XXEN/10.2016
Page 2
Bender GmbH & Co. KG
Londorfer Str. 65 • 35305 Gruenberg • Germany Postfach 1161 • 35301 Gruenberg • Germany
Tel.: +49 6401 807-0 Fax: +49 6401 807-259
Email: info@bender.de Web: http://www.bender.de
© Bender GmbH & Co. KG
All rights reserved. Reprinting only with permission of the publisher. Subject to change!
Photos: Bender archives and bendersystembau archives.
Page 3
Table of Contents
1. Important information .................................................................................... 7
1.1 How to use this manual ................................................................................. 7
1.2 Technical support: service and support ................................................... 8
1.2.1 First level support ............................................................................................. 8
1.2.2 Repair service ..................................................................................................... 8
1.2.3 Field service ........................................................................................................ 9
1.3 Training courses ............................................................................................. 10
1.4 Delivery conditions ....................................................................................... 10
1.5 Inspection, transport and storage ........................................................... 10
1.6 Warranty and liability ................................................................................... 11
1.7 Disposal ............................................................................................................ 12
2. Safety instructions ......................................................................................... 13
2.1 General safety instructions ........................................................................ 13
2.2 Work activities on electrical installations ............................................. 13
2.3 Device-specific safety information ......................................................... 14
2.4 Intended use ................................................................................................... 16
2.5 Directions for installation ........................................................................... 17
3. Function ........................................................................................................... 19
3.1 Common characteristics (IRDH275 and IRDH275B) .......................... 19
3.2 Additional characteristics IRDH275B ...................................................... 19
3.3 Product description ...................................................................................... 20
3.4 Function ............................................................................................................ 20
3.5 Additional functions IRDH275B ............................................................... 24
IRDH275_D00122_02_M_XXEN/10.2016
3
Page 4
Table of Contents
4. Connection ..................................................................................................... 29
4.1 Wiring ................................................................................................................ 29
4.2 Wiring diagrams with coupling devices ................................................ 32
4.2.1 Connection with AGH150W-4 .................................................................. 32
4.2.2 Connection with AGH520S ........................................................................ 33
4.2.3 Connection with AGH204S-4 .................................................................... 34
5. Commissioning flow chart (threepart) ...................................................... 37
6. Operation and setting .................................................................................. 41
6.1 Operating features and displays IRDH275(B) ...................................... 41
6.1.1 Display in the standard mode ................................................................... 42
6.1.2 Display in the menu mode ......................................................................... 43
6.1.3 Function keys .................................................................................................. 43
6.2 Menu structure and menu mode ............................................................ 45
6.2.1 Diagram menu structure ............................................................................ 47
6.3 Menu HISTORY INFO (IRDH275B) ............................................................ 48
6.3.1 Diagram HISTORY INFO (IRDH275B) ....................................................... 49
6.4 Menu ISO SETUP: Setting of the basic ISOMETER® functions ........ 50
6.4.1 Response values Alarm 1 and Alarm 2 ................................................... 50
6.4.2 Operating principle of the alarm relays ................................................ 50
6.4.3 Memory setting (on/off) .............................................................................. 53
6.4.4 Current output for external measuring instruments (IRDH275B) 53
6.5 Menu ISO ADVANCED: Setting of the extended functions ........... 54
6.5.1 External coupling devices (AGH: no) ...................................................... 54
6.5.2 Adaptation to the system leakage capacitance
(Cemax: 150 μF) .............................................................................................. 55
6.5.3 Changing the measuring principle from AMP to DC
(Measure: AMP) .............................................................................................. 55
6.5.4 Setting the repetition time for automatic self tests
(Autotest: 24h) ................................................................................................ 55
6.5.5 Setting the real-time clock (Clock) (IRDH275B) .................................. 55
6.5.6 Setting the date (Date) (IRDH275B) ........................................................ 55
4
IRDH275_D00122_02_M_XXEN/10.2016
Page 5
Table of Contents
6.5.7 Specifying the starting time of the automatic self test (Test)
(IRDH275B) ....................................................................................................... 56
6.5.8 Diagram ISO ADVANCED ............................................................................ 57
6.6 Menu COM SETUP: Setting the BMS interface .................................... 58
6.6.1 Bus address „Addr:“ (IRDH275B) ............................................................. 58
6.6.2 ISOnet function (IRDH275B) ...................................................................... 58
6.6.3 ISO monitor (IRDH275B) ............................................................................. 59
6.6.4 Diagram COM SETUP (IRDH275B) ........................................................... 60
6.7 Menu PASSWORD ......................................................................................... 61
6.7.1 Activating and setting the password ..................................................... 61
6.7.2 Diagram PASSWORD .................................................................................... 62
6.8 Menu LANGUAGE .......................................................................................... 63
6.8.1 Setting the national language .................................................................. 63
6.8.2 Diagram Language ....................................................................................... 63
6.9 Menu SERVICE ................................................................................................ 64
6.10 Parameterization via Internet ................................................................... 64
7. Serial interfaces .............................................................................................. 65
7.1 RS485 interface with IsoData protocol (IRDH275) ............................. 65
7.2 RS485 interface with BMS protocol (IRDH275B) ................................ 67
7.3 Topology RS485 network (IRDH275B) ................................................... 68
7.3.1 Correct arrangement ................................................................................... 68
7.3.2 Wrong arrangement .................................................................................... 68
7.3.3 Wiring ................................................................................................................ 68
7.4 BMS protocol (IRDH275B) .......................................................................... 69
7.4.1 BMS Master ...................................................................................................... 69
7.4.2 BMS Slave ......................................................................................................... 70
7.4.3 Commissioning of an RS485 network with BMS protocol .............. 71
IRDH275_D00122_02_M_XXEN/10.2016
5
Page 6
Table of Contents
8. Technical data IRDH275(B) .......................................................................... 73
8.1 Data in tabular form ..................................................................................... 73
8.2 Standards, approvals and certifications ................................................ 77
8.3 Characteristic curves .................................................................................... 78
8.4 Ordering details ............................................................................................. 85
8.4.1 ISOMETER® ....................................................................................................... 85
8.4.2 Coupling devices ........................................................................................... 86
8.4.3 Measuring instruments ............................................................................... 86
INDEX .................................................................................................................... 87
6
IRDH275_D00122_02_M_XXEN/10.2016
Page 7

1. Important information

DANGER
WARNING
CAUTION

1.1 How to use this manual

This manual is intended for qualified personnel working in electrical engineering and electronics!
Always keep this manual within easy reach for future reference.
To make it easier for you to understand and revisit certain sections in this man­ual, we have used symbols to identify important instructions and information. The meaning of these symbols is explained below:
This signal word indicates that there is a high risk of danger that will result in electrocution or serious injury if not avoided.
This signal word indicates a medium risk of danger that can lead to death or serious injury if not avoided.
This signal word indicates a low-level risk that can result in minor or moderate injury or damage to property if not avoided.
This symbol denotes information intended to assist the user in making optimum use of the product.
IRDH275_D00122_02_M_XXEN/10.2016
7
Page 8
Important information
This manual has been compiled with great care. It might nevertheless contain errors and mistakes. Bender cannot accept any liability for injury to persons or damage to property resulting from errors or mistakes in this manual.

1.2 Technical support: service and support

For commissioning and troubleshooting Bender offers you:

1.2.1 First level support

Technical support by phone or e-mail for all Bender products
Questions concerning specific customer applications
Commissioning
Troubleshooting
Telephone: +49 6401 807-760* Fax: +49 6401 807-259
In Germany only: 0700BenderHelp (Tel. and Fax) E-mail: support@bender-service.de

1.2.2 Repair service

Repair, calibration, update and replacement service for Bender products
Repairing, calibrating, testing and analysing Bender products
Hardware and software update for Bender devices
Delivery of replacement devices in the event of faulty or incorrectly
delivered Bender devices
Extended guarantee for Bender devices, which includes an in-house repair service or replacement devices at no extra cost
Telephone: +49 6401 807-780** (technical issues)
Fax: +49 6401 807-789 E-mail: repair@bender-service.de
8
+49 6401 807-784**, -785** (sales)
IRDH275_D00122_02_M_XXEN/10.2016
Page 9
Important information
Please send the devices for repair to the following address:
Bender GmbH, Repair-Service, Londorfer Str. 65, 35305 Grünberg

1.2.3 Field service

On-site service for all Bender products
Commissioning, configuring, maintenance, troubleshooting of Bender products
Analysis of the electrical installation in the building (power quality test, EMC test, thermography)
Training courses for customers
Telephone: +49 6401 807-752**, -762 **(technical issues)
+49 6401 807-753** (sales)
Fax: +49 6401 807-759 E-mail: fieldservice@bender-service.de Internet: www.bender-de.com
*Available from 7.00 a.m. to 8.00 p.m. 365 days a year (CET/UTC+1) **Mo-Thu 7.00 a.m. - 8.00 p.m., Fr 7.00 a.m. - 13.00 p.m
IRDH275_D00122_02_M_XXEN/10.2016
9
Page 10
Important information

1.3 Training courses

Bender is happy to provide training regarding the use of test equipment. The dates of training courses and workshops can be found on the Internet at www.bender-de.com -> Know-how -> Seminars.

1.4 Delivery conditions

Bender sale and delivery conditions apply. For software products the "Softwareklausel zur Überlassung von Standard­Software als Teil von Lieferungen, Ergänzung und Änderung der Allgemeinen Lieferbedingungen für Erzeugnisse und Leistungen der Elektroindustrie" (software clause in respect of the licensing of standard software as part of de­liveries, modifications and changes to general delivery conditions for prod­ucts and services in the electrical industry) set out by the ZVEI (Zentralverband Elektrotechnik- und Elektronikindustrie e. V.) (German Electrical and Electron­ic Manufacturer's Association) also applies. Sale and delivery conditions can be obtained from Bender in printed or elec­tronic format.

1.5 Inspection, transport and storage

Inspect the dispatch and equipment packaging for damage, and compare the contents of the package with the delivery documents. In the event of damage in transit, please contact Bender immediately. The devices must only be stored in areas where they are protected from dust, damp, and spray and dripping water, and in which the specified storage tem­peratures can be ensured.
10
IRDH275_D00122_02_M_XXEN/10.2016
Page 11
Important information

1.6 Warranty and liability

Warranty and liability claims in the event of injury to persons or damage to property are excluded if they can be attributed to one or more of the follow­ing causes:
Improper use of the device.
Incorrect mounting, commissioning, operation and maintenance of the
device.
Failure to observe the instructions in this operating manual regarding transport, commissioning, operation and maintenance of the device.
Unauthorised changes to the device made by parties other than the manufacturer.
Non-observance of technical data.
Repairs carried out incorrectly and the use of replacement parts or
accessories not approved by the manufacturer.
Catastrophes caused by external influences and force majeure.
Mounting and installation with device combinations not recom-
mended by the manufacturer.
This operating manual, especially the safety instructions, must be observed by all personnel working on the device. Furthermore, the rules and regulations that apply for accident prevention at the place of use must be observed.
IRDH275_D00122_02_M_XXEN/10.2016
11
Page 12
Important information

1.7 Disposal

Abide by the national regulations and laws governing the disposal of this de­vice. Ask your supplier if you are not sure how to dispose of the old equip­ment. The directive on waste electrical and electronic equipment (WEEE directive) and the directive on the restriction of certain hazardous substances in electri­cal and electronic equipment (RoHS directive) apply in the European Commu­nity. In Germany, these policies are implemented through the "Electrical and Electronic Equipment Act" (ElektroG). According to this, the following applies:
Electrical and electronic equipment are not part of household waste.
Batteries and accumulators are not part of household waste and must
be disposed of in accordance with the regulations.
Old electrical and electronic equipment from users other than private households which was introduced to the market after 13 August 2005 must be taken back by the manufacturer and disposed of properly.
For more information on the disposal of Bender devices, refer to our homepage at www.bender-de.com -> Service & support.
12
IRDH275_D00122_02_M_XXEN/10.2016
Page 13

2. Safety instructions

DANGER

2.1 General safety instructions

Part of the device documentation in addition to this manual is the enclosed "Safety instructions for Bender products".

2.2 Work activities on electrical installations

Only qualified personnel are permitted to carry out the work necessary to install, commission and run a device or system.
Risk of electrocution due to electric shock!
Touching live parts of the system carries the risk of:
An electric shock
Damage to the electrical installation
Destruction of the device
Before installing and connecting the device, make sure
that the installation has been de-energised. Observe the rules for working on electrical installations.
If the device is used outside the Federal Republic of Germany, the applicable local standards and regulations must be complied with. The European stand­ard EN 50110 can be used as a guide.
IRDH275_D00122_02_M_XXEN/10.2016
13
Page 14

2.3 Device-specific safety information

WARNING
CAUTION
CAUTION
Children and unauthorised persons must not have access to or contact with the ISOMETER®.
Make sure that the operating voltage is correct!
Prior to insulation and voltage tests, the ISOMETER® must be disconnected from the IT system for the duration of the test. In order to check the correct connection of the device, a functional test has to be carried out before starting the system.
Make sure that the basic settings meet the requirements of the IT system.
In the event of an alarm message of the ISOMETER®, the insulation fault should be eliminated as quickly as possible.
If the ISOMETER® is installed inside a control cabinet, the insulation fault message must be audible and/or visible to attract attention.
Safety instructions
14
IRDH275_D00122_02_M_XXEN/10.2016
Page 15
Safety instructions
When using ISOMETER®s in IT systems, make sure that only one active ISOMETER® is connected in each interconnected system. If IT systems are interconnected via coupling switches, make sure that ISOMETER®s not currently used are disconnected from the IT system and deactivated. IT systems coupled via diodes or capacitances may also influence the insulation monitoring process so that a central control of the different ISOMETER®s is required.
Prevent measurement errors!
When a monitored IT system contains galvanically coupled DC circuits, an insulation fault can only be detected correctly if the rectifier valves (e.g. rectifier diode, thyristors, IGBTs, frequency inverters, …) carry a minimum current of > 10 mA.
Unspecified frequency range
When connecting to an IT system with frequency components below the specified frequency range, the response times and response values may differ from the indicated technical data. However, depending on the application and the selected measurement method, continuous insulation monitoring is also possible in this frequency range. There is no influence on the insulation monitoring for IT systems with frequency components above the specified frequency range, e.g. within the range of typical switching frequencies of frequency inverters (2…20 kHz).
IRDH275_D00122_02_M_XXEN/10.2016
15
Page 16
Safety instructions

2.4 Intended use

The ISOMETER® is intended for:
monitoring the insulation resistance of IT systems
Any other use, or any use which goes beyond the foregoing, is deemed to be use other than for the intended purpose. The Bender companies shall not be liable for any losses or damage arising therefrom. Use for the intended purpose also includes
compliance with all information in the operating instructions, and
compliance with test intervals.
In order to meet the requirements of the applicable standards, customised pa­rameter settings must be made on the equipment in order to adapt it to local equipment and operating conditions. Please heed the limits of the range of application indicated in the technical data.
Any use other than that described in this manual is regarded as improper.
16
IRDH275_D00122_02_M_XXEN/10.2016
Page 17
Safety instructions
CAUTION
CAUTION

2.5 Directions for installation

Risk of property damage due to unprofessional installation!
If more than one insulation monitoring device is connected to a conductively connected system, the system can be damaged. If several devices are connected, the device does not function and does not signal insulation faults. Make sure that only one insulation monitoring device is connected in each conductively connected system.
Ensure disconnection from the IT system!
When insulation or voltage tests are to be carried out, the device shall be isolated from the system for the test period. Otherwise the device may be damaged.
The terminals and KE shall be connected by a separate wire to the pro­tective conductor (PE). If the terminals L1, L2 of the device are connected to a system under operation, the terminals and KE must not be disconnected from the protective conductor (PE).
Check proper connection!
Prior to commissioning of the installation, check that the device has been properly connected and check the device functions. Perform a functional test using an earth fault via a resistance that is suitable for the mains voltage.
IRDH275_D00122_02_M_XXEN/10.2016
17
Page 18
Safety instructions
The devices, variant -4.. are delivered with the following factory setting:
ISO SETUP:
ISO SETUP:
ISO SETUP:
ISO ADVANCED:
COM SETUP:
Please check if the basic setting of the ISOMETER® complies with the require­ments of the system to be monitored.
Alarm 1 / Alarm 2 (response values)
Operating principle K1/K2 = N/O operation
Memory = off
System leakage capacitance = 150 μF
Bus address = 3 (slave)
Prevent measurement errors!
When an AC system being monitored contains galvanically coupled DC circuits, take into consideration that: an insulation fault can only be detected correctly when the rectifier valves carry a minimum current of 5…10 mA.
=40 kΩ / 10 kΩ
18
IRDH275_D00122_02_M_XXEN/10.2016
Page 19

3. Function

3.1 Common characteristics (IRDH275 and IRDH275B)

ISOMETER® for IT AC systems with galvanically connected rectifiers and for IT DC systems (IT = unearthed systems)
The operating range of the nominal voltage U coupling devices.
Automatic adaptation to the existing system leakage capacitance
measuring principle (European Patent: EP 0 654 673 B1)
Two separately adjustable ranges of the response value1 kΩ…10 MΩ
(Alarm 1, Alarm 2)
Two-line LC display
Connection monitoring (monitoring of the measuring leads)
Automatic device self test
Option "W":
This option provides: improved shock and vibration resistance for use in ships, on rolling stock and in seismic environment.

3.2 Additional characteristics IRDH275B

Memory with real-time clock to store all alarm messages with date and time stamp.
BMS interface (BMS protocol) for data exchange with other Bender devices (RS485 electrically isolated).
Internal disconnection of the ISOMETER from the IT system to be moni­tored (using a control signal; terminals F1/F2) , e.g. if several ISOMETERs® are interconnected.
Current output 0(4)…20mA (galvanically separated) in relation to the measured insulation value.
Remote setting of certain parameters via the Internet (option; COM460 additionally required)
can be extended via
n
IRDH275_D00122_02_M_XXEN/10.2016
19
Page 20
Function

3.3 Product description

The ISOMETER® type IRDH275 monitors the insulation resistance of IT systems. It is suitable for universal use in 3(N)AC, AC/DC and DC systems. AC systems may include extensive DC supplied loads, such as converters or thyristor-con­trolled DC drives. The device automatically adapts itself to the existing system leakage capacitance.
Suitable coupling devices are available to extend the nominal voltage range
The IRDH275B can be used in combination with a control and indicating de­vice, e.g. PRC1470 version 2 or higher, on the BMS (BMS = Bender Measuring Device Interface) bus.
Un.

3.4 Function

The ISOMETER® IRDH275 is connected between the unearthed system (IT sys­tem) and the protective conductor (PE). The response values and other function parameters are set via the function keys. The parameters are indicated on the LC display and are stored in a non­volatile memory (EEPROM) after the setting is completed. A microprocessor-controlled pulsating AC measuring voltage is superim­posed on the IT system to be monitored ( measuring principle*). The measuring cycle consists of positive and negative pulses of the same am­plitude. The period of these pulses depends on the respective system leakage capacitances and the insulation resistances of the IT system to be monitored. An insulation fault between the IT system and earth closes the measuring cir­cuit. From the measured current value, the microprocessor calculates the in­sulation resistance which is indicated on the LC display or the external kΩ measuring instrument. The measuring time is determined by the system leakage capacitances, the in­sulation resistance, and the system-related interference disturbances. System leakage capacitances do not influence the measuring accuracy.
20
IRDH275_D00122_02_M_XXEN/10.2016
Page 21
Function
If the reading is below the selected response values Alarm 1/Alarm 2, the as­sociated alarm relays respond and the alarm LEDs "Alarm 1/2“ light up and the measuring value is indicated on the LC display (in the event of DC insulation faults, the faulty supply line is indicated). If the terminals R1/R2 are bridged (external RESET button [NC contact] or wire bridge), the fault indication will be stored. Pressing the RESET button, resets the insulation fault message, provid­ed that the currently displayed insulation resistance is at least 25% above the actual response value when the reset is carried out. The fault memory behav­iou r can also be set in the "ISO S ETUP " men u, by selec ting the s ub menu Mem­ory: on/off.
The connections for external kΩ display supplied by the current output 0…400 μA or 0/4…20 mA (IRDH275B) at M+/M- are galvanically isolated.
*) measuring principle "adaptive measuring pulse", a measuring principle developed by Bender (European Patent: EP 0 654 673 B1).
Self test
A self test can be carried out manually using the TEST button or automatically. In order to guarantee high functional reliability, the ISOMETER vides comprehensive self test functions. After switching the supply voltage on, all internal measuring functions, the components of the process control such as data and paramete r memory as well as system and earth connections are checked using the self test functions. The progress of the self test is indi­cated on the display by a bar graph. Depending on the conditions in the IT sys­tem to be monitored, the self test is running for 15…20 seconds, then the message "Test ok!" appears on the LC display for approximately 2 seconds. Then the device returns to normal measuring mode and the current measur­ing value is displayed after the expiry of the measuring time.
®
IRDH275 pro-
IRDH275_D00122_02_M_XXEN/10.2016
21
Page 22
Function
When a device error or connection fault is found, the message "!Error!" ap­pears on the display, the device fault LED lights up, the relay K2 (21-22-24) switches and the respective fault message (see table) is indicated. If such a de­vice fault occurs, a self test is started again every minute. If no more malfunc­tion is detected, the fault message is deleted automatically and the device fault LED extinguishes.
During operation, the self test function can be started by pressing the TEST button (internal or external). The self test can also be started automatically every hour or every 24 hours by selecting "ISO ADVANCED: Autotest" menu. The alarm relays Alarm1/2 only switch after starting the self test function by pressing the TEST button, that means if an automatic self test has been select­ed, the alarm relays do not switch.
Behaviour of the analogue output
Setting Manual test Automatic test
0-20 mA 20 mA
while test procedure
4-20 mA 20 mA
while test procedure
0 mA The current value depends on the insulation value
4 mA The current value depends on the insulation value
22
IRDH275_D00122_02_M_XXEN/10.2016
Page 23
Function
Error
message
System connection?
Connection PE?
Device error xInternal device error 1. Press TEST button
Meaning Steps to be taken
No low-resistance connection of terminals L1, L2, L3 to the IT system
No low-resistance connection of the
terminals and KE to earth (PE)
If the on/off switching of the supply voltage is not possible for technical reasons, a RESET of the process control can be carried out by pressing the "ESC“, "RESET“ and "MENU“ key.
9. Check the wiring of terminal L1, L2 to the IT system
10. Press the test button
11. Switch the supply voltage off and on.
12. Check the fuses
1. Check wiring of terminal and KE to earth (PE)
2. Press TEST button
3. Switch the supply voltage off and on
2. Switch the supply voltage off and on
3. Contact Bender
IRDH275_D00122_02_M_XXEN/10.2016
23
Page 24
Function

3.5 Additional functions IRDH275B

Current output for external measuring instrument
The current output of IRDH275B provides 0(4)…20 mA. The current output is galvanically isolated from the device electronics and the RS485 interface. The ISO SETUP menu, on page 50, allows to switch over between 0…20 mA and 4…20 mA.
Real-time clock
The real-time clock serves as a time base for the memory and self test func­tions. At first, the correct time and date must be set in the menu "ISO AD­VANCED". If time and date are not set, a „C“ (clock) is flashing in the standard display. In the event of a supply voltage failure, time and date will be stored for at least thirty days. If the 24 h test is activated in the "ISO ADVANCED" menu, a special time of day can be selected for the execution of the self test in the menu "TEST: 12:00". Then a self test will be started automatically once a day exactly at the preset time. If the 1 h auto test has been selected, the self test is automatically carried out every full hour.
Interconnected IT systems
When using ISOMETERs® in IT systems, make sure that only one active ISOMETER connected via coupling switches, make sure that ISOMETER used are disconnected and deactivated via a control system. IT systems cou­pled via diodes or capacitances may also influence the insulation monitoring process. Hence, also in this case a central control of the different ISOMETER is required.
®
is connected in each interconnected system. If IT systems are inter-
®
s not currently
®
s
24
IRDH275_D00122_02_M_XXEN/10.2016
Page 25
Function
Function input F1/F2 for connection or disconnection of IT systems being monitored
The ISOMETER® can be disconnected from the IT system and set to STANDBY mode with the function input F1/F2. If the input F1/F2 is bridged, the connec­tions L1/L2 are switched off via internal coupling relays, the measuring func­tion is stopped and the message "STANDBY" appears on the display. Software version 1.4 or higher does not indicate the measured insulation resistance during the disconnection, but indicates the value > 10 MΩ. Furthermore, the alarm relays and alarm LEDs no longer provide alarm messages. After opening the function input F1/F2, the connection to the IT system will be restored and a completely new measuring cycle for insulation monitoring is started. With this function, selective disconnection of an IRDH275 in interconnected IT systems can be carried out via auxiliary contacts of the respective coupling switch. One coupling switch each in a line-type or ring-type arrangement can deactivate a subsequent IRDH275. This arrangement guarantees that only one ISOMETER arrangement with all coupling switches closed, it can be assumed that all ISOMETER BMS address 1) monitors the condition of the function input F1/F2 of all slave ISOMETER When all slave ISOMETER ing function of the Master ISOMETER the Master are without function in this mode. Details are shown in the graphic below.
®
is active in each ga lvanically connected system. In a ring-t ype
®
s are deactivated. In order to prevent this, a BMS Master (IRDH275B
®
s.
®
s are in the STANDBY mode, the insulation monitor-
®
and hence the function input F1/F2 of
IRDH275_D00122_02_M_XXEN/10.2016
25
Page 26
Function
BMS bus (A/B, RS485)
F1/F2
PE PE
PE PE
IT system 1 IT system 2
IT system 3IT system 4
G
G
G
G
Addr. 1
Addr. 2
Addr. 4
Addr. 3
IRDH275B
IRDH275B
IRDH275B
IRDH275B
F1/F2
F1/F2
F1/F2
26
IRDH275_D00122_02_M_XXEN/10.2016
Page 27
Function
ISOnet Function (COM SETUP)
Select "ISOnet=ON" from the COM SETUP menu to activate this function. This function is a type of scanning function. The BMS Master activated via the ISOnet function controls the ISOnet slave devices via the BMS bus. Once an ISOMETER ing the insulation resistance is passed on from the ISOnet Master to the next slave. While an ISOMETER in the STANDBY mode. In this way it can be prevented that the ISOMETERs disturb each other in interconnected systems. In com par iso n t o th e so lut ion cou pli ng switches and function input F1/F2, the response time is prolonged, since no continuous measurement takes place. The advantage is that no auxiliary contacts of a coupling switch are required. Furthermore, this solution is ideally suited for capacitive IT systems or IT sys­tems connected via diodes. An ISOnet slave checks whether there is a Master available in the network. If there is no Master available, the fault message "ISOnet Master?" appears on the display after approximately 1 hour. Additionally, the LED for device errors lights and the Relay K2 switches. When the ISOnet function is activated, the function input F1/F2 will be disconnected.
®
has finished its measurement cycle, the authorization for measur-
®
is carrying out a measurement all other ISOMETER®s are
®
IRDH275_D00122_02_M_XXEN/10.2016
27
Page 28
Function
BMS bus (A/B, RS485)
PE PE
PE PE
IT system 1 IT system 2
IT system 3IT system 4
G
G
G
G
Addr. 1
Addr. 2
Addr. 4
Addr. 3
IRDH275B
IRDH275B
IRDH275B
IRDH275B
28
IRDH275_D00122_02_M_XXEN/10.2016
Page 29

4. Connection

DANGER
Only qualified personnel are permitted to carry out the work necessary to install, commission and run a device or system.
Risk of electrocution due to electric shock!
Touching live parts of the system carries the risk of:
An electric shock
Damage to the electrical installation
Destruction of the device
Before installing and connecting the device, make sure
that the installation has been de-energised. Observe the rules for working on electrical installations.

4.1 Wiring

Connect the terminals A1/+ and A2/- to the supply voltage US in accordance with IEC 60364-4-43. The connections to the supply voltage shall be provided with protective devices to afford protection in the event of a short circuit (a 6 A fuse is recommended). For UL and CSA applications, the use of 5 A fuses is mandatory.
Devices for protection against short-circuit in conformity with IEC 60364-4-43 for the IT system coupling L1/L2 can be omitted if the wiring is carried out in such a manner as to reduce the risk of a short-circuit to a minimum (a short­circuit-proof and earth-fault-proof wiring is recommended).
IRDH275_D00122_02_M_XXEN/10.2016
29
Page 30
Connection
L1 L2 L3
2
3
4
5
U
n
3 AC - System
L2
L1
L+
L-
DC - System
L2L1
U
n
L1
L2
AC - System
L2L1
U
n
-
/~
+/~
PE
A1/+ A2/- L1 L2 AK KE
T1 T2 R1 R2 F1 F2 M+ M- A B 11 12 14 21 22 24
IRDH275(B)
mA
120W
K1
K2
1
6
7 8 9 10 11 12 13
U
s
U
n
L1 L2 L3
3/N AC - System
L2L1
N
Only one ISOMETER® may be connected to an external TEST or RESET button. A galvanic parallel connection of several TEST and RESET inputs for collective testing of ISOMETER
®
s is not permitted.
External coupling devices connected via the terminal AK cannot be switched off via the internal coupling relays. If no coupling device is used, the terminal AK remains free.
30
IRDH275_D00122_02_M_XXEN/10.2016
Page 31
Connection
Legend to wiring diagram:
Supply voltage Us (see nameplate) via 6 A fuse
1
For UL and CSA applications, the use of 5 A fuses is mandatory
Connection to the 3AC system to be monitored:
2, 3
connect terminals L1, L2 to neutral conductor N or terminals L1, L2 to conductor L1, L2
Connection to the AC system to be monitored:
4
connect terminals L1, L2 to conductor L1, L2
Connection to the DC system to be monitored:
5
connect terminal L1 to conductor L+, terminal L2 to conductor L-
6
Separate connection of and KE to PE
External TEST button (NO contact)
*7
External RESET button (NC contact or wire jumper),
*8
when the terminals are open, the fault message will not be stored
STANDBY by means of the function input F1, F2:
*9
When the contact is closed, insulation measurement does not take place; system disconnection
IRDH275: current output, galvanically separated: 0…400 μA
10
IRDH275B: current output, galvanically separated: 0…20 mA or 4…20 mA
Serial interface RS485 (termination 120 Ω resistor)
11
Alarm relay 1; changeover contacts provided
12
Alarm relay 2; (device fault relay) changeover contacts provided
13
The terminal pairs 7, 8 and 9 must be wired galvanically isolate
*
and must not have a connection to PE !
IRDH275_D00122_02_M_XXEN/10.2016
31
Page 32
Connection
L+
L­PE
U
n
DC 0 ... 1760 V
IRDH275
KE
AK
Achtung Hochspannung
Danger High Voltage
AGH150W-4
AK160
+ -

4.2 Wiring diagrams with coupling devices

Please observe the settings in the "ISO ADVANCED AGH“ menu ! Adapt the settings to the coupling device to be used.

4.2.1 Connection with AGH150W-4

Connected to the ISOMETER® this coupling device extends the nominal volt­age range to DC 1760 V in DC systems.
32
IRDH275_D00122_02_M_XXEN/10.2016
Page 33

4.2.2 Connection with AGH520S

2
534
AGH520S
PE
IRDH275
L1
L2 L3
Un
3/(N)/ AC 0...7200 V 42...460 Hz
N
3 AC
3/N/ AC
KE
AK
Connected to the ISOMETER® this coupling device extends the nominal volt­age range to AC 7200 V in pure AC systems. In case of 3 AC systems, Pin 2 of AGH520S is to be connected to L1, in case of 3/N/AC systems, Pin 2 is to be connected to the N-conductor.
IRDH275_D00122_02_M_XXEN/10.2016
33
Page 34
Connection
L1 L2 L3
PE
Un
N
AGH204S-4
1
2
AK160
AK80
U3
V3
W3
IRDH275
KE
AK

4.2.3 Connection with AGH204S-4

This coupling device extends the nominal voltage range of ISOMETER®s used in AC systems including rectifiers.
1
without rectifiers
2
with rectifiers
34
= 3AC 0….1650 V (DC max. 1000 V)
U
n
U
= 3AC 0….1300 V (max. AC voltage; max. DC vol-
n
tage after quency converters:1840 V)
rectifiers in intermediate circuits of fre-
IRDH275_D00122_02_M_XXEN/10.2016
Page 35
Connection
The maximum DC voltage is the voltage permitted to occur in the AC part of an IT system to PE when the IRDH275 is coupled with AGH204S-4 in this part of the system. This voltage is dependent on the level of the nominal voltage, the type of rectification 6 pulse, 12 pulse,…), the type of converter intermedi­ate circuit (current… or voltage…), and the converter technology. In case of converters, the maximum DC voltage in the intermediate circuit usually corre­sponds to the phase-to-phase voltage of the supplying AC system multiplied by 1.414. In case of current-controlled intermediate circuits of frequency con­verters, higher DC voltages are to be expected.
The given voltage values for AC/DC systems take into account values found by previous experience (factor 1.414 between DC voltage and AC voltage). The maximum DC voltage in case of insulation faults in the DC part of the IT system, for example converter intermediate circuit, is DC 1840 V. From this, the maximum nominal AC voltage is calculated:
U
= DC 1840 V / 1.414 = AC 1300 V
max
IRDH275_D00122_02_M_XXEN/10.2016
35
Page 36
Connection
36
IRDH275_D00122_02_M_XXEN/10.2016
Page 37

5. Commissioning flow chart (threepart)

Is the system to be monitored an unearthed system (IT system)?
The IRDH275 is not suitable for this application( contact BENDER).
Un is too high for direct connection. A coupling device providing the respective voltage range must be connected.
Device connection Optional device
connection
no
no
yes
The terminals L1 and L2 must be connected to Un of the system to be moni­tored according to the wiring diagram.
An external kW measuring instrument at M+/M- with a display range of 10 kW...1000 kW, Scale centre point: 120 kW
Output current IRDH275: 0...400 mA Output current IRDH275B: 0/4...20 mA
Connect the supply voltage Us to the terminals A1/+ and A2/-. Consider the details indicated on the nameplate.
External TEST button (NO contact) to the terminals T1 and T2
External RESET button (NC contact) to the terminals R1 and R2
The output contacts of the alarm relays System fault (21-22-24) Alarm 1 (11-12-14) Alarm 2 (21-22-24)
When using the RS485 interface, take care that a 120 W resistor is connected at the beginning and the end of the network.
13
12
11
7
8
10
Deenergize the installation
before connecting the device!
Recommended wire cross section of
connecting cable
single wire 0.2...4 mm
2
flexible 0.2... 2.5 mm
2
Is the maximum nominal voltage U
n
AC 793 V
or Un
DC 650 V
yes
The two PE connections
and KE must be connected separately to the equipotential bonding.
6
2 3 4 5
1
The encircled figures in the flow chart correspond to the figures in the legend to the wiring diagram.
Commissioning of the ISOMETER® (1)
IRDH275_D00122_02_M_XXEN/10.2016
37
Page 38
Commissioning of the ISOMETER® (2)
Commissioning flow chart (threepart)
38
IRDH275_D00122_02_M_XXEN/10.2016
Page 39
Commissioning flow chart (threepart)
In order to check the proper
connection, a functional test
using a resistance that is
suitable for the mains voltage
is to be carried out.
Size of the resistance:
50% of the present
response value Alarm2.
Commissioning of the ISOMETER® (3)
IRDH275_D00122_02_M_XXEN/10.2016
39
Page 40
Commissioning flow chart (threepart)
40
IRDH275_D00122_02_M_XXEN/10.2016
Page 41

6. Operation and setting

6.1 Operating features and displays IRDH275(B)

INFO key: to query standard information /
1
ESC key: back (menu function), confirmation parameter change TEST button: to call up the self test /
2
Up key: parameter change, moving up in the menu RESET button: to delete insulation fault alarms
3
Down key: parameter change, moving down in the menu MENU key: to activate the menu system /
4
Enter key: confirmation parameter change Alarm LED 1 lights: insulation fault, first warning level reached
5
Alarm LED 2 lights: insulation fault, second warning level reached
6
Device fault LED lights: IRDH275 defective
7
Two-line display for standard and menu mode
8
A detailed description of the operating elements is given on the following pages.
IRDH275_D00122_02_M_XXEN/10.2016
41
Page 42

6.1.1 Display in the standard mode

1
3
4
Insulation Fault Rs=011k
W . H
Indication of the insulation resistance in kΩ
1
Additional information about the insulation resistance:
2
"+" = insulation fault at L+ "–" = insulation fault at L– "s" = new measurement has started
= polarity of the measuring pulse
3
. = valid bus communication signals
H = new entry in the memory data base C = flashing, clock is to be set
Messages:
4
- Insulation fault
- Connection system?
- Connection PE?
- Device error x
- *****STAND BY*****
Operation and setting
42
IRDH275_D00122_02_M_XXEN/10.2016
Page 43
Operation and setting
1. EXIT
2. HISTORY INFO
INFO
ESC

6.1.2 Display in the menu mode

Parameter change is permitted
Parameter change is blocked, enabling by a password

6.1.3 Function keys

Two functions are assigned to each function key. In addition to the basic func­tion marked with a circle, all the keys allow navigation within the menu.
Pressing the INFO key provides the following information without opening the menu:
Device name, firmware version
Response values Alarm 1 and Alarm 2
Leakage capacitance C
resistances > 20 kΩ)
Setup status (for details refer to the table of the status numbers on page 83)
COM-Setup (IRDH275 bus address)
Please have the details above on hand if you have a problem and if you con­tact Bender for technical questions.
(only indication if insulation
e
IRDH275_D00122_02_M_XXEN/10.2016
43
Page 44
Operation and setting
TEST RESET
MENU
TEST
RESET
Activating the TEST button starts the ISOMETER
®
self test.
Pressing the RESET button resets insula­tion fault alarms stored in the ISOMETER
The memory function is only available af­ter activating the fault memory in the ISO SETUP menu or after bridging the terminals R1/R2. Furthermore, the ISOMETER
®
can only be reset when the
present insulation value is 25 % higher than the set response value.
The menu system is called up by pressing the MENU key.
For controlling the menu system, the arrow keys, the ENTER key and the ESC key are used:
Arrow up key: Moving up in the menu, increasing a parameter
Arrow down key: Moving down in the menu, reducing a parameter
®
.
44
IRDH275_D00122_02_M_XXEN/10.2016
Page 45
Operation and setting
MENU
INFO
ESC
ESC
ENTER key Selecting a menu item or sub menu item, confirming or stor­ing a parameter change and going back to the associated sub menu item or going to the next input area.
ESC key: Returning from a sub menu to the previous menu.
If you do not quit the menu, the device automatically returns to the standard mode again after approximately five minutes.
For the sake of clarity, the following symbols are used for the functions ENTER, UP/DOWN and ESCAPE in the menu diagrams of this operating manual:

6.2 Menu structure and menu mode

Switchover to the menu mode
After pressing the MENU key, you can change from the standard mode to the menu mode. From the menu mode you can link to the different sub menus.
IRDH275_D00122_02_M_XXEN/10.2016
45
Page 46
Operation and setting
Navigation within the menu
Select the desired menu item using the UP/DOWN keys. The selected menu item is indicated by a flashing cursor. Press the ENTER key to open the associ­ated sub menu. Use the UP/DOWN keys again to select the desired parameters. Move the cur­sor to the edit field by pressing the ENTER key. If you have reached the end of the main menu list, it will be indicated by the "Arrow UP" symbol.
Changing the parameters
When password protection is activated, indicated by the symbol "padlock closed" , the first thing to enter is the correct password before the param­eters can be changed using the UP/DOWN keys. Entering the correct pass­word once allows all parameters to be changed as long as you do not leave the menu.
Changing the parameter usually has an immediate effect on the measuring and alarm functions. The changed parameter is stored in a volatile memory by pressing the ENTER or ESC key after returning to the sub menu (flashing cursor in column 1). During menu operations, all measuring and alarm functions car­ry on working as usual in the background.
Changing from the menu mode to the standard mode
Pressing the ESC key allows fast changing from the menu mode to the stand­ard mode. Thus, the menu item "EXIT" need not to be activated. Automatic switchover from the menu mode to the standard mode takes place when no key is pressed for approximately 5 minutes in a main or sub menu.
46
IRDH275_D00122_02_M_XXEN/10.2016
Page 47
Operation and setting
1. EXIT
2. HISTORY INFO
3. ISO SETUP
4. ISO ADVANCED
5. COM SETUP
6. PASSWORD
7. LANGUAGE
8. SERVICE
1. Exit
2. AGH : no
3. Ce max: 150 µF
4. Measure: AMP
5. Autotest: 24h
6. Clock: 19:08
7. Date: 01.01.01
8. Test: 00:00
1. Exit
2. Alarm1 040 kW
3. Alarm2 010 kW
4. K1 : N.O
5. K2 : N.O
6. Memory: on
7. M+/M-: 0-20 mA
Nr.: 01 #Nr.: 02
Power on
1. Exit
2. Addr: 003
3. ISONet: off
4. ISO Monitor
Insert Service Password: XXX
ISO ADVANCEDISO SETUPHISTORY INFO COM SETUP SERVICE
1. Exit
2. Password: XXX
3. Status: off
PASSWORD
1. Exit
2. Text: Deutsch
LANGUAGE
IRDH275B
IRDH275
ESC
*** IT-SYSTEM *** R >010 MW H
ESC
MENU

6.2.1 Diagram menu structure

IRDH275_D00122_02_M_XXEN/10.2016
47
Page 48
Operation and setting
Data record Event Display indication
1 Switch the supply voltage on Power On 2 Lowest measured insulation value Rmin
3...99 Response value Alarm 1 released
Alarm1
3...99 Response value Alarm 1 cleared
Alarm1
3...99 Response value Alarm 2 released
Alarm2
3...99 Response value Alarm 2 cleared
Alarm2
3...99 Error system connection released
System connection?
3...99 Error system connection cleared
System connection?
3...99 Error PE connection released
PE connection?
3...99 Error PE connection cleared
PE connection?
3...99 Device error released
Device error
3...99 Device error cleared
Device error
3...99 System reset (watchdog) System reset

6.3 Menu HISTORY INFO (IRDH275B)

99 events with date and time stamp can be stored in the memory database. The database is designed as a ring memory, i.e. the eldest entry is overwritten. Data is written into a non-volatile memory and therefore provides protection against voltage failure.
Before storing the events with the actual date and time stamp, set the real­time clock in the ISO ADVANCED menu (refer to page 57). The following function keys are provided to query data from the "HISTORY IN­FO" menu: the UP/DOWN keys to change the data record number, the ENTER key to change from the data record number to the menu item "Clear all:on" to delete the memory storage, and the ESC key to leave the menu. A new entry into the memory is signalled with an "H" on the display in the standard mode. The "H" will be deleted as soon as the "HISTORY INFO" menu is called up.
48
IRDH275_D00122_02_M_XXEN/10.2016
Page 49
Operation and setting
1. EXIT
2. HISTORY INFO
3. ISO SETUP
4. ISO ADVANCED
5. COM SETUP
6. PASSWORD
7. LANGUAGE
8. SERVICE
Nr.: 01 #Nr: 08
Power on
Nr.: 01 #Nr: 08
Clear all: off
Nr.: 01 #Nr: 08
28.08.01 17:43
Nr.: 02 #Nr: 08
Clear all: off
Nr.: 02 #Nr: 08
Rmin: 010k
Nr.: 02 #Nr: 08
25.08.01 10:13
Nr.: 02 #Nr: 08
Clear all: off
Nr.: 02 #Nr: 08
Clear all: off
ESC
IRDH275
IRDH275B
*** IT-SYSTEM *** R >010 MW H

6.3.1 Diagram HISTORY INFO (IRDH275B)

IRDH275_D00122_02_M_XXEN/10.2016
49
Page 50
Operation and setting
6.4 Menu ISO SETUP: Setting of the basic ISOMETER®
functions
All alarm functions such as Alarm 1 and Alarm 2 (prewarning and main alarm), the operating principle of the alarm relays K1 and K2 (N.O = N/O operation, N.C = N/C operation), the fault storage behaviour and a selection of two cur­rent output ranges are set in this menu.

6.4.1 Response values Alarm 1 and Alarm 2

The response values Alarm 1 and Alarm 2 are selected with the UP/DOWN keys and stored with the ENTER key.

6.4.2 Operating principle of the alarm relays

K1/K2 are factory set to N.O Test, that means N/O operation. When the supple­ment "Test" has been selected, the alarm relays switch over during a manual self test. If, for any reason, the alarm relays may not switch over during a manual self test, the settings N.C or N.O are to be selected.
50
IRDH275_D00122_02_M_XXEN/10.2016
Page 51
Operation and setting
K1: N.C Test = N/C operation contacts 11-12-14, with relay test
K1: N.O Test = N/O operation contacts 11-12-14, with relay test
K1: N.C = N/C operation contacts 11-12-14, without relay test
K1: N.O = N/O operation contacts 11-12-14, without relay test
K1: Flash = Flashing function contacts 11-12-14
K2: N.C Test = N/C operation contacts 21-22-24, with relay test
K2: N.O Test = N/O operation contacts 21-22-24, with relay test
K2 : N.C = N/C operation contacts 21-22-24, without relay test
K2 : N.O = N/O operation contacts 21-22-24, without relay test
K2 : Flash = Flashing function contacts 21-22-24
(the alarm relay is energized during normal operation)
(the alarm relay is deenergized during normal operation)
(the alarm relay is energized during normal operation)
(the alarm relay is deenergized during normal operation)
(the alarm relay and the LED flash in the event of an alarm
message, approximately 0.5 Hz
(the alarm relay is energized during normal operation)
(the alarm relay is deenergized during normal operation)
(the alarm relay is energized during normal operation)
(the alarm relay is deenergized during normal operation)
(the alarm relay and the LED flash in the event of an alarm message, approximately 0.5 Hz)
IRDH275_D00122_02_M_XXEN/10.2016
51
Page 52
Diagram ISO SETUP
1. EXIT
2. HISTORY INFO
3. ISO SETUP
4. ISO ADVANCED
5. COM SETUP
6. PASSWORD
7. LANGUAGE
8. SERVICE
1. Exit
2. Alarm1: 100 KW
3. Alarm2: 200 KW
4. K1 : N.O
5. K2 : N.O
6. Memory: off
7. M+/M-: 0-20 mA
Alarm1 : 100 KW
Alarm2 : 200 KW
K1: N.O
K2: N.O
Memory: off
M+/M-: 0-20 mA
K1: N.O Test K1: N.C Test K1: Flash K1: N.O K1: N.C
Memory: on Memory: off
M+/M-: 0-20 mA M+/M-: 4-20 mA
IRDH275B
IRDH275
*** IT-SYSTEM *** R >010 MW H
Operation and setting
52
IRDH275_D00122_02_M_XXEN/10.2016
Page 53
Operation and setting
RF =
20 mA x 120 kW
I
- 120 kW
RF =
16 mA x 120 kW
I - 4 mA
- 120 kW
During the automatic self test, the alarm relays are not switched over.
When a device fault occurs at the ISOMETER®, the relay K2 will automatically be activated as a device fault relay.

6.4.3 Memory setting (on/off)

Memory: on = Fault memory is activated
The device must be reset with the RESET button after
Memory: off = Fault memory deactivated (factory setting)
clearing the fault.

6.4.4 Current output for external measuring instruments (IRDH275B)

Factory setting: 0…20 mA The current output of the IRDH275 can be set to "0…20 mA" or "4…20 mA" via the menu point "M+/M-:". The maximum load is 500 Ω.
Function 0…20 mA: R
= insulation fault, I= current in mA
F
Function 4…20 mA:
= insulation fault, I= current in mA
R
F
The associated characteristic curves are illustrated on page 81.
IRDH275_D00122_02_M_XXEN/10.2016
53
Page 54
Operation and setting

6.5 Menu ISO ADVANCED: Setting of the extended functions

6.5.1 External coupling devices (AGH: no)

Basic setting "no", when no coupling device is used (factory setting).
AGH: 204 AK80
Terminal AK of the IRDH275 is connected to terminal AK80 of the AGH204S-4. The nominal voltage range is extended to 3AC 0…1650 V. Only current converters with an output voltage not exceeding DC 1000 V are al­lowed to be connected (see "operation with coupling device" on page 34).
AGH: 520S
Terminal AK of the IRDH275 is connected to terminal 5 of the AGH520S. The nominal voltage range is extended to AC 0…7200 V. Only current converters wi th an out put v olt age n ot e xce edin g DC 1 000 V ar e all owe d to b e co nnec ted .
AGH: 204 AK160
Terminal AK of the IRDH275 is connected to terminal AK160 of the AGH204S-4. The nominal voltage range is extended to 3AC 0…1300 V. Only current converters with an output voltage not exceeding DC 0…1840 V are al­lowed to be connected (see page 34).
AGH: 150 AK160
Terminal AK of the IRDH275 is connected to terminal AK160 of the AGH150W-4. The nominal voltage range is extended to DC 0…1760 V.
54
The coupling monitoring is deactivated when an external coupling device is connected.
IRDH275_D00122_02_M_XXEN/10.2016
Page 55
Operation and setting
6.5.2 Adaptation to the system leakage capacitance
(Cemax: 150 μF)
This menu allows to adapt the ISOMETER® to the maximum system leakage ca­pacitance (max. 500 μF). Please note that the basic measuring time will be in­creased to approximately 10 seconds when the setting is C setting = 150 μF.
= 500 μF. Factory
e

6.5.3 Changing the measuring principle from AMP to DC (Measure: AMP)

The DC measuring principle is only suitable for pure AC systems. Factory setting = AMP.

6.5.4 Setting the repetition time for automatic self tests (Autotest: 24h)

The time for the repetition of automatic self tests can either be set to 1 hour or to 24 hours or can be deactivated. Factory setting = 24 h

6.5.5 Setting the real-time clock (Clock) (IRDH275B)

The setting of the real-time clock is the time base for the memory and for the automatic self test. In case of failure of the supply voltage, the real-time clock keeps running for approximately 30 days. When the device will be switched on after this period, a flashing "C" appears on the display and the clock has to be set again.

6.5.6 Setting the date (Date) (IRDH275B)

As well as the time, the date is required for the memory, too. In the event of power supply failure, the date function is not influenced for at least 30 days. If the device is switched on again after this period, a new setting of date and time of the real-time clock is required.
IRDH275_D00122_02_M_XXEN/10.2016
55
Page 56
Operation and setting

6.5.7 Specifying the starting time of the automatic self test (Test) (IRDH275B)

If the 24h self test is activated in the ISO ADVANCED menu, it is possible to set the time (hour) when the self test is to be carried out by means of the "TEST: 12:00" sub menu. Then the self test is automatically carried out once a day at a given time. If the 1 hour auto test has been selected, the self test will be car­ried out at every full hour.
56
IRDH275_D00122_02_M_XXEN/10.2016
Page 57
Operation and setting
1. EXIT
2. HISTORY INFO
3. ISO SETUP
4. ISO ADVANCED
5. COM SETUP
6. PASSWORD
7. LANGUAGE
8. SERVICE
1. Exit
2. AGH: no
3. Ce max : 150µF
4. Measure: AMP
5. Autotest: 24h
6. Clock: 21:09
7. Date: 01.01.01
8. Test: 12:00
AGH: no
Ce max : 150µF
Autotest: 24h
no 150 AK160 204 AK160 520S 204 AK80
150µF 500µF
24h no 01h
Clock: 21:09
Date: 01.01.01
Test: 00:00
00:00
. . .
23:00
IRDH275B
IRDH275
Measure: AMP
DC AMP
*** IT-SYSTEM *** R >010 MW H

6.5.8 Diagram ISO ADVANCED

IRDH275_D00122_02_M_XXEN/10.2016
57
Page 58
Operation and setting

6.6 Menu COM SETUP: Setting the BMS interface

6.6.1 Bus address „Addr:“ (IRDH275B)

This menu item is used to set the BMS bus address of the IRDH275. Since there are several ISOMETERs in one system, take care that the bus address is not as­signed twice. The device is factory set to address 3 and hence acts as a slave.
If several IRDH275 are operated on one BMS bus, the addresses of other ISOMETER
®
s must be assigned one after
the other, since only one device may represent the Master.

6.6.2 ISOnet function (IRDH275B)

In the ISOnet = ON sub menu of the COM SETUP, the ISOnet function can be set. The ISOnet function of all ISOMETERs existing in the system must be in "ON" position. A BMS Master with the ISOnet function activated, controls the ISOnet slave de­vices via the BMS bus. If an ISOMETER the permission for insulation measurement is given from the ISOnet Master to the next slave. During the measurement process carried out by an ISOMETER all other ISOMETER
®
s are in the STANDBY mode.
58
®
has completed the measuring cycle,
IRDH275_D00122_02_M_XXEN/10.2016
®
,
Page 59
Operation and setting
<<Bus SCANNING>> R= K ADR:02
!!!!NO DATA!!!! R= K ADR:02
Insulation Fault R= 010K ADR:03

6.6.3 ISO monitor (IRDH275B)

This function allows to query the current measured value as well as the mes­sages of all bus-capable ISOMETERs existing in the BMS network. After select­ing the bus address, the entire information stored by the selected device is indicated on the display. The display indication is structured similar to the standard indication, but instead of the indication of the measuring pulse, the selected bus address is indicated. Without pressing a key, the indication changes to the standard indication of the IRDH275B after about five minutes. If there is no information available from the selected ISOMETER "!!!!NO DATA!!!!" will be displayed.
Information is being searched
No data found
Current data address 03
®
, the message
IRDH275_D00122_02_M_XXEN/10.2016
59
Page 60

6.6.4 Diagram COM SETUP (IRDH275B)

1. EXIT
2. HISTORY INFO
3. ISO SETUP
4. ISO ADVANCED
5. COM SETUP
6. PASSWORD
7. LANGUAGE
8. SERVICE
1. Exit
2. Addr: 003
3. ISONet: off
4. ISO Monitor
Addr : 003
ISONet : off
! ! ! ! NO DATA ! ! ! ! R= ADR: 01
ISONet : off ISONet : on
ADR: 01
. . .
ADR: 30
ADR: 001
. . .
ADR: 030
IRDH275B
IRDH275
*** IT-SYSTEM *** R >010 MW H
Operation and setting
60
IRDH275_D00122_02_M_XXEN/10.2016
Page 61
Operation and setting

6.7 Menu PASSWORD

6.7.1 Activating and setting the password

This menu can be used to activate a "Password" query. This protects the ISOMETER password (menu item 2. Password: xxx) can be set with the UP/DOWN keys and confirmed with the ENTER key. The password can be activated in the menu item "3. Status: on" by clicking the ENTER key. The basic setting is "3. Status: off", that means that the password is deactivated.
®
against unauthorized settings and modifications. The desired
IRDH275_D00122_02_M_XXEN/10.2016
61
Page 62

6.7.2 Diagram PASSWORD

*** IT-SYSTEM *** R >010 M
1. EXIT
2. HISTORY INFO
3. ISO SETUP
4. ISO ADVANCED
5. COM SETUP
6. PASSWORD
7. LANGUAGE
8. SERVICE
1. Exit
2. Password: XXX
3. Status: off
Status: off
Password: XXX
Status: off Status: on
Password: XXX Password: 000 Password: . . . Password: 999
Operation and setting
62
IRDH275_D00122_02_M_XXEN/10.2016
Page 63
Operation and setting
*** IT-SYSTEM *** R >010 M
1. EXIT
2. HISTORY INFO
3. ISO SETUP
4. ISO ADVANCED
5. COM SETUP
6. PASSWORD
7. LANGUAGE
8. SERVICE
1. Exit
2. Text: Deutsch
2. Text: Deutsch
2. Text: Deutsch
2. Text: English

6.8 Menu LANGUAGE

6.8.1 Setting the national language

The menu item "Language" allows fault messages of the ISOMETER® to be set to different languages. There is the choice of German and English. The device menu is not influenced by the language selection.

6.8.2 Diagram Language

IRDH275_D00122_02_M_XXEN/10.2016
63
Page 64
Operation and setting

6.9 Menu SERVICE

This menu item is provided for the Bender service personnel and is protected by a password against erroneous settings. It is intended to provide fast fault clearance by qualified experts in the event of a device error.

6.10 Parameterization via Internet

The parameters of an IRDH275B indicated below can be checked and set from a remote place of use by using a personal computer. In addition, a browser (viewing program for Internet application) and the BMS-Ethernet-Gateway COM460 are required. Remote setting is possible for:
Response value Alarm 1 (1…10,000 kΩ) (Y1)
Response value Alarm 2 (1…10,000 kΩ) (Y2)
Operating principle alarm relay 1 (e.g. N/O operation)
Operating principle alarm relay 2 (e.g. N/O operation)
Measuring principle (AMP or DC)
Current output ranges for external measuring instruments
(0/4…20 mA)
Maximum system leakage capacitance (150 μF or 500 μF)
Time for repetition of the automatic self test (off/ 1 h/ 24 h
Starting time of the automatic self test (0.00…23.00 h)
Language of the alarm messages to be displayed (D, GB)
Setting the fault memory to ON or OFF
64
IRDH275_D00122_02_M_XXEN/10.2016
Page 65

7. Serial interfaces

The ISOMETER®s IRDH275 and IRDH275B have differently designed serial in­terfaces.
- RS485 and IsoData protocol
IRDH275
IRDH275B

7.1 RS485 interface with IsoData protocol (IRDH275)

Data transmission is continuously carried out and can neither be interrupted by the data slave station nor be influenced in any other way. This protocol cannot be used in combination with the BMS protocol. For data evaluation via PC or Laptop, the terminal software "IsoData" and an interface converter of the ASCII-RS485/RS232 type is required.
Interface data:
RS485 interface galvanically isolated from the device electronics
Connection to terminal A and B
Maximum cable length 1200 m
Transmission protocol 9600 baud - 1 start bit - 1 stop bit - 8 data bit
After each valid measurement, the following data block is provided:
- galvanically isolated
- ASCII, unidirectional
- RS485 and BMS protocol
- galvanically isolated
- ASCII, bidirectional
IRDH275_D00122_02_M_XXEN/10.2016
65
Page 66
Serial interfaces
02H0FH30H30
H
30H31H32H38
H
0FH30H30
H
30H30H36H30H0F
H
30H30
H
30H31H32H30
H
0FH30H0FH30
H
0FH30H0FH03
H
Start US= Unit separator
US US
US US
US US End
Measuring value
e.g. 128 kW
Response value
Alarm1 e.g. 60 kW
Response value
Alarm2 e.g. 120 kW
30
H
= No alarm
31
H
= Alarm1 32H = Alarm2 33
H
= Alarm1/2
30H = K1 off, K2 off
31
H
= K1 on, K2 off 32H = K1 off, K2 on 33H = K1 on, K2 on
30
H
= AC fault
31
H
= DC- fault
32H = DC+ fault
10H13
H
LF CR
Example: terminal display
Measuring value
128 KW
Alarm1
60 KW
Alarm2 120 KW
AC fault
Alarm2
K1 off, K2 on
66
IRDH275_D00122_02_M_XXEN/10.2016
Page 67
Serial interfaces
AB AB AB
1st device ... device last device
120 W
0.4 W
120 W
0.4 W
Stub feeder maximum 1 m
Maximum length of the RS485 bus: 1200 m

7.2 RS485 interface with BMS protocol (IRDH275B)

The RS485 interface galvanically isolated from the device electronics and cur­rent output serves as a physical transmission medium for the BMS protocol. If several IRDH275B or other bus-capable devices are interconnected in a net­work via the BMS bus, the BMS bus must be terminated at both ends with a 120 Ω resistor. An RS485 network that is not terminated, is likely to get instable and may re­sult in malfunctions. Only the first and the last device in one line may be ter­minated. Devices in between must not be terminated with 120 Ω. Hence, stub feeders in the network must not be terminated. The length of the stub feeders is restricted to 1 meter.
IRDH275_D00122_02_M_XXEN/10.2016
67
Page 68
Serial interfaces
DI1
1
32
33
64

7.3 Topology RS485 network (IRDH275B)

The optimum topology for the RS485 network is a daisy-chain connection. In this connection, device 1 is connected to device 2, device 2 to device 3, device 3 to device n etc. The RS485 network represents a continuous path without branches.

7.3.1 Correct arrangement

Three examples for correct arrangement:

7.3.2 Wrong arrangement

Three examples for wrong arrangement:

7.3.3 Wiring

A suitable type of cable for the wiring of the RS485 network is: screened cable, core diameter 0.6 mm (e.g. J-Y(St)Y 2 x 0.6), screen on one side connected to earth (PE). Connection to the terminals A and B. The number of bus nodes is restricted to 32 devices. When more devices are to be connected, Bender recommends to use an RS485 repeater DI1.
68
IRDH275_D00122_02_M_XXEN/10.2016
Page 69
Serial interfaces
Fault RS485 Rs=011k
W . H

7.4 BMS protocol (IRDH275B)

This protocol is an essential part of the Bender Measuring Device Interface. Data transmission generally makes use of ASCII characters. Interface data are:
Baud rate: 9600 baud
transmission: 1 start bit, 7 data bits, 1 parity bit, 1 stop bit (1, 7, E, 1)
Parity: even
Checksum: sum of all transmitted bytes = 0 (without CR and LF)
The BMS bus protocol works according to the MASTER-SLAVE principle. That means that one device represents the MASTER while all other bus nodes are SLAVES. It is important that only one MASTER is present in each network. All bus nodes are identified by a unique address. The MASTER scans all other de­vices on the bus cyclically, listens to their signals and then carries out specific commands. Bus address 1 must be assigned to the Master, thus to one of the IRDH275B devices.

7.4.1 BMS Master

A Master can query all warning and operating messages from a slave. If the bus address 1 has been selected for one IRDH275B, this device automat­ically represents the Master, that means that all addresses between 1 and 150 are cyclically scanned via the BMS bus for alarm and operating messages. If the Master receives no answer from five subsequent addresses, the scanning cycle is started again. If the Master recognizes incorrect answers from a slave, the fault message "Fault RS485" is issued by the Master.
IRDH275_D00122_02_M_XXEN/10.2016
69
Page 70
Serial interfaces
***IT-SYSTEM*** R+=500K
Faults may be caused when:
addresses are assigned twice
a second master exists on the BMS bus
interference signals occur on the bus lines
a defective device is connected to the bus
terminating resistors are not activated

7.4.2 BMS Slave

All IRDH275B are factory set to slave mode (address 3). In a BMS network, one address must be selected from the address range 2…30 for each slave. There may be no gaps of more than five subsequent addresses, so that all slaves can be scanned by the Master. For IRDH275B a BMS address can be selected from the address range 1…30. When assigning the addresses, also other devices such as the EDS47x-12 must be considered. The correct reception of BMS data is indicated by a flashing point on the dis­play on the right of the measuring pulse indication.
Flashing point: BMS data re­ceived
If no flashing point appears, it may be attributed to the following:
no Master available in the network
more than one Master available in the network
RS485 interface (terminal A/B) not connected or reversed
70
IRDH275_D00122_02_M_XXEN/10.2016
Page 71
Serial interfaces
The following table gives an overview about essential alarm messages and the assignment of the messages indicated on the display or operator panels, e.g. PRC1470.
Message
Channel
Meaning
Insulation Fault 1 Insulation resistance < setting Alarm 1
Insulation Fault 2 Insulation resistance < setting Alarm 2
Connection system 3 Connection error L1/L2 against system
Connection PE
Connection error /KE against PE
4
conductor
Device error 5 Internal device error
The BMS function is completely available in the standby mode (Stand-by: F1/F2).

7.4.3 Commissioning of an RS485 network with BMS protocol

Connect the terminals A and B of all bus nodes in one line
Switch the terminating resistors on at the beginning and end of the
RS485 network or in case of devices without a terminating switch, at the end of the bus, connect a 120 Ω resistor to the terminals A and B.
Switch the supply voltage U
Determine one IRDH275 as the Master and assign address 1.
Assign the addresses (2…30) subsequently to all other IRDH275B
devices and other bus nodes (see table below).
Check whether a flashing point appears on all devices (BMS commands are being received).
The sub menu "ISO-Monitor" in the COM SETUP menu allows insulation values of the ISOMETER address of the ISOMETER
on.
S
®
s to be queried. Before starting the query, the
®
has to be entered.
IRDH275_D00122_02_M_XXEN/10.2016
71
Page 72
BMS-bus address ranges
Addresses* Device Meaning
0 There is no device with address 0 !
Information sent to address 0 applies to all devices connected to the interface (broadcast)
1 PRC1470 Control and indicating device
1…30 IRDH275B/
375B/575 1…30 COM460 Protocol converter 2…30 EDS47x-12 Insulation fault evaluators (localisation)
31…60 SMO480-12 Signal converter relay
61…90 EDS47xE-12 Insulation fault evaluators (localisation) 111…119 PGH47x Test device for insulation fault location 121…150 PGH47xE Test device for insulation fault location
Malfunctions due to wrong address assignment!
Assigning wrong addresses to external devices may cause malfunctions. Assign the addresses in a way that there are no gaps of more than five subsequent addresses (1…30, 31…60, 61…90, 111…119 and 121…151).
Insulation monitoring device
Serial interfaces
72
IRDH275_D00122_02_M_XXEN/10.2016
Page 73

8. Technical data IRDH275(B)

8.1 Data in tabular form

The values marked with * are absolute values
Insulation coordination acc. to IEC 60664-1
Rated voltage.....................................................................................................................................................AC 800 V
Rated impulse voltage/pollution degree............................................................................................................8 kV / 3
Voltage ranges
IRDH275....:
Nominal voltage range U Nominal frequency f Nominal voltage range U IRDH275….-435: Supply voltage U Frequency range U Supply voltage U IRDH….-427: Supply voltage U IRDH275….:
Power consumption .......................................................................................................................................... ≤ 14 VA
Response values
Response value R Response value R
Relative uncertainty (20 kΩ…1 MΩ) (acc. to IEC 61557-8:2007-01) ............................................................. ±15 %
Relative uncertainty (1 kΩ…20 kΩ).................................................................................................... +2 kΩ / +20 %
Relative uncertainty (1 MΩ…10 MΩ).............................................................................................. 0,2 MΩ / +20 %
Response time t
Measuring time.......................................................................................................................... see characteristic curve
Hysteresis (1 kΩ…10 kΩ) ................................................................................................................................... +2 kΩ
Hysteresis (10 kΩ…10 MΩ)................................................................................................................................. 25 %
..................................................................................................1AC / 3 (N) AC 0…793 V*
n
(for f < 50 Hz see characteristic curve on page 79) ............................................0,1…460 Hz
n
...................................................................................................................... DC 0…650 V*
n
(see nameplate).......................................................................................................AC 88…264 V*
s
................................................................................................................................... 42…460 Hz
s
(see nameplate)...................................................................................................... DC 77…286 V*
s
(see nameplate)..................................................................................................... DC 19.2…72 V*
s
(Alarm 1) ................................................................................................................1 kΩ…10 MΩ
an1
(Alarm 2) ................................................................................................................1 kΩ…10 MΩ
an2
at RF = 0.5 x Ran and Ce = 1 μF.............................................................................................. ≤ 5 s
an
IRDH275_D00122_02_M_XXEN/10.2016
73
Page 74
Technical data IRDH275(B)
Measuring circuit
Measuring voltage U Measuring current I Internal DC resistance R Internal impedance Z Permissible extraneous DC voltage U Permissible system leakage capacitance C
........................................................................................................................................ ≤ 50 V
m
max. (at RF = 0 Ω)...................................................................................................... ≤ 280 μA
m
.................................................................................................................................. ≥ 180 kΩ
i
at50 Hz......................................................................................................................... ≥ 180 kΩ
i
.................................................................................................... ≤ DC 1200 V
fg
................................................................................................... ≤500 μF
e
Factory setting....................................................................................................................................................... 150 μF
Displays
Display, illuminated.............................................................................................................................. two-line display
Characters (number of characters)........................................................................................................................2 x 16
Display range, measuring value ............................................................................................................. 1 kΩ…10 MΩ
Operating uncertainty (20 kΩ…1 MΩ) (acc. to IEC 61557-8:2007-01) .................................................... ±15 % **
Operating uncertainty (1 kΩ…20 kΩ).......................................................................................... ±1 kΩ
/
±15 % **
Operating uncertainty (1 MΩ…10 MΩ).................................................................................. ±0,1 MΩ / ±15 % **
** = under test conditions according to IEC 61326-2-4, the tolerances may double
Outputs/inputs
TEST/ RESET button..............................................................................................................................internal /external
Cable length TEST/RESET button external ......................................................................................................... ≤ 10 m
Current output for measuring instrument SKMP (scale centre point = 120 kΩ):..........................................................
Current output IRDH275 (load) ...................................................................................................... 400 μA (≤ 12.5 kΩ)
Current output IRDH275B (load) .........................................................................................................20 mA (≤ 500 Ω)
Accuracy current output (1 kΩ…1 MΩ)
in relation to the displayed measured value........................................................................................ ±10 %, ±1 kΩ
Serial interface
Interface / Protocol IRDH275.......................................................................................................RS485 / ASCII-IsoData
Interface / Protocol IRDH275B....................................................................................................................RS485 / BMS
Connection ................................................................................................................................................ terminals A/B
Cable length ................................................................................................................................................... ≤ 1200 m
Shielded cable (shield on one site to PE)................................................. two-core, ≥ 0.6 mm
2
, e.g. J-Y(St)Y 2 x 0.6
Terminating resistor..................................................................................................................................120 Ω (0.5 W)
Device address, BMS bus .................................................................................................. 1…30 (factory setting = 3)
74
IRDH275_D00122_02_M_XXEN/10.2016
Page 75
Technical data IRDH275(B)
Switching components
Switching components.............................................2 changeover contacts: K1 (Alarm 1), K2 (Alarm 2, device fault)
Operating principle K1, K2 (Alarm 1, Alarm 2).............................................................................N/O or N/C operation
Factory setting (Alarm 1/Alarm 2)........................................................................................................... N/O operation
Electrical endurance...........................................................................................................12 000 switching operations
Contact class ...................................................................................................................................... IIB (IEC 60255-23)
Rated contact voltage.....................................................................................................................AC 250 V / DC 300 V
Making capacity...............................................................................................................................................AC/DC 5 A
Breaking capacity............................................................................................................... 2 A, AC 230 V, cos phi = 0.4
.......................................................................................................................................... 0,2 A, DC 220 V, L/R = 0.04 s
Minimum contact current at DC 24 V .....................................................................................................2 mA (50 mW)
General data
EMC ................................................................................................................. acc. to IEC 61326-2-4:2006-06 Ed. 1.0
Shock resistance IEC 60068-2-27 (device in operation)...........................................................................15 g / 11 ms
Bumping IEC 60068-2-29 (during transport) .............................................................................................40 g / 6 ms
Vibration resistance IEC 60068-2-6 (device in operation)................................................................1 g / 10…150 Hz
Vibration resistance IEC 60068-2-6 (during transport) ....................................................................2 g / 10…150 Hz
Ambient temperature (during operation) ..........................................................................................- 10 °C…+55 °C
Storage temperature range.................................................................................................................-40 °C…+70 °C
Climatic class acc. to IEC 60721-3-3......................................................................................................................... 3K5
Operating mode............................................................................................................................ continuous operation
Mounting ............................................................................................................................. as indicated on the display
Distance to adjacent devices ............................................................................................................................≥ 30 mm
Connection............................................................................................................................................. screw terminals
Connection, rigid, flexible........................................................................................... 0.2…4 mm
2
/ 0.2…2.5 mm
Connection, flexible with connector sleeve, without/with plastic sleeve ........................................ 0.25…2.5 mm
Conductor sizes (AWG).......................................................................................................................................... 24-12
Tightening torque ............................................................................................................................................... 0.5 Nm
Protection class, internal components (DIN EN 60529) .......................................................................................... IP30
Protection class, terminals (DIN EN 60529)............................................................................................................. IP20
Type of enclosure..................................................................................................................... X112, free from halogen
DIN rail mounting ............................................................................................................................................ IEC 60715
Flammability class ........................................................................................................................................... UL94 V-0
Software version IRDH275 ............................................................................................................................. D160 V1.8
2
2
IRDH275_D00122_02_M_XXEN/10.2016
75
Page 76
Technical data IRDH275(B)
Software version IRDH275B .......................................................................................................................... D159 V1.8
Weight approx. ...................................................................................................................................................... 510 g
Option „W“
Shock resistance IEC 60068-2-27 (Device in operation) ........................................................................... 30 g / 11 ms
Bumping IEC 60068-2-29 (during transport).............................................................................................. 40 g / 6 ms
Vibration resistance IEC 60068-2-6 .............................................................................................1.6 mm / 10…25 Hz
............................................................................................................................................................ 4 g / 25…150 Hz
Ambient temperature (during operation) ..........................................................................................-40 °C…+70 °C
Storage temperature range .................................................................................................................-40 °C…+85 °C
Screw mounting.................................................................................................................................................... 2 x M4
The values marked with * are absolute values
76
IRDH275_D00122_02_M_XXEN/10.2016
Page 77
Technical data IRDH275(B)

8.2 Standards, approvals and certifications

The ISOMETER® was designed under consideration of the following standards:
- DIN EN 61557-8 (VDE 0413-8)
- IEC 61557-8:2007 + Corrigendum
- IEC 61326-2-4
- DIN EN 60664-1 (VDE 0110-1)
- DIN EN 60664-3 (VDE 0110-3)
- ASTM F1669M-96(2007)
- ASTM F1207M-96(2007)
IRDH275_D00122_02_M_XXEN/10.2016
77
Page 78
Technical data IRDH275(B)
1
10
100
1000
1 10 100 1000
C
e
[μF]
10 MΩ
0 kΩ
R
F
t
an
[s]

8.3 Characteristic curves

ISOMETER® response times in relation to system leakage capacitances of:
Ce = 1…500 μF, Un = 0…793 V / 50 Hz
78
IRDH275_D00122_02_M_XXEN/10.2016
Page 79
Technical data IRDH275(B)
100
1000
10000
0,1 1 10 100
f
n
[Hz]
U
n
[V]
AGH520S
AGH204S-4
IRDH275
0,3
Max. AC voltage between the IT system and earth in the frequency range <50 Hz
IRDH275_D00122_02_M_XXEN/10.2016
79
Page 80
Current output 0…400 μA (only IRDH275)
R
F
[ kW]
I
[ mA]
RF =
400 mA x 120 kW
I
- 120 kW
Technical data IRDH275(B)
RF =Insulation fault in kΩ I =Current output in mA
80
IRDH275_D00122_02_M_XXEN/10.2016
Page 81
Technical data IRDH275(B)
1
10
100
1000
10 000
0 5 10 15 20 25
I [mA]
R
F
[kW]
RF =
20 mA x 120 kW
I
- 120 kW
Current output 0…20 mA (IRDH275B)
RF =Insulation fault in kΩ I =Current output in mA
IRDH275_D00122_02_M_XXEN/10.2016
81
Page 82
Current output 4…20 mA (IRDH275B)
1
10
100
1000
10 000
0 5 10 15 20 25
I [mA]
R
F
[kW]
RF =
16 mA x 120 kW
I - 4 mA
- 120 kW
Technical data IRDH275(B)
RF =Insulation fault in kΩ I =Current output in mA
82
IRDH275_D00122_02_M_XXEN/10.2016
Page 83
Technical data IRDH275(B)
Value of the respective number
os
iti
on
of
numbers
from the
left
0 = 1 = 2 = 3 = 4 =
1
K1: N/O operation Test K1: N/C operation Test K1: flashing function K1: N/O operation K1: N/C operation
2
K2: N/O operation Test K2: N/C operation Test K2: flashing function K2: N/O operation K2: N/C operation
3
no external coupling AK AGH204S 80K AK AGH520S AK AGH204S 160K AK AGH150W 160K
4
Cemax 1 μF ** Cemax 10 μF ** Cemax 150 μF Cemax 500 μF
5
6
Self test every 24 hours Self test every hour no periodic self test
7
Language German Language English
8
Password protection not
activated
Password protection
activated
9
AMP measuring
principle
DC measuring principle
10
max. filter frequency
0.1Hz **
max. filter frequency 1Hz
**
max. filter frequency
10Hz **
max. filter frequency
50Hz **
11
min. filter frequency
0,1Hz **
min. filter frequency 1Hz
**
min. filter frequency
10Hz **
min. filter frequency
50Hz **
12
BMS mode ** Isodata ** test data **
13
Bus address in the tens
place IRDH275
Value: 5 ... 9
14
Bus address in the units
place IRDH275
Value: 5 ... 9
15
Number of pulses 2-9 **
Value: 5 ... 9
** The parameters marked with two asterisks are settable via the Service menu item! A password is required for that
purpose !
Status number
IRDH275_D00122_02_M_XXEN/10.2016
83
Page 84
Dimension diagram enclosure IRDH275(B)
DIN rail mounting according to IEC 60715 or
Screw mounting by means of a plug-in trapezoidal support Order No.: 990056 (Option W)
Technical data IRDH275(B)
84
IRDH275_D00122_02_M_XXEN/10.2016
Page 85
Technical data IRDH275(B)

8.4 Ordering details

8.4.1 ISOMETER®

Typ e
IRDH275-435 3(N)AC 0…793 V
IRDH275W-435 B91065100W
IRDH275B-435 B91065101
IRDH275BW-435 B91065101W
IRDH275-427 AC 19,2…55 V
IRDH275W-427 B91065104W
IRDH275B-427 B91065105
IRDH275BW-427 B91065105W
IRDH275-425 10,2…36 V B91065108
IRDH275B-425 B91065109
Nominal
voltage U
DC 0…650 V
42…460 HZ
n
Supply
voltage U
AC 88…264 V DC 77…286 V
DC 19.2…72 V
s
Art.-No.
B91065100
B91065104
Series …B…
The 275B series provides a BMS interface, a memory with real-time clock and other features. An overview about these features is shown in the menu struc­ture on page 45 and in the product and function description on page 20.
IRDH275_D00122_02_M_XXEN/10.2016
85
Page 86
Technical data IRDH275(B)
Option "W"
Devices with ending "W" provide improved shock and vibration resistance. A special varnish of the electronics provides higher resistance against mechan­ical stress and moisture. This makes the devices suitable for use in ships, on rolling stock and in seismic environment.

8.4.2 Coupling devices

Type Nominal voltage Art. No.
AGH204S-4 AC 0…1650 V B914013 AGH520S AC 0…7200 V B913033 AGH150W-4 DC 0…1760 V B98018006
range U
n

8.4.3 Measuring instruments

Type Measuring range Dimensions Art. No.
7204-1421 0…400 μA 72 x 72 mm B986763 9604-1421 0…400 μA 96 x 96 mm B986764 7204S-1421 0…400 μA 72 x 72 mm B986804 9604S-1421 0…400 μA 96 x 96 mm B986784
9620-1421 0…20 mA 96 x 96 mm B986841 9620S-1421 0…20 mA 96 x 96 mm B986842
86
IRDH275_D00122_02_M_XXEN/10.2016
Page 87

INDEX

A
Additional characteristics IRDH275B 19 AGH...
32
Alarm LED 1 Alarm LED 2 Alarm messages Approvals Automatic self test
B
Bender Measuring Device Interface 69 BMS bus
BMS-bus
BMS-bus address ranges BMS-Master BMS-Slave
C
Changing the measuring principle 55 Characteristic curves Commissioning flow chart Commissioning of a BMS network Common characteristics Coupling devices
41 41
71
77
55
- correct arrangement
- wrong arrangement
- address ranges
72
72
69
70
78
19
- ordering details
- wiring diagram
86
32
68
68
29
71
Current output 0...400 mA Current output 4...20 mA
D
Device fault LED 22 Dimension diagram enclosure IRDH275 Directions for installation Display in the menu mode Display in the standard mode
E
Explanations of symbols and warnings 19 External coupling devices External RESET button External TEST button
F
Factory setting 18 Fault memory ON/OFF Flashing point Function Function input F1/F2
H
Historical memory 48 How to use this manual
I
INFO key 41
70
20
80
82
19
43
42
54
31
31
53
25
7
84
IRDH275_D00122_02_M_XXEN/10.2016
87
Page 88
Intended use 16 Interconnected systems ISO monitor (IRDH275B) IsoData protocol
M
Measuring instruments 86 Memory database Menu
- COM SETUP
- HISTORY INFO
- ISO ADVANCED
- ISO SETUP
- LANGUAGE
- PASSWORD
- SERVICE
Menu structure
24
59
65
48
58
49
54
50
63
61
64
47
S
Self test, ISOMETER 41 Service
8
Setting the bus address for IRDH275B Setting the date (IRDH275B) Setting the language of the fault message
63
Setting the operating principle of the alarm
relays
50
Setting the password Setting the real-time clock Setting the response values Alarm 1 and
Alarm 2 Setting the system leakage capacitance Standards Status number Support
8
61
50
77
83
58
55
55
55
O
Operating features and displays 41 Option „W“
19
Ordering details
P
Parameterization via Internet 64 Product description
R
Real-time clock 24 RESET button RS485 interface
85
20
21, 41
67
88
T
Technical data IRDH275 73 Terminating resistor TEST button Topology (IRDH275B) Training courses
W
Wiring diagram ISOMETER 31 Wiring of the RS485 network Work activities on electrical installations workshops Wrong arrangement
IRDH275_D00122_02_M_XXEN/10.2016
67
41
68
10
68
13
10
68
Page 89
IRDH275_D00122_02_M_XXEN/10.2016
89
Page 90
Page 91
Page 92
Bender GmbH & Co. KG
Londorfer Str. 65 • 35305 Gruenberg • Germany Postfach 1161 • 35301 Gruenberg • Germany
Tel.: +49 6401 807-0 Fax: +49 6401 807-259
Email: info@bender.de Web: http://www.bender.de
Photos: Bender archives and bendersystembau archives.