Bell & Gossett VSX, VSH, VSC, VSCS Instruction Manual

INSTRUCTION MANUAL
P5002169 REVISION E
INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.
Series VSX VSH, VSC®, and VSCS® Models Centrifugal Pumps
TABLE OF CONTENTS
INTRODUCTION .............................................................. 1
DESCRIPTION PUMP APPLICATION
OPERATIONAL LIMITS ................................................ 1
Maximum Suction Pressure ................................... 1
Maximum Working Pressure ................................. 1
SEAL OPERATING LIMITS ........................................... 1
Mechanical Seals .................................................... 1
Packing ..................................................................... 1
PUMP IDENTIFICATION .............................................. 2
SAFETY INSTRUCTIONS ............................................. 3
ADDITIONAL SAFETY INSTRUCTIONS ..................... 4
Electrical Safety ....................................................... 4
Thermal Safety ........................................................ 4
Mechanical Safety ................................................... 4
GENERAL INSTRUCTIONS
PURPOSE OF THE MANUAL ...................................... 5
RECEIVING THE PUMP ................................................ 5
STORAGE REQUIREMENTS ........................................ 5
SAFE HANDLING REQUIREMENTS ........................... 5
LOCATION .................................................................... 7
Important ................................................................. 7
FOUNDATION .............................................................. 7
BASE PLATE SETTING ................................................. 8
Optional Grouting .................................................. 8
ROTATION .................................................................... 8
COUPLING ALIGNMENT ............................................ 8
To align using straight edge and calipers ........... 9
To align using dial indicator ................................ 10
Final Alignment ..................................................... 12
SUCTION AND DISCHARGE PIPING ....................... 12
Suction Piping ....................................................... 13
Valves in Suction Piping ....................................... 14
Discharge Piping .................................................. 14
Pressure Gauges ................................................... 15
Pump Insulation .................................................... 15
PUMP SEALING .......................................................... 15
Mechanical Seals .................................................. 15
Packing ................................................................... 15
VEE-CUT IMPELLER TRIMS ....................................... 16
OPERATION
FLUSHING ................................................................... 18
FILLING ....................................................................... 18
PRIMING...................................................................... 18
PRE-START CHECKS .................................................. 18
STARTING ................................................................... 19
OPTIONAL CHECKLIST FREEZE PROTECTION
FIELD TESTS ............................................................... 19
MAINTENANCE
GENERAL MAINTENANCE AND PERIODIC INSPECTION LUBRICATION
Pump Bearings ...................................................... 20
Couplings .............................................................. 20
SEAL INFORMATION................................................. 20
Mechanical Seals
Packing (Non-Asbestos)
MAINTENANCE OF FLOOD DAMAGED PUMPS ....21
.............................................................. 1
................................................... 1
............................................. 5
.................................................................... 18
............................................. 19
............................................... 19
............................................................. 20
............................................................... 20
............................................................ 20
.................................................. 20
....................................... 20
TROUBLESHOOTING .................................................... 22
GUARDS
SERVICE
NOTE: The information contained in this book is
intended to assist operating personnel by providing information about the characteristics of the purchased equipment. It does not relieve the user of their re­sponsibility of using accepted engineering practices in the installation, operation, and maintenance of this equipment.
For additional questions, contact
BELL & GOSSETT (847) 966-3700
http://www.bellgossett.com
.......................................................................... 24
ANSI/OSHA COUPLING GUARD
REMOVAL/INSTALLATION
Removal ................................................................. 24
Installation ............................................................. 24
BRACKET GUARDS .................................................... 25
........................................................................... 26
GENERAL DISASSEMBLY PROCEDURES ................ 27
SHUTDOWN ............................................................... 27
DISASSEMBLY PROCEDURE TO REMOVE BEARING
FRAMES – ALL PUMPS .................................... 27
DISASSEMBLY PROCEDURE TO REMOVE
STANDARD MECHANICAL SEALS ................ 28
DISASSEMBLY PROCEDURE TO REMOVE
STUFFING BOX AND PACKING ..................... 29
DISASSEMBLY PROCEDURE TO REMOVE
CARTRIDGE SEALS .......................................... 29
DISASSEMBLY PROCEDURE TO REMOVE
COVERPLATES AND SHAFT ASSEMBLY –
ALL PUMPS ....................................................... 30
ASSEMBLY PROCEDURE TO INSTALL
COVERPLATES AND SHAFT ASSEMBLY –
ALL PUMPS ....................................................... 30
ASSEMBLY PROCEDURE TO INSTALL STANDARD
MECHANICAL SEALS ...................................... 32
ASSEMBLY PROCEDURE TO INSTALL STUFFING
BOX AND PACKING ........................................ 33
ASSEMBLY PROCEDURE TO INSTALL CARTRIDGE
SEALS ................................................................ 33
ASSEMBLY PROCEDURE TO INSTALL BEARING
FRAMES – ALL PUMPS .................................... 34
GENERAL ASSEMBLY INSTRUCTIONS .................... 35
TO CHANGE ROTATION .......................................... 36
TO CHANGE STANDARD MECHANICAL SEALS ... 37
TO CHANGE CARTRIDGE SEALS ............................ 37
TO CHANGE THE PACKING OR SLEEVE ................ 37
ORDERING PARTS ..................................................... 37
DEALER SERVICING .................................................. 37
............................. 24
INTRODUCTION
DESCRIPTION
The Series VSX centrifugal pumps are frame­mounted pumps that feature high efficiency, rugged construction, compact design, foot­mounted volute, alignment-friendly coupling, and unitized seals. These features, along with the vertically split case make installation, operation, and service easy to perform.
WARNING: This product can expose you to chemicals including Lead, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to: www.P65Warnings.ca.gov.
PUMP APPLICATION
The standard Series VSX centrifugal pump’s bronze fitted c
onstruction makes it ideal for service with the following liquids: hydronic cooling or heating, boiler feed water, condensate, pressure boosting, general pumping, unheated domestic and fresh water, and benign liquids.
For other applications contact your local Bell &
sett representative.
Gos
OPERATIONAL LIMITS
Unless special provisions have been made for your pump by Bell & Gossett, the operational limits
for Series VSX pumps are as follows:
Maximum Suction Pressure
Table 1 shows the maximum suction pressures allowed for pump size and seal type:
Table 1: Maximum Suction Pressures
Unitized Seal Balanced Seal
2” Seal Sizes
4x6x10.5 5x6x10.5 5x6x13.5 6x8x10.5 6x8x13.5 8x10x10.5
2.5” Seal Sizes
8x10x13.5 10x12x10.5 10x12x13.5
3” Seal Sizes
12x14x13.5 14x16x13.5
3.5” Seal Sizes
12x14x17.5
175 psi 300 psi
175 psi 300 psi
160 psi 300 psi
125 psi 300 psi
SEAL OPERATING LIMITS
Mechanical Seals NOTE: For
use on closed or open systems that are relatively free of dirt and/or other abrasive particles.
°
Unitized EPR/Car/SiC: 0
F to 300°F
Temperature range; 6.5 to 8.5 pH range
°
Unitized Viton/Car/SiC: 0
F to 225°F
Temperature range; 6.5 to 8.5 pH range
°
Unitized EPR/Graphite Loaded SiC: 0
°
F Temperature range; 7 to 12.5 pH range
300
Balanced EPR/Graphite Loaded SiC: 0
°
F Temperature range; 7 to 12.5 pH range
300
Balanced Viton/Graphite Loaded SiC: 0
°
F Temperature range; 7 to 12.5 pH range
225
CAUTION: Equipment Damage
F to
°
F to
°
F to
To prevent premature seal failure or possible injury, the unitized seals should not be used as an alternate or substitute for the balanced seals installed in a high suction pressure rated VSX pump.
Failure to follow these instructions could result in serious property damage and/or moderate personal injury.
Packing NOTE: For use on open or closed systems
that require a large amount of makeup water, as well as systems that are subjected to widely varying chemical conditions and solids buildup.
Braided Graphite PTFE: 0°F to 200°F Temperature range; 7 to 9 pH range
Maximum Working Pressure
Listed on pump nameplate.
1
PUMP IDENTIFICATION
Bell & Gossett pumps are designated by a series of numbers such as Series VSX, Model VSH, VSC, or VSCS. The pump nameplate gives identification and rating information as shown in Figures 1 and 2.
Permanent records for this pump are referenced by the serial number and it must be used with all correspondence and spare parts orders.
Figure 1: Rating Plate
Figure 2: Suction Limitation
2
ADDITIONAL SAFETY INSTRUCTIONS
Electrical Safety
WARNING: Electrical Shock Hazard
Electrical connections to be made by a qualified electrician in accordance with all applicable codes, ordinances, and good practices.
WARNING: Rotating Components Hazard
Do not operate the pump without all guards in place.
Failure to follow these instructions could result in serious personal injury or death, or property damage.
WARNING: Electrical Overload Hazard
Three-phase motors must have properly sized heaters to provide overload and under voltage protection. Single-phase motors have built-in overload protectors.
Failure to follow these instructions could result in serious personal injury or death, or property damage
Thermal Safety
WARNING: Extreme Temperature Hazard
If pump, motor, or piping are operating at extremely high or low temperatures, guarding or insulation is required.
Failure to follow these instructions could result in serious personal injury or death, or property damage.
Mechanical Safety
WARNING: Unexpected Startup Hazard
Failure to follow these instructions could result in serious personal injury or death, or property damage.
WARNING: Excessive System Pressure
Hazard
The maximum working pressure of the pump is listed on the nameplate. Do not exceed this pressure.
Failure to follow these instructions could result in serious personal injury or death, or property damage.
WARNING: Excessive Pressure Hazard Volumetric Expansion
The heating of water and other fluids causes volumetric expansion. The associated forces may cause failure of system components and release of high temperature fluids. This will be prevented by installing properly sized and located compression tanks and pressure relief valves.
Failure to follow these instructions could result in serious personal injury or death, or property damage.
Disconnect and lockout power before servicing.
Failure to follow these instructions could result in serious personal injury or death, or property damage.
4
GENERAL INSTRUCTIONS
PURPOSE OF THE MANUAL
This manual is furnished to acquaint you with some of the practical ways to install, operate, and maintain this pump. Read it completely before any installation, operation, or maintenance on your unit and keep it handy for future reference.
Equipment cannot operate well without proper
care. To keep this unit at top efciency, follow the
recommended installation and servicing procedures outlined in this manual.
RECEIVING THE PUMP
Check the pump for shortages and damage immediately upon arrival. (An absolute must!) Prompt reporting of any damage to the carrier’s agent, with notations made on the freight bill, will expedite satisfactory adjustment by the carrier. Pumps and drivers are normally shipped from the factory mounted on a base plate and paint-
ed with primer and one nish coat. Couplings
may either be completely assembled or have the coupling hubs mounted on the shafts and the connecting members removed. When the connecting members are removed, they will be packaged in a separate container and shipped with the pump or attached to the base plate.
Shafts are in alignment when the unit is shipped; however, due to shipping, the pumps may arrive misaligned. Alignment must be established during installation. Bell & Gossett has determined that proper and correct alignment can only be made by accepted erection practices. (See the Foundation, Baseplate Setting, and Coupling Alignment sections.)
STORAGE REQUIREMENTS
If the unit will not be installed and put into opera­tion immediately upon arrival at the site, or for an extended shutdown after the unit is in operation, the following requirements for short-term storage apply:
• Store in a covered and dry location.
• Store the unit free from excessive cold or heat (below 32°F and above 110°F), dirt, and vibration.
• Rotate the shaft by hand several times (10–15 turns) at least every 30 days.
For initial storage longer than three months, or for pump shut down after being in operation lon­ger than three months, contact your local sales and service representative for long-term storage guidelines.
SAFE HANDLING REQUIREMENTS
WARNING: Falling Objects Hazard
Eyebolts or lifting lugs, if provided, are for lifting only the components to which they are attached.
• Personal protective equipment should be worn when handling this equipment.
• Transportation & installation of this equipment
should only be performed by qualied
personnel.
• A professional rigging company should be consulted before lifting the pump assembly.
• Only use properly sized, certied lifting
equipment & lifting devices, including slings, suitably rated for the weights to be lifted.
• Slings, when used, must be of identical materials to avoid differences in stretch rates.
• Do not use lifting devices that are frayed, kinked, unmarked, or worn.
• Lifting eyebolts tted on single components
of the assembly (pump or motor) must not be used to lift the complete assembly.
Failure to observe these instructions could result in equipment or property damage, serious injury, or death.
The pump assembly can arrive in a variety of ways. It can be shipped as pump end only (bare pump), pump less motor, or pump, motor, & baseplate. Use the following recommended ways of handling VSX pump assemblies.
The pump assembly should remain horizontal during transport and lifting.
5
Lifting the pump end only (bare pump) should be done by placing one end of the slings around or as close to the volute barrel as possible (See Fig. 4a). After the slings are attached to the unit, re­check to ensure they are securely in place. Make sure the slings are adjusted to obtain an even lift.
Appropriate lifting device
Figure 4a
Lifting the pump less motor or the pump, motor, & baseplate should be done by utilizing a forklift under the entire unit (Fig. 4b). Always take extra precaution to ensure the weight is balanced & equally distributed across both forks. When the baseplate of the assembly is structural channel construction, the pump and base plate should
be set in place rst. The motor should then be
separately lifted & mounted to the unit.
As an alternative to lifting by forklift, lifting devices can be used to lift the complete pump & motor assemblies. When lifting the complete pump assembly (Fig. 4c), securely place the lifting devices around the volute barrel or nozzle. The remainder of the lifting device should be placed under the back end of the motor housing (as close to the motor feet as possible). Precau­tion should be taken to ensure the placement of the lifting devices will not damage the motor end bell and conduit boxes.
Figure 4c
Figure 4b
6
LOCATION
Locate the pump so there is sufficient room for inspection, maintenance, and service. If the use of a hoist or tackle is needed, allow ample head room. For outdoor installations, it is advisable to shelter the pump unit.
WARNING: Falling Objects Hazard
Eyebolts or lifting lugs, if provided are for lifting only the components to which they are attached.
Failure to follow these instructions could result in serious personal injury or death, or property damage.
The best pump location for sound and vibration absorption is on a concrete floor with subsoil underneath. If the pump location is overhead, special precautions should be undertaken to reduce possible sound transmission. Consult a sound specialist.
If the pump is not on a closed system, it should be placed as near as possible to the source of the liquid supply, and located to permit installation with the fewest number of bends or elbows in the suction pipe.
Important
Do not install and operate Bell & Gossett Pumps, 3D Valves, Suction Diffusers, etc., in closed systems unless the system is constructed with properly sized safety devices and control devices. Such devices include the use of properly sized and located pressure relief valves, compression tanks, pressure controls, temperature controls, and flow controls as appropriate. If the system does not include these devices, consult the responsible engineer or architect before making pumps operational.
FOUNDATION
The concrete foundation or isolation pad must be substantial enough to absorb vibration (Hydraulic Institute Standards recommends that the foundation weigh at least five times the weight of the pump unit). It must form a permanent and rigid support for the base plate and should be built to suit local conditions. This is important in maintaining the alignment of the flexibly coupled unit. Do not use the base as the isolation pad.
Foundation bolts of the proper size should be embedded in the concrete with either of the methods shown in Figure 6. See Table 2 for anchor bolt hole and anchor bolt sizes. Allow the foundation to cure for several days before proceeding with the pump installation.
Figure 5: Pump Location
The installation must be evaluated to determine that the Net Positive Suction Head Available (NPSHA) meets or exceeds the Net Positive Suction Head Required (NPSHR), as stated by the pump performance curve.
The pump must be primed before starting. Whenever possible, the pump should be located below the fluid level to facilitate priming and ensure a steady flow of liquid. This condition provides a positive suction head on the pump. It may also be possible to prime the pump by pressurizing the suction vessel.
Figure 6: Foundation
Table 2: Anchor Bolt/Hole Sizes
Diameter of Anchor
Bolt Hole
Diameter of Anchor
Bolt
1.125” 1.000”
1.375” 1.250”
BASE PLATE SETTING
Place the pump unit on its concrete foundation, supporting it with steel wedges or shims. The wedges or shims should be machined and be put on both sides of each anchor bolt to provide a means for leveling the base. The wedge or shim width should be equal to or greater than the base rail width. The length of the wedge or shim should be at least four times the diameter of the anchor bolt. It is acceptable to place additional shims between the existing anchor bolts.
Use an anchor bolt for each anchor bolt hole provided, and plain, flat Type-W washers at each anchor bolt.
CAUTION: Equipment Damage
Use an anchor bolt and plain, flat Type-W washer at each anchor bolt hole. Otherwise, shifting of the pump unit may occur.
Figure 7: Setting Base Plate
ROTATION
The Series VSX pump is available in both right­and left-hand rotation. An arrow cast into the pump body shows the direction of rotation.
Failure to follow these instructions could result in serious property damage and/or moderate personal injury.
It is very important that the pump base be set level to avoid any mechanical difficulties with the motor or pump. This pump was properly aligned (if furnished with a motor) at the factory. However, since all pump bases are flexible, they may spring and twist during shipment. Do not pipe the pump until it is realigned. After piping is completed and after the pump is installed and bolted down, align it again. It may be necessary to re-adjust the alignment from time to time while the unit and foundation are new.
Optional Grouting
It is permissible to grout the base after the pump unit has been leveled, securely bolted to the floor, and properly aligned. A good grade of non-shrinking grout should be used inside the pump base.
COUPLING ALIGNMENT
All alignment should be done by moving or shimming the motor only. Adjustments in one direction may alter alignment in another. Therefore, check alignment in all directions after a correction is made. All measurements should be taken with the pump and motor bolts tightened. Final alignment check should be made after the unit has attained its final operating temperature.
WARNING: Unexpected Startup Hazard
Disconnect and lockout power before servicing.
Failure to follow these instructions could result in serious personal injury or death, or property damage.
1. Check the pump and motor shafts and remove any paint, burrs, rust, etc. Slide the hubs (and bushings, QD or Taper­Lock style) on the shafts with keys.
2. When high speed rings are used for spacer couplings, loosely install one ring on each half element.
8
3. Hold one half element on the hubs to determine the appropriate hub spacing. If using spacer elements with high speed rings, hold both half elements on the hubs to make sure the hubs do not interfere with the rings. The hubs may be installed with the hub extension facing in or out. Make sure the shaft extends into the hubs at least .8 times the diameter of the shaft.
4. Lightly fasten the hubs to the shafts to prevent them from moving during alignment.
5. The hubs should be aligned to at least the values shown in Figure 10 for allowable misalignments. Alignment may be done with lasers, dial indicators, or with a straight edge and calipers.
To align using straight edge and calipers
Angular misalignment may be checked by using a caliper to gauge the distance between the two hubs at various points around the circumference. Do not rotate the shafts. Reposition the equipment until the difference between the minimum and maximum distance values is within the permissible value.
Figure 8: Checking Alignment with
Straight Edge
Angular misalignment may also be checked by inserting feeler gauges between the coupling faces at various points around the circumference. Do not rotate the shafts. Reposition the equipment until the difference between the minimum and maximum distance values is within the permissible value.
Parallel alignment may be checked by placing a straight edge across the two hubs and measuring the maximum offset at various points around the periphery of the hubs. Do not rotate the shafts. Reposition equipment until the offset is within the permissible value.
Figure 9: Checking Alignment with Calipers
9
Figure 10: Maximum Allowable Misalignment for Wood’s Duraflex®1 Couplings
Example: A WE10 coupling with a 3° angular misalignment will have a .191” difference in measurements between L1 and L2. (See Figure
9.)
Table 3: Angular Inch Gap Hub Size
1 2 3 4
Degrees
WE2 0.032 0.065 0.097 0.129 WE3 0.040 0.081 0.121 0.162 WE4 0.045 0.091 0.136 0.181
WE5 0.055 0.109 0.164 0.218 WE10 0.064 0.127 0.191 0.218 WE20 0.078 0.156 0.234 WE30 0.095 0.189 0.284 WE40 0.116 0.231 0.347 WE50 0.142 0.284 0.425 WE60 0.153 0.305 WE70 0.161 0.323 WE80 0.196 0.393
To align using dial indicator
Angular misalignment may be checked by mounting the dial indicator base to one coupling half, or shaft, and positioning the dial indicator button on the front face or rear face of the opposite coupling half. Scribe index lines on coupling halves as shown in Figure
11. Set the dial to zero. Rotate both coupling halves together, making sure the index lines remain matched. Reposition the equipment until the offset is within the permissible value.
Parallel misalignment may be checked by mounting the dial indicator base to one coupling half, or shaft, and positioning the dial indicator button on the outside diameter of the opposite coupling half. Set the dial to zero. Rotate both coupling halves together, making sure the index lines remain matched. Reposition the equipment until the offset is within the permissible value.
Figure 11: Checking Alignment with
Dial Indicators
6. Recheck the hubs to be certain both angular and parallel alignments are still within the values given in Figure 10.
7. Loosen the set screw on the pump hub. Loosely install one half element opposite the hub set screws. Torque both hub set screws to the value shown in Table 4. For QD or Taper-Lock hubs, follow the instructions supplied with the bushings. Loosely install the other half element onto the hubs. Install capscrews on the high­speed rings. If the capscrews and the holes in the elements do not line up
1
Duraflex is a registered trademark of T.B. Wood’s, Inc.
10
properly due to hub misalignment, rotate the shafts slightly. Torque all element and high speed ring capscrews to the values shown in Table 4. If possible, recheck angular and parallel alignments.
WARNING: Flying Objects Hazard
Coupling capscrews and set screws are to be installed using torque wrench or other torque measuring device. Hardware not installed per the listed torque values may become loose and dislodge from coupling assembly.
Failure to follow these instructions could result in serious personal injury or death, or property damage.
8. Capscrews supplied with the coupling have a thread lock coating that aids in resisting loosening from vibration. The capscrews should not be reused more than four times or if the coating is absent. Replacement capscrews are to be purchased through your local Bell & Gossett representative.
WARNING: Flying Objects Hazard
Capscrews with damaged or absent thread lock coating should be not be used. Otherwise the required counterforce will not be achieved and hardware may become loose and dislodge from coupling assembly.
Failure to follow these instructions could result in serious personal injury or death, or property damage.
Figure 13: Woods Duraflex Coupling
– Typical Spacer
Table 4: Fastener Torque Values and
Maximum RPM for Woods Duraflex
Couplings
Basic
Size
Element
& Ring
Capscrew
Torque
(ft-lb)
Standard Hubs Set
screw
Torque
(ft-lb)
Maximum RPM
Standard Spacer
WE2 7 7500 1800 WE3 7 7500 1800 WE4 14 7500 1800
17
WE5 23 7500 1800
WE10
23 7500 1800 WE20 50 6600 1800 WE30 50 5800 1800 WE40 100 5000 1800 WE50
30
100 4200 1800 WE60 167 3800 1800 WE70 167 3600 1800 WE80
75
167 2000 1800
Figure 12: Woods Duraflex Coupling
– Typical Non-spacer
1
Final Alignment
Final alignment cannot be accomplished until the pump as been operated initially for a sufficient length of time to attain operating temperature. When normal operating temperature has been attained, secure the pump to re-check alignment and compensate for temperature accordingly. (See the section entitled Coupling Alignment.)
NOTE: Elastomeric couplings are specifically designed to accommodate angular shaft misalignment, as well as parallel offset of the pump and motor shafts. However, the amount of the offset and/or misalignment is dependent on the style of flexible coupling applied. Left unchecked, coupling misalignment has a significant impact on the overall life of the mechanical seals and the bearings of the pump.
WARNING: Rotating Components Hazard
Do not operate pump without all guards in place.
Failure to follow these instructions could result in serious personal injury or death, or property damage.
SUCTION AND DISCHARGE PIPING
When installing piping, refer to the Hydraulics Institute Standards and observe the following
precautions:
Where flanged joints are used, ensure that inside diameters match properly.
Remove burrs and sharp edges when making up joints.
Do not “spring” piping when making any connections. Coupling and bearing wear will result if the suction or discharge lines are forced into position.
When considerable temperature changes are anticipated, equipment for absorbing expansion should be installed in the system in such a way as to avoid strain on the pump.
When using an isolation pad, flexible piping should also be used on both the suction and discharge sides of the pump.
The pipeline should have isolation valves around the pump and have a drain valve in the suction pipe.
See Technical Bulletin B-876 or BX-876, Table 5 for allowable static flange loading for vertical flange configuration. (Models VSC and VSCS)
A Bell & Gossett Triple Duty Valve installed in the discharge line will serve as a check valve to protect the pump from water hammer, as a gate valve for servicing, and for throttling.
Piping should always be run to the pump.
Do not move pump to the pipe. This could make final alignment impossible.
Both the suction and discharge piping should be supported independently near the pump and properly aligned so that no strain is transmitted to the pump when the flange bolts are tightened. Use pipe hangers or other supports at necessary intervals to provide support. When expansion joints are used in the piping system they must be installed beyond the piping supports closest to the pump. Tie bolts should be used with expansion joints to prevent pipe strain. Do not install expansion joints next to the pump or in any way that would cause a strain on the pump resulting from system pressure changes.
Install the piping as straight as possible, avoiding unnecessary bends. Where necessary, use 45° or long sweep 90° fittings to decrease friction losses.
Make sure that all piping joints are leak tight.
1
Loading...
+ 30 hidden pages