Bell System BFD2-72 Installation And Operating Manual

Bell System (Telephones) Ltd.
PD-307 Issue 2 June 2017
tabellet
2-72 Multi Way
Video Door Entry System
With
Installation & Operation Manual
This manual applies to the following: ­BFD2-72 Way Door controller – Version 1 Builds 1 tabellet Colour Apartment Station – Version 1 Build 1 to 2 BS Colour Videophone – Version 2 Builds 1 to 3 XL5-BS Audio Phone – Version 1 Build 1 BSC4 Video Controller – Version 2 Build 7
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 2 of 48
tabellet Apartment Station
BFD8 controller
BSC4 controller
XL5-BS audiophone
BS videophone
BS Deskphone
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 3 of 48
TABLE OF CONTENTS
TABLE OF CONTENTS ...................................................................................................... 3
INTRODUCTION ................................................................................................................. 4
DESCRIPTION ..................................................................................................................... 4
MAIN FEATURES ................................................................................................................. 4
BASIC SYSTEM OPERATION ............................................................................................ 6
DESIGN CONSIDERATIONS .............................................................................................. 9
EQUIPMENT LIST ................................................................................................................. 9
OPTIONS ................................ ................................ ............................................................ 9
POWER SUPPLY REQUIREMENTS ....................................................................................... 11
CABLE SPECIFICATION ...................................................................................................... 13
CABLE DISTANCES ............................................................................................................ 14
INSTALLATION & COMMISSIONING ................................................................ .............. 15
CHECKLIST ....................................................................................................................... 15
WIRING ............................................................................................................................ 15
COMMISSIONING ............................................................................................................... 19
BFD8/72 DOOR CONTROLLER SWITCH SETTINGS ............................................................... 20
BFD8/72 DOOR CONTROLLER JUMPER SETTINGS .............................................................. 22
BSC4 VIDEO CONTROLLER SETTINGS ................................................................................ 23
DOOR SPEECH VOLUME ADJUSTMENT ................................................................................ 25
TABELLET APARTMENT STATION SWITCH SETTINGS ............................................................. 26
BS VIDEOPHONE SWITCH SETTINGS .................................................................................. 27
TROUBLESHOOTING ...................................................................................................... 28
COMMON FAULTS ............................................................................................................. 28
QUICK FAULT REFERENCE ................................................................................................. 28
SPECIFICATIONS ............................................................................................................. 31
DIAGRAM A – 2-72 WAY BASIC SYSTEM WIRING OVERVIEW ................................... 33
DIAGRAM B – BFD8 PCB DETAIL .................................................................................. 34
DIAGRAM C – 2-72 WAY BASIC SYSTEM WIRING DETAIL .......................................... 35
DIAGRAM D – BSC4 PCB DETAIL .................................................................................. 36
DIAGRAM E – BSC4 WIRING DETAIL ............................................................................. 37
DIAGRAM F – LARGE SYSTEM OVERVIEW .................................................................. 38
DIAGRAM G – EXTENSION APARTMENT STATION WIRING ....................................... 39
DIAGRAM H – APARTMENT STATION LOCAL POWER WIRING ................................. 40
DIAGRAM I – CAMERA SHARING & TIME CLOCK SHARING ...................................... 41
DIAGRAM J – 2-72 WAY ADDITIONAL DDA WIRING .................................................... 42
DIAGRAM K – COMBINED CONNECTIONS BELL
FREE
WITH LOCK .......................... 43
DIAGRAM L – COMBINED CONNECTIONS THIRD PARTY LOCK................................ 45
SAFETY INFORMATION AND DECLARATIONS ............................................................ 47
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 4 of 48
Introduction
Description
A tabellet video door entry system consists of a door panel, positioned at the entrance of a building, video apartment stations, placed inside of the building for the convenience of the occupants and a power supply and controller which are usually located inside an electrical cupboard. The door panel comprises of a two-way speech unit, a camera and several push buttons – one of which must be depressed by a visitor to initiate a call. The apartment station, which rings in response, allows a two-way hands free conversation (a touch is required to initiate the conversation and end the conversation) whilst the caller can be observed through the integral display. The operator can selectively allow visitors access to the building by touching a pad on the apartment station and so electrically releasing the door.
The tabellet 2-72-way Video Door Entry System is suitable for any building requiring multiple push buttons at the entrance, such as blocks of flats or multiple offices. For buildings requiring a single push button at the entrance, such as houses, individual flats and offices, please refer to the “tabellet 1-way Video Entry System” manual. For a digital panel with display, refer to the tabellet Digital System.
The tabellet “2-72-way” system is supplied with a dedicated door controller, for each entrance, and a video controller for every four apartment stations. The basic system supports 1 apartment station per call button, and up to 3 extension apartment stations (more with additional power supplies). Multiple entrances can be supported with the addition of one panel and one door controller for each entrance.
Main Features
Enhanced audio for hands free operation
Cat5 cable throughout; no co-ax required!
● 3.5” Flat screen high resolution TFT colour display.
High resolution CCD colour day/night camera with infrared lamps.
12V d.c. operation
High quality full-duplex speech amplifier.
Automatic picture display while ringing.
Ringer mute function.
Ringer volume control.
Fail safe or fail secure lock releases and magnetic locks (maglock).
Lock release timer.
Tradesman facility (optional).
Facility for exit button and/or fire switch.
Door open indication.
Second camera option.
Up to 3 extension Apartment stations per flat.
DDA panel options.
Multiple entrances supported.
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 5 of 48
tabellet Colour Apartment Station
Mode
Handset
Camera
Sounder
Key
Idle
Off
Off
Off
Off
Idle Mute Active
Off
Off
Red
Off
Idle Door Open
Off
Off
Off
Red
Idle Mute and Door Open
Off
Off
Red
Red
Ringing
Blue Flash
Blue Flash
Off
Off
Muted Ring
Blue Flash
Blue Flash
Red
Off
Video Answer or CCTV
Blue Flash
Yellow
Off
Green Flash
Talking
Blue
Yellow
Off
Green Flash
Adjustment Mode
Blue
Yellow
Red
Green
Doorbell
Off
Off
Red Flash
Green Flash
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 6 of 48
Basic System Operation
Call sequence
When the call button is pressed at the entrance panel the apartment station will ring and its blue pickup / view lamp will flash, highlighting the pickup and view symbols. The apartment station will continue to ring for up to 30 seconds or until the resident responds by touching the view symbol (see silent viewing below) or the pickup symbol. After using the pickup symbol the resident can freely converse with the visitor whose image is now displayed on the apartment station; at the same time the green lock symbol will flash to highlight the lock function.
The call may be terminated by touching the pickup symbol again or more usually by touching the lock symbol first to allow the visitor access through the entrance; the speech and picture will persist for a further 3 seconds while the door is being released.
Silent viewing
When the apartment station is ringing the resident can touch the view symbol to answer the call instead of the pickup symbol; this will stop the apartment station ringing and enable them to view the visitor for up to 60 seconds or until the lock symbol is touched to release the door. Silent viewing can be ‘normalised’ at any time by touching the pickup symbol and conversing with the visitor as described above.
Apartment Station Controls
The diagram in the introduction shows the apartment station and its controls. The controls are adjusted by touching the end of the slider and sliding the finger up and down. The default setting is ringer volume halfway and contrast slider fully down.
Auto Display
When ‘Auto Display’ mode is selected the picture will come on while the apartment station
is ringing, otherwise the picture will only come on when the call is answered. Auto Display mode is usually pre-selected at installation and generally only one apartment station per flat should be set in this mode (see ‘Extension Apartment Stations’ below).
Ringer Mute
The resident can mute the ringing sound in the apartment station when they do not wish to be disturbed. Ringer mute is activated by touching the mute symbol on the apartment station, which then illuminates in red as a reminder. Touching the mute symbol a second time will disengage the mute function. Ringer Mute only stops the audible ring, but the blue ring lamp will still flash and all other functions work normally. Ringer mute will continue for the pre-set time even if a call is answered.
During installation it is possible to set a time limit for the mute function in various values from 2 minutes up to 10 hours or indefinitely. When this time period has elapsed the mute function will automatically disengage. Default timeout is never (See ‘mute timer’, page 26).
Door Status Indication
The green lock lamp on the apartment station will illuminate to warn the resident that a door has been left open following a call. This feature requires a door monitor contact to be fitted.
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 7 of 48
Call Privacy
Once a call has been made from an entrance panel only the apartment station(s) which is / are ringing may answer the call. Once the call is answered another apartment station will not activate (including extensions of the active apartment station).
User Activation (CCTV Mode)
User activation is a feature of the bellfree 1 way system and is not available on multi-way systems. User activation is generally not recommended on larger systems as the
conflicting demands of residents and callers can result in confusion and erroneous fault reports.
Cameras
The door controller has the capability of using one or two cameras, for instance a second
panel camera for DDA or a ‘third party’ ‘CCTV’ camera located to offer a different entrance
viewpoint. Touching the view symbol will alternate the view between camera 1 and camera 2 (if enabled).
Note. The camera to controller wiring has termination options which allow for connections to other video equipment. See the Camera sharing diagram on page 41 for details.
Extension Apartment Stations
Additional apartment stations may be added to the basic system. The number of extensions is limited only by power supply considerations. All apartment stations for that
‘flat’ will ring when called however typically only the master unit will display a picture while ringing. Once the master or extension apartment station is ‘picked-up’ the picture will
display on that unit alone. An extra power supply may be used to allow extension apartment stations to display a picture while ringing.
Lock Type
The door controller supports both fail-secure and fail-safe locks including magnetic locks of up to 1A rating. The lock time may be programmed between 1 and 99 seconds. (See ‘Lock Operating time’ and ‘Lock Type’ on page 21.
Exit Button and Fire Switch
An input is provided for an exit button, which can be installed on the inside of the door and allow residents to exit freely. Momentary operation of this button will operate the lock release for the programmed lock time. A Fire switch or other override device may use the same input to hold the door open indefinitely. Note. Fail secure locks must be continuously rated.
Trades Facility
Use of a time clock in conjunction with a trades button will allow free access during the programmed time(s).
DDA Functionality
The bellfree video system has a range of options for entrance panels to help meet the requirements of the Disability Discrimination Act (DDA), including Illuminated Tactile
buttons, reassurance tones and LED indicators for “Speak Now” and “Door Open”.
Contact your sales representative for further details. Reassurance tone setting is on page 22.
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 8 of 48
Multiple Entrances
The bellfree system allows multiple entrances to be catered for by the addition of a door controller and entrance panel for each entrance and additional power supplies.
In a multiple entrance system an optional feature allows the resident to view the cameras at all the entrances with successive touches of the view symbol.
For details of this camera feature and user activation see the setting for ‘Camera Numbering’ on page 22.
Gate and Block Systems
Sites with two or more blocks sharing one or more site entrances are catered for with our BSSW Gate controller. The blocks can then work independently but will receive calls from the shared entrance.
For further details see the “bellissimo and Bellcall Manual Gate and Block (PD-120)”.
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 9 of 48
Design Considerations
Equipment List
A tabellet-n tabellet Video Kit (where n is the no of ways) comprises the following: -
Model No
Description
N x tabellet
Colour apartment station
1 x BFPn
Vandal resistant panel with a BF-AMP speech unit, VR buttons and camera.
1 x BFD8 or BFD72
Door controller (BFD72 required for > 8 ways)
M x BSC4
Video controller (one required for every 4 ways = N/4 rounded up)
K x PS4
4A 12V power supply. (one required for every 8 to 16 ways)
1 x 203
Fail-secure lock release, alternate types available
E.g. A TB6 Six way tabellet Video Kit comprises the following: -
Model No
Description
6 x tabellet
Colour apartment station
1 x BFP6
Panel with a speech unit and camera
1 x BFD8
Door controller
2 x BSC4
Video controller
1 x PS4
4A 12V power supply
1 x 203
Fail-secure lock release
E.g. A TB22 Twenty two way tabellet Video Kit comprises the following: -
Model No
Description
22 x tabellet
Colour apartment station
1 x BFP22/VR
Vandal resistant panel with a speech unit and camera
1 x BFD72
Door controller
6 x BSC4
Video controller
2 x PS4
4A 12V power supply
1 x 203
Fail-secure lock release
Options
The following options are available: -
Extensions using model tabellet apartment station(s).
Extensions using Videophone model BS.
Extensions using Audio only phones model XL5-BS.
Additional entrances, each comprising a BFD8 or BFD72 controller and BFPn
panel. (See also power supply requirements).
Alternative lock releases, fail-safe and fail-secure.
Timed Trades facility; specify TRBS to add another button and a TS2000-BST time- clock. The extra button will be engraved “TRADES”
Exit button. Model 5077 surface and model 5078 flush versions are available.
Battery back-up power supply, Model 840 (12V 4A).
DDA panels (Contact sales for further information).
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 10 of 48
Entrance Panel – Important Note
Careful consideration should be given to the location of the entrance panel to ensure the best possible lighting conditions for the camera. In general strong back lighting of the subject (by the sun and sky) should be avoided, as the contrast between foreground and background may be too great for the camera. The field of view should contain as little of the sky as possible, particularly if south facing. If a backlit situation is unavoidable, additional lighting may be necessary to illuminate the caller and avoid a dark outline image (silhouette). A light coloured or reflective surface around the panel will redirect backlight to illuminate the caller.
Door Controller
The door controller and power supply should be wall-mounted in a convenient cupboard or other protected environment with available mains power. Cable length to the entrance should be less than 50m. The door controller for the second and subsequent entrances may be situated in the same location, or to meet the 50m requirement may be situated in another location. Power supplies may be shared between door controllers placed in the same location, but controllers in separate locations must be separately powered.
Video Controller
The video controller(s) and power supply(ies) should be wall-mounted in a convenient cupboard or other protected environment with available mains power. Cable length to the apartment station should be less than 150m, see ‘Cable Distances’ page 14. In many cases the video controllers will be in the same location as the door controller(s), but they may be distributed as required to reduce wiring distances. When placed in different locations, each location must have its own local power supplies.
Gate Controller
The gate switch controller BSSW is wired between the block door controllers and the video controllers, so would normally be wall mounted next to a door controller.
For further details see the “bellissimo and Bellcall Manual Gate and Block (PD-120)”.
Separately Powered Apartment Stations
The limitation of up to 4 apartment stations ringing but only one displaying, as indicated in the power supply and cable distance tables on page 14, can be overcome by the use of supplementary power from a 340C.
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 11 of 48
Power Supply Requirements
The system is powered by 12V power supplies only: ­Model PS4 12V, 4A. Model 840 12V, 4A battery backup supply. Model 340C 12V, 1.5A optional for extensions. Note 1. The 28V referred to on the apartment station, video controller and wiring diagrams
is internally generated in the controller. DO NOT use any power supply other than 12V or damage may occur.
Note 2. The PS4 power supply has been specifically designed to operate with the high­surge requirements of the system. Bell System is unable to guarantee functionality or provide support for systems which use third party power supplies.
Exact power supply requirements depend upon many factors. The number of power supplies included within a standard ‘kit’ or quotation assumes that all controllers are installed in one location and that there are no extensions.
The following table gives examples of the minimum number of controllers and power supplies for a given number of entrance doors and flats.
System
Control Equipment and Power Supplies
1 door 6 flats
1 x BFD8 door controller 2 x BSC4 video controller 1 x PS4 12V 4A power supply
2 door 6 flats
2 x BFD8 door controller 2 x BSC4 video controller 2 x PS4 12V 4A power supply
1 door 20 flats
1 x BFD72 door controller 5 x BSC4 video controller 2 x PS4 12V 4A power supply
2 door 20 flats
2 x BFD72 door controller 5 x BSC4 video controller 3 x PS4 12V 4A power supply
Distributed installations will typically require more power supplies. Also the use of other equipment such as coded access or proximity readers must be taken into account.
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 12 of 48
The following table is a guide to how much equipment a PS4 power supply can safely and reliably feed, please contact technical support for other variations.
Equipment 1 x PS4 can power
Comments
4 x BSC4 video controllers with 1 tabellet apartment station per output.
16 apartment station s directly powered. Extensions may be added if separately powered by 340C’s.
2 x BSC4 video controllers with up to 4 tabellet apartment station per output.
Extension apartment stations must be set to ring only, use the above configuration to allow the extensions to have a picture while ringing.
1 to 3 BSC4’s with phones plus extensions
16 apartment station s directly powered.
1 x BFD8/72 door controller and 3 x BFC4 video controllers with 1 tabellet apartment station per output
12 apartment stations directly powered. Extensions may be added if separately powered by 340C’s.
1 x BFD8/72 door controller and 1 x BSC4 video controllers with up to 4 tabellet apartment stations per output
Extension apartment stations must be set to ring only, use the above configuration to allow the extensions to have a picture while ringing.
2 x BFD* door controllers (any type) with up to 2 cameras and 1A fail safe locks.
Both door controllers must be in the same location. No spare current available for other equipment unless both cameras or all the lock current is not used.
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 13 of 48
Cable Specification
All system wiring must be carried out using Cat5 signal cable and where necessary 1mm² (or greater) power cable as tabulated below. Cat5 cable has a known performance for the transmission of video signals, whilst telephone or alarm cables are not suitable.
Bell System will be unable to offer any warranty or support for systems installed using incorrect cables.
Cat5 Cable Specification
Cat5 is our short reference for EIA standard UTP Category 5 Unshielded Twisted Pair data cable. This is a standard solid core twisted pair cable having 4 pairs (8-cores) and no shield. The cores are in pairs where Blue and ‘Blue with a White stripe’ are twisted together as the first pair. The other three pairs are similar with main colours Orange, Green and Brown.
Also available and acceptable are:
UTP Category 5e (Cat5e) UTP Category 6 (CAT6) UTP Category 6e (CAT6e)
The exact cable can be chosen from the above on cost and availability grounds.
STP (Shielded Twisted Pair) cables are not recommended. UTP “patch cables” are not recommended.
NOTE: Cat5 cable is easily identifiable as the specification is printed on the sheath
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 14 of 48
Cable Distances
Video Controller to tabellet Apartment Station
System
Distance
Cable
Comments
Single apartment station per output or first apartment station
< 100m
1 x Cat5
< 300m
1 x Cat5 2 x 1mm2
Single apartment station + 3 extensions on each output, all cable powered
< 50m
1 x Cat5
Only Master apartment station has ‘Auto display’; extensions are daisy-chained
< 200m
1 x Cat5 2 x 1mm2
Single apartment station per output with separately powered extensions
< 100m
1 x Cat5
150m maximum to the cable powered apartment station; daisy-chain up to 300m total.
< 300m
1 x Cat5 2 x 1mm2
All apartment stations locally powered with a 340C power supply
< 300m
1 x Cat5
Locally powered apartment stations have ‘Auto display’; extensions are daisy-chained
<25m to 340C
2 x pair of Cat5
<100m to 340C
2 x 1mm2
Door Controller to Video Controller(s)
Distance
Cable
Comments
<200m
1 x Cat5
N.B. maximum total length from any camera to any apartment station to be less than 300m Entrance to Door Controller
Connection
Distance
Cable
Comments
Entrance Panel
<50m
7 x pair of Cat5 +1 wire per button
See page 33 for detail
Lock Release up to 1A <10m
1 x pair of Cat5
<50m
2 x 1mm2
Option: Exit button
<50m
1 x pair of Cat5
Option: Trades button
<50m
1 x pair of Cat5
Requires a Time-clock
Option: Door Monitor Switch
<50m
1 x pair of Cat5
Option: Second Camera
<50m
2 x pair of Cat5
Power Supply to Controller
System
Distance
Cable
Comments
All Systems, each PS4 to BFD8 or BFD72 or BSC4
<3m
2 x 1mm2
Total length of any daisy chain <5m
2 x 1.5mm2
NB. A Cat5 cable has 4-pairs (8 cores)
For larger cable distances please contact manufacturer.
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 15 of 48
Installation & Commissioning
Checklist
The following checklist is a summary of what is required. Refer to the relevant pages for further details.
● Review the section headed ‘Safety Information’ on page 47.
● Ensure that ‘Design Considerations’ on page 9 have been understood.
Confirm that Cat5 cable has been specified.
Install the system according to instructions in this section.
Check/set the door controller jumper and switch settings.
Check/set the video controller jumper and switch settings.
Check/set each apartment station dip-switch settings.
Wiring
Refer to the diagrams from page 33 onwards as appropriate for the equipment you have. All wiring is carried out using a mixture of Cat5 for the signal wiring and 1mm² (or greater)
cores for the power wiring; refer to Page 13 for further details. It is strongly recommended that a consistent colour code be used throughout such as that indicated on the connection diagram. Certain signals must be interconnected using a twisted pair from the Cat5 cable. These are clearly marked on the connection diagram and should be strictly observed.
Entrance Panel
The panel should be mounted at an optimum height of 1.6 m, measured between the ground and the centre of the camera window. DDA considerations may reduce this height to 1.4m. With flush mounting panels it is advisable to apply mastic to the top and side edges of the panel to prevent water ingress behind the panel, but not to the bottom edge. On construction sites the panel must be protected from corrosive substances such as
‘brick acid’. The panel should be cleaned only with a damp cloth containing dilute
detergent.
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 16 of 48
Apartment Station
The tabellet is designed to be surface mounted onto a plaster or plasterboard wall using the supplied steel bracket. The optimum screen height is 1.6m however DDA considerations may reduce this height to 1.4m.
Instructions:
Warning. The heads of the countersunk screws must protrude less than 1mm or there will
be difficulty attaching the apartment station to the plate.
1) Using the bracket as a template, cut a square hole into the plasterboard ensuring that the terminal block and other components on the back of the tabellet will clear.
2) A back-box is not required, however a standard flush-mounted single gang back­box can be fitted if desired. The back box does not have to be secured to the bracket but if this is desired, it is recommended that the bracket and back box be bolted together first and then fitted to the wall as a single item.
3) Fix the bracket to the plasterboard using up to 8-off No8 (4mm) screws and suitable plasterboard plugs. Ensure that the bracket is absolutely level when fitted.
4) Fit the tabellet unit by aligning it onto the 4 hooks of the wall bracket, and then
pushing gently towards the wall and sliding the tabellet down until it “clicks” into
place.
5) The tabellet can be removed from the wall mounting box by pushing upwards until it slides off the bracket. When up far enough it will come forward and the wiring can be accessed.
Doorbell
The tabellet has a doorbell function which typically would be operated by a local, non­illuminated door push having a normally open contact.
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 17 of 48
Extension Ringer
Primarily included for activating third party DDA devices the auxiliary ring output consists of a pair of volt free contacts which close while the phone is ringing.
If the phone is muted the contacts do not close even though the phone may flash to indicate ringing.
The contact rating is 1A non-inductive load.
XL5-BS Audio Phone
The XL5-BS audio phone can be used as a lower cost alternative to an extension apartment station. The phone is manufactured in high-impact ABS plastic that imparts high durability and compliments most wall furnishings. It incorporates both mute and lock illuminated buttons and it has an Electronic Ringing Tone with an internal rotary pre-set volume control.
Remove the top cover of the XL5-BS phone, which is secured by clips, by using a screwdriver in the slots at the bottom to release the clips.
The XL5-BS audio phone should be fixed with two No 8 screws (not supplied).
Videophone (Alternative to Apartment Station)
The videophone is designed to be wall mounted onto plasterboard or other masonry at an optimum height of 1.6m. It should be fixed with three No 8 pan head screws (not supplied). Use the dimensions shown on the adjacent diagram. If the cable is to be fed from the wall cavity then make a hole for this at the same time, the surface cable exit is to the left of the cut-out. The top two screws are hidden fixings, so screw in but do not fully tighten. Test hang the videophone and adjust the screws as required.
Now remove the top cover of the videophone, which is secured by a clip at the bottom. Hang the videophone on the two screws already fitted allowing the cable (if present) to feed through and the third screw to be inserted at the bottom. Tighten the third screw.
If the silicone rubber buttons fall out, clip them back into the PCB. Before replacing the Front Cover remove the protective film from the display lens and also check that the DipSwitch settings are correct or change as necessary (see Page 27).
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 18 of 48
Electric Door Release
Both fail-secure and fail-safe lock releases (including magnetic locks) use the same
terminals. To set the lock type, refer to the ‘Door Controller Settings’. When installing lock
releases please allow a little movement on the door, as operation will be impaired if fitted too tight.
NB. Magnetic locks (maglocks) must be fitted with a suppressor at the lock terminals. Some manufacturers fit an acceptable internal suppressor.
Fail Safe Exit: Notes
Fail safe exits using maglocks require an exit button and this should be normally open so that the controller can be used to give a timed exit. If the exit button has both normally open and normally closed contacts, then the normally closed contact can be wired in series with the release or maglock along with the break glass in case of equipment failure.
A not uncommon problem with maglocks, because they cannot be mechanically overridden, is being locked out of the building due to lost codes, fobs or equipment failure. So consider an alternate building entrance, or an externally accessible secure keyswitch, or a reliable method of disabling the system during overnight secure lockup.
Fail Secure Exit: Notes
Commonly fail secure exit doors incorporate a thumb-turn, door handle or mini push bar rather than use of an exit button. Fire officers usually require a minimum of door handle or push bar to open a door on a fire exit route – not a thumb-turn.
Most fail secure locks are not continuously rated and if an electrical hold open system is used for say busy times, then a continuously rated release must be used.
Powered bolt, shoot-bolt or other more secure door locking systems may require the use of separate power supplies or a suppressor to be fitted. Shoot-bolt systems for instance tend to require at least 1.5A peak current and this will require the use of an isolation relay and a separate power supply for the lock.
Exit Button Input
The exit button is used to unlock the door for the pre-set lock operating time. The input is designed only for use with a normally open push button. ‘Exit +’ is the input and ‘Exit -’ is internally connected to 0V.
The ‘Exit +’ input can also be used for connection to other equipment to open the door as
shown in Diagram K Combined Connections bellfree With Lock.
Door Open Switch
The door open switch is used to provide an indication at the apartment station that the door has been left open. This switch can have closed contacts when the door is closed or open contacts when the door is closed, the choice being made in Panel Programming. The default of ‘contacts open when door closed’ must be selected when this feature is not required.
Time Clock Sharing
In a large system a single time clock can be shared between distributed equipment areas
by borrowing one of the ‘comm -’ wires in the interconnecting Cat5 to use as the shared “Time clock common”. See the detailed diagram on page 41.
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 19 of 48
Commissioning
The major components of the bellfree Video system are fitted with high quality pluggable screw terminal blocks. This enables all the connections to the system to be fully
completed, whilst easily isolating individual pieces of equipment during testing and commissioning.
When powering up for the first time, it is highly recommended that only the most basic system be connected. i.e. 1 tabellet apartment station, 1 door controller and panel, and 1 video controller; the remaining equipment can be isolated by unplugging terminal blocks.
NB: Ensure the 1 door and video controller remain interconnected and that the ‘end of line’ controller is terminated temporarily using the jumpers (see page 23).
Proceed to test the system by calling the apartment station from the door panel in the usual way. Any problems can be resolved by rechecking wiring and connections, assisted
by the various suggestions and tests in the section “Troubleshooting”. Once the basic
system is fully functioning, continue to reconnect and test the remaining equipment item by item until completed.
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 20 of 48
BFD8/72 Door Controller Switch Settings
Talking Time/ Apartment station Active DIP SW1 (1-4)
4 3 2 1 Talk Time
On
On
On
On
15s
On
On
On
Off
20s
On
On
Off
On
30s
On
On
Off
Off
45s
On
Off
On
On
60s
On
Off
On
Off
75s
On
Off
Off
On
90s
On
Off
Off
Off
120s
Off
On
On
On
150s
Off
On
On
Off
180s
Other settings
60s
Off
Off
Off
Off
60s*
*Default setting
Ringing Time/Call Time and Ring Effect DIP SW1 (5-8)
8 7 6 5 Call Time
Ring Cadence or Sound Effect
On
On
On
On
5s
1 in 3 – 1 ring every 3 seconds
On
On
On
Off
8s
1 in 3 – 1 ring every 3 seconds
On
On
Off
On
10s
1 in 3 – 1 ring every 3 seconds
On
On
Off
Off
15s
1 in 3 – 1 ring every 3 seconds
On
Off
On
On
20s
1 in 3 – 1 ring every 3 seconds
On
Off
On
Off
30s
1 in 3 – 1 ring every 3 seconds
On
Off
Off
On
40s
1 in 3 – 1 ring every 3 seconds
On
Off
Off
Off
45s
1 in 3 – 1 ring every 3 seconds
Off
On
On
On
50s
1 in 3 – 1 ring every 3 seconds
Off
On
On
Off
60s
1 in 3 – 1 ring every 3 seconds
Off
On
Off
On
30s
1 in 3 (Reserved For future use)
Off
On
Off
Off
30s
1 in 3 (Reserved For future use)
Off
Off
On
On
30s
2 in 15 – 2 rings, 15S silence, repeat
Off
Off
On
Off
30s
1 in 15 – 1 ring, 15S silence, repeat
Off
Off
Off
On
30s
1 in 5 – 1 ring every 5 seconds
Off
Off
Off
Off
30s*
1 in 3* – 1 ring every 3 seconds
*Default setting
SW1
SW2
SW3
(QWERGHJK)
(ASDFGHJK)
(ASDFGHJK)
OFF ↔ ON
SW1
SW2
SW3
(ASDFTYUI)
(ASDFGHJK)
(ASDFGHJK)
OFF ↔ ON
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 21 of 48
Lock Operate Time Dip SW2 (1-3)
3 2 1
Lock Time
On
On
On
3s*
On
On
Off
4s
On
Off
On
5s
On
Off
Off
6s
Off
On
On
8s
Off
On
Off
10s
Off
Off
On
15s
Off
Off
Off
20s
*Default setting
Individual Functions DIP SW2 (4-8)
SW2-4
Lock Type
Lock behaviour during power failure
*Off
Fail secure lock
Requires alternate mechanical means, key or thumb-turn to open on power failure
On
Fail safe lock
Lock opens on power failure
SW2-5
Door Status Switch
Monitors doors left open
*Off
Contacts Open when Door is Closed
The default allows for no switch fitted
On
Contacts Closed when Door is Closed
Standard normally closed switch
SW2-6
Camera 2
How many cameras at this door
*Off
Camera 1 only
Default – single camera per door
On
Enable Camera 2
Second camera at the door
SW2-7
View Function
Camera action when view symbol touched
*Off
Local View
View symbol only selects the camera(s) at this door
On
Global View (See DIP SW3 below)
View symbol sequentially selects all cameras at doors with this switch set
SW2-8
Reserved
*Off
On
*Default setting
SW1
SW2
SW3
(ASDFGHJK)
(123FGHJK)
(ASDFGHJK)
OFF ↔ ON
SW1
SW2
SW3
(ASDFGHJK)
(ASDRTYUI)
(ASDFGHJK)
OFF ↔ ON
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 22 of 48
Camera Numbering DIP SW3 (1-8)
Camera 1 at this door
Last Camera
4 3 2 1 Number
8 7 6 5
Number
On
On
On
On
*1 On
On
On
On
*1
On
On
On
Off 2
On
On
On
Off 2 On
On
Off
On 3 agama
On
On
Off
On 3 On
On
Off
Off 4
On
On
Off
Off 4 On
Off
On
On 5
On
Off
On
On 5 On
Off
On
Off 6
On
Off
On
Off 6 On
Off
Off
On 7
On
Off
Off
On 7 On
Off
Off
Off 8
On
Off
Off
Off 8 Off
On
On
On 9
Off
On
On
On 9 Off
On
On
Off
10 Off
On
On
Off
10
Off
On
Off
On
11 Off
On
Off
On
11
Off
On
Off
Off
12 Off
On
Off
Off
12
Off
Off
On
On
13 Off
Off
On
On
13
Off
Off
On
Off
14 Off
Off
On
Off
14
Off
Off
Off
On
15 Off
Off
Off
On
15
Off
Off
Off
Off
16 Off
Off
Off
Off
16
*Default setting
View Activated by User (CCTV mode)
User activation on 2-72 way system is not available.
‘Global View’ at Multiple Entrances
For information on this feature consult Bell System (Telephones) Ltd. technical department at the number shown on the last page.
BFD8/72 Door Controller Jumper Settings
Camera Terminator
There is a separate jumper for both video Camera inputs. This has three settings, 75R for terminating coaxial cable, 100R for terminating twisted pair Cat5 cable and None for use when passing the cable on to another device or controller.
Video Gain Control
The “Video Gain” jumper on door controllers should always be set to “0” unless directed by
‘Bell System Technical Support’. This jumper is only required on some systems with very
long cable runs, camera to apartment station well in excess of 150m. Inappropriate use of this jumper with short runs will cause picture problems.
Reassurance tones
DDA reassurance tones for “ringing” and “door open” are available at the door panel. The volume is adjustable from 0 using the volume control on the BFD8/BFD72 controller PCB (see diagram on page 34).
The lock tone is always active and the ring tone is activated by placing a jumper between pins 5 & 6 of the “Prog-6” pin header on the BFD8/BFD72 controller PCB, the jumper is stored between pins 1 & 2.
SW1
SW2
SW3
(ASDFGHJK)
(ASDFGHJK)
(12345678)
OFF ↔ ON
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 23 of 48
BSC4 Video Controller Settings
Jumper settings
The “Video Gain” jumper on video controllers should always be set to “0” unless directed
by Bell System Technical. This jumper is only required on some systems with very long camera to apartment station cable runs well in excess of 150m. Inappropriate use of this jumper with short runs will cause picture problems.
The “Video Terminator” jumper must be set to OFF on all but the furthest Video Controller from the Door Controller(s), this one must be set to ON.
Switch settings
SW6 is a rotary 16 position switch which sets the apartment station (Phone) addresses as per the following table. These numbers represent actual flat numbers for the digital controller; they also correspond to the inputs on the BFD8 or BFD72.
SW6 Setting
Pos
Phone 1
Phone 2
Phone 3
Phone 4
0
None
None
None
None 1 1 2 3
4 2 5 6 7
8 3 9
10
11
12 4 13
14
15
16 5 17
18
19
20 6 21
22
23
24 7 25
26
27
28 8 29
30
31
32 9 33
34
35
36 A 37
38
39
40 B 41
42
43
44 C 45
46
47
48 D 49
50
51
52 E 53
54
55
56 F 57
58
59
60
Address Offset SW7
SW7 is an 8 bit switch that is used to increase the addressing range. For each bit that is switched ON add the corresponding value to the amount set by SW6. This allows flat addresses up to 3210 to be set.
Bit
Offset
1
+1 2 +2 3 +50
4
+100
5
+200
6
+400
7
+800
8
+1600
SW6
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
Shown at 0
SW7
(QWERTYUI)
OFF ↔ ON
ATTENTION
Each SW6 MUST be set correctly for the phones to ring.
This switch is shipped set to 0 to prevent multiple phones ringing on initial installation.
Each bit on SW7 adds the corresponding amount to the address set by SW6. Do not set a total value above 9995
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 24 of 48
Odd/Even Addressing Jumper PROG pins 1-2
This jumper alters the addressing of Phone outputs 2, 3 and 4 such that they all become either odd or even numbers. So if the address of output Phone 1 is 12 say the other outputs become 14, 16 and 18. If the address were 31 then the other outputs are 33, 35 and 37.
The use of this jumper precludes the use of extended addressing by PROG pins 2-3, if both are required contact Bell System Technical. The jumper is stored on pins 4-5.
Extended Addressing Jumper PROG pins 2-3
This jumper adds +3200 to the Phone 1 address set using SW6 and SW7. Phone addresses up to 6410 (Phone 1 output) can be set. Custom versions will show the custom offset on the build label.
The use of this jumper precludes the use of Odd/Even addressing by PROG pins 1-2, if both are required contact Bell System Technical. The jumper is stored on pins 4-5.
Custom Alternate Addressing Option
Special versions of the BSC4 can be ordered to allow addressing above 6413. The value +nn00 is shown on the build label. This jumper adds +nn00 to the Phone 1 address set using SW6 and SW7The jumper is stored on pins 4-5.
For instance by a custom version Build 7+5000 would make the jumper add 5000, the BSC4 would then be able to address from 1 to 3210 and 5001 to 8210 (Phone 1 output).
The use of this jumper precludes the use of Odd/Even addressing by PROG pins 1-2, if both are required contact Bell System Technical. The jumper is stored on pins 4-5.
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 25 of 48
Door Speech Volume Adjustment
Introduction
The speech level heard by a caller at the door is adjustable by use of three pushbuttons on the BFD8/72 door controller. This is useful if the door is on a noisy street, or alternatively in a quiet location. Speech gain in the other direction is fixed.
Method
To perform volume adjustment, first borrow the jumper from Prog-6 and place it on the two pin header ZLK. The Yellow Speech LED should light.
WARNING. A power fail during a Save may require the unit to be returned to Bell System for reprogramming. Do not perform volume adjustment without the jumper in place.
8 presses of Vol+ doubles the volume level and 8 presses of Vol– halves it. Pressing Save stores the new value. Increasing the volume too far will make speech less stable and there will be a tendency for feedback – intermittent screeching and howling. If this happens press Vol– four times and Save and test again.
The new level is tested by ringing one or more apartment stations and talking to them. Finally return the jumper to its original location on Prog-6.
5 6 7 831
VideoCamera 1 Camera 2 Video
Exit
Call Buttons
Commn
12V12V
Audio Audio
Door
Data Data
Lock
Commn
42
bell
BFD8/72
free
Enhanced Speech
Door Controller
DDA
Power
Input Output
Status
1
1
Prog-6
ZL Prog
Vol+
Speech
Vol-
Panel
Speaker
Save
Lock
Power
Test
SW1
Off-On Off-On Off-On
SW2 SW3
Cam2
Audio
Video
100
75
High
100
75
High
Cam1 Cam2
4 3 2 1 0
Video
Gain
Label BFD8/72
Version No
Build No
Panel Tone Volume
bell
System
© 2010
2 2M M 1 1S S B BA A
– –
+ + + +
+++
Speech Unit
PM
12V
SPKR
LS LL LC
LRB1B2
+ + + + +
ZLK
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 26 of 48
tabellet Apartment Station Switch Settings
Mute Time Setting SW (1-4)
1 2 3 4 Mute Time
On
On
On
On
Disabled¹
Off
On
On
On
2 minutes
On
Off
On
On
5 minutes
Off
Off
On
On
10 minutes
On
On
Off
On
15 minutes
Off
On
Off
On
20 minutes
On
Off
Off
On
30 minutes
Off
Off
Off
On
45 minutes
On
On
On
Off
1 hour
Off
On
On
Off
2 hours
On
Off
On
Off
4 hours
Off
Off
On
Off
5 hours
On
On
Off
Off
6 hours
Off
On
Off
Off
8 hours
On
Off
Off
Off
10 hours
Off
Off
Off
Off
*Indefinite²
*Default setting¹Disabled means touching the mute symbol has no effect. ²Indefinite; the mute is cancelled by touching the symbol again.
Individual Functions DIP-SW (5-8)
SW-5
Master / Extension
Which Apartment Station to set
*Off
Master
Only or first apartment station per BSC4 output.
On
Extension / Slave
Second and subsequent apartment stations per BSC4 output.
SW-6
Auto Display on Ring
Apartment Station display behaviour
*Off
Display during ring
Picture is on while ringing, stays on when answered.
On
No display during ring
Picture is off while ringing, comes on when answered.
SW-7
Spare
Spare
*Off
On
SW-8
Spare
Spare
*Off
On
*Default setting
Video Terminator Jumper Setting
The jumper is situated next to the input connector. It is 3 pin and labelled On and Off. The jumper should be on when there is only one apartment station on an individual BSC4
output. Otherwise only the last apartment station should have a jumper set to On the rest being set to Off.
SW
(QWERGHJK)
OFF ↔ ON
SW
(ASDFTYUI)
OFF ↔ ON
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 27 of 48
BS Videophone Switch Settings
Mute Time Settings (1-4)
4 3 2 1 Mute Time
On
On
On
On
Disabled¹
On
On
On
Off
2 minutes
On
On
Off
On
5 minutes
On
On
Off
Off
10 minutes
On
Off
On
On
15 minutes
On
Off
On
Off
20 minutes
On
Off
Off
On
30 minutes
On
Off
Off
Off
45 minutes
Off
On
On
On
1 hour
Off
On
On
Off
2 hours
Off
On
Off
On
4 hours
Off
On
Off
Off
5 hours
Off
Off
On
On
6 hours
Off
Off
On
Off
8 hours
Off
Off
Off
On
10 hours
Off
Off
Off
Off
*Indefinite²
*Default setting¹Disabled means touching the mute symbol has no effect. ²Indefinite; the mute is cancelled by touching the symbol again.
Individual Functions Settings (5-8)
SW-5
Master / Extension
Which Videophone to set
*Off
Master
Only or first apartment station per BSC4 output.
On
Extension / Slave
Second and subsequent videophones per BSC4 output.
SW-6
Auto Display on Ring
Videophone display behaviour
*Off
Display during ring
Picture is on while ringing, stays on when answered.
On
No display during ring
Picture is off while ringing, comes on when answered.
SW-7
Spare
Spare
*Off
On
SW-8
Spare
Spare
*Off
On
*Default setting
Video Terminator Jumper Setting
The jumper is situated above the input connector. It is 3 pin and labelled On and Off. The jumper should be on when there is only one videophone on an individual BSC4
output. Otherwise only the last videophone should have a jumper set to On the rest being set to Off.
Settings
(QWERGHJK)
OFF ↔ ON
Settings
(ASDFTYUI)
OFF ↔ ON
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 28 of 48
Troubleshooting
Common Faults
A very high percentage of calls to our technical support number, regarding new installations, are resolved to faulty wiring. The reasons for these are various: -
Broken cores, especially short links, sometimes broken inside the insulation! Connectors clamped onto the insulation instead of copper. Wire in the wrong side of a rising clamp connection, the clamps need to be unscrewed
far enough to stop the wire going “underneath”. Shorts or opens due to cables having been stapled or nailed through. A common fault is wiring a connector left to right instead of right to left, or one or more
twisted pairs the wrong way round.
Tip. The heads of screws on connectors are not a reliable means of making a connection with a meter, try pushing the probe into the wire entry point.
Quick Fault Reference
These tables provide a quick indication of the possible fault.
Power Problems
Apartment station resetting (The three indicators lights show the power on sequence).
Power supply intermittent short or overload. More than 1 extension enabled for auto display. Lock output short-circuit; see ‘Lock Problems’
28V LED does not light on controller.
Temporarily remove connection to 28V+ output. If it
now comes on there is a short on the apartment station wiring.
12V input connections are reversed.
PS4 output voltage fluctuating, meter reading unstable.
Output overload is causing current limit to operate,
check grouping of controllers to power supplies, see page 11 for details
See Lock Problems below
Call Problems
Apartment station does not ring or flash when called
No power to apartment station; check that red
lamp illuminates when mute is touched.
Data wiring has a fault, Data A or Data B
connection broken.
0V to controller missing on separately powered
apartment station.
Pushbutton wiring error, try short length at
controller.
No extension apartment station rings or flashes when called
Data wiring has a fault, Data A or Data B
connection broken.
Green Lock light on apartment station flashes once when called
Apartment station set to extension with no
master present or responding.
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 29 of 48
BSC4 Video Controller Tests
When the system is idle (no calls in progress) pressing the ‘Test’ button activates the ‘Audio On, ‘Status’ and one of the ‘Select n’ LED’s for 3S. If the system is not idle (Version
2 only) pressing the ‘Test’ button will cause a system wide reset. There are 4 green LED’s which indicate power to the individual apartment stations, on
board fuses will operate if a short exists.
The BSC4 also has 4 ‘Phone’ test buttons which can be used to verify the ‘data’ connection to the apartment station. Pressing the ‘Test Phone n’ button should cause the apartment station and extensions, if any, to ring and the associated ‘Select n’ Led to light.
Touching pickup or touching view will cause the ‘Audio On’ and ‘Select n’ LED’s to light. There will be no audio as no door panel is active. The display on the apartment station will light up to grey or blue unless the video camera is directly wired to the BSC4 input.
Touching pickup again will cause all the LED’s to extinguish. Touching the lock symbol instead will cause the ‘Status’ LED to light and after 3S all the LED’s will go off.
If this sequence works repeatedly then the A and B data connections are probably OK. and the +28V and 0V must also be OK. The test also shows that the BSC4 software is running and diagnostics can now focus on the door controller to video controller wiring.
If it fails an apartment station can be connected locally with a short cable to eliminate the cable being faulty.
Lock Release Problems
Lock release does not operate or clicks but does not open.
Connections to Lock Release are open or shorted. Voltage drop due to cable too thin. Lock current is too high; Power supply is resetting. Lock release jammed due to over tight fitting.
Maglock does not hold strongly.
Voltage drop due to cable too thin.
TEST:
Press ‘Test’ Button on Door
Controller (when system idle):
Confirm ‘LOCK’ LED illuminates for 3 seconds. Check Output Voltage at LOCK terminals.
Lock release operates all the time or in reverse.
Check fail safe/fail secure SW2-4 selection matches
the lock type.
Normally closed switch has been used for exit button.
Lock operates from the exit button but not the test button or apartment station.
Normally closed switch has been used for exit button.
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 30 of 48
Video Problems
Blank picture when: ­Calling apartment station or touching view
Broken or missing Video + or Video -
connection.
Cameras incorrectly configured refer to SW2-6
settings on page 21
Call is from an audio only panel.
No picture when calling apartment station
Check auto display switch is on. See page 26
No picture when touching view
CCTV not available on multi-way systems.
Touching view locks up system
Ensure BFD8/72 SW2-8 is OFF
Repeated touching of view does not select cameras in sequence as expected.
Check SW2-6 at all entrances is set for correct
number of cameras at that entrance
Check settings for SW3 if SW2-7 is enabled See section ‘Global View’ on page 22
Unstable picture
Power supply voltage low. Terminator switch not set on last apartment
station.
Too many terminator switches set on. Video gain jumper set to high on a short run. Very bright area in background upsetting
camera.
Unstable picture possibly with areas looking like a photographic negative.
Video + and Video - reversed, or M and S
reversed.
Entrance cannot be seen at night
Power not connected to camera IR night
illumination. Connect 1 to + on camera.
Speech Problems
Loud tone at the entrance speaker. (Acoustic feedback)
Broken Audio 1 or Audio 2 connection. Intermittent or broken Data A or Data B connection. Apartment station has reset; see the power faults table.
No speech from apartment station to entrance
Missing or Broken Spkr + or Spkr - connection.
No speech from entrance to apartment station
Missing or Broken PM + or PM - connection.
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 31 of 48
Specifications
BFD8/72 Door controller
Size
BFD8: 185mm x 230mm x 42mm BFD72: 360mm x 240mm x 40mm
Supply Voltage
10.8V min, 13.8V typical, 15V max
Current Consumption
80mA idle @13.8V, 250mA active includes speech not cameras
Model CAMBS-C Colour Camera
Size
60mm x 57mm x 31mm
Supply Voltage
10V d.c. minimum, 15V d.c. maximum
Current consumption
175mA maximum without IR 215mA maximum with IR (Link 1 to +)
Image Device
1/3” CCD
Sensitivity
0.01 lux, auto switching to B/W in low light levels
Minimum Focus
100mm
Viewing Angle
92º (typical)
Video Output
PAL composite video 1Vpk-pk (75 Ohm)
Resolution
More than 330 lines
Back light compensation
Yes
BSC4 Video Controller
Size
185mm x 230mm x 42mm
Supply Voltage
10.8V min, 13.8V typical, 15V max
Current Consumption
350mA idle, 3A max @13.8V
tabellet Colour Apartment Station
Size
144mm x 202mm x 50mm (20mm When flush)
Fixing
Wall Mounted – Surface or Flush
Supply Voltage
11V minimum – local power supply only. 20V to 28V typical
Current Consumption
25mA @28V idle, 375mA @ 11V active
Buzzer Mute Time
Disabled, 1minute through 10 hours, indefinite
BS Colour Videophone
Size
180mm x 225mm x 60mm
Fixing
Wall Mounted
Supply Voltage
11V minimum – local power supply only. 20V to 28V typical
Current Consumption
25mA @28V idle, 375mA @ 11V active
Buzzer Mute Time
Disabled, 1minute through 10 hours, indefinite
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 32 of 48
Model XL5-BS Phone
Size
235mm x 105mm x 25mm
Supply Voltage
10V d.c. minimum, 30V d.c. maximum
Current consumption
20mA idle, 67mA ringing @13.8V
Model BF-AMP Speech Unit
Size
98mm x 60mm x 24mm
Supply Voltage
10.5V d.c. minimum, 15V d.c. maximum
Current consumption
250mA d.c. maximum
PS4 Power Supply
Size
236mm x 105mm x 81mm
Output Voltage (regulated)
13.5V d.c. min, 13.8V d.c. nom, 14.1V d.c. max
Output Current
3A continuous, 4A peak (5 minutes max)
Mains Supply Internal Fuse
Not user replaceable
Supply Voltage
230V 50Hz nominal
Temperature Range
0 ºC to 50 ºC
340C Power Supply
Size
140mm x 60mm x 53mm
Output Voltage (regulated)
13.5V Min, 13.8V Nom, 14.1V Max
Output Current
1A continuous, 1.5A peak (5 minutes max)
Mains Supply Internal Fuse
Not user replaceable
Supply Voltage
230V 50Hz nominal
Temperature Range
0 ºC to 50 ºC
840 Power Supply – Battery Backed
Size
350mm x 330mm x 80mm
Output Voltage (regulated)
13.5V Min, 13.8V Nom, 14.1V Max
Output Current
3A continuous, 4A peak (5 minutes max)
Mains Supply Internal Fuse
T2A 20mm HBC (HRC) Ceramic
Battery Fuse
F4A 20mm Glass
Supply Voltage
230V 50Hz nominal
Temperature Range
0 ºC to 50 ºC
BSSW Gate Switcher / Block Isolator
Size
185mm x 230mm x 42mm
Supply Voltage
10.8V min, 13.8V typical, 15V max
Current Consumption
80mA idle, 210mA max @13.8V
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 33 of 48
Diagram A – 2-72 Way Basic System Wiring Overview
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 34 of 48
Diagram B – BFD8 PCB Detail
5 6 7 831
VideoCamera 1 Camera 2 Video
Exit
Call Buttons
Commn
12V12V
Audio Audio
Door
Data Data
Lock
Commn
42
bell BFD8/72
issimo
Enhanced Speech
Door Controller
Door Panel
DDA
Entrance
Power
Input Output
Status
1
1
Prog-6
HF Prog
Vol+
Speech
Vol-
Panel
Speaker
Save
Lock
Power
Test
SW1
Off-On Off-On Off-On
SW2 SW3
Cam2
Audio
Video
100
75
High
100
75
High
Cam1 Cam2
4 3 2 1 0
Video
Gain
Label BFD8
Version No
Build No
Panel Tone Volume
bell
System
© 2010
2 2M M 1 1S S B BA A
– –
+ + + +
+++
Speech Unit
PM
12V
SPKR
LS LL LC
LRB1B2
+ + + + +
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 35 of 48
Diagram C – 2-72 Way Basic System Wiring Detail
3 4 5 6
Trades
(optional)
12V
LS
Spkr
LL LCB2B1
Speech Unit
Call Buttons
DDA
LR
PM
Camera Inputs
Entrance
Power
Supply
Cat5 Input Cat5 Output
Door Panel
Lock wiring options Lock 0.5A 1.0A 12m 1 pair 1 pair 25m 1 pair 2 pair 50m 2 pair 4 pair 50m 2x1mm² 2x1mm²
BFD8/72
Door Controller
Door Panel
Brn
Brn
W/Brn
W/Brn
Org
Org
W/Org
W/Org
Grn
Grn
W/Grn
W/Grn
Blu
Blu
Red Black
W/Blu
W/Blu
Lock
Exit button or
Fire Switch
(optional)
Door Monitor
Switch
(optional)
2 x 1mm²
+
CO
NO NC
TS2000
Time Clock
(Optional)
230V
Mains
PS4
Power Supply
12V
+
CAMBS
Camera
(Optional Link
For Infra Red
Lamp)
S
1
M
+
From
previous
controller
To Next
Controller
12V Spkr
+
+
+
+
+
+
+
PMMic
BF-AMP
Speech Unit
Panel
Mic
2
63 7 84 5
1
Brn
Brn
W/Brn
W/Brn
Grn pair
Grn pair
Blu
Blu
W/Blu
W/Blu
All signal cable MUST be Cat5
See "Cable Specification"
Cat5 4 twisted pairs data cable.
One pair in the Cat5 cable
This symbol is used to indicate
where a twisted pair
connection must be used
Brn
W/Brn
Org
W/Org
Grn
W/Grn
Blu
W/Blu
2 2M M 1 1S S B BA A
VideoCamera 1 Camera 2 Video 28VAudio AudioData DataCommn
+ + + +
Exit 12V12VDoor Lock
+ + + + +
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 36 of 48
Diagram D – BSC4 PCB Detail
28V Generator
Input
Power 1 Power 2 Power 3 Power 4
Passthru
Status
Test
Test
Phone 1
Phone 1 Phone 2 Phone 3 Phone 4
Test
Phone 2
Test
Phone 3
Test
Phone 4
Audio on
Select 1 Select 2 Select 3 Select 4
OFF ON
Video
Termination
4 3 2 1 0
Video
Gain
Label BSC4
Version No
Build No
1
Prog
Power
Supply
SW7
Off-On
SW6
1 2 3 4 5 6 7 8
+1 +2
+50 +100 +200 +400 +800
+1600
Set Phone Address
Then Add values below to get address
0 = AD Mode
1 = 1, 2, 3, 4
2 = 5, 6, 7, 8
: : : : : :
F = 57,58,59,60
2
2
2
2
2
2
1
1
1
1
1
1
B
B
B
B
B
B
A
A
A
A
A
A
++
Video
Video
Video
Video
Video
Video
12V12V
Audio
Audio
Audio
Audio
Audio
Audio
Data
Data
Data
Data
Data
Data
28V
28V
28V
28V
Commn
Commn
+
+
+
+
+
+
+
+
+
+
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 37 of 48
Diagram E – BSC4 Wiring Detail
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 38 of 48
Diagram F – Large system Overview
Illustration of Power Supply Distribution
PS4 12V
PS4 12V
PS4 12V
Door
Panel
Door
Panel
Door
Panel
Further
Entrances
Further
Controllers
Cat5
Cat5
Cat5
Cat5
Cat5
Cat5
Cat5
2 x 1mm²
2 x 1mm²
Input
Passthru
Input
Passthru
Input
Passthru
Input
Passthru
Output
Input
Output
Input
Output
Input
2 x 1mm²
2 x 1mm²
2 x 1mm²
2 x 1mm²
2 x 1mm²
x 4
Monitors
x 4
Monitors
x 4
Monitors
x 4
Monitors
BFDxxx
Controller
BFDxxx
Controller
BFDxxx
Controller
BSC4...
Controller
BSC4...
Controller
BSC4...
Controller
BSC4...
Controller
Detailed Wiring and
Power Supply
Calculations
are in Manual
Correct
Video
Operation
Requires
This
Daisychain
Wiring
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 39 of 48
Diagram G – Extension Apartment station Wiring
When additional power cores are required replace the Blu and W/Blu wires with the additional wires
Note. For each cable run :-
Only one unit must be Master (Recommend the first unit) Auto display on one video unit only (For auto display on multiple video units see next
Diagram)
Extension video units must be "daisy chain" wired to preserve video quality The last (or only) video unit on the cable requires the Video Terminator "ON" all other
video units must have the Video Terminator "OFF"
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 40 of 48
Diagram H – Apartment station Local Power Wiring
Where more than one extension video unit is required to provide "auto display" then additional power supplies will be required
Note. For each cable run :-
Only one unit must be Master (Recommend the first unit) Extension video units must be "daisy chain" wired to preserve video quality The last (or only) video unit on the cable requires the Video Terminator "ON" all other
video units must have the Video Terminator "OFF"
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 41 of 48
Diagram I – Camera Sharing & Time Clock Sharing
Camera Termination Options
Cameras may be wired in either twisted pair or coax and shared with other equipment.
Time Clock Sharing
A time clock can be shared between distributed equipment areas by borrowing one of the
‘comm -’ wires in the interconnecting Cat5 to use as the shared “Time clock common”. The “Time clock common” signal is sharable across all Bell controller types.
M
M M
MS
S S
S
Camera 1 Camera 1
Camera 1 Camera 1
+
+ +
+
Twisted Pair Through Connection
Door Controller Door Controller
Door ControllerDoor Controller
From other
equipment or Camera
From other
equipment or Camera
To other
equipment
To other
equipment
From
Camera
From
Camera
Coax Through Connection
Twisted Pair Termination
Coax Termination
100
75
High
100
75
High
100
75
High
100
75
High
Cam1
Cam1 Cam1
Cam1
22 11 BB AA
++
Controller Controller
Control
Area 2
Equipment
Control
Equipment
Area 1
Blu
Time Clock
Common
Time Clock
Common
Wire "Time Clock Common"
as if time clock is Local
Blu
W/Blu
W/Blu
Cat5
VideoVideo CommnCommn AudioAudio DataData
+
CO
NO
NC
TS2000
Time Clock
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 42 of 48
Diagram J – 2-72 Way Additional DDA Wiring
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 43 of 48
Diagram K – Combined Connections bell
free
With Lock
Connecting a Bell PAX1 Proximity Reader
Connect the lock release as per this manual. Leave the Proximity Reader set to
fail secure, the BFD controller sets the lock type.
Use a lock time card to reduce the lock time to 1 or 2 seconds, otherwise the
PAX1 will extend the bellfree lock time to 7 seconds. Lock time cards are in all Fob packs except the starter pack.
Note 1. A normally open exit button can still be wired to the BFD controller in addition to
the proximity wiring. Alternatively the exit button can be wired to the proximity reader
ACT 1000/2000/3000 Proximity Controller or 100e/200e Extender
The lock output on an ACT controller is a volt free relay contact, so as long as it is not used for another purpose it can be directly connected to the exit input of a
bellfree door controller. A 2 wire interface is shown, but if a common 12V supply is in use then the Exit-
input may be left unconnected and the corresponding ACT relay connection can be connected to a local 0V terminal.
bellfree
Door
bellfree
Door
bellfree
Door
Exit
Exit
PAX1
Proximity
Reader
PAX1
Proximity
Reader
+
+
12V
12V
+
+
Lock
Lock
Exit
Exit
OV
OV
+12V
+12V
+
+
Z
Z
O
O
H
H
C
C
Exit button
(Optional)
Exit button
(Optional)
NO
C
NC
Exit
+
ACT
OP1 or
Relay 1
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 44 of 48
Diagram K – Continued
Connecting a Bellcode Coded Access Controller
Connect the lock release as per this manual. Leave the Bellcode controller set
to fail secure, the BFD controller sets the lock type.
See "Bellcode Manual inc CK200 CS109 (PD-078)" for the other installation and
setting instructions.
Note 1. A normally open exit button can still be wired to the Bellcode unit in addition to
the bellfree wiring.
Note 2. A “12V-” connection will be required if the 2 units are not sharing a power
supply.
Taking an Output From a Third Party System
For 12V a.c. systems use an 88 relay and for 12 d.c. systems use an 89 relay. For systems with other lock voltages, a relay with a suitably rated coil will be required.
For systems with a fail safe output the common and normally closed contacts will be required.
bellfree
Door
bellfree
Door
Exit
Bellcode
200
Controller
+
Lock
+
Exit button
(Optional)
SupplySupply
Third Party
Controller
Lock
Coil Coil
Com NO NC
88/89 Relay
+
Exit
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 45 of 48
Diagram L – Combined Connections Third Party Lock
Connecting a Bell PAX1 Proximity Reader
The bellfree door controller is set to fail secure. The diagram assumes a common power supply, if not an extra wire will be required to connect the PAX1 Exit O to the
bellfree 12V-. N.B. The power wiring to the PAX1 must be able to carry the lock current with less
than 2V voltage drop.
ACT 1000/2000/3000 Proximity Controller or 100e/200e Extender
Notes
1. Connect the lock release or Maglock using the ACT Manuals.
2. Leave the bellfree controller set to Fail Secure regardless of the type of release used.
3. A normally open exit button can still be fitted to the ACT controller in addition to the bellfree wiring.
4. If the 2 units are not sharing a power supply, then a connection from bellfree controller Exit- to ACT 0V will be required.
5. Look for the notes on the ACT installation diagram concerning the use of links when the door contact is not used and when a power supply without power fail is not used.
bellfree
Door
bellfree
Door
PAX1
Proximity
Reader
Exit button
(Optional)
Exit Z Exit O
Z O
+
Lock
Exit button
(Optional)
Supply
IP3 IP2 IP1 0V OP2 OP3
Lock
+
ACT
Push button Door contact Aux input
Exit
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 46 of 48
Diagram L – Continued
Connecting a Bellcode Coded Access Controller
The bellfree door controller is set to fail secure. The Exit- to Exit- wire is only needed if the two units do not share a common
power supply.
Opening a Gate or Locks on Third Party Systems
The bellfree door controller is set to fail secure. Use COM and NO or COM and NC as required for the gate controller or third
party access system.
bellfree
Door
bellfree
Door
Exit
Bellcode
200
Controller
+
Lock
+
Exit
Lock
+
Coil Coil
Com
NO NC
89 Relay
Volt Free Contacts
For Gate
ETC.
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 47 of 48
Safety Information and Declarations
Connections to the 240VAC mains supply must be carried out by a qualified electrician or similar competent person, and made in accordance with current legislative requirements. A two-pole switch (as provided by a Consumer Unit or Switch-Fuse) must be included to isolate both Live and Neutral during Installation or Maintenance. The circuit must be protected by a fuse or other current-limiting device, rated according to the capacity of the cable used, up to a maximum of 10A. Use only mains cable to BS6004 or equivalent, within the following specified limits:
Min
Max
Conductor Diameter
1.0mm (0.8mm2)
2.25mm (4mm2)
Cable Diameter
4.0mm
8.0mm
Model 840 Power Supply (with battery standby)
The Model 840 power supply must be placed in a protected indoor environment such as an electrical cupboard. It must be secured to the wall with adequate fixings so that there is no possibility of it falling. The lead-acid battery for the standby power supply is shipped in separate packaging. It should only be connected once the system has been fully tested. Connection is made by 2 leads with spade terminals; observe the correct polarity – red to positive, black to negative. Care must be taken to ensure that the terminals of the battery are not shorted together by metal objects, as this may constitute a Fire Hazard. The Control Cabinet is IP55 rated (to exclude dust) and is vented to avoid the build-up of gases. Do not block any vents that may be apparent.
A good mains safety earth must be connected to the cabinet housing the power supply Where the power supply is fitted with a replaceable internal mains fuse and or battery fuse,
always replace with the same type as indicated on the power supply. The fuse must be approved to BS EN 60127 or equivalent.
Power Supply Model
Mains Fuse (Time Delay)
Battery Fuse (Quick Blow)
840
T2A 20mm HBC (HRC) Ceramic
F4A 20mm Glass
Model PS4 and 340C Power Supplies
These power supplies must be wall-mounted onto plasterboard, or a similar non­conductive material, in a protected indoor environment such as an electrical cupboard.
When fitting the power supply cable (both mains and low voltage) ensure the cable entry cut-outs in the enclosure lid are no larger than necessary for the cable diameter used and under no circumstances must they be taken beyond the outer cut-out zones.
tabellet Apartment Station 2-72 Way System
PD-307 Issue 2 Installation and Operating Manual Page 48 of 48
Bell System (Telephones) Ltd.
Presley Way, Crown Hill, Milton Keynes MK8 0ET.
Tel: 01908 261106 (Sales and Technical Support) FAX: 01908 261116
E-mail: sales@bellsystem.co.uk technical@bellsystem.co.uk Website: www.bellsystem.co.uk
Standards
This product complies with European directive 2004/108/EC on Electromagnetic Compatibility and Low Voltage Directive 2006/95/EC. Emissions: Generic BSEN 61000-6-3 Immunity: Generic BSEN 61000-6-1 Low Voltage: Generic BSEN 60950
BS EN ISO 9001:2008 Certificate number GB2000389
Loading...