4.2Installing the device ............................................................................................................. 17
4.2.1 Essential information on mounting ............................................................................... 17
4.2.2 Type of installation ............................................................................................................... 18
4.2.3 Practice ..................................................................................................................................... 18
4.3Connection of the device ................................................................................................... 20
4.3.1 Overview of the bus device interfaces .......................................................................... 20
4.3.2 DC 24 V power supply ........................................................................................................ 21
INDEX ......................................................................................................................... 167
8
CP700_D00005_02_M_XXEN/06.2014
1. Making effective use of this document
DANGER
WARNING
CAUTION
1.1 How to use this manual
This operating manual will concern qualified experts in electrical engineering and communication technology!
To make it easier for you to understand and revisit certain sections of text and instructions in the
manual, we have used symbols to identify important instructions and information. The meaning of
these symbols is explained below:
The signal word indicates that there is a high risk danger that will result in electrocution or serious injury if not avoided.
This signal word means that there is a medium risk of danger that can lead to
death or serious injury, if not avoided.
This signal word indicates a low level risk that can result in minor or moderate
injury or damage to property if not avoided.
This symbol denotes information intended to assist the user
to make optimum use of the product.
1.2 Quick start
Connection of the CP700
If you are familiar with the installation and connection of electrical devices as well as networking,
particularly with Ethernet, you can start right away with the wiring diagram on "Connection of the
device" on page 20.
Using the web user interface
You can easily access the CP700 using a standard web browser. For details refer to page 35.
Using the Modbus/TCP functions
Information about this complex field can be found as of page 121.
CP700_D00005_02_M_XXEN/06.2014
9
Making effective use of this document
10
CP700_D00005_02_M_XXEN/06.2014
2. Safety instructions
DANGER
CAUTION
2.1 Work activities on electrical installations
Risk of fatal injury from electric shock
Any work on electrical installations which is not carried out properly can lead to
death and injury!
► Only skilled persons are permitted to carry out the work necessary to
install, commission and run a device or system.
Compliance with applicable regulations governing work on electrical installations, and with the
regulations derived from and associated with them, is mandatory. EN 50110 is of particular
importance in this regard.
If the device is being used in a location outside the Federal Republic of Germany, the applicable
local standards and regulations must be complied with. European standard EN 50110 can be
used as a guide.
2.2 Intended use
The Condition Monitor CP700 connects the following devices to Ethernet TCP/IP networks:
Devices on the Bender internal serial BMS bus
Bender universal measuring devices PEM… to Modbus/RTU or Modbus/TCP.
The CP700 converts alarms, measured values and statuses into Modbus/TCP protocols and HTTP.
That allows connection to Modbus/TCP networks as well as visualisation and evaluation using standard web browsers with Silverlight
TM
plugin.
The CP700 has been designed, developed and produced for normal use in the industrial sector. The
CP700 has not been designed for use bearing high risks and dangers, which can result in death, injury, serious physical harm or any other loss unless exceptionally high safety measures are ensured.
In particular, its application for the monitoring of nuclear reactions in nuclear power stations, monitoring of flight control systems, for air traffic control, control of means of mass transport, medical life
support systems, and weapon system control involve these risks.
CP700_D00005_02_M_XXEN/06.2014
The device is only suitable for use in the industrial sector. The emissions of the device may exceed the permissible limits for residential, business or commercial areas or small companies.
The CP700 is not intended for use on smartphones or
tablet PCs.
11
Safety instructions
CAUTION
2.3 Address setting and termination
In order to ensure proper functioning of the Condition Monitor CP700, correct address assignment
and termination of the connected bus systems according to their specification is of utmost importance.
Assigning addresses that are already used by existing devices on the bus systems
concerned may cause serious malfunctions.
► Ensure correct address setting and termination of the CP700.
2.4 Delivery conditions, guarantee, warranty and liability
The conditions of sale and delivery set out by Bender apply.
Conditions of sale and delivery can be obtained from Bender in printed or electronic format.
The five year guarantee "5forU" does not include parts subject to wear, such as
the touch screen and the battery.
12
CP700_D00005_02_M_XXEN/06.2014
3. Product description
3.1 Scope of supply
You will receive:
The CP700
This operating manual as pdf file in the device memory,
accessible via the web user interface under "Tools" > "Manual"
A short operating instruction
A pluggable screw clamp for the voltage supply
Two RS-485 cables for the connection to the BMS bus and the Modbus/RTU, 2 m
Two terminating resistors each for BMS bus and Modbus/RTU (bus termination set)
Four mounting brackets for panel mounting
3.2 Device features
Condition Monitor for Bender BMS devices and universal measuring devices
7“ TFT WVGA Colour Display
Analogue resistive touch screen
Small mounting depth
Fanless operation
Integrated gateway to Ethernet (TCP/IP), 10/100/1000 Mbit/s
Remote access via LAN, WAN or Internet
Support of devices connected to the internal bus via Modbus/RTU or Modbus/TCP
Access to all devices connected to the BMS bus using the web server
Can be operated on Modbus/RTU
History memory for 1000 entries
12 data loggers, freely configurable with 1000 entries each
3.3 Possible applications
Clearly presented information about the status of devices and systems via 7“ touch screen
Specific system overview according to individual system description
Display und visualisation of device and system statuses via web browser
Selective e-mail notification to various user groups in the event of alarms
Support of professional visualisation programs
Observing and analysing of compatible Bender products (universal measuring devices, RCMS,
Isometer, EDS systems)
Parameter setting for devices, storing, documentation and restoring of parameters in a clear
and practice-oriented manner
Remote diagnosis, remote maintenance
CP700_D00005_02_M_XXEN/06.2014
13
Product description
Condition
Monitor
CP700
PEM..5
PEM..3, PEM..5*
Modbus/RTU
Modbus/TCP
BMS-Bus
PC
Ethernet/TCP/IP
3.4 Description of function
3.4.1Interfaces
The CP700 communicates with the associated devices via three different interfaces:
BMS bus (RS-485) for Bender systems such as EDS46x/49x, RCMS46x/49x and MEDICS. The
CP700 can be operated as master or slave. With the CP700 in master mode, requests can be
answered faster. The CP700 can only be operated on the internal BMS bus.
Modbus/RTU (RS-485) CP700 in master mode for Bender universal measuring devices PEM..3
and also PEM..5 with reduced functionality (*).
Modbus/TCP Ethernet) for Bender universal measuring devices PEM..5
The CP700 can usually be integrated into existing LAN structures, but can also be operated on a single PC via Ethernet/TCP/IP. The CP700 can also be used as master for Bender BMS devices and/or universal measuring devices without being connected to a PC.
3.4.2Process image
Using the information from communication with the assigned devices, the CP700 creates and saves
a process image. This process image contains all alarms, status information and measured values of
the associated devices.
The CP700 combines the information of three different interfaces and makes it available for:
indication on the integrated touch screen
the operation of a PC via the web user interface
the transmission to external visualisation programs or PLCs via Modbus/TCP.
The CP700 provides a uniform user interface for the devices associated via different interfaces (max.
247 devices). In order to be able to identify each individual device, one individual address is available
for each device on this interface. BMS and Modbus/RTU devices receive the appropriate address for
their interface. A virtual address is assigned to Modbus/TCP devices.
3.4.3CP700-compatible devices
For an up-to-date list of the Bender BMS devices compatible with CP700 and the universal measuring
devices PEM…. refer to:
http://www.bender-de.com/en/products/system-components/cp700-compatible-devices.html
14
CP700_D00005_02_M_XXEN/06.2014
Product description
3.4.4Functions available via touch screen
Display of current alarm messages including help texts
Bus overview of the assigned devices. Indication of alarm and measured values. Indication of the
interfaces of the devices in use. In case of universal measuring devices, also the indication of the
harmonics in tabular form or as a chart. Waveform recorder and graphical representation of measuring values (bar graph, phasor diagram, power triangle).
Interface settings with password protection
Operating language, selectable
3.4.5Functions available via the web user interface
The device utilises an integrated web server which can be used to display data in a convenient way
on any PC by means of a web browser and Silverlight
In addition, it provides a Modbus/TCP server which converts data of the associated devices for a
Modbus client. Also, the CP700 contains an FTP server for file access. Functions available via the web
user interface are:
Bus overview of the associated devices (max. 247 devices).
– Indication of alarm and measured values.
– Indication of the interfaces of the devices in use.
– In case of universal measuring devices, also the indication of the harmonics in tabular form
or as a chart. Waveform recorder and graphical representation of measuring values (bar
graph, phasor diagram, power triangle).
– Parameter setting
– Device failure monitoring
– The "Backup/Report" function saves measured values and settings. Saved settings from pre-
vious configurations can be compared with the current settings made on the CP700. The
saved settings can be reloaded into the CP700.
– Assignment of individual texts for devices, measuring points (channels) and alarms.
– E-mail notifications to different user groups according to a time controlled schedule in the
event of alarms and system faults. The sender's e-mail address can be entered.
– Display of virtual devices. A virtual "measuring point" is obtained by evaluating "real" meas-
ured values of devices connected to the CP700 logically or numerically.
Manage Modbus devices
– Adding/deleting devices to/from the bus overview.
– Creating a template with selected measured values
Visualisation
– Fast and simple visualisation without any programming. Measured values or alarms can be
displayed in front of a graphic (system diagram, room plan).
– Displaying an overview page. Click to jump to another view. Return to the overview page.
From an external application (e.g. visualisation software) commands can be sent to BMS devices.
The "Modbus control commands" menu provides Modbus control commands for selected BMS
commands. These commands can be copied to the clipboard of the PC and then included in the
programming for external application.
A graphical representation for the CP700 data logger and compatible Bender devices is avail-
able. The time axis can be varied to view different periods.
TM
plug-in.
CP700_D00005_02_M_XXEN/06.2014
15
Product description
System visualisation: Displaying several gateways (COM460IP, CP700) on one website. Display-
ing common alarms of the devices. Clicking on a device being displayed will open its web user
interface.
Displaying the CP700 operating manual
3.5 Software products used
MIT license (http://opensource.org/licenses/mit-license.php)
If you are familiar with the configuration of computer networks, you can carry
out the connection of the CP700 yourself. Otherwise please contact your EDP
administrator!
4.1 Preliminary considerations
1. Have all the questions as regards the installation been answered by the technician responsible
for the installation?
2. Do you know the BMS address to be set?
Can CP700 be operated as the master (BMS address 1)? If apart from the CP700, an alarm indicator and test combination MK800 is connected to the internal bus, the CP700 must not have
address 1 (Master).
You will find more detailed information on the BMS topic, in particular about the wiring of bus
devices, in the separate document "BMS bus". You can download the document from the
download area of the website www.bender.de.
3. Does the computer network comprise a DHCP server?
Otherwise, the network data such as the IP address and netmask allocated by the person
responsible for the electrical installation have to be set manually.
4. Ask for the IP address of the NTP server, which is required for automatic time setting.
5. Are suitable PC hardware and software available for commissioning?
Minimum system requirements: 1.6-GHz prozessor/512 MB RAM/Windows XP/Vista/7/web
browser with Microsoft Silverlight
System requirements (recommended): Dual-Core processor/1024 MB RAM/
Windows XP/Vista/7/web browser with Microsoft Silverlight
For initial connection, the basic configuration of the CP700 is to be undertaken outside the installation, depending on the specific situation.
TM
(version 5.0 or higher).
TM
(version 5.0 and higher)
4.2 Installing the device
4.2.1Essential information on mounting
Mounting is to be carried out with suitable equipment and tools according to the documenta-
tion.
The device must only be installed by appropriately qualified personnel in de-energised state.
Disconnect the switchboard cabinet from the power supply and protect the system against
accidental switch-on.
The general safety conditions as well as the prevailing national accident prevention regulations
are adhered to. Electrical installation is to be carried out according to all applicable local laws
(e.g. wire cross section, protection, PE connection).
The climatic conditions must be complied with. The device is only permitted to be used in
enclosed rooms. The device must not be exposed to direct sunlight.
CP700_D00005_02_M_XXEN/06.2014
17
Installation, connection and commissioning
The device must be installed on a flat surface. While tightening the screws, irregularities may
damage the display.
The ventilation holes must not be covered.
When installing the device, the permissible mounting positions are to be observed.
Take into consideration that the wall or the sheet metal of the switchboard cabinet can hold
four times the total weight of the device.
When connecting the cables it is essential to note the bending radius.
The device should be positioned in such a way that it is visible for the user and that reflexions
on the screen are avoided as far as possible.
4.2.2Type of installation
The CP700 is preferably installed into consoles and control panel doors using the mounting brackets
supplied with the device. Strength of the material to be clamped: minimum 2 mm, maximum 6 mm.
4.2.3Practice
1. Insert the device frontally into the prepared, plane and smooth installation cut-out. The dimensions for the installation cut-outs can be found on page 161.
2. Attach the mounting brackets to the CP700. For this purpose, insert all mounting brackets into
the slots (marked with orange circles) at the CP700 and slide them down.
18
CP700_D00005_02_M_XXEN/06.2014
Installation, connection and commissioning
3. Fix the mounting brackets to the wall resp. to the sheet metal of the switchboard cabinet by
tightening the screws using a large flat-tip screwdriver. A tightening torque of approx. 0.5 Nm
is recommended.
CP700_D00005_02_M_XXEN/06.2014
19
4.3 Connection of the device
15
910
234
678
4.3.1Overview of the bus device interfaces
Installation, connection and commissioning
Key
Modbus/RTU interface. (cable included in the scope of delivery)
1
Switch for terminating resistor/bus bias voltage for Modbus/RTU interface.
2
BMS bus (Bender measuring device interface, cable included in the scope of delivery)
3
Switch for BMS bus termination/bus bias voltage.
4
USB interface, is not used
5
Connection to the supply voltage,
6
"see chapter "DC 24 V power supply" on page 21
Functional earth, see chapter "Earthing" on page 21
7
USB interfaces, are not used
8
Ethernet 10/100/1000, RJ45 socket for connection to a personal computer or to the local
9
network (hub, switch, router)
RS-232 interface, is not used
10
Details on the items 2 and 4:
"Terminating resistor/bus bias voltage" switch for Modbus/RTU interface:
Communication
mode
MASTERleftactivatedon
Switch position
Terminating resistor/
bus bias voltage
LED
"Terminating resistor/bus bias voltage" switch for BMS interface.
Communication
mode
MASTERleftactivatedon
Slaverightdeactivatedoff
Switch position
Terminating resistor/
bus bias voltage
20
LED
CP700_D00005_02_M_XXEN/06.2014
Installation, connection and commissioning
1 2 3
CAUTION
4.3.2 DC 24 V power supply
The 3-pole plug required for the connection of the power supply is included in the scope of delivery.
The pin assignment is shown in the following table or is printed on the enclosure. The supply voltage
is internally protected by a permanently soldered fuse (10 A, fast-acting), so that in case of overload
(replacement of the fuse required) or wrong connection of the supply voltage the device will not be
damaged. If the fuse is damaged due to a fault, the device has to be returned to Bender for repair.
PinDescription
1 +
2 Functional earth
3-
Recommended power supply units:
Material
number/Type
0PS1025.2 B&R DC 24 V power supply unit, 2.5 A,
0PS1020.0 B&R DC 24 V power supply unit, 2 A,
1SVR427044R0200/
CP-D 24/2.5
EAN:
4016779661188
Manu-
facturer
DIN rail mounting/wall mounting
ABBPower supply unit
In: AC 100…240 V Out: DC 24 V/2.5 A,
Description
input AC 100…240 V,
WxHxD: 72 x 90 x 61 mm
input AC 100…240 V,
DIN rail mounting
WxHxD: 45 x 99 x 107 mm
DIN rail mounting
WxHxD: 71 x 91 x 57.5 mm
4.3.3Earthing
Connect the functional earth (Pin 2) to the earth connection (e.g. switchboard
cabinet) using a cable as short as possible. Use the largest possible conductor
cross section that is permitted for the supply plug.
In addition, the earthing connection on the rear of the device has to be connected as follows.
CP700_D00005_02_M_XXEN/06.2014
21
Installation, connection and commissioning
1
CP700
BMS
device
2
BMS
device
1
BMS
device
3
A2
A1
B2B1
15
69
BMS
BABABA
CP700
RTU
device
2
RTU
device
1
RTU
device
3
A2
A1
B2B1
15
69
Modbus/RTU
D-D+D-D+D-D+
BMS bus
Modbus/RTU
An earthing connection (1) is located at the rear of the CP700 for connection to a central earthing
point in the switchboard cabinet or the system where the device is to be installed. The largest possible wire cross section (minimum 2.5 mm²) should be used.
4.3.4BMS bus, Modbus/RTU
Two connecting cables (RS-485 cable) are included in the scope of delivery. The double cable ends
facilitate the connection of the device if it is arranged in the middle of the bus. Both cables have the
same pin assignment.
Plug connector
Bridge 4--9
Bridge 1--6
Not connectedshieldblackshieldshield
Loose cable
ends
A1white
A2yellow
B1brown
B2green
Core colour
Connection to
the BMS bus
AD+
BD-
Connection to
Modbus
Wiring examples
22
CP700_D00005_02_M_XXEN/06.2014
Installation, connection and commissioning
4.4 Commissioning
1. Switch the supply voltage on. - The "Settings" > "Interface" menu appears on the touch screen
(for details and factory settings refer to page 29).
Click on "Login" enter the settings.
2. Set the IP address.
If the connected computer network contains a DHCP server, activate the "DHCP" button. An IP
address is automatically assigned and displayed.
If the computer network does not include a DHCP server, the IP address, network mask (SN)
and standard gateway must be specified by the EDP administrator.
An IP address has been permanently assigned to the device. Therefore, deactivate the "DHCP"
button.
3. Set the BMS bus address for the CP700.
4. Set the baud rate and parity for the Modbus/RTU.
5. Set the display timeout. If no entry is made via the touchscreen of the CP700 for a predefined
time (e.g. five minutes), the screen is blanked.
The touch screen will be activated again when
– a new alarm occurs
– the number of alarms changes
– the screen is touched
6. Deactivate the "Show at startup" button. The "Settings" > "Interface" menu will no longer be
displayed during startup.
7. Confirm the changed settings with "OK". Tap on "Log out" when no more settings are to be
changed (not logged in).
CP700_D00005_02_M_XXEN/06.2014
23
Installation, connection and commissioning
24
CP700_D00005_02_M_XXEN/06.2014
5. Display and operating elements
1
2
7
6
5
4
3
11
10
9
8
5.1 Operating elements at the rear of the device
Key
LED "Run"
1
LED "Link"
2
LED "CF"
3
LED "Power".
4
"Reset" button,
5
operation is not required. CP700 starts as soon as supply voltage is applied.
When the "Reset" button is pressed, a hardware reset will be initiated. The device restarts (cold
start). A system reset may result in data loss!
"Power" button“, operation not required. CP700 starts as soon as supply voltage is applied.
6
The function of the "Power" button is identical to that of a mains switch of current desktop personal computers:
Pressing the button for a short timewill switch the device on resp. will shut the operating system
down and switch the device off.
Pressing the button for a long timewill switch the device off without shutting down the operating system (Risk of data loss!)
"Mode/Node x16" switch, has no function
7
"Mode/Node x1" switch, has no function
8
SD memory card slot, has no function. Must not be used!
9
CompactFlash Slot. Must not be removed.
10
Battery, see chapter "Battery" on page 26
11
CP700_D00005_02_M_XXEN/06.2014
25
Display and operating elements
LEDColorStatusMeaningLED indicator
OnSupply voltage OK
The device has booted, the battery status is "BAD".
Green
Blinking
Information:
For more information, see see " Battery" on page 33.
OnThe system is in standby mode (S5: soft-off mode or S4: hiber-
nate mode - suspend-to-disk)
Red
BlinkingThe MTCX is running, the battery status is "BAD". The system
is in standby mode (S5: soft-off mode or S4: hibernate mode suspend-to-disk)
Faulty or incomplete BIOS, MTCX or I/O FPGA update, battery
status OK, power supply OK
Faulty or incomplete BIOS, MTCX or I/O FPGA update, battery
status OK, standby mode (S5: soft-off mode or S4: hibernate
mode - suspend-to-disk)
Faulty or incomplete BIOS, MTCX or I/O FPGA update, battery
status BAD, power supply OK
Faulty or incomplete BIOS, MTCX or I/O FPGA update, battery
status BAD, standby mode (S5: soft-off mode or S4: hibernate
mode - suspend-to-disk)
Power
Red / green Blinking
Information:
An update must be performed again.
CFYellowOnIndicates IDE drive access (CF)
OnIndicates an active SDL connection on the panel plug.
An active SDL connection has been interrupted by a loss of
power in the display unit.
LinkYellow
Blinking
Information:
Check the power supply / power connector of the
connected display unit.
GreenBlinkingAutomation Runtime booting
Handled by Automation Runtime (ARemb and ARwin).
GreenOnApplication running
Handled by Automation Runtime (ARemb and ARwin).
Run
RedOnApplication in service mode
Handled by Automation Runtime (ARemb and ARwin).
CAUTION
5.1.1Status LEDs
For the status LEDs (Power, CF, Link, Run), the following time frame is being used:
Box width: 250 ms
Interval: 500 ms; Hence, 2 boxes correspond to one interval
5.1.2 Battery
The lithium battery (3 V, 950 mAh) buffers the internal real-time clock (RTC) and is located behind the
black cover. The duration of the battery is at least four years (at 50 °C, 8.5 μA current requirements of
the supplied components and a self-discharge of 40 %). The battery is subject to wear and should be
replaced regularly (at least following the specified life span) (see chapter "Battery change" on
page 165).
5.1.3CompactFlash card
Do not remove the CompactFlash card in order to ensure that all device properties are available!
If a replacement of the CompactFlash card becomes necessary, you have to disconnect the device from the power supply.
26
CP700_D00005_02_M_XXEN/06.2014
Display and operating elements
CAUTION
5.2 Touchscreen
Do not apply excessive force to the screen. Do not use a ballpoint pen, a pencil or
other sharp objects to operate the touch screen. This may damage or destroy the
touch screen.
The integrated 7 inch touch screen is used at the same time for indication and operation. This is a
resistive touch screen which responds to pressure.
For operation solely use finger or a touch pen. When sliding your finger over the display (e.g. when
scrolling through the language selection), apply the necessary pressure to the display.
CP700_D00005_02_M_XXEN/06.2014
27
Display and operating elements
4
321
98756
5.3 Operation via touch screen
After the initial power-up, the CP700 enters the "Settings" > "Interface" menu. By tapping the ""
button you will access the main menu. If no entry has been made via the touch screen for several
minutes and the touch screen has switched to standby mode, the CP700 will automatically switch to
the main menu.
5.3.1Main menu
The CP700 is equipped with a touch screen. That allows intuitive operation using your finger or a
special touch screen stylus.
Key
"Bus overview" button. Shows a list of the bus devices for selection, querying and parameterisa-
1
tion. BMS-bus device, Modbus/RTU devices, Modbus/TCP devices and virtual devices are displayed in the same list.
"Alarms" button. Shows a table of the pending alarms.
2
The background of the button
- is red when an alarm exists
- is white when no alarm exists.
"Settings" button. Allows the setting of the interface and the operation language of the device.
3
"Back" button. One operating step back.
4
5
"" button. Return to the main menu.
Device type or an individually entered text in the web user interface.
6
Date and time display.
7
Display "Logged in". Settings in the "Interface" menu can only be carried out after "Login". This
8
login applies to the operation of the touch screen only.
"Alarms" button. Shows a table of the pending alarms.
9
The same function as "2", but accessible from each submenu.
28
CP700_D00005_02_M_XXEN/06.2014
Display and operating elements
5.3.2"Settings" menu
Select:
Interface Interface parameter setting
Language Selection of the operation language for the CP700
5.3.2.1"Interface" menu
Display settings
The existing settings will be displayed.
If you have not logged in, you cannot change the settings. Therefore the buttons for the setting values are not active (greyed out).
CP700_D00005_02_M_XXEN/06.2014
29
Display and operating elements
Changing settings
The settings can only be changed in the "Logged in" mode. Tap on the "Login" button.
A password can be set in the "Bus overview > "Settings" > "Password" menu via the web user interface. The password consists of a 3-digit number. If a password has been set and activated (status
"on"), the following entry field will appear:
Enter the password. Then tap on "OK". The status "Logged in" is displayed.
If no password has been set, the status "logged in" will be displayed immediately.
Tap on the entry to be changed. An entry field appears. Enter the new value and Tap on "Close".
CP700 will check the settings:
identifies a permissible setting value
identifies an impermissible setting value or a setting value that makes no sense
30
CP700_D00005_02_M_XXEN/06.2014
Loading...
+ 142 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.