Bell & Gossett V57050B User Manual

INSTRUCTION MANUAL
SRS Pneumatic Purge Valve
WARNING LABEL PART NO. V56845 INSTALLED IN THIS LOCATION. IF MISSING, IT MUST BE REPLACED.
V57050B
INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.
SAFETY INSTRUCTIONS
This safety alert symbol will be used in this manual to draw attention to safety related instructions. When used, the safety alert symbol means ATTENTION! BECOME ALERT! YOUR SAFETY IS INVOLVED! FAILURE TO FOLLOW THESE IN­STRUCTIONS MAY RESULT IN A SAFETY HAZARD.
DESCRIPTION
The SRS Pneumatic Purge Valve is an air-operated diaphragm valve with programmable timer. It is used to purge sediment from an open or closed loop hydronic system that is sepa­rated out and collected in the bottom of the SRS.
OPERATIONAL LIMITS
Maximum Fluid Operating Temperature: 250°F (121°C)
Maximum Fluid Operating Pressure: 150 PSI (1034 kPa)
Min/Max Ambient Temperature: 32-130°F (0-54°C)
Min/Max Control Air Pressure: 65-145 PSI (450-1000 kPa)
INSTALLATION INSTRUCTIONS
Connections Required To Valve/Timer: 120V AC (±10%) to timer 3-terminal strip. Air connection to 1/4" FNPT port on solenoid Valve. 1" FNPT inlet and outlet.
1. Reference Sediment Removal Separator Instruction Manual A05767.
2. For best results, purge valve/timer should be installed up­stream of any pipe bends.
3. The purge valve/timer can be installed in any orientation.
4. A manual gate or ball valve is recommended between the SRS and the purge valve/timer in the event that the purge valve needs repair. During normal operation, this manual valve must remain fully open.
CAUTION: The use of PTFE impregnated pipe com-
pound and PTFE tape on pipe threads provides lubricity which can lead to overtightening and breakage. Do not overtighten. Failure to follow this instruction can result in MODERATE personal injury from hot water and/or property damage.
AUTOMATIC
Figure 1
INLET
FROM BOILER
CHILLER OR CONVERTER
B&G SEDIMENT
REMOVAL
SEPARATOR
MANUAL
SHUTOFF
VALVE
AIR VENT
OUTLET
TO PUMP SECTION
BLOW DOWN
VALVE
5. Pipe as required to allow gravity flow of sediment and water, and proper drainage.
6. Apply approximately 2 wraps of PTFE tape to the male end of 1" field piping as it comes from the SRS and recom­mended service valve, and install into the inlet of the 1" FNPT connection of the purge valve. Do the same for the 1" FNPT outlet and run the piping to a nearby drain.
7. Run air for the valve in accordance with local code. Be cer­tain that the minimum and maximum control pressure for the air are complied with. Purchase a 1/4" air hose adapter, apply PTFE tape to the threads, and insert into the 1/4" air port on the side of the solenoid valve as shown in Figure 2. Then attach tubing.
Timer
OPERATING INSTRUCTIONS
The timer is factory set as follows: Cycle Time (how often the valve opens): 4 hrs. Purge Duration (how long valve remains open per cycle): 10 sec
At start-up, the valve can be manually purged by depressing the button located on the side of the solenoid. (See Figure 4). We recommend manually purging the valve approximately every 30 minutes for 2 hours to determine if the factory setting is sufficient to handle the sediment problem in the system. Keep in mind that the first hour of start up will typically have a greater concentration of sediment than that found after several hours of operation.
If the factory setting is insufficient, adjustment is made by a series of DIP switches in the timer. The switches are accessed by removing the cover of the timer. Figure 3 is a sketch of the timer assembly, and Figure 5 is a diagram of the DIP switches and the range of settings available.
TIMER CONNECTIONS & ADJUSTMENTS
Valve
Actuator
Pilot Valve
Figure 2
WARNING: Water at temperatures above 100°F
(38°C) can be very hazardous. Piping from valve to drain should be such that there is no risk of exposure of hot water to personnel or equipment. Failure to follow these instructions could result in serious personal injury or death and property damage.
WARNING: Electrical shock and potential circuit
damage. Disconnect power before beginning instal­lation. Failure to follow these instructions could result in serious personal injury or death and property damage.
Cycle Time Potentiometer
Output
Led
Figure 3
Duration of Purge Time Potentiometer
Dip Switches
Power
Led
WARNING: Improper wiring and wire can cause
electrical shock and fires. Wiring connections must be made in accordance with all applicable electrical codes and ordinances. Use copper wire only. Failure to follow these instructions could result in serious personal injury or death and property damage.
8. Install 120V AC to the timer per local code. Remove the timer cover to expose the 3 terminal strip. Connect 120V AC to the terminal strip. Attach the middle terminal to ground. These connections provide the power for the sole­noid and timer. See Figure 3.
2
Manual
Purge
Button
Figure 4
Loading...
+ 2 hidden pages