Bender A-ISOMETER IRDH275, A-ISOMETER IRDH275B Operating Manual

Operating Manual

A-ISOMETER® IRDH275

Power in electrical safety

IRDH275B

Insulation monitoring device for
IT AC systems with galvanically connected
rectifiers and converters
and for IT DC systems
Software version IRDH275B: D159 V1.4
TGH1361en/11.2009
Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 65 • 35305 Grünberg • Germany Postfach 1161 • 35301 Grünberg • Germany
Tel.: +49 6401-807-0 Fax: +49 6401-807-259
E-mail: info@bender-de.com Web: http://www.bender-de.com
© Dipl.-Ing. W. Ben der GmbH & Co . KG
All rights reserved.
Reprinting only with permission
of the publisher.
Subject to change!
Table of Contents
1. Safety information .................................................................................. 7
1.1 Use for the intended purpose ............................................................................. 7
1.2 Warranty and liability ............................................................................................. 7
1.2.1 Personnel .................................................................................................................... 8
1.2.2 About the operating manual .............................................................................. 8
1.2.3 Hazards when handling the A-ISOMETER® IRDH275 .................................. 8
1.2.4 Inspection, transport and storage ..................................................................... 9
1.2.5 Note .............................................................................................................................. 9
1.3 Explanations of symbols and warnings ........................................................... 9
1.4 Directions for installation ................................................................................... 10
2. Function ................................................................................................. 11
2.1 Common characteristics (IRDH275 and IRDH275B) .................................. 11
2.2 Additional characteristics IRDH275B .............................................................. 11
2.3 Product description .............................................................................................. 12
2.4 Function .................................................................................................................... 12
2.5 Additional functions IRDH275B ........................................................................ 15
3. Commissioning flow chart (threepart) ............................................. 19
4. Connection ............................................................................................ 23
4.1 Wiring ......................................................................................................................... 23
4.2 Wiring diagrams with coupling devices ........................................................ 26
4.2.1 Connection with AGH150W-4 ........................................................................... 26
4.2.2 Connection with AGH520S ................................................................................ 27
4.2.3 Connection with AGH204S-4 ............................................................................ 28
TGH1361en/11.2009
3
Table of Contents
5. Operation and setting .......................................................................... 31
5.1 Operating features and displays IRDH275(B) .............................................. 31
5.1.1 Display in the standard mode ........................................................................... 32
5.1.2 Display in the menu mode ................................................................................. 32
5.1.3 Function keys .......................................................................................................... 33
5.2 Menu structure and menu mode ................................................... 36
5.2.1 Diagram menu structure ..................................................................................... 37
5.3 Menu HISTORY INFO (IRDH275B) .................................................. 38
5.3.1 Diagram HISTORY INFO (IRDH275B) ............................................................... 39
5.4 Menu ISO SETUP:
Setting of the basic A-ISOMETER® functions ................................ 40
5.4.1 Response values Alarm 1 and Alarm 2 ........................................................... 40
5.4.2 Operating principle of the alarm relays ......................................................... 40
5.4.3 Memory setting (on/off) ...................................................................................... 42
5.4.4 Current output for external measuring instruments (IRDH275B) ........ 42
5.5 Menu ISO ADVANCED:
Setting of the extended functions ................................................ 43
5.5.1 External coupling devices (AGH: no) .............................................................. 43
5.5.2 Adaptation to the system leakage capacitance (Cemax : 150 μF) ....... 44
5.5.3 Changing the measuring principle from AMP to DC (Measure: AMP) 44
5.5.4 Setting the repetition time for automatic self tests (Autotest: 24h) ... 44
5.5.5 Setting the real-time clock (Clock) (IRDH275B) .......................................... 44
5.5.6 Setting the date (Date) (IRDH275B) ................................................................ 44
5.5.7 Specifying the starting time of the automatic self test (Test)
(IRDH275B) ............................................................................................................... 44
5.5.8 Diagram ISO ADVANCED .................................................................................... 45
5.6 Menu COM SETUP:
Setting the BMS interface .............................................................. 46
5.6.1 Bus address „Addr:“ (IRDH275B) ...................................................................... 46
5.6.2 ISOnet function (IRDH275B) .............................................................................. 46
5.6.3 ISO monitor (IRDH275B) ...................................................................................... 46
5.6.4 Diagram COM SETUP (IRDH275B) .................................................................... 47
5.7 Menu PASSWORD ........................................................................... 48
5.7.1 Activating and setting the password ............................................................. 48
5.7.2 Diagram PASSWORD ............................................................................................ 48
4
TGH1361en/11.2009
Table of Contents
5.8 Menu LANGUAGE ........................................................................... 49
5.8.1 Setting the national language .......................................................................... 49
5.8.2 Diagram Language ............................................................................................... 49
5.9 Menu SERVICE ......................................................................................................... 50
5.10 Parameterization via Internet ........................................................................... 50
6. Serial interfaces ..................................................................................... 51
6.1 RS485 interface with IsoData protocol (IRDH275) ..................................... 51
6.2 RS485 interface with BMS protocol (IRDH275B) ......................................... 53
6.3 Topology RS485 network (IRDH275B) ............................................................ 54
6.3.1 Correct arrangement ............................................................................................ 54
6.3.2 Wrong arrangement ............................................................................................. 54
6.3.3 Wiring ......................................................................................................................... 54
6.4 BMS protocol (IRDH275B) ................................................................................... 55
6.4.1 BMS Master .............................................................................................................. 55
6.4.2 BMS Slave ................................................................................................................. 56
6.4.3 Commissioning of an RS485 network with BMS protocol ...................... 57
7. Technical data IRDH275(B) .................................................................. 59
7.1 Data in tabular form ............................................................................................. 59
7.2 Standards and approvals .................................................................................... 62
7.3 Characteristic curves ............................................................................................ 63
7.4 Ordering details ..................................................................................................... 70
7.4.1 A-ISOMETER® ........................................................................................................... 70
7.4.2 Coupling devices ................................................................................................... 71
7.4.3 Measuring instruments ....................................................................................... 71
7.4.4 Label for modified versions ............................................................................... 71
5
TGH1361en/11.2009

1. Safety information

1.1 Use for the intended purpose

The A-ISOMETER® is intended for:
z monitoring the insulation resistance of IT systems
Any other use, or any use which goes beyond the foregoing, is deemed to be use other than for the intended purpose. The BENDER companies shall not be liable for any losses or damage arising therefrom. Use for the intended purpose also includes
z compliance with all information in the operating instructions, and
z compliance with test intervals.
As a basic principle, our "General conditions of Sale and Delivery" shall ap­ply. At the latest, these shall be available to the operator when the contract is concluded.

1.2 Warranty and liability

Warranty and liability claims in cases of damage to persons and property shall be excluded if they are attributable to one or more of the following causes:
z Use of the A-ISOMETER® other than for the intended purpose
z Incorrect assembly or installation, commissioning, operation and mainte-
nance of the A-ISOMETER®.
z Failure to comply with the information in the operating instructions regarding
transport, commissioning, operation and maintenance of the A-ISOMETER®.
z Unauthorized structural modifications to the A-ISOMETER®.
z Failure to comply with the technical data
z Improperly executed repairs, and the use spare parts or accessories which are
not recommended by the manufacturer.
z Cases of disaster and force majeure
z Assembly and installation with device combinations not recommended.
TGH1361en/11.2009
7
Safety information
This operating manual, especially the safety information, must be observed above all by personnel who work on the A-ISOMETER®. In addition, the rules and regulations that apply for accident prevention at the place of use must be observed.

1.2.1 Personnel

Only appropriately qualified staff may work on the A-ISOMETER®. Qualified means familiar with the installation, commissioning and operation of the product and with training appropriate to the work. Personnel must have read and understood the safety section and warning in­formation in this operating manual.

1.2.2 About the operating manual

This operating manual has been compiled with the greatest possible care. Nevertheless, errors and mistakes cannot be entirely ruled out. The BENDER companies assume no liability whatsoever for any injury to persons or dam­age to property which may be sustained as a result of faults or errors in this operating manual.

1.2.3 Hazards when handling the A-ISOMETER® IRDH275

The A-ISOMETER® IRDH275 is constructed according to the state-of-the-art and recognized technical safety rules. Nevertheless, when it is being used, hazards may occur to the life and limb of the user or third parties, or there may be adverse effects on the A-ISOMETER® or on other valuable property. The A-ISOMETER® must only be used:
z for the purpose for which it is intended
z when it is in perfect technical condition as far as safety is concerned
Any faults which may impair safety must be eliminated immediately. Imper­missible modifications and the use of spare parts and additional devices which are not sold or recommended by the manufacturer of the devices may cause fires, electric shocks and injuries. Unauthorized persons must not have access to or contact with the A-ISOME­TER®. Warning signs must always be easily legible. Damaged or illegible signs must be replaced immediately.
8
TGH1361en/11.2009
Safety information

1.2.4 Inspection, transport and storage

Inspect the dispatch packaging and equipment packaging for damage, and compare the contents of the package with the delivery documents. In the event of damage in transit, please inform the BENDER company immediate­ly. The devices must only be stored in areas protected from dust, damp and spray or dripping water, and in which the specified storage temperatures are maintained.

1.2.5 Note

Make sure that the operating voltage is correct! Prior to insulation and voltage tests, the A-ISOMETER® must be disconnected from the power system for the duration of these tests. In order to check the proper connection of the device, it is recommended to carry out a functional test. Make sure that the basic settings meet the requirements of the system. Children and unauthorized persons must not have access to or contact with the A-ISOMETER®.

1.3 Explanations of symbols and warnings

The following symbols are used in BENDER documentation to draw atten­tion to important information and to make it easier to find certain text pas­sages. The following examples explain the meaning of the symbols:
TGH1361en/11.2009
The "Attention" symbol is used to draw attention to information warning employees of hazardous situations.
Information you should know for correct handling of the product is marked with the "Info" symbol.
9
Safety information

1.4 Directions for installation

Only one insulation monitoring device may be used in each intercon­nected IT system. When insulation or voltage test are to be carried out, the device shall be isolated from the system for the test period.
The terminals and KE shall be connected by a separate wire to the pro­tective conductor (PE). If the terminals L1, L2 of the device are connected to a system under operation, the terminals and KE must not be disconnect­ed from the protective conductor (PE).
In order to check the proper connection of the device, it is recommended to carry out a functional test using a genuine earth fault, e.g. via a suitable re­sistance, before starting the A-ISOMETER®.
The devices, variant -4.. are delivered with the following factory setting:
ISO SETUP:
Alarm 1 / Alarm 2 (response values)
=40 kΩ / 10 kΩ
ISO SETUP: Operating principle K1/K2 = N/O operation
ISO SETUP: Memory = off
ISO ADVANCED: System leakage capacitance = 150 μF
COM SETUP: Bus address = 3 (slave)
Please check if the basic setting of the A-ISOMETER® complies with the re­quirements of the system to be monitored.
When an AC system includes galvanically connected DC circuits, the following shall be considered: Insulation faults in DC circuits can only be monitored correctly when the rectifiers carry a continuous load of 5...10 mA.
10
TGH1361en/11.2009

2. Function

2.1 Common characteristics (IRDH275 and IRDH275B)

z A-ISOMETER® for IT AC systems with galvanically connected rectifiers
and for IT DC systems (IT = unearthed systems)
z The operating range of the nominal voltage U
devices.
z Automatic adaptation to the existing system leakage capacitance
z measuring principle (European Patent: EP 0 654 673 B1)
z Two separately adjustable ranges of the response value1 kΩ...10 MΩ
(Alarm 1, Alarm 2)
z Two-line LC display
z Connection monitoring (monitoring of the measuring leads)
z Automatic device self test
z Option "W":
This option provides: improved shock and vibration resistance for use in ships, on rolling stock and in seismic environment.

2.2 Additional characteristics IRDH275B

z Memory with real-time clock to store all alarm messages with date and time
stamp.
z BMS interface (BMS protocol) for data exchange with other Bender devices
(RS485 electrically isolated).
z Internal disconnection of the A-ISOMETER from the IT system to be monitored
(using a control signal; terminals F1/F2) , e.g. if several A-ISOMETERs® are inter­connected.
z Current output 0(4)...20mA (galvanically separated) in relation to the meas-
ured insulation value.
z Remote setting of certain parameters via the Internet (option; FTC470XET
additionally required)
can be extended via coupling
n
TGH1361en/11.2009
11
Function

2.3 Product description

The A-ISOMETER® type IRDH275 monitors the insulation resistance of IT systems. It is suitable for universal use in 3(N)AC, AC/DC and DC systems. AC systems may include extensive DC supplied loads, such as converters or thyristor-controlled DC drives. The device automatically adapts itself to the existing system leakage capacitance.
Suitable coupling devices are available to extend the nominal voltage range U
.
n
The IRDH275B can be used in combination with a control and indicating de­vice, e.g. PRC1470 version 2 or higher, on the BMS (BMS = Bender Measur­ing Device Interface) bus.

2.4 Function

The A-ISOMETER® IRDH275 is connected between the unearthed system (IT system) and the protective conductor (PE). The response values and other function parameters are set via the function keys. The parameters are indicated on the LC display and are stored in a non­volatile memory (EEPROM) after the setting is completed. A microprocessor-controlled pulsating AC measuring voltage is superim­posed on the IT system to be monitored ( measuring principle*). The measuring cycle consists of positive and negative pulses of the same ampli­tude. The period of these pulses depends on the respective system leakage capacitances and the insulation resistances of the IT system to be monitored. An insulation fault between the IT system and earth closes the measuring cir­cuit. From the measured current value, the microprocessor calculates the in­sulation resistance which is indicated on the LC display or the external kΩ measuring instrument. The measuring time is determined by the system leakage capacitances, the insulation resistance, and the system-related interference disturbances. Sys­tem leakage capacitances do not influence the measuring accuracy. If the reading is below the selected response values Alarm 1/Alarm 2, the as­sociated alarm relays respond and the alarm LEDs "Alarm 1/2“ light up and the measuring value is indicated on the LC display (in the event of DC insu­lation faults, the faulty supply line is indicated). If the terminals R1/R2 are bridged (external RESET button [NC contact] or wire bridge), the fault indi­cation will be stored. Pressing the RESET button, resets the insulation fault
12
TGH1361en/11.2009
Function
message, provided that the currently displayed insulation resistance is at least 25% above the actual response value when the reset is carried out. The fault memory behaviour can also be set in the "ISO SETUP" menu, by select­ing the sub menu Memory: on/off.
The connections for external kΩ display supplied by the current output
0...400 µA or 0/4...20 mA (IRDH275B) at M+/M- are galvanically isolated.
*) measuring principle "adaptive measuring pulse", a measuring principle developed by BENDER (European Patent: EP 0 654 673 B1).
Self test
A self test can be carried out manually using the TEST button or automatical­ly. In order to guarantee high functional reliability, the A-ISOMETER® IRDH275 provides comprehensive self test functions. After switching the supply voltage on, all internal measuring functions, the components of the process control such as data and parameter memory as well as system and earth connections are checked using the self test functions. The progress of the self test is indicated on the display by a bar graph. Depending on the conditions in the IT system to be monitored, the self test is running for
15...20 seconds, then the message "Test ok!" appears on the LC display for
approximately 2 seconds. Then the device returns to normal measuring mode and the current measuring value is displayed after the expiry of the measuring time. When a device error or connection fault is found, the message "!Error!" ap­pears on the display, the device fault LED lights up, the relay K2 (21-22-24) switches and the respective fault message (see table) is indicated. If such a device fault occurs, a self test is started again every minute. If no more mal­function is detected, the fault message is deleted automatically and the device fault LED extinguishes.
During operation, the self test function can be started by pressing the TEST button (internal or external). The self test can also be started automatically every hour or every 24 hours by selecting "ISO ADVANCED: Autotest" menu. The alarm relays Alarm1/2 only switch after starting the self test function by pressing the TEST button, that means if an automatic self test has been se­lected, the alarm relays do not switch.
TGH1361en/11.2009
13
Error message Meaning Steps to be taken
1. Check the wiring of terminal L1, L2 to the IT system
2. Press the test button
3. Switch the supply voltage off and on.
4. Check the fuses
1. Check wiring of terminal and KE to earth (PE)
2. Press TEST button
3. Switch the supply voltage off and on
1. Press TEST button
2. Switch the supply voltage off and on
3. Contact BENDER
System connection?
Connection PE?
Device error x
If the on/off switching of the supply voltage is not possible for technical reasons, a RESET of the process control can be carried out by pressing the "ESC“, "RESET“ and "MENU“ key.
No low-resistance connection of ter­minals L1, L2, L3 to the IT system
No low-resistance connection of the terminals and KE to earth (PE)
Internal device error
Function
14
TGH1361en/11.2009
Function

2.5 Additional functions IRDH275B

Current output for external measuring instrument
The current output of IRDH275B provides 0(4)...20 mA. The current output is galvanically isolated from the device electronics and the RS485 interface. The ISO SETUP menu, on page 43, allows to switch over between 0...20 mA and 4...20 mA.
Real-time clock
The real-time clock serves as a time base for the memory and self test func­tions. At first, the correct time and date must be set in the menu "ISO AD­VANCED". If time and date are not set, a „C“ (clock) is flashing in the standard display. In the event of a supply voltage failure, time and date will be stored for at least thirty days. If the 24 h test is activated in the "ISO ADVANCED" menu, a special time of day can be selected for the execution of the self test in the menu "TEST: 12:00". Then a self test will be started automatically once a day exactly at the preset time. If the 1 h auto test has been selected, the self test is automatically carried out every full hour.
Interconnected IT systems
When using A-ISOMETERs® in IT systems, make sure that only one active A-ISOMETER® is connected in each interconnected system. If IT systems are interconnected via coupling switches, make sure that A-ISOMETERs® not currently used are disconnected and deactivated via a control system. IT sys­tems coupled via diodes or capacitances may also influence the insulation monitoring process. Hence, also in this case a central control of the different A-ISOMETERs® is required.
Function input F1/F2 for connection or disconnection of IT systems being monitored
The A-ISOMETER® can be disconnected from the IT system and set to STANDBY mode with the function input F1/F2. If the input F1/F2 is bridged, the connections L1/L2 are switched off via internal coupling relays, the meas­uring function is stopped and the message "STANDBY" appears on the dis­play. Software version 1.4 or higher does not indicate the measured insulation resistance during the disconnection, but indicates the value > 10 MΩ. Furthermore, the alarm relays and alarm LEDs no longer provide alarm messages. After opening the function input F1/F2, the connection to the IT system will be restored and a completely new measuring cycle for in-
TGH1361en/11.2009
15
Function
sulation monitoring is started. With this function, selective disconnection of an IRDH275 in interconnected IT systems can be carried out via auxiliary contacts of the respective coupling switch. One coupling switch each in a line-type or ring-type arrangement can deactivate a subsequent IRDH275. This arrangement guarantees that only one A-ISOMETER® is active in each galvanically connected system. In a ring­type arrangement with all coupling switches closed, it can be assumed that all A-ISOMETER®s are deactivated. In order to prevent this, a BMS Master (IRDH275B BMS address 1) monitors the condition of the function input F1/ F2 of all slave A-ISOMETERs®. When all slave A-ISOMETERs® are in the STANDBY mode, the insulation monitoring function of the Master A-ISOMETER® and hence the function input F1/F2 of the Master are without function in this mode. Details are shown in the graphic below.
BMS bus (A/B, RS485)
16
Addr. 1
PE PE
F1/F2
IRDH275B
F1/F2
IRDH275B
G
Addr. 2
G
IT system 1 IT system 2
G
G
IT system 3IT system 4
IRDH275B
PE PE
Addr. 4
F1/F2
F1/F2
IRDH275B
Addr. 3
TGH1361en/11.2009
Function
ISOnet Function (COM SETUP)
Select "ISOnet=ON" from the COM SETUP menu to activate this function. This function is a type of scanning function. The BMS Master activated via the ISOnet function controls the ISOnet slave devices via the BMS bus. Once an A-ISOMETER® has finished its measurement cycle, the authorization for measuring the insulation resistance is passed on from the ISOnet Master to the next slave. While an A-ISOMETER® is carrying out a measurement all other A-ISOMETERs® are in the STANDBY mode. In this way it can be pre­vented that the A-ISOMETERs® disturb each other in interconnected sys­tems. In comparison to the solution coupling switches and function input F1/ F2, the response time is prolonged, since no continuous measurement takes place. The advantage is that no auxiliary contacts of a coupling switch are required. Furthermore, this solution is ideally suited for capacitive IT systems or IT systems connected via diodes. An ISOnet slave checks whether there is a Master available in the network. If there is no Master available, the fault message "ISOnet Master?" appears on the display. When the ISOnet function is activated, the function input F1/F2 will be disconnected.
BMS bus (A/B, RS485)
G
G
TGH1361en/11.2009
IRDH275B
Addr. 1
IRDH275B
PE PE
IT system 1 IT system 2
IT system 3IT system 4
IRDH275B
Addr. 4
IRDH275B
PE PE
Addr. 2
G
G
Addr. 3
17
Function
18
TGH1361en/11.2009

3. Commissioning flow chart (threepart)

Due to limitations of space, the three-part flow chart begins on the next page.
TGH1361en/11.2009
19
Commissioning flow chart (threepart)
The encircled figures in the flow chart correspond to the figures in the leg­end to the wiring diagram.
Commissioning of the A-ISOMETER® (1)
Is the system to be monitored an unearthed system (IT system)?
no
The IRDH275 is not suitable for this application( contact BENDER).
Is the maximum nominal voltage
AC 793 V
U
n
or Un DC 650 V
no
Un is too high for direct connection. A coupling device providing the respective voltage range must be connected.
Deenergize the installation
before connecting the device!
yes
Device connection Optional device
The two PE connections be connected separately to the equipotential bonding.
The terminals L1 and L2 must be connected to Un of the system to be moni­tored according to the wiring diagram.
Connect the supply voltage Us to the terminals A1/+ and A2/-. Consider the details indicated on the nameplate.
Recommended wire cross section of
connecting cable
single wire 0.2...4 mm
flexible 0.2... 2.5 mm
and KE must
6
2
3
4
5
1
2
2
An external kW measuring instrument at M+/M- with a display range of 10 kW...1000 kW, Scale centre point: 120 kW
Output current IRDH275: 0...400 mA Output current IRDH275B: 0/4...20 mA
External TEST button (NO contact) to the terminals T1 and T2
External RESET button (NC contact) to the terminals R1 and R2
yes
connection
10
7
8
When using the RS485 interface, take care that a 120 W resistor is connected at the beginning and the end of the network.
20
11
The output contacts of the alarm relays System fault (21-22-24) Alarm 1 (11-12-14) Alarm 2 (21-22-24)
TGH1361en/11.2009
12
13
Commissioning flow chart (threepart)
Commissioning of the A-ISOMETER® (2)
Connect the supply
voltage U
Connect the voltage Un of the
IT system to be monitored
Only IRDH275B: set the clock
S
The A-ISOMETER carries out a self test. The display indicates
the insulation value after finishing
the measurement.
Shall the basic setting
be changed?
Alarm1 = 40 kW Alarm2 = 10 kW
K1/K2 = N/O operation
Memory = off
no
Does one of the alarm LEDs
light up?
no
yes
yes
Select ISO SETUP
(see chapter operation and setting)
The insulation value of the system being monitored is below the preset response value. Change the response
value or improve the insulation
condition of the system.
TGH1361en/11.2009
21
Commissioning of the A-ISOMETER® (3)
In order to check the proper connection, a functional test using a suitable resistance is
to be carried out.
Size of the resistance:
50% of the preset response
value Alarm 2.
Commissioning flow chart (threepart)
Do both alarm LEDs light up?
Did the alarm relays switch ?
yes
Remove the resistor !
Alarm LEDs extinguished ?
Did the output relays change
their position ?
yes
The IRDH275 is correctly
connected and functions reliably !
no
no
yes
Check the connecting leads !
Is voltage Un applied to the
terminals L1/L2 ?
When a coupling device is
used, is it correctly connected ?
Check the voltages with a voltmeter !
Do both alarm LEDs light ?
Did the alarm relays switch?
22
TGH1361en/11.2009

4. Connection

4.1 Wiring

Connect the terminals A1/+ and A2/- to the supply voltage US in accordance with IEC 60364-4-43. The connections to the supply voltage shall be provid­ed with protective devices to afford protection in the event of a short circuit (a 6 A fuse is recommended).
Devices for protection against short-circuit in conformity with IEC 60364-4­43 for the IT system coupling L1/L2 can be omitted if the wiring is carried out in such a manner as to reduce the risk of a short-circuit to a minimum (a short-circuit-proof and earth-fault-proof wiring is recommended).
Only one A-ISOMETER® may be connected to an external TEST or RESET button. A galvanic parallel connection of several TEST and RESET inputs for collective testing of A-ISOMETER®s is not permitted.
External coupling devices connected via the terminal AK cannot be switched off via the internal coupling relays. If no coupling device is used, the terminal AK remains free.
TGH1361en/11.2009
23