Bender EDS3090, EDS3096, EDS3092 User Manual

Page 1
Manual
EN

EDS3090

EDS195P
ISOSCAN®
I
s
I
n
AL
ARM
I
n
I
s
INF
O
M
EN
U
H
OL
D
R ESE
T
ESC
O
K
…91, …92, …96
Portable equipment for insulation fault location for energised and deenergised AC and DC systems Software version: D399 V2.0
EDS309x_D00012_03_M_XXEN/11.2014
Page 2
Bender GmbH & Co. KG
P.O.Box 1161 • 35301 Grünberg • Germany Londorfer Straße 65 • 35305 Grünberg • Germany Tel.: +49 6401 807-0 • Fax: +49 6401 807-259 E-mail: info@bender.de • www.bender.de
Photos: Bender archives and bendersystembau archives.
© Bender GmbH & Co. KG
All rights reserved.
Reprinting only with permission
of the publisher.
Subject to change!
Page 3
Table of Contents
1. How to get the most out of this manual ............................................................. 7
1.1 How to use this manual ......................................................................................................... 7
1.2 Explanations of symbols and notes ................................................................................... 7
1.3 Overview of chapters .............................................................................................................. 8
2. Safety instructions .................................................................................................. 9
2.1 Intended use .............................................................................................................................. 9
2.2 Device-specific safety instructions .................................................................................... 9
2.3 General safety instructions ................................................................................................ 10
2.4 Qualified personnel .............................................................................................................. 10
3. System description .............................................................................................. 11
3.1 System components ............................................................................................................11
3.1.1 Overview of system components ................................................................................... 11
3.1.2 Insulation fault location equipment type list ............................................................. 12
3.1.3 Accessories .............................................................................................................................. 13
3.2 Function of the system components ............................................................................. 14
3.2.1 Locating current injector PGH18… ................................................................................ 14
3.2.2 Insulation fault locator EDS195P ..................................................................................... 14
3.2.3 Measuring clamps ................................................................................................................. 14
3.2.4 Coupling device AGE185 .................................................................................................... 15
3.3 Operating principle for insulation fault location (IΔL) ............................................. 15
3.3.1 Schematic diagram EDS system ...................................................................................... 16
3.3.2 Test cycle .................................................................................................................................. 16
3.3.3 Definitions ............................................................................................................................... 17
3.3.4 Currents in the EDS system ............................................................................................... 17
3.4 Operating principle for residual current measurement (IΔn) ............................... 18
4. Considerations prior to use ................................................................................ 19
4.1 How does the equipment for insulation fault location work ................................ 19
4.2 Requirements for reliable insulation fault location .................................................. 20
4.3 Reduced locating current .................................................................................................. 22
4.4 Response sensitivity characteristics of the EDS195P ............................................... 22
4.4.1 Response characteristics for main circuits in 3AC systems .................................... 23
EDS309x_D00012_03_M_XXEN/11.2014
3
Page 4
Table of Contents
4.4.2 Response characteristics for main circuits in AC systems ....................................... 24
4.4.3 Response characteristics for main circuits in DC systems ....................................... 24
4.4.4 Response characteristics for control circuits in AC systems ................................... 25
4.4.5 Response characteristics for control circuits in DC systems .................................. 25
5. Connecting the locating current injector ....................................................... 27
5.1 Disconnecting insulation monitoring device .............................................................. 27
5.2 Locating current injector in an electrically isolated IT system .............................. 27
5.3 Connection to a live IT system .......................................................................................... 28
5.4 Connection to a PV system ................................................................................................ 29
6. Operation ............................................................................................................... 31
6.1 Short description of insulation fault location (EDS mode) ..................................... 31
6.1.1 Commissioning the PGH18… for locating current injection ................................. 31
6.1.2 Insulation fault location using EDS195P ....................................................................... 31
6.2 Detailed description of insulation fault location ........................................................ 31
6.3 Description of a residual current measurement ......................................................... 31
6.4 Displays and controls on the PGH18… ......................................................................... 32
6.5 Displays and controls on the EDS195P .......................................................................... 33
6.6 Operating the EDS195P ....................................................................................................... 34
6.6.1 Switching on and off the device ...................................................................................... 34
6.6.2 Changing the measuring clamp ....................................................................................... 35
6.6.3 Improved legibility due to display lighting .................................................................. 35
6.6.4 Changing between insulation fault location IΔL and
residual current measurement IΔn operating modes .............................................. 35
6.6.5 Quickly checking the response values for IΔL and IΔn ............................................ 35
6.6.6 Checking Info menu ............................................................................................................. 35
6.6.7 Significance of the display elements .............................................................................. 36
6.7 Standard displays on the EDS195P ................................................................................. 36
6.7.1 EDS measurement (IΔL) ....................................................................................................... 36
6.7.1.1 Standard display if there is no cable to be measured in the clamp ............. 36
6.7.1.2 Standard display for EDS measurement (IΔL) with cable in the clamp ....... 37
6.7.1.3 Standard display for measuring faults or pauses between changes in polarity
of the measuring pulse ................................................................................................. 37
6.7.2 RCM measurement (IΔn) ..................................................................................................... 37
6.7.2.1 Standard display for RCM measurement (IΔn) with cable in the clamp ..... 37
6.8 Alarms during EDS measurement or RCM measurement ....................................... 37
6.9 Indication of device and measuring errors .................................................................. 38
6.10 Factory settings EDS195P (state as supplied) .............................................................. 38
6.11 Menu structure ....................................................................................................................... 39
4
EDS309x_D00012_03_M_XXEN/11.2014
Page 5
Table of Contents
6.11.1 Navigating in the menu ...................................................................................................... 40
6.11.2 Menu item: Settings ............................................................................................................. 40
6.11.3 Menu item: System .............................................................................................................. 41
6.11.4 Menu item: Harmonics ........................................................................................................ 41
6.11.5 Menu item: IΔL alarms ......................................................................................................... 41
6.11.6 Menu item: IΔn logger ........................................................................................................ 42
6.12 Practical usage ....................................................................................................................... 42
6.12.1 Insulation fault location in a system without a permanently installed EDS
6.12.2 Insulation fault location in a system with a permanently installed EDS system ..
6.12.3 Insulation fault location in diode-decoupled DC systems ..................................... 47
6.12.4 Usage of the EDS195P as a residual current meter ................................................... 49
6.12.5 Indication of the harmonics during residual current measurement .................. 50
6.13 Coupling device AGE185 for higher system voltages ............................................. 51
6.14 Power supply for the EDS195P ......................................................................................... 52
6.14.1 Displaying charge state ...................................................................................................... 52
6.14.2 Changing batteries ............................................................................................................... 52
6.14.3 Power supply unit supplied .............................................................................................. 52
system ....................................................................................................................................... 42
45
7. Technical specifications ...................................................................................... 53
7.1 Technical specifications for the system EDS309… ................................................... 53
7.2 Technical specifications PGH18… .................................................................................. 53
7.3 Technical specifications EDS195P ................................................................................... 54
7.4 Technical specifications measuring clamps ................................................................ 55
7.5 Technical specifications AGE185 ..................................................................................... 56
7.6 Standards ................................................................................................................................. 56
7.7 Dimension diagrams ............................................................................................................ 57
7.8 Status word ............................................................................................................................. 58
7.9 Ordering data including accessories ............................................................................. 59
7.10 Component list ...................................................................................................................... 60
8. Frequently Asked Questions .............................................................................. 61
INDEX ...........................................................................................................................63
EDS309x_D00012_03_M_XXEN/11.2014
5
Page 6
Table of Contents
6
EDS309x_D00012_03_M_XXEN/11.2014
Page 7

1. How to get the most out of this manual

DANGER
WARNING
CAUTION

1.1 How to use this manual

This operating manual describes the basic principles of insulation fault location as well as connecting and operating an item of portable equipment for insulation fault location. It is designed for qualified electricians, and in particular for those designing, installing and operating electrical equipment.
Please read this detailed operating manual and the enclosed sheet entitled "Important safety in­structions for Bender products" prior to using the EDS3090. This document must be kept in easy reach in the case.
If you have any questions, please do not hesitate to contact us. Please contact our Technical Sales Department. We are also happy to provide on-site service. Please contact our Service Department for more information. Service helpline: 0700-BenderHelp (telephone and fax) Carl-Benz-Strasse 10 • 35305 Gruenberg • Germany Tel: +49 6401 807-760 • Fax: +49 6401 807-629 E-mail: info@bender-service.com • www.bender.de

1.2 Explanations of symbols and notes

To make it easier for you to understand and revisit certain sections of text and instructions in the manual, we have used symbols to identify important instructions and information. The meaning of these symbols is explained below:
The signal word indicates that there is a high risk danger that will result in elec­trocution or serious injury if not avoided.
This signal word means that there is a medium risk of danger that can lead to death or serious injury, if not avoided.
This signal word indicates a low level risk that can result in minor or moderate injury or damage to property if not avoided.
This symbol denotes information intended to assist the user to make optimum use of the product.
EDS309x_D00012_03_M_XXEN/11.2014
7
Page 8
How to get the most out of this manual

1.3 Overview of chapters

1. How to get the most out of this manual: This chapter provides information about using this documentation.
2. Safety instructions: This section provides information about risks affecting installation and operation.
3. System description: In this chapter you will find an overview of the system components, a description of their func­tion and the basic principles of insulation fault location. The principle of residual current measurement is described in the final section.
4. Considerations prior to use: This chapter describes the practical aspects of insulation fault location and provides numerous characteristic curves for assessing the response values to be set.
5. Connecting the locating current injector: The connection of the PGH18… to a system to be tested is described here.
6. Operation: This chapter contains a description of the graphical user interface on the EDS195P. There is also an illustration of the menu structure as well as illustrations of the various standard dis­plays. You will also find information of the supply of power to the EDS195P here.
7. Technical specifications: Along with tabular data this chapter contains information on standards and the dimensions of the system components.
8. Frequently Asked Questions: Use this chapter to quickly identify and rectify any malfunctions that occur.
9. INDEX: Use the index to quickly find the desired keywords.
8
EDS309x_D00012_03_M_XXEN/11.2014
Page 9

2. Safety instructions

CAUTION
CAUTION

2.1 Intended use

The portable insulation fault location system EDS309… is used to locate insulation faults in IT sys­tems. All variants are suitable for the measurement of residual currents in TN and TT systems. The EDS3096PG is particularly suitable for insulation fault location in electrically isolated systems.
Please observe the limits on the area of application stated in the technical specifications, as well as the measuring categories for the measuring clamps used. If, in the specific case, measuring current transformers other than the measuring clamps supplied are used with the EDS195P, attention is to be paid to ensuring the connection wires and transformer have an adequate nominal insulation volt­age (overvoltage category, see Technical specifications) Use which deviates from or is beyond the scope of these technical specifications is considered non­compliant.
System interference and high system leakage capacitances can degrade the ac­curacy of the measurement.

2.2 Device-specific safety instructions

Hazard due to excessively high locating current or excessively high locating voltage!
An excessively high PGH18… locating current may damage sensitive loads (e.g. in control circuits) or trigger unintended switching processes. For this reason select a lower locating current for these systems (1 or 10 mA). For instance it is only allowed to use the EDS3091 or EDS3091PG in systems with programmable logic controllers (PLCs).
The locating voltage of DC 50 V produced by the locating current injector PGH186 can cause interference at sensitive system components. In case of doubt, contact Bender.
The locating current from the PGH185 or PGH186 can cause residual current de­vices to trip. The locating current is limited to maximum 25 mA (or 10 mA), how­ever 30 mA residual current devices may trip, for instance, between 15 and 30 mA.
It is necessary to aim for the best possible conductor symmetry in the measuring clamp. Otherwise the measuring clamp may go into saturation due to an exces­sively high load current and cause an alarm I
Δ
n
>10A.
EDS309x_D00012_03_M_XXEN/11.2014
9
Page 10
Safety instructions

2.3 General safety instructions

Along with this operating manual, the enclosed "Important safety instructions for Bender products" form part of the documentation for this device.

2.4 Qualified personnel

Only a qualified electrician is allowed to use the EDS3090 devices. The electrician should be familiar with the assembly, commissioning and operation of the equipment and have undergone appropri­ate training. The person using the EDS system must have read this manual and understood all the instructions relating to safety.
10
EDS309x_D00012_03_M_XXEN/11.2014
Page 11

3. System description

P
S
A
3
0
2
0
PGH186
100mA
M
10mA
25mA
Imax
ON
ON
Us
L1(+)
L2(-)
L3
3(N)AC 0...575V mit/with 500...790V DC 0...504V AGE185 400...960V
PSA3052
M
E
S
S
Z
A
N
G
E
/ C
L
A
M
P
O
N
P
R
O
B
E
D
a
te
n
bla
tt / D
ata
sh
e
e
t : T
G
H
132
0
D
u
rc
h
m
e
sse
r / D
ia
m
et
er : 5
2
m
m
A
rt.-N
r. / A
rt.-n
o
. : B
98
0 6
94
m
ax
. 1 A
6
0
0
V
C
A
T
III
1
0
0
0
m
A
/ 0
,1 m
A
~
1
2
3
4
5

3.1 System components

On page 60, you will find a detailed overview of the scope of delivery of the EDS309x versions. The following illustration provides a choice of the possible components.

3.1.1 Overview of system components

The primary task of the EDS309… is insulation fault location in IT systems. For this purpose the individual components of the EDS309… are used in combination.
EDS195P
ILI
ISOSCAN®
n
ALARM
I n I
L
ESC
HOLD
INFO
OK
MENU
RESET
Aluminium case with handle
1
Measuring clamp PSA3020 (main circuits) or PSA3320 (control circuits)
2
Clamp inside diameter 20 mm
Locating current injector PGH18…
3
For generating a locating current for insulation fault location
Insulation fault locator EDS195P
4
For connecting measuring clamps and for finding insulation faults
Measuring clamp PSA3052 (main circuits) or PSA3352 (control circuits)
5
Clamp inside diameter 52 mm
EDS309x_D00012_03_M_XXEN/11.2014
11
Page 12
System description

3.1.2 Insulation fault location equipment type list

It is possible to undertake a residual current measurement in TT and TN systems (earthed systems) using all the device variants listed below. The following overview describes which measuring tasks can be undertaken with which models:
Equipment for insulation fault location in main circuits
1. Permissible system voltage in the main circuits:
– Insulation fault location in IT systems up to AC 42…460 Hz, 20…575 V and DC 20…504 V
– Insulation fault location using AGE185 up to AC 42…460 Hz, 500…790 V and DC 400…960 V
EDS3090:
Can be used in IT systems in which a locating current injector PGH471 or an IRDH575 is already
installed.
EDS3090PG:
Can be used in IT systems in which neither a locating current injector PGH471 nor an IRDH575 is
already installed.
Supply voltage for the locating current generator PGH185 supplied:
AC 50…60 Hz, 230 V
EDS3090PG-13:
Can be used in IT systems in which neither a locating current injector PGH471 nor an IRDH575 is
already installed.
Supply voltage for the locating current generator PGH185-13 supplied:
AC 50…60 Hz, 90…132 V
2. Permissible system voltage in the main circuits:
– Insulation fault location in IT systems up to AC 42…460 Hz, 0…575 V and DC 0…504 V
– Insulation fault location using AGE185 up to AC 42…460, Hz 500…790 V and DC 400…960 V
EDS3096PG:
Can be used in IT systems in which neither a locating current injector PGH471 nor an IRDH575 is
already installed.
Supply voltage for the locating current generator PGH186 supplied:
AC 50…60 Hz, 230 V
Insulation fault location, also in IT systems electrically isolated on all poles
EDS3096PG-13:
Can be used in IT systems in which neither a locating current injector PGH471 nor an IRDH575 is
already installed.
Supply voltage for the locating current generator PGH186-13 supplied:
AC 50…60 Hz, 90…132 V
Insulation fault location, also in IT systems electrically isolated on all poles
12
EDS309x_D00012_03_M_XXEN/11.2014
Page 13
System description
EDS3096PV:
Applicable in PV systems without a locating current injector installed.
Supply voltage for the delivered locating current injector PGH186: AC 50…60 Hz, 230 V.
Insulation fault location, also in IT systems disconnected on all poles or in de-energised IT sys-
tems.
Equipment for insulation fault location in control circuits
Permissible system voltage in the control circuits: Insulation fault location in IT systems up to AC 42…460 Hz, 20…265 V and DC 20…308 V.
EDS3091:
Can be used in IT systems in which a locating current injector PGH473 or an IRDH575 is already
installed.
EDS3091PG:
Can be used in IT systems in which neither a locating current injector PGH473 nor an IRDH575 is
already installed.
Supply voltage for the locating current generator PGH183 supplied:
AC 50…60 Hz, 230 V
EDS3091PG-13:
Can be used in IT systems in which neither a locating current injector PGH473 nor an IRDH575 is
already installed.
Supply voltage for the locating current generator PGH183-13 supplied:
AC 50…60 Hz, 90…132 V
Equipment for insulation fault location in main circuits and control circuits
EDS3092PG:
Contains the components and combines the features of the EDS3090PG and EDS3091PG

3.1.3 Accessories

You will find information on the standard accessories as well as on optional accessories in the order­ing data on page 59 and in the component list on page 60.
Only use the components supplied by us on working with the EDS309…. Com­mercially available measuring clamps are not allowed to be used! This state­ment also applies to measuring clamps or measuring current transformers from the Bender range that are not expressly intended to be used with the EDS309…. Along with the measuring clamps supplied, it is allowed to connect to the EDS195P the following measuring current transformers from the Bender series: WF… W… /WR… /WS… W…-8000/WS…-8000 Series W…AB current transformers cannot be used!
For series WF… current transformers you will need a BNC to PS2 adapter cable, see page 59.
EDS309x_D00012_03_M_XXEN/11.2014
13
Page 14
System description

3.2 Function of the system components

3.2.1 Locating current injector PGH18…

The PGH18… generates a defined locating current. The magnitude of the current is dependent on the insulation fault present and the system voltage.
The PGH185 or PGH186 limits the locating current to maximum 25 mA or maximum 10 mA
depending on the switch setting.
The PGH183 limits the locating current to maximum 2.5 mA or maximum 1 mA depending on
the switch setting.
The PGH186 applies the locating current in electrically isolated IT systems or in IT systems with
a system voltage < 50 V using an integrated voltage source (DC 50 V). In IT systems with a sys­tem voltage > 50 V the existing voltage in the system is used to drive the locating current.

3.2.2 Insulation fault locator EDS195P

The insulation fault locator EDS195P has the following measuring functions:
Insulation fault location I
– Either as a component of the portable equipment for insulation fault location EDS309…
– Or as an additional insulation fault locator in permanently installed equipment for insulation
fault location with IRDH575 or PGH1… as well as EDS46…/49….
Residual current measurement I
value range can be found in table 3.1 on page 14.
(EDS mode) for use in IT AC or DC systems:
ΔL
(RCM mode) for usage in TN or TT AC systems. The response
Δn
Response value
The response value is defined by the sensitivity of the EDS195P. This value can be set in both DC and AC and 3AC IT systems as an arithmetic mean in accordance with Tabelle 3.1 auf Seite 14. System in­terference and high system leakage capacitances can degrade the accuracy.

3.2.3 Measuring clamps

Measuring clamps measure the locating current or the residual current. They have a test lead approx. 2 m long. The connection to the EDS195P is made using a BNC connection. The following table summarises the most important data for the usage of the different measuring clamps.
IT system
TN/TT system
Tab. 3.1: Measuring clamps and response values for the EDS195P
Main circuit
(EDS3090…, 3092…, 3096…)
Measuring
clamps
Measuring range 2…50 mA 0.2…5 mA
Response value
Measuring
clamps
Measuring range 5 mA…10 A 2 mA…2 A
Response value 10 mA…10 A 5 mA…1 A
PSA3020, PSA3052, PSA3165 PSA3320, PSA3352
2…10 mA,
PSA3020, PSA3052, PSA3165 PSA3320, PSA3352
±30% / ±2 mA
Control circuit
(EDS3091…)
0.2…1 mA, ±30 % / ±0.2 mA
If measuring current transformers are used instead of measuring clamps, you will need the adapter supplied: BNC/4-mm connector. See table on page 60.
14
EDS309x_D00012_03_M_XXEN/11.2014
Page 15
System description

3.2.4 Coupling device AGE185

The coupling device AGE185 expands the nominal voltage range of the equipment for insulation fault location EDS309…. It enables the equipment to be connected to system nominal voltages up to AC 790 V or DC 960 V.

3.3 Operating principle for insulation fault location (IΔL)

On the occurrence of the first insulation fault in IT systems a residual current flows that is essentially defined by the system leakage capacitances. The basic concept of fault location is therefore to briefly close the fault circuit using a defined resistance. With this principle a locating current is provided by the system voltage and this locating current contains a signal that can be evaluated.
The locating current is generated periodically by the locating current injector PGH18… (part of the EDS309…PG system). The locating current can also be generated by an IRDH575 or a locating current injector PGH47…. The amplitude and duration of the locating current is limited. During this process the system con­ductors are alternately connected to earth via a defined resistance. The locating current produced as a result is dependent on the magnitude of the insulation fault present and the system voltage. For example the locating current on the EDS3090 is limited to maximum 25 mA; with the setting
I
= 10mA it is limited to 10 mA. During planning it is to be ensured that there are no system com-
max
ponents in which this locating current could cause a reaction involving damage in unfavourable cir­cumstances.
The locating current pulse flows from the locating current injector through the live conductors to the insulation fault by the shortest route. From there it flows via the insulation fault and the earth cable (PE cable) back to the locating current injector. This locating current pulse is detected by the meas­uring clamps or measuring current transformers in the insulation fault path and is indicated by the insulation fault locator EDS195P connected.
You must ensure that all live conductors are routed through the measuring clamp. Do not route any protective earth conductors or screens on screened cables through the measuring clamp! Commercial measuring clamps are not suitable for the EDS309… and must not be used. Only if these notes are observed will you obtain a correct measurement result. You will find additional information in our technical information Techinfo08 "Transformer installation".
EDS309x_D00012_03_M_XXEN/11.2014
15
Page 16

3.3.1 Schematic diagram EDS system

U
n
IT-System
PSA...
EDS195P
PGH...
PE
R
F
L2(L-)
L1(L+)
2
3
1
EDS Start
Position PGH...
12331
2 sec
4 sec
2 sec
4 sec
System description
EDS195P Insulation fault locator
PGH… Locating current injector
U
n
IT system voltage
PSA… Measuring clamp
R
F
Insulation fault
PE Protective earth conductor

3.3.2 Test cycle

The locating current pulse cycle has a duration of 6 seconds. The PGH… sends alternating positive and negative locating current pulses. The sketch below shows the test cycle of the PGH… with the different switch settings (1, 2, 3) on the device, see schematic diagram above.
16
EDS309x_D00012_03_M_XXEN/11.2014
Page 17
System description

3.3.3 Definitions

I
= Locating current that flows through the locating current injector while the fault location
L
is running (EDS mode).
I
= Locating current measured by the insulation fault locator (EDS mode).
ΔL
I
= Residual current produced by an insulation fault (RCM mode).
Δn

3.3.4 Currents in the EDS system

As an addition to the schematic diagram on page 16, here the path of the residual currents and the locating current is shown:
U
n
PE
.............
. .. .. ..
I
ΔL
C
E-V
C
E-N
R
F-V
R
F-N
IT-System
I
PSA...
Δn
IΔL
PGH...
3
R
F-V
EDS195P
C
E-N
1
2
C
E-V
I
L
Locating current circuit due to the insulation fault R
Residual currents I
(example)
Δn
F-N
R
F-N
Locating current measured by the EDS195P
Upstream capacitances, system leakage capacitances upstream of the measuring current transformer
Downstream capacitances, system leakage capacitance downstream of the measuring current transformer
Insulation fault upstream of measuring current transformer
Insulation fault downstream of the measuring current transformer
The following residual currents flow through the measuring current transformer of the EDS195P:
The locating current caused by the insulation fault R
The residual currents I
C
, or that are caused by R
E-N
Transient leakage currents that are caused by switching and control activities in the system
Low-frequency leakage currents generated by the use of converters
EDS309x_D00012_03_M_XXEN/11.2014
F-N
that flow through the system leakage capacitances C
Δn
F-V
and R
F-N
E-V
and
17
Page 18
System description
I
I
I

3.4 Operating principle for residual current measurement (IΔn)

In the RCM mode the EDS309… operates based on the principle of residual current measurement. In this case only the insulation fault locator EDS195P and a measuring clamp are used, the locating cur­rent injector PGH18… is not required.
As per Kirchhoff's law the sum of the currents flowing into any node in a network is equal to the sum of the currents flowing out.
II
I
EDS195P
ILI
n
ISOSCAN®
ALARM
In
L
I
ESC
INFO
HOLD
OK
MENU
RESET
Abb. 3.1: The two currents Izu and Iab have the same magnitude, however their signs are different,
such that the sum of the two currents is zero. The EDS195P detects this situation, there is no message.
EDS195P
ILI
n
ISOSCAN®
ALARM
In
L
I
ESC
INFO
HOLD
OK
MENU
RESET
Abb. 3.2: Part of the current flows through an insulation fault R
. The sum of the two currents
F
is no longer zero. As soon as the residual current reaches or exceeds the response value
there is an alarm message on the EDS195P.
In the RCM mode it is possible to measure residual currents in single and three­phase TT or TN systems. If the system leakage capacitance ahead of the measur­ing clamp is sufficiently high, the EDS195P can also be used for measurements in single and three-phase IT systems. The suitability of the device is to be checked in the specific case.
18
EDS309x_D00012_03_M_XXEN/11.2014
Page 19

4. Considerations prior to use

PGH18...
EDS195P
PSA...
I
L

4.1 How does the equipment for insulation fault location work

The equipment comprises a locating current injector PGH18… and an insulation fault locator EDS195P with measuring clamp PSA3… connected.
Functional sequence
Insulation fault location is started by activating the locating current injector PGH18…
The locating current injector PGH18… briefly connects the live conductors to earth with cur-
rent limiting.
The insulation fault creates a closed circuit in which a locating current I
tem voltage flows. The locating current is limited to a maximum value of 25 mA or 10 mA (PGH185/186), 2.5 mA or 1 mA (PGH183).
The locating current flows from the locating current injector via the live cables, the insulation
fault R
The locating current signal can be measured using measuring clamp placed around the cables
in the outgoing circuit from the distribution system and evaluated by the insulation fault loca­tor EDS195P.
The location of the fault can be determined exactly by moving along the cable with the measur-
ing clamp.
and the earth cable (PE cable) back to the locating current injector.
F
dependent on the sys-
L
EDS309x_D00012_03_M_XXEN/11.2014
Abb. 4.1: EDS operating principle
19
Page 20
Considerations prior to use

4.2 Requirements for reliable insulation fault location

The insulation fault locator has the task of locating the insulation fault R uring clamp. For this purpose, it must reliably detect the locating current caused by the insulation fault. Requirements:
The insulation fault must be present for at least 30s
The locating current is in the following ranges:
– Main circuits with EDS3090, EDS3090PG, EDS3090PG-13, EDS3092PG,
EDS3096PG-13, EDS3096PV, EDS3096PG: I
– Control circuits with EDS3091, EDS3091PG, EDS3091PG-13, EDS3092PG:: I
The upstream capacitances C
must be at least as large as the downstream capacitances C
E-V
See also chapter "3.3.4 "
The total system leakage capacitance must not exceed the maximum values in the characteris-
tics in chapter "4.4 ".
The sum of the locating current and residual current flowing through the measuring clamp or
the measuring current transformer must not exceed the following values:
– Main circuits with EDS3090, EDS3090PG, EDS3090PG-13, EDS3092PG,
EDS3096PG-13, EDS3096PV, EDS3096PG: maximum 10 A
– Control circuits with EDS3091, EDS3091PG, EDS3091PG-13, EDS3092PG: maximum 1 A
There must be no connections to other outgoing circuits downstream of a measuring clamp or
measuring current transformer, see sketch.
downstream of the meas-
F-N
= 2…50 mA
L
= 0.2…5 mA
L
E-N
.
EDS195P
ILI
n
ISOSCAN®
ALARM
In
L
I
ESC
HOLD
INFO
OK
MENU
RESET
Abb. 4.2: Connections between outgoing circuits will result in measuring errors
As well as the magnitude of the residual current, the frequency of the residual current also
affects the reliable detection of the locating current. Residual currents at frequencies other than the system frequency may, e.g., be caused by the usage of frequency converters. The behaviour of the EDS309… is described by the fault curve shown below:
– If the residual currents measured in main circuits exceed 10 A, the EDS195P outputs the
alarm message "I
>10 A".
Δ
n
This statement applies to the system frequencies 50/60/400 Hz for the EDS3090, EDS3090PG, EDS3090PG-13, EDS3092PG, EDS3096PG-13, EDS3096PV and EDS3096PG.
– If the residual currents measured in control circuits exceed 1 A, the EDS195P outputs the
alarm message "I
>1 A".
Δ
n
This statement applies to the system frequencies 50/60/400 Hz for the EDS3091, EDS3091PG, EDS3091PG-13 and EDS3092PG.
20
EDS309x_D00012_03_M_XXEN/11.2014
Page 21
Considerations prior to use
0
1
2
3
4
5
6
7
8
9
10
110100
Permissible residual current [A]
Frequency [Hz]
Frequency range Insulaon fault locaon EDS195P
EDS3090..., EDS3096...
EDS3091...
1
0,9
0,8
0,7
0,6
0,5
0,4
0,3
0,2
0,1
Permissible Frequency and Residual current range
Abb. 4.3: Fault curve:
A residual current of 2 A at 10 Hz is outside the permitted
frequency range (red dot) ==> a valid measurement is not possible!
There must be no connections between outgoing circuits downstream of the measuring clamp because such connections will produce interfering residual currents. For example, the message "IΔn>10A" may be output as a consequence.
Symmetrical insulation faults downstream of the measuring current transform­er will not be detected in certain circumstances. Low frequency residual currents (e.g. caused by converters) can mean that insulation faults are not found if their frequency is the same as or approximately the same as the frequency of the lo­cating cycle of the PGH18….
Parallel cables routed to the same load are to be routed together through the measuring clamp during the measurement.
EDS309x_D00012_03_M_XXEN/11.2014
21
Page 22
Considerations prior to use

4.3 Reduced locating current

Particularly in DC control voltage systems in the power station and public utility sector there may be relays or PLCs installed that switch at relatively low currents. In such a case the I
switch on the
max
PGH18… must be placed in the 10 mA or 1 mA position. The switch's label, e.g. 10 mA or 25 mA, de­fines the magnitude of the locating current only for DC systems. For AC locating currents see "chapter 4.4". It must also be checked prior to a measurement with reduced locating current (switch position 10 mA or 1 mA) whether sensitive system components could be triggered unintentionally.

4.4 Response sensitivity characteristics of the EDS195P

The type of system, system voltage, system frequency, system leakage capacitance and locating cur­rent all affect the EDS system's response sensitivity. The magnitude of the locating current can be set on the locating current injector PGH18…. A reduced locating current is produced in AC systems de­pending on the type of system. In comparison to DC systems the related factor in AC systems is 0.5 and in 3AC systems 0.67. For this reason set the response value on the EDS195P for usage in AC and 3AC systems as follows:
Settings Main circuit Control circuit PV system
Equipment for insulation fault location
EDS195P setting: select the measuring clamp type using button
PGH18… setting: locating current I
Response range EDS195P Menu item 2.2: I
PGH18… setting: reduced locating current I
Response range EDS195P with reduced locating current Menu item 2.2: I
L
ΔL ALM
L
ΔL ALM
EDS3090
EDS3090PG
EDS3090PG-13
EDS3092PG EDS3096PG
PSA3020, PSA3052,
PSA3165
Measuring range
2…50 mA
25 mA
(PGH185/186)
2…10 mA 0,2…1 mA 2…10 mA
10 mA
(PGH185/186)
2…5 mA 0,2…0,5 mA 2…5 mA
EDS3091
EDS3091PG
EDS3091PG-13
EDS3092PG
PSA3320, PSA3352
Measuring range
0,2…5 mA
2,5 mA
(PGH183)
1 mA
(PGH183)
EDS3096PV
PSA3052
Measuring range
2…50 mA
25 mA
(PGH186)
10 mA
(PGH186)
Tab. 4.1: Settings for the EDS195P and the PGH18…
For the response value setting see menu item “2. Settings/ 2. IΔL) on page 39. The response values are given as characteristics that can have a maximum error of ±30 %. Measuring clamp tolerances are included here. The characteristics apply at the related nominal voltage stated. In case of variation in the nominal voltage, a proportional change in the response values is to be ex­pected. In case of system voltages that change dynamically or in case of superimposed DC currents and AC currents that vary from the system frequency (e.g. due to frequency converters), response values outside the ranges shown may result.
22
EDS309x_D00012_03_M_XXEN/11.2014
Page 23
Considerations prior to use
0
20
40
60
80
100
120
140
160
0 50 100 150
R
F
[k]
Ce[uF]
3AC230V
2mA
5mA
10mA
0
20
40
60
80
100
120
0 20406080
R
F
[k]
Ce[uF]
3AC400V
2mA
5mA
10mA
0
20
40
60
80
100
120
140
160
0 102030405060
R
F
[k]
Ce[uF]
3AC500V
2mA
5mA
10mA
0
50
100
150
200
250
0 1020304050
RF[k]
Ce[uF]
3AC690V
2mA
5mA
10mA
The characteristics below enable you to simply determine a practical response value for the EDS195P. If the insulation monitoring device in a monitored system indicates an alarm message, manual insulation fault location can be started. Proceed as follows:
1. Select the characteristics (3AC, AC, DC) that are appropriate for your type of system.
2. From these, select the diagram that best matches the desired system voltage.
3. Calculate the expected leakage capacitance C devices in the IRDH… series can indicate the magnitude of the leakage capacitance (press INFO button). Apply this value to the diagram in the form of a vertical line. If it is not possible to check the capacitance, the highest capacitance in the related diagram is to be taken.
4. The characteristics shown indicate the response sensitivity of the EDS195P in main circuits for 2 mA, 5 mA and 10 mA and in control circuits for 0.2 mA, 0.5 mA and 1 mA. Values above the related curve cannot be measured. Values and characteristics that lie in the area between the upper and lower characteristic can be estimated approximately using the existing characteristics.
5. Set the required response value, on the left of the line from point 3., on the EDS195P.
6. The characteristics for DC 24 V and AC 42 V do not apply to the EDS3096, as the locating cur­rent generator operates with a locating voltage of DC 50 V. For this reason the curves for DC 60 V and AC 110 V apply at these nominal voltages.
of the system monitored. Insulation monitoring
e

4.4.1 Response characteristics for main circuits in 3AC systems

EDS309x_D00012_03_M_XXEN/11.2014
23
Page 24

4.4.2 Response characteristics for main circuits in AC systems

0
2
4
6
8
10
12
14
16
18
0 50 100 150 200 250 3 00
R
F
[k]
Ce[uF]
AC42V
2mA
5mA
10mA
0
5
10
15
20
25
30
0 50 100 150 2 00 250 3 00
R
F
[k]
Ce[uF]
AC110V
2mA 5mA 10mA
0
10
20
30
40
50
60
050100150
R
F
[k]
Ce[uF]
AC230V
2mA 5mA 10mA
0
10
20
30
40
50
60
70
80
90
100
0 20406080100
R
F
[k]
Ce[uF]
AC400V
2mA 5mA 10mA
0
2
4
6
8
10
0 100 200 300 400 500
R
F
[k]
Ce[uF]
DC24V
2mA 5mA 10mA
0
5
10
15
20
25
0 50 100 150 200 250 300
R
F
[k]
Ce[uF]
DC60V
2mA 5mA 10mA
0
5
10
15
20
25
30
35
40
45
50
0 50 100 150 200 250 300
R
F
[k]
Ce[uF]
DC110V
2mA 5mA 10mA
0
10
20
30
40
50
60
70
80
90
100
050100150
RF [k]
Ce[uF]
DC230V
2mA 5mA 10mA
Considerations prior to use

4.4.3 Response characteristics for main circuits in DC systems

24
EDS309x_D00012_03_M_XXEN/11.2014
Page 25
Considerations prior to use
0
20
40
60
80
100
120
0 5 10 15 20 25
R
F
[k]
Ce[uF]
AC42V
0,2mA 0,5mA 1mA
0
50
100
150
200
250
024681012
R
F
[k]
Ce[uF]
AC110V
0,2mA 0,5mA 1mA
0
100
200
300
400
500
600
02468
R
F
[k]
Ce[uF]
AC230V
0,2mA 0,5mA 1mA
0
20
40
60
80
100
120
0 102030405060
R
F
[k]
Ce[uF]
DC24V
0,2mA 0,5mA 1mA
0
50
100
150
200
250
0 5 10 15 20
RF[k]
Ce[uF]
DC60V
0,2mA 0,5ma 1mA
0
50
100
150
200
250
300
350
400
450
0246810
R
F
[k]
Ce[uF]
DC110V
0,2mA 0,5mA 1mA
0
100
200
300
400
500
600
700
800
900
1000
0123456
RF[k]
Ce[uF]
DC230V
0,2mA 0,5mA 1mA

4.4.4 Response characteristics for control circuits in AC systems

4.4.5 Response characteristics for control circuits in DC systems

EDS309x_D00012_03_M_XXEN/11.2014
25
Page 26
Considerations prior to use
26
EDS309x_D00012_03_M_XXEN/11.2014
Page 27

5. Connecting the locating current injector

CAUTION
US = 0 V
IT-System
PSA...
EDS195P
PGH186
PE
R
F
L2(L-)
L1(L+)
2
3
1
G
+
-
L1
Hazard due to excessively high locating voltage!
Check the information on the nameplate to ensure the devices to be connected are suitable for the supplying system. The operation of the PGH18… and possi­bly the power supply unit with an incorrect supply voltage can cause irreparable damage to the devices.
Prior to commissioning check whether all system components are correctly connected together.

5.1 Disconnecting insulation monitoring device

During insulation fault location using the EDS309… an existing insulation monitoring device must be disconnected from the system for the duration of the fault location if its internal resistance is
R
<120 kΩ. During this process the connection to the system must be interrupted on all poles, shut-
i
ting down the supply voltage to the insulation monitoring device is insufficient. On the usage of such a device with R ever the PGH18… will affect the measurement made by the insulation monitoring device.

5.2 Locating current injector in an electrically isolated IT system

For insulation fault location in electrically isolated systems using the EDS3096PG, the integrated voltage source G in the PGH186 supplies a locating voltage. The locating voltage DC 50 V is provided by the PGH186 at the socket L1(+). Ma ke sure that this sock­et is coupled to the system to be monitored during insulation fault location, only then will the inte­grated voltage source in the PGH186 be effective.
120 kΩ the effect is negligible, disconnection is not required in this case. How-
i
Note that the active conductors in the system to be checked must be coupled together via loads or the electrically isolated power supply.
EDS309x_D00012_03_M_XXEN/11.2014
27
Page 28

5.3 Connection to a live IT system

DANGER
DANGER
U
U
U
Risk of electric shock!
On touching live uninsulated conductors, death or serious injury may be caused. For this reason prevent any physical contact with active conductors and follow the rules for working on electrical systems.
Risk of electric shock!
If the PGH18… is connected using terminals L1, L2, L3 (or L1, L2) to a system that is live due to its operation, the terminal must not be disconnected from the protective earth conductor (PE). Otherwise the terminal will be at the dangerous system voltage!
Connect the locating current injector PGH18… as follows:
Connecting the locating current injector
EDS195P
ILI
n
ISOSCAN®
ALARM
In I
L
ESC
HOLD
I
L
F
INFO
OK
MENU
RESET
28
EDS309x_D00012_03_M_XXEN/11.2014
Page 29
Connecting the locating current injector
DANGER
DANGER
CAUTION
Central inverter
=
AGE185
PGH186
PE
E
L1(+)
L2(-)
IT system
Transformer
EDS
195P
BNC
EDS
195P
BNC
EDS
195P
BNC
Junction Box
PSA30..
PSA30..
PSA30..
EDS-
SET
Insulation fault
Strings
PSA30..

5.4 Connection to a PV system

Risk of electric shock!
On touching live uninsulated conductors, death or serious injury may be caused. For this reason prevent any physical contact with active conductors and follow the rules for working on electrical systems.
Risk of electric shock!
If the PGH186 is connected using terminals L1(+) und L2(–) to a system that is live due to its operation, the terminal must not be disconnected from the protec­tive earth conductor (PE). Otherwise the terminal will be at the dangerous system voltage!
Risk of short circuit!
When the EDS3090PV is connected with test leads without integrated fuses a short circuit may occur due to incorrect wiring. Connect the EDS3090PV with the accompanying test lead with integrated fuses to reduce the risk of a short circuit.
Connect the locating current injector PGH186 as follows:
Legend:
PGH186 Locating current injector AGE185 Coupling device EDS3096PV Equipment for insulation fault location EDS195P Insulation fault locator PSA30.. Measuring clamp (locating current sensor) EDS-SET BNC Tee connector and 2 BNC cables for fault localisation in diode-decoupled systems
EDS309x_D00012_03_M_XXEN/11.2014
29
Page 30
Connecting the locating current injector
For insulation fault location within the junction box, it is essential that the ± cables of a string are ar­ranged in a way that the measuring clamp PSA30… can be put around the cables. Insulation faults in the strings can be localised by means of two measuring clamps connected in par­allel and an EDS-SET. For this purpose, place the measuring clamps on both sides of the module sup­ply conductors in the direction indicated by the arrows.
30
EDS309x_D00012_03_M_XXEN/11.2014
Page 31

6. Operation

DANGER

6.1 Short description of insulation fault location (EDS mode)

6.1.1 Commissioning the PGH18… for locating current injection

1. The PGH18… is to be connected first to PE in the system to be checked, see page 28
2. Then connect the PGH18… to the active conductors
3. Connect device to U
If the locating current I vice and set to EDS=On.

6.1.2 Insulation fault location using EDS195P

1. There must be no conductors in the measuring clamp and the measuring clamp must be sta­tionary during
2. Switch on EDS195P without current transformer using the button
3. Wait for the end of the self test and the message "No CT connected"
4. Set required current transformer type using the button
5. Connect selected current transformer and wait for end of the self-test
6. Fit measuring clamp to PE conductor between PGH18… (IRDH575) and, for example, PE rail to demonstrate that the necessary locating current I
7. Place measuring clamp around the associated active conductors for the related outgoing cir­cuit. Caution! Do not include PE in the cables in the clamp!
8. Read measured value and evaluate. If the response value set has been exceeded, the "ALARM" LED flashes.
Risk of electric shock!
On touching live uninsulated conductors, death or serious injury may be caused. For this reason avoid any contact whatsoever with active conductors on posi­tioning the measuring clamp.
and switch on
S
is to be supplied by an IRDH575, select the EDS-Setup menu item on this de-
L
commissioning
is flowing.
L

6.2 Detailed description of insulation fault location

For information on using the EDS309… without a permanently installed EDS system, see
page 42
For information on using the EDS309… in addition to a permanently installed EDS system, see
page 45
For information on using the EDS309… in diode-decoupled DC systems, see page 49

6.3 Description of a residual current measurement

Using the EDS195P it is also possible to undertake residual current measurements up to a value of 10 A, see page 49.
EDS309x_D00012_03_M_XXEN/11.2014
31
Page 32

6.4 Displays and controls on the PGH18…

PGH186
100mA
M
10mA
25mA
Imax
ON
ON
Us
L1(+)
L2(-)
L3
3(N)AC 0...575V mit/with 500...790V DC 0...504V AGE185 400...960V
1
2
6
7
8
1
3
4
5
Operation
1
2
3
4
5
6
7
ON/OFF switch, switch on or off locating current
Changeover switch for maximum locating current values: 25/10 mA or 2.5/1 mA
Not shown: magnetic strip on rear of housing for fastening to metal items (e.g. switch cabinet)
3 sockets for coupling to system
Socket for PE connection
Indicator LEDs: ON Operation LED
Indication of positive locating current cycle Indication of negative locating current cycle
Fine-wire fuse 100 mA
8
Flush mounted connector for supply voltage
32
EDS309x_D00012_03_M_XXEN/11.2014
Page 33
Operation
EDS195P
ALARM
RESET
HOLD INFO
MENU
ESC
I
Δs
I
Δn
EDS195P
Bender GmbH&CoKG
D-35305 Grünberg
EDS195P
Bender GmbH&CoKG
D-35305 Grünberg
12
1
2
3
4
5
6
7
8
9
10
11
INFO
ESC
MENU
OK

6.5 Displays and controls on the EDS195P

1
2
3
4
5
6
EDS309x_D00012_03_M_XXEN/11.2014
ISOSCAN®
I I
HOLD
RESET
EDS195P
L n
ALARM
INFO
MENU
InI
L
ESC
OK
BNC connection for measuring clamp
LC display, illuminated 3 lines of 16 characters
ALARM LED:
- Flashes if the response value is exceeded
- Illuminates continuously on rectification of the fault, if the fault memory is activated
Button for selecting the current transformer:
- PSA30xx = PSA30… / PSA3165 (suitable for I
- W/WR/WS = W…. / WR…. / WS…. (suitable for I
- PSA33xx = PSA33… (suitable for I
- W/WS-8000 = W….-8000 / WS….-8000 (suitable for I
- WF = WF…. (only suitable for I
Lmax
Lmax
Lmax
Lmax
= 50 mA) = 50 mA) = 5 mA) = 5 mA)
)
Δn
INFO button:
- Device type, date, time, manufacturer
- Software version
- Actual response values I
and IΔn
ΔL
- Status word (setup status) ESC button: Leave a menu function without changing parameters
MENU button: Open the menu Enter button: Accept modified parameter values or selected menu items
33
Page 34
Operation
RESET
HOLD
I
I

EDS195P
BENDER GmbH&CoKG
D-35305 Grünberg
>>>Self test<<< CT in rest pos.!
>> >> >> >>
No CT connected
M
PSA30xx
10
11
12
7
8
9
On/Off button
Button for switching on/off the display lighting
RESET button: delete fault memory Down button: move down in the menu, reduce parameter values
HOLD button: save the measured value Up button: move up in the menu, increase parameter values
Button for selecting the operating mode: L = Insulation fault location in IT systems (EDS mode)
= Residual current measurement in TN-S systems (RCM mode)
I
Δn
Micro USB connection for charging the device's rechargeable battery

6.6 Operating the EDS195P

6.6.1 Switching on and off the device

1. Switch on the device without current transformer using On/Off button. The self-test is started after switching on. If the self-test is completed normally "No CT connected" appears.
2. You can switch off the device by pressing the On-Off button for around 2 s.
Abb. 6.1: Start sequence for the EDS195P
34
EDS309x_D00012_03_M_XXEN/11.2014
Page 35
Operation

6.6.2 Changing the measuring clamp

Two methods can be used to change the measuring clamp.
Changing with EDS195P switched off:
– Disconnect clamp no longer required
– Switch on EDS195P
– Wait for "No CT connected" message
– Set required clamp type
– Connect related clamp
– Wait for end of self-test.
Changing with the EDS195P in operation:
– Disconnect clamp from the device
– Wait for "No CT connected" message
– Set required clamp type
– Connect related clamp
– Wait for end of self-test.

6.6.3 Improved legibility due to display lighting

Press the button at the bottom left to improve the legibility of text and symbols. Switch off the lighting by pressing the button again.
6.6.4 Changing between insulation fault location IΔL and residual current measurement I
Here you can select the measuring function. IΔn for residual current measurement preferably in TN/TT systems. I
for insulation fault location in IT systems.
ΔL
Avoid changing the mode during insulation fault location.
6.6.5 Quickly checking the response values for IΔL and I
Press the INFO button three times to display the actual response values.
operating modes
Δn
Δn

6.6.6 Checking Info menu

The following information appears on the display in succession on pressing the INFO button:
Device name, time, date and manufacturer
Software version with date
Actual response values I
Status information, coded, see page 58
ΔL
and I
Δn
EDS309x_D00012_03_M_XXEN/11.2014
35
Page 36

6.6.7 Significance of the display elements

1
2
3
4
5
7
8
6
I L = mA Anspr. = 5mA
M
PSA30xx
29
The elements shown relate to the EDS mode (IΔL). This mode is used for insulation fault location.
I L = 8mA Resp. = 5mA
MH
Indication of the locating current pulse:
= Positive pulse,
1
2
= Pause or no measurement possible when permanently displayed = Negative pulse
29
= Timer (29…0) shows the duration of a measurement of an outgoing
circuit
Indication of the selected transformer type:
- PSA30xx = PSA30… / PSA3165 (suitable for I
- W/WR/WS = W…. / WR…. / WS…. (suitable for I
- PSA33xx = PSA33… (suitable for I
- W/WS-8000 = W….-8000 / WS….-8000 (suitable for I
- WF = WF…. (only suitable for IΔn)
PSA30xx
Lmax
Lmax
Lmax
Lmax
= 50 mA) = 50 mA) = 5 mA) = 5 mA)
Operation
H = Hold function is activated; measured value indication "frozen"
3
M = Fault memory is activated
4
Loudspeaker symbol visible:
5
The presence of an alarm is also output audibly
Charge state of the rechargeable battery in the steps 0%, 33%, 66%,100%
6
Resp. = Response value IΔL
7
IΔL = Indication of the actual locating current measured
8

6.7 Standard displays on the EDS195P

6.7.1 EDS measurement (IΔL)

6.7.1.1 Standard display if there is no cable to be measured in the clamp
The device is in the EDS mode ( A measured locating current The display shows the timer count (29…0).
I
).
ΔL
I
is not indicated, as there is no conductor in the measuring clamp.
ΔL
36
EDS309x_D00012_03_M_XXEN/11.2014
Page 37
Operation
I L = mA Anspr. = 5mA
M
PSA30xx
I L = mA Anspr. = 5mA
M
PSA30xx
I n = 16mA H1 = 10mA THD = 39%
M
PSA30xx
ALARM
I n = 1.6A Resp. = 100mA
M
PSA30xx
ALARM
6.7.1.2 Standard display for EDS measurement (IΔL) with cable in the clamp
The display is indicating a measured fault current by the change in the polarity of the measuring pulse (
I
of 3 mA. A measurement in progress is indicated
ΔL
) with a pause (- - -) in between.
I L = 3mA Resp. = 5mA
M
PSA30xx
Note that only half the magnitude of the locating current I
generated by the PGH18… in AC systems
L
is indicated by EDS195P. The half-wave rectification used in the PGH18… reduces the value indicat­ed in AC systems to 50 %, in 3AC systems to 67 %.
6.7.1.3 Standard display for measuring faults or pauses between changes in polarity of the
measuring pulse
When no measurement is possible due to low frequency residual currents or because the measuring clamp is not being held still, the display permanently indicates a pause (- - -) at the top right corner. During the evaluation of the measurement the display indicates a pause (- - -) for a short time only.

6.7.2 RCM measurement (IΔn)

6.7.2.1 Standard display for RCM measurement (IΔn) with cable in the clamp
The display is indicating the measured residual current
I
of 16 mA.
Δn
The residual current response value set is 100 mA.
I n = 16mA Resp. = 100mA
M
The following display appears if menu item "2.Settings/7.Harmonics: on" is activated. This setting can only be used for 50 Hz or 60 Hz systems. For the 1st harmonic (fundamental) the display is indicating a measured current of 10 mA as well as a total harmonic distortion THD of 39 %.
PSA30xx

6.8 Alarms during EDS measurement or RCM measurement

If one of the response values set IΔL or IΔn is exceeded, the ALARM LED flashes. If the fault memory M is activated, the ALARM LED continues to illuminate after the removal of the fault. The alarm saved is cleared using the RESET button.
EDS309x_D00012_03_M_XXEN/11.2014
I L = 8mA Resp. = 5mA
M
PSA30xx
Alarm during insulation fault
location (EDS):
LED flashes
Alarm during a residual current
measurement (RCM):
LED flashes
37
Page 38

6.9 Indication of device and measuring errors

Self test error PRESS ->RESET
M
PSA30xx
No CT connected
M
PSA30xx
I L = mA Anspr. = 5mA
M
PSA30xx
Error I
ΔL
M
PSA30xx
The following table explains the error messages that may occur.
Can only occur after the end of the self-test:
- Incorrect current transformer type set
- During the self-test the clamp was: Not stationary Or a residual current was flowing through it Or the PGH locating current was flowing through it
- EDS195P hardware faulty Press the "RESET" button to restart a self test.
No measuring clamp or no measuring current transformer on the measuring input or incorrect transformer type connected Measures: Connect correct measuring clamp or correct measuring current transformer
A permanent display of pause (- - -) indicates no measurement is possible. Steps:
- Hold the measuring clamp still
- Avoid low frequency residual currents
A malfunction has occurred during insulation fault location Possible causes:
- The measuring clamp was not held still.
- There is a low frequency residual current flowing through the measuring clamp that is interfering with the EDS measurement
- There a magnetic field around the measuring clamp that is
interfering with the EDS measurement
- EDS195P hardware faulty
Operation
If the EDS195 can no longer detect the locating current due to system interfer­ence and an existing alarm is therefore cleared, an insulation fault will be detect­ed again at the end of the interference.

6.10 Factory settings EDS195P (state as supplied)

Most of the settings are made on the menu. If this is not the case, the setting is marked with (button).
Operating mode (button): I Current transformer (button): Measuring clamp PSA3052 (for EDS3090 and 3096)
Illumination (button): Off Fault memory: On Buzzer: On Response value I Response value I Response value I System frequency I Measurement of harmonics I
with PSA30…: 5 mA
Δ
L
with PSA33…: 0.5 mA
Δ
L
:100 mA
Δ
n
:50 Hz
Δ
n
:Off
Δ
n
User interface language: English Time: CET
ΔL (EDS mode = insulation fault location)
Measuring clamp PSA3352 (for EDS3091)
38
EDS309x_D00012_03_M_XXEN/11.2014
Page 39
Operation

6.11 Menu structure

The menu structure is shown schematically in the following.
Level 1 Level 2 Level 3
1. Exit
2. Settings
3. System 1. Exit
4. Harmonics 1. Exit
1. Exit
2. I
ΔL ALM: 0.2…10 mA
3. IΔn ALM: 10 mA…10 A
Response value measured locating current IΔL Response value residual current I
4. Memory: on/off
5. Buzzer: on/off
6. Frequ.: 50/60Hz/up to 1kHz
7. Harmonics: on/off
2. Language
Audible alarm Frequency of the system monitored Indication of harmonics and total harmonic distortion THD in %
1. Exit
2. German
3. English
4. French
5. Russian
3. Clock 1. Exit
2. Format: D.M.Y
3. Date
4. Time
4. Contrast: 0…15
2. H1 < 10 mA
3. H2 < 10 mA
.....
9. H8 < 10 mA
Contrast setting for display
This menu item is used only for the indication of harmonics from H1 to H8. To display the harmonic with the greatest amplitude in the standard display with the menu closed, the menu item "7. Harmonics: on/off" on the Set­tings menu is to be activated
or explanation
Δ
n
5. IΔL alarms 1. Exit
Δn logger 1. Exit
6. I
7. Service
EDS309x_D00012_03_M_XXEN/11.2014
2. Entries
Alarm No. 001 No. 002
No. ......
3. Delete 1. Exit
2. Delete Data
2. Entries
3. Change: 10…100 %
4. Overwrite: yes/no
Entry No. 001 No. 002
No. ......
Percentage change from which logging becomes active
Overwrite oldest data record
5. Delete 1. Exit
2. Delete Data
For serv ice only
39
Page 40

6.11.1 Navigating in the menu

MENU
OK
HOLD
RESET
INFO
ESC
- Open the menu using MENU
- Select a menu item or accept a value using OK
- Navigate up or down in the menu
- Increase or reduce values
ESC:
- Return from the last menu item selected
- Discard modified setting without saving

6.11.2 Menu item: Settings

Using this menu item you can access the following parameters for the insulation fault location and for the residual current measurement to:
Set the response value for the locating current I
between 0.2…10 mA. This value range is equally suitable for control circuits (0.2…1 mA) and main circuits (2…10 mA). On the usage of the locating current injector note that the permissible locating current defined for control circuits is I
Set the response value for the residual current I
= 5 mA, while for main circuits it is I
Lmax
between 10 mA and 10 A
Activate or deactivate the fault memory
Activate or deactivate audible signalling of alarms
Set the frequency of the system monitored
Enable the indication of the harmonics to display the current for the harmonic with the greatest
amplitude in the standard display. All harmonics from H1 to H8 can be checked using menu item "4. Harmonics", see also page 41. Note that with harmonics activated only system frequen­cies of 50 Hz and 60 Hz can be selected.
measured with the measuring clamp to
ΔL
= 50 mA.
Lmax
measured with the measuring clamp to
Δn
Operation
Level 1 Level 2 Meaning
2. Settings 1. Exit
ΔL ALM: 0.2…10 mA
2. I
3. IΔn ALM: 10 mA…10 A
Response value measured locating current I Response value residual current I
4. Memory: on/off
5. Buzzer: on/off
6. Frequ.: 50/60Hz/up to 1kHz
7. Harmonics: on/off
Audible alarm Frequency of the system monitored Indication or harmonics and total harmonic distortion THD
Alarms are signalled by the Alarm LED and the buzzer (delivery condition).
40
Δ
L
Δ
n
EDS309x_D00012_03_M_XXEN/11.2014
Page 41
Operation

6.11.3 Menu item: System

Use this menu item to select the language for the user interface and to set the correct date and time. The date format can be changed. You can adjust the quality of the display by adjusting the contrast.
Level 1 Level 2 Level 3 or explanation
3. System 1. Exit
2. Language
1. Exit
2. German
3. English
4. French
5. Russian
3. Clock 1. Exit
2. Format: D.M.Y
3. Date
4. Time
4. Contrast: 0…15
Contrast setting for display

6.11.4 Menu item: Harmonics

This menu item is used only for the indication of harmonics from H1 to H8.
Level 1 Level 2 Meaning
4. Harmonics 1. Exit
2. H1 < 10 mA
3. H2 < 10 mA
.....
9. H8 < 10 mA
This menu item is used only for the indication of har­monics from H1 to H8. To display the harmonics, acti­vate the menu item "2.Setting/7. Harmonics: on/off"

6.11.5 Menu item: IΔL alarms

Using this menu item you can check the alarms recorded automatically during insulation fault loca­tion. The data records are numbered and contain the following information:
The start of the alarm
The end of the alarm
The minimum locating current I
The maximum locating current I
A maximum of 300 data records are saved. The existing data records can be deleted using the menu.
measured
ΔL
measured
ΔL
Level 1 Level 2 Level 3 Meaning
5. IΔL alarms 1. Exit
2. Entries Alarm No. 001
3. Delete 1. Exit
EDS309x_D00012_03_M_XXEN/11.2014
No. 002
No. ......
2. Data delete
Period for the recording and min./ max. values measured for I
Δ
L
41
Page 42
Operation
DANGER
6.11.6 Menu item: I
logger
Δ
n
Using this menu item you can check the measured values recorded automatically during a residual current measurement. The data records are numbered and contain the following information:
The start time for the measurement and the change in the residual current monitored
The residual current I
measured
Δ
n
A maximum of 300 data records are saved. The existing data records can be deleted using the menu.
Level 1 Level 2 Level 3 Meaning
6. IΔn logger 1. Exit
2. Entries Entry No. 001 No. 002
No. ......
3. Change:
10…100 %
4. Overwrite:
yes/no
5. Delete 1. Exit
2. Data delete
Time of the recording and residual current I
Percentage change from which log­ging becomes active
Overwrite oldest data record
measured
Δ
n

6.12 Practical usage

6.12.1 Insulation fault location in a system without a permanently installed EDS system

Risk of electric shock!
On touching live uninsulated conductors, death or serious injury may be caused. For this reason avoid any contact whatsoever with active conductors on con­necting the PGH and positioning the measuring clamp.
The EDS309… is primarily used as a portable insulation fault location system in unearthed IT sys­tems. Once all the instructions in chapter “Considerations prior to use” on page 19 have been fol­lowed, insulation fault location can be started. Proceed as follows during this process:
1. Check whether the system voltage is within the permissible limits. The permissible voltages are stated in the user interface on the PGH18….
2. Connect the locating current injector PGH18… close to the feed, see connection diagram on page 28. During this process follow the general guidelines for working with electrically live sys­tems!
– First connect the PE socket on the PGH18… to the system's PE using the green-yellow wire.
– Then connect the PGH18… to the system to be checked using the connection wires pro-
vided.
Three-phase system Connect sockets L1, L2 and L3 to the system
Single-phase AC or DC Connect sockets L1 and L2 to the system
42
EDS309x_D00012_03_M_XXEN/11.2014
Page 43
Operation
3. Connect the PGH18… to a suitable power supply using the power cable supplied (see name­plate).
4. If there is an insulation monitoring device with an Ohmic internal resistance < 120 kΩ in the IT system to be checked, disconnect it from the system to be checked on all poles. It is not suffi­cient to switch off the power supply to the insulation monitoring device.
5. Set the maximum locating current using the I
switch on the PGH18…. Follow the instruc-
max
tions in chapter “Reduced locating current” on page 22.
6. Switch on the PGH18…. The "ON" LED illuminates and the two
alternately in synchronism with the
test cycle. If there is no activity indicated on the LEDs, check
"" and "" LEDs flash
the supply voltage and the fine-wire fuse that can be accessed from the front panel.
7. Switch on the EDS195P without a current transformer connected by pressing the button. The device undertakes a self-test and outputs the error message "No CT connected" because a current transformer is not connected.
8. Now select the type of measuring clamp or measuring current transformer to be connected using the button. The device undertakes a further self-test and outputs the error message "No CT connected" because a current transformer is not connected
9. Then connect the pre-selected measuring clamp or the pre-selected measuring current trans­former to the EDS195P. The device undertakes a further self-test and is then in the EDS mode. "I
" appears in the first line of the display.
ΔL
10. On handling the measuring clamp note:
– Do not bring measuring clamp into contact with system voltages above the rated insulation
voltage (see nameplate on the measuring clamp with information on measuring category, e.g. CAT III)
– Always keep contact surfaces on measuring clamp's iron core clean.
– Do not use measuring clamp in the immediate vicinity of devices that produce magnetic
fields such as transformers or chokes and also not near adjacent conductors carrying high currents.
– Never disconnect measuring clamp from the EDS195P while it is placed around electrically
live conductors. Otherwise the measuring clamp may be irreparably damaged!
– Aim for the best possible symmetry of the conductors in the measuring clamp. Otherwise
the measuring clamp may go into saturation due to an excessively high load current and cause an alarm I
>10 A.
Δ
n
Keep the measuring clamp still during the measurement!
– During the measurement do not apply any pressure to the clamp limb.
11. Cover the green and yellow lead between PHG18… and earth with the measuring clamp. A measurement process should take no more than 30 seconds. When the EDS195P is ready to take a measurement, the countdown (29…0) at the top right corner of the display starts. If the time has expired and no error has been found, the countdown starts again. During a measure­ment, the EDS195P shows recognized test current signals with pauses in between: i.e. - - - . In the case of a measurement fault, the display permanently indicates pause (- - -). There are 3 reasons for this:
– The insulation fault resistance is too high and cannot be measured by the EDS195P.
– The measuring clamp is not being held still. Hold the clamp still during measurement.
– Low frequency residual currents or magnetic fields in the environment have been superim-
posed on the test current pulse. Avoid these disturbances.
EDS309x_D00012_03_M_XXEN/11.2014
43
Page 44
12. Start the insulation fault location from the main distribution area of the IT system. Place the measuring clamp around all system conductors, but not the PE conductor. During each meas­urement wait one test cycle (approx. 30 seconds). A flashing alarm LED on the EDS195P signals an insulation fault after (from the point of view of the locating current injector) the measuring clamp. It recommended to have the buzzer activated during the search.
13. Now measure along the cable using the EDS195P until the fault is found. During this process move into sub-distribution systems using a star-shaped approach. The location of the fault is found when the locating current in the measuring clamp generated by the PGH18… exceeds as a minimum the response value set on EDS195P.
Possible error messages
Self test error:
– Incorrect current transformer type set
– EDS195P hardware faulty
– Clamp moved while the indication ">>>Self test<<<" was displayed
– An interfering residual current is flowing through the clamp
– There is a PGH locating pulse acting on the clamp
No CT connected:
Measuring clamp or measuring current transformer not connected or faulty.
Error I
(can only be indicated while a measurement is in progress):
ΔL
– Low frequency interference, measurement not possible
– EDS195P hardware faulty
I
>10 A / >1 A:
Δn
There is a residual current > 10 A or >1 A flowing through the measuring clamp. In this case it is not possible to locate the insulation fault on the related outgoing circuit. Residual currents of this magnitude in an IT system can be caused by large system leakage capacitances or multiple insulation faults. It is therefore possible that there is an insulation fault on this outgoing circuit also with this alarm message.
Operation
44
At operating currents < 10 A a measurement can also be made by placing the clamp around only one conductor. At currents > 10 A it may no longer be possi­ble to open the measuring clamp. This risk is particularly apparent in DC systems. If this effect occurs, under no circumstances apply force; this action would irrep­arably damage the measuring clamp. Instead the related system must be shut down. It will then be possible to open the measuring clamp without the need to apply force.
EDS309x_D00012_03_M_XXEN/11.2014
Page 45
Operation
DANGER

6.12.2 Insulation fault location in a system with a permanently installed EDS system

The EDS195P can also be used in a permanently installed EDS system (EDS460/490 or EDS461/491). In a large, complex IT system the main outgoing circuits are often monitored by the permanently in­stalled EDS system. Once the main outgoing circuit affected by an insulation fault is detected, the search is continued from there using the portable EDS195P. During this process the EDS195P uses the locating current pulse from the permanently installed EDS system (IRDH575, PGH47…). The PGH18… is not required for this application. The PGH18… is not included in the items supplied with the EDS3090 and EDS3091. Insulation fault location is therefore only possible in electrically live IT systems. Also follow the operating instruc­tions for the permanently installed EDS system.
Risk of electric shock!
On touching live uninsulated conductors, death or serious injury may be caused. For this reason avoid any contact whatsoever with active conductors on posi­tioning the measuring clamp.
Example: The insulation monitoring device has signalled an insulation fault below its response value and started the permanently installed EDS system. The main outgoing circuit affected by the insula­tion fault has been detected. Proceed as follows for the further insulation fault location:
1. Set the mode of the EDS system to continuous insulation fault location:
– IRDH575: On the "EDS Setup" menu set the "EDS on" mode
– PGH471: Press "Start/Stop" button
2. Switch on the EDS195P without a current transformer connected by pressing the button. The device undertakes a self-test and outputs the error message "No CT connected" because a current transformer is not connected.
3. Now select the type of measuring clamp or measuring current transformer to be connected using the button. The device undertakes a further self-test and outputs the error message "No CT connected" because a current transformer is not connected
4. Then connect the pre-selected measuring clamp or the pre-selected measuring current trans­former to the EDS195P. The device undertakes a further self-test and is then in the EDS mode. "I
ΔL" appears in the first line of the display.
5. On handling measuring clamps note:
– Do not bring measuring clamp into contact with system voltages above the nominal insula-
tion voltage. (See nameplate on the measuring clamp with information on measuring cate­gory, e.g. CAT III)
– Always keep contact surfaces on measuring clamp's iron core clean.
– Do not use measuring clamp in the immediate vicinity of devices that produce magnetic fields
such as transformers or chokes and also not near adjacent conductors carrying high currents.
– Never disconnect measuring clamp from the EDS195P while it is placed around electrically
live conductors. Otherwise the measuring clamp may be irreparably damaged!
– Aim for the best possible symmetry of the conductors in the measuring clamp.
Otherwise the measuring clamp may go into saturation due to an excessively high load cur­rent and cause an alarm I
Keep the measuring clamp still during the measurement!
– During the measurement do not apply any pressure to the clamp limb.
6. Place the measuring clamp around the green-yellow wire between the IRDH575 or PGH47… and earth. If the EDS195P does not react, the insulation fault has an excessively high impedance and cannot be detected. Locating current pulses detected are indicated using the symbol.
>10 A.
Δn
EDS309x_D00012_03_M_XXEN/11.2014
45
Page 46
7. Start the insulation fault location in the outgoing circuit of the IT system already detected as faulty. Place the measuring clamp around all system conductors,
but not the PE conductor
During each measurement wait one test cycle (approx. 30 seconds). A flashing alarm LED on the EDS195P signals an insulation fault after (from the point of view of the locating current injector) the measuring clamp. It recommended to have the buzzer activated during the search.
8. Now measure along the cable using the EDS195P until the insulation fault is found. During this process move into sub-distribution systems using a star-shaped approach. The location of the fault is found when the locating current generated by the IRDH575 or PGH47… in the measur­ing clamp exceeds as a minimum the response value set on EDS195P.
Possible error messages
Self test error:
– Incorrect current transformer type set
– EDS195P hardware faulty
– Clamp moved while the indication ">>>Self test<<<" was displayed
– An interfering residual current is flowing through the clamp
– There is a PGH locating pulse acting on the clamp
No CT connected:
Measuring clamp or measuring current transformer not connected or faulty.
Error IΔL (can only be indicated while a measurement is in progress):
– Low frequency interference, measurement not possible
– EDS195P hardware faulty
IΔn >10 A / >1 A:
There is a residual current > 10 A or > 1 A flowing through the measuring clamp. In this case it is not possible to locate the insulation fault on the related outgoing circuit. Residual currents of this magnitude in an IT system can be caused by large system leakage capacitances or multiple insulation faults. It is therefore possible that there is an insulation fault on this outgoing circuit also with this alarm message.
Operation
.
At operating currents < 10 A a measurement can also be made by placing the clamp around only one conductor. At currents > 10 A it may no longer be possi­ble to open the measuring clamp. This risk is particularly apparent in DC systems. If this effect occurs, under no circumstances apply force; this action would irrep­arably damage the measuring clamp. Instead the related system must be shut down. It will then be possible to open the measuring clamp without the need to apply force.
46
EDS309x_D00012_03_M_XXEN/11.2014
Page 47
Operation
DANGER

6.12.3 Insulation fault location in diode-decoupled DC systems

In diode-decoupled DC systems equalising currents occur in and between the decoupled circuits. The direction and magnitude of these equalising currents is dependent on voltages in the system, the characteristics of the decoupling diodes and the characteristics of the loads. On the usage of the insulation fault location system EDS309… in such systems these equalising cur­rents make themselves apparent and can degrade the accuracy of the measurement. For this reason we recommend the usage of the EDS309… in diode-decoupled systems as shown in the sketch on the next page.
Risk of electric shock!
On touching live uninsulated conductors, death or serious injury may be caused. For this reason avoid any contact whatsoever with active conductors on con­necting the PGH and positioning the measuring clamp.
During this process please note:
Always use two measuring clamps of the same type.
Attention: this clamp type must also be set on the EDS195P.
For this purpose use the EDS195P set (see ordering data, page 59).
Take into account the maximum length of the coax cable of 10 m per measuring clamp.
The usage of two measuring clamps results in a sensitivity loss of around 10 %.
It is imperative both measuring clamps are used such that the direction of the flow of energy
corresponds to the arrow printed on the clamp.
Example: The central insulation monitoring device in a DC system without permanently installed in­sulation fault location system (EDS) has signalled an insulation fault that is below the insulation value that can be located using the EDS system. Once all the instructions from chapter "4. Considerations prior to use" have been followed, fault location in a modified form can be started. Proceed as follows during this process:
1. Read the actual insulation resistance on the insulation monitoring device. If the value read for the insulation resistance is lower than the maximum insulation fault that can be located by the EDS system, two appropriate identical measuring clamps (e.g. 2 x PSA3020 or 2 x PSA3052) are required for the insulation fault location.
2. Switch on the EDS195P without a current transformer by pressing the button. The device undertakes a self-test and outputs the error message "No CT connected".
3. Now select the type of measuring clamp(s) to be connected using the button. The device undertakes a further self-test and outputs the error message "No CT connected" because a cur­rent transformer is not connected
4. Then connect the pre-selected measuring clamp(s) to the EDS195P. The device undertakes a further self-test and is then in the EDS mode. "I
ΔL" appears in the first line of the display
5. Connect the PGH18… to the locating current injection points are shown on page 48.
6. Start the EDS system: Switch on the PGH18…. The "ON" LED illuminates and the two and LEDs flash in synchronism with the test cycle. If there is no activity indicated on the LEDs, check the supply voltage and the fine-wire fuse fitted in the PGH18….
7. Insulation fault location in the system:
– Place a measuring clamp around each of the supply cables to the redundantly supplied
loads. During this process ensure that the clamp is placed around all related load supply cables for a diode-decoupled load.
EDS309x_D00012_03_M_XXEN/11.2014
47
Page 48
– Pay attention to identical directions of flow on the two measuring clamps (see connection
PSA3052
MESSZANGE / CLAM
P
ON PROBE
Datenblatt / Da
t
asheet :
TGH13xx
Durchmesser / Diameter : 52 mm
Art.-N
r
. / Art.-no. : B 980 xxx
PSA3052
MESSZANGE / CLAM
P ON PROBE
Datenblatt / Dat
asheet :
TGH13xx
Durchmesser / Diameter : 52 mm
Art.-Nr. / Art.-no. : B 980 xx
PSA3052
MESSZANGE / CLAM
P ON PROBE
Datenblatt / Da
tasheet :
TGH13xx
Durchmesser / Diameter : 52 mm
Art.-N
r
. /
Art.-no. : B 980 6xx
PGH186
100mA
10 mA
25 mA
Imax
ON
ON
Us
L1(+)
L2(-)
L3
AC/DC
L-
L+
L+
L-
PGH185
S1
Selector switch EDS/IMD
DC main distribution (DC 20-360 V)
Central coupling of the insulation monitoring device (IMD) and the locating current injector PGH185
Us AC 230 V
PSA3052/3020
PSA3052/3020
EDS195P
DC sub distribution
l
max.
= 10 m
l
m
a
x
.
=
1
0
m
L+
L-
Load
Insulation fault
Load
EDS195P
PSA3052/3020
PE
IMD
diagram). For this purpose the measuring clamps are marked with an arrow
Place the two measuring clamps successively and systematically around all parallel outgoing cables for loads. Outgoing cables for loads with an insulation fault are indicated by the flashing alarm LED on the EDS195P. The alarm messages are output in the same way as for an application with a single measuring clamp. For possible error messages see page 44.
Operation
EDS195P
ISOSCAN®
In I
L
HOLD
RESET
ILI
n
ALARM
ESC
INFO
OK
MENU
EDS195P
ILI
n
ISOSCAN®
ALARM
In I
L
ESC
INFO
HOLD
OK
MENU
RESET
Abb. 6.2: Insulation fault location in diode-decoupled DC systems (connection diagram)
48
EDS309x_D00012_03_M_XXEN/11.2014
Page 49
Operation

6.12.4 Usage of the EDS195P as a residual current meter

The EDS195P can be used as a residual current meter up to AC 10 A in TN and TT systems. Residual current measurement is only possible in electrically live systems. The locating current injector PGH18… is not required for this application.
1. Check whether the system voltage is within the permissible limits.
2. Switch on the EDS195P without a current transformer connected by pressing the button. The device undertakes a self-test and outputs the error message "No CT connected" because a current transformer is not connected.
3. Now select the type of measuring clamp or measuring current transformer to be connected using the button. The device undertakes a further self-test and outputs the error message "No CT connected" because a current transformer is not connected
4. Then connect the pre-selected measuring clamp or the pre-selected measuring current trans­former to the EDS195P. The device undertakes a further self-test and is then in the EDS mode. "I
ΔL" appears in the first line of the display.
5. Make the following settings:
– Change to the I
– Set residual current response value using the menu path "2. Settings /3. I
6. On handling measuring clamps note:
– Do not bring measuring clamp into contact with system voltages above the nominal insula-
tion voltage. (See nameplate on the measuring clamp)
– During the measurement place the clamp around all system conductors, but not PE. Do not
place the clamp around screened conductors.
– Always keep contact surfaces on measuring clamp's iron core clean.
– Do not use measuring clamp in the immediate vicinity of devices that produce magnetic
fields such as transformers or chokes and also not near adjacent conductors carrying high currents.
– Never disconnect measuring clamp from the EDS195P while it is placed around electrically
live conductors. Otherwise the measuring clamp may be irreparably damaged!
– Aim for the best possible symmetry of the conductors in the measuring clamp.
Otherwise the measuring clamp may go into saturation due to an excessively high load cur­rent and cause an alarm I
Keep the measuring clamp still or let go of it during the measurement!
– During the measurement do not apply any pressure to the clamp limb.
7. Start the measurement from the main distribution area of the system. Now measure along the cable using the EDS195P until the insulation fault is found. During this process move into sub­distribution systems using a star-shaped approach.
8. EDS195P indicates the residual current at each measuring point. If the residual current is greater than the response value set, the "ALARM" LED illuminates and the measured value is displayed. If the buzzer is activated, there is also an audible signal.
9. For long-term measurements at a point in the system, the fault memory is to be activated in the menu 2.4 (Settings/Memory). In this way it is also possible to find intermittent residual cur­rents provided they are above the response value set. The highest residual current measured is saved.
Δn (RCM mode) function using the related button
Δn ALM:"
Δn >10A.
EDS309x_D00012_03_M_XXEN/11.2014
49
Page 50
Possible error messages
I I

Self test error:
– Incorrect current transformer type set
– EDS195P hardware faulty
– Clamp moved while the indication ">>>Self test<<<" was displayed
– An interfering residual current is flowing through the clamp
– There is a PGH locating pulse acting on the clamp
No CT connected:
Measuring clamp or measuring current transformer not connected or faulty.
Error IΔL (can only be indicated while a measurement is in progress):
– Low frequency interference, measurement not possible
– EDS195P hardware faulty
IΔn >10 A / > 1 A:
There is a residual current > 10 A or >1A flowing through the measuring clamp. In this case it is not possible to locate the insulation fault on the related outgoing circuit. Residual currents of this magnitude in an IT system can be caused by large system leakage capacitances or multiple insulation faults. It is therefore possible that there is an insulation fault on this outgoing circuit also with this alarm message
Operation

6.12.5 Indication of the harmonics during residual current measurement

Using the EDS195P it is also possible to measure harmonics of the fundamental frequencies of 50 or 60 Hz.
1. Switch on the EDS195P by pressing the button.
The device is in the EDS mode. IΔL appears in the first line of the display
2. Check correct setting for the selection of the clamp or current transformer on the display, cor­rect if necessary
3. Now select the measurement type I
4. Then make the following settings:
– Check response value on menu 2.3 (Settings I
– Check system frequency on menu 2.6 (Settings I
– Activate measurement of the harmonics on menu 2.7 (Settings /Harmonics)
– Select the required harmonics on menu 4.
The EDS195P indicates the harmonics of a residual current at each measuring point. If the residual current is greater than the response value set, the "ALARM" LED flashes and the measured value is displayed. If the buzzer is activated, there is also an audible signal. After the activation of the harmonics in menu 2.7, the harmonic with the greatest amplitude and the total harmonic distortion in % can be seen in the standard display with the menu closed.
Δn (RCM mode) using the button
) and change if necessary
Δ
n
) and change if necessary
Δ
n
50
EDS309x_D00012_03_M_XXEN/11.2014
Page 51
Operation
DANGER

6.13 Coupling device AGE185 for higher system voltages

This option is available for the variants EDS3090PG, EDS3090PG-13 and EDS3096PG with the locat­ing current injectors PGH185 and PGH186. The coupling device AGE185 expands the nominal volt­age range of the insulation fault location system EDS309… The AGE185 reduces the losses in the locating current injector PGH18… As a result it makes it possi­ble to connect the PGH18… to nominal system voltages up to AC 790 V or DC 960 V.
Risk of electric shock!
On touching live uninsulated conductors, death or serious injury may be caused. For this reason avoid any contact whatsoever with active conductors on con­necting the PGH or the AGE.
Assembly, connection and placing in operation
Connection and placing in operation only by an electrical technician! It is imperative the existing safety regulations are followed! The ends of the wires from the AGE185 can be connected, as necessary and to suit the local situation, to the system's PE terminal and the PE socket on the PGH186; it is not necessary to take into account the polarity.
Connection diagram
IT System
PE
U
s
PGH186
ON
Imax
25 mA
10 mA
AC/DC
L2(-)
L3
EDS195P
ILI
n
ISOSCAN®
ALARM
In
L
I
ESC
INFO
HOLD
OK
MENU
RESET
TGH13xx
asheet : t
Art.-no. : B 980 6xx
r. /
MESSZANGE / CLAMP ON PROBE
Datenblatt / Da
Durchmesser / Diameter : 52 mm
Art.-N
PSA3052
To the loads
100mA
PGH186
Us
ON
L1(+)
AGE185
EDS195P
Abb. 6.3: Connection diagram EDS309… with AGE185
EDS309x_D00012_03_M_XXEN/11.2014
51
Page 52

6.14 Power supply for the EDS195P

I L = 8mA Resp. = 5mA
MH
PSA30xx
CAUTION
The device is supplied with power using 3 NiMH cells of 1.2 V each
or 3 mignon cells of type LR6 AA of 1.5 V each.
The power supply unit is not allowed to be connected with non-rechargeable batteries
fitted!
On the connection of a power supply unit, there must be 3 correctly functioning rechargeable
batteries in the battery compartment.
Rechargeable battery charging time ≤ 5 h.

6.14.1 Displaying charge state

The display can indicate 4 different charge states: 100 %, 66 %, 33 % and a flashing empty battery symbol.
Operation

6.14.2 Changing batteries

The battery compartment is on the rear of the EDS195P. The settings in the EDS195P are retained on changing the batteries.
1. Undo 2 screws in the cover on the rear, remove cover.
2. Remove old batteries.
3. Fit new batteries in the battery compartment with correct polarity as indicated by the mark­ings.
4. Close cover.

6.14.3 Power supply unit supplied

Risk of incorrect triggering due to wrong measuring values!
Power supply unit influences the measuring accuracy of EDS195P.
Therefore, do not connect the power supply unit during measurements.
A power supply unit with a USB connector and USB cable is included in the items supplied. The primary purpose of the power supply unit supplied is to charge the rechargeable batteries in the EDS195P. See the display on the EDS195P for the charge state of the rechargeable batteries.
52
EDS309x_D00012_03_M_XXEN/11.2014
Page 53

7. Technical specifications

7.1 Technical specifications for the system EDS309…

The technical specifications stated in this section apply to the components PGH18…, EDS195P, AGE185.
Environment/EMC
EMC ................................................................................................................................................................................................................ IEC 61326-2-4
Operating temperature ................................................................................................................................................................................ -10…+ 55 °C
Climatic classes acc. to IEC 60721:
Stationary use (IEC 60721-3-3) ................................................................................................................................. 3K5 (without condensation or icing)
Transport (IEC 60721-3-2) ......................................................................................................................................... 2K3 (without condensation or icing)
Long-term storage (IEC 60721-3-1) ......................................................................................................................... 1K4 (without condensation or icing)
Classification of mechanical conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3) .....................................................................................................................................................................................3M4
Transport (IEC 60721-3-2) ............................................................................................................................................................................................. 2M2
Long-term storage (IEC 60721-3-1) .............................................................................................................................................................................1M3
Other
Operating mode .......................................................................................................................................................................................... Continuous duty
Position in normal use...................................................................................................................................................................................................... Any
Weight EDS309… ................................................................................................................................................................................................ ≤ 7000 g
Weight EDS309… with PSA3165 ....................................................................................................................................................................... ≤ 8500 g
Weight EDS3092 ................................................................................................................
Dimensions, case W x H x D ................................................................................................................................................................ 430 x 340 x 155 mm
................................................................................... ≤ 9000 g

7.2 Technical specifications PGH18…

Insulation coordination according to IEC 60664-1/IEC 60664-3
Rated voltage .......................................................................................................................................................................................................... 500 V AC
Rated surge voltage / degree of pollution ................................................................................................................................................................. 4 kV/3
Nominal system voltage U
PGH183 .........................................................................................................................................................AC 42…460 Hz 20…265 V, DC 20…308 V
PGH185 ................................................................................................................................................ 3AC/AC 42…460 Hz 20…575 V, DC 20…504 V
PGH186 .................................................................................................................................................... 3AC/AC 42…460 Hz 0…575 V, DC 0…504 V
Supply voltage
Supply voltage U Operating range of U
Supply voltage US version -13 ................................................................................................................................................. AC 50…60 Hz 90…132 V
PGH 183, PGH 185:
Power consumption ................................................................................................................................................................................................. ≤ 3 VA
PGH 186:
Power consumption ................................................................................................................................................................................................. ≤ 6 VA
................................................................................................................................................................................ AC 50…60 Hz 230 V
S
................................................................................................................................................................................ 0.85…1.15 x U
S
n
S
EDS309x_D00012_03_M_XXEN/11.2014
53
Page 54
Technical specifications
Locating current
PGH183:
Locating current max., can be selected .................................................................................................................................................................. 1/2.5 mA
PGH185/186:
Locating current max., can be selected .................................................................................................................................................................10/25 mA
PGH183/185/186
Test cycle ............................................................................................................................................................................................................................ 2 s
Pause duration ................................................................................................................................................................................................................... 4 s
Locating voltage
PGH186.......................................................................................................................................................................................................................DC 50 V
Other
Degree of protection of built-in components DIN EN 60529 (VDE 0470-1) ................................................................................................................ IP40
Enclosure material.................................................................................................................................................................................................ABS plastic
Flammability class.................................................................................................................................................................................................... UL94V-0
Weight...................................................................................................................................................................................................................... ≤ 700 g
Dimensions ............................................................................................................................................................................................ 160 x 148 x 81 mm

7.3 Technical specifications EDS195P

( )* = Factory settings
Insulation coordination according to IEC 60664-1/IEC 60664-3
Rated voltage .................................................................................................................................................................................................................. 50 V
Rated surge voltage/degree of pollution ................................................................................................................................................................ 0.8 kV/3
Supply voltage
Power supply U
.................................................................................................................... Rechargeable batteries, batteries or USB power supply unit
S
Rechargeable batteries......................................................................................................................................................................3 x NiMH ≥ 2000 mAh
Operating time (without display lighting).............................................................................................................................................................. ≥ 150 h
Charging time .............................................................................................................................................................................................................. ≤ 5 h
Size................................................................................................................................................................................................................................ AA R6
Batteries....................................................................................................................................................................................................3 x LR6 AA – 1.5 V
USB power supply unit:
Primary ....................................................................................................................................................................................... 100…240 V, 50…60 Hz
Secondary .................................................................................................................................................................................................... DC 5 V, ± 10 %
Power consumption................................................................................................................................................................................................. ≤ 0.5 W
Measuring circuit, insulation fault location
Nominal system voltage .............................................................................................. With uninsulated conductors with measuring clamp up to 600 V
Rated frequency ....................................................................................................................................................................................... DC, 42…2000 Hz
Main circuit (I
Lmax
= 50 mA):
Measuring range ................................................................................................................................................................................................. 2…50 mA
Measuring clamps................................................................................................................................................................. PSA3020, PSA3052, PSA3165
Response sensitivity I
adjustable .................................................................................................................................................... 2… 10 mA (5 mA)*
ΔL
Operating uncertainty ............................................................................................................................................ ±30 % / ±2 mA of the nominal value
Control circuit: (I
Lmax
= 5 mA)
Measuring range ................................................................................................................................................................................................ 0.2…5 mA
Measuring clamps.................................................................................................................................................................................. PSA3320, PSA3352
Response sensitivity I
adjustable ............................................................................................................................................. 0.2…1.0 mA (0.5 mA)*
ΔL
Operating uncertainty 0.2…0.9 mA ................................................................................................................. ±30 % / ± 0.2 mA of the nominal value
Operating uncertainty 1…5 mA .......................................................................................................................... ±30 % / ± 2 mA of the nominal value
54
EDS309x_D00012_03_M_XXEN/11.2014
Page 55
Technical specifications
Measuring circuit, residual current
With measuring clamps ........................................................................................................................................................ PSA3020, PSA3052, PSA3165
Measuring range ........................................................................................................................................................... 5 mA…10 A (crest factor up to 3)
Response sensitivity I
Measuring clamps ................................................................................................................................................................................. PSA3320, PSA3352
Measuring range ............................................................................................................................................................. 2 mA…2 A (crest factor up to 3)
Response sensitivity I
Frequency range ............................................................................................................................................................................................. 42…1000 Hz
Operating uncertainty, 42…60 Hz ........................................................................................................................................................................... ±5 %
Operating uncertainty, 61…1000 Hz ..................................................................................................................................................................... ±20 %
Hysteresis....................................................................................................................................................................................................................... 20 %
Harmonics, indication can be disabled ................................................................................................................................................. 1st to 8th harmonic
Inputs
Connection for measuring clamp........................................................................................................................................................................ BNC socket
Connection for power supply unit (DC 5 V) ..................................................................................................................................................... μUSB socket
Display
LCD............................................................................................................................................................... 3 x 16 characters, illumination can be enabled
LED ............................................................................................................................................................................................................................... Alarm
Other
Degree of protection of built-in components DIN EN 60529 (VDE 0470-1) ................................................................................................................ IP40
Protective class according to IEC 60947-1, DIN EN 60947-1 (VDE 0660-100)....................................................................................................... Class III
Enclosure material ............................................................................................................................................................................................... ABS plastic
Flammability class ................................................................................................................................................................................................... UL94V-0
Weight ...................................................................................................................................................................................................................... ≤ 350 g
Software version .................................................................................................................................................................................................. D399 V2.0
Dimensions WxHxD.................................................................................................................................................................................. 84 x 197 x 30 mm
adjustable........................................................................................................................................... 10 mA…10 A (100 mA)*
Δn
adjustable............................................................................................................................................... 5 mA…1 A (100 mA)*
Δn

7.4 Technical specifications measuring clamps

Electrical safety
Standard .................................................................................................................................................................................................... IEC 61010-2-030
Degree of pollution.............................................................................................................................................................................................................. 2
System class......................................................................................................................................................................................................................... III
Operating voltage......................................................................................................................................................................................................... 600 V
Nominal insulation voltage ........................................................................................................................................ AC 600 V CAT III or AC 300 V CAT IV
Transformer ratio
PSA30… ........................................................................................................................................................................................................... 10 A/10 mA
PSA33… ............................................................................................................................................................................................................ 1 A/0.1 mA
PSA3165 ........................................................................................................................................................................................................... 10 A/10 mA
Other
Degree of protection of built-in components DIN EN 60529 (VDE 0470-1) ............................................................................................................... IP40
Protective class according to IEC 60947-1, DIN EN 60947-1 (VDE 0660-100)....................................................................................................... Class III
Measurement output ................................................................................................................................................................................... BNC connector
Dimensions PSA3052 / 3352 ................................................................................................................................................................ 216 x 111 x 45 mm
Dimensions PSA3020 / 3320 .................................................................................................................................................................. 135 x 65 x 30 mm
Dimensions PSA3165 ............................................................................................................................................................................ 285 x 179 x 45 mm
Permissible cable diameter PSA3052 / 3352 ........................................................................................................................................................... 52 mm
Permissible cable diameter PSA3020 / 3320 .....................................................................................
Permissible cable diameter PSA3165 .................................................................................................................................................................... 115 mm
Weight PSA3052 / 3352 ......................................................................................................................................................................................... ≤ 700 g
Weight PSA3020 / 3320 ......................................................................................................................................................................................... ≤ 300 g
Weight PSA3165 ................................................................................................................................................................................................... ≤ 1300 g
...................................................................... 20 mm
EDS309x_D00012_03_M_XXEN/11.2014
55
Page 56
Technical specifications

7.5 Technical specifications AGE185

Insulation co-ordination according to IEC 60664-1
Rated insulation voltage ...................................................................................................................................................................................... AC 1000 V
Rated impulse voltage/degree of pollution ............................................................................................................................................................... 4 kV/3
Nominal system voltage U
.......................................................................................................... 3AC/AC 42…460 Hz, 500…790 V, DC 400…960 V
n
Other
Degree of protection of built-in components DIN EN 60529 (VDE 0470-1) ................................................................................................................ IP30
Connection type/wire: ................................................................................... Safety laboratory connectors with green-yellow connection wire 1 mm
Weight ..................................................................................................................................................................................................................... ≤ 200 g
Dimensions WxHxD: ............................................................................................................................................................................... 88.5 x 42 x 21 mm

7.6 Standards

Observe the applicable national and international standards. The series EDS309… complies with the standards:
DIN VDE 0100-410 (VDE 0100-410)
Low-voltage electrical installations – Part 4-41: Protection for safety – Protection against electric shock (IEC 60364-4-41, modified); German version HD 60364-4-41
DIN EN 61557-9
Electrical safety in low voltage distribution systems up to 1000 V a.c. and 1500 V d.c. – Equipment for testing, measuring or monitoring of protective measures - Part 9: Equipment for insulation fault location in IT systems (IEC 61557-9); German version EN 61557-9
DIN EN 61010-1; VDE 0411-1
Safety requirements for electrical equipment for measurement, control and laboratory use – Part 1: General requirements (IEC 61010-1); German version EN 61010-1
2
56
EDS309x_D00012_03_M_XXEN/11.2014
Page 57
Technical specifications
430
310
340
145
155
ca. 1950
88.5
ca. 450
42
21

7.7 Dimension diagrams

All dimensions are given in mm.
Aluminium case
AGE185
EDS309x_D00012_03_M_XXEN/11.2014
57
Page 58
Technical specifications
0500010000EE N010P0024001609ABCD
IdL ALM [µA]
Idn ALM [mA]
CT type p -> PSA30xx P -> PSA33xx w->W/WR/WS W -> W/WR-8000 F -> WF...
Fault memory E->on A -> off
Buzzer: E->on A -> off
Idn Data logger Overwrite J->Yes N->No
Idn Data logger Change [%]
L of the CT
[H]
Rcu of the CT
[Ohm]
LCD contrast
Error Code: Output in hex format, binary coded

7.8 Status word

The status word can be checked by pressing the "INFO" button several times. This word contains the current configuration and provides an error code if there is a device error.
58
EDS309x_D00012_03_M_XXEN/11.2014
Page 59
Technical specifications
Type Supply voltage Nominal voltage Art.-No.
Insulation fault
locator
Locating current
injector
Measuring
clamps 20 mm
Measuring
clamps
52 mm
EDS3090 EDS195P PSA3020 PSA3052 B91082026
EDS3090PG EDS195P PGH185 PSA3020 PSA3052 AC 50...60 Hz, 230 V B91082021
EDS3090PG-13 EDS195P PGH185-13 PSA3020 PSA3052 AC 50...60 Hz, 90…132 V B91082022
EDS3091 EDS195P PSA3320 PSA3352 B91082027
EDS3091PG EDS195P PGH183 PSA3320 PSA3352 AC 50...60 Hz, 230 V B91082023
EDS3091PG-13 EDS195P PGH183-13 PSA3320 PSA3352 AC 50...60 Hz, 90…132 V B91082024
PGH183 PSA3320 PSA3352 AC 50...60 Hz, 230 V
AC 42...460 Hz, 20...265 V
und DC 20...308 V
PGH185 PSA3020 PSA3052 AC 50...60 Hz, 230 V
AC 42...460 Hz, 20...575 V
und DC 20...504 V
EDS3096PG EDS195P PGH186 PSA3020 PSA3052 AC 50...60 Hz, 230 V B91082025
EDS3096PG-13 EDS195P PGH186-13 PSA3020 PSA3052 AC 50...60 Hz, 90…132 V B91082029
PSA3165
B980852
AGE185
AC 42...460 Hz, 500...790 V,
DC 400...960 V
B980305
Adapter cable
BNC-PS2
B91082045
EDS-SET B91082007
Plug power
supply with USB
connector
A167054
DC 5 V for external supply of the EDS195P via µUSB connector
Measuring clamp 115 mm for EDS3090... and EDS3096...
AC 42...460 Hz, 20...575 V
und DC 20...504 V
AC 42...460 Hz, 20...265 V
und DC 20...308 V
EDS3092PG
AC 42...460 Hz, 0...575 V
und DC 0...504 V
EDS195P B91082030
Items supplied
Optional Accessories
BNC T-piece and 2 BNC cables for fault location in diode-decoupled systems
Coupling device for increasing the voltage range of the PGH185/186
Adapter cable for operating a WF current transformer on the EDS195P
Type Supply voltage Nominal voltage Art.-No.
,QVXODWLRQIDXOW
ORFDWRU
/RFDWLQJFXUUHQW
LQMHFWRU
0HDVXULQJ
FODPSVPP
0HDVXULQJ
FODPSV
PP
('6 ('63 36$ 36$ %
('63* ('63 3*+ 36$ 36$ $&+]9 %
('63* ('63 3*+ 36$ 36$ $&+]«9 %
('6 ('63 36$ 36$ %
('63* ('63 3*+ 36$ 36$ $&+]9 %
('63* ('63 3*+ 36$ 36$ $&+]«9 %
3*+ 36$ 36$ $&+]9
$&+]9
XQG'&9
3*+ 36$ 36$ $&+]9
$&+]9
XQG'&9
('63* ('63 3*+ 36$ 36$ $&+]9 %
('63* ('63 3*+ 36$ 36$ $&+]«9 %
('639 ('63 3*+ ± [36$ $&+]9 %
36$
%
$*(
$&+]9
'&9
%
$GDSWHUFDEOH
%1&36
%
('66(7 %
3OXJSRZHU
VXSSO\ZLWK86%
FRQQHFWRU
$
%
Items supplied
Optional Accessories
%1&
7HHFRQQHFWRUDQG%1&FDEOHVIRUIDXOWORFDWLRQLQGLRGHGHFRXSOHGV\VWHPV
&RXSOLQJGHYLFHIRULQFUHDVLQJWKHYROWDJHUDQJHRIWKH3*+
$GDSWHUFDEOHIRURSHUDWLQJD:)FXUUHQWWUDQVIRUPHURQWKH('63
'&9IRUH[WHUQDOVXSSO\RIWKH('63YLD86%FRQQHFWRU
0HDVXULQJFODPSPPIRU('6DQG('6
$&+]9
XQG'&9
$&+]9
XQG'&9
('63* ('63
$&+]9
XQG'&9

7.9 Ordering data including accessories

EDS309x_D00012_03_M_XXEN/11.2014
59
Page 60

7.10 Component list

Device type
Aluminium case with carrying handle
Operating manual
Insulation fault locator
Clamping connector on 4 mm
Adapter BNC/4mm connector for curr. transform.
Adapter BNC-PS2 for WF-CT,
optional
Plug power supply for EDS195P
Locating current injector
Supply cable for PGH18...
Safety measuring cable, black
Safety measuring cable, green/yellow
Safety claw grip, black
Safety claw grip, green/yellow
Coupling device,
optional
(EDS3096PV only: in the scope of delivery)
Measuring clamps 20 mm
Measuring clamps 52 mm
Measuring clamps 115 mm,
optional
EDS-Set,
optional
EDS3090 1 1 EDS195P 1111 PSA3020 PSA3052 PSA3165 1
EDS3090PG 1 1 EDS195P 1111 PGH185 13131AGE185 PSA3020 PSA3052 PSA3165 1
EDS3090PG-13 1 1 EDS195P 1111PGH185-13 13131AGE185 PSA3020 PSA3052 PSA3165 1
EDS3091 1 1 EDS195P 1111 PSA3320 PSA3352 1
EDS3091PG 1 1 EDS195P 1111 PGH183 13131 PSA3320 PSA3352 1
EDS3091PG-13 1 1 EDS195P 1111PGH183-13 13131 PSA3320 PSA3352 1
EDS3096PG 1 1 EDS195P 1111 PGH186 13131AGE185 PSA3020 PSA3052 PSA3165 1
EDS3096PG-13 1 1 EDS195P 1111PGH186-13 13131AGE185 PSA3020 PSA3052 PSA3165 1
211
PSA3320
PSA3020
PSA3352
PSA3052
11 26261
PGH183
PGH185
Components EDS309...
EDS195P with Accessories PGH18... with accessories for Measuring clamps
EDS3092PG 1 1 EDS195P
Technical specifications
60
EDS309x_D00012_03_M_XXEN/11.2014
Page 61

8. Frequently Asked Questions

The ISOMETER® indicates an insulation fault but this fault cannot be located using the
EDS309…. What could cause this problem?
– Individual outgoing circuits in the IT system monitored may be earthed. Check all outgoing
circuits for unintentional earthing. The N conductor for the transformer that supplies the IT system must also not be earthed.
– There may not be any locating current flowing. Check the earth connection on the locating
current injector PGH18…, IRDH575 for correct connection.
– The PE conductor may have been unintentionally included in the cables in the measuring
clamp or the measuring current transformer.
EDS195P displays the error message "No CT connected". What could cause this problem?
– A measuring clamp is not connected or it is faulty.
– A measuring clamp or a measuring current transformer of the incorrect type has been con-
nected to the EDS195P, see table on page 33.
In case of residual current measurement (I
ard display. What could cause this problem?
– The menu item "2. Settings/ 7. Harmonics:" is not activated.
) the harmonic H… does not appear in the stand-
Δn
EDS309x_D00012_03_M_XXEN/11.2014
61
Page 62
Frequently Asked Questions
62
EDS309x_D00012_03_M_XXEN/11.2014
Page 63

INDEX

A
Accessories
13
- optional
51
AGE185 Alarm is also output audibly
33
Alarm LED Alarms during EDS measurement or RCM
measurement
B
Buttons on the EDS195P 33
C
Cables
- screened Characteristics, response sensitivity Charge state of the rechargeable battery
36 Checking Info menu Checking the actual response values
35 Checking the device type Checking the software version Clamp change Clamp selection button Component list Connecting the locating current injector
42 Connection for external power supply unit
34 Connection to an IT system Coupling device AGE185
15
35
60
D
Deleting fault memory 34 Device and measuring errors Device-specific safety instructions Diode-decoupled DC system Disconnecting insulation monitoring de-
27
vice Display lighting Displaying harmonics Down button 34
34
36, 39
37
23
35
33,
33
33
33, 36
28, 29
51
38
9
31, 47
37
40
E
EDS mode 14 EDS195P
- controls
33
- Settings
- System
Menu structure
41
39
N
F
Factory settings 38 Fault circuit Fault memory M is activated Frequently Asked Questions
15
36
61
H
HOLD button 34 Hold function activated
I
Indication of the locating current pulse 36 INFO button Insulation fault location
Insulation fault locator 14 Intended use
58
- in a system without a permanently installed EDS system
- in diode-decoupled DC systems
- with permanently installed EDS sys-
45
tem
L
Leakage currents 17 Locating current Locating current limiting
36
42
47
9
15
22
M
Malfunction 38 Measuring clamps
43
- handling
Measuring current transformers
- commercially available
Measuring harmonics Measuring residual current Menu item
- Harmonics
- IΔL alarms
- IΔn logger
41 41 42
13
50
14, 49
Navigating in the menu on the EDS195P
40
O
Opening the menu 33 Operating mode button Operating principle Operating the EDS195P Ordering data Outline drawings
34
15
34
59
57
P
Permanently installed EDS system 31 PGH18...
32
- controls
22
PLC Power supply for the EDS195P Practical usage
42
52
Q
Quick check on the response values 35
R
RCM mode
18
- function
Rechargeable batteries 54 Rechargeable battery
- changing Reduced locating current RESET button Residual currents
- path Response characteristics for control circuits
25
Response characteristics for main circuits
23
52
22
34
17
S
Saving the measured value using HOLD 34
EDS309x_D00012_03_M_XXEN/11.2014
63
Page 64
Selecting the current transformer 33 Selecting the operating mode Setting language Settings Significance of the display elements Standard display for EDS measurement Standard displays on the EDS195P Standards Status word Switch on-off System components Systems
- electrically isolated
39
40
56
58
34
34
36
36
11
27
T
Technical specifications
56
- AGE185
54
- EDS195P
- measuring clamps
- PGH18...
16
Test cycle Type list EDS309...
55
53
12
INDEX
37
U
Up button 34 USB power supply unit
54
64
EDS309x_D00012_03_M_XXEN/11.2014
Page 65
Page 66
Page 67
Page 68
Bender GmbH & Co. KG
Londorfer Str. 65 • 35305 Grünberg • Germany Postfach 1161 • 35301 Grünberg • Germany
Tel.: +49 6401 807-0 Fax: +49 6401 807-259
E-Mail: info@bender.de Web: http://www.bender.de
Loading...