Bell & Gossett V58303B User Manual

INSTRUCTION MANUAL
WARNING: Label Part No. 9017-078 must be installed in this location. If missing, it must be replaced.
WARNING: Label Part No. 9015-463 must be installed in this location. If missing, it must be replaced.
V58303B
Expansion Tanks for Potable Water Systems
ASME And Non-Code
INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.
SAFETY INSTRUCTION
WARNING: Explosion Hazard.
A relief valve must be installed to prevent pressure in
excess of local code requirements or maximum working pressure in manual, whichever is less. This product must be installed by a qualified professional. Failure to follow the instructions in the accompanying product manual may cause a rupture or explo­sion. Failure to follow this instruction may result in serious personal injury or death and property damage and void product warranty.
DESCRIPTION
Series “PT” and “PTA” expansion tanks are precharged diaphragm­type vessels. The PTA Series meet the requirements of the ASME boiler and pressure vessels code. The Series “PT” and “PTA” tanks are designed to absorb the force of expanding water and protect the potable water system from pressure build up. Refer to table 1 on page 2 for pressure and temperature information.
limitation specified. Refer to Table 1 on page 2 for the maximum lim­itations specified. Failure to follow this instruction may result in seri­ous personal injury or death and property damage.
leaking or flooding could cause property damage. Failure to follow this instruction may result in property damage.
INSTALLATION INSTRUCTIONS
A. Pre-Installation
WARNING: Carefully read the Instruction Manual to avoid
serious personal injury and property hazards and to ensure safe use and proper care of this product.
WARNING: Use only potable water. Installer must comply with all plumbing codes. Do not operate in a setting where the temperature or pressure can exceed the maximum
WARNING: Do not locate this product where leaking or flood could cause damage to the surrounding area. A drip pan connected to an adequate drain must be installed if
1. Visually inspect expansion tank and check for damage prior to installation.
WARNING: If the expansion tank is damaged, it must be replaced. Failure to follow this instruction may result in serious personal injury or death and property damage.
2. Adjust pre-charge to equal incoming pressure.
3. Replace and tighten plastic cap on air fitting.
TABLE 1
MAXIMUM LIMITATIONS FACTORY
MODEL NUMBER PRESSURE TEMPERATURE PRE-CHARGE
PT-5, PT-12, PT-25V, PT-30V, PT-42V, PT-60V, PT-80V, PT-180V, PT-210V 150 PSIG (1035 kPa) 200°F (93°C) 40 PSIG (379 kPa) PT-447 through PT-457 150 PSIG (1035 kPa) 240°F (115°C) 55 PSIG (379 kPa) PTA-5, PTA-12, PTA-20V, PTA-30V, PTA-42V, PTA-60V,PTA-80V, PTA-180V, PTA-210V 150 PSIG (1035 kPa) 200°F (115°C) 55 PSIG (379 kPa) PTA-447 through PTA-457 125 PSIG (862 kPa) 240°F (115°C) 55 PSIG (379 kPa)
*Water temperature not to fall below 35°F (1.6°C).
WARNING: State of California Residents.
This product contains a chemical known by the State of
California to cause cancer. This product contains a chemical known by the State of California to cause birth defects or other reproductive harm.
temperatures can be very hazardous. Before servicing,
WARNING: Do not adjust the pressure or re-pressurize
this product except for any adjustments at the time of the
initial installation when the product is new. Only qualified professionals should check, adjust or re-charge the pre-charge of tanks. failure to follow this instruction may result in serious per­sonal injury or death and property damage.
B. Installation
1. Install the expansion tanks on the cold water supply (CWS) line at a point between the water heater and back­flow preventer, check valve or pressure reducing valve
(see Figure 1).
2. Once tank is installed fill system and check for any leak­age. Make repairs if necessary.
WARNING: Rupture or Explosion Hazard. Like most pressurized tanks, this tank can over time cor­rode, weaken, and burst or explode. Failure to follow this
instruction may result in serious personal injury or death and prop-
erty damage.
WARNING: Chlorine & Aggressive Water Warning. The water quality can significantly influence the life of
your product. You should test for corrosive elements, acidity, total solids, and other relevant contaminants, including chlo­rine and treat your water appropriately to insure satisfactory per­formance and prevent premature failure. Failure to follow this instruction may result in serious personal injury or death and prop-
erty damage.
WARNING: Install or store where tank will not be
exposed to temperatures below freezing or above rated
working temperature. Do not expose to any type of
weather.
3. Before the initial firing of the water heater, open a hot water fixture and draw water until all air is removed from the system. Turn the water heater temperature control to desired ending temperature level (see water heater
instructions).
4. To relieve initial thermal expansion, slightly open a hot water faucet. Continue until water heater aquastat tem­perature is satisfied. Once heater is at its operating range, no further bleeding of expanded water is required.
SERIES “PT” OR “PTA” IN-LINE MOUNT MODELS
SERIES “PT” OR “PTA” FLOOR MOUNT MODELS
5. The system water heater and expansion tank will now be operational. The expansion tank will absorb pressure increases caused by thermal expansion to a level well below the water heater relief valve setting.
OPERATING INSTRUCTIONS
1. The expansion tank is installed in the supply line between
the backflow preventer and the water heater. Its sealed-in air pre-charge prevents water from entering the tank until the system pressure exceeds the pre-charge pressure.
2. As the water temperature rises, expanded water enters
the expansion tank’s non-corrosive water reservoir. The pre-charge air chamber absorbs the pressure increase, keeping system pressures below the relief valve setting.
3. As hot water is used, the pressure in the air chamber
forces water back into the system until the expansion tank is empty. At this point, the pressure in the air cham­ber once again equals the supply pressure.
NOTE: Models PT-5, PT-12 and PT-25V are IAPMO listed.
Models PT-5 thru PT-210V are listed under ANSI/NSF Std
61 and City of Los Angeles.
Models PTA-5 thru PTA-210V are listed under ANSI/NSF Std. 61 and City of Los Angeles.
Xylem Inc.
8200 N. Austin Avenue Morton Grove, Illinois 60053 Phone: (847) 966-3700 Fax: (847) 965-8379 www.xyleminc.com/brands/bellgossett
Bell & Gossett is a trademark of Xylem Inc. or one of its subsidiaries. © 2012 Xylem Inc. V58303B May 2012